1 GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19

2 Table of Contents 1.0 SCOPE PURPOSE LIMITATIONS GENERAL INTERCONNECTION AND PROTECTION REQUIREMENTS Distribution System System Frequency System Voltage Micro Generation Equipment Inverter Operational Settings Sheet Synchronism Voltage Regulation and Power Factor Frequency Control Interconnection Facility Safety Point of Common Coupling (PCC) Point of Disconnection Interconnection Grounding Phase and Ground Fault Protection Over-Voltage and Under-Voltage Protection Over-Frequency and Under-Frequency Protection Anti-Islanding Special Interconnection Protection Flicker Harmonics Typical Interconnection Requirements Single-Phase Inverters Three-Phase Inverters Mitigation of Protection Scheme Failure Maximum Generator Power to be Exported Interconnection Protection Approval CONSTRUCTION General METERING General Meter Requirements Net Billing INSPECTION TESTING Type Testing Verification Testing Protective Function Testing INFORMATION REQUIREMENTS MARKING AND TAGGING...13 Page 2 of 19

3 11.0 MAINTENANCE...13 TABLE 1 RECOMMENDED SERVICE VOLTAGE VARIATION LIMITS...14 TABLE 2 SINGLE PHASE INTERCONNECTION PROTECTION FUNCTION REQUIREMENTS..15 TABLE 3 THREE PHASE INTERCONNECTION PROTECTION FUNCTION REQUIREMENTS...16 APPENDIX 1 DEFINITIONS...17 APPENDIX 2 SINGLE LINE DIAGRAM FOR GRID-DEPENDENT MICRO-DG SYSTEMS...18 APPENDIX 3 SINGLE LINE DIAGRAM FOR GRID-INTERACTIVE MICRO-DG SYSTEMS...19 Page 3 of 19

4 GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC UTILITY DISTRIBUTION SYSTEM 1.0 SCOPE The intent of this Guide is to establish the interconnection requirements of microgeneration with the City of Medicine Hat Electric (City Electric) distribution system. While every precaution has been taken in the preparation of this Guide, it may contain inaccuracies or inconsistencies. The authors of this Guide assume no liability for errors or omissions, or damages resulting from the use or reliance upon the information contained herein. This Guide has been developed without regard to whether its adoption may involve patents on articles, materials, or processes. Such adoption does not assume any liability to any patent owner, nor does it assume any obligation whatsoever to parties adopting this Guide. 2.0 PURPOSE This document is an interconnection application guide that applies to grid dependent and grid interactive microgeneration systems. It establishes minimum uniform requirements relevant to the performance, operation, testing, safety considerations, and maintenance of the interconnection of microgeneration systems with the City Electric distribution dystem and is based on the following principles: The addition of microgeneration systems to the distribution system will not appreciably change the distribution system and its characteristics. The microgeneration inverter must meet the requirements of this Guide. Users, owners, and operators of microgeneration systems need not have any technical expertise. The installation shall meet the requirements of the latest version of the Canadian Electrical Code. Microgeneration systems are deemed to be operating unattended. Microgeneration installations shall require a permit from the City of Medicine Hat Safety Code Services or the authority having jurisdiction in the City of Medicine Hat Electric service area outside the corporate boundaries of Medicine Hat. City Electric personnel will need to be aware of the microgeneration system specifications, operating characteristics, and installed location. Page 4 of 19

5 3.0 LIMITATIONS The criteria and requirements in this guide are applicable to microgeneration facilities with a rated generation capacity of 5 kw or less per service that use a single phase or three phase inverter to generate AC electricity that is in parallel with the City Electric distribution system and have a nominal operating voltage of 600 volts phase to phase AC or lower. 4.0 GENERAL INTERCONNECTION AND PROTECTION REQUIREMENTS The Microgenerator s interconnection installation must meet all applicable national, provincial and local construction and safety codes. The Microgenerator is required to install, operate and maintain in good order and repair at all times, in conformity with good electrical practice, the equipment required by this Guide for the safe parallel operation with the City Electric distribution system. 4.1 Distribution System A Microgenerator's inverter shall be certified to meet this Guide's provisions as detailed in Section 4.1 which defines the power quality and characteristics of the City Electric system to which the Microgenerator is interconnecting. It is the manufacturer's responsibility to ensure that the inverter operates in this environment System Frequency The distribution system operates at 60 hertz. Frequency deviations are typically 59.7 hz to 60.2 Hz System Voltage See Table Micro Generation Equipment Inverter Operational Settings Sheet The Microgenerator owner needs to ensure that the inverter has an Inverter Operational Settings Sheet (IOS) document. The IOS document must certify that the inverter operates within the ranges specified in Section Synchronism Inverters will automatically restart following automatic re-closing of distribution facility electrical equipment as per CSA 22.2 #107.1 (or other equivalent and recognized standard such as UL 1741).It will not be possible for City Electric to co-ordinate inverter Page 5 of 19

6 restart. A synchronizing scheme does not need to be submitted for grid-dependent inverters Voltage Regulation and Power Factor The Microgenerator shall be responsible for ensuring that the voltage levels at the point of interconnection are maintained within the guidelines prescribed by City Electric and/or at least equal to the voltage levels, at all feeder load conditions, prior to the interconnection. City Electric will decide if voltage regulation is expected to be a concern and identify possible solutions at time of application. The Microgenerator is not required to be capable of adjusting the power factor but shall operate in the range of ±0.9. City Electric will not require the inverter to operate in a power factor control mode Frequency Control A Microgenerator's operating frequency must lie between 59.5 and 60.5 Hz. Underfrequency over-frequency protection that automatically disconnects the Microgenerator from City Electric shall not operate for frequencies in the range of 59.5 to 60.5 Hz. The Microgenerator is not required to remain synchronously connected for any frequency excursions beyond this range. 4.3 Interconnection Facility Safety Safety of personnel, the public and of equipment is of primary concern in the design of the interconnection Point of Common Coupling (PCC) The PCC will be considered to be the service entrance unless otherwise stated Point of Disconnection Low Voltage Disconnecting Means To enable City Electric s personnel to work on their facilities, a manual disconnecting means is required between City Electric s facilities and the Microgenerator's inverter. The Microgenerator is responsible for installation of the disconnecting means. The characteristics of this disconnecting means must meet the following requirements and be subject to the approval of the authority having jurisdiction enforcing the Canadian Electrical Code: must provide safe isolation for City Electric s personnel from the inverters. not required to have a lockable, direct, visible means to verify contact operation. do not need a City Electric switch number, and do not need to undergo annual inspections and maintenance. Page 6 of 19

7 All low voltage disconnecting means must: Be adequately rated to break the connected generation/load; Allow simultaneous disconnection of all ungrounded conductors of the circuit; Be externally operable without exposing the operator to contact with live parts; Be capable of being closed without risk to the operator when there is a fault on the system; Be capable of being energized from both sides; Plainly indicate whether in the open or closed position; and Meet all applicable CSA Part II standards and all applicable codes. No switching, clearance, and tagging procedures will be required of the Microgenerator. For all grid-interactive inverters, the manual disconnecting means must also: Be within 5 meters horizontal walking distance of the PCC, unless otherwise approved by City Electric; Be readily accessible to City Electric Interconnection Grounding Single-phase generating systems must be grounded as per the manufacturer s recommendations and the Candian Electric Code Part 1. The inverter manufacturer shall certify that their inverter isolates all sources of fault contribution from a faulted line or distribution element, blocks the transmission of harmonic currents and voltages; and protects the low voltage side from high fault current damage Phase and Ground Fault Protection The Microgenerator shall use an inverter that detects faults or power outages occurring on all ungrounded conductors to which it is connected and then promptly ceases to energize such conductors and does not re-energize until at least 5 minutes after the normal voltage of the City Electric system is restored. The Microgenerator shall employ over-current protection in their interconnection equipment if the inverter is capable of producing current greater than the ratings of the interconnection equipment Over-Voltage and Under-Voltage Protection Provided that the inverter utilized by the Microgenerator is certified to CSA 22.2 #107.1 (or other equivalent and recognized standard such as UL 1741), the Microgenerator will not be required to install additional relays to trip the circuit breaker when the voltage, measured phase to ground is outside the predetermined limits in Page 7 of 19

8 This recognizes: a) that the certification to CSA 22.2 #107.1 (or other equivalent and recognized standard such as UL 1741) guarantees and tests the appropriate protection functionality to operate on abnormal voltage; b) the Microgenerator's generating equipment operates automatically and unattended; c) the generating facility is not manually controlled nor operated by the Microgenerator beyond being turned off and on; and d) it is acceptable that the under-voltage and over-voltage setpoints and reaction times are not adjustable for Microgenerator inverters. The inverter manufacturer shall indicate the time delay for reconnection after City Electric s distribution system voltage and frequency return to normal range and are stabilized. Minimum time for reconnection to be 5 minutes as per CSA C22.2 No The Microgenerator and City Electric will work together to arrive at a solution to any concerns about the voltage levels on the distribution facility. The Microgenerator's automatic reconnection will not be governed by any local operating orders that require manual reconnection upon authorization from City Electric Over-Frequency and Under-Frequency Protection City Electric recognizes that the Microgenerator's generating equipment disconnects on manufacturer preset over-frequency and under-frequency conditions and at manufacturer preset delay times. Additional frequency selective relays to separate the inverter(s) from the electric system in cases of extreme variations in frequency will not be required Anti-Islanding The Microgenerator s generation facility must be equipped with protective hardware and software designed to prevent the generator from being connected to a deenergized circuit owned by City Electric. Certification of the Microgenerator's inverter by an accredited certification organization shall be deemed to meet the anti-islanding requirements of this Guide without any further assessment requirements The Microgenerator is responsible for any damage caused to his equipment or City Electric s infrastructure resulting from improper operation of the Microgenerator s anti-islanding protection. In spite of the above certification of inverters, it is recognized that the effect on antiislanding schemes used by different inverters may require on site testing and/or further evaluation when there is a mixture of generation connected to the same feeder. Page 8 of 19

9 4.3.9 Special Interconnection Protection No special inverter-specific protection and controls, such as out-of-step or loss of synchronism, will be required. City Electric recognizes that the Microgenerator's inverter and its manufacturer preset protection limits are the prime protection mechanism that the Microgenerator will be employing. No additional protection other than the already specified will be required Flicker The microgeneration system shall not cause objectionable flicker on the distribution system. It is recognized that flicker is a site-dependent condition. See CAN/CSA- C and City Electric for specific site requirements Harmonics The microgeneration system employing an inverter certified to CSA C22.2 No is assumed to comply with harmononic distortion limits of City Electric. It is recognized that voltage harmonics is a site-dependent condition. Exceeding the limits may require the Microgenerator or City Electric to take compensatory measures the cost of which would be borne by the Microgenerator. Current harmonics are specified in CSA C22.2 No Typical Interconnection Requirements An Inverter Operational Settings document shall be made available by the Microgenerator to the City Electric to determine if the interconnection equipment and settings are acceptable to its system requirements. The City Electric will work closely with customer to determine whether interconnection and operation within a specific distribution facility is possible. The interconnection equipment shall meet the required protective functions specified in Table Single-Phase Inverters Table 2 of this Guide shows the protective functions required to meet this Guide. Inverters must be certified to CSA 22.2 #107.1 (or other equivalent and recognized standard such as UL 1741) Three-Phase Inverters Table 2 of this Guide shows the protective functions required to meet this Guide. Inverters must be certified to CSA 22.2 #107.1 (or other equivalent and recognized standard such as UL 1741) Mitigation of Protection Scheme Failure If the protective device functions required in Table 2 and Table 3 are performed by the microgeneratoration s control, then the microgeneration shall be designed to have self-diagnostic and fail-safe features. In case of failure of the Page 9 of 19

10 microgeneration s protection function, the microgeneration shall automatically cease to operate in parallel with the City Electric s system Maximum Generator Power to be Exported A Microgenerator's microgeneration system output shall never exceed 5.5 kilowatts (10% above nominal rating). 4.5 Interconnection Protection Approval The Microgenerator shall provide to City Electric complete inverter documentation for review against the requirements of this Guide and for potential impacts on the City Electric distribution system. The documentation should include: a completed application form, an overall description of the inverter and its protection functions, including the manufacturer, model, and Inverter Operational Settings document along with Independent Testing Laboratory certification documentation or equivalent documentation provided by the inverter manufacturer that describes its protection settings, a detailed single line diagram if the system is different than shown in Appendix 2 or Appendix 3. the disconnecting means details (i.e., manufacturer, model and associated certification). The Microgenerator shall revise and re-submit the inverter or protection information for any proposed modification. 5.0 CONSTRUCTION 5.1 General The Microgenerator s generation facility must be constructed and installed to meet all applicable regulations. All permitting and safety code requirements must be completed and copies of inspection reports must be provided to City Electric. All Single Line Diagrams provided to the City Electric shall be drawn in accordance with IEEE standards and conventions. Professional stamps shall only be required where required by permitting authorities. Page 10 of 19

11 6.0 METERING 6.1 General Metering must comply with Measurement Canada requirements and the latest revision of City Electric s By-law Bi-directional metering shall be installed so that kwh (delivered) and kwh (received) are separately recorded. 6.2 Meter Requirements For microgeneration systems the bi-directional billing meter will be supplied and installed by City Electic. Cost of metering equipment will be borne by City Electric, but labor, equipment and material associated with the installation of the metering equipment will be charged to the customer. 6.3 Net Billing Customers are given credit for the excess power generated from their microgeneration system up to a maximum of their energy usage in any twelve month period. Customers are still charged the non-energy variable charges based on their usage of the distribution system. 7.0 INSPECTION The Microgenerator shall maintain a quality control and inspection program according to the recommendations of the inverter manufacturer. In addition to the Microgenerator's normal inspection procedures, the City Electric reserves the right to witness any part of work that concerns the subject equipment; to inspect materials, documents and installation procedures, to witness tests and to evaluate results of non-destructive examinations. The Microgenerator shall supply the City Electric with a complete set of detailed drawings, which will be used by the City Electric to assist in the inspection during the testing of equipment. 8.0 TESTING 8.1 Type Testing Is performed or witnessed once by an independent testing laboratory for a specific protection package. Once a package meets the type testing criteria described in this section, the design is accepted by City Electric. Page 11 of 19

12 8.2 Verification Testing Prior to completion of commissioning of a microgeneration system, or when interconnection system hardware or software is changed, a verification test shall be performed. City Electric reserves the right to witness verification testing or to require written certification that the testing was performed. All verification tests relating to the interconnection system prescribed by the manufacturer or developed by the Microgenerator that are agreed to by City Electric shall be performed prior to interconnection. The Microgenerator shall maintain verification test reports for inspection by City Electric. Any system that depends upon a battery for trip power shall be verified to be of fail-safe design by disconnecting the battery and verifying that the system ceases to energize the distribution system. 8.3 Protective Function Testing If microprocessor-controlled protective functions are used, and production line testing has been done according to section 8.1, then a repeat of the production line testing (subject to item (ii) below) in the field is not required. The non-islanding function shall be checked by operating a disconnecting means to verify that the inverter ceases to energize its output terminals and does not restart for the required time delay after the disconnecting means is closed. 9.0 INFORMATION REQUIREMENTS The following table identifies the drawings and information the Microgenerator is required to submit to the City Electric when applying for interconnection to City Electric s distribution system. Page 12 of 19

13 Drawing/Data Proposal Acceptance * Verified Manufacturer s equipment data sheet including the Inverter Operational Settings (IOS) document Single line diagram (not required if as per Appendix 2 or Appendix 3) Commissioning report c/w protection settings Plot plan showing location of disconnecting means X X X X X X X X X X Operating Manual X X X *The minimum time requirement for review of information is generally 20 working days MARKING AND TAGGING The disconnecting means shall be clearly marked in accordance with the Canadian Electrical Code Part 1. City Electric may choose to place warning tags or labels on parts of the Service Entrance MAINTENANCE The Microgenerator has full responsibility for routine maintenance of the Microgenerator's complete system, control and protective equipment up to and including the PCC in accordance with the manufacturer's recommendations, and the keeping of records for such maintenance. The Microgenerator must maintain the equipment to accepted industry standards. Failure to do so may result in disconnection of the microgenerator at the PCC. Page 13 of 19

14 TABLE 1 RECOMMENDED SERVICE VOLTAGE VARIATION LIMITS Nominal system voltages Single phase 120/ Recommended voltage variation limits for circuits up to 100 V, applicable at service entrance Extreme operating conditions Normal operating conditions 106/ / / / Three phase 4-conductor 120/208Y 240/416Y 277/480Y 347/600Y 110/ / / / / / / / / / / / / / / /635 Three phase 3-conductor Source: CSA CAN3-C235, Table 3. Page 14 of 19

15 TABLE 2 SINGLE PHASE INTERCONNECTION PROTECTION FUNCTION REQUIREMENTS Notes: 1. Exporting to the City Electric's system may require coordination of operations with the City Electric. 2. This is as required in Section Function # Protection Function Required Inverter AC disconnect means X 59T Over-voltage trip X 27 Under-voltage trip X 81/O, 81/U Over/Under frequency trip X 25 Automatic Synchronizing (1) X Anti-islanding (2) Page 15 of 19

16 TABLE 3 THREE PHASE INTERCONNECTION PROTECTION FUNCTION REQUIREMENTS Function # Protection Function Inverter Size 5kW or less # of Phases 2 Inverter Disconnect Means X (3) 25 Automatic Synchronizing 1 X (1) 27 Under-Voltage Trip X (3) 50/51 Inst/Timed Over-Current X (3) 59 Over-Voltage Trip X (3) 81/O, 81/U Over/Under-Frequency Trip X (3) Anti-islanding 5 X (3) Note: 1. For inverters with standalone capability. 2. Number of phases to be monitored shown in parentheses, e.g., (3). 3. X designates functions that are a protection requirement. 4. To be in accordance with the Canadian Electrical Code. 5. As required in Section Page 16 of 19

17 APPENDIX 1 DEFINITIONS The following terms are defined here to assist in the understanding of microgeneration. Though some of these terms are not used in this Guide, they may arise in discussions of microgeneration systems and so would be useful to understand. 1. Microgenerator Distributed generation up to 5 kw typically installed in a residential or small business building. It is deemed to be operating unattended using untrained personnel. 2. Inverter An electronic device that converts DC electricity to AC electricity. 3. Voltage-following inverter An inverter in which the output follows the waveform of an external device. 4. Stand-alone mode An inverter which operates in isolation from the City of Medicine Hat Electric Distribution System (City Electric). 5. Grid-interactive mode An inverter which operates in parallel with City Electric and contains provision for synchronizing with City Electric. 6. Grid-dependent mode An inverter which automatically ceases to operate upon loss of voltage from City Electric and resumes operation when City Electric voltage is restored. 7. Single phase inverter An inverter that generates a single phase electrical output. 8. Point of common coupling (PPC) The point where City Electric is connected to the Microgenerator s facility. 9. Disconnecting means A device which disconnects a circuit from its source of supply. 10. Islanding A condition in which a portion of City Electric is energized by a Microgeneration facility thru a PCC while that portion of City Electric is separated from the rest of City Electric distribution system.. Page 17 of 19

18 APPENDIX 2 SINGLE LINE DIAGRAM FOR GRID-DEPENDENT MICRO-DG SYSTEMS PROTECTION LEGEND: AI - Anti-Islanding 27 - Under-Voltage 59 - Over-Voltage 81O - Over-Frequency 81U - Under-Frequency Micro-DG Source Wire Owner distribution system Interconnection Protection Functions AI /O 81/U [Note 3] Local loads Point of Common Coupling Service entrance Label: Two power source, parallel system [Note 1] 120/240 VAC [Note 1] [Note 1] Outdoor Indoor NOTES: 1. This shows all possible locations of meters. The number and location of metering points are given by commercial agreement. 2. Some inverters may not contain internal disconnects. 3. Protection schematic shown is for micro- DG systems. Refer to Table 2 for requirements on specific systems. 4. Location and specification of S1 and S2 are given by requirements of Wire Owner and CE Code. [Note 4] S1 Label: DG Source Disconnect Internal disconnects DC = ~ Grid-Dependent Inverter [Note 2] AC 1φ [Note 4] S2 Label: DG Inverter Disconnect [Note 1] New installation Main AC breaker panel Breaker with no line and load markings. Label: DG System Disconnect Single-Phase, Grid-Dependent, Micro-Distributed Generator Single Line Diagram for Interconnection through Wire Owner Distribution Transformer Submitted by: Date: Site Description: This single line diagram is intended for use during the application for interconnection. It is not intended to be used for system design or installation. DRAWING NO. SCALE: NOT TO SCALE REV 1 SHEET Site Location: Page 18 of 19

19 APPENDIX 3 SINGLE LINE DIAGRAM FOR GRID-INTERACTIVE MICRO-DG SYSTEMS PROTECTION LEGEND: AI - Anti-Islanding 25 - Synchronism Check 27 - Under-Voltage 59 - Over-Voltage 81O - Over-Frequency 81U - Under-Frequency Electrical Storage Device Micro-DG Source DC S1 Label: DG Source Disconnect [Note 4] Wire Owner distribution system Interconnection Protection Functions [Note 3] S3 Label: Electrical Storage Device Disconnect AI /O 81/U DC Essential loads AC breaker panel = ~ Grid-Interactive Inverter [Note 2] Internal transfer switch AC 1φ S2 Label: DG Inverter Disconnect [Note 4] Point of Common Coupling Service entrance Internal disconnects Label: Two power source, parallel system Local loads [Note 1] Single-Phase, Grid-Interactive, Micro-Distributed Generator Single Line Diagram for Interconnection through Wire Owner Distribution Transformer 120/240 VAC [Note 1] [Note 1] Outdoor Indoor Submitted by: Date: Site Description: NOTES: 1. This shows all possible locations of meters. The number and location of metering points are given by commercial agreement. 2. Some inverters may not contain internal disconnects. 3. Protection schematic shown is for micro- DG systems. Refer to Table 2 for requirements on specific systems. 4. Location and specification of S1 and S2 are given by requirements of Wire Owner and CE Code. New installation Main AC breaker panel Breaker with no line and load markings. Label: DG System Disconnect This single line diagram is intended for use during the application for interconnection. It is not intended to be used for system design or installation DRAWING NO. SCALE: NOT TO SCALE REV 1 SHEET Site Location: Page 19 of 19

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS

GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS 1. INTRODUCTION... 3 1.1 POLICY ON CUSTOMER GENERATION.... 3 1.2 GENERATION SOURCES AND

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

Definitions. Scope. Customer Generation Interconnection Requirements

Definitions. Scope. Customer Generation Interconnection Requirements Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power

More information

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities New Ulm Public Utilities Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities INDEX Document Review and History... 2 Definitions... 3 Overview... 3 Application

More information

Copyright 2003 Advanced Power Technologies, Inc.

Copyright 2003 Advanced Power Technologies, Inc. Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design

More information

Technical Requirements for Renewable Energy Power System

Technical Requirements for Renewable Energy Power System Hotline: 2843 3228 Email address: RE@hkelectric.com Issued on 20 Nov 2018 1. Introduction 1.1. This document aims to provide the technical requirements for renewable energy power system (the REPS) connected

More information

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

Distributed Generation Interconnection Policy

Distributed Generation Interconnection Policy Distributed Generation Interconnection Policy 1 Introduction Carroll Electric Membership Corporation Distributed Generation Interconnection Policy Carroll Electric Membership Corporation (herein after

More information

Net +Plus Connection Code

Net +Plus Connection Code Net +Plus Connection Code LANKA ELECTRICITY COMPANY (PRIVATE) LIMITED 1.0 BACKGROUND The existing Net Metering Concept launched in the year 2010 noticed an exponential growth in the recent year and at

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates

More information

REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS

REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS 1. PURPOSE This document describes the general provisions and technical requirements for connecting Renewable Generation Systems (

More information

SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT

SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT INTERCONNECTION AGREEMENT FOR SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION THIS AGREEMENT MUST ACCOMPANY

More information

NET METERING PROGRAM. Technical Interconnection Requirements

NET METERING PROGRAM. Technical Interconnection Requirements NET METERING PROGRAM Technical Interconnection Requirements Updated: December 2017 LIMITATION OF LIABILITY AND DISCLAIMER Qulliq Energy Corporation (QEC), its officers, directors and employees, make no

More information

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5 Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS XXV. NET METERING A. Applicability and Availability 1. The terms Net Metering Service, Demand Charge-based Time-of- Use Tariff, Net Metering Customer, Customer, Time-of-Use Customer, Time-of-Use Tier,

More information

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Northeastern Rural Electric Membership Corporation Columbia City, Indiana Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),

More information

Minnesota Dept. of Commerce, Division of Energy Resources. Distributed Generation Workshop Interconnection Standards

Minnesota Dept. of Commerce, Division of Energy Resources. Distributed Generation Workshop Interconnection Standards Minnesota Dept. of Commerce, Division of Energy Resources Distributed Generation Workshop Interconnection Standards Presented by Michael Sheehan, P.E. October 11, 2011 Germans Solar Projected Cost Reductions

More information

NORRIS PUBLIC POWER DISTRICT DISTRIBUTED GENERATION (DG) INTERCONNECTION

NORRIS PUBLIC POWER DISTRICT DISTRIBUTED GENERATION (DG) INTERCONNECTION NORRIS PUBLIC POWER DISTRICT DISTRIBUTED GENERATION (DG) INTERCONNECTION PURPOSE... 2 SCOPE... 2 STANDARD... 2 INTRODUCTION... 2 Objective... 2 Regulatory Compliance and Interconnection Requirements...

More information

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS. 25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements

More information

Purpose. Background. Exclusions

Purpose. Background. Exclusions Guidance No. 1 for the Interconnection of Electric Storage as Stand-Alone Sources, Parallel Operation for Customers without Generation, and in Parallel with Self-Generation 1 Purpose This document provides

More information

DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase

DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:

More information

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT INTRODUCTION Lathrop Irrigation District has created a policy to allow safe connection

More information

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655) - (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility

More information

STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS

STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS Foreword 2 1. Introduction 3 2. References 6 3. Types of Interconnections 7 4. Interconnection Issues and Technical

More information

SOUTHERN PUBLIC POWER DISTRICT DISTRIBUTED GENERATION STANDARD

SOUTHERN PUBLIC POWER DISTRICT DISTRIBUTED GENERATION STANDARD SOUTHERN PUBLIC POWER DISTRICT DISTRIBUTED GENERATION STANDARD PURPOSE... 2 SCOPE... 2 STANDARD... 2 INTRODUCTION... 2 Objective... 2 Regulatory Compliance and Interconnection Requirements... 3 Responsibility...

More information

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection

More information

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,

More information

RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS

RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 1. PURPOSE This document describes the technical requirements for connecting Renewable Generation Systems ( RGS ) up to 150kW, or larger if approved

More information

ACTION FORM. EXHIBIT #1 Regular Council Meeting of 11/27/2006

ACTION FORM. EXHIBIT #1 Regular Council Meeting of 11/27/2006 EHIBIT #1 Regular Council Meeting of 11/27/2006 PROCEEDING: Utility Committee ACTION FORM AGENDA ITEM NO.: 11/13/06 1A DEPARTMENT OF ORIGIN: Public Utilities - Electric DATE SUBMITTED: 10-26-06 PREPARED

More information

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _ Application for Operation of & Net Metering for Member-Owned Generation -------------- OWNER/APPLICANT INFORMATION Name: Mailing Address: City: County: State: Zip Code: _ Phone Number: Email Address:.Representative:

More information

MICHIGAN ELECTRIC UTILITY

MICHIGAN ELECTRIC UTILITY MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 1 Projects with Aggregate Generator Output 20 kw or Less August 3, 2009 Page 1 Introduction Category 1 This Generator Interconnection

More information

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Processed Date Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Customer s Printed Name Installation Street Address Account Number Please note: Columbia Water & Light

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

Louisville Gas and Electric Company

Louisville Gas and Electric Company P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer

More information

Consumer Guidelines for Electric Power Generator Installation and Interconnection

Consumer Guidelines for Electric Power Generator Installation and Interconnection Consumer Guidelines for Electric Power Generator Installation and Interconnection Habersham EMC seeks to provide its members and patrons with the best electric service possible, and at the lowest cost

More information

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES Last Revised Date: October 15, 2015 Contents Chapter 1 - Purpose and Scope 2 Chapter 2 - Application of Rules 2 Chapter 3 - Definitions

More information

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER RS-N SECOND REVISED SHEET NO. 8.2.1 CANCELLING FIRST SHEET NO. 8.2.1 NAME OF UTILITY CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER DEFINITION Net Metering means calculating

More information

White River Electric Association, Inc. Net Metering Information & Service Requirements

White River Electric Association, Inc. Net Metering Information & Service Requirements White River Electric Association, Inc. Net Metering Information & Service Requirements What is Net Metering? Net Metering is an electric policy and service for consumers who own and utilize renewable energy

More information

REQUIREMENTS FOR GRID INTERCONNECTION RENEWABLE GENERATION SYSTEMS

REQUIREMENTS FOR GRID INTERCONNECTION RENEWABLE GENERATION SYSTEMS REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS FINAL APPROVED BY THE FAIR TRADING COMMISSION JUNE 19, 2015 Table of Contents 1. PURPOSE... 4 2. SUMMARY OF APPLICATION AND INTERCONNECTION

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent

More information

Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System

Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System A. INTRODUCTION This document outlines the technical requirements

More information

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT

SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT SANTA CLARA CITY RENEWABLE NET METERING & INTERCONNECTION AGREEMENT This Net Metering and Interconnection Agreement ( Agreement ) is made and entered into as of this day of, 2018, by the City of Santa

More information

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS TABLE OF CONTENTS Purpose and Scope...2 Authority...2 Applicability... 2 Intent.. 2 Maximum Connected Generation Allowed. 2 Definitions.

More information

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board Policy Description: In an effort to ensure fair treatment of all of its customers,

More information

Backfeed, Safety, and Work Practices

Backfeed, Safety, and Work Practices Backfeed, Safety, and Work Practices Michael T. Sheehan, P.E. March, 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, operated by the

More information

MICHIGAN ELECTRIC UTILITY

MICHIGAN ELECTRIC UTILITY MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 3 Projects with Aggregate Generator Output Greater Than 150 kw, but Less Than or Equal to 550 kw August 3, 2009 Page 1 Introduction

More information

Adopted: September 24, 2015 Version: Version 1.0

Adopted: September 24, 2015 Version: Version 1.0 Interconnection Standards for Parallel Installation and Operation of Customer Owned Renewable Electric Generating Facilities for Coon Rapids Municipal Utilities Adopted: September 24, 2015 Version: Version

More information

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Policy Bulletin No. 25 Net Metering Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Interconnection Standards For Residential Net Energy Metering With Electric

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

DAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS

DAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS DAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS Foreword 2 1. Introduction 3 2. References 6 3. Types of Interconnections 7 4. Interconnection Issues and

More information

REVISION NO.: 7 EFFECTIVE: 07/07/16

REVISION NO.: 7 EFFECTIVE: 07/07/16 SOLAR PROGRAM INTERCONNECTION PROCESS OVERVIEW FOR RESIDENTIAL AND SMALL GENERAL SERVICE REVISION NO.: 7 EFFECTIVE: 07/07/16 Required Steps for ED3 s Solar Program Interconnection Process for Residential

More information

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016 DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all

More information

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff. JERSEY CENTRAL POWER & LIGHT UNIFORM TECHNICAL AND PROCEDURAL INTERCONNECTION REQUIREMENTS FOR NET METERING FACILITIES FOR INVERTER BASED WIND AND PHOTOVOLTAIC SYSTEMS OF 100 kw OR SMALLER for Atlantic

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References

More information

SERVICE CLASSIFICATION "CEF" COMMUNITY ENERGY FACILITY

SERVICE CLASSIFICATION CEF COMMUNITY ENERGY FACILITY P.S.C. Del. No. 8 - Electric Original Leaf No. 95a SERVICE CLASSIFICATION "CEF" COMMUNITY ENERGY FACILITY A Community Energy Facility (CEF) consists of one or more generators located in Company s service

More information

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY

RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY Outline 1. Introduction 2. Legal Basis 3. Scope, Applicability & Qualification 4. Interconnection Set-Up 5. Pricing Methodology 6. Net-Metering

More information

Guidelines for Inverter-Based Micro-Generating Facility (10 kw and Smaller)

Guidelines for Inverter-Based Micro-Generating Facility (10 kw and Smaller) Guidelines for Inverter-Based Micro-Generating Facility (10 kw and Smaller) Cover: Photos courtesy of Balance Solutions for Today Inc OVERVIEW Today many home, farm and small business owners are considering

More information

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW) City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems

More information

Interconnection Requirements for Generation Systems

Interconnection Requirements for Generation Systems Interconnection Requirements for Generation Systems I. Foreword...1 II. Introduction...2 III. Definitions...2 IV. Interconnection Requirements Goals...4 V. Protection...4 VI. Nodak System Modifications...4

More information

Omaha Public Power District. Distributed Generation (DG) Manual

Omaha Public Power District. Distributed Generation (DG) Manual Omaha Public Power District Distributed Generation (DG) Manual A Guide to the Interconnection of Distributed Generation with the OPPD System This document is subject to change without notice. Please contact

More information

INTERCONNECTION REQUIREMENTS POLICY

INTERCONNECTION REQUIREMENTS POLICY Issue Date: January 8, 2018 Resolution No. 2097-18 INTERCONNECTION REQUIREMENTS POLICY 1. Purpose and Scope A. The purpose of these Interconnection Requirements is to establish rules for determining the

More information

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power 40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power WHO SHOULD FILE THIS APPLICATION: Anyone expressing interest to install generation which will interconnect

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Pacific Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system to

More information

DISTRIBUTED GENERATION INTERCONNECTION GUIDE

DISTRIBUTED GENERATION INTERCONNECTION GUIDE FLORESVILLE ELECTRIC LIGHT & POWER SYSTEM DISTRIBUTED GENERATION INTERCONNECTION GUIDE Updated September - 2017 1 FELPS developed Distribution Generation Guidelines that establish the requirements for

More information

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW PROGRAM REQUIREMENTS Important Information from Your Local Non-Profit Utility INTERCONNECTION for GENERATING FACILITIES Up to 20 MW Interconnecting to the Electrical Distribution System of Public Utility

More information

The Use of Electricity In Mines Regulations

The Use of Electricity In Mines Regulations The Use of Electricity In Mines Regulations Repealed by Chapter E-6.3 Reg 4 (effective February 28, 1996). Formerly Chapter E-7.1 Reg 5. Table of Contents 1 Title 2 CSA Standard adopted with amendment

More information

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES Beartooth Electric Cooperative, Inc. MEMBER RELATIONS POLICY NO. 416 1. SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES 2. OBJECTIVE: Beartooth Electric Cooperative, Inc. (BEC) recognizes that

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

Small Electrical Systems (Microgrids)

Small Electrical Systems (Microgrids) ELG4126: Microgrids Small Electrical Systems (Microgrids) A microgrid is a localized, scalable, and sustainable power grid consisting of an aggregation of electrical and thermal loads and corresponding

More information

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System Adopted Based on State and Tariff Interconnection Rules Applicable to Northern States Power,

More information

Net Metering Program

Net Metering Program Net Metering Program Chapter 1 Purpose and Scope. The purpose of this chapter is to establish rules for determining the terms and conditions governing the interconnection of electric generation facilities

More information

Interconnection Process for Generation Systems

Interconnection Process for Generation Systems Interconnection Process for Generation Systems I. INTRODUCTION...1 II. GENERAL INFORMATION...2 A. Definitions...2 B. Nodak Electric Cooperative, Inc. Generation Interconnection Contacts...3 C. Engineering

More information

Noble County Rural Electric Membership Corporation

Noble County Rural Electric Membership Corporation Albion, Indiana Page 1 of 7 SCHEDULE LPDG-1 LARGE POWER AND COMMERCIAL MEMBER-OWNED GENERATION I. AVAILABILITY This Generation rate is available to any member in good standing of Noble REMC (Noble) who

More information

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program As part of our commitment to support renewable energy, Kissimmee Utility Authority

More information

To complete the process for a net metering interconnection, please follow the steps below:

To complete the process for a net metering interconnection, please follow the steps below: We appreciate your interest in Rocky Mountain Power s net metering program. Before purchasing any net metering equipment, we recommend you review the requirements for interconnecting a net metering system

More information

TECHNICAL REQUIREMENTS FOR PARALLEL OPERATION OF MEMBER-OWNED GENERATION

TECHNICAL REQUIREMENTS FOR PARALLEL OPERATION OF MEMBER-OWNED GENERATION TECHNICAL REQUIREMENTS FOR PARALLEL OPERATION OF MEMBER-OWNED GENERATION EFFECTIVE JANUARY 27, 2014 TECHNICAL CONSIDERATIONS COVERING PARALLEL OPERATIONS OF CUSTOMER OWNED GENERATION INTERCONNECTED WITH

More information

Municipality Generator Interconnection Application Single Meter Application Part I

Municipality Generator Interconnection Application Single Meter Application Part I Municipality Generator Interconnection Application Single Meter Application Part I New Application Revised Application A single customer interconnecting to a single meter at a single premise makes a new

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

DIVISION 311 MISCELLANEOUS ELECTRICAL RULES

DIVISION 311 MISCELLANEOUS ELECTRICAL RULES DIVISION 311 MISCELLANEOUS ELECTRICAL RULES 918-311-0000 Design, Planning and Lay Out of Electrical Installations by Supervising Electricians A licensed supervising electrician may design, plan and lay

More information

City of, Kansas Electric Department. Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources

City of, Kansas Electric Department. Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources Ordinance No. Exhibit A ----------------------------------------- City of, Kansas Electric Department Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources -------------------------------------

More information

MISSOURI SERVICE AREA

MISSOURI SERVICE AREA MO.P.S.C. SCHEDULE NO. 6 2nd Revised 170 6 1st Revised 170 FROM QUALIFYING FACILITIES 1. *STANDARD RATES FOR PURCHASE The standard rates for purchase from a customer with a design capacity of 100 kw or

More information

Overview of State Distributed Generation Interconnection Rules

Overview of State Distributed Generation Interconnection Rules Overview of State Distributed Generation Interconnection Rules Presentation to EPA CHP Webinar Series June 26, 2008 Wayne Shirley Director The Regulatory Assistance Project 50 State Street, Suite 3 Montpelier,

More information

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less Original: October 31, 2006 Table of Contents: INTRODUCTION and SCOPE... 3 DEFINITIONS... 3 QUALIFICATIONS FOR AN EXPEDITED

More information

ELECTRIC SERVICE REQUIREMENTS FOR MEDIUM-SIZED COMMERCIAL INTERCONNECTED DISTRIBUTED GENERATION SOURCES

ELECTRIC SERVICE REQUIREMENTS FOR MEDIUM-SIZED COMMERCIAL INTERCONNECTED DISTRIBUTED GENERATION SOURCES ELECTRC SERVCE REQUREMENTS FOR 1. Purpose These electric service requirements include information and criteria for use by TEP/UES employees and customers in regard to the interconnection and parallel operation

More information

Bulletin Interconnection of electric power production sources Rules 2-010, , , , , , and

Bulletin Interconnection of electric power production sources Rules 2-010, , , , , , and Bulletin 84-1-11 Interconnection of electric power production sources Rules 2-010, 64-078, 64-110, 84-004, 84-008, 84-018, 84-022 and 84-030 Scope Issued May 2018 Supersedes Bulletin 84-1-10 1) Requirements

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES 3. Definitions ( cont'd) Parallel System: A generating facility that is electrically interconnected

More information

SCHEDULE NO. ACG33 NET METERING SERVICE

SCHEDULE NO. ACG33 NET METERING SERVICE Approved by Decision No.: 75408 Effective: January 19, 2016 Applicability Applicable to "Net Metering Facility" as defined below, or applicable Arizona Corporation Commission ("Cmnn1ission") Decision,

More information