1 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and maintenance of arc resistant type MVS rcgard metal-enclosed switchgear assemblies ontents escription Page Introduction Installation Switchgear assembly inspection before startup...11 Operation Maintenance uplex switchgear configuration Plenum installation MVS switchgear bolt tightness for bus connections rc resistant type MVS rcgard metal-enclosed switchgear field taping procedure (5/15 kv)

2 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and 2 TON

3 Instructions for installation, operation, and Instruction ooklet I022002N ffective pril 2018 isclaimer of warranties and limitation of liability This instruction booklet is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized aton sales representative. The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate aton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and aton. NO WRRNTIS, XPRSS OR IMPLI, INLUING WRRNTIS OF FITNSS FOR PRTIULR PURPOS OR MRHNTILITY, OR WRRNTIS RISING FROM TH OURS OF LING OR USG OF TR, R M RGRING TH INFORMTION, ROMMNTIONS, N SRIPTIONS ONTIN HRIN. In no event will aton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect,incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein. TON 3

4 Instruction ooklet I022002N ffective pril 2018 Read and understand these instructions before attempting installation, operation, or maintenance of this equipment. This equipment must be installed and serviced only by qualified electrical personnel. Retain this document for future use. WRNING HZR OF LTRIL SHOK OR URN. OPRTING TH SWITHGR SSMLY OUTSI OF ITS RTINGS MY US FILUR RSULTING IN PROPRTY MG, SVR PRSONL INJURY, OR TH. TH SWITH- GR SSMLY MUST OPRT WITHIN ITS NMPLT RTINGS. WRNING HZRS OF R FLSH, R LST, N LTRI SHOK XIST WHN THIS QUIPMNT IS NRGIZ, WHIH MY L TO TH OR SVR INJURY. LL WORK SSOIT WITH THIS LTRIL QUIPMNT MUST PRFORM ONLY Y QULIFI PRSONNL S FIN IN NFP-70. ONSULT NFP-70, OSH, N NY OTHR PPLIL RGULTION PRTINING TO OPRTOR SFTY PRIOR TO SRVIING QUIPMNT. TH QULIFI PRSONNL MUST FOLLOW LL PPLIL PRSONL PROTTIV QUIPMNT RQUIRMNTS. O NOT TTMPT NY WORK ON THIS QUIPMNT SUH S INSTLLING OMPONNTS, PRFORMING NY XMINTIONS, PRFORMING NY JUSTMNTS, PRFORMING NY SRVIING, OR PRFORMING NY MINTNN WHIL IT IS NRGIZ. FOR PRFORMING NY WORK, FOLLOW LL PPROPRIT HZR SSSSMNT N NRGY ONTROL PRUTIONS N PROURS. VRIFY NO VOLTGS R PRSNT ON LL INOMING N OUTGOING ONUTORS, N NY NRGY SOURS ONTIN WITHIN TH QUIPMNT PRIOR TO SRVIING, THN GROUN (ONNT TO RTH) LL INOMING N OUTGOING ONUTORS TTH TO THIS QUIPMNT N TO NY INTRNL NRGY SOURS. NGR LL PPLIL SFTY OS, SFTY STNRS, N SFTY RGULTIONS MUST HR TO WHN INSTLLING, OPRTING, OR MINTINING THIS QUIPMNT. Instructions for installation, operation, and Section 1: Introduction 1.1 Purpose This instruction book is expressly intended to cover the installation, operation, and maintenance of arc resistant Medium Voltage type MVS rcgard metal-enclosed switchgear assemblies. It is not encompassing of all possible contingencies, variations, and details that may arise during installation, operation, or maintenance of this equipment. If further information is desired by the purchaser regarding this particular installation or application information, contact the local aton lectrical, Inc. sales office, see the appropriate section of aton lectrical, Inc. onsulting pplication Guide, and review the appropriate industry standards. 1.2 escription and application The arc resistant type MVS rcgard metal-enclosed switchgear assemblies consists of one or more vertical sections of metalenclosed switchgear as defined in industry standard merican National Standards Institute/Institute of lectrical and lectronic ngineers (NSI/I) Typically, each vertical section contains an air insulated, three-pole, gang-operated, quick-make, quickbreak, load interrupter switch. It can be applied in combination with power fuses to provide safe, economical switching and overcurrent protection where infrequent disconnecting means is required. 1.3 ocumentation references Refer to the customer drawing package for order specific information. For further information on installation and application, refer to the applicable descriptive bulletins, publications, and/or industry standards. ownload aton information from For receiving, handling, storing and installation instructions: I022014N. For arc plenum and duct installation: I For MVS/MVS2 switch: I aton contact information For additional information about aton products please call or log onto dditional medium voltage switchgear information regarding Pricing/ftermarket, ustomer Service, ngineering/technical Information, or Warranty, can be found by calling aton lectrical Services and Systems (SS) can be reached at If further information is desired regarding this particular installation or application information, contact the local aton sales office, reference aton s onsulting pplication Guide, or the appropriate industry standards. 1.5 Terminology Metal-enclosed load interrupter switchgear: This is an assembly of metal vertical sections as defined in NSI/ I Load interrupter switch: The basic switching and fault-closing device used in metal enclosed, load interrupter switchgear. Fuse: device used in conjunction with a load interrupter switch to provide overcurrent and short-circuit protection. 4 TON

5 Instructions for installation, operation, and 1.6 Safety precautions WRNING ONLY QULIFI LTRIL WORKRS WITH TRINING N XPRIN ON HIGH VOLTG IRUITS SHOUL PRMITT TO WORK ON THIS QUIPMNT. THY SHOUL FMILIR WITH TH WORK TO PRFORM, TH SFTY QUIPMNT RQUIR, N HZRS INVOLV. Instruction ooklet I022002N ffective pril 2018 Table 1. Power Frequency Withstand Test Voltages Rated Maximum Voltage (kv) Power Frequency Withstand (rms) (kv) Read and understand these instructions before attempting any assembly, operation, or maintenance of an arc resistant MVS switchgear assembly. 2. isconnect all low voltage and medium voltage power sources before working on the equipment per Occupational Safety and Health ct (OSH) and local lockout and tag out procedures. Verify voltages have been removed, both ground load and line side connections. Observe the National Fire Protection ssociation s (NFP) Publication #70 that is commonly known as the National lectrical ode (N), OSH, and local procedures and standards. This includes visual inspections while the vertical section door is open, making any adjustments inside or outside the switchgear vertical section, performing maintenance, or installing replacement parts. 1.7 Switchgear identification nameplate is located inside the small access door of each arc resistant type MVS switchgear vertical section (see Figure 1). ontained on this nameplate are the aton master parts list number and all the necessary switchgear ratings. This information should be given to the aton sales office if a question should arise concerning the switchgear or if renewal parts are required. This information is sufficient for aton to find the manufacturing information for the switchgear. 3. The front lower/upper doors cannot be opened with the switch in the LOS position. In addition, the switch cannot be closed with the vertical section doors open. This is prevented with the use of the key interlock system. 4. efore opening the lower door of the vertical section, look through the window on the upper door to ensure that all three main blades and flicker blades are OPN. If necessary, use an additional suitable light source. WRNING FTING OR ISNGGING SFTY INTRLOKS ON MVS2 SWITH THT IS PROPRLY INSTLL IN MVS SWITHGR SSMLY N ONNT TO POWR SOUR MY RSULT IN PROPRTY MG, OILY INJURY, OR TH. O NOT FT OR ISNGG NY SFTY INTRLOKS WHN TH SWITHGR IS IN SRVI. efore energizing the switchgear assembly: 5. Make sure the MVS switchgear assembly is securely fastened to a true and level surface according to the floor plan of the customer drawings. 6. lways be sure that all hardware is in place and secured by tightening or using safety fasteners before putting an MVS2 switch into operation (see Section 6). 7. onfirm that all arc chutes and barriers are installed. 8. onfirm that no tools or other objects are left inside the vertical section. 9. onfirm that all devices, doors, and covers are in place. 10. efore startup, perform a field power frequency withstand (Hi-Pot) test, using test voltages given in Table 1. Figure 1. Typical Nameplate. WRNING XING NMPLT RTINGS OF R RSISTNT MVS SWITHGR OUL US PROPRTY MG, SVR INJURY, OR TH. R RSISTNT MVS SWITHGR MUST OPRT WITHIN ITS NMPLT RTINGS. TON 5

6 Instruction ooklet I022002N ffective pril Safety features rc resistant type MVS load interrupter switchgear has several built-in features to reduce hazards and to provide proper operating sequences. 1. door key interlock prevents opening the enclosure s lower front door while the load interrupter switch is in the losed position. 2. switch key interlock prevents manual operation of the switch s operating mechanism with the door open. Instructions for installation, operation, and WRNING OPRTING MVS2 SWITH WITH KY INTRLOK OLT XTN WILL RSULT IN QUIPMNT MG N MY LSO XPOS PRSON TO OILY INJURY OR TH. TH KY MUST INSRT INTO TH INTRLOK N ROTT TO RTRT TH LOKING OLT FOR OPRTING MVS2 SWITH. 3. viewing window is provided in the upper front door to visually verify the switch contact position. 4. Facilities are provided for padlocking the switch in the Open or losed position (manually operated only). 5. Mechanical indicators show whether the switch mechanism is Open or losed. 1.9 Ratings and standards Table 2. rc-resistant MVS Metal-enclosed Load Interrupter Switchgear ssembly Ratings. Switchgear ssembly Ratings per I Rated Maximum Voltage Power Frequency Withstand Voltage, 60 Hz, 1 Minute Lightning Impulse Withstand Voltage (L/WV) (IL) Rated Main us ontinuous urrent Rated Momentary Short-ircuit urrent Withstand (10 cycle) (167 ms) Rated Shorttime Short- ircuit urrent Withstand (2 Second) Switchgear ssembly Internal rc Withstand ccessibility Type Rated Internal rc Short-circuit Withstand urrent kv rms kv rms kv Peak mperes k rms sym k Peak k rms sym k rms Sym k Peak Sec , , , , , , , Rated Internal rc Short- ircuit uration Table 3. rc Resistant MVS Switchgear Standards. Related apability Underwriters Laboratory (UL) or anadian Standards ssociation (S) Listing to: Standards ocument Rating NSI/I NSI/I NSI S (anada) Listing to: N/S 22.2 No 31 6 TON

7 Instructions for installation, operation, and Section 2: Installation For information regarding the receiving, handling, storing, and installation of the equipment, please reference I022014N: Instructions for receiving, handling, sotrying, and installation of medium voltage switchgear, in addition to the customer drawing package. Refer to shipping list for location of the bus, hardware, and all other joining and installation material. 2.1 Floor requirements The finished foundation surface shall be flat and level within 0.06 in. (1.6 mm) in 36 in. (914 mm) in any direction, left to right, front to back, and diagonally. lternatively a local flatness FF value of 50 or higher and an accompanying FL value of 37 to 40 as defined in industry standard STM and industry standard I may be used to establish the flatness and levelness of the finished foundation. 2.2 Joining type MVS enclosures ccess to MVS switchgear vertical sections containing switches ach MVS2 switch is shipped from the factory in the closed position to maintain alignment during shipping and handling. When handling MVS switchgear, be sure the switches are in the losed position. The safety key interlocking prevents opening of the door of the vertical section when the switch is closed. In order to gain access to the interior, be sure the switchgear assembly is on a true and level surface (according to the floor plan of the customer drawings). To open a manually operated MVS2 switch insert the operating handle and push down. When the switch opens the door may be opened. o not operate MVS2 switches unless the switchgear assembly is setting on a true and level surface Id entification of shipping splits Refer to the front view on the switchgear assembly drawing. eneath this view, shipping splits will be identified in relation to group numbers for each vertical section. Normally, shipping sections will not exceed 92 in. ( mm) in width Proced ures for joining rcgard MVS enclosures at shipping splits uring the following steps, please refer to Figure 2. Instruction ooklet I022002N ffective pril Supplied to connect the units where shipping split are necessary are in. bolts, flat washers, lock washers, and nuts from each connection point. 2. Position the shipping sections next to each other. The four holes will match holes in the adjacent side sheets. In some cases, it may be necessary to use of an aligning tool such as a punch to move the structures into alignment. 3. olt the side sheets together using the supplied hardware. 4. Make the main and ground bus connections using the links and hardware furnished. The bus bar is tin or silver-plated. To insure a proper electrical connection, care should be taken to protect the plating from damage. O NOT use joint compound. UTION LNING US JOINTS WITH RSIV OR HMIL LNSRS MY RMOV PLTING, WHIH MY US JOINT OVRHTING. TO LN TH SURFS, WIP THM WITH LN, RY LOTH. 5. olted connections should be tightened to the torque values given in Table 5 in Section onnection of customer power cables Figures 3 through 13 show the suggested means for connection of the incoming or exiting cables (maximum of two per phase, 500 kcmil) in MVS switchgear. The letters in each figure apply to the itemized subjects following. ll necessary materials to perform the cable installation are to be provided by others unless specifically noted otherwise in the detailed instructions below, or where specifically purchased with the switchgear assembly. To install the incoming and exiting cables, follow these instructions.. The switchgear terminals For incoming power, the terminals are usually located at the top of the switch in a vertical section. For outgoing circuits, the terminals are beneath the switch if unfused, or on the fuse mounting if fused. ach terminal pad has a 2-hole pattern suitable for either a single-hole terminal or a terminal with a 2-hole National lectrical Manufacturers ssociation (NM) drilling pattern. The terminal lugs for the cable, if purchased with the switchgear, will be bolted to the switchgear terminals. If the terminal lugs are not there, then they are to be provided by others. The terminals of the switchgear are not suitable to support the weight of the cable. It will be necessary to support the weight of the cable with the cable support angle discussed in below.. able electrical stress relief devices The design of rcgard MVS switchgear is based upon the use of pre-formed type electrical stress relief devices such as 3-M Quickterm-II, Raychem heat shrink termination systems, etc. The stress relief devices are to be provided by others.. able support channel(s). The cable support devices are supplied by the installer unless specifically purchased with the rcgard MVS switchgear. MVS cable supports, when supplied, are made of structural framing channel. The cable supports must be mounted to suit the geometry of the installation. The means to fasten the cable to the cable supporting devices are to be provided by others. There are a large number of commercially available cable support devices that can be fastened to the structural framing channel to support the cable so the cable weight is not hanging on the switchgear terminals. Figure 2. Joining the MVS nclosures. TON 7

8 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and WRNING FILUR TO INSTLL TH L SUPPORT MY RSULT IN MG TO TH SWITHGR TRMINLS, WHIH IN TURN MY RSULT IN MJOR QUIPMNT MG N US SVR PRSONL INJURY OR TH. T ON US TH L SUPPORT MUST INSTLL S INSTRUT IN THIS OUMNT.. Lashing cord or other equivalent materials/means The cables must be lashed together to restrain the cables if a short circuit should occur. This material is to be provided by others. For large cables and/or cable reverse loops, it may also be necessary to lash the cable bundle(s) to the support channel. The views show this suggested fastening of the cable bundles. WRNING FILUR TO LSH TH LS TOGTHR MY RSULT IN MG TO TH SWITHGR, WHIH IN TURN MY RSULT IN MJOR QUIPMNT MG N US SVR PRSONL INJURY OR TH. TH L MUST LSH TOGTHR S INSTRUT IN THIS OUMNT.. urrent transformer(s) The current transformers are to be mounted on the side of the cable support that will physically support the current transformers so they will not slide down onto the stress relief devices. The high voltage cable is to be routed through the current transformer. SI STION VIW RR STION VIW Figure Top 4. Top able able ntrance ntrance (nergy (nergy Source) Source), Rear Rear ccess ccess. The H1 side of each current transformer is to be towards the normal source of electric power. ach current transformer secondary wiring is terminated at a plug. This plug is to be placed in the terminal block receptacle to match the phase on which the current transformer is mounted. The switchgear terminals will have phase labeling. The secondary wires are to be fastened to the support channel so they cannot fall into high voltage parts. WITH OR WITHOUT FUSS T ON US T ON US SI STION VIW RR STION VIW Figure 5. Unfused ottom ottom able able xit xit (to Load) (to Load), Rear Rear ccess ccess. SI STION VIW RR STION VIW Figure 3. ottom able ntrance (nergy Source), Rear ccess. 8 TON

9 Instructions for installation, operation, and Instruction ooklet I022002N ffective pril 2018 WITH OR WITHOUT FUSS T ON US SI STION VIW Figure 6. Top able xit (to Load), Rear ccess. RR STION VIW FRONT STION VIW SI STION VIW Figure 8. Top able ntrance (nergy Source), Front Front ccess ccess. T ON US T ON US FRONT STION VIW SI STION VIW FRONT STION VIW SI STION VIW Figure 7. ottom able ntrance (nergy Source), Front ccess Pull Section. Top Figure able 9. Top ntrance able ntrance (nergy Source) (nergy Source) Front ccess Front ccess Pull Section Pull Section. TON 9

10 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and FRONT STION VIW SI STION VIW Figure 10. ottom able xit (to Load of Fuse), Front ccess or able in Front. FRONT STION VIW SI STION VIW Figure Top 12. able Top able xit xit (to Load (to Load of Switch) of Switch), Front Front ccess ccess. FRONT STION VIW SI STION VIW Figure Top 11. able Top able xit xit (to Load (to Load of Fuse) of Fuse), Front Front ccess ccess. FRONT STION VIW SI STION VIW Figure 13. ottom able xit (to Load of Switch), Front and Rear ccess. ottom able xit (to Load of Switch) Front and Rear ccess 10 TON

11 Instructions for installation, operation, and 2.4 Securing rcgard MVS switchgear ssemblies to foundations ll anchoring hardware and necessary devices are supplied by aton. If the switchgear assembly was purchased for seismic applications, follow the instructions on the specific drawings provided for the switchgear assembly that address the anchoring details. nother drawing addresses the load bearing requirements. Indoor or outdoor vertical sections are secured using clips and foundation bolts. nchors and lag screws may be used in place of J-bolts if desired. 2.5 onnection of space heaters to customers source Space heaters, when supplied, must be energized to prevent condensation. Heaters are supplied for 120- or 240-volt sources as shown on the drawings. For switchgear assemblies with or without heater control devices, heaters will be internally wired and brought to a terminal block. wiring diagram will be furnished with the drawings showing connection points for power. Instruction ooklet I022002N ffective pril 2018 Section 3: Switchgear assembly inspection before startup ach switch is properly adjusted at the factory before shipment. However, vibration and mechanical stresses imposed by transit and installation can adversely affect switch adjustment. Therefore, a final inspection is essential before energizing. If this inspection reveals any defects in adjustment, they should be corrected according to alignment procedures in I heck the bolted bus connections for proper tightness, referring to Section 8 for torque values. 2. If bolt-in type mounted fuses are supplied, check the hardware that hold the fuses in place is tightened to specified values. 3. For units fitted with expulsion-type, boric acid fuses, check the discharge filters on the lower end of the fuses are securely hand tight or ideally 62 in.-lbs (7.0 N m). 4. heck to see if the space heaters, if supplied, are energized. 5. Wipe away any dust or dirt that may have accumulated in compartment(s), paying particular attention to insulators and insulating material. WRNING US OF SOLVNTS, OILS, JOINT OMPOUNS, OR GRSS ON OR NR NORYL INSULTION WILL STROY IT. LN ONLY WITH WTR OR ISOPROPYL LOHOL. WRNING NORYL INSULT QUIPMNT: LTRIL JOINT OMPOUNS MUST NOT US ON ONNTIONS OR TRMINTIONS TO OR FROM THIS QUIPMNT. O NOT US SOLVNTS, OILS, OR GRSS ON OR NR THIS QUIPMNT. WTR N ISOPROPYL R TH ONLY PPROV LNRS FOR THIS QUIPMNT. UTION ISOPROPYL LOHOL IS FLMML. PROVI QUT VNTILTION N KP WY FROM FLMS N OTHR IGNITION SOURS. ONSULT YOUR SFTY PRTMNT FOR USING. 6. final thorough inspection should be made to ensure that no tools or other objects are accidentally left inside the enclosure. WRNING FTING OR ISNGGING SFTY INTRLOKS ON MVS2 SWITH THT IS ONNT TO POWR SOUR MY RSULT IN PROPRTY MG, OILY INJURY OR TH. O NOT FT OR ISNGG NY SFTY INTRLOKS. TON 11

12 Instruction ooklet I022002N ffective pril 2018 Section 4: Operation The MVS2 manually operated switch is equipped with switch interlocks and door interlocks as well as provisions for padlocking in either the open or closed position. See I for details of the interlocks and their functions. 4.1 Fuse replacement WRNING FILUR TO OMPLTLY ISONNT TH MVS SWITHGR SSMLY FROM LL POWR SOURS PRIOR TO INSPTION MY RSULT IN SVR INJURY OR TH. TH SWITHGR SSMLY MUST OMPLTLY ISONNT FROM LL POWR SOURS N GROUN FOR PRFORMING NY INSPTION. WRNING WHN SSING FUSS, FILUR TO SSUR THT TH FUSS R -NRGIZ MY RSULT IN QUIPMNT MG, OILY INJURY, OR TH. MK SUR THT LL POWR SOURS R -NRGIZ FOR TTMPTING TO SS TH FUSS. 1. ll devices that could energize the fuse should be opened, padlocked, and tagged so that inadvertent closure cannot create a hazard. 2. The MVS2 switch should be opened by rotating the handle downward. 3. efore opening the door, look through a window to visually verify that all blades are disengaged from their break jaws. 4. fter opening the door, an appropriate medium voltage sensing device should be used to determine if voltage is present. 5. If no voltage is present, a suitable grounding device should be attached to the fuse terminals to discharge any static charge and assure that the fuse terminals remain at ground potential. 6. Remove the two bolts at the top of the fuse along with the two bolts at the bottom of the fuse. Fuses are then free to be removed. Re-install the new fuse using the same hardware and torque to proper value listed in Section 8. Instructions for installation, operation, and Section 5: Maintenance WRNING FILUR TO OMPLTLY ISONNT TH MVS SWITHGR SSMLY FROM LL POWR SOURS PRIOR TO INSPTION MY RSULT IN SVR INJURY OR TH. TH SWITHGR SSMLY MUST OMPLTLY ISONNT FROM LL POWR SOURS N GROUN FOR PRFORMING NY INSPTION. 5.1 Inspection schedule The switchgear should be inspected on a regular periodic basis to ensure all components are functioning correctly and the insulation system integrity is being maintained. See the appropriate instruction documents for the component devices. 5.2 Inspection procedure Wipe away any dust or dirt that may have accumulated inside each switchgear vertical section, paying close attention to insulators and insulating material. 5.3 Insulation and conductor maintenance lectrical parts e-energize primary circuits before removing any enclosure parts. efore cleaning, take MGGR readings between live parts and to ground. Inspect for signs of overheating or weakened insulation. Remove dust from conductors, live parts, insulators, component insulation, and enclosure surfaces. n industrial grade vacuum cleaner would assist this procedure. Wipe clean with isopropyl alcohol or distilled water only, then wipe dry. UTION ISOPROPYL LOHOL IS FLMML. PROVI QUT VNTILTION N KP WY FROM FLMS N OTHR IGNITION SOURS. ONSULT YOUR SFTY PRTMNT FOR USING. fter the live parts and drive rod links have been dusted and wiped clean, take MGGR readings again between the live parts and between phases. Keep a record of these readings for future reference in determining when trends occur that would indicate a lowering of the insulation resistance. Periodic high potential tests are not required after initial start-up and are recommended only after repair of high voltage live parts or insulation, or when the trend of MGGR readings indicates it to be advisable. This field test should be made before the main cables are connected and should not exceed the values in the Table 4. Table 4. Field ielectric Test Values. kv LSS Test Voltage, 60 Hz, pplied for One (1) Minute TON

13 Instructions for installation, operation, and The intent of the cleaning procedure is to remove as much dirt, dust, and other foreign material as possible from the insulation with minimum exposure to any solvents. The recommended cleaning procedure is to use a lint-free cloth. In most cases this will be sufficient. For accumulations that cannot be removed by the above procedure, a lint-free cloth, slightly dampened with water, can be used. llow the apparatus to dry for at least four hours at room temperature before energizing or testing. If a lint-free, water dampened cloth does not produce satisfactory results, use a lint-free cloth dampened with isopropyl alcohol. ry the same as when using a water-dampened cloth. Instruction ooklet I022002N ffective pril 2018 Section 6: uplex switchgear configuration When supplied, the duplex configuration consists of two vertical sections containing MVS2 switches connected together by a common bus on the hinge terminals of each switch. This, in turn, is connected to one set of fuses located in one of the switch compartments. This arrangement allows the selection of either of two incoming lines. UTION ISOPROPYL LOHOL IS FLMML. PROVI QUT VNTILTION N KP WY FROM FLMS N OTHR IGNITION SOURS. ONSULT YOUR SFTY PRTMNT FOR USING. 5.4 Lubrication Lubrication should be done during routine maintenance. ll excess lubrication must be removed with a clean cloth to prevent any accumulation of dust or dirt. void any lubrication on insulation. are must be taken to prevent any non-conductive lubricant from reaching any current carrying contact surface. See I for the MVS2 switch lubrication requirements. For other components see the appropriate instruction documents for those components, for their lubrication requirements. Figure 14. uplex Selective Switch Operation. This arrangement is always supplied with key interlocking for safe operation. Key interlocking consists of a lock on each switch to lock the switch in the Open position and a lock on each lower door to lock each lower door closed. ach of the locks is keyed alike and only one key must be available to operating personnel. Since the key is retained in its lock when a switch is closed or when a door is opened, two things are assured: Only one switch may be closed at a time to prevent paralleling of incoming lines. oth switches must be locked in the open position to unlock either lower door, preventing access to energized load side bus or fuses. WRNING ONLY ON KY SHOUL VILL TO OPRTING PRSONNL FOR THIS INTRLOK SHM. WHN SHIPP FROM TH FTORY, H LOK WILL HV SPRT KY. LL XTR KYS MUST STROY OR OTHRWIS M INSSIL TO OPRTING PRSONNL. FILUR TO O SO OUL RSULT IN SVR INJURY OR TH. TON 13

14 Instruction ooklet I022002N ffective pril 2018 Section 7: Plenum installation Note: This section is for rcgard MVS style enclosures only. If you have a MVS section connected to V-W rc Resistant Switchgear or MPGR rc Resistant Motor ontrol enters please refer to I WRNING O NOT OVR-TIGHTN SLF-TPPING SRWS. IF NY SLF TP- PING SRWS STRIP URING INSTLLTION, THY MUST HV NUT INSTLL ON TH INSI TO SUR THM. TH NUT SHOUL INSTLL TO TH SM TIGHTNSS VLU S TH SLF TPPING SRW. FOR THIS RSON, IMPT TOOLS R NOT ROMMN. LL SRWS MUST INSTLL WITH FLT WSHR UNR TH H OF TH SRW. ONNTIONS USING STNR SRW N NUT MUST HV FLT WSHR UNR TH SRW H N OTH FLT WSHR N LOK WSHR UNR TH NUT. IF USING KPS NUTS, TH FLT WSHR N LOK WSHR SHOUL OMITT FROM TH NUT. Note: t least one section in every lineup will have an exhaust duct exiting from either the side or the front of the plenum. These sections can be identified because they have a square opening for the duct collar. Identify these sections and install them first, for ease of assembly. If possible, install the duct collar before moving the plenum into position. If this is not possible, first install the plenum sections which have duct cutouts, then lift the duct collar inside the plenum and install it before installing additional plenum sections. The duct collars can ONLY be installed from the INSI of the plenum, so it is critical that they are not left until the end. Instructions for installation, operation, and 1. nsure all shipping splits of the switchgear are installed, coupled, and bolts are torqued. 2. Use an overhead crane to lift the first plenum group onto the switchgear. Install and make snug but do not tighten the 5/16-18 x 7/8 hex bolts, 5/16 lock washer, and 5/16 flat washer onto the flanges on the front and rear of the plenum (see Figures 15 through 17). o not tighten hardware until all of the following plenum parts are attached and connected this will allow parts to shift and eliminate hole-alignment problems. 3. If not able to already have installed duct collar to the plenum before lifting into place attach now by using 1/4-20 hex bolts, 1/4 flat washers, and 1/4-20 KPS nuts. 4. (See Figure 17 If single section skip this step). nsuring that all plenum and duct sections are in place, loosely attach the plenum INT seam cover(s) to the gear with 5/16-18 x 7/8 hex bolts, 5/16 lock washer, and 5/16 flat washer. For ease of assembly, make snug but do not tighten bolts. 5. (See Figure 17 If single section skip this step). nsuring that all plenum INT seam cover(s) are in place, loosely attach the plenum XT seam covers to the gear with 1/4-20 self tapping screws. For ease of assembly, make snug but do not tighten screws. 6. Loosely attach the plenum ends to the gear with 1/4-20 self tapping screws, 5/16-18 x 7/8 hex bolts, 5/16 lock washer, and 5/16 flat washer. For ease of assembly, make snug but do not tighten screws until all plenum groups are attached and connected. 7. Tighten all previously snugged hardware to specified torque values using the values from Table 5 in Section 8. Figure 15. Plenum Parts List. 14 TON

15 Instructions for installation, operation, and Instruction ooklet I022002N ffective pril 2018 Figure 16. Plenum Parts List. TON 15

16 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and ITM QTY SRIPTION OUTOOR ROOF TOP OUTOOR LH WLL OUTOOR RH WLL 4 1 OUTOOR FRONT VRT SM OVR LH 5 1 OUTOOR FRONT VRT SM OVR RH ROOF N P 7 1 OUTOOR FRONT WLL 8 1 OUTOOR RR WLL WITH UT 9 2 OUTOOR ROOF RIP SHIL 10 1 XHUST LL UT OLLR WITH OUTOUT WL 11 1 UT OLLR HW SS OVR /4" - 20 X 3/4" HX OLT /4" HLIL LOK WSHR /4"- 20, 3/4" O, RUR K WSHR /4" WI FLT WSHR /4"- 20 HX NUT /4" - 20 X 3/4" THR ROLLING SRW /4" - 20 RTINR NUT ULK LL (8) ORNRS FTR SSMLY X X X X X X 14 6 X X X X 9 13 X 9 14 X 9 18 X 9 17 X X X 17 8 X X 6 14 X X X 12 5 Figure 17. Plenum Parts List. Section 8: MVS switchgear bolt tightness for bus connections Use the following torque value for tightening bus joints. Table 5. Hardware Tightness Values. olt iameter ecimal Size In. (mm) olt iameter Standard Nominal Torque ft-lb (N m) (6.35) 1/ (6.78) (7.93) 5/ (16.27) (9.53) 3/ (33.90) (12.70) 1/ (67.79) (15.88) 5/ (128.82) 16 TON

17 Instructions for installation, operation, and Section 9: rc resistant type MVS rcgard metal enclose switchgear field taping procedure (5/15 kv) 9.1 usbar taping Materials for taping Reference Figures 18 and 19 for details on proper busbar taping. Filler: putty-like material: Trade name: ScotchfilT or NashauT 102. Pieces of insulating tape may be used. Insulating tape and pad High voltage PR insulating tape: Trade name: ScotchT Using an insulating boot Instruction ooklet I022002N ffective pril 2018 Step 1: lean the area of dirt and foreign matter. Use a clean, dry cloth or, if necessary, dampen slightly with distilled water. o not use any abrasives or solvents. Step 2: Place the boot over the joint so it fits in place. Fasten together with plastic wire ties. ut off excess ends of plastic wire ties. 9.3 able termination taping If cable termination insulation boots are not provided, aton recommends using tape material, Trade name: Scotch 130, for all cable termination insulation. Refer to 3M s taping method instructions, Tape Method for Insulating us-ar onnections 5-35 kv to Meet NSI Requirements, for installation techniques when using this tape. THRU-JOINTS, WITH-HRWR 1. LN R OF IRT N FORIGN MTTR 2. WIP PRINSULTION WITH ISOPROPYL LOHOL IF NSSRY 3. PPLY FILLR OVR R ONUTOR N HRWR TO OVR N SMOOTH OUT SURF. ONTOUR INTO PRINSULTION SURFS. TRY TO PRVNT IR POKTS. OVR ONUTORS N HRWR WITH T LST.12 INH OF FILLR PR FIG PPLY 6.0X.030 THIK P #1 OVR JOINT WITH MINIMUM OF 1.0 INH OVRLP ON FLUIIZ (1 1/4 LPS). PPLY 6.0X.030 THIK P #2 OVR P #1 UT STRTING ON RIGHT SI WITH 1.0 INH OVRLP ON PRINSULTION S FIG PPLY 6.0X.030 THIK P #3 OVR PS #1 & #2 N NTR ON JOINT PR FIG PPLY ON LYR OF 1.00X.030 INSULTING TP USING 2/3 LP N XTNING 0.75 INH MINIMUM YON TH PS ON TH PRINSULTION PR FIG. 8. Figure 18. T-Joint Field Taping Methods. TON 17

18 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and MTRILS FILLR - PUTTY-LIK MTRIL.TR NMS: UTSLR, UT SL, SOTHFIL, TON. NO N 53351WX. TP - HIGH VOLTG PR INSULTING TP. TR NM: SOTH 130 TP, TON S. FINITIONS JOINT - R TO OVR WITH TP. ONSISTS OF R ONUTOR N 1.5 INHS OF NY PR-INSULTION NXT TO TH R ONUTOR. PR-INSULTION - NY INSULTING OVRING OR OTING SUH S POXY OTING OR INSULTING TUING JNT TO N XPOS ONUTOR PRIOR TO TPING. P - NY INSULTING TP WHIH IS WIR THN ON INH ONSISTING OF ON LYR OR MULTIPL LYRS WRPP IRTLY ON TOP OF H OTHR. LYR - INSULTING TP, 1 INH WI, WRPP FROM ON N OF TH JOINT TO TH OTHR, SO H SUING TURN LPS TH PRVIOUS TURN Y TH MOUNT SPIFI IN TH MTHOS PROUR. OVRLP - SPIFI ISTN MSUR LONG TH INSULTION STRTING FROM TH POINT WHR TH INSULTION NS MTHOS GNRL 1. LONGT INSULTING TP 10 TO 25 PRNT URING PPLITION TO INSUR SMOOTH, TIGHT FIT. ON PS LONGT ORNRS ONLY. 2. SHOUL TP ROLL XPIR, STRT TH NW ROLL Y OVRLPPING TH PRVIOUS N Y.5 TURN. "T"-JOINTS, WITH-HRWR 1. LN R OF IRT N FORIGN MTTR 2. WIP PRINSULTION WITH ISOPROPYL LOHOL IF NSSRY 3. PPLY FILLR OVR R ONUTOR N HRWR TO OVR N SMOOTH OUT TH SURF. ONTOUR INTO PR-INSULTION SURFS. TRY TO PRVNT IR POKTS. OVR ONUTORS N HRWR WITH T LST.12 INH OF FILLR PR FIG PPLY 6.00 X.030 THIK P #1 OVR JOINT WITH MINIMUM OF 1.0 INH OVRLP ON PRINSULTION. PPLY 6.00 X.030 THIK P #2 OVR P #1 UT STRTING ON RIGHT SI WITH 1.0 INH OVRLP ON PRINSULTION S FIG PPLY 6.00 X.030 THIK P #3 OVR PS #1 N #2 N NTR ON JOINT PR FIG PPLY ON LYR OF 1.00 X.030 INSULTING TP USING 2/3 LP N XTNING.75 INH MINIMUM YON TH PS ON TH PRINSULTION (FIG. 4). Figure 19. Thru-joint Field Taping Methods. 1 RVISION HISTORY 2 GMV-1733 TYLOR 10/19/07 UPT WG. HNG FLUIZ. NOTS TO PR-INSULTION. 3 O SI 03/22/2016 J. ROINSON 03/22/2016 RRWN TO INVNTOR SHT 2- RMOV JOINTS, WITH L/OOT ONTIONS INFO. Table 6. Taping chart. Switchgear Voltage Pre-insulation or Pad Overlap Minimum Insulating Tape kv In. (mm) Lap of Tape Layers Number of Pads Up to (38.1) and (38.1) Responsibility of installer For incoming or outgoing terminations, these approved materials are not supplied by aton and must be obtained and installed by others as identified above in the definitions. For connections involving shipping splits within an assembly, or connecting to a transformer, or to an MPGR M, or to an MV assembly, insulating materials will be supplied by aton only if necessary. It is the responsibility of the installer to insulate the connections in accordance with these instructions. For an assembly that does not have continuous insulating sleeving on the phase bus conductors, cable connections, or bus connections to other apparatus, insulation of these connections must be made. UTION FILUR TO INSTLL FIL INSULTION WHR NSSRY IN OR- N WITH THS INSTRUTIONS WILL OMPROMIS TH LTRIL RTINGS OF TH SWITHGR SSMLY. INSTLL FIL INSULTION TO MINTIN TH LTRIL RTINGS. 18 TON

19 Instructions for installation, operation, and Instruction ooklet I022002N ffective pril 2018 Switchgear Terminals Power ables ll connections to ground (Such as shielding) must be carried through the current transformer and solidly grounded on the load side of the T as shown. Use #6 wire with 600V insulation. Zero Sequence Transformer Lead, armor, conduit, and so on Lead, armor, conduit, Interstice ground conductors, and so on. Must be terminated and solidly grounded on the load side of the current transformer. To Load able connections to switchgear terminals when used with Zero Sequence Transformers Insulated pothead bushing Insulated pothead mounting Pothead ground lead must be carried through the Zero Sequence current transformer and solidly grounded on the load side of the ct as shown. Use #6 wire with 600V insulation. lectrical joint required between pothead and lead covered or armored power cables. Zero Sequence transformer Power ables onduit, when used onduit must be terminated and solidly grounded on the load side of the current transformer. To Load able connections to switchgear terminals when used with Insulated Pothead. Figure 20. Zero Sequence urrent Transformer onnections. TON 19

20 Instruction ooklet I022002N ffective pril 2018 Instructions for installation, operation, and aton lectrical Sector 1000 aton oulevard leveland, OH United States 877-TN-R ( ) aton.com 2018 aton ll Rights Reserved Printed in US Publication No. I022002N / TG pril 2018 aton is a registered trademark of aton orporation. ll other trademarks are property of their respective owners.

Instruction Booklet IB E. Contents

Instruction Booklet IB E. Contents Instruction Booklet IB02102001 Instructions for installation, operation, and maintenance of type MVS/MVS2, MB, and MSB metal-enclosed switchgear assemblies: 4.76 kv or 15.0 kv class ontents escription

More information

Indoor MVS Switchgear Assembly. Outdoor MVS Switchgear Assembly. New Information. For more information visit:

Indoor MVS Switchgear Assembly. Outdoor MVS Switchgear Assembly. New Information. For more information visit: Instructions for Installation, Operation, and Maintenance of Type MVS, MEB, and MSB Metal Enclosed Switchgear Assemblies: 4.76 kv or 15.0 kv Class Instructional Booklet New Information Description Page

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

Tractor - Setup Instructions

Tractor - Setup Instructions Trtor - Stup Instrutions WARNING AVOID SERIOUS INJURY OR DEATH: R n follow th trtor oprtor mnul for running ngin. Not: Follow th prours tht pply to your mol. Trtor Mols Mowr Mols 69595 4 69098 69596 69099

More information

O & M Manual for the EATON Generator Ready Loadcenter

O & M Manual for the EATON Generator Ready Loadcenter O & M Manual for the EATON Instructional Booklet New Information Description Page 1. Introduction............................... 2 2. Receiving, Handling, and Storage................ 4 3. Equipment Description........................

More information

with Electronic Trip Units

with Electronic Trip Units Instruction Leaflet IL0001 ffective ugust 011 Supersedes February 011 Instruction Leaflet for LG-Frame Circuit Breakers with lectronic Trip Units Warning 1 O NOT TTMPT TO LL OR PRFORM MINTNNC ON QUIPMNT

More information

Instruction Booklet IB E. Contents

Instruction Booklet IB E. Contents Instructions for operation and maintenance of breaker lifting device and breaker lift pan accessory for 5-27 kv type VCP-W circuit breakers and medium voltage switchgear Contents Description Page IIntroduction...

More information

GE Industrial Solutions. Limitamp * AR. Arc Resistant Medium Voltage Motor Control. Installation Guide

GE Industrial Solutions. Limitamp * AR. Arc Resistant Medium Voltage Motor Control. Installation Guide GE Industrial Solutions Limitamp AR Arc Resistant Medium Voltage Motor ontrol Installation Guide Table of ontents Introduction...3 Opening Medium Voltage oor...3 Medium Voltage oor Latches... Isolation

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches Instruction Leaflet IL 0106001E Contents Description Page Introduction.......................... Installation............................ Manual Operation and Thermal Magnetic Trip Unit Adjustment.......................

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Instructions for installation, operation, and maintenance of type MVS/MVS-c load interrupter switches 4.76 kv, 15 kv, 27 kv, and 38 kv

Instructions for installation, operation, and maintenance of type MVS/MVS-c load interrupter switches 4.76 kv, 15 kv, 27 kv, and 38 kv Contents Description Page Introduction.... 4 Receiving, handling, and storage... 6 Installation.... 7 Inspection before initial energizing of an MVS/ MVS-c switch... 7 Operation.... 9 Maintenance.... 10

More information

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers Instruction Leaflet IL2A12995H02 effective March 2012 Trip Indicator with Remote Reset for Magnum WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS

More information

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit Instruction Leaflet IL01210020E Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit Contents Description Page 1. Removal of R-Frame Electronic Seltronic (RES) Trip Unit and Obsolete Components...

More information

CCP2-FLR1-21_ flange-rod operating mechanism

CCP2-FLR1-21_ flange-rod operating mechanism Installation manual 3A3747 Rev A Contents Description Page General information 1 Required tools 2 Hardware contents 2 Installation and adjustment 2-6 Flange drilling pattern 7 HAZARD OF ELECTRIC SHOCK,

More information

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers Supersedes IL 33-GS8-2 Dated 10/00 (Manually Operated Only) Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:...............................

More information

DRAWING APPROVAL SHEET

DRAWING APPROVAL SHEET O S.J. RWING PPROVL SHT RWING NUMR: MMRO--0-M-0 RWING TITL:Passenger Seats Layout ISSU T OMPIL Y HK Y STRSS Y V/PPROV 0/0/0 Gytis Leonavicius rawford Murray rawford Murray rawford Murray The drawing referenced

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear Contents Description Page Introduction.... 4 Installing indoor switchgear.... 6 A further description of arc-resistant VacClad-W switchgear.... 13 Adjusting and testing.... 20 Operation of the system....

More information

CUSTOMER COPY PCB LAYOUT RECOMMENDED E D B .075[1.90] SEE NOTE 13 2X THRU C INSERTION DEPTH

CUSTOMER COPY PCB LAYOUT RECOMMENDED E D B .075[1.90] SEE NOTE 13 2X THRU C INSERTION DEPTH RVISIONS RV. O. NO SRIPTION T Y ST KY IN POSITION & KY TWN POSITION OPTION, OSOLT WG 0(S99), (S), 0(S), (S00), 09(S, UPLIT WITH S99), 0(S00), 9(S), 9(S), 00(S), (S0), RPL WITH WG 0, POSITION OR MTG & POSI

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Factory Authorized Mechanism Enhancement (FAME)

Factory Authorized Mechanism Enhancement (FAME) Instruction Leaflet IL182403EN Supersedes April 2017 Effective July 2018 Factory Authorized Mechanism Enhancement (FAME) FAME Upgrade Shown Factory Authorized Mechanism Enhancement (FAME) DISCLAIMER OF

More information

Ni - Cd THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

Ni - Cd THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. LP600U Installation Instructions UNIVRSL INPUT, SLF-TIN MRN LIHTIN QUIPMNT! IMPORTNT SFURDS! WHN USIN LTRIL QUIPMNT, BSI SFT PRUTIONS SHOULD LWS B FOOWD, INLUDIN TH FOOWIN: RD ND FOOW SFT INRUTIONS 1.

More information

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

OPERATOR S MANUAL. Double & Triple Bag Grass Collection Systems. with Blower Setup Instructions FERRIS

OPERATOR S MANUAL. Double & Triple Bag Grass Collection Systems. with Blower Setup Instructions FERRIS FRRIS OPRTOR S MNUL with lower Setup Instructions ouble & Triple ag Grass ollection Systems ouble ag ollection System for: Ferris 1000Z Series - 48 & 52 Mowers erby olt ZT2148 & ZT2352-48 & 52 Mowers Triple

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Instructions for installation, operation, and maintenance of 5/15 kv type VacClad-W arc resistant metal-clad switchgear Contents

Instructions for installation, operation, and maintenance of 5/15 kv type VacClad-W arc resistant metal-clad switchgear Contents arc resistant metal-clad switchgear Contents Description Page Introduction.... 4 Installing indoor switchgear.... 6 Description of arc resistant VacClad-W switchgear.... 13 Adjusting and testing.... 21

More information

Current-limiting fuse mounts

Current-limiting fuse mounts Fusing quipment atalog ata 132046N Supersedes November 2015 urrent-limiting fuse mounts OOPR POWR SRIS eneral aton provides overload protection for all indoor and underground cable distribution systems

More information

CM52 Network Protector with Arc Flash Reduction Module

CM52 Network Protector with Arc Flash Reduction Module Contents Description Page 1: General.............................. 2 2: Maintenance Mode Settings.............. 2 3: Arming Maintenance Mode.............. 2 4: Remote Indicator....................... 2

More information

Manual Transfer Switch

Manual Transfer Switch Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal

More information

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters

More information

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003 Type DTU De-energized Tap Changer Application, Installation & Selection Guide IL 44-750-1A Page 1 September, 2003 Page 2 September, 2003 Scope This leaflet contains general information about ordering and

More information

F6125HD, 5, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6125HD, 5, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 6125H, 5, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc pplication Valve is designed for use in NSI flanged piping systems to meet the needs of bi-directional high flow HV hydronic applications

More information

H81xx. H81xx Energy Meter. quick install POWER MONITORING INSTALLATION GUIDE. Installer s Specifications

H81xx. H81xx Energy Meter. quick install POWER MONITORING INSTALLATION GUIDE. Installer s Specifications POWR MOITORIG ISTLLTIO GUI H81xx H81xx nergy Meter H06 (optional mounting bracket) Installer s Specifications Insulation lass 600V Sample Rate 1280 Hz Internal Isolation 2500V Operating Temp. Range 0 to

More information

A FORMAT: Met-lega-master-tb-prod-A3 REVISION: C DATE: 2017/02/06

A FORMAT: Met-lega-master-tb-prod-A3 REVISION: C DATE: 2017/02/06 RL WITH OMPON UL SHT(S) (QTY. VRIL) LL PRT NO. QTY. O TP PRTS ORINTTION RFR TO SHT RO LL NO. OF RLS WITH M G (QTY. VRIL) RL WITH OMPON NTR UL SHT(S) (QTY. VRIL) 0.0 MOSS TP RO LL NO. OF RLS WITH M G (QTY.

More information

Two-way cable interlock kit for Magnum fixed circuit breakers

Two-way cable interlock kit for Magnum fixed circuit breakers warning (1) Only qualified electrical personnel should be permitted to work on the equipment. (2) Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

GE 8000-Line Motor Control Centers

GE 8000-Line Motor Control Centers GE 8000-Line -1 ENCLOSURE TYPES TYPE 1 General Purpose, Indoor Intended for use indoors, primarily to prevent accidental contact of personnel with the enclosed equipment, in areas where unusual service

More information

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide Table of contents 1 Introduction... 3 1.1 Style Number... 3 1.1.1 Style Number Examples... 3 2 Basic Characteristics... 4 2.1

More information

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc 6100H, 4, 2-Way utterfly Valve Resilient Seat, 304 Stainless Steel isc pplication Valve is designed for use in NSI flanged piping systems to meet the needs of bi-directional high flow HV hydronic applications

More information

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2

More information

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER

OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER DESCRIPTION OHIO MODEL RD-1W AUTO / MANUAL DROP MAGNET CONTROLLER Th RD-1W Automti Controllr is hvy uty mgnt ontrollr us or mgnts whos ol urrnt rngs rom 0 A to 100 A. Col urrnt rrns th urrnt lowing through

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

SECTION C-C SCALE 1 / 2 SECTION E-E SECTION AT-AT SCALE 1 / 2 SCALE 1 / 2 SECTION F-F SCALE 1 / 2 SECTION M-M SCALE 1 / 2 DETAIL D SCALE 2 : 1

SECTION C-C SCALE 1 / 2 SECTION E-E SECTION AT-AT SCALE 1 / 2 SCALE 1 / 2 SECTION F-F SCALE 1 / 2 SECTION M-M SCALE 1 / 2 DETAIL D SCALE 2 : 1 RVIS PRT SRIPTION IN OM, TO MK - //0 Y.LI IT LRR 6 dded fillet at bottom of PM pocket in item. //0 TIO 4. R. dded a new part # //0 Y.LI T 4 (.7) Revised welding note at etail View /6/0 Y.LI WTR TIGHT Ø6.7

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

EXHAUST SYSTEM MANIFOLD AND ELBOWS 7 B

EXHAUST SYSTEM MANIFOLD AND ELBOWS 7 B EXHAUST SYSTEM 72990 MANIFOLD AND ELBOWS 72991 7 B Tl o Contnts P Torqu Spiitions..................... 7B-1 Slnts................................ 7B-1 Rmovl................................ 7B-1 Clnin n

More information

Ni - Cd THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

Ni - Cd THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 50 Installation Instructions mergency Lighting quipment! IPORTNT SFURDS! WHN USIN LTRIL QUIPNT, SI SFT PRUTIONS SHOULD LWS FOOWD, INLUDIN TH FOOWIN: RD ND FOOW SFT INRUTIONS 1. To prevent high voltage

More information

hat channel purlins B SCREW PATTERNS: DOUBLE SCREW PATTERN ON UPPER AND LOWER ROOF PURLINS (FOR ROOF PANELS).

hat channel purlins B SCREW PATTERNS: DOUBLE SCREW PATTERN ON UPPER AND LOWER ROOF PURLINS (FOR ROOF PANELS). 6.2.524.524.524.524.524.524.524.524.524.524.524.524.524.524.524 3.2 +3.920 +3.094 note: dimensions including sheet metal transparent polymer panels, glass fiber enforced roof metal panel +3.920 +3.094

More information

R-Rated medium voltage fuses for motor circuit protection

R-Rated medium voltage fuses for motor circuit protection Technical ata 6001 Supersedes ecember 2015 Features and benefits escription: Indoor/enclosure, R-Rated medium voltage, current-limiting fuses for motor circuit protection. urrent-limiting R-Rated fuses

More information

6.5 FT PRE-LIT WALDEN PINE TREE MODEL #LWCP112003

6.5 FT PRE-LIT WALDEN PINE TREE MODEL #LWCP112003 Holiday Living & esign is a registered trademark of L, LL. ll rights reserved. R ITM #0349488 6.5 T PR-LIT WLN PIN TR MOL #LWP2003 rançais p. 6 TTH YOUR RIPT HR Serial Number Purchase ate Questions, problems,

More information

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

Direct-Fired Heating, Ventilation and Pressurization Systems

Direct-Fired Heating, Ventilation and Pressurization Systems 2000-Series irect-ired Heating, Ventilation and Pressurization Systems imension and Selection uide 1.800.536.3461 www.rapidengineering.com N: 100% OUTSI IR ONLY 2000-Series Selection uide NOT: ll information

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

3-way multi-family drawout cable interlock kit - type 32 - RF

3-way multi-family drawout cable interlock kit - type 32 - RF Supersedes August 2015 Power Defense ICCB 3-way multi-family drawout cable interlock kit - type 32 - RF Instructions apply to: Contents Description Page UL489 IEC : PD-RF : PD-RF, IZMX40 General information....

More information

QO and QOU Miniature Circuit Breakers QO Circuit Breaker Accessories

QO and QOU Miniature Circuit Breakers QO Circuit Breaker Accessories QO and Miniature ircuit reakers QO ircuit reaker ccessories lass 1130 / Refer to atalog 0730T9801 IRUIT RKRS ccessories for Use with QO and QO Miniature ircuit reakers Handle ttachments escription at.

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Instruction and Installation Guide

Instruction and Installation Guide Instruction and Installation Guide Type 2A Arc Resistant tiastar Motor Control Center www.usa.siemens.com/mcc DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualified personnel

More information

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S ) Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The

More information

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit Instruction Leaflet IL0131075EN Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit Contents Description Page General information.... 2 Installation

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Air Handlers Series. Direct-Fired Heating Pressurization. Dimension and Selection Guide

Air Handlers Series. Direct-Fired Heating Pressurization. Dimension and Selection Guide 2000-Series ir andlers irect-ired eating Pressurization imension and Selection uide 1.800.536.3461 www.rapidengineering.com N: 100% OUTSI IR ONLY 2000-Series Selection uide IMPORTNT NOTS: ll information

More information

36" Galvanized Direct Drive Hyflo Fan Installation and Operators Instruction Manual. Fan and Framing Dimensions

36 Galvanized Direct Drive Hyflo Fan Installation and Operators Instruction Manual. Fan and Framing Dimensions 6" Galvanized Direct Drive Hyflo Fan Installation and Operators Instruction Manual Fan and Framing Dimensions Planning the layout of the spacing between Fans is very important. Spacing too close together

More information

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Powergrid Solution s Metal Enclosed Switchgear has many different customizable options and configurations. Customers

More information

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the

More information

R-Rated medium voltage fuses for motor circuit protection

R-Rated medium voltage fuses for motor circuit protection Technical ata 6001 Supersedes September 2017 Features and benefits escription: Indoor/enclosure, R-Rated medium voltage, current-limiting fuses for motor circuit protection. urrent-limiting R-Rated fuses

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers Supersedes IL 33-A46-2 Dated 01/04 Contents Description Page Introduction.............................. 3 Step 1: General Breaker Preparation......... 4 Step 2: Removing the Original Components.. 5 Step

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION Page: 1 Instructions for the Type VCP-W Ground & Test Device (Simple) Upper Terminal Set Version IB131007EN Effective May 2015 Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear

More information

READ THIS BEFORE INSTALLING SWITCHGEAR

READ THIS BEFORE INSTALLING SWITCHGEAR READ THIS BEFORE INSTALLING SWITCHGEAR SYSTEM 2000 SWITCHGEAR INSTALLATION GUIDE PM073 Rev 1 14/02/17 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604) 888-3381 E-Mail:

More information

TIG Welding (Outside) Cooldown LN2 Input Bayonet DIA. CYLINDER O.D. SECTION A-A SECTION B-B

TIG Welding (Outside) Cooldown LN2 Input Bayonet DIA. CYLINDER O.D. SECTION A-A SECTION B-B ryogenic Triple Feedthru NOT: FLNGS (PRTS 5 N 5) MUST LIGN S SHOWN WITH.250 I. OWL HOLS N LIFT HOLS T TH TOP. TIG Welding (Outside) TIG Welding (Inside) Stack Port TIG Welding (Outside) TIG Welding (Outside)

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

More information

Sequence of Operation. Installation. Commissioning. Testing and replacement of dampers and actuators. Troubleshooting. Maintenance

Sequence of Operation. Installation. Commissioning. Testing and replacement of dampers and actuators. Troubleshooting. Maintenance 0 Helgesen Drive, Madison, WI (0) -, (00) -, Fax: (0) - support@renewaire.com www.renewaire.com Supplemental Instructions for Optional Isolation Dampers for HEX Indoor Models Purpose of this Manual: To

More information

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2 SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism Effective October 2010 Supersedes June 2010 IL01301018EH03 Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers Supersedes IL 33-AG6-2 Dated 02/08 Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:............................... 4 Step 3:...............................

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information