EULR Fan. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

Size: px
Start display at page:

Download "EULR Fan. Fläkt Woods 8192 GB Specifications are subject to alteration without notice"

Transcription

1 Page Installation Installation alternatives Connection to the inlet/outlet duct..3 Connection of duct to the fan outlet..3 Electrical connections Guards To adjust the V-belt tension To change the belts Installation of HABASIT flat-belt drive...5 Moveing the motor to adjust the belt tension Dismantling the EULR belt guard (principle) Belt pulleys Variable-pitch guide vanes Checks to be made prior to starting the fan Starting the fan Storage before installation Installation Filling with manometer liquid Hose connections Checks Temperature correction Air flow measurement with q-dysa and analogue flow indicating instrument.10 Installation of the frequency converter.11 Fläkt Woods 8192 GB Specifications are subject to alteration without notice

2 Installation : EULZ-64 Protective screen EULZ-63 counterflange EULZ-61 flexible connection EULZ-62 connection piece Inlet: Fig. 1 EULZ-65 damper EULZ-62 connection piece EULZ-61 flexible connection EULZ-63 counterflange EULZ-64 protective screen Installation alternatives The fan can be installed to discharge into a duct or into some other unit section. Alternative directions of discharge and locations of discharge opening are shown in Fig. 2 and 3. Horizontal installation Vertical installation (sizes 11 32) Top 1) inlet upwards forward Rear inlet forward Left side inlet upwards downwards Normal inlet (end wall Top 1) inlet Fig. 2 Bottom inlet 2) downwards 1) Upward outlet not possible 2) Downward outlet not possible Fig. 3 Normal inlet (end wall) Fläkt Woods 8192 GB Specifications are subject to alteration without notice

3 Connection to the inlet/outlet duct Ducts can be connected to the connection parts of the unit in accordance with one of the examples shown in Fig. 4. Important! For all alternatives, make sure that the deadweight of the duct system is not applied to the unit casing. Connection piece Flexible connection Counterflange Duct EULZ-61 EULZ-62 EULZ-63 Connection pece Flexible connection Counterflange Duct EULZ-61 EULZ-62 EULZ-63 Fig. 4a Fig. 4b Fig. 4c The duct can be connected to the casing in accordance with one of the following alternatives: A. By means of a connection piece secured to the unit casing with self-tapping screws. The duct can then be connected by means of a PG-joint or a flanged joint as shown in Fig. 4a. B. By means of a flexible connection secured to the unit casing with self-tapping screws. The duct can then be connected by means of a PG-joint or a flanged joint as shown in Fig. 4b. C. By means of a collared duct with sheet steel angles at the corners. Connection of duct to the fan outlet Installation principle: All connections should be fitted edge-to-edge with the back plate of the fan. N.B. Not all connection facilities are shown, see Fig. 5 and 6. Fig. 6 Electrical connections Electrical connections are to be carried out by an authorized electrician. Use a rubber insulated cable but do not run the cable through the inspectiondoor. Allow about 1.2 m of extra cable on the inside of the casing of the EULR-11 through -32, to enable the fan to be withdrawn for service. See Fig. 9. Use a trepanning drill, for instance, for drilling a hole for the cable gland at a suitable point on the casing. The cable gland can be arranged as shown in Fig. 8. Safety isolating switch The fan should be equipped with a safety isolating switch such as the EULZ-17. Always open the safety isolating switch before doing any work on the fan. The safety isolating switch should be located at a point that enables the fan to be withdrawn without having to disconnect the electrical connections. Do not use the safety isolation switch as an operating switch. Fig. 7 Fig. 8 Fig. 5 Fig. 9 Fläkt Woods 8192 GB Specifications are subject to alteration without notice

4 Guards The provisions of the EEC Machinery Directive concerning guards must be met. This means that the fan must be equipped with screen protection for belt drive and inlet or screen protection (requiring tools to dismantle it) behind the inspection cover or a door lock. To adjust the V-belt tension The belts must be correctly tensioned to ensure good contact with the pulleys. If insufficiently tensioned, the belts may slip, and if excessively tensioned, the motor and fan bearings may be overloaded. When correctly tensioned, the belt deflection L will be 15 mm per metre of distance between centres (c/c) when a force P (N) is applied. The deflection and force should preferably be measured by means of a tensiometer (see Fig. 10 and 11). The force P is dependent on the belt type as shown in the table below. c/c L To change the belts To change the belts, first move the motor towards the fan by a sufficient amount to enable the old belts to be easily prised off the pulleys and the new belts to be prised on. Change all the belts at the same time. Use matched belts (with the same production number), i.e. belts of exactly the same length. Tension the belts according to the instructions on this page and align them as shown in Fig. 12. Retension the belts after 30 minutes of operation. Fig. 12 P Fig cm N Fig. 11 Belt section SPZ SPZ SPA SPA SPB SPB SPC SPC 1) New belts. Effective diameter of smaller pulley, mm P in N / belt Normal Max. 1) Fläkt Woods 8192 GB Specifications are subject to alteration without notice

5 Installation of HABASIT flat-belt drive Caution! Never fit an ice cold and stiff belt; allow the belt to thaw out, become flexible and pliable before fitting it. Exposure to cold impairs the elasticity of the belt material. This will make the belt difficult to fit and, in the future, may cause it to break apart at the weld. 1. Fit the motor and fan pulleys to their corresponding shafts but do not tighten the bushes. 2. Fit the belt around the pulleys and push the motor by hand to stretch the belt. 3. Align the pulleys by means of a straight edge and tighten the pulley bushes. 4. Tighten the motor mounting bolts only so hard that the motor will still be able to slide on the guide rails. 5. Measure the longest free measurement distance on the belt to the nearest 100 mm. The belt must not be in contact with the pulleys along the measurement distance. 6. Remove the belt, place it on a flat surface and mark off the above measurement distance to the nearest 100 mm. 7. Refit the belt to the pulleys and tension it by means of the tensioning screws of the motor guide rails. Keep the shafts of the motor and fan as parallel as possible. 8. Conclude the tensioning when the belt has achieved the elongation specified in the table. 9. Rotate the belt drive by hand in both directions. If the belt tends to move axially in one direction or the other, this is because the shafts are not parallel. Adjust by means of the tensioning screws on the slide rails until the belt remains in the centre of the pulleys when the pulleys are rotating. 10. When tensioning has been completed and the belt remains in position when the drive is rotating, securely tighten the motor mounting bolts. Start by tightening the bolts nearest to the pulley. Before tensioning (mm) Distance between marks After tensioning (mm) Type: F 0, F 1 Type: F 14, A 2, A 3, A 4 2,8% 2,5% ,8 102, ,6 205, ,4 307, ,2 410, ,0 512, ,8 615, ,6 717, ,4 820, ,2 922, ,0 1025,0 Tension the belt until the elongation tabulated above has been achieved. Measurement distance Use a straight edge to check that the pulleys are in line. If the belt moves sideways, adjust by means of the tensioning screws of the guide rails or motor bracket. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

6 Moveing the motor to adjust the belt tension The belt tension can be adjusted by moving the motor. 1. Remove the belt guard, if fitted. 2. Slightly back off the 4 mounting screws. 3. Use the tensioning screws to adjust the belt tension. 4. Check the alignment of the drive. Align by means of the adjustment screw. 5. Retighten the mounting bolts. 6. Refit the belt guard if one was fitted EULR-60 through -84 Tensioning pad Tensioning screw EULR-11 through -53 Mounting screw Slide rail Tensioning screw Mounting screw Fig. 14 Adjustment screw Mounting bolt Dismantling the EULR belt guard (principle) Adjustment screw Sliding cover plate for motor shaft Fig. 13 Fig. 15 Fläkt Woods 8192 GB Specifications are subject to alteration without notice

7 Belt pulleys To remove and refit the belt pulley Never hammer the belt pulley onto or off a shaft, since even light blows and shocks may damage the bearing, which will give rise to noise and an abnormally high rate of wear. To remove: 1. Remove the screws, oil them sparingly and screw one of them into the extractor hole, i.e. the tapped hole in the bush (see Fig. 16 and 17). 2. Tighten the screw until the bush is free of the hub and the unit is free of the shaft. 3. Remove the pulley and the bush from the shaft as one unit. To fit: 1. Clean the bore of the pulley and the inside and outside of the bush to remove any anti-corrosion agent, and make certain that the surfaces are completely free from oil and dirt. Fit the bush into the pulley. 2. Oil the screws sparingly and loosely screw them into the tapped holes in the pulley (see Fig. 16). 3. Clean the shaft and fit the pulley and bush onto the shaft as one unit. 4. Tighten the screws alternately until they are all securely tightened. Variable-pitch guide vanes If the fan is equipped with variable-pitch guide vanes at both inlets, check that the guide vanes can be reset from the fully open position (max. air flow) to the required partially closed position (reduced air flow). Resetting is carried out by the control lever being turned by means of an actuator. To avoid damage to the guide-vane linkage, check that the actuator does not attempt to force the guide vanes past the fully open or fully closed position. All pivotal joints of the guide vanes have glass-fibre reinforced nylon bearings which must not be lubricated. Suitable actuators should have a torque of 15 Nm. Fig. 18 Extractor hole Fig. 16 Screw Screw Fig. 17 Fig. 19 Fläkt Woods 8192 GB Specifications are subject to alteration without notice

8 Checks to be made prior to starting the fan that the fan section is connected to the ducting or equipped with necessary EULZ-64 protective screen, Fig. 1, page 1, on the fan inlet and fan outlet. that an authorized electrician has given approval for commissioning the unit. that the fan impeller rotates freely and that no objects which can be drawn in and damage the fan have been left in the installation. Important! If the fans are not operated for more than 3 months before or after installation, the load on the belt drive must be relieved and the fans rotated by hand at regular intervals. If not, the ball bearing may suffer the following damage; see the illustration. Starting the fan The fan must not be started with the damper on the suction or delivery side closed. However, the motor can be briefly energized with the inspection cover open for checking the direction of rotation. Caution! When commissioning a new unit, check the belt tension and adjust, if necessary, after 30 minutes of operation. Belastningss Load-induced damage Storage before installation The storage area must not be exposed to vibrations from the surroundings of a kind which can give bearing damage. If the storage period exceeds 3 months, the belt drive tension should be released and the fans should be rotated by hand at regular intervals. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

9 1 (Pa) 3 MODEL M 700 PA MANOMETER DWYER INSTRUMENTS, INC. MICH. CITY IND U.S.A. EU Air Handling Unit Air flow measurement with q-dysa and analogue flow indicating instrument p Flow sensor q-dysa Filling screw + Pa 1.4 EULF Resetting screw J q = p m /s Level Flow indicating instrument The q-dysa flow sensor is supplied if the EULR fan is ordered with flow sensor (code suffix d = 5, 6). The accuracy of the flow sensor is ±7% of the differential pressure reading provided that the installation and maintenance instructions are observed. The analogue indicator instrument shows the air pressure in m 3 /sec. Installation Vertically mount the instrument on a wall or against a panel on the unit and secure it by means of the screws supplied. The horizontal position of the instrument can be adjusted by means of the built-in level. Filling with manometer liquid Back off the resetting screw completely and then screw it in three full turns. This will enable zero setting adjustment in both directions. Remove the filling screw. Fill the instrument with the manometer liquid supplied, pouring the liquid into the filler hole until the level of liquid reaches the zero setting. Caution! Do not use any type of liquid other than the manometer liquid supplied. Use the resetting screw for fine adjustment of the zero setting. Refit the filling screw and tighten it. If you have filled the instrument with too much manometer liquid and cannot adjust the zero setting to the proper position, insert a pipe cleaner or the like in the filler hole to remove excessive liquid or pour out a slight amount of liquid. Hose connections The 4 mm i.d. hoses supplied should be cut to the appropriate length and should be connected from the nipples on the upper frame member on the inspection side to the nipples on the instrument, plus to plus and minus to minus. Fasten the hoses as appropriate so that they cannot be damaged or kinked. Checks The zero setting of the manometer should be checked at regular intervals. To check the zero setting, remove the hoses connected to the pressure connections of the manometer. Whenever the need arises, use the resetting screw to adjust the zero setting. Top up with manometer liquid, if required. The measurement nozzle should be blown clean with compressed air once or twice a year depending on the quality of the air. This can easily be done by disconnecting the hoses from the instrument and blowing them with compressed air to free the air passages from impurities. Another type of pressure gauge may also be connected for use as an alternative meter or for checking the performance of the flow indicating instrument. In this case, fit T-nipples in the hoses to the indicating instrument and run hoses from them to the pressure gauge. The air flow can be calculated by the expression: q = 1 p m 3 /s k where the value of k is stated on the unit rating plate and p is the measurement pressure in Pa. Temperature correction The flow scale on the indicator instrument and the above flow equation are applicable to air at a temperature of +20 C. At other air temperatures, the flow must be corrected with the formula: q = q 20 (273 + t) 293 m 3 /s where q = the actual flow through the fan, q 20 = the flow reading and t = the present temperature in C. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

10 Air flow measurement with q-dysa and analogue flow indicating instrument EU size F-impeller B-impeller size 1 B-impeller size 2 B-impeller size 3 B-impeller size 1 B-impeller size 2 B-impeller size 3 size 2 normal normal normal reinforced reinforced reinforced K-factor m 3 /s at K-factor m 3 /s at K-factor m 3 /s at K-factor m 3 /s at K-factor m 3 /s at K-factor m 3 /s at K-factor m 3 /s at 500 Pa 500 Pa 500 Pa 500 Pa 500 Pa 500 Pa 500 Pa 11 30,76 0, ,89 1,41 21,34 1,05 16,42 1, ,07 2,22 16,42 1,36 10,72 2,09 8,12 2, ,21 2,72 10,72 2,09 8,12 2,75 6,51 3,43 6,51 3, ,21 2,72 10,72 2,09 8,12 2,75 6,51 3,43 6,51 3, ,07 4,41 6,51 3,43 4,57 4,89 3,90 5,73 6,51 3,43 4,57 4,89 3,90 5, ,61 6,19 4,57 4,89 3,90 5,73 3,03 7,38 4,57 4,89 3,90 5,73 3,03 7, ,61 6,19 3,90 5,73 3,03 7,38 3,90 5,73 3,03 7, ,61 6,19 4,57 4,89 3,90 5,73 3,03 7,38 4,57 4,89 3,90 5,73 3,03 7, ,89 7,74 3,90 5,73 3,03 7,38 2,30 9,72 3,90 5,73 3,03 7,38 2,72 8, ,22 10,1 3,03 7,38 2,30 9,72 1,99 11,24 3,03 7,38 2,72 8,22 2,23 10, ,22 10,07 2,30 9,72 1,99 11,24 2,72 8,22 2,23 10, ,22 10,1 3,03 7,38 2,30 9,72 1,99 11,24 3,03 7,38 2,72 8,22 2,23 10, ,69 13,2 2,30 9,72 1,99 11,24 1,50 14,91 2,72 8,22 2,23 10,03 1,75 12, ,69 13,2 2,30 9,72 1,99 11,24 1,50 14,91 2,72 8,22 2,23 10,03 1,75 12, ,4 16,0 1,99 11,24 1,50 14,91 1,35 16,56 2,23 10,03 1,75 12,78 1,35 16, ,4 16,0 1,99 11,24 1,50 14,91 1,35 16,56 2,23 10,03 1,75 12,78 1,35 16, ,09 20,5 1,50 14,91 1,35 16,56 1,08 20,70 1,75 12,78 1,35 16,56 1,08 20, ,85 26,3 1,35 16,56 1,08 20,70 0,80 27,95 1,35 16,56 1,08 20,70 0,80 27, ,85 26,3 1,35 16,56 1,08 20,70 0,80 27,95 1,35 16,56 1,08 20,70 0,80 27, ,08 20,70 0,80 27,95 0,68 32,88 1,08 20,70 0,80 27,95 0,68 32, ,85 26,3 1,35 16,56 1,08 20,70 0,80 27,95 1,35 16,56 1,08 20,70 0,80 27, ,08 20,70 0,80 27,95 0,68 32,88 1,08 20,70 0,80 27,95 0,68 32, ,80 27,95 0,68 32,88 0,52 43,00 0,80 27,95 0,68 32,88 0,52 43,00 Fläkt Woods 8192 GB Specifications are subject to alteration without notice

11 Fan EUL(B,F) Installation of the frequency converter Warning: Incorrect installation of the frequency converter can damage the bearings in the motor. It is Fläkt Woods' policy to only except claims when the motor and frequency converter have been supplied and installed by us. Damage to the motor will not be accepted when the motor has been connected to the frequency converter by an installation engineer not provided by Fläkt Woods. Frequency converter Connection of the screening conductor shall be made via an EMC approved union in the frequency converter's casing or by using a clamp intended for this purpose. The screen conductor must not be connected to an earth bolt. The frequency converter and the motor must be installed by a qualified electrician with good knowledge of speed regulated, drive system installations (frequency converters) and EMC-safety. The following recommendations should be seen as a supplement to the manufacturer's installation instructions. In those cases where there are differences, the manufacturer's instructions shall take precedence over the following; this is due to the warranty undertaking from the manufacturer. The screen should have 360 contact with the casing Screen Insulating tape General The installation between the motor and the frequency converter should be carried out using screened, unbroken 4- wire cable intended for EMC-installations for motor operations, the screen shall have at least 80% optical density, for example, Nexan s NCY or Ölflex Classic. The screen shall have 360 contact with the casing both in the motor and in the frequency converter to give the maximum contact surface. Safety switches or connection boxes fitted between the frequency converter and motor are not recommended. Motor The cable gland in the motor's outlet box should consist of an EMC approved cable gland, for example, Miltronic SKINTOP MS-SC. The screen conductor may only be connected via EMC unions, not to earth bolts. The screen should have 360 contact with the casing Casing Screen Connection of the screen conductor In those cases the screen conductor must be connected to an earth bolt in the motor or frequency converter, this should be done so that the impedance is as low as possible, in these cases, this conductor is limited in length to 5 times its width. For example, when the screen conductor is 1 cm wide it must not be longer than 5 cm. Insulating tape Diverse Besides this, the following should be observed: type of mains supply. local regulations and provisions. the manufacturer's installation instructions for the frequency converter. Outputs over 22 kw In the event of outputs over 22 kw, a symmetrical screened cable with concentric or in some other way symmetrically designed protective earth conductor should be used, please refer to the installation instructions for the frequency converter for recommendations concerning these installations. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

LQLR Fan. Installation instruction. Outlet: Installation. Inlet:

LQLR Fan. Installation instruction. Outlet: Installation. Inlet: Installation : LQLZ-04 Protective screen LQLZ-03 counterflange LQLZ-01 flexible connection LQLZ-02 connection piece Inlet: Fig. 1 LQLZ-09 damper LQLZ-06 connection piece LQLZ-05 flexible connection LQLZ-07

More information

EUL(B,F) FAN. Fläkt Woods 3178 GB Specifications are subject to alteration without notice

EUL(B,F) FAN. Fläkt Woods 3178 GB Specifications are subject to alteration without notice Page Storage before installation.........2 Before starting................2 Maintenance..................2 Cleaning.....................2 Withdrawing the fan from the unit Applicable to size 11 32 EUL(B,F)

More information

CENTRIFUGAL FANS INSTALLATION AND MAINTENANCE INSTRUCTIONS EQLR CENTRIFUGAL FAN

CENTRIFUGAL FANS INSTALLATION AND MAINTENANCE INSTRUCTIONS EQLR CENTRIFUGAL FAN CENTRIFUGAL FANS INSTALLATION AND MAINTENANCE INSTRUCTIONS EQLR CENTRIFUGAL FAN Size 008-090 CONTENTS PAGE STORAGE BEFORE INSTALLATION...2 INSTALLATION...3 INSTALLATION ALTERNATIVES...3 CONNECTION TO FAN

More information

Instructions for the FMLB, FKLB, FAMB, FAHB (P,R)-1-3 Centrifugal fans

Instructions for the FMLB, FKLB, FAMB, FAHB (P,R)-1-3 Centrifugal fans Instructions for the FMLB, FKLB, FAMB, FAHB (P,R)-1-3 Centrifugal fans 1. GENERAL These instructions, wherever relevant, are applicable to the entire range of Swegon centrifugal fans. The instructions

More information

Rotary heat exchanger EURA, 20 53

Rotary heat exchanger EURA, 20 53 Rotary heat exchanger EURA, 0 5 Fig. Adjustment At a constant speed, check that the rotor is rotating in the right direction. The direction of rotation is indicated on the casing. If the purging sector

More information

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY Jet Fans Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY All Leader Fan products are guaranteed to be free from defects of workmanship or material and to function satisfactorily when properly

More information

SLR / SLR-S/N. Instruction Manual. Walrus America Inc

SLR / SLR-S/N. Instruction Manual. Walrus America Inc SLR / SLR-S/N Instruction Manual Walrus America Inc 1. Installation and Connection 1.1. Pump Installation The pump should be sited in a well ventilated and frost-free position. The distance between pumps-motors

More information

ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers

ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers Plant: Heat exchanger designation: ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers Contents Design, Condition on delivery........................................3 Handling,

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Contents Section 1. General Observations... 2 2. Operation... 4 3. Control During Operation... 5 4. Trouble Shooting... 6 5. Maintenance... 7 Please

More information

AUTOGARD SERIES 820 TORQUE LIMITER Installation and Maintenance Manual DB0009 Issue 11 21 Feb 2017 British Autogard Ltd 2 Wilkinson Rd., Love Lane Industrial Estate, Cirencester, Glos., GL7 1YT UK Tel.

More information

EC MACHINE DIRECTIVE COMPLIANCE DECLARATION

EC MACHINE DIRECTIVE COMPLIANCE DECLARATION 770 EC MACHINE DIRECTIVE COMPLIANCE DECLARATION (DIRECTIVE 89/392 EEC, APPENDIX II, PART B) Manufacturer: FAAC S.p.A. Address: Via Benini, 1 40069 - Zola Predosa BOLOGNA - ITALY Hereby declares that: the

More information

SERIES PC INSTRUCTION AND OPERATION MANUAL

SERIES PC INSTRUCTION AND OPERATION MANUAL MEGGA SERIES PC INSTRUCTION AND OPERATION MANUAL Models PCT and PCF Close-coupled and frame-mounted single-stage horizontal end-suction pumps. WARNING: Read this manual before installing or operating this

More information

500R MIXER SYPHON TYPE WATER TANK WORKSHOP MANUAL

500R MIXER SYPHON TYPE WATER TANK WORKSHOP MANUAL 500R MIXER SYPHON TYPE WATER TANK WORKSHOP MANUAL WINGET LIMITED PO BOX 4 EDGEFOLD INDUSTRIAL ESTATE PLODDER LANE BOLTON LANCS BL4 OLS TEL: ++ 44 (0) 04 854650 FAX: ++ 44 (0) 04 854663 service@winget.co.uk

More information

Rotary heat exchanger EURA split rotor, sizes 50 53

Rotary heat exchanger EURA split rotor, sizes 50 53 Delivery units Sizes 50 53 are always supplied as two delivery units with a split rotor; see Fig. 2. Measurement nipples 1835 Fig. 1 Fig. 2 Dimensions and weights 3348 ø D Service access space D/2 Lifting

More information

ROSTA MOTORBASES ROSTA. Self-Tensioning Motor Mount for Belt Drives. without slippage self-adjusting maintenance-free

ROSTA MOTORBASES ROSTA. Self-Tensioning Motor Mount for Belt Drives. without slippage self-adjusting maintenance-free MOTORBASES Self-Tensioning Motor Mount for Belt Drives without slippage self-adjusting maintenance-free Technology Tensioning Motorbase Type MB for Belt Drives The elastic tensioning motorbase type MB,

More information

1. GENERAL SAFETY INSTRUCTIONS 2. GENERAL SAFETY RULES GENERAL OBSERVATIONS.

1. GENERAL SAFETY INSTRUCTIONS 2. GENERAL SAFETY RULES GENERAL OBSERVATIONS. ENGLISH IMPORTANT: The manual you are reading contains fundamental information regarding the safety measures to be adopted when installing and starting up. It is therefore of utmost importance that both

More information

VEM motors Thurm GmbH

VEM motors Thurm GmbH VEM motors Thurm GmbH Installation, Operating and Maintenance Instructions Single-Phase Squirrel-Cage Induction Motors, Standard Version March 2005 1. General To avoid damage to the motors and equipment

More information

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL FRP BALL VALVES TABLE OF CONTENTS MAINTENANCE AND INSTALLATION INSTRUCTIONS 1. 2. 2.1 2.2 2.3 2.4 GENERAL...Page 1 HANDLING...1 Receiving and Storing...1

More information

Medium and high pressure pumps

Medium and high pressure pumps Screw pumps Medium and high pressure pumps Installation and Start-up Instruction This instruction is valid for all standard high pressure pumps: E4, D4 and D6 Contents Page Pump identification 2 Installation

More information

INSTRUCTION MANUAL MAGNA RAIL

INSTRUCTION MANUAL MAGNA RAIL R ENGLISH NR. 148293 00 INSTRUCTION MANUAL MAGNA RAIL 1999-05-01 List of contents Declaration of conformity, CE Delivery check Mounting instruction (rail, trolley units) Mounting instruction (exhaust pipe,

More information

EUP(A,B,C) Filters. Replacmeent filters. Size (bb) 11, 20, 21, 22, 30, 31, 32, 33, 40, 41, 42, 44, 50, 51, 52, 53

EUP(A,B,C) Filters. Replacmeent filters. Size (bb) 11, 20, 21, 22, 30, 31, 32, 33, 40, 41, 42, 44, 50, 51, 52, 53 As dust gradually accumulates in the filter, the air flow resistance will increase and this will cause the air flow to decrease. The filter must therefore be changed at regular intervals, the frequency

More information

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive Technology ROSTA Tensioning Type MB for Belt Drives The ROSTA elastic tensioning motorbase type MB, with the rubber suspension unit as swivel mounting, compensates continuously for all stretching, hopping,

More information

Shaft Mounted Speed Reducer. Technical Catalogue

Shaft Mounted Speed Reducer. Technical Catalogue Shaft Mounted Speed Reducer Technical Catalogue Where others fit, We perform Contents The Challenge SMSR stands tall amongst the crowd. Packed full of attention to detail, the Challenge SMSR delivers performance

More information

PURA INSTALLATION AND MAINTENANCE INSTRUCTION

PURA INSTALLATION AND MAINTENANCE INSTRUCTION PURA INSTALLATION AND MAINTENANCE INSTRUCTION 2 Installation and maintenance Content Page Delivery Version PURA... 3 Handling, Loads on the Unit, Inspection Facilities... 4 Connection, Checks, Rotor Seals...

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP The purpose of this manual is to aid in the proper installation and operation of the fans.

More information

PART 8 MACHINERY INSTALLATIONS

PART 8 MACHINERY INSTALLATIONS PART 8 MACHINERY INSTALLATIONS PART 8 MACHINERY INSTALLATIONS SECTION SUBJECT 8.1 General 8.2 Auxiliary engines 8.3 Stern gear 8.4 Propeller and nozzles 8.5 Rudders 8.6 Steering gear 8.7 Tables 8.7.1

More information

Instruction and Installation Manual

Instruction and Installation Manual Instruction and Installation Manual ROSTA Tensioner Devices Tensioners Accessories -G -W -R Sprocket wheel N Chain rider P Oil resistant Up to + 120 C Reinforced Sprocket wheel set Chain rider set -I -F

More information

EC MACHINE DIRECTIVE COMPLIANCE DECLARATION

EC MACHINE DIRECTIVE COMPLIANCE DECLARATION EC MACHINE DIRECTIVE COMPLIANCE DECLARATION (DIRECTIVE 89/392 EEC, APPENDIX II, PART B) Manufacturer: FAAC S.p.A. Address: Via Benini, 1 40069 - Zola Predosa BOLOGNA - ITALY Hereby declares that: the 770

More information

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation:

Installation Vertical Pump: Installation 'CM' and 'CDM' Style: Operation: Installation Vertical Pump: Gusher vertical end suction pumps with integral shaft is easily installed and put into service. With the one piece shaft design there is no couplings to align, no shims or no

More information

DB4604 GMR-SD and GMR40-SD Disc Brake Caliper - Spring Applied, Air Released

DB4604 GMR-SD and GMR40-SD Disc Brake Caliper - Spring Applied, Air Released DB464 GMR-SD and GMR4-SD Disc Brake Caliper - Spring Applied, Air Released Nominal dimensions given. For specific dimensions please contact Twiflex Limited. For GMR Mk 2 caliper details see DB 364 Air

More information

Toothed belt axis ELGC-TB-KF. Operating instruction [ ]

Toothed belt axis ELGC-TB-KF. Operating instruction [ ] Toothed belt axis ELGC-TB-KF en Operating instruction 8068220 2017-02 [8068222] Original instructions Identification of hazards and instructions on how to prevent them: Danger Immediate dangers which can

More information

GMR-S and GMR40-S Disc Brake Caliper - Spring Applied, Air Released

GMR-S and GMR40-S Disc Brake Caliper - Spring Applied, Air Released (GMR) 9 (GMR) ø GMR-S and GMR-S Disc Brake Caliper - Spring Applied, Air Released DB Nominal dimensions given. For specific dimensions please contact Twiflex Limited. For GMR Mk caliper details see DB

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Part #469003 Model Vektor -H Installation Operation and Maintenance Manual for Vektor-H Laboratory Exhaust System Receiving Greenheck model Vektor-H fans are thoroughly

More information

Edition Manual Chapter Page Workshop Manual, Stiga Park 5 Belts 11

Edition Manual Chapter Page Workshop Manual, Stiga Park 5 Belts 11 2008-05-19 Workshop Manual, Stiga Park 5 Belts 11 Pro 20 1. Dismantle the belts A and B as described above. 2. Block up the rear frame and remove the right rear wheel. Clean carefully the insex hole in

More information

NAF-Turnex pneumatic actuators NAF /92/94, sizes 0, 1-3 and 4-5 Maintenance instructions and spare parts list

NAF-Turnex pneumatic actuators NAF /92/94, sizes 0, 1-3 and 4-5 Maintenance instructions and spare parts list NAF-Turnex pneumatic actuators NAF 79290/92/94, sizes 0, -3 and 4-5 Maintenance instructions and spare parts list Fi 74.59(3)GB 05.2 Contents General... Maintenance... 2 Dismantling... 2. Checking for

More information

SAI GM Series Piston Hydraulic Motor Crankshaft Design Radial Piston Motors

SAI GM Series Piston Hydraulic Motor Crankshaft Design Radial Piston Motors SAI GM Series Piston Hydraulic Motor Crankshaft Design Radial Piston Motors www.chinawinches.cn (Dimension: inch) Brief Performance Table of Sai GM Series Piston Hydraulic Motor (Full range GM05- GM9 series)

More information

Townsend Bearings. Rosta Tensioner Devices. Revision 1

Townsend Bearings. Rosta Tensioner Devices. Revision 1 Townsend Bearings Rosta Revision 1 Tensioning Technology Chain Tensioning Roller chains are power transmission components with positive transmission which, by virtue of their design are subject, depending

More information

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting READ AND SAVE THESE INSTRUCTIONS INSTALLATION, OPERATING INSTRUCTIONS & PARTS MANUAL Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting Electrical wiring and connections should be done

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Centrimaster, GX Installation and Maintenance Instructions

Centrimaster, GX Installation and Maintenance Instructions Centrimaster, GX Installation and Maintenance Instructions 31.1.2001 Centrimaster, GX Installation General... 2 1. Receiving and inspecting the product... 2 1.1 Inspection... 2 1.2 Data on the rating plate...

More information

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c.

Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c. 24V DC-CW332 DOC531/11 Installation, Operating, Maintenance and Safety Instructions for CW332 Pressurised water system for boats 24 volt d.c. To obtain the best performance from your Pressurised water

More information

MEGADYNEDTM-MICRO INSTRUCTIONSMANUAL

MEGADYNEDTM-MICRO INSTRUCTIONSMANUAL MEGADYNEDTM-MICRO INSTRUCTIONSMANUAL 1 MEGADYNE DTM-MICRO INSTRUCTIONS MANUAL The MEGADYNE DTM - MICRO is used to check the static tension of drive belts by means of frequency measurement. It is fully

More information

D8 - Distributor. D9 - Auxiliary unit belts

D8 - Distributor. D9 - Auxiliary unit belts D8 - Distributor l ubricate Lubricate the distributor shaft sparingly (1-2 drops of oil) D9 - Auxiliary unit belts check/adjust Applies to engines which do not have multi-tooth belts Check belt tension.

More information

Monocellular centrifugal electro-pumps

Monocellular centrifugal electro-pumps Réf. 2100 - O33 / a - 5.95 This manual must be given to the end user LS Monocellular centrifugal electro-pumps Installation and maintenance 1 - GENERAL The LS range of monobloc electro-pump units should

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul

KLINGER Piston Valves KVN DN PN 16 I/III with valve ring KX-GT Modul Page 1 Assembly Instructions and Handling Regulations for KLINGER Piston Valves KVN DN 65 150 PN 16 I/III with valve ring KX-GT Modul DN 125-150 1 Body 2 Bonnet 3 Hand wheel 4 Piston 5 Lantern bush 8 Threaded

More information

Shaft Mounted Speed Reducer Selection

Shaft Mounted Speed Reducer Selection GEARBOX SELECTION PROCEDURE (a) Service Factor From Table 1 select the service factor applicable to the drive. (b) Design Power Multiply the absorbed power (or motor power if absorbed power not known)

More information

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive

ROSTA Tensioning Motorbases Type MB. self-adjusting maintenance-free overload-proof non-slip dampen harmful vibrations extend belt drive 83 Technology ROSTA Tensioning Motorbase Type MB for Belt Drives The ROSTA elastic tensioning motorbase type MB, with the rubber suspension unit as swivel mounting, compensates continuously for all stretching,

More information

The ELM Series Slurry Pump Installation and Operating Manual

The ELM Series Slurry Pump Installation and Operating Manual The ELM Series Slurry Pump Installation and Operating Manual Excellence Pump Industry Co., Ltd. SAFETY INFORMATION The following safety information relating to pump operation and maintenance should be

More information

Instructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: )

Instructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: ) EN Instructions for Fitting, Operating and Maintenance Canopy Door 1 818 012 RE / (St.: 12.2010) 12.2010 ENGLISH Contents 1 Safety Instructions... 3 1.1 Qualified persons... 3 1.2 Symbols and signal words

More information

Pressure Reducing Valve Type 2114/2415

Pressure Reducing Valve Type 2114/2415 Pressure Reducing Valve Type 2114/2415 Fig. 1 Type 2114/2415 1. Design and principle of operation The Type 2114/2415 Pressure Reducing Valve consists of the Type 2114 Valve and the Type 2415 Actuator.

More information

1 Mounting V-belt drive (motor pulley, fly wheel, V-belts and guard)

1 Mounting V-belt drive (motor pulley, fly wheel, V-belts and guard) Mounting V-belt drive (motor pulley, fly wheel, V-belts and guard) General safety instructions, requirements and procedures 1 Mounting V-belt drive (motor pulley, fly wheel, V-belts and guard) 1.1 General

More information

IMPORTANT! READ BEFORE PROCEEDING! PHR Axial Flow Hooded Roof Ventilators

IMPORTANT! READ BEFORE PROCEEDING! PHR Axial Flow Hooded Roof Ventilators PHR Axial Flow Hooded Roof Ventilators OPERATION & MAINTENANCE Revised: 08/24/15 IMPORTANT! READ BEFORE PROCEEDING! The information contained herein is, to the best of our knowledge, accurate and applicable

More information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone. INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is

More information

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS READ AND SAVE THESE INSTRUCTIONS 9668-D Heinrich Hertz Drive, San Diego, CA 92154 PH: 619-946-1224 MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS SHIPPING INSPECTION Romlair Model VBO-HV & VBO fans are

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Removing and installing toothed belt

Removing and installing toothed belt Page 1 of 10 Special tools and workshop equipment required Diesel injection pump locking pin -3359- (2x) Pin wrench -T10020- Crankshaft stop -T10050- for engines with circular crankshaft sprocket Locking

More information

DPL/DPL-AF SERIES PLENUM FANS OPERATION INSTRUCTIONS AND PARTS MANUAL MODELS: DPL/DPL-AF-12, 13, 15, 16, 18, 20, 22, 24, 27, 30, 33, 36 GENERAL SAFETY

DPL/DPL-AF SERIES PLENUM FANS OPERATION INSTRUCTIONS AND PARTS MANUAL MODELS: DPL/DPL-AF-12, 13, 15, 16, 18, 20, 22, 24, 27, 30, 33, 36 GENERAL SAFETY DPL/DPL-AF SERIES PLENUM FANS OPERATION INSTRUCTIONS AND PARTS MANUAL MODELS: DPL/DPL-AF-12, 13, 15, 16, 18, 20, 22, 24, 27, 30, 33, 36 GENERAL SAFETY Rotating parts on fans should not be exposed. Where

More information

Service Handbook HD /97

Service Handbook HD /97 Service Handbook HD 1050 5.905-032 07/97 Foreword HD 1050 Foreword Indispensable prerequisites for the competent execution of service procedures are comprehensive, real-life training workshops for technical

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX: TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie HU SERIES SERVICE MANUAL INTRODUCTION To keep apace of new market

More information

Assembly Instructions and Handling Regulations for KLINGER. Piston Valves KVN DN VI,VIII and Regulating Piston KVRLN DN , PN 40 VI, VIII

Assembly Instructions and Handling Regulations for KLINGER. Piston Valves KVN DN VI,VIII and Regulating Piston KVRLN DN , PN 40 VI, VIII Page 1 Assembly Instructions and Handling Regulations for KLINGER Piston Valves KVN DN 65-200 VI,VIII and Regulating Piston KVRLN DN 65-200, PN 40 VI, VIII pressure released type with valve ring KX-GT

More information

Maintenance Information

Maintenance Information 16573370 Edition 2 February 2014 Air Grinder 99V Series Maintenance Information Save These Instructions Product Safety Information WARNING Failure to observe the following warnings, and to avoid these

More information

Für Modellreihen / for Series / pour les séries

Für Modellreihen / for Series / pour les séries Montage- und Betriebsanleitung Installation and operating instructions Instructions de montage et d utilisation D F Member of JOST-World Für Modellreihen / for Series / pour les séries RO i850 B RO i860

More information

Dr. TRETTER AG. Tolerance Rings. safe cost-effective fast assembly

Dr. TRETTER AG. Tolerance Rings. safe cost-effective fast assembly Dr. TRETTER AG Tolerance Rings safe cost-effective fast assembly Tolerance Rings are corrugated metal strips manufactured of high quality spring steel. Tolerance Rings are a fastening device between two

More information

M Series Condensate Recovery Unit

M Series Condensate Recovery Unit 0898050/3 IM-P089-29 ST Issue 3 M Series Condensate Recovery Unit Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Wiring diagram

More information

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS PACKING, HANDLING, TRANSPORTING AND STORING MOTORS Make sure that the shaft of the motor is not loaded in any way and is protected from knocks. Axial loads or shocks may easily damage the bearings inside

More information

NOTES ON ELEVATOR SYSTEMS

NOTES ON ELEVATOR SYSTEMS 1. Electrohydraulic Lifts 2. Escalators 3. Electrical Requirements 4. Ventilation in Lift Machine Room 5. Lifts for Persons with Limited Mobility Disclaimer 1 Electrohydraulic Lifts Pascal's law of fluid

More information

ABS Dry Installed Waste Water Pumps Series FR

ABS Dry Installed Waste Water Pumps Series FR A Operating Instruction 3 ABS Dry Installed Waste Water Pumps Series FR Shaft Seal Close-coupled and Bearing Assemblies 3R, 4R, 5R, 5F and 6F! Observe for hazardous liquids that there can be liquid left

More information

Preventive maintenance 4

Preventive maintenance 4 00 Series Preventive maintenance Preventive maintenance periods Use the procedures in this chapter to maintain your engine in accordance with the preventive maintenance schedule. Check the periods given

More information

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery Table 6-1. and solutions with pump operations No Fluid Delivery Fluid level in the reservoir is low. Oil intake pipe or inlet filter is plugged. Air leak in the inlet line prevents priming or causes noise

More information

Vacuum Pumps PM80T MORO USA, INC. Use and maintenance manual. ST. LOUIS, MO OFFICE PO Box 632 UNION, MO (866) Fax: (636)

Vacuum Pumps PM80T MORO USA, INC. Use and maintenance manual. ST. LOUIS, MO OFFICE PO Box 632 UNION, MO (866) Fax: (636) MORO USA, INC. ST. LOUIS, MO OFFICE PO Box 632 UNION, MO 63084 (866) 383-6304 Fax: (636) 583-2044 PITTSBURGH, PA OFFICE SALES OFFICE (800) 383-6304 (412) 415-0421 Fax: (412) 415-3154 Email: sales@morousa.com

More information

User Guide IM/TORBAR-EN Rev. D. Averaging pitot tubes

User Guide IM/TORBAR-EN Rev. D. Averaging pitot tubes User Guide IM/TORBAR-EN Rev. D Torbar The Company We are an established world force in the design and manufacture of measurement products for industrial process control, flow measurement, gas and liquid

More information

CL2-B INSTRUCTION BOOKLET CONTENTS

CL2-B INSTRUCTION BOOKLET CONTENTS CONTENTS PAGE SUBJECT 1 Contents 2 Health & Safety Notice 3 Operating instructions 3 Extracting Old Rivets & Hints of Extracting 4 5 Clinching New Rivets & tooling selection 6 Anvil Height Adjustment 7

More information

Sub Section Title Page No.

Sub Section Title Page No. Sub Section Title Page No. 1 Introduction 3 2 Routine Maintenance 3 3 Disassembly 4 3.1 Disassembly of Double Crank Design 4 3.2 Disassembly of Scotch Yoke Design 5 3.3 Disassembly of Actuator Cylinder

More information

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX: TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie SERIES SERVICE MANUAL INTRODUCTION The gasoline engine industry

More information

Breezair TBA 550 Installation Manual

Breezair TBA 550 Installation Manual Breezair TBA 550 Installation Manual Table of Contents ITEM Safety Instructions Specifications Exploded View of the Air Cooler Components of the Air Cooler Dismantling the Air Cooler Installing the Transition

More information

NAF-Duball ball valves Maintenance and installation instructions List of spare parts

NAF-Duball ball valves Maintenance and installation instructions List of spare parts NAF-Duball ball valves Maintenance and installation instructions List of spare parts Fi 41.61(4)GB 08.01 Contents SAFETY General 1 Lifting 2 Receiving inspection 3 Installation 4 Flange gaskets 5 Starting

More information

Mixer Discharge Door Adjustment on models; 30, 42, 54, 81, 108, 135 mixers.

Mixer Discharge Door Adjustment on models; 30, 42, 54, 81, 108, 135 mixers. Knowledge Base Article Type: Instructions Mixer Discharge Door Adjustment on models; 30, 42, 54, 81, 108, 135 mixers. Description: Instructions on How to set-up and adjust the discharge door on Columbia

More information

IMPORTANT! READ BEFORE PROCEEDING! PAF Axial Propeller Fans

IMPORTANT! READ BEFORE PROCEEDING! PAF Axial Propeller Fans PAF Axial Propeller Fans OPERATION & MAINTENANCE Revised: 08/24/15 MODELS PAFM / PAFH MODEL PAFL MODEL PAFC MODEL PAFB MODEL PAFP IMPORTANT! READ BEFORE PROCEEDING! The information contained herein is,

More information

1 Recommended tools. removing - refitting : timing belt INJECTION ES9J4. PAGE 1 - b1eg1bp0 - removing - refitting : timing belt. - Fig.

1 Recommended tools. removing - refitting : timing belt INJECTION ES9J4. PAGE 1 - b1eg1bp0 - removing - refitting : timing belt. - Fig. PAGE 1 - b1eg1bp0 - removing - refitting timing belt removing - refitting timing belt INJECTION ES9J4 1 Recommended tools - Fig. 1 - [ 1 ] camshaft setting pegs (-).0187 B. - Fig. 2 - PAGE 2 - b1eg1bp0

More information

10. Lower Fuselage Assembly Undercarriage

10. Lower Fuselage Assembly Undercarriage 10. Lower Fuselage Assembly Undercarriage Undercarriage 10.27 2 230399 0 Jabiru Undercarriage Configurations There are four combinations of tyres available, utilising two sets of hubs (standard and heavy

More information

ROOF FAN ROOFMASTER STEC

ROOF FAN ROOFMASTER STEC AIR COMFORT AIR MOVEMENT ROOF FANS ROOF FAN ROOFMASTER STEC INSULATED VERSION» TECHNICAL CATALOGUE 2 STEC Roofmaster - Technical Catalogue CONTENTS GENERAL DESCRIPTION Application/specification... 3 Features...

More information

Shaft Mounted Speed Reducers

Shaft Mounted Speed Reducers s Metric Range Features The Challenge SMSR stands tall amongst the crowd. Packed full of attention to detail, the Challenge SMSR delivers performance in the harshest of applications. Shaft mounted drives

More information

[DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary. Document No:

[DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary. Document No: Three-Piece ball valve EA-307 Series PED Category I, II EA-307 User Manual English Version [DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary.

More information

2007 Pontiac G BRAKES Disc Brakes - G6

2007 Pontiac G BRAKES Disc Brakes - G6 REAR DISC BRAKE PADS REPLACEMENT Removal Procedure CAUTION: Refer to Brake Dust Caution. 1. Inspect the fluid level in the brake master cylinder reservoir. 2. If the brake fluid level is midway between

More information

Section 10 Chapter 17

Section 10 Chapter 17 Section 10 Chapter 17 24 Valve, 8.3 Liter Engine Air Intake System Note: All coding used in the 8.3 Liter and 9 Liter engine manuals are Cummins engine codes. These engine codes have no meaning to New

More information

This chapter describes how to perform periodic inspection and maintenance to ensure the long operating life of the chamber.

This chapter describes how to perform periodic inspection and maintenance to ensure the long operating life of the chamber. Basic guide Chapter 5 Inspection and maintenance Air to Air Thermal Shock Chamber Chapter 5 Inspection and maintenance This chapter describes how to perform periodic inspection and maintenance to ensure

More information

AVK SERIES 55 AND 06 GATE VALVES, DN 450/500/600

AVK SERIES 55 AND 06 GATE VALVES, DN 450/500/600 AVK SERIES 55 AND 06 GATE VALVES, DN 450/500/600 1. Introduction The valve has a full and straight bore corresponding to the nominal diameter and can be installed independently of the flow direction. Although

More information

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:

TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX: TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie HS SERIES SERVICE MANUAL INTRODUCTION The demand for a miniature

More information

Series 100 Slam Shut Valve

Series 100 Slam Shut Valve IMP 8775 Series 00 Slam Shut Valve Sizes ", ", 4" Installation & Maintenance Instructions Read carefully and follow all instructions shipped with this regulator. The incorrect installation of this equipment

More information

Removing and installing cylinder head Removing, installing and tensioning toothed belt

Removing and installing cylinder head Removing, installing and tensioning toothed belt Page 1 of 10 Removing and installing cylinder head Removing, installing and tensioning toothed belt Special tools, workshop equipment, test and measuring appliances and auxiliary items required 3359 Locking

More information

WATER TRAP EQAZ-08-01, EQAZ-08-02

WATER TRAP EQAZ-08-01, EQAZ-08-02 8644 GB 2015.09.23 WATER TRAP EQAZ-08-01, EQAZ-08-02» INSTALLATION AND MAINTENANCE EQAZ-08-01 WATER TRAP DESIGNED FOR PRESSURE BELOW ATMOSPHERIC INSTALLATION Air handling units with the following: EQRC

More information

PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user

PV4 - PIV6. Submersible multistage centrifugal electro-pumps. Installation and maintenance. This manual is to be given to the end user Réf. 3483 GB - 4.33/a - 09.2001 This manual is to be given to the end user PV4 - PIV6 Submersible multistage centrifugal Installation and maintenance PV4 - PIV6 1 - GENERAL PV4 and PIV6 series should be

More information

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1

26 - COOLING SYSTEM CONTENTS ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 COOLING SYSTEM FAULTS... 1 26 - COOLING SYSTEM CONTENTS Page LAND ROVER V8 DESCRIPTION AND OPERATION ENGINE COOLING - DESCRIPTION... 3 ENGINE COOLING - OPERATION... 9 FAULT DIAGNOSIS COOLING SYSTEM FAULTS... 1 REPAIR COOLANT - DRAIN

More information

WELDING FUME EXHAUSTERS & ARMS

WELDING FUME EXHAUSTERS & ARMS WELDING FUME EXHAUSTERS & ARMS The Ace 75 Series is our flexible and effective line of welding fume exhausters and extraction arms for shops that elect to exhaust their weld fumes outdoors instead of through

More information

3 Axles and brakes. 3.1 Function and construction of the axles Construction Function

3 Axles and brakes. 3.1 Function and construction of the axles Construction Function 3 Axles and brakes 3.1 Function and construction of the axles 3.1.1 Function Each wheel has an independent suspension system in the axle body (1), so that individual wheel suspension is provided. The swinging

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN Bulletin 62-January-20-09 ROOF UPBLAST & SIDEWALL CENTRIFUGAL FIBERGLASS EXHAUST FAN INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN The M.K. Plastics catalog on the above corrosion resistant

More information

Engineering Data Tensioner Arms idler Sprocket Sets Idler Roller Pulley Sets

Engineering Data Tensioner Arms idler Sprocket Sets Idler Roller Pulley Sets CHAIN & PULLEY TENSIONERS Engineering Data Tensioner Arms idler Sprocket Sets Idler Roller Pulley Sets ENGINEERING DATA TENSIONING TECHNOLOGY Chain & V-Belt Tensioning Roller chains are power transmission

More information

ROSTA Motorbases. Self-tensioning Motor Mounts for all Friction Belt Drives slippage-free belt protecting maintenance-free ROSTA

ROSTA Motorbases. Self-tensioning Motor Mounts for all Friction Belt Drives slippage-free belt protecting maintenance-free ROSTA ROSTA Self-tensioning Motor Mounts for all Friction Belt Drives slippage-free belt protecting maintenance-free ROSTA Customer Benefits of the ROSTA MB 7 Offers short-term slippage by the start-up of large

More information