1 Current sensor Instructions for installation, use and maintenance Type KECR 17,5 AC1 ABB
2 Current sensor Instructions for installation, use and maintenance Type KECR 17,5 AC1 Sensors are new solutions for measuring currents needed for protection and monitoring in medium voltage power systems. They are used to: convert large currents in the primary circuit of the network to appropriate signal for secondary equipment (e.g. relays) insulate primary and secondary circuits from each other protect the secondary equipment from the harmful effects of large voltages and currents during abnormal situations in network The output circuit of the sensor shall be connected to secondary equipment (e.g. relay) specified by the manufacturer. The use of sensor for other purposes than those described above is forbidden. These instructions for installation, use and maintenance are valid for the Current Sensors type KECR 17,5 AC1. The routine test report is normally delivered with the sensor and it includes results from accuracy measurements. 1. SERVICE CONDITIONS The current sensor is intended for indoor mounting. The temperature category is 25/55 meaning that the ratings are valid in an ambient temperature between 25 and +55 o C. The ambient air shall not be significantly polluted by dust, smoke, corrosive gases, vapours or salt. The sensor must be protected against direct sunshine. The altitude for mounting is up to 1000 m above sea level, if exceeded please contact the manufacturer. 2. RATING For sensor dimensions see separate dimension drawings. Rated values for each individual sensor are mentioned on the rating delivered with the sensor. Values mentioned on the rating plate must not be exceeded. Page 2
3 Example of rating plate for KECR 17,5 AC1 sensor: ABB Type: KECR 17,5 AC1 IEC U: 17,5/42/95 kv f r : 50/60 Hz Ipr: 180 A Icth: 1250A Ith/Idyn: 31,5(3 s)/80 ka cl: 1(5) Class: 1(5) With (without) correction factor Used in phase: Cor. fac.: 0,9969 Usr: 0,150 V, 50 Hz L1 L2 L3 Usr: 0,180 V, 60 Hz No: where: Type IEC U f r Ipr Icth Ith/Idyn cl Usr Cor. fac. No Type of sensor. KECR 17,5 AC1 IEC standards referred to Rated insulation level in kv 17,5 highest voltage for equipment 42 rated power frequency withstand voltage 1 min 95 rated lightning impulse withstand voltage (peak) Rated frequency in Hz Rated primary current Rated continuous thermal current Rated short-time (3s) thermal current in ka and rated dynamic current in ka (peak) Accuracy class (number in the brackets indicates worse accuracy in case when correction factor is not used) Rated secondary voltage Correction factor for current sensor. Correction factor is measured and calculated separately for each sensor. Correction factor is the number by which the output of sensor must be multiplied. Sensor identification code 2005 Year of manufacturing Used in phase To be filled by the user of this sensor. One from the three checkboxes corresponding to phases L 1, L 2, or L 3 should be checked during installation in order to recognize the phase in which the particular sensor is used. This will help to specify which rating plate (containing the value of correction factor used in relay) belongs to the sensor after installing it on the three-phase circuit breaker (identification of the sensor is placed only on the output cable that is hidden after installation). Page 3
4 3. TRANSPORT AND STORAGE Temperature limits for storage and transportation is 40 to +70 C. During transport and storage the sensors must be protected against precipitation and direct sunshine. 4. INSTALLATION 4.1 Mounting The current sensor has been type-tested installed to the CB type IN-CB, 17,5 kv, 1250 A, 31,5 ka. It can be used as well in derived CB type IN-CB with lower rated voltages, lower rated currents or lower rated short-circuit currents. Use in other equipment is prohibited. The sensor is to be fixed to the CB with an M8 screw; care must be taken to ensure a reliable earthing via the screw. Tightening torque 9-10Nm 4.2 Secondary connections The secondary cable is designed to give a maximum EMI shielding. Every sensor is accuracy tested equipped with its own, individual cable. The routine test report is not valid for the accuracy measurements if the cable is changed, shortened, lengthened or replaced. The minimum bending radius for the cable is 30 mm. It is not allowed to bend the cable, when the temperature is below 25 C. 4.3 Connection to the relay The secondary cable has a Twin-BNC connector that shall be connected to the inputs of the relay. Special precaution shall be taken to avoid mechanical strain or bending on the cable and the connectors during installation and use. A cable not connected to the relay can be left open or short-circuited without any harm for the sensor. Even during a primary short-circuit the voltage in the secondary circuit of the current sensor will be below 100 V. Nevertheless it is a good safety practice to earth cables not connected. Twin-BNC connectors have polarized contacts and two-stud bayonet lock coupling. When mating the Twin-BNC connector it is important to check that the plug s polarized contacts mates with the contacts of the receptacle. The plug must be inserted properly with the matting receptacle before completing the coupling with the bayonet lock. Take care and do not use force to plug-in these connectors. Do not rotate and press at the same time the connector is sensitive and could be damaged or destroyed. Page 4
5 4.4 Installation inspection Voltage test: Maximum power frequency test voltage for current sensor secondary terminals is 1,5 kv. Test voltage can be connected between two signal connectors in cable terminal connected together and earth. 5. MAINTENANCE Excessive dust or other kind of pollution must be brushed off the sensor. Polluted sensors can be cleaned with spirit, petrol or toluene. Traces of arcs and minor surface damages can be easily removed with sandpaper after which the surface is to be treated by applying a thin layer of silicone paste on it. Instructions for repairing greater surface damages (such as cracks) must be requested from the manufacturer. 6. RECOMMENDED PROCEDURE FOR DISPOSAL OF THE SENSOR The sensor does not contain environmentally hazardous materials. For disposal of the product after taken out of use, local regulations if any should be followed. Page 5
6 ABB ABB, s.r.o. Vídeňská Brno, Czech Republic Tel.: Fax.: VLM Rev.-, en The data and ilustrations in this instruction are not binding. We reserve the right to make changes of the content, in the course of technical development of the product. Page 6
Medium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance
Medium voltage products KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVCD A combined current
More informationKECA 80 C85 Current Sensor Instructions for installation, use and maintenance
Medium Voltage Products KECA 80 C85 Current Sensor Instructions for installation, use and maintenance 1. Operating conditions 2 2. Technical details 2 3. Instructions for installation 3 Safety instruction
More informationMEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 250 B1 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 C184; KECA 80 C216 CURRENT SENSORS INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope
More informationMedium Voltage Products. KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance
Medium Voltage Products KEVA 24 B20; KEVA 24 B21 Voltage Sensors Instructions for installation, use and maintenance Instructions for installation, use and maintenance for the KEVA 24 B20 and KEVA 24 B21
More informationMEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 80 D85 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 D85 CURRENT SENSOR INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope of Contents 2
More informationMEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance
MEDIUM VOLTAGE PRODUCT KECA 80 C85 Current Sensor Instructions for installation, use and maintenance 2 KECA 80 C85 CURRENT SENSOR INSTRUCTIONS FOR INSTALLATION, USE AND MAINTENANCE Scope of Contents 2
More informationKEVA 24 Cxx(c) Indoor voltage sensors for NEXANS Instructions for installation, use and maintenance
Medium Voltage Products KEVA 24 Cxx(c) Indoor voltage sensors for NEXANS Instructions for installation, use and maintenance 1. Operating conditions 2 2. Technical details 2 3. Instructions for installation
More informationKEVA 24 Cxx(c) Indoor voltage sensors Instructions for installation, use and maintenance
Medium Voltage Products KEVA 4 Cxx(c) Indoor voltage sensors Instructions for installation, use and maintenance 1. Operating conditions 3. Technical details 3 3. Instructions for installation 4 Safety
More informationCurrent accuracy class. Sensor principles
Indoor Combi Sensor 12, 17.5 and 25 kv 1250 A and 3200 A KEVCD Highest voltage for equipment kv 12.24 Rated continuous primary current A 1250.3200 Rated transformation ratio for current measurement, K
More informationInstruction manual. EK6 Earthing switch 36/40.5 kv
Instruction manual EK6 Earthing switch 36/40.5 kv Your safety first always! That s why our instruction manual begins with these recommendations: Only install switchgear and/or switchboards in enclosed
More informationMedium Voltage. KOFD Indoor Type Current Transformers Cast Resin Insulated. Catalogue. 12, 13.8, 17.5, 24 and 36 kv KOFD 1 GB
Catalogue Indoor Current Transformers Cast Resin Insulated 1, 13.8, 17.5, 4 and 36 kv 97-1 96-1054 Medium Voltage 1 Indoor Current Transformers Cast Resin Insulated 1, 13.8, 17.5, 4 and 36 kv Index Description...
More informationMEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers
MEDIUM VOLTAGE PRODUCT TJC 4 Indoor voltage transformers 2 TJC 4 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning impulse test voltage
More information1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide
1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationCombined Current and Voltage Instrument Transformer CVS-P-24-O Technical Specifications
4-O 1/15 Combined Current and Voltage Instrument Transformer CVS-P-4-O Technical Specifications Rev. Date Revision Description Prepared by Checked by Approved by 0 3/10/15 First Issue E. Scala L. Peretto
More informationTransformer bushings, type GOH. Technical guide
Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required
More information1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide
1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationResin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide
1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationCable current transformers for indoor applications. Product overview. Cable current transformers. for indoor applications.
Cable current transformers for indoor applications Product overview Cable current transformers for indoor applications Product overview 2 2 Contents 03 Introduction 05 Transformers for residual current
More information11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls
11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the
More informationIndoor switches for railway lines. single-pole design rated voltage up to 27,5 kv rated current up to 4000 A
Indoor switches for railway lines single-pole design rated voltage up to 27,5 kv rated current up to 4000 A General These Driescher indoor switching devices are specifically designed for railway applications.
More informationCGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv
Medium Voltage Switchgear Secondary Distribution CGMCOSMOS Fully gas-insulated modular and compact (RMU) system MV Switchgear Secondary Distribution Networks General description Introduction Ormazabal
More informationSurge arrester POLIM-H..SD
Data sheet Surge arrester POLIM-H..SD Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10
More informationCATALOGUE TRACTION OUTDOOR DISCONNECTORS TYP QAD 3. 3 kv DC; 2500; 3000; 4000; 4500 A
CATALOGUE TRACTION OUTDOOR DISCONNECTORS Unsere Handelsvertretung in Deutschland TYP QAD 3 3 kv DC; 2500; 3000; 4000; 4500 A ISO 9001:2009 ISO 14001:2005 APPLICATION The outdoor traction disconnectors
More informationUniSec Maintenance solutions
DISTRIBUTION SOLUTIONS UniSec Maintenance solutions ABB supports you to improve the reliability, safety and efficiency of your electrical equipment UniSec Maintenance solutions Table of contents 004 00
More information1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide
1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More information1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide
1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationOutdoor vacuum breaker for railway applications - FSK II
Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL
More informationVoltage limiting device HVL
Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3
More informationZinc Oxide Surge Arrester PEXLIM Q
Zinc Oxide Surge Arrester Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. in areas with high lightning intensity and high
More informationMCset kv Medium voltage equipment
Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide
More informationNXPLUS C Single busbar. Maintenance-free for lifetime
NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage
More informationResin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK
1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,
More informationElectronic overload relays EF205 and EF370
Data sheet Electronic overload relays EF205 and EF370 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents
More informationVoltage limiting device HVL
Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3
More informationZinc Oxide Surge Arrester EXLIM R
Zinc Oxide Surge Arrester EXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. For use when requirements of lightning intensity, energy
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More information8DJ. Maintenance-free for lifetime
8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and
More informationCATALOGUE TYP QDS. 7,2-25 kv
CATALOGUE TYP QDS 7,2-25 kv Unsere Handelsvertretung in Deutschland ISO 9001:2009 ISO 14001:2005 GENERAL INFORMATION switches) are switching devices used to switch electrical circuits in load operating
More information1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationPIX-H Metal-clad switchgear up to 17.5kV
AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...
More informationSurge arrester POLIM-H.. ND
DATA SHEET Surge arrester POLIM-H.. ND Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10
More informationINSTRUCTION MANUAL CRS Combined insulation bushing
INSTRUCTION MANUAL CRS Combined insulation bushing 5COH020200 CRS REV03 2 TABLE OF CONTENTS 1 SAFETY... 5 1.1 SAFETY INSTRUCTION... 5 1.2 SPECIFIED APPLICATION... 5 1.3 SAFETY NOTES ON THE EQUIPMENT OPERATION...
More informationContactors. CL1115/02, CL1215/02, CL1315/02 1, 2 and 3 pole AC and DC NO contactors for voltages up to 1,500 V Catalogue C25.en
Connect - Contact - Control 3 Contactors CL1115/02, CL1215/02, CL1315/02 1, 2 and 3 pole AC and DC NO contactors for voltages up to 1,500 V Catalogue C25.en 2 CL1115/02, CL1215/02, CL1315/02 1, 2 and 3
More informationcor Long Run Experience
Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30
More informationZX-Family Gas-insulated medium voltage switchgear
ZX-Family Gas-insulated medium voltage switchgear Minimum overall costs ZX offers maximum economy The compact design of the panels reduces the space required and therefore the size of the station. Freedom
More informationZinc-Oxide Surge Arrester TEXLIM Q-C
Zinc-Oxide Surge Arrester TEXLIM Q-C Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching overs. in areas with very high lightning intensity where
More information1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide
1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationHigh Voltage Surge Arresters Buyer s Guide Section PEXLIM R
High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching
More informationType SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear
Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated
More informationSurge arrester POLIM-C.. HD
DATA SHEET Surge arrester POLIM-C.. HD Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-A High current impulse I hc (4/10
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays are the alternative to the thermal overload relays. An electronic overload relay offers reliable and fast protection
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More informationSpecial Purpose Fuses
Special Purpose Fuses Fuses for DC voltage applications www.eti.si ETI Elektroelement d.d. Obrezija 5, SI - 111 Izlake Slovenija Tel. + 38 03 5 57 570 Faks + 38 03 5 7 077 eti@eti.si NH DC 80 V - Telecom
More informationVacuum Circuit Breaker VS1
Vacuum Circuit Breaker VS1 Product features Conform to GB, IEC, DL and JB standards KEMA type test Level A certificate Ideal contact material and shape, ensuring low current carrying value and stable contact
More informationTHP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com
THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated
More informationThermal-Magnetic Circuit Breaker 2210-S291-P9M A
Thermal-Magnetic Circuit Breaker 0-S9-P9M-40033-...A Description Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact
More informationType HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv
Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other
More informationKYN28-12(GZSI-12Z)Armoured Middle-Mounted Metal. Enclosed Switch. 1.General. 2.Model Definition
KYN28-12(GZSI-12Z)Armoured Middle-Mounted Metal Enclosed Switch 1.General KYN28-12 armoured middle-mounted metal enclosed switchgear (hereinafter referred to as switchgear) is a new product with own design
More informationAIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE
AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly
More informationPABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY
PABS Air-to-SF 6 Bushings 7.5-800 kv BUSHINGS AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS 7 - ANSI STANDARDS AN ALSTOM COMPANY PABS bushings are gas-insulated types that meet IEC 7, ANSI/IEEE or
More informationMiniature circuit-breaker (MCB) SH200M Series
Miniature circuit-breaker (MCB) SH200M Series 25 mm² cage terminals, a well proven and reliable technology. IP20 - finger safety. Scratch and solvent resistant marking due to laser printing. Easy identification
More informationInnovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual
Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION
More informationType IMC Indoor current transformer
Instrument transformers Type IMC Indoor current transformer Product features 600 volt indoor 10 kv BIL 25 through 400 Hertz amperes: 50-1000 2.5" (64 mm) round window Designed for variable applications
More informationUniGear. Technical Guide
UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating
More informationThe vacuum circuit breaker for commercial buildings, industrial plants and utilities
The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing
More informationUniGear type ZS1. Medium voltage, arc-proof, air-insulated, metal-clad switchboard
UniGear type ZS1 Medium voltage, arc-proof, air-insulated, metal-clad switchboard 2 UNIGER TYPE ZS1 UNIGER DOUBLE LEVEL UNIGER TYPE ZVC TECHNICL DT 4 6 8 10 1 2 3 4 3 UNIGER TYPE ZS1 UniGear is the new
More informationATM Lighting sp. z o.o
INSTALLATION AND MAINTENANCE MANUAL FOR LIGHT FITTING INX230LED Carefully read the instructions before mounting the light fitting. ATM Lighting sp. z o.o., ul. Budowlanych 31, 80-298 Gdańsk, tel: +48 58
More informationThermal overload relay TF140DU and TF140DU-V1000
Data sheet Thermal overload relay TF140DU and TF140DU-V1000 Thermal overload relays are economic electromechanical protection devices for the main circuit. They are used mainly to protect motors against
More information15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly
More informationTransformer bushings, type GOA 250. Installation and maintenance guide
Transformer bushings, type GOA 250 Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor
More informationDRX 125 Circuit breaker (not adjustable)
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 272 20/21/22/23/24/25/26/27/55/56/57/58/59/60 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4.
More informationMetal Clad Air Insulated Switchgear
Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system
More informationUniSec licensed by ABB, produced by Metix WHERE ENERGY LIVES COMPLETE SOLUTIONS
COMPLETE SOLUTIONS WHERE ENERGY LIVES METAL AND CONCRETE TRANSFORMER SUBSTATIONS DISTRIBUTION SWITCHGEAR UP TO KV - UNISEC ELECTRICAL SWITCHBOARDS LOW AND MEDIUM VOLTAGE ELECTRICAL EQUIPMENT UniSec licensed
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationR-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A
R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic
More informationMEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear
MEDIUM VOLTAGE PRODUCTS Powerbloc Pre-assembled modules for building medium voltage switchgear Powerbloc are the ideal solution for replacing fixed circuit breakers with withdrawable circuit breakers,
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationMEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices
MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect
More informationشركة كهرباء محافظة القدس المساهمة المحدودة
Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories
More informationM-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)
M-RING 24 SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A) Contents General Description Advanced facilities and process Advanced design philosophy Definition of M-RING 24 Standards Service conditions
More informationMedium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A
Medium voltage compact switchgears rated voltage 12 and 25 kv rated current 400 and 630 A 1 General The new air-insulated DRIESCHER medium voltage compact switchgears are ideal for application in secondary
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does
More informationCPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards
Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1
More informationProduct presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution
Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 New RIS transformer bushings The paper-free solution Transformer condenser bushings Why a new technology? To preserve
More information023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA
023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir
More informationHigh reliability against cyclic and peak current loads / age resistant due to high motor start up currents
HHM High Voltage Fuses Motor Circuit Protection DIN and British Standard SIBA Motor Rated Fuses are available in - German DIN Standard and - British Standard Design The large variety in body sizes / mounting
More informationEMPAC Metal enclosed capacitor bank for wind applications
EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More informationInductive voltage transformers
Inductive voltage transformers Outdoor operation Oil-paper insulated EOF (24 245) kv General description Voltage transformers type EOF are used in high voltage networks within the 24 245 kv range. They
More informationContactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control
Connect - Contact - Control 3 Contactors CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en More information at: schaltbau-gmbh.com 42 CH1130/02 Single pole high-voltage contactor
More informationMotorized switch-disconnectors OTM 40 to 125 Amperes
Motorized switch-disconnectors OTM to 125 mperes With the new range of motorized-switch disconnectors, BB offers now a full range from to 2500 mperes. Thanks to the design, OTM...125 are a good solution
More informationSurge arrester POLIM-H..N
Data sheet Surge arrester POLIMH..N Technical data Arrester class SH, Station High Line discharge class (LD) 4 Nominal discharge current I n (8/20 µs) 20 ka peak Repetitive charge transfer rating Q rs
More informationUltra Fast Earthing Switch UFES retrofit Overview
Gordon van der Linde ABB PTMV - Service Ultra Fast Earthing Switch UFES retrofit Overview May 20, 2013 UFES Slide 1 Ultra Fast Earthing Switch UFES retrofit Content 1. Effects of an internal arc 2. The
More informationPHOENIX CONTACT
Current transformers INTERFACE Data sheet 03359_en_03 PHOENIX CONTACT 20-04-04 Description The PACT Analog current transformers form a complete range of bus-bar, plug-in and winding current transformers
More informationDRX 100 B/N/H Circuit breaker (not adjustable)
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4. MOUNTING 2 5. CABLING 3 6. ELECTRIC AND MECHANICAL
More information