1 Practical Demonstration of FLOW INSTRUMENTS MODULE NO. : I-4 MODULE SUBJ.: Flow Instruments Module I-4 Page 1

2 Tasks: I-4.1 I-4.2 I-4.3 I-4.4 I-4.5 Describe the procedures used to remove an orifice plate from a Daniel s senior orifice fitting. Demonstrate servicing and calibration of a pneumatic differential pressure flow transmitter. Demonstrate servicing and calibration of an electronic differential pressure flow transmitter. Demonstrate ability to isolate the transmitter from process without damage to equipment. Perform zero check procedure (static zero adjustment). I-4.6 I-4.7 Perform servicing of a turbine meter. Check magnetic pickup for damage. Calibrate pulse to ma converter. Perform service and check of a Rotameter. I-4.8 Service and calibrate a Foxboro 43AP controller. I-4.9 Calibrate square root extractor. I-4.10 Troubleshooting 3 way / 5 way valve manifold. MODULE No.: TASK No.: I-4 Flow Instruments I-4.1 Describe the procedures used to remove an orifice plate from a Daniel s senior orifice fitting. Module I-4 Page 2

3 Reference: TASK DETAILING MANUAL Materials: None. Equipment & Tools: None. Conditions: None. Requirements By Trainee: To study the task and familiarise himself, Be able to identify parts of Daniel s senior orifice, Be able to state the differences between Senior / Junior and flange orifices, Be able to remove and reinstall an orifice plate from senior orifice fitting, Draw / Sketch types of orifice fittings used in his working area, Describe an understanding to his trainer, and Write observations and procedures in his workbook. TASK No.: I-4.1 Details: Orifice Plates Orifices are the most common form of custody transfer meter for Oil and Gas production facilities. Numerous types of devices are available for transmission, recording, and accumulation of data from orifice meters. Module I-4 Page 3

4 An Orifice plate is a thin metal plate with a precisely machined circular opening be inserted in the flow stream. As flow passes through the opening (orifice) some of the upstream pressure head is converted into velocity head. The velocity head is greatest and pressure head smallest at the "vena contracta" located slightly downstream of the orifice. The differential pressure across the orifice is related to velocity by Bernoulli's equation. When the differential pressure and static pressure are measured, and the orifice size, pipe size, and the gas properties are known, the flow rate can be calculated. TASK No.: I-4.1 Figure I-4.1A, Senior Orifice Fitting Module I-4 Page 4

5 Figure I-4.1B To Remove Orifice Plate (a) Open No. 1 (Max. two turns only). (b) Open No. 5. (c) Rotate No. 6. (d) Rotate No. 7. TASK No.: I-4.1 (e) Close No. 5. (f) Close No. 1. (g) Open No. 10 B. Module I-4 Page 5

6 (h) Lubricate through No. 23. TASK DETAILING MANUAL (i) Loosen No. 11 (Do not remove No. 12). (j) Rotate No. 7 to free Nos. 9 and 9A. (k) Remove Nos. 12,9 and 9A. To Replace Orifice Plate (a) Close 10B. (b) Rotate No. 7 slowly until plate carrier is clear of sealing bar and gasket level. Do not lower plate carrier onto slide valve. (c) Replace Nos. 9 A, 9 and 12. (d) Tighten No. 11 (e) Open No. 1. (f) Open No. 5. (g) Rotate No. 7. (h) Rotate No. 6. (i) Close No. 5. (j) Close No. 1. (k) Open 10 B. (l) Lubricate through No. 23. (m) Close No. 10 B. MODULE No.: TASK No.: I-4 Flow Instruments I-4.2 Demonstrate servicing and calibration of a pneumatic differential pressure flow transmitter. Reference: OJT Instructor to arrange reference catalogue / service manual for pneumatic DP flow transmitter relevant to each working area. Module I-4 Page 6

7 Materials: Cleaning rags. Equipment & Tools: 1. Tool Box, 2. Standard Output gauge, and 3. Pneumatic / Hydraulic pressure calibrator. Conditions: Work permit Requirements By Trainee: To study the task and familiarise himself, To select the proper tools / equipment to perform this task, Understand the principle of operation of pneumatic DP flow transmitter, Be able to perform calibration adjustments of the pneumatic flow transmitter, Draw / Sketch the calibration set-up in his workbook, Be able to perform routine service of a pneumatic flow transmitter, Discuss an understanding to his trainer, and Write observations and procedures in his workbook. TASK No.: I-4.2 Details: Differential Pressure Transmitters (DPT.) These transmitters are used when the controller, recorder, or indicator needs to be located in a control room or panel where it is undesirable to pipe the process fluid. They are also used when several devices are to be operated from a single measurement or when elevated zero is required. The output is usually 4-20, milliamps for electronic transmitters or 3-15 psig ( kpa) for pneumatic transmitters. Other signals can be used if required by the receiver, but these are the most common and should be used if possible. Elevated zero occurs when the base value of the measured variable is not at atmospheric pressure. Most transmitters have this as an option, while most Module I-4 Page 7

8 controllers do not. Elevated zero is used when the pressure range of interest is narrow and at a fairly high level. Suppressed zero, where the base value of the measured variable is below atmospheric pressure, is sometimes available. Usually, the zero is as near to perfect vacuum as possible and the unit is called a absolute pressure transmitter. The use of pneumatic transmitters is decreasing; however, a number of manufacturers still make them for the replacement market and some new installations are still being made. Pneumatic transmission may be advantageous when existing equipment is pneumatic with which operating personnel are already familiar. The next figure shows the main parts of a pneumatic differential pressure transmitter, these are: 1. Twin diaphragm Capsule as a sensing element, 2. Force Bar, 3. Leaf Spring, 4. Range Adjusting Bar, 5. Booster Relay, and 6. Feedback Bellows. Module I-4 Page 8

9 TASK No.: I-4.2 Figure I-4.2A, Pneumatic Differential Pressure Transmitter. TASK No.: I-4.2 Calibration Module I-4 Page 9

10 Calibration is required if the transmitter has been taken apart for cleaning or for parts replacement, if a change of range is desired, or if the amount of zero elevation or suppression is changed substantially. If the capsule was removed or the flexure cap screw loosened, before calibrating, make the flexure cap screw adjustment above. The transmitter to be calibrated to 3 to 15 psi signal pressure range, at which the receiver signal is used. Calibration procedures; detailed bench calibration and in-line calibration procedures of the pneumatic differential pressure transmitter are listed in the reference catalogue or service manual of the applied model. Consult your trainer. Regulate air supply to pressure at which transmitter will be operating Calibrating Air Supply Vent low-pressure side of transmitter. Bleeder Valve Test gauge or reading input signal pressure. manometer for 0 to 20 psi Output test gauge TASK No.: I-4.2 Figure I-4.2B, DP flow transmitter calibration setup Maintenance and Servicing Maintenance and servicing of pneumatic differential pressure transmitter are limited to clean or replace its parts, such as: 1. Supply Air Filter blow out at least once a day, 2. Replace Screen Filter of the process inlet, 3. Clean Nozzle Assembly, Module I-4 Page 10

11 4. Clean booster relay Restrictor, 5. Replace Booster Relay, 6. Change Range Bar, 7. Remove / Replace Diaphragm Capsule, and 8. Adjusting Flexure Cap Screw. Disassembly; Normal servicing of the transmitter does not require the removal of any parts other than those already mentioned. Further disassembly is not recommended because of possible loss of accuracy or damage to the transmitter, detailed servicing procedures are mentioned in maintenance section of the selected transmitter model. Consult your trainer. MODULE No.: TASK No.: Reference: Materials: I-4 Flow Instruments I-4.3 Demonstrate servicing and calibration of an electronic differential pressure flow transmitter. OJT Instructor to arrange reference catalogue / Service manual for an electronic differential pressure flow transmitter model relevant to each working area. 1. Cleaning rags, and 2. Solvent. Module I-4 Page 11

12 Equipment & Tools: 1. Tool Box, 2. Hydraulic or Pneumatic pressure calibrator, and 3. Function Generator and digital Multimeter. Conditions: Work permit. Requirements By Trainee: To study the task and familiarise himself, Be able to describe the operation principle of the electronic DP transmitter, Be able to identify the main parts of an electronic DP transmitter, Perform periodic adjustments / calibration of an electronic transmitter, Perform periodic and corrective maintenance or replace parts of an electronic DP transmitter, Draw / Sketch calibration set-up of the electronic DP transmitter, Discuss an understanding with his trainer, and Write observation and procedures in his work book. TASK No.: I-4.3 Details: Electronic Differential Pressure Flow Transmitters Electronic transmitters with 4-20 milliamp outputs are the most common. Differential pressure flow transmitters are available in a variety of ranges. The ranges available vary from one manufacturer to another. The range and the span are two different parameters: The span; is the actual differential pressure range to be measured after the transmitter has been adjusted. The range; is the differential pressure range within which the span can be adjusted. Most transmitters have two adjustments, zero and span: Module I-4 Page 12

13 The zero; is adjusted so that the output is minimum (4 ma) at zero differential pressure, or the bottom of the span if elevated zero is used. The span; is adjusted so that the output is maximum (20 ma) when the pressure is at the top of the span. But the zero must always be rechecked after the span has been adjusted and the span checked after the zero adjustment. Next figure shows the main parts of an electronic differential pressure transmitter; Sensing module, and Electronic housing contains; header assembly board, DC amplifier board, and calibration board TASK No.: I-4.3 Module I-4 Page 13

14 Figure I-4.3A, Electronic Differential Press. Transmitter, Main Parts. Module I-4 Page 14

15 TASK No.: I-4.3 Principle of operation Figure I-4.3B This electrical block diagram illustrates the operation of the electronic differential pressure transmitter. The process pressure is transmitted through an isolating diaphragm and oil fill fluid to a sensing diaphragm located in the centre of the cell. The position of the sensing diaphragm is detected by the capacitance plates, the sensor is التذبذب. oscillator driven by an Demodulator consists of a diode bridge, which rectifies the ac signal to dc to drive the oscillator. Voltage regulator provide a constant voltage of 6.4 V dc for the reference and 7 V dc to supply the oscillator. Current control amplifier drives the current control circuitry to a level that causes the current detector to feedback a signal. The current limit prevent output current from exceeding 30 ma in case of overpressure. Module I-4 Page 15

16 TASK No.: I-4.3 This figure shows the signal terminals, which are located in the electrical housing in a separate compartment. All power to the transmitter is supplied over the signal wiring and there is no additional wiring required. Signal wiring needs to be shielded, but twisted pair should be used for best result. Output current is limited to 30 ma dc on the 4-20 ma dc unit. Calibration Figure I-4.3C Span Adjustment Range; is continuously adjustable to allow calibration anywhere between maximum span and 1/6 of maximum span. Zero Adjustment Range; Transmitter s zero is the lowest value of the transmitter range, at which the output of the electronic DP transmitter is 4 ma. The zero and span adjustment potentiometers are accessible externally and are located behind the nameplate of the transmitter. TASK No.: I-4.3 Module I-4 Page 16

17 The recommended procedure for zero and span adjustment detailed in the reference catalogue / service manual of the electronic differential pressure transmitter model, consult your trainer. Linearity Adjustment; this is a factory calibration adjusted for optimum performance over the calibrated range of the instrument and is not normally adjusted in the field, however only maximise linearity over particular range be applicable. Damping Adjustment; the output amplifier boards are designed to permit damping of rapid pulsations in the pressure source by adjusting the control marked Damping located on the solder side of the amplifier board. Calibration procedures for adjusting or changing ranges are outlined in the calibration section of the transmitter catalogue, consult your trainer to proceed. Maintenance Maintenance is a technique for checking out the transmitter components, the method for disassembly and reassembly, and a troubleshooting guide. Test Terminal; to assure that there is no leakage current through the diode when a test reading is resistance of the test connection or meter should not exceed 10 ohms. Sensing Module Checkout; the sensing module is not a field repairable and must be replaced if found to be defective. If no obvious defect, such as a punctured isolating diaphragm or loss of fill fluid is observed, the sensing module may be checked. The detail procedure to checkout the sensing module is listed in the maintenance section of the transmitter s catalogue. Consult your trainer. Circuit Boards Checkout; the printed circuit boards Amplifier board and Calibration board can most easily be checked for a malfunction by substituting into the circuit TASK No.: I-4.3 Troubleshooting 1) SYMPTOM: HIGH OUTPUT Module I-4 Page 17

18 Potential source and Corrective action. Impulse Piping Check for leaks or blockage. Check for liquid in dry lines. Check for sediment in transmitter process flanges. Transmitter Electronics Connections Make sure bayonet connectors are clean and check out the sensor connections. Check that bayonet pin #8 is properly grounded to the case. Transmitter Electronics Failure Determine faulty circuit board by trying spare boards. Replace faulty circuit board. Power Supply Check output of power supply. 2) SYMPTOM: LOW OUTPUT OR NO OUTPUT Potential source and Corrective action Loop Wiring Check for shorts and multiple grounds. Check polarity of connections. Check loop impedance. Impulse Piping Check that pressure connection is correct. Check for leaks or blockage. Check for entrapped gas in liquid lines. Check for sediment in transmitter process flanges. TASK No.: I-4.3 Transmitter Electronics Connections Check for shorts in sensor lead. Make sure bayonet connectors are clean and check the sensor connections. Check that bayonet pin #8 is properly grounded to the case. Test Diode Failure Replace test diode or jumper test terminals. Module I-4 Page 18

19 Transmitter Electronics Failure Determine faulty circuit board by trying spare boards. Replace faulty circuit board. 3) SYMPTOM: ERRATIC OUTPUT Potential source and Corrective action Loop Wiring Check for intermittent shorts, open circuits and multiple grounds. Process Fluid Pulsation Adjust electronic damping pot (4-20 ma dc only). Impulse Piping Check for entrapped gas in liquid lines and for liquid in dry lines. Transmitter Electronics Connections Check for intermittent shorts or open circuits. Make sure that bayonet connectors are clean and check the sensor connections. Check that bayonet pin#8 is properly grounded to the case. Transmitter Electronics Failure Determine faulty circuit board by trying spare boards. Replace faulty circuit board. MODULE No.: TASK No.: I-4 Flow Instruments I-4.4 Demonstrate ability to isolate the transmitter from process without damage to equipment. Reference: None Materials: Cleaning Rags. Module I-4 Page 19

20 Equipment & Tools: Tool Box. Conditions: None. Requirements By Trainee: To study the task and familiarise himself, Be able to select proper tools to perform this task, Be able to demonstrate safe isolation procedure of a flow transmitter in service, Discuss an understanding with his trainer, and Write observations and procedure in his workbook. TASK No.: I-4.4 Details: Module I-4 Page 20

21 Figure I-4.4A, Piping and Tubing arrangement of a DP transmitter TASK No.: I-4.4 To perform safe isolation of a DP transmitter in service, follow the next: 1. Fill in your work permit. Module I-4 Page 21

22 2. Using Soap solution and brush, check for any process leakage. 3. In case of crude oil (only visual inspection). If there is any leakage from fitting, tighten it. 4. Close the high and low blocking valves. 5. Open the by pass valve. 6. Slowly open high and low drain plugs. 7. Slowly start to open high pressure blocking valve to flush the high pressure impulse line, then close it. 8. Slowly open low pressure blocking valve to FLUSH THE LINE, then close it. 9. Fix high and low drain plugs, and tighten them. 10. Open high and low blocking valves. 11. Close the By-pass valve so that the transmitter in service. MODULE No.: TASK No.: I-4 Flow Instruments I-4.5 Perform zero check procedure (static zero adjustment). Reference: Materials: 1. Cleaning rags, and 2. Solvent. Module I-4 Page 22

23 Equipment & Tools: 1. Tool Box, and 2. Standard output gauge. Conditions: Work permit. Requirements By Trainee: To study the task and familiarise himself, Be able to select proper tools to perform this task, Be able to perform static zero adjustment of a DP flow transmitter, Discuss an understanding with his trainer, and Write observation and procedures in his workbook. TASK No.: I-4.5 Module I-4 Page 23

24 Details: TASK DETAILING MANUAL Figure I-4.5A, Field Mounted Recorder Piping Arrangement Figure I-4.5A, illustrates piping and tubing arrangement of a field mounted flow recorder as an example to proceed static zero adjustment. TASK No.: I-4.5 Static Zero Check; If the instrument has a static pressure element, perform the following check: Module I-4 Page 24

25 With no pressure applied, check static pressure zero. If minor adjustments are required, make adjustments using the zero adjust screw. Leak Checking and Zero Adjustment: 1. OPEN block and shut-off valves, 2. CLOSE block valves, 3. OPEN equaliser valve(s), 4. OBSERVE DP pen position, with calibration chart installed: If pen position is slightly off of zero, make fine adjustment using pen zero adjust screw. 5. CLOSE equaliser valve(s), 6. OBSERVE DP pen position: a) If pen position at ZERO, no further check required, b) If pen position UPSCALE, possible leak on low-pressure side (Check / tighten connections), and c) If pen position DOWNSCALE, possible leak on high-pressure side (Check / tighten connections). MODULE No.: TASK No.: Reference: I-4 Flow Instruments I-4.6 Perform servicing of a turbine meter. Check magnetic pickup for damage. Calibrate pulse to ma converter. OJT Instructor to arrange reference catalogue / service manual for turbine meter model relevant to each working area. Module I-4 Page 25

26 Materials: TASK DETAILING MANUAL 1. Cleaning Rags, and 2. Solvent. Equipment & Tools: 1. Frequency generator / counter, 2. Digital Multimeter, and 3. Function generator. Conditions: Work permit. Requirements By Trainee: To study the task and familiarise himself, Be able to describe the main parts of a turbine flow meter and its principle of operation, Be able to define the meter factor of a turbine flow meter, Understand flow calculation of using turbine flow meter, Perform periodic maintenance and troubleshooting of turbine flow meter, Be able to calibrate turbine flow analyser, Draw / Sketch calibration set-up, Discuss an understanding to his trainer, and Write observations and procedures in his workbook. TASK No.: I-4.6 Details: Turbine Meters Turbine meters consist of: 1. A propeller mounted in a precisely machined housing, and 2. One or two pickup devices are mounted externally in the body in the same plane as the rotor blades. Principle of Operation; Module I-4 Page 26

27 Fluid flowing through the meter causes the rotor to rotate at a speed proportional to the flow velocity and viscosity. As each blade tip passes the pickup a signal pulse is generated. The number of pulses per unit time allows calculation of the flow velocity, which can be used to determine flow rate. Q = T f / K Where Q is the volumetric flow rate (gallon/min.), K is turbine meter factor, pulses per volume unit ( pulses/gal ). f is number of frequency (Hz). T is a time constant ( such as 60 for gpm ). Most turbine meters are threaded or mounted between flanges. Some turbine meters are available which insert into user supplied piping. Flow Analyser; receives an electronic pulse train from a flow meter and provides a registration of totalised flow and an indication of flow rate by utilisation of its microprocessor-based circuitry. The totalised flow and flow rate are displayed on two six digit liquid crystal displays (LCD s). Both displays are properly labelled with respective units of measurement. TASK No.: I-4.6 Module I-4 Page 27

28 Figure I-4.6A, Turbine Flow Meter, Main Parts. 0 Maintenance and Repairs; 1) Turbine flow meter is virtually maintenance-free. The frequency of periodic checks depends on the service to which the meter is applied. TASK No.: I-4.6 The following suggestions may prove helpful toward determining when to inspect the meter for possible wear or damage: a) Significant variations from normal flow rates should be sufficient notice to remove the meter from the line and examine its internal parts for damage or wear. b) Other operators may prefer to make periodic inspections even though marked variations from normal flow rates have not been observed. Module I-4 Page 28

29 Figure I-4.6B, Turbine Flow Meter Principle of Operation. TASK No.: I-4.6 2) A specific sequence of steps and certain precautions should be observed in removing the meter from the line, disassembling and reassembling it. Particular care should be given to note the direction-of-flow arrows on the various parts of the meter. Preparing for Installation: 1. Remove magnetic pickup or protect it to prevent damage. 2. Remove the three socket head capscrews from each end of the housing. 3. Remove upstream and downstream bearing supports and rotor. Module I-4 Page 29

30 If bearing supports are stuck, drive them out with a small wooden or plastic rod and hammer. Use extreme caution in prying on the beam supports since the internal parts may break or shatter. Tap alternately on blades of supports to prevent damaging housing. 4. Clean bore of housing with a swab and remove any burrs or rough spots. 5. Clean screw hole area to insure proper seating of new capscrews. Installing Replacement Kit: 1.Grease and insert downstream bearing support so direction of flow arrow corresponds with the arrow on outside of housing. Align the index marks (punch marks) on the bearing support and the edge of the housing. 2. Install downstream retaining capscrews and tighten. 3. Insert rotor with direction arrow properly aligned. Be sure its shaft enters the downstream bearing. 4. Grease and insert upstream bearing support in housing and align the index marks. It may be necessary to spin the rotor to permit its shaft to enter the bearing. Do not force the bearing support down against the rotor as this may break the rotor shaft. 5. Install upstream retaining capscrews and tighten. 6. Be sure rotor is free to spin before placing meter in flow line. TASK No.: I For positive factor identification, wrap strap of plastic tag bearing factor around conduit adapter, thread end through hole in tag and pull tight. Cut off excess strap length. 8. Screw magnetic pickup in all the way and then screw out 1/4 tum. Lock pickup retainer nut. Module I-4 Page 30

31 Figure I-4.6C, Turbine Flow Meter Parts Replacement. MODULE No.: TASK No.: Reference: I-4 Flow Instruments I-4.7 Perform service and check of a Rotameter. OJT Instructor to arrange reference catalogue / Service manual for the Rotameter model relevant to each working area. Materials: 1.Cleaning rags, and Module I-4 Page 31

32 2. Solvent. Equipment & Tools: 1. Tool Box, and 2. Digital Multimeter. Conditions: Work permit. Requirements by Trainee: To study the task and familiarize himself, Understand the operation principle of the variable area flow meter, Be able to identify the main parts of the Rotameter, Understand the difference between Orifice flow meter and Rotameter, Perform periodic and corrective maintenance or replace parts of Rotameter, Draw / Sketch process piping arrangement of the Rotameter, Discuss an understanding with his trainer, and Write observation in his workbook. TASK No.: I-4.7 Details: Variable Area Meters Variable area meters, which are also known as rotameters have a vertical tapered tube, which is partially blocked by a piece of material, called the float. The float is not actually buoyant in the process fluid and is constructed from a heavy material, often stainless steel. When fluid enters the bottom of the rotameter it exerts Pressure on the float and causes the float to rise in the tube. As the float rises, the space around the float in the tube increases and allows the pressure above and below the float to equalize. When the difference in pressure is such that the weight of the float is counter balanced, the float becomes stationary and the flow can be determined. The float height is proportional to the flow rate. The tube can be transparent to allow direct observation of the float if the pressure is low enough for safety. If the pressure is high enough to cause safety concerns or Module I-4 Page 32

33 the fluid is considered too dangerous for other reasons, the tube can be made of stainless steel and the position of the float sensed magnetically. This type is known as an armored rotameter As illustrated in figures I-4.7A&B, at equilibrium there are three forces working on the float: 1. A downwards directed force exerted by the gravity which is constant. 2. An upwards directed buoyancy (Archimedes law) which is constant if the density of the measured liquid or is constant. 3. An upwards directed force exerted by the flowing liquid or gas. TASK No.: I-4.7 Figure I-4.7A, Float at equilibrium position Module I-4 Page 33

34 Figure I-4.7B, Rotameter, main parts TASK No.: I-4.7 Maintenance There is no routine maintenance to be performed of the Rotameter. If meter operation is affected by defective parts these parts to be replaced. Detailed procedures to service or replace Rotameter parts are listed in the reference service manual. Consult your trainer to perform the following: 1. Float and 0-ring Replacement, 2. Magnetic Switch and Relay replacement, 3. Indicator Reference Mark (Zero) Adjustment, 4. Alarm Set Point Adjustment, and 5. Adding the Alarm Option. Module I-4 Page 34

35 TASK No.: I-4.7 Figure I-4.7C, Metal Rotameter with Magnetic Indicator MODULE No.: TASK No.: I-4 Flow Instruments I-4.8 Module I-4 Page 35

36 Service and calibrate a Foxboro 43AP controller. Reference: Materials: OJT Instructor to arrange reference catalogue / Service manual for pneumatic controllers models relevant to each working area. 1. Plastic / St.St. Tubing, 2. Regulated Air Supply. Equipment & Tools: 1. Pneumatic calibrator bench or Druck Pump, 2. Standard test gauges, 3. Service/ Repair Kit, and 4. Tool Box. Conditions: None. Requirements by Trainee: To study the task and familiarise himself, Be able to identify the major components of pneumatic controller, To describe the principle of operation of pneumatic indicating controller, Be able to perform periodic adjustments / calibration of the controller, To perform preventive maintenance, service, parts replacement of the controller, Draw/ Sketch calibration set-up in his work book, Discuss an understanding to his trainer, and Write observations and procedure in his workbook. TASK No.: I-4.8 Details: 43AP Controllers 43AP controller is a device, which senses the pressure in the process and develops an output, which controls a device to regulate that pressure. The control device, or end element, is usually a pneumatic-control valve. The Module I-4 Page 36

37 controller output is usually either a 3-15 or 6-30 psig ( or kpa) pneumatic signal. These controllers can be categorized either as indicating or blind. The indicating controller has a mechanism so that the operator can read the process pressure directly from the controller. The blind controller has no direct-reading mechanism and the operator must rely on an adjacent pressure gauge or other device to know the process pressure. The indicating controller set point is usually marked on the indicator; thus it is easy to adjust to the desired point. Adjustment of the blind controller is more of a trial and error process. Indicating controllers are somewhat more expensive than blind controllers, but the cost difference is moderate if a pressure gauge can be eliminated. Pressure controllers must provide an output to control the end element. This can be an electric or pneumatic signal, but is most often pneumatic for field-mounted controllers. The pneumatic signal is usually 3-15 psig ( kpa), but it can be 6-30 psig ( kpa) if required to reduce the control valve actuator size. The control action needed for pressure control is proportional plus integral, or P and I (integral is also referred to as reset by some manufacturers). The proportional action varies the output in proportion to the difference between the measured pressure and the set pressure. The integral or reset action gradually increases the amount of the correction until the measured pressure is returned to the set point. A more extensive discussion of control modes and controller tuning can be found in the controller s catalogue or service manual, consult your trainer. TASK No.: I-4.8 Preparations A common option for pressure controllers is an auto/manual switch. This is a valve, which allows the output of a manual regulator to be directed to the end element (valve actuator) instead of the controller's automatic output. The transfer can be either bumbles where the outputs are automatically matched to each other when the auto/manual switch is transferred, or manual balance where the operator must match the manual regulator output to the automatic output transfer to manual or the set point to the process variable before transfer to automatic. Module I-4 Page 37

38 Pressure controllers are either surface, panel, pipe-stand, or yoke mounted. Surface-mounted controllers are fastened to a wall or other vertical surface. Panelmounted, also called flush-mounted, controllers are mounted in a cutout in a control panel. Pipe-stand mounting occurs where a vertical or horizontal pipe support is constructed and the controller is provided with a bracket and U-bolts to attach it to a two-inch pipe-stand. It is not a good idea to support controllers on process piping. Yoke mounted controllers are fastened to the valve yoke with special brackets. Yoke mounting is convenient when the valve is accessible. TASK No.: I-4.8 Principle of operation Figure I-4.8A, explains in steps how the pneumatic indicator controller works; Module I-4 Page 38

39 Figure I-4.8 A, Controller s Principle of Operation. TASK No.: I-4.8 Control Adjustments Proportional Controller (P controller); Module I-4 Page 39

40 Figure I-4.8B, illustrates the effect of various proportional band settings Figure I-4.8B, PB Effects at Various Settings Proportional plus Reset Controller (PI Controller); Figure I-4.8C, illustrates the effect of various Reset Times Figure I-4.8C, Effects of Various Reset Times TASK No.: I-4.8 Calibration Calibration is required if the controller has been taken apart for cleaning or for parts replacement, if a change of range is desired, or if the amount of zero is changed substantially. Module I-4 Page 40

41 If the capsule was removed or the flexure cap screw loosened, before calibrating, make the flexure cap screw adjustment above. The controller to be calibrated to 3 to 15 psi signal pressure range, at which the receiver signal is used. Calibration procedures; detailed bench calibration and in-line calibration procedures of the pneumatic indicating controller are listed in the reference catalogue or service manual of the applied model. Consult your trainer. Maintenance and Servicing Maintenance and servicing of pneumatic indicating controller are limited to clean or replace its parts, such as: 1. Supply Air Filter blow out at least once a day, 2. Replace Screen Filter, 3. Clean Nozzle Assembly, 4. Clean booster relay Restrictor, 5. Replace Booster Relay, 6. Change measuring Range, 7. Remove Measurement Pointer or Set Point Index, and 8. Adjusting controller s Alignment. Disassembly; normal servicing of the controller does not require the removal of any parts other than those already mentioned. Further disassembly is not recommended because of possible loss of accuracy or damage to the controller, detailed servicing procedures are mentioned in maintenance section of the selected pneumatic indicating controller model. Consult your trainer. MODULE No.: TASK No.: Reference: I-4 Flow Instruments I-4.9 Calibrate square root extractor. OJT Instructor to arrange reference catalogue / Service manual for Square root extractor model in each working area. Materials: Module I-4 Page 41

42 Equipment & Tools: 1. Tool Box, 2. Standard test gauges / Digital Multimeter, and 3. Pneumatic calibrator / Function generator. Conditions: Work permit. Requirements by Trainee: To study the task and familiarise himself, Understand the function of the square root extractor, To state the purpose of using the square root extractor in a control loop, Be able to calibrate, inspect and replace square root extractor unit, Discuss an understanding to his trainer, and Write observations in his workbook. TASK No.: I-4.9 Details: Function: Pneumatic or Electronic Square-Root Extractor receives a pneumatic or electronic analogue input signal, and provides a pneumatic or electrical output signal proportional to the square root of the input signal. Principle: This instrument solves the equation A = Square root of E, where E and A are input and output signals, respectively. It is used for linearising, differential pressure flow signals Method of Operation: To understand square root extractor method of operation, figure I-4.9A illustrates ECKARDT pneumatic square root extractor as an example and the following steps explains its method of operation Module I-4 Page 42

43 Figure I-4.9A, Pneumatic Square root Extractor Operation Method TASK No.: I-4.9 The input signal is applied to a 1) Diaphragm which causes the 2) Force beam carrying the 3) Flapper to move towards the 4) Nozzle. The thereby increased nozzle back pressure is applied to the 5) Roll diaphragm which is displaced upwards against the pressure of the 6) Spring. The movement of roll diaphragm (5) is transmitted without loss of movement via the 7) Piston rod and a tape-driven 8) Segment to the 9) Shaft. A root extracting, or respectively, function generating 10) Cam is rigidly attached to the external extension of this shaft. By means of 11) Cam follower and Module I-4 Page 43

44 12) Tension spring, the rotary movement is converted into a vertical movement which, by being applied to force beam (2), opposes the force generated by diaphragm (1), so as to bring forces into equilibrium. The rotation of shaft (9) is also transmitted via the 13) Tape drive which alters the tension of the 14) Spring, and thereby alters the tension of the 15) Force beam and attached flapper in relation to the 16) Nozzle, the change in back pressure so generated being applied to the 17) Double diaphragm in the amplifier unit. The resultant output pressure is fed back to the TASK No.: I ) Input diaphragm acting on the force beam (15) which is then brought to a position of equilibrium. Calibration: Square root extractor is factory calibrated at a reference supply pressure. To maintain specified accuracy at a different supply pressure, the instrument must be recalibrated to the new pressure, figure I-4.9B illustrates calibration setup of our model device. The instrument to be calibrated in the same position of service installation. Detailed calibration procedure is listed in the reference catalogue or service manual. Consult your trainer. Module I-4 Page 44

45 Figure I-4.9B, Square root Extractor Calibration Setup. TASK No.: I-4.9 Maintenance: Maintenance of a pneumatic square root extractor is limited to periodic checks of supply pressure or input / output signals and clean or replace parts, such as; supply air filter, clean restrictor, replace relay, replace screen filters and service the service manifold. Fault Finding: 1) Output signal rises but does not reach full value, possible cause is input signal line not pressure tight, or blocked restrictor, check connections or clean restrictor. 2) Output signal fluctuates, possible cause is cam follower track or roller dirty, clean cam, track and follower roller. Module I-4 Page 45

46 MODULE No.: TASK No.: I-4 Flow Instruments I-4.10 Troubleshooting 3 way / 5 way valve manifold. Reference: Materials: OJT Instructor to arrange reference catalogue / Service manual for manifold type relevant to each working area. 1. Cleaning Rags, and 2. Solvent Equipment & Tools: Tool Box Conditions: Work permit Module I-4 Page 46

47 Requirements by Trainee: TASK DETAILING MANUAL To study the task and familiarise himself, Select proper tools to perform this task, To understand the purpose of using manifolds for DP measurement, To perform preventive maintenance, service, parts replacement of manifolds, Draw/ Sketch manifold process piping in his workbook, Discuss an understanding to his trainer, and Write observations and procedure in his workbook. TASK No.: I-4.10 Details: Function: Meter manifolds are made for use with field meters or differential pressure transmitters to achieve meter operation, calibration and service in easy and safe way. Features: There are two types of meter manifolds, 3-valve and 5-valve. In 3-valve manifolds, there are two main block valves and one block equalising valve. In 5- Module I-4 Page 47

48 valve manifolds, there are two main block valves along with double block and bleed for the bypass line. Manifolds are available in both hard or soft seat configurations, to withstand process pressure and temperature. TASK No.: I-4.10 Figure I-4.10B, 5-Valve Manifold in case of meter calibration. Figures I-4.10 A&B, illustrates 5-valve manifolds status in case of normal operation and meter calibration. Consult your trainer for safe isolation procedure. Module I-4 Page 48

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work?

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work? Exercise 4-1 Flowmeters EXERCISE OBJECTIVE Learn the basics of differential pressure flowmeters via the use of a Venturi tube and learn how to safely connect (and disconnect) a differential pressure flowmeter

More information

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters Table of Contents Page 1. Principle of Operation...2 2. Installation Planning......2 3. Installation...3 3.1 Safety Considerations...

More information

EZ-IN Series Turbine Flowmeter

EZ-IN Series Turbine Flowmeter Class I, Group A, B, C, D, Division I Complies with ASME Standard B31.3 NUFLO EZ-IN Series Turbine Flowmeter Installation Manual Part No. 9A-100062997, Rev. 01 Measurement Systems EZ-IN Series BF Turbine

More information

Contents. Pressure measurement technology Pressure calibrators 18 Exercises 19-20

Contents. Pressure measurement technology Pressure calibrators 18 Exercises 19-20 1 Pressure Contents Topics: Slide No: Pressure measurement technology 03-17 Pressure calibrators 18 Exercises 19-20 2 Pressure Gauges Barometer Used to measure Barometric Pressure Reference is 0 psia,

More information

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners. INSTALLATION & OPERATING INSTRUCTIONS SERIES 40 Positioners Form IO2-0406 Description of Device Moniteur's Series 40 pneumatic (3-15psi) and electropneumatic (4-20mA) positioners are advanced control devices

More information

Fisher 4194HS Differential Pressure Indicating Controllers

Fisher 4194HS Differential Pressure Indicating Controllers Instruction Manual Fisher 4194HS Differential Pressure Indicating Controllers Contents Introduction... 2 Scope of Manual... 2 Description... 2 Specifications... 5 Educational Services... 5 Installation,

More information

Fisher 4194S Differential Pressure Controllers

Fisher 4194S Differential Pressure Controllers Instruction Manual 4194S Controllers Fisher 4194S Differential Pressure Controllers Contents 1. Introduction... 2 Scope of Manual... 2 Description... 2 Specifications... 5 Educational Services... 5 2.

More information

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:TRQSMAN16 Table of Contents Contents Table of Contents... 2

More information

IFOA Integral Flow Orifice Assembly

IFOA Integral Flow Orifice Assembly Instruction MI 022-333 July 2007 Introduction IFOA Integral Flow Orifice Assembly The IFOA integral flow orifice assembly is used in conjunction with a Foxboro electronic or pneumatic differential pressure

More information

Instruction. MI June E69F Current-to-Pneumatic Signal Converter

Instruction. MI June E69F Current-to-Pneumatic Signal Converter Instruction MI 018-430 June 2005 E69F Current-to-Pneumatic Signal Converter ! DANGER This converter may have agency certification for installation in hazardous locations or for intrinsic safety. Use of

More information

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP Installation, Operation, & Maintenance Manual Welker Sampler Model GSS-4HP The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

Transmitters. Differential Pressure Transmitters Pneumatic Design FOXBORO 13A D/P Cell

Transmitters. Differential Pressure Transmitters Pneumatic Design FOXBORO 13A D/P Cell Transmitters Differential Pressure Transmitters Pneumatic Design FOXBORO 13A D/P Cell Oldest design, developed during WW 2. Can be used for flow, level, and pressure, vent low side. Several ranges 0 to

More information

PMV P36C AND P41C POSITIONERS ACTUATORS

PMV P36C AND P41C POSITIONERS ACTUATORS PMV P36C AND P41C POSITIONERS USED WITH DeZURIK PNEUMATIC ACTUATORS Instruction D10327 August 2012 Instructions These instructions provide information about Models P36C and P41C PMV Positioners. They are

More information

LTX RF LEVEL SENSOR. Instruction Manual

LTX RF LEVEL SENSOR. Instruction Manual LTX RF LEVEL SENSOR Instruction Manual FOR MODELS LTX01, LTX02, LTX05 Intempco Document No: LTX - M01 Rev. 1 Issue Date: April 2005 LTX01 RF LEVEL SENSOR USER MANUAL Software Rev : Rev. Date : June 2004

More information

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood TABLE OF CONTENTS 1. General valve description and start-up... 1 2. Main valve maintenance... 1 3. Pilot maintenance... 5 4. Pilot

More information

Liquid Turbine Flowmeter

Liquid Turbine Flowmeter NUFLO Liquid Turbine Flowmeter User Manual 167018 Explosion-proof for use in Class I, Division I, Groups A, B, C, D Hazardous Environments ANSI 12.27.01-2003 Single Seal Part No. 9A-100062201, Rev. 01

More information

Fisher 2506 and 2516 Receiver/Controllers

Fisher 2506 and 2516 Receiver/Controllers Instruction Manual Fisher 2506 and 2516 Receiver/Controllers Contents Introduction... 2 Scope of Manual... 2 Description... 2 Specifications... 2 Educational Services... 4 Installation... 5 Mounting the

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 2 Float Switch EXERCISE OBJECTIVE Learn the working principle of float switches and how to use the float switch, Model 46935. DISCUSSION OUTLINE The Discussion of this exercise covers the following

More information

RUN ACCUM. TOTAL STOP BAT LOW HIGH

RUN ACCUM. TOTAL STOP BAT LOW HIGH TURBOPULSE TURBINE FLOWMETER INSTRUCTION MANUAL gal RUN ACCUM. TOTAL STOP BAT LOW HIGH RESET > PROGRAM ENTER ACCUM TOTAL ^ RATE TOTAL TP050 TABLE OF CONTENTS 1. INTRODUCTION Overview 1 1.1 Model number

More information

Operation and Maintenance Manual

Operation and Maintenance Manual BM / BMA Hydrometers ½ Operation and Maintenance Manual i This manual is intended for use by the users of this equipment. The information contained herein is the property of the Arad Ltd. Dalia and may

More information

MODEL 1100 TURBINE FLOW METER

MODEL 1100 TURBINE FLOW METER MODEL 1100 TURBINE FLOW METER INSTALLATION & INSTRUCTION MANUAL 8635 Washington Ave. Racine, Wisconsin 53406 Phone: 800.433.5263 Fax: 800.245.3569 www.hedland.com 2 OPERATIONAL START-UP Fluid entering

More information

LIQUID MEASUREMENT STATION DESIGN Class No

LIQUID MEASUREMENT STATION DESIGN Class No LIQUID MEASUREMENT STATION DESIGN Class No. 2230.1 Michael Frey Systems Sales Manager Daniel Measurement & Control, Inc. 5650 Brittmoore Rd. Houston, Texas 77041 INTRODUCTION The industry continues to

More information

2506 Series Multi-Trol Receiver/Controllers (Types 2506, 2516, 2516F)

2506 Series Multi-Trol Receiver/Controllers (Types 2506, 2516, 2516F) Instruction Manual 2506, 2516, 2516F Receiver/Controllers 2506 Series Multi-Trol Receiver/Controllers (Types 2506, 2516, 2516F) Contents Introduction............................... 2 Scope of Manual.........................

More information

Powers Controls TT 184 Temperature Transmitters

Powers Controls TT 184 Temperature Transmitters Powers Controls Document No. 155-077P25 TT 184-1 Room Transmitter Remote Bulb Average Bulb Rigid Bulb Description The are direct acting, one-pipe instruments that sense temperature and transmit a proportional

More information

Lease Automatic Custody Transfer

Lease Automatic Custody Transfer Lease Automatic Custody Transfer Angus Manufactured LACT Units Updated 19-Dec-01, Slide 2 LACT Unit Requirements Are used for the automatic unattended measurement of crude oil. Accurately measure the quantity

More information

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE*

CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* CAPSU-PHOTOHELIC PRESSURE SWITCH/GAGE* Specifications - Installation and Operating Instructions Bulletin B-34 Series 43000 CAPSU-Photohelic Switch/Gage The CAPSU-Photohelic Switch/Gage is a most versatile,

More information

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information. Type 500X Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions Ordering Information Type 500X I/P Transducers Output Range Part Number Input psi kpa Impedance 500-AA

More information

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 ) I & M Mark 8 Series 0 Wasson Road Cincinnati, OH 4509 USA Phone 5-5-5600 Fax 5-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (-/ - ) Warning:

More information

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 ) I & M Mark 8 Series 30 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (/ -

More information

1100 Series Piston Type Differential Pressure Gauges

1100 Series Piston Type Differential Pressure Gauges 1100 Series Piston Type Differential Pressure Gauges 1. Safety Before installing, check the Series Number and verify compatibility to the process media and temperature in contact with the wetted parts.

More information

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31 LACT MEASUREMENT Prepared By: Ken A. Steward. P.E. Linco-Electromatic, Inc. 4580 West Wall Street Midland, Texas 79703 The Operation of L.A.C.T. Units The simplest approach to the understanding of the

More information

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting I & M 8000 Series 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 lowflow@richardsind.com www.lowflowvalve.com Installation & Maintenance Instructions for 8000 Series Low

More information

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual Mechanical Specifications Flow Meter with Polypropylene Body (ES version) Maximum Operating Pressure: 150 PSIG Maximum

More information

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual COMPANY Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:SANITARYMAN16 Mechanical Specifications Measuring Accuracy ± 1.0%

More information

CENTAC Inlet and Bypass Valve Positioners

CENTAC Inlet and Bypass Valve Positioners CENTAC Inlet and Bypass Valve Positioners INGERSOLL-RAND AIR COMPRESSORS INLET AND BYPASS VALVE POSITIONERS Copyright Notice Copyright 1992, 1999 Ingersoll-Rand Company THIS CONTENTS OF THIS MANUAL ARE

More information

Control Valves Positioner

Control Valves Positioner Control Valves Positioner HiFlo Valve Positioner Easy calibration Corrosion-resistant cover and base Withstands 150 psi at all parts Two -sided cam for easy field reversibility Optional / NPT for piped

More information

Control Valves Positioner

Control Valves Positioner Control Valves Positioner HiFlo HiFlo Valve Positioner Corrosion-resistant cover and base Easy calibration Withstands 150 psi at all parts Two -sided cam for easy field reversibility Optional / NPT for

More information

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)

More information

Lecture 3.3. Velocity, motion, force and pressure sensors

Lecture 3.3. Velocity, motion, force and pressure sensors 1. Tachogenerator Lecture 3.3 Velocity, motion, force and pressure sensors Figure 2.4.1 Principle of working of Techogenerator[1] Tachogenerator works on the principle of variable reluctance. It consists

More information

Models NAA, NAB, NAD Pneumatic differential pressure transmitters. Deltapi N Series A complete range of pneumatic pressure transmitters

Models NAA, NAB, NAD Pneumatic differential pressure transmitters. Deltapi N Series A complete range of pneumatic pressure transmitters Operating Instruction OI/NAX-EN Rev. C Models NAA, NAB, NAD Pneumatic differential pressure transmitters Deltapi N Series A complete range of pneumatic pressure transmitters CONTENTS Section Page INTRODUCTION...2

More information

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions 6677 N. Gessner, Houston, Texas 77040 Throughout the oil and gas industry, there stems the need for accurate, economical measurement

More information

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN Electropneumatic Converters i/p Converters Type 6111 Fig. 1 Type 6111 in standard version Fig. Type 6111 mounted on a supply air manifold Fig. 3 Type 6111 in field enclosure Mounting and Operating Instructions

More information

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual COMPANY Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual 2016 AW-Lake Company. All rights reserved. Doc ID:PADDLEMAN082416 Mechanical Specifications Flow Meter with Polypropylene

More information

Masoneilan Models 8007 and 8008 Electropneumatic Transducers Instructions

Masoneilan Models 8007 and 8008 Electropneumatic Transducers Instructions Masoneilan Models 8007 and 8008 Electropneumatic Transducers Instructions Instructions N ES 60004 E Rev. A 12/97 Masoneilan Valve & Controls installation These instructions apply to the Masoneilan Models

More information

Welker Jet Insert Model Control Valve

Welker Jet Insert Model Control Valve Welker Jet Insert Model Control Valve Model WJ-1N, WJ-2N, WJ-4N, WJ-6N, & WJ-8N The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for the installation,

More information

Chapter 11. Control System Instrumentation

Chapter 11. Control System Instrumentation Chapter 11 Control System Instrumentation Measuring Instrumentations Transducers and Transmitters The typical process measuring instrument consists of sensing elements and transmitters (driving elements).

More information

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/

DWYER INSTRUMENTS, INC. Phone: 219/ P.O. BOX 373 MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/ Series 43000 Capsu-Photohelic Pressure Switch/Gage Specifications - Installation and Operating Instructions Bulletin B-34 Ø4-3/4 [120.65] 3-7/8 SQ [98.43] 3/4 CONDUIT 4-3/8 [111.13] HOUSING REMOVAL 3-1/16

More information

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information. Type 500X Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions Ordering Information Type 500X I/P Transducers Output Range Part Number Input psi kpa Impedance 500-AA

More information

three different ways, so it is important to be aware of how flow is to be specified

three different ways, so it is important to be aware of how flow is to be specified Flow-control valves Flow-control valves include simple s to sophisticated closed-loop electrohydraulic valves that automatically adjust to variations in pressure and temperature. The purpose of flow control

More information

Operating Instructions. Pneumatic Control Valve Low Temperature. Type Series GS3

Operating Instructions. Pneumatic Control Valve Low Temperature. Type Series GS3 Operating Instructions Pneumatic Control Valve Low Temperature Type 8026 Series GS3 With: Digital Positioner Type 8048 Electro-pneumatic Positioner Type 8047 Pneumatic Positioner Type 8047 Version: 03/2006

More information

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring.

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring. Test 1 1. Which statement is True? A. Pneumatic systems are more suitable than hydraulic systems to drive powerful machines. B. Mechanical systems transfer energy for longer distances than hydraulic systems.

More information

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been

More information

INSTRUCTION AND MAINTENANCE MANUAL GC31 COMMANDAIRE POSITIONER

INSTRUCTION AND MAINTENANCE MANUAL GC31 COMMANDAIRE POSITIONER Enidine / Conoflow 15 Commerce Way Westminster, SC 29693 Tel: (864) 647-9521 Fax: (864) 647-7993 WARNING Conoflow products are designed and manufactured using materials and workmanship required to meet

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-3 Venturi Tubes EXERCISE OBJECTIVE In this exercise, you will study the relationship between the flow rate and the pressure drop produced by a venturi tube. You will describe the behavior of

More information

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes: SECTION 15970 HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Thermostats, temperature transmitters, controllers, automatic valves, dampers, damper operators, pneumatic/ electric

More information

Operating Instruction for Plastic Vortex Flow Transmitter. Model: UV

Operating Instruction for Plastic Vortex Flow Transmitter. Model: UV Operating Instruction for Plastic Vortex Transmitter Model: UV DESCRIPTION INTRODUCTION The UV series vortex-shedding flow meter is a general-purpose electronic liquid flow meter. The standard output is

More information

Copper Sleeve, Unit Injector, Replacement

Copper Sleeve, Unit Injector, Replacement Volvo Trucks North America Greensboro, NC USA This service bulletin replaces SB 237-46, Copper Sleeve, Unit Injector, Replacement dated 6.2007, publication no. PV776-20177417. DService Bulletin Trucks

More information

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value.

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value. E X S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s EX Series Electromagnetic FLOW SENSOR instructions EX EX The Leader in Flow Meter Value. Table of Contents General

More information

walton TEMPERATURE CONTROL SYSTEMS Pneumatically Operated (Rotary)

walton TEMPERATURE CONTROL SYSTEMS Pneumatically Operated (Rotary) walton TEMPERATURE CONTROL SYSTEMS Pneumatically Operated (Rotary) WALTON ENGINEERING CO. LTD. 61 London Road St Albans Hertfordshire AL1 1LJ England Telephone +44 (0)1727 855616 Fax +44 (0)1727 841145

More information

Pneumatic components (Electro pneumatic Regulator) Safety Precautions. 3 When releasing secondary control pressure,

Pneumatic components (Electro pneumatic Regulator) Safety Precautions. 3 When releasing secondary control pressure, Pneumatic components (Electro pneumatic Regulator) Safety Precautions Read this before starting use. Please refer to Intro 43 for general details on the pneumatic components, and to " Precautions" in this

More information

NDM Rotary Gas Meter Installation and Operation Manual

NDM Rotary Gas Meter Installation and Operation Manual The NMT TM NDM Rotary Displacement Gas Meter is a positive displacement type of meter which, by means of two counter-rotating impellers and a counting mechanism, measures a known volume of gas with each

More information

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version MD10 Engine Controller Installation and User Manual for the MD10 Engine Controller. Full Version File: MartinMD10rev1.4.doc May 16, 2002 2 READ MANUAL BEFORE INSTALLING UNIT Receipt of shipment and warranty

More information

XL90 Series High-Performance Positioner

XL90 Series High-Performance Positioner XL90 Series High-Performance Positioner GENERAL INFORMATION This bulletin is designed to assist in installing, calibrating, troubleshooting and performing maintenance as required for the XL90 Series high-performance

More information

Fisher 657 Diaphragm Actuator Sizes and 87

Fisher 657 Diaphragm Actuator Sizes and 87 Instruction Manual 657 Actuator (30-70 and 87) Fisher 657 Diaphragm Actuator Sizes 30 70 and 87 Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Mounting

More information

XL90 Series High-Performance Positioner

XL90 Series High-Performance Positioner Flowserve Corporation 765 South 100 East Phone: 801 373 3028 Flow Control Division Provo, Utah 84606 Facsimile: 801 489 2228 Automation Business Unit www.flowserve.com Email: actuators@flowserve.com XL90

More information

Reference Manual Rev AA June Rosemount 3155 Nuclear Pressure Transmitter

Reference Manual Rev AA June Rosemount 3155 Nuclear Pressure Transmitter Reference Manual June 2015 Rosemount 3155 Nuclear Pressure Transmitter Reference Manual June 2015 Rosemount 3155 Rosemount 3155 Nuclear Pressure Transmitter NOTICE Read this manual before working with

More information

Fisher 2506 and 2516 Receiver Controllers

Fisher 2506 and 2516 Receiver Controllers 2506/2516 Receiver Controllers Product Bulletin Fisher 2506 and 2516 Receiver Controllers The 2506 receiver controller takes the input from a pneumatic transmitter, matches it against the adjustable set

More information

Model 1000 Vortex Meter

Model 1000 Vortex Meter Model 1000 Vortex Meter Installation and Instruction Manual Table of Contents General Information... 1 1-1 General... 1 1-2 Principles of Operation... 1 1-3 Sensor Operation... 1 1-4 Calibration Factor...

More information

Model 4000 Pressure Controller Operation, Parts, and Instruction Manual

Model 4000 Pressure Controller Operation, Parts, and Instruction Manual TABLE OF CONTENTS General 2 Relay Manifold 14 Scope 2 Replacement 14 Table 1 - Bourdon Tube Pressure Range 2 Reconditioning 14 Specifications 3 Figure 6 - Tubing Connections 15 Unpacking 5 Figure 7 - New

More information

Flow Control Valve IOM 770-U

Flow Control Valve IOM 770-U IOM 770-U Flow Control Valve (Sizes 1½-14"; DN40-350) Description The Model 770-U Flow Control Valve is a hydraulically operated, diaphragm actuated, control valve that maintains pre-set maximum flow,

More information

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves Installation, Operation, Maintenance Instructions Standard Valves Series 035 000 Globe Valves Series 031 000 Angle Valves Series 033 000 3-Way-Valves 1 GENERAL INFORMATION These instructions are designed

More information

Series 20 Installation Instructions

Series 20 Installation Instructions Series 20 Installation Instructions Installation Instructions and field service checklist Read these instructions carefully. Failure to follow them could result in a fire or explosion causing property

More information

Baumann Sanitary Diaphragm Angle and Inline Control Valve

Baumann Sanitary Diaphragm Angle and Inline Control Valve Instruction Manual 84000 Valve Baumann 84000 Sanitary Diaphragm Angle and Inline Control Valve Contents Introduction... 1 Scope of Manual... 1 Safety Precautions... 2 Maintenance... 2 Flow Direction...

More information

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators Fig. 1 Type 3761 Positioner Mounting and Operating Instructions EB 8386 EN Edition July 2007 Contents Contents Page 1 Design and

More information

R & D SPECIALTIES ROTROL I USER'S MANUAL

R & D SPECIALTIES ROTROL I USER'S MANUAL R & D SPECIALTIES ROTROL I USER'S MANUAL TABLE OF CONTENTS INTRODUCTION...2 SPECIFICATIONS...2 CONTROLS AND INDICATORS...3 TIME DELAYS...4 INSTALLATION...5 SYSTEM OPERATION...9 TROUBLESHOOTING...13 OPTIONAL

More information

Troubleshooting Bosch Proportional Valves

Troubleshooting Bosch Proportional Valves Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves

More information

Experiment (4): Flow measurement

Experiment (4): Flow measurement Introduction: The flow measuring apparatus is used to familiarize the students with typical methods of flow measurement of an incompressible fluid and, at the same time demonstrate applications of the

More information

User s Manual OM th edition

User s Manual OM th edition FloWing Eccentric Rotary type Control Valves Model: VFR (1, 1½, 2 inches) User s Manual OM2-8130-0300 5th edition Copyright, Notices and Trademarks 2012 Azbil Corporation All Rights Reserved. While this

More information

ROOTS Meters Series B3 Meter Models 8C175-56M175

ROOTS Meters Series B3 Meter Models 8C175-56M175 ROOTS Meters Series B3 Meter Models 8C175-56M175 Refer to IOM-B3 for Complete Instructions IS:B3 3.03 RECEIVING, HANDLING AND STORAGE ROOTS rotary positive displacement gas meters are precision measurement

More information

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX: TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie SERIES SERVICE MANUAL INTRODUCTION The gasoline engine industry

More information

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators I & M Mark (/ ) 0 Wasson Road Cincinnati, OH 0 USA Phone --00 Fax -8-00 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark Pressure Regulators Warning: Jordan Valve

More information

OM Field-Type I/P Converter Model : KUX113 User's Manual

OM Field-Type I/P Converter Model : KUX113 User's Manual OM2-5900-1130 Field-Type I/P Converter Model : KUX113 User's Manual Copyright, Notices and Trademarks 1994-2012 Azbil Corporation All Rights Reserved. While this information is presented in good faith

More information

Industrial Turbo Meters, Sizes 2" through 6"

Industrial Turbo Meters, Sizes 2 through 6 Industrial Turbo Meters Sizes 2" through 6" TUR-UM-00530-EN-19 (October 2014) User Manual Industrial Turbo Meters, Sizes 2" through 6" User Manual CONTENTS Scope of the Manual 5 Specifications 5 Product

More information

Familiarize yourself with the pressure loss phenomenon. The Discussion of this exercise covers the following point:

Familiarize yourself with the pressure loss phenomenon. The Discussion of this exercise covers the following point: Exercise 3-2 Pressure Loss EXERCISE OBJECTIVE Familiarize yourself with the pressure loss phenomenon. DISCUSSION OUTLINE The Discussion of this exercise covers the following point: Pressure loss Major

More information

To ensure proper installation, digital pictures with contact information to before startup.

To ensure proper installation,  digital pictures with contact information to before startup. Check List for Optimal Filter Performance? There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing or

More information

Installation, Operation, and Maintenance Manual GENERAL VALVE GENERAL VALVE TRUSEAL / IOM-GEN-TRUSEAL. Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual GENERAL VALVE GENERAL VALVE TRUSEAL / IOM-GEN-TRUSEAL. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual GENERAL T GENERAL VALVE Installation, Operation, and Maintenance Manual Cameron s Valves & Measurement Group Revised 10/07 IOM-GEN-TRUSEAL Installation,

More information

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300)

Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12; DN80-DN300) IOM IR-472-50-bRU Flow Control & Pressure Reducing Valve with Hydraulic Control (Sizes 3''- 12"; DN80-DN300) Description: The BERMAD Flow Control and Pressure Reducing Valve with Hydraulic Control is a

More information

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual Electro-Pneumatic Positioner Series 830/831-WP/EX Operation & Maintenance Manual Electro-Pneumatic Positioner Model 830/831- WP/EXP This operation & maintenance manual corresponds to Forbes Marshall Arca

More information

Model 1100 Turbine Flow Meter

Model 1100 Turbine Flow Meter Model 1100 Turbine Flow Meter INSTALLATION & INSTRUCTION MANUAL 8635 Washington Avenue Racine, Wisconsin 53406 Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267 www.hedland.com TABLE

More information

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82 E X S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s EX Series Electromagnetic FLOW SENSOR instructions EX EX The Leader in Flow Meter Value. Table of Contents General

More information

The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output. GENERAL INFORMATION T5220 SERIES TRANSDUCER Electro-Pneumatic (I/P, E/P) APPLICATIONS The T5220 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional

More information

Installation Instructions

Installation Instructions Quick-Mount Visual Instructions for Quick-Mount Visual Instructions 1. Rotate the damper to its failsafe position. If the shaft rotates counterclockwise, mount the CCW side of the actuator out. If it rotates

More information

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN Pneumatic or Electropneumatic Positioner for Rotary Actuators Type 3761 Fig. 1 Type 3761 Positioner Mounting and Operating Instructions EB 8386 EN Edition June 2004 Contents Contents Page 1 Design and

More information

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet) Flow Control 500a DESCRIPTION The Viking 1-1/2 is a quick opening, differential type flood valve with a spring loaded rolling diaphragm clapper. The can be used to facilitate manual or automatic on/off

More information

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Pg. 1 of 10 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING HAYWARD TBH SERIES

More information

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves Series 250 Type 3252 1 and Type 3252 7 Pneumatic Control Valves Type 3252 High-pressure valve with Type 3277 Pneumatic Actuator and Type 3767 Electropneumatic Positioner Mounting and Operating Instructions

More information

NECO Pumping Systems

NECO Pumping Systems INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS For Your NECO Pumping Systems PACKAGED CIRCULATING SYSTEM THIS COMPLETELY ASSEMBLED, TESTED, PACKAGED CIRCULATING SYSTEM IS OF THE HIGHEST QUALITY AND

More information

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS INTRODUCTION The two most common methods of measuring the volume of petroleum liquids are tank gauging and liquid metering. The problems associated with

More information

Kimray reserves the right to modify or improve the designs or specifications of such products at any time without prior notice Kimray Inc.

Kimray reserves the right to modify or improve the designs or specifications of such products at any time without prior notice Kimray Inc. TREATER VALVE All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been made to ensure their accuracy, they are not to be construed

More information

Fisher 4194A, B, and C Differential Pressure Controllers1 1

Fisher 4194A, B, and C Differential Pressure Controllers1 1 Instruction Manual 4194A, B, and C Controllers Fisher 4194A, B, and C Differential Pressure Controllers1 1 Contents 1. Introduction Scope of Manual... 3 Description... 5 Specifications... 5 Educational

More information