Architecture - Engineering - Planning

Size: px
Start display at page:

Download "Architecture - Engineering - Planning"

Transcription

1 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Switchboards SPEC. REFERENCE: MNUFCTURER: Eaton Cutler Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: SEE THE TTCHED DOCUMENTS

2 MKC SSOCITES, INC. RCHITECTS - ENGINEERS - PLNNERS 40 West 4th Street Mansfield Ohio SHOP DRWING REVIEW : PROJECT: Westlake New Lee Burneson Middle School JOB NO.: 09-ED1-045C SPECIFICTION : SWITCHBORDS (ONLY) SPECIFICTION NUMBER: MNUFCTURER: Eaton Cutler-Hammer FILE NME: COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: GENERL S: 1. ll lugs shall be listed for aluminum and/or copper conductors. 2. The contractor is responsible to verify lug sizes with conductors used. 3. The contractor shall verify lug locations. 4. Switch arrangement or placement per section is the responsibility of the contractor. 5. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Final quantities shall be the responsibility of the contractor. 7. The SPD device at the switchboard shall be Cat no. SPD400480Y1. 8. Provide arc flash labeling per Spec Section MSB SPECIFIC S: 1. SURGE PROTECTION DEVICE SHLL BE MOUNTED T THE END OF THE SWITCHBORD (SECTION #1) WITH THE FRONT FCING THE WORKING SPCE ND FED FROM 100 MP SWITCH LOCTED IN SECTION #1 WITH NIPPLE BETWEEN. 2. THE GROUND FULT ELECTRIC TRIP UNIT POWER SHLL BE INTERNLLY WIRED, NO EXTERNL POWER REQUIRED. TPDP SPECIFIC S: 1. THE SWITCHBORD MIN SWITCH SHLL BE 600 VOLT RTED ND SHLL BE CLSS J. Page 1 of 1

3 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Panelboards SPEC. REFERENCE: MNUFCTURER: Eaton Cutler Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: SEE THE TTCHED DOCUMENTS

4 MKC SSOCITES, INC. RCHITECTS - ENGINEERS - PLNNERS 40 West 4th Street Mansfield Ohio SHOP DRWING REVIEW : PROJECT: Westlake New Lee Burneson Middle School JOB NO.: 09-ED1-045C SPECIFICTION : PNELBORDS (ONLY) SPECIFICTION NUMBER: MNUFCTURER: Eaton Cutler-Hammer FILE NME: COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: GENERL S: 1. ll lugs shall be UL listed for aluminum conductors for the sizes as specified. 2. The contractor is responsible to verify lug sizes with conductors used. 3. The contractor shall verify lug locations. 4. Breaker arrangement or placement per tub is the responsibility of the contractor. 5. ny multi-section (tub) panelboard may be converted to single tub at the contractors option. 6. ll multi-section panelboards shall have full capacity conductors between each section, verify lugs meet conductor requirements. 7. ll multi-section (tub) panelboards shall have all tubs the same height. 8. Final quantities shall be the responsibility of the contractor. 9. The SPD device for the panelboards shall be Cat no. SPD160208Y Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Provide arc flash labeling per Spec Section PNEL SPECIFIC S: 1. PNEL EP1:. THE (1) 20-2P SHLL BE CHNGED TO 15-2P FOR THE COOLER COND. B. THE 20-1P SHLL BE TOTL QUNTITY OF (40). C. THE (1) 25-2P SHLL REMIN BUT BE USED FOR THE FREEZER COND. D. THE (1) 60-2P SHLL BE REPLCED WITH 15-2P USED FOR THE FREEZER EVP. E. THE 30-1P SHLL BE TOTL QUNTITY OF (5). 2. PNEL KP1:. THE (2) 40-1P SHLL BE CHNGED TO (1) 50-2P FOR EQUIP. #35. B. DD (1) 30-1P SHLL BE USED FOR EQUIP. #34. C. THE (1) 20-2P WITH SHUNT TRIP SHLL BE REPLCED WITH 20-1P WITH SHUNT TRIP USED FOR EQUIP. #22. D. THE 20-1P SHLL BE TOTL QUNTITY OF (31), BOTH SECTIONS. E. THE 15-1P SHLL BE TOTL QUNTITY OF (11), BOTH SECTIONS. F. DD (1) 20-2P SHLL BE USED FOR EQUIP. # PNEL P3:. THE 20-1P SHLL BE TOTL QUNTITY OF (38), BOTH SECTIONS. Page 1 of 2

5 4. PNEL P2:. THE 20-1P SHLL BE TOTL QUNTITY OF (37), BOTH SECTIONS. B. THE 20-1P WITH SHUNT TRIP SHLL BE TOTL QUNTITY OF (13), BOTH SECTIONS. 5. PNEL P1C:. THE 30-2P DESIGNTED FOR SUH-1 SHLL BE CHNGED TO 15-2P. B. THE 40-2P DESIGNTED FOR CU-1 SHLL BE CHNGED TO 50-2P. Page 2 of 2

6 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Surge Protection Devices SPEC. REFERENCE: MNUFCTURER: Eaton Cutler-Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: GENERL S: 1. The SPD device at the switchboard shall be Cat no. SPD400480Y1. 2. The SPD device for the panelboards shall be Cat no. SPD160208Y1. 3. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Provide arc flash labeling per Spec Section

7 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Transformers SPEC. REFERENCE: MNUFCTURER: Eaton Cutler-Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: GENERL S: 1. Transformer T-PDP & T-TPDP shall be mounted exterior, weather shields required. 2. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Provide arc flash labeling per Spec Section

8 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Enclosed Controllers (Starters) SPEC. REFERENCE: MNUFCTURER: Eaton Cutler-Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: 1. Final quantities are the responsibility of the Contractor. 2. ll starters shall include ground kit. 3. Starters for B-1 & B-2 must be NEM size 1 4. Submit manual motor starters for review. 5. Submit manual motor starters with hand-off-auto for review. 6. Submit motor starters switches for review. 7. Submit timer switches for review. 8. HU heat wheel starters, verify quantity. 9. Dock Leveler starter must be NEM size 1, coordinate with equipment for exact control functions required. 10. Submit starters for freezer and cooler condensers and evaporators 11. Provide the properly sized overload for each manual motor starter. 12. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Provide arc flash labeling per Spec Section

9 rchitecture - Engineering - Planning Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio phone phone phone fax fax fax SHOP DRWING REVIEW PROJECT NME: Westlake New Middle School JOB NO: 09-ED1-045C SUBMITTL : Enclosed Switches(Disconnects) SPEC. REFERENCE: MNUFCTURER: Eaton Cutler-Hammer REVIEWED REVISE ND RESUBMIT REVIEWED S NOTED NOT CCEPTED Checking is only for conformance with the design concept of the project and compliance with the information given in the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site. For information that pertains solely to the fabrication processes or to techniques of construction and for coordination of the work of all trades. : BY: TMM COMMENTS: THE FOLLOWING COMMENTS HVE NOT BEEN MRKED ON THE TTCHED SHOP DRWINGS: 1. Final quantities are the responsibility of the Contractor. 2. ll disconnects shall have lock-on provisions. 3. ll disconnects shall have a ground kit. 4. The dishwasher and booster heater disconnects shall be NEM 4X Stainless steel. 5. Provide aux. contact kits on all disconnects as required. 6. Submit disconnects for SUH-1 and CU-1 for review. 7. Disconnects for HWP-1 & HWP-2 shall have class J fuse spacing 8. Nameplate quantity and nomenclature is the responsibility of the contractor and as per Spec Section Provide arc flash labeling per Spec Section

10 Westlake City Schools Submittal Cover Sheet (To be filled out and submitted with each submittal) School Lee Burneson Middle School Contractor: _Turner Logistics_ Date 02/06/12 Item: SWITCHGER & PNEL BORDS Specification Section: _ Sub Specification Section: _262200, , , _ Contractor s Submittal # Revision # 0 Submittal Type PDF Lead Time fter pproval (wks) _10_ Manuf/Supplier: _ETON ELECTRICL _ Intended rea of Use, Drawing # and Detail Reference: Contractor Stamp CM Stamp PED ETON ELECTRICL Mike Mammone 02/06/12 TURNER/RESOURCE Reviewed for general acceptance only. This review does not relieve the Contractor of the responsibility for making the work conform to the requirements of the contract. The Contractor is responsible for all dimensions, correct fabrication and accurate fit with the work of other trades. SUBJECT TO RCHITECT S PL Signed: Date: CM Submittal #: rchitect Stamp Engineer Stamp

11 1422 Euclid venue Suite 1400 Cleveland, OH Telephone (216) Fax (216) To: Dave Conant, Project Engineer Company: Turner Construction ddress: Hilliard Blvd. Westlake, OH Phone: Date: 02/06/12 T R N S M I T T L From: Dale Schmid Re: Middle School Eaton Electrical Submittals The following is included: No. of Drawing No. Dated Description Copies 1 pdf 02/06/12 Switchgear, Panelboard submittal Remarks: 1. For pproval. 2. To be approved for fabrication by no later than 4/01/12. Thank you. Sent for: pproval Correction Files Information Estimate Signature Comment Turner Logistics, LLC

12 Burneson Middle School Submittal for pproval General Order Volume 1 of 1 Equipment: Engineering Services & Systems Switchboards Panelboards Surge Protection Device Dry Type Transformers Enclosed Control (NEM) Safety Switches Date: 01/27/2012 PEPCO ESTLKE OH PO# S TURNER LOGISTICS 2012, ll Rights Reserved

13 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:14:41 Customer Bill of Material 1 ESS Study-BidManager Short-Circuit and Overcurrent Coordination Studies Short circuit and overcurrent coordination studies would be detailed only for the proposed equipment supplied by the sales office and listed in the Bill of Material. Short circuit currents would be calculated and compared to the proposed equipment ratings down to the low voltage panelboards. Overcurrent coordination plots and recommended settings would be provided for the proposed adjustable-trip protective devices. In order to minimize the number of short circuit bus nodes and coordination plots, similar documentation may be used for system redundancy. The accuracy and delivery of the study are greatly dependent upon timely receipt of accurate field information provided by others. Selective Coordination nalysis is NOT included. Selective Coordination nalysis of Elevators, Emergency Systems, Legally Required Standby Systems, and Critical Operations Power Systems per the 2011 NEC requirements (detailed in rticles , , , , and ) is NOT included in the scope of work. PE Review / Stamp will be provided by a registered professional engineer in the state of Ohio. Study Lead Times Lead time for data request = within 2 weeks of receipt of one-line, specifications, detailed bill of material, and vista order paper. Lead time for final study results = 3-4 weeks after all remaining data received, including equipment submittals and answers to data request. Eaton s quotation is based on the specific overcurrent protective device frame sizes shown on the contract drawings unless specifically listed otherwise in our Bill of Material. Where only circuit breaker trip sizes and/or fuse sizes are shown on the contract drawings, Eaton's quotation is based on the minimum frame size breaker or fusible switch which can accommodate those trip sizes/fuse sizes unless specifically listed otherwise in our Bill of Material. Protective devices will have short circuit interrupting ratings as indicated in the contract documents unless specifically listed otherwise in our Bill of Material. Where Selective Coordination requirements are specified in the contract documents and/or are required by the legally adopted version of the National Electrical Code (NEC) or other codes, a short circuit study indicating the fault current at each bus and a selective coordination study is required. If Eaton is to perform the short circuit/coordination study, this will be performed at an appropriate price addition, unless a short circuit/coordination study is already specifically listed in our Bill of Material as included. The study will determine if there are any situations or devices which do not comply with selective coordination requirements of the legally adopted version of the National Electric Code. It is the project design engineer s responsibility to propose changes needed for upgrading of protective device type or frame size to meet Selective Coordination requirements. If desired, at an appropriate price addition, Eaton can assist the design engineer in developing the most economically feasible changes to the design and/or equipment to meet code requirements. These upgraded changes in type or frame size will only be supplied at an appropriate price increase. Notes: 1) Eaton will not be responsible for any costs associated with required additional physical space, additional equipment, or extra installation requirements because of the increased size or required extra equipment.

14 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:14:41 Customer Bill of Material 2) The requirement for mandated selective coordination per NEC may substantially increase the arc-flash energy available at the various pieces of electrical equipment. n rc-flash study to determine the procedures and Personal Protective Equipment required is strongly recommended for personnel safety. can provide the rc-flash study at additional cost. 1 ESS Study-BidManager 1 2 Weeks Lead Time for Data Request Submittal Weeks Lead Time for Study Completion 1 Quoted by Bid Manager 1 PE Review Stamp Required (Ohio) Designations: Study ll orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required, drawings must be returned approved for release within 60 days of mailing. If drawings are not returned accordingly, and/or if shipment is delayed for any reason, the price of the order will increase by 1.0% per month or fraction there of for the time the shipment is delayed.

15 CHESS_ST PREPRED BY ChristopherJCross PED BY JOB NME Burneson Middle School DESIGNTION Study DRWING NEG-LT NUMBER OF 2

16 PREPRED BY ChristopherJCross PED BY JOB NME Burneson Middle School DESIGNTION Study DRWING NEG-LT NUMBER OF 2

17 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:14:49 Customer Bill of Material 1 PRLC Switchboard Pow-R-Line C Switchboard, Front ccess/ Front and Rear lign, Type 1 480Y/277V 3-Phase 4-Wire, 2500 luminum, Minimum Interrupt Rating: 65k, Bus Bracing Rating: 65k 1 Pow-R-Line C 3 Vertical Isol. Barrier (Service Entrance) 1 Service Entrance Label 4 Copper.25 X 2.0 Ground Bus mp L Main Structure 42 Nameplate 1 Bottom Fed Switch 1 Ground fault protection mp L Distribution Structure 3 Gutter Doors Pole Bolted Pressure Switch, Class L fuse clips provided, (fuses provided by others), (7) 3/0-750 kcmil, Mechanical, 2 600/600V 3 Pole Chas. Mtd. FDPW Sw [J], (2) #4-500 kcmil, Mechanical 1 400/600V 3 Pole Chas. Mtd. FDPW Sw [J], (2) 3/0-250 kcmil, Mechanical 2 200/600V 3 Pole Chas. Mtd. FDPB Sw [J], (1) #4-300 kcmil, Mechanical 2 100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical 9 30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical 7 60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical Designations: MSB 1 PRLC Switchboard Pow-R-Line C Switchboard, Front ccess/ Front and Rear lign, Type 1 208Y/120V 3-Phase 4-Wire, 600 luminum, Minimum Interrupt Rating: 35k, Bus Bracing Rating: 65k 1 Pow-R-Line C 2 Neutral Rating - 200% 1 Vertical Isol. Barrier 2 Copper.25 X 2.0 Ground Bus mp L Main Structure 6 Nameplate 1 Bottom Fed Switch mp L Distribution Structure 1 Gutter Doors 1 600/250V Ind. Mtd. Main 3P FDPW Fus. Sw. R-Fuse, (2) #4-500 kcmil, Mechanical, Bottom 3 400/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) kcmil, Mechanical 1 100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical Designations: TPDP

18 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:14:49 Customer Bill of Material 1 PRLC Switchboard Pow-R-Line C Switchboard, Front ccess/ Front and Rear lign, Type 1 208Y/120V 3-Phase 4-Wire, 1200 luminum, Minimum Interrupt Rating: 42k, Bus Bracing Rating: 65k 1 Pow-R-Line C 2 Vertical Isol. Barrier 3 Copper.25 X 2.0 Ground Bus mp L Main Structure 11 Nameplate 1 Bottom Fed Switch mp L Distribution Structure 2 Gutter Doors /250V Ind. Mtd. Main 3P FDPW Fus. Sw. L-Fuse, (4) #4-500 kcmil, Mechanical, Bottom 2 400/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) kcmil, Mechanical 1 100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical 1 60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J], (1) #14-1/0, Mechanical 4 200/600V 3 Pole Chas. Mtd. FDPB Sw [J], (1) #4-300 kcmil, Mechanical Designations: PDP ll orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required, drawings must be returned approved for release within 60 days of mailing. If drawings are not returned accordingly, and/or if shipment is delayed for any reason, the price of the order will increase by 1.0% per month or fraction there of for the time the shipment is delayed.

19 Switchboard General Information Pow-R-Line C -Specifications Quantity: 1 lignment: Front ccess/ Front and Rear lign Service: 480Y/277V 3-Phase 4-Wire Minimum Interrupt Rating: 65 k Bus Specifications Bus mps: 2500 Bus Bracing Rating: 65k Neutral mps: 2500 Bus Material: luminum Heat Test Copper.25 X 2.0 Ground Bus Bolted To Frame, (1) 350 kcmil Ground Lug Incoming Information Incoming Entry: Bottom Incoming Location: Right Incoming Qty & Size: Terminals, Mechanical, (7) 3/0-750 kcmil, Bottom Structure Specifications Service Entrance Enclosure Type: Type 1 Nameplates: Screw On - White with Black letters Enclosure properties Struct # Description/Modifications 1 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) 2 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) Vertical isolating barrier 3 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) Vertical isolating barrier 4 Bottom incoming main device (Incoming Main Device/MLO Section) Vertical isolating barrier PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION MSB DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 5

20 Front View * 10 2 * 3 * 4 * Power Flow Floor Plan See For Floor Plan Detail Top/Bottom Cable Exit See For Floor Plan Detail Top/Bottom Cable Exit See For Floor Plan Detail Top/Bottom Cable Exit See For See For See For Detail Conduit readetail Conduit readetail Conduit rea Total of 4 Structures, Total Width of 153 Inches Total of 4 Structures, Total Weight of 2670 Weight-Lbs. Width-Inches Width-MM Depth-Inches Depth-MM Height-Inches Height-MM Weight-Lbs.(Est.) Weight-Kg.(Est.) PREPRED BY orderentryepod PED BY JOB NME DESIGNTION Burneson Middle School MSB DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 5

21 Switchboard Units Information Str# Unit Description/Modifications Nameplate 1 1 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 HWP-1 HWP-2 2 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 3 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 EF-25 SPRE SPRE DISHWSHER 4 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 HU-6 S. RTU-1 5 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 HU-4 S. HU-5 S. 2 6 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 7 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 8 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 9 Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 1 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 2 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 3 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 4 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 5 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 6 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 TS-1 HU-2 S. CWP-1 SPRE PNEL L3 PNEL HP3 PNEL HP1 PNEL HP2 HU-6R HU-6HW HU-5R HU-5HW HU-4R HU-3HW HU-3S HU-3R HU-2R HU-2HW HU-1S HU-1R PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION MSB DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 5

22 3 7 Feeder Switch - Chassis Mtd-30/30/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 8 Feeder Switch - Chassis Mtd-100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 9 Feeder Switch - Chassis Mtd-100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 10 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil 1 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil 2 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (2) 3/0-250 kcmil 3 Feeder Switch - Chassis Mtd-600/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (2) #4-500 kcmil 4 Feeder Switch - Chassis Mtd-600/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (2) #4-500 kcmil DCK LVLR BTR HTR HPC-1 SPRE TVSS PNEL L2 PNEL L1 PNEL TS-2 XFMR T-TPDP CC-1 XFMR T-PDP 4 Main Switch - Ind Mtd Pole Bolted Pressure Switch, Class L fuse clips provided, (fuses provided by others) Terminals, Mechanical, (7) 3/0-750 kcmil, Bottom MIN SWITCH Ground fault protection (with electric trip switch and test panel) Bottom Fed Switch PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION MSB DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 5

23 PREPRED BY orderentryepod PED BY NEG-LT NUMBER 1 JOB NME DESIGNTION Switchboards Burneson Middle School MSB DRWING Sumter, SC Customer ppr OF 5

24 Switchboard General Information Pow-R-Line C -Specifications Quantity: 1 lignment: Front ccess/ Front and Rear lign Service: 208Y/120V 3-Phase 4-Wire Minimum Interrupt Rating: 35 k Bus Specifications Bus mps: 600 Bus Bracing Rating: 65k Neutral mps: % Rated Neutral Bus Material: luminum Heat Test Copper.25 X 2.0 Ground Bus Bolted To Frame, (1) 350 kcmil Ground Lug Incoming Information Incoming Entry: Bottom Incoming Location: Left Incoming Qty & Size: Terminals, Mechanical, (2) #4-500 kcmil, Bottom Neutral Terminals Double bove Qty. for 200% Rating Structure Specifications Non Service Entrance Enclosure Type: Type 1 Nameplates: Screw On - White with Black letters Enclosure properties Struct # Description/Modifications 1 Bottom incoming main device (Incoming Main Device/MLO Section) Vertical isolating barrier 2 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION TPDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

25 Front View 1 * 2 * Power Flow Floor Plan See For Floor Plan Detail Top/Bottom Cable Exit See For Detail Conduit rea Total of 2 Structures, Total Width of 66 Inches Total of 2 Structures, Total Weight of 925 Weight-Lbs. Width-Inches Width-MM Depth-Inches Depth-MM Height-Inches Height-MM Weight-Lbs.(Est.) Weight-Kg.(Est.) PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION TPDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

26 Switchboard Units Information Str# Unit Description/Modifications Nameplate 1 Main Switch - Ind Mtd-600/250V Ind. Mtd. Main 3P FDPW Fus. Sw. R-Fuse Terminals, Mechanical, (2) #4-500 kcmil, Bottom MIN SWITCH Bottom Fed Switch 2 1 Feeder Switch - Chassis Mtd-100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 CONTRCTOR TO IDE PIN CONNECTOR/REDUCER. 2 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) kcmil 3 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) kcmil 4 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) kcmil T1B SPRE T3 T2 T1 PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION TPDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

27 PREPRED BY orderentryepod PED BY NEG-LT NUMBER 1 JOB NME DESIGNTION Switchboards Burneson Middle School TPDP DRWING Sumter, SC Customer ppr OF 4

28 Switchboard General Information Pow-R-Line C -Specifications Quantity: 1 lignment: Front ccess/ Front and Rear lign Service: 208Y/120V 3-Phase 4-Wire Minimum Interrupt Rating: 42 k Bus Specifications Bus mps: 1200 Bus Bracing Rating: 65k Neutral mps: 1200 Bus Material: luminum Heat Test Copper.25 X 2.0 Ground Bus Bolted To Frame, (1) 350 kcmil Ground Lug Incoming Information Incoming Entry: Bottom Incoming Location: Left Incoming Qty & Size: Terminals, Mechanical, (4) #4-500 kcmil, Bottom Structure Specifications Non Service Entrance Enclosure Type: Type 1 Nameplates: Screw On - White with Black letters Enclosure properties Struct # Description/Modifications 1 Bottom incoming main device (Incoming Main Device/MLO Section) Vertical isolating barrier 2 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) Vertical isolating barrier 3 50x chassis mounted feeders (Feeder Structure) (Hinged Gutter Doors) PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION PDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

29 Front View 1 * 2 * 3 * Power Flow Floor Plan See For Floor Plan Detail Top/Bottom Cable Exit See For Floor Plan Detail Top/Bottom Cable Exit See For See For Detail Conduit readetail Conduit rea Total of 3 Structures, Total Width of 102 Inches Total of 3 Structures, Total Weight of 1390 Weight-Lbs. Width-Inches Width-MM Depth-Inches Depth-MM Height-Inches Height-MM Weight-Lbs.(Est.) Weight-Kg.(Est.) PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION PDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

30 Switchboard Units Information Str# Unit Description/Modifications Nameplate 1 Main Switch - Ind Mtd-1200/250V Ind. Mtd. Main 3P FDPW Fus. Sw. L-Fuse Terminals, Mechanical, (4) #4-500 kcmil, Bottom MIN SWITCH uxiliary switch: N Bottom Fed Switch Feeder Switch - Chassis Mtd-60/60/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 uxiliary switch: N CONTRCTOR TO IDE PIN CONNECTOR/CBLE REDUCERS 2 Feeder Switch - Chassis Mtd-100/100/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) #14-1/0 uxiliary switch: N 3 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) kcmil uxiliary switch: N 4 Feeder Switch - Chassis Mtd-400/600V 3 Pole Chas. Mtd. FDPW Sw [J] Terminals, Mechanical, (1) kcmil uxiliary switch: N 1 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil uxiliary switch: N 2 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil uxiliary switch: N 3 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil uxiliary switch: N 4 Feeder Switch - Chassis Mtd-200/600V 3 Pole Chas. Mtd. FDPB Sw [J] Terminals, Mechanical, (1) #4-300 kcmil uxiliary switch: N CONTRCTOR TO IDE CBLE REDUCER/CONNECTOR. P2B P3B SPRE P1C P1B P1 SPRE KP1 P2 P3 PREPRED BY orderentryepod PED BY JOB NME Burneson Middle School DESIGNTION PDP DRWING Sumter, SC Switchboards Customer ppr. NEG-LT NUMBER OF 4

31 PREPRED BY orderentryepod PED BY NEG-LT NUMBER 1 JOB NME DESIGNTION Switchboards Burneson Middle School PDP DRWING Sumter, SC Customer ppr OF 4

32 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line1a 42 Circuits, 100, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 18k IC,60, 3P QBHW-H Main Breaker[Top Fed], Surface Mounted 1 60, 3P QBHW-H Main Breaker 24 1P QBHW Branch Provision Only 12 20, 1P QBHW Branch Breaker 6 20, 1P QBHW Branch Breaker, w/ Shunt Trip 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2048R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2048S 1 CONTRCTOR TO IDE PIN CONNECTOR/CBLE REDUCER. Designations: P2B 1 Pow-R-Line1a 42 Circuits, 100, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 10k IC,60, 3P BB-H Main Breaker[Top Fed], Surface Mounted 1 60, 3P BB-H Main Breaker 10 20, 1P BB Branch Breaker 2 40, 2P BB Branch Breaker 22 1P BB Branch Provision Only 5 20, 1P BB Branch Breaker, w/ Shunt Trip 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2048R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2048S 1 CONTRCTOR TO IDE PIN CONNECTOR/CBLE REDUCER. Designations: P3B

33 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a 42 Circuits, 100, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 35k IC,100, Main Lugs Only[Top Fed], Surface Mounted 1 100, Main Lugs Only 15 20, 1P GHQ Branch Breaker 1 20, 2P GHB Branch Breaker 1 40, 2P GHB Branch Breaker 2 15, 2P GHB Branch Breaker 1 30, 2P GHB Branch Breaker 17 15, 1P GHQ Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2042R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2042S Designations: P1C 1 Pow-R-Line3a 42 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 50k IC,100, Main Lugs Only[Top Fed], Surface Mounted 1 100, Main Lugs Only 11 20, 1P HFD Branch Breaker 14 1P HFD Branch Provision Only 17 15, 1P HFD Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2060R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2060S Designations: HP1

34 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a 42 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 14k IC,60, 3P GHB Main Breaker[Top Fed], Surface Mounted 1 60, 3P GHB Main Breaker 13 20, 1P GHQ Branch Breaker 18 1P GHQ Branch Provision Only 11 15, 1P GHQ Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2042R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2042S Designations: HP2 1 Pow-R-Line2a 42 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 14k IC,60, 3P GHB Main Breaker[Top Fed], Surface Mounted 1 60, 3P GHB Main Breaker 14 20, 1P GHQ Branch Breaker 18 1P GHQ Branch Provision Only 10 15, 1P GHQ Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2042R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2042S Designations: HP3 1 Pow-R-Line3a 42 Circuits, 250, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 50k IC,250, Main Lugs Only[Top Fed], Surface Mounted 1 250, Main Lugs Only 9 1P HFD Branch Provision Only 33 20, 1P HFD Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2060R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2060S Designations: L1

35 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a 42 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 14k IC,100, 3P GHB Main Breaker[Top Fed], Surface Mounted 1 100, 3P GHB Main Breaker 27 20, 1P GHQ Branch Breaker 9 1P GHQ Branch Provision Only 3 20, 2P GHB Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2042R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2042S Designations: L2 1 Pow-R-Line2a 30 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 14k IC,60, 3P GHB Main Breaker[Top Fed], Surface Mounted 1 60, 3P GHB Main Breaker 16 20, 1P GHQ Branch Breaker 12 1P GHQ Branch Provision Only 1 20, 2P GHB Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2036R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2036S Designations: L3

36 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a Multi-Section Panel:2 Sections, 84 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 35k IC,400, Main Lugs Only[Top Fed], Surface Mounted 2 400, Main Lugs Only 1 400, Through-Feed Lugs 62 20, 1P GHQ Branch Breaker 11 1P GHQ Branch Provision Only 1 20, 2P GHB Branch Breaker 3 15, 1P GHQ Branch Breaker 1 30, 2P GHB Branch Breaker 2 50, 2P GHB Branch Breaker 2 Std. Bolted l Ground Bar (l/cu Cable) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2060R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2060S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: P1B 1 Pow-R-Line1a 42 Circuits, 225, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 22k IC,200, 3P EDB Main Breaker[Top Fed], 225, Through-Feed Lugs, Surface Mounted 1 200, 3P EDB Main Breaker 1 225, Through-Feed Lugs 4 25, 1P QBHW Branch Breaker 8 1P QBHW Branch Provision Only 9 20, 1P QBHW Branch Breaker, w/ Shunt Trip 20 20, 1P QBHW Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2060R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2060S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: P2 (1)

37 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a Multi-Section Panel:2 Sections, 84 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 35k IC,400, Main Lugs Only[Top Fed], Surface Mounted 2 400, Main Lugs Only 1 400, Through-Feed Lugs 6 25, 1P GHB Branch Breaker 6 1P GHQ Branch Provision Only 1 20, 3P GHB Branch Breaker 69 20, 1P GHQ Branch Breaker 2 Std. Bolted l Ground Bar (l/cu Cable) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2060R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2060S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: P1 1 Pow-R-Line1a Multi-Section Panel:2 Sections, 60 Circuits, 225, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 18k IC,150, 3P EDB Main Breaker[Top Fed], Surface Mounted 1 225, Main Lugs Only 1 150, 3P EDB Main Breaker 1 225, Through-Feed Lugs 1 20, 2P QBHW Branch Breaker 4 30, 1P QBHW Branch Breaker 6 1P QBHW Branch Provision Only 3 15, 1P QBHW Branch Breaker 41 20, 1P QBHW Branch Breaker 1 25, 2P QBHW Branch Breaker 1 60, 2P QBHW Branch Breaker 2 Std. Bolted l Ground Bar (l/cu Cable) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2048R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2048S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: EP1

38 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line3a 42 Circuits, 250, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 50k IC,250, Main Lugs Only[Top Fed], Surface Mounted 1 250, Main Lugs Only 3 45, 3P HFD Branch Breaker 9 1P HFD Branch Provision Only 9 20, 1P HFD Branch Breaker 4 15, 3P HFD Branch Breaker 1 70, 3P HFD Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2060R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2060S Designations: EPDP 2 Pow-R-Line1a 30 Circuits, 100, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 10k IC,60, 3P BB-H Main Breaker[Top Fed], Surface Mounted 1 60, 3P BB-H Main Breaker 1 30, 1P BB Branch Breaker 15 1P BB Branch Provision Only 14 20, 1P BB Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2036R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2036S Designations: EP2, EP3 1 Pow-R-Line3a 24 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 35k IC,100, Main Lugs Only[Top Fed], Surface Mounted 1 100, Main Lugs Only 2 60, 3P FD Branch Breaker 6 1P FD Branch Provision Only 12 20, 1P FD Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2048R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2048S Designations: EL1

39 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 2 Pow-R-Line2a 30 Circuits, 100, Fully Rated, 480Y/277V 3Ph 4W, luminum Bus, 14k IC,60, 3P GHB Main Breaker[Top Fed], Surface Mounted 1 60, 3P GHB Main Breaker 15 1P GHQ Branch Provision Only 15 20, 1P GHQ Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2036R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2036S Designations: EL2, EL3 1 Pow-R-Line1a Multi-Section Panel:2 Sections, 84 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 18k IC,250, 3P DK Main Breaker[Top Fed], Surface Mounted, Surge Protective Device, 160 k SPD Series - Standard 1 400, Main Lugs Only 1 250, 3P DK Main Breaker 1 400, Through-Feed Lugs 1 30, 1P QBHW Branch Breaker 21 1P QBHW Branch Provision Only 62 20, 1P QBHW Branch Breaker 1 Surge Protective Device, 160 k SPD Series - Standard 2 Copper Main Bus, 400 mps 2 200% Rated Neutral (800) 2 Insulated / Isolated and Std Cu Ground Bar (Cu Cable Only) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2090R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2090S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: T3

40 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a Multi-Section Panel:2 Sections, 84 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 35k IC,400, Main Lugs Only[Top Fed], Surface Mounted, Surge Protective Device, 160 k SPD Series - Standard 2 400, Main Lugs Only 1 400, Through-Feed Lugs 78 20, 1P GHQ Branch Breaker 4 1P GHQ Branch Provision Only 2 30, 1P GHB Branch Breaker 1 Surge Protective Device, 160 k SPD Series - Standard 2 Copper Main Bus, 400 mps 2 200% Rated Neutral (800) 2 Insulated / Isolated and Std Cu Ground Bar (Cu Cable Only) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2072R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2072S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: T1 1 Pow-R-Line1a Multi-Section Panel:2 Sections, 84 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 18k IC,250, 3P DK Main Breaker[Top Fed], Surface Mounted, Surge Protective Device, 160 k SPD Series - Standard 1 400, Main Lugs Only 1 250, 3P DK Main Breaker 1 400, Through-Feed Lugs 1 30, 1P QBHW Branch Breaker 21 1P QBHW Branch Provision Only 62 20, 1P QBHW Branch Breaker 1 Surge Protective Device, 160 k SPD Series - Standard 2 Copper Main Bus, 400 mps 2 200% Rated Neutral (800) 2 Insulated / Isolated and Std Cu Ground Bar (Cu Cable Only) 2 Panel Nameplate - White with Black Letters - Screw on 2 Circuit Directory - Metal Frame with Plastic Cover 2 Type 1 Enclosure:EZB2090R 2 EZ Trim, Door in Door, Concealed Hardware:EZT2090S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: T2

41 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line2a 42 Circuits, 100, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 35k IC,100, Main Lugs Only[Top Fed], Surface Mounted, Surge Protective Device, 160 k SPD Series - Standard 1 100, Main Lugs Only 12 1P GHQ Branch Provision Only 30 20, 1P GHQ Branch Breaker 1 Surge Protective Device, 160 k SPD Series - Standard 1 Copper Main Bus, 100 mps 1 200% Rated Neutral (225) 1 Insulated / Isolated and Std Cu Ground Bar (Cu Cable Only) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2048R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2048S Designations: T1B 1 Pow-R-Line1a 42 Circuits, 225, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 22k IC,200, 3P EDB Main Breaker[Top Fed], 225, Through-Feed Lugs, Flush Mounted 1 200, 3P EDB Main Breaker 1 225, Through-Feed Lugs 1 20, 1P QBHW Branch Breaker, w/ Shunt Trip 2 40, 1P QBHW Branch Breaker 10 15, 1P QBHW Branch Breaker 7 1P QBHW Branch Provision Only 5 15, 1P QBHW Branch Breaker, w/ Shunt Trip 1 15, 3P QBHW-H Branch Breaker 2 15, 2P QBHW Branch Breaker 1 20, 2P QBHW Branch Breaker, w/ Shunt Trip 7 20, 1P QBHW Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Trim, LT Trim, 304 Brushed Stainless Steel 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Optional F Frame Terminal, (1) #6-300 kcmil 1 Type 1 Enclosure:YS LT Trim, 304 Brushed Stainless Steel:SS304 Trim 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: KP1 (1)

42 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line1a 42 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 18k IC,400, Main Lugs Only[Bottom Fed], Surface Mounted 1 400, Main Lugs Only 1 15, 2P QBHW Branch Breaker 11 15, 1P QBHW Branch Breaker 8 1P QBHW Branch Provision Only 17 20, 1P QBHW Branch Breaker 4 20, 1P QBHW Branch Breaker, w/ Shunt Trip 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2090R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2090S Designations: P3 (2) 1 Pow-R-Line1a 42 Circuits, 400, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 18k IC,200, 3P JD Main Breaker[Top Fed], 400, Through-Feed Lugs, Surface Mounted 1 200, 3P JD Main Breaker 1 400, Through-Feed Lugs 4 25, 1P QBHW Branch Breaker 8 1P QBHW Branch Provision Only 20 20, 1P QBHW Branch Breaker 9 20, 1P QBHW Branch Breaker, w/ Shunt Trip 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:EZB2090R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2090S 1 COMPRESSION LUGS ON THRU FEED LUGS ONLY Designations: P3 (1)

43 ETON Cutler Hammer Michael Mammone Phone: Neg# LT160914Y101 lt# 0005 Job Name: Burneson Middle School 13:15:33 Customer Bill of Material 1 Pow-R-Line1a 42 Circuits, 225, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 22k IC,225, Main Lugs Only[Bottom Fed], Flush Mounted 1 225, Main Lugs Only 1 30, 2P QBHW Branch Breaker 3 15, 1P QBHW Branch Breaker 12 1P QBHW Branch Provision Only 1 20, 2P QBHW Branch Breaker 23 20, 1P QBHW Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Trim, LT Trim, 304 Brushed Stainless Steel 1 Panel Nameplate - White with Black Letters - Screw on 1 Circuit Directory - Metal Frame with Plastic Cover 1 Type 1 Enclosure:YS LT Trim, 304 Brushed Stainless Steel:SS304 Trim Designations: KP1 (2) 1 Pow-R-Line1a 42 Circuits, 225, Fully Rated, 208Y/120V 3Ph 4W, luminum Bus, 22k IC,225, Main Lugs Only[Bottom Fed], Surface Mounted 1 225, Main Lugs Only 5 20, 1P QBHW Branch Breaker, w/ Shunt Trip 1 15, 2P QBHW Branch Breaker 11 1P QBHW Branch Provision Only 8 15, 1P QBHW Branch Breaker 15 20, 1P QBHW Branch Breaker 1 Std. Bolted l Ground Bar (l/cu Cable) 1 Panel Nameplate - White with Black Letters - Screw on 1 Type 1 Enclosure:EZB2060R 1 EZ Trim, Door in Door, Concealed Hardware:EZT2060S Designations: P2 (2) ll orders must be released for manufacture within 90 days of date of order entry. If approval drawings are required, drawings must be returned approved for release within 60 days of mailing. If drawings are not returned accordingly, and/or if shipment is delayed for any reason, the price of the order will increase by 1.0% per month or fraction there of for the time the shipment is delayed.

Detail Bill of Material Page 1 of 2 Project Name: Arc Eng Exposition Negotiation No: LAEC0706X6K1 General Order

Detail Bill of Material Page 1 of 2 Project Name: Arc Eng Exposition Negotiation No: LAEC0706X6K1 General Order Detail Bill of Material Page 1 of 2 Project Name: Negotiation No: LAEC0706X6K1 General Order Alternate No: 0000 No: Item No. Qty Product Description 1 Pow-R-Line C Switchboard, Front Access/ Front and

More information

Submittal Transmittal

Submittal Transmittal Submittal Transmittal Standard St. Joe's - Sonntag Pavillion St. Joseph s Hospital 350 W. Thomas Road Phoenix, AZ 85013 Project # 5690A Tel: Fax: Kitchell Contractors Inc of AZ Date: 9/12/2011 Reference

More information

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description .5 Types PRL1a, 2a, a, E, 4 and Column Modifications s Types PRL1a, 2a, a, E, 4, Column Modifications Selection Guide Modifications Alphabetical Index Modification Item Contents Types PRL1a, 2a, a, E,

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Pow-R-Line 3E Panelboard

Pow-R-Line 3E Panelboard This is a photographic template your photograph should fit precisely within this rectangle. Pow-R-Line 3E Panelboard 2008 Eaton Corporation. All rights reserved. Pow-R-Line 3E Panelboard Design guided

More information

Electrical Notes: For PDC-1 provide a minimum of 6 spare circuits.

Electrical Notes: For PDC-1 provide a minimum of 6 spare circuits. Waynetown Water System Improvements Division A -New Water Treatment Plant Town of Waynetown, IN Submittal Review Sheet Attached is the submittal for the Switchboards and Panelboards for the Waynetown Water

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Panelboard Renewal Parts Supplement

Panelboard Renewal Parts Supplement Panelboard Renewal Parts Supplement Contents Page Page Contents Page PRL 1a and a Neutral Assemblies..................................................... 3 PRL 1a and a Ground Assemblies.......................................................

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

2.7. Panelboards Solar Applications. Contents Description. Product Description. Pow-R-Line C Panelboards

2.7. Panelboards Solar Applications. Contents Description. Product Description. Pow-R-Line C Panelboards Panelboards Solar Applications.7 Contents Description Introduction.............................. Product Selection Guide.................. EZ Box and EZ Trim........................ Type PRL1a...........................

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Fused Coordination Panelboard

Fused Coordination Panelboard Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined

More information

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD BRANCH CIRCUIT PROTECTION FUSED COORDINATION BOARD MERSEN S FUSED COORDINATION BOARD Selective Coordination is required in several locations as defined in the National Electrical Code (NEC). Mersen s Fused

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

PROJECT MANAGEMENT Transmittal No 17D

PROJECT MANAGEMENT Transmittal No 17D GH Phipps Construction Co. 5995 Greenwood Plaza Blvd. Suite 00 Greenwood Village CO 80-470 PROJECT MANAGEMENT Transmittal No 7D5780-00 PROJECT: Thistle-Valmont Square Interior & Exterior Renovation DATE:

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Boxes C " wide, 5 3 4" deep. C " wide, 5 3 4" deep. Branch Breaker Side Gutters. Type Breaker (inches) C1 BL, BLH, HBL C2 BQD 3.

Boxes C  wide, 5 3 4 deep. C  wide, 5 3 4 deep. Branch Breaker Side Gutters. Type Breaker (inches) C1 BL, BLH, HBL C2 BQD 3. Circuit Breaker / Column Type Type C1 240 Volts AC Mains Branch UL Short Circuit Rating 200,000 IR Branch Breaker Symmetrical Interrupting Rating Based on Underwriters Test Procedure Type C2 480Y/277 Volts

More information

Lighting and Power Distribution Panelboards

Lighting and Power Distribution Panelboards EXPLOSIONPROOf Lighting and Power Distribution Panelboards The design offers sufficient gutter space on sides to allow through wiring and easy lug connection. All enclosures are furnished with hinges,

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

Panelboards Circuit Breaker / Lighting and Distribution

Panelboards Circuit Breaker / Lighting and Distribution Circuit Breaker / Lighting and Distribution 480Y/277 Vac Maximum 600Y/ 347 Vac (CSA only) Maximum 400 Ampere Mains 400 Ampere Maximum Branch UL Short Circuit Rating 200,000 A. @ 240 Vac / 100,000 A. @

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com J QMB Panel boards Switchboards 200,000A. short circuit rating QMB Fusible Switches Throughout our complete line of 30-SOOA. ULiisted QMB fusible switches, we've combined timeproven Square D safety switches

More information

Division 1 Explosionproof Panelboards

Division 1 Explosionproof Panelboards Division 1 Explosionproof Panelboards Designed for use in Class 1, Division 1 Zone 1 areas such as petroleum refineries, chemical or petrochemical facilities, the X1Pb panelboards are used to control lighting

More information

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible

More information

Unassembled Pow-R-Stock panelboards EZE Boxes and EZ Trims

Unassembled Pow-R-Stock panelboards EZE Boxes and EZ Trims Unassembled Pow-R-Stock EZE Boxes and EZ Trims Single-Phase, -Wire 10/40 Catalog Number Interiors (Less Main Device) mpere Max. No. of Poles luminum Bus Copper Bus 0 18 PRL110X18 PRL110X18C 0 0 PRL110X0

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

Selection and application guide

Selection and application guide Selection and application guide 30A 400A fusible panelboards Coordination Panelboard www.usa.siemens.com/fusiblepanel Coordination panelboards Table of contents Subject Page Specifications 2-3 Enclosure

More information

Multi-Pak Group Control

Multi-Pak Group Control Multi-Pak Grouping.1 Product....................................... Application.................................... Features Enclosures........................................... V-T-2 V-T-2 V-T-2 Feeder

More information

Quik-Spec Coordination Panelboard A fusible panelboards

Quik-Spec Coordination Panelboard A fusible panelboards Supersedes July 2018 Quik-Spec Coordination Panelboard 30-400 fusible panelboards Contents Description Page Specifications... 2-3 Enclosure types and voltages/systems.... 4 using, main and feed-through

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

SECTION ELECTRIC DISTRIBUTION

SECTION ELECTRIC DISTRIBUTION SECTION 16400 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary General Conditions and other Division

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

3.6. Panelboards and Lighting Control. Contents Description Product Overview... Product Selection Guide... Pow-R-Command 750 Panelboard...

3.6. Panelboards and Lighting Control. Contents Description Product Overview... Product Selection Guide... Pow-R-Command 750 Panelboard... .6 Panelboards and Lighting Control PRC25 Panelboard PRC25 Panelboard Product The PRC25 panelboard is designed to meet the needs for control of lighting and small branch circuits. Used as a standalone

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

X1PB: Explosionproof Panelboards

X1PB: Explosionproof Panelboards X1PB: Explosionproof FEATURES Spring-loaded through the door circuit breaker handles for 1P, 2P, and 3P breakers Padlock provision for breaker handles Copper bus bars Aluminum hinge with stainless steel

More information

Fused Coordination Panelboard

Fused Coordination Panelboard Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined

More information

Quik-Spec Coordination Panelboard A fusible panelboards

Quik-Spec Coordination Panelboard A fusible panelboards USSMNN Supersedes December 2015 SERIES Quik-Spec Coordination Panelboard 30-400 fusible panelboards Contents Description Page Specifications.... 2-3 Enclosure types and voltages/systems.... 4 using, main

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

Application guide. Tmax Link OEM UL 891 Switchboard Program

Application guide. Tmax Link OEM UL 891 Switchboard Program Application guide Tmax Link OEM UL 891 Switchboard Program 04 Tmax Link Overview 04 Standards 04 UL File Extension Process Overview 05 Electrical Data 05 Technical Data 05 Ambient Conditions 08 Circuit

More information

PANELBOARDS C1/C2 SECTION 6

PANELBOARDS C1/C2 SECTION 6 SECTION 6 C1/C2 PANELBOARDS Page General Specifications 6-2 Box Sizing 6-2 Gauge Steel Boxes 6-2 Fronts 6-2 Main Breaker Connectors 6-2 Main Lug Connectors 6-2 Selection 6-3 6-5 Main Lugs Only C1 and C2

More information

PANELBOARDS SECTION 1

PANELBOARDS SECTION 1 SECTION 1 P1 PANELBOARDS Description Page General Information 1-2 Selection and Application 1-2 Application 1-3 1-6 Main Breaker Panel Size Selector 1-3 Main Breaker Selection 1-3 Main Lugs Size Selector

More information

Now - Up To 400A Mains!

Now - Up To 400A Mains! Quik-Spec Family Specification has never been easier or faster for the distribution products you need to achieve selective coordination, and improve electrical system safety and performance Quik-Spec Coordination

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

Quik-Spec Electrical Gear

Quik-Spec Electrical Gear Section Contents Page Quik-Spec Coordination Panel Boards......... 266-267 Quik-Spec Power Module Switches and Panels.. 268-269 Quik-Spec DC Safety Switches.................. 270 Quik-Spec AC Safety Switches..................

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

EOEM panelboard and switchboard (OPS) Program

EOEM panelboard and switchboard (OPS) Program Instructional Leaflet IL02009EN EOEM panelboard and switchboard (OPS) Program OPS Program overview The OPS Program enables EOEMs to purchase panelboard/switchboard chassis, boxes, trims, molded-case circuit

More information

Assembly not available for new installations.

Assembly not available for new installations. Catalog Symbol: EP Voltage Ratings: 120/208V, 120/240V, 277/480V Main Device Type: MLO (200A), Main Circuit Breaker (up to 200A) Enclosure: NEMA 1 Trim: Surface Mount Agency Information: UL 67, UL 50 The

More information

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Table of Contents TPS NQ & AQ Series Overview 2 Switchboard Technical Data 3-5 Panelboard Technical Data 5-11 1 Tier Power

More information

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? White paper Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? Darryl Moser, Business Development Manager, DEM Sales, ABB, Electrification Products Division

More information

AGNES SCOTT OBSERVATORY - SOLAR

AGNES SCOTT OBSERVATORY - SOLAR GNES SCOTT OBSERVTORY - SOLR ELECTRICL NOTES ELECTRICL REQUIREME PV SYSTEM NOTES Roof-Mounted Installation 6kW W N S E MTERILS ND METHODS REVISION NUMBER - FOR CONSTRUCTION REVISION HISTORY DESCRIPTION

More information

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1 GE 8000-Line -1 Mains, coming Lines MAINS GENERAL Main units consist of an externally operable circuit disconnect, either a fusible switch or a circuit breaker. Sizes by ampere rating, short-circuit rating,

More information

Panelboards and Lighting Controls

Panelboards and Lighting Controls Product Guide and Lighting Controls Assembled Unassembled and Lighting Controls and Lighting Control Contents 1.1 Introduction Product Selection... 1-2 1.1 EZ Box and EZ Trim Product Description... 1-4

More information

For Options, Modifications and Accessories, see pages Discount Schedule A6

For Options, Modifications and Accessories, see pages Discount Schedule A6 Main and Feeder Units Bulletin 191F and 191M Outgoing Feeder Lug Compartment (FLUG) and Incoming Main Lug Compartment (MLUG)................................................. The Bulletin 191M and 191F

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

Quik-Spec. Section Contents

Quik-Spec. Section Contents Section Contents Page Quik-Spec Coordination Panel Boards......... 238-239 Quik-Spec Power Module Switches and Panels.. 240-241 Quik-Spec DC Safety Switches.................. 242 Quik-Spec Solar Combiner

More information

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak Powergrid Solution s Metal Enclosed Switchgear has many different customizable options and configurations. Customers

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

6.1. Low Voltage Busway. Low Voltage Busway Pow-R-Way and 100V. Features, Benefits and Functions

6.1. Low Voltage Busway. Low Voltage Busway Pow-R-Way and 100V. Features, Benefits and Functions .1 Features, Benefits and Functions Pow-R-Way III Offers a Full Line of to Meet the Needs of the Global Marketplace Eaton Corporation has combined the requirements of NEMA, UL, CSA and IEC into one design

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3 Introduction P1 Panelboards P1 Feature Overview Key Panelboard Features Lighting and Appliance Applications Power Panelboard Applications Convertible From Top Feed to Bottom Feed and Vice Versa Change

More information

Applying Interrupting Rating: Circuit Breakers

Applying Interrupting Rating: Circuit Breakers Series Rating: Protecting Circuit Breakers Generally, a circuit breaker should not be applied where the available shortcircuit current at its line side terminals exceeds the circuit breaker s interrupting

More information

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA: Supersedes: 160.55-PW4 (1199) FORM 160.55-PW4 (600) PRODUCT DRAWING YORK INTERNATIONAL CORPORATION P.O. Box 1592, YORK, PA 17405 CONTRACTOR ORDER NO. YORK CONTRACT NO. YORK ORDER NO. WIRING DIAGRAM FIELD

More information

Panelboards. Panelboards Contents

Panelboards. Panelboards Contents -1 February 7 Contents Description Page EZ Box and EZ Trim.............................................. -2 Product Selection............................................... -4 Product Description.............................................

More information

Applying Interrupting Rating: Circuit Breakers

Applying Interrupting Rating: Circuit Breakers The professional engineer must be qualified by primarily working in the design or maintenance of electrical installations. Documents on the selection shall be stamped and available to all necessary parties.

More information

American Electric Supply, Inc.

American Electric Supply, Inc. American Electric Supply, Inc. 6 S. Maple Street Date: 0/8/204 Corona, CA 92880 Telephone: 95-80-4665 Email: bmcdonald@amelect.com Fax: 95-552-626 Speedi Version: V 0.6 Valued Customer, Bill of Material

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

GE Energy. GE Panelboards. The right panelboard for any application. imagination at work

GE Energy. GE Panelboards. The right panelboard for any application. imagination at work GE Energy GE Panelboards The right panelboard for any application imagination at work GE Panelboards Right on design, right on manufacture, right on service From design through manufacture and delivery,

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

Quick selector reference guide. Pow-R-Stock panelboards, safety switches, and transformers

Quick selector reference guide. Pow-R-Stock panelboards, safety switches, and transformers uick selector reference guide Pow-R-Stock panelboards, safety switches, and transformers Table of contents Pow-R-Stock panelboards uestions to ask... 5 Catalog numbering... 6 Interiors, EZ boxes, and trims...

More information

4.5. Switchboards. Contents Description Instant Service Switchboards Product Selection...

4.5. Switchboards. Contents Description Instant Service Switchboards Product Selection... .5 Type 1 Indoor Product Description Eaton s Instant are designed as stocked units to provide fast delivery to match the needs of the construction market. Suitable for use as service entrance equipment,

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 16410 Enclosed Switches and Circuit Breakers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

Specification made simple for selective coordination in a compact size

Specification made simple for selective coordination in a compact size Quik-Spec family of circuit protection solutions BUSSMANN Specification made simple for selective coordination in a compact size SERIES The Quik-Spec Coordination Panelboard (QSCP) simplifies selective

More information

Quick Connection Panel (QCP) Installation Guide

Quick Connection Panel (QCP) Installation Guide Quick Connection Panel (QCP) Installation Guide DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read this document first. The installer is responsible for compliance with National Electrical

More information

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

Vintage Westinghouse panelboards

Vintage Westinghouse panelboards Supersedes February 9 PRL1-LX PRL1 / PRL2 PRL CDP, HCDP FDP Contents Description Page Procedure for identifying renewal parts................................................... 2 Distributor ordering instructions.........................................................

More information

Laser Service Factory-assembled Panelboards

Laser Service Factory-assembled Panelboards Factory-assembled Panelboards Price List 1600PL0701 2009 Class 1600 CONTENTS Description............................................. Page Product Overview........................................ Page

More information

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E

100-Ampere Busway. Effective November 2005 New Information. Elbow, Busway and Cable Tap Box. Technical Data TD E 100-Ampere Busway Technical Data TD01701002E Effective November 2005 New Information Elbow, Busway and Cable Tap Box Contents General Information.............................. 2 Connections...............................

More information

type P1 Lighting and Power Distribution Panelboards Overview P1 Panelboards

type P1 Lighting and Power Distribution Panelboards Overview P1 Panelboards type P Lighting and Power Distribution Panelboards Specifications Main Breaker: 400A Maximum Main Lugs only: 400A Maximum Voltages: 480Y/277V AC Maximum 250V DC Maximum 3Ø3W, 3Ø4W, Ø3W, Ø2W General P panelboards

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

CONTRACTOR/CM: DISTRIBUTION PANELBOARDS

CONTRACTOR/CM: DISTRIBUTION PANELBOARDS SUBMITTAL TRANSMITTAL OCPS CLAY SPRINGS ES SUBMITTAL NUMBER: 647-0.00 SUBMITTAL DETAILS: SUBJECT: CONTRACTOR/CM: DISTRIBUTION PANELBOARDS : WILLIAMS COMPANY : BRAD KUBIN 30 SILVER STAR RD. ORLANDO, FL,

More information

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant Applications Protection and control of electrical equipment and circuits such as lighting and heat tracing in hazardous locations or in damp, wet or corrosive conditions. D2P Series designed for use in

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information