1 Sliding doors / fire doors Installation Instructions for SCDmini TSm01.3 Please note that this documents relates to software for sliding doors and requires that program no. 20 is selected. If using UPS emergency power please use program no. 21 / Escape way with UPS program no. 22 SPEED TECH A/S Nybrovej 97. DK2820 Gentofte. Phone: Fax: info@speed-tech.dk
2 Contents: SCDmini TSm01.3 Sliding doors 1 DESCRIPTION SAFETY WARNINGS UNITS USED FOR SLIDING DOORS ELECTRICAL CONNECTIONS CONTROL PANEL CONNECTIONS Safety edge MIG encoder Photocells Fire signal UPS signal Control panel MOTOR AND MAINS POWER CONNECTIONS Connecting mains power Motor Motor brake UPS EMERGENCY POWER EMERGENCY POWERED ESCAPE WAY (UPS) START-UP / SET-UP POWERING UP THE CONTROLLER PARAMETER SETTING Parameter overview Description of parameters CONTROLLER SET-UP FAULT DESCRIPTION ERROR CODES Frequency inverter part Door Controller part Input diagnostic: Relay status: TECHNICAL DATA DECLARATION OF CONFORMITY...18 Ver: Rights to changes reserved
3 1 Description You have chosen a Door controller based on the newest microprocessor technology. It uses PWM signal (Puls With Modulation) for driving the motor with frequency inverter. Opposite normal door controls that uses relays (Motor connected directly to Mains supply), is this Door controller able to control the motor torque and revolutions. Advantages: Soft start and stop of the door. Less mechanical wear Increased lifetime of door. Door moves with optimum speed increased comfort and faster opening. High safety level Meets the current EU standard for doors. The Speed Commander Door mini is produced by the best components and SMT technology that ensures long and faultless operation. 2 Safety warnings A qualified person that has experience with electro mechanical doors, and the EU regulations that belong must only install this control. It is the responsibility of the installer for the CE marking of the door. And informing / advising the end user in how to use the door. This Door control is developed so it complies with the demands of EN regarding electrical controlled gates and doors. All units used must be CE approved so that it is possibly to make a final CE- marking of the complete system. Safety edge must comply with EN and must only be connected to the terminals prepared for this. These inputs are of Safety Class II and are internally supervised for correct function before each run. The controller must be set up so that EN is meet. The control setting must be lock before it is handed over to the end user. (Speed and torque). The cable between the motor and control must be shielded and connected as shown in part about motor connections. Do not mount the controller in direct sunlight; this might cause internal overheating of the controller. Do not make changes or modifications to the controller. This might cause personal damage. Do not work with the door without disconnecting the mains supply first. Terminals might contain high voltages up to 5 min s after disconnecting the mains supply. The door might start without warning therefore it might require a warning light. The controller does not start if the internal +24V power supply is short-circuited. The display stays off. Ver: Rights to changes reserved
4 3 Units used for sliding doors MIG encoder Motor Controller 230V User control Photocell Safety edge Figure 1 (Overview Required units) 4 Electrical Connections Description of control connections: Nr. Text: Function: Type: Signal: Notes: 1 SAFE Safety edge. Selectable function for NO/NC 2 0V (Rear edge in series with front edge) NC or NO < 0,5 0,5-2,5V > 2,5 V NC: Error E09/NO: Activated NC or NO: normal NC: Activated/NO: Error E09 3 REF Not used in this set-up. The reference point is 4 0V found by torque measuring in closed position V Power supply for MIG Brown wire 6 A in MIG A Yellow wire 7 B in MIG B Green wire 8 AUX2 Fire input NC Activate Fire function 9 AUX3 10 0V GND for MIG White wire 11 OPEN Open door with close timer NO 12 CLOSE Close door NO 13 HALF Reduced open door, for personal walk NO through, with timer. 14 FLIP/FLOP Open / Close door with without NO 15 STOP Stops door NC +24V V supply for control inputs. 17 OFF Stops door NC +24V Emergency stop button PHOTO Tx Photocell transmitter (Red) 20 0V Transmitter and receiver s shield is connected D.O.T. Photocells together here. 21 PHOTO Rx Photocell receiver (White) volt supply for e.g. radar 23 0V RL1 Multifunction relay. Function is set by parameter C* NO COM NC Max load: 230 VAC / 1 A 30 VDC / 2 A Ver: Rights to changes reserved
5 4.1 Control panel connections Warning: Do not touch the Electronic components they can be! damaged or destroyed by electrostatic discharge Safety edge Fireequiptment Fire signal T1 R1 Photocells +24V for magnet Magnet for firedoor 8K2 Safety edge Figure 2 (Connecting units) Safety edge MIG encoder Always mount a front safety edge. There must also be a safety edge on the rear side of the door if it is possible to be squeezed on the rear edge. The rear edge is connected in series with the front edge. (Mount an 8K2 Ohm resistor as shown at drawing below). If it is activated when door is closing the door stops and returns to open position. If it is activated when closing the door stops. The display shows E10 when the safety edge is activated. Connect the safety edge to the terminals 1 and 2 as shown at Figure 2 (Connecting units). Remember to mount a 8K2 ohm resistor in the end of the edge. Figure 3 (Front and rear edge in series) Ver: Rights to changes reserved
6 4.1.2 MIG encoder A MIG encoder is a magnetic pulse encoder that divides each motor rotation into a number of positions. These positions are used to control the door positions. When the door powers up it doesn t know where it is so a reference run is needed. The door finds it reference point and set the position counter to 0. See Figure 10 (Door positions). A MIG encoder with a pulse no of 50 gives 200 positions at each rotation. (No of pulses x 4). Use the mounting instruction enclosed to the MIG to install it at the motor. Connect the 4 wires from the encoder as shown in the table below: MIG: Function: SCDmini Terminal: Brown Supply +24V Terminal 5 Yellow A signal Terminal 6 Green B signal Terminal 7 White 0V Terminal Photocells This controller has an integrated photocell module for a transmitter and receiver. There is no need for any external modules. Note: use only recommended photocell types as described in part 7 Technical data. Install the photocells in the in the door frame and mount the wires in the controller (Do not place the wires close to the motor cable to avoid noise and place receiver closest to the controller). If you are using photocells type D.O.T. connection is like this: Transmitter (Red wire + shield) is connected to Terminal 20 / 21. Receiver (White wire + shield) is connected to 20 / 21. See Figure 2 (Connecting units). To adjust the photocells see part 5.3 Control setup Fire signal If the controller is used on a fire door, that must close when a firesignal is activated, then use the input at terminal 8 AUX1. This is a NC signal (Normally: +24 / Activated: 0V). When the input is activated is it no longer possible to operate the door. Then after the timer function 17 times out the relay function for fire doors is activated (Closing the door by releasing the magnet) UPS signal If an emergency power supply is used to power the door in case of fire, connect a +24V volt fire signal to terminal 9 (NC). If the signal is activated (0V) then the door starts to close with Tip frequency. All safety functions are turned off. Only the safety edge is still monitored, the door stops if it is activated and waits for 3 sec. then it tries to close again. The display shows UPS when terminal 9 is active. See section 4.3 for more information. Please note that parameter 8** must be changed from standard value for this function to work Control panel The drawing below shows an example on how to connect the buttons for the user panel. If a box is mounted at both side of the door, connect the emergency stop and the stop circuit in series. The open and close circuit is connected in parallel. See drawing: Ver: Rights to changes reserved
7 Open Stop Close Figure 4 (Control panel) 4.2 Motor and mains power connections Connecting mains power Emergency stop EN418 Connect the mains supply from a CEE wall plug (Placed beside the controller). Connect the cable to the terminals L, N and PE as shown at the drawing below. See part: Technical data for recommended fuses. Connect motor cable to the terminals U, V,W and PE. Connect the shield of the cable to one of the PE terminals (Keep the shield wire as short as possible). Motor Mains Relay 230V - 50Hz Mains Supply Figure 5 (Power terminals at bottom panel) Motor The motor can be connected in two ways depending on witch type of application it has to operate. In both cases is it necessary to use a shielded EMC cable. The shield is connected together with the PE wire to the motor frame (Must be as short as possible). The cable is connected to the controller as shown in Figure 5. Connect the motor in one of the following ways (depending you application): Ver: Rights to changes reserved
8 1. The motor is connected in star if no gearbox is used. See Figure 6 (Star connection). A 6-pole motor (400/690V) is used to obtain more torque. The controllers Voltage / Frequency relation parameter is set to 16,5Hz (This means that the motor gets full voltage at 16,5Hz). This makes is possible to run the door with very low frequency. 2. The motor is connected in delta if a gearbox is used. See Figure 7 (Delta connection). The V/F relation is set to 50 Hz. Figure 6 (Star connection) 400/690V motor Figure 7 (Delta connection) 230/400V motor Always disconnect mains supply before working with the door or controller Motor brake Power relay K0 is set up to control the brake. This is done by setting the parameter B* = 1 (default). Then the relay is activated when output frequency is above 0 Hz. Motor Mains Relay L N Brake 230V Figure 8 (Connecting Motor brake) Ver: Rights to changes reserved
9 4.3 UPS emergency power To use this function it is necessary to select program no. 21. This is done by pressing all 3 control buttons when powering up and keep them pressed until the display shows P. 20. Then select program P. 21 by using the UP/DOWN buttons and store it by pressing the STEP/STORE. The display will now show P. 21 at start-up. If door needs to be closed in case of fire, running on emergency power from an UPS, (Not using mechanical closing) a fire signal is needed at terminal 9. This function is activated when input is 0V.(+24V when not activated). This makes the door close with TIP frequency. All normal safety features is switched off, only safety edge will be monitored. If the safety edge is activated, the door stops and waits for 3 sec then it tries to close again. All open function is blocked when the signal on terminal 9 is active. The controller is not set up for this function as standard. It is necessary to change parameter 8** (Reference function) to 10. This is done by setting J=33 and then set 8**=10 and then set J= Safety edge UPS Control T1 R1 Photocells 8K2 Safety edge MIG encoder 4.4 Emergency powered escape way (UPS) To use this function it is necessary to select program no. 22. This is done by pressing all 3 control buttons when powering up and keep them pressed until the display shows P. 20. Then select program P. 22 by using the UP/DOWN buttons and store it by pressing the STEP/STORE. The display will now show P. 22 at start-up. This function is the opposite of a fire door, it opens the door in case of a fire signal on terminal 9 (0V). This will cause the door to open with dead man speed. It is not possible to close the door as long as the fire signal is active. When the signal is restored (+24V) the door is returned to normal operation. The display shows UPS when the signal is active. Relay function 19 flashes when the UPS signal is active. Please note that run timer is 4 times as long when running in deadman speed. Ver: Rights to changes reserved
10 5 Start-up / Set-up 5.1 Powering up the controller After connecting units as shown in part 4 Electrical Connections, controller is ready to be power up. Turn on the mains supply. The display shows short information about the Type, Power Range, Program no. and Program version. Example: SCD P U.0.15 Witch means this is a SCD controller, of 0,75Kw with program no. 20 Version Parameter setting Now the controller is ready to be operated. Note that this controller contains a lot of settings that gives the user possibility to adjust it to almost any application. See document Standard Installation guide for SCDmini, for a full description of all parameters and functions. It is only possible to change the settings (Parameters) that are shaded after powering up. To gain full control over the parameters, enter an operator code in parameter J (Get this code from your controller supplier). When this code is entered is the controller ready for installation / set-up. If this code is not entered the display will show E13 when trying to install. The 3 buttons to the right of the display carry out the parameter setting. The button STEP/STORE is used for STEP/ STORE stepping up through the parameters and store changed values. The UP and DOWN button is used for changing the actual parameter value. The green display shows the actual parameter, the 3 red digits show the parameter value. To get more parameter numbers, are there a flashing, and a fast flashing parameter no. (Shown in the parameter list as * and **) Note: The display scrolls when displaying large or negative parameter values. UP Figure 9 (Internal user buttons) DOWN Pressing STEP/STORE and keep it pressed inside a parameter makes a jump back to normal readout. Press UP and DOWN for 10 sec to force a reset of the controller (In normal readout) Parameter overview Par: Name: Range: Def: Description: 1 1. Frequency 0,5 150 Hz 15,0 Open speed from P0 P4 (At automatic mode) 2 2. Frequency 0,5 100 Hz 6,0 Close speed from P4 P2 (At automatic mode) 3 3. Frequency 0,5 100 Hz 3,0 2nd Close speed from P2 P0 (Reduced close speed) 4 Timer 1 0,0-999 sec 15,0 Open time (Multifunction timer - Par.7*) 5 Timer 2 0,0 999 sec 3,0 Warning time before automatic closing. (Multifunction timer Par. 8*) J Operation Mode : Deadman mode 2: Set-up / Service mode4: Automatic Mode 0* Position P / Door closed position 1* Position P Distance from P0, where safety edge is disabled. To make sure that the 50 safety edge is not activated when closing door fully against floor. 2* Position P Speed change position, when closing door (Par. 2 -> Par. 3) 3* Position P Reduced opening position e.g. for personal walk through 4* Position P4 0 / Door fully open position 5* Timer 4 0,0 999 sec 0,2 Fire input delay (Multifunction timer - Par. A*) 6* Timer 5 3,0 999 sec 25.0 Travel time limit. 4 time as long at reference run G* TIP frequency 3-25 Hz 4,0 Frequency used at Manual / Deadman run 0** Readout choice Choice of display readout. 1** Error Message 0 or Error code 0 Shows the latest error message. If no error last active input is shown 2** Motor Direction Changes the motor direction without switching motor wires 5** Cycle counter cycle = open and close / in thousands / Showing 1.00 = 1000 cycles D** Slow opening Reduces the open speed to Par. 3 above this position. 0 = deactivated (Note this is a reduced parameter list. See Standard installation guide for SCDmini for complete parameter set.) Only the shaded parameters can be changed without entering a service code Ver: Rights to changes reserved
11 X Not flashing parameters X* Flashing parameter X** Fast flashing parameter Description of parameters Par. 1, 2, 3: Frequencies (Door speed) for automatic mode. Parameter 1 sets the maximum speed for opening the door at automatic mode (P0->P4) Parameter 2 sets the maximum speed for closing the door from P4 to P2. When the door reaches P2 is the speed changed to the one set in Parameter 3. See Figure 10 (Door positions). Par. 4-6: Timer 1-3 This parameter sets the time for the timers 1-3. Set the desired time in seconds. (Min. time is 0,1 sec) Note: The function for the timers is set by parameter 7* - 9*. A timer is disabled if it is set to 0. Par. J: Operation mode The operation modes is described at part 5.3 Control set-up Value: Operation mode: 1 Manual / Deadman mode 2 Installation / Service 3 Not used for sliding doors 4 Automatic mode with electrical test of the safety edge before each closing cycle. Par. 0* - 4*: Door positions Door positions are described at part 5.3 Control set-up. See Figure 10 (Door positions) for more information. Par. 5*: Timer 4 Same as Par Note: The function for timer 4 is set by Par. A*. The timer is disabled if it s set to 0. Par. 0**: Readout choice No. Function: No. Function: 0 Door position [Counter value] 8 Internal temperature - NTC value 1 Motor current [A] 9 Torque measured at open cycle 2 Internal DC link voltage [V] 10 Photocell receiver signal 3 Analogue input terminal 1 [V] Safety edge 11 Cycle counter (No of cycles / 10) 4 Internal +24V supply [V] 5 Analogue input terminal 3 [V] Reference 6 Motor slip [Hz] 12 Shows Open/Closed in display. OPn / CLo When doors moving the internal positions are shown. If a reference run is needed the display shows REF. 7 Motor slip [U/min] 13 As no. 12 but shows the motor current when the door moves. Note: Read out function is a good tool for debugging. E.g. if you have a fault at the safety edge, Set Par. 0** to 3 and set the operation mode to 1 (J=1). Now it s possible to se the internal measured value for the edge. Try activating the edge and see the no. In the display change. Otherwise there might be a problem with the connection. Par. G*: Frequency used at manual or deadman mode. (Reference run). Par. 1**: Last error Shows the last present error code (Remembered at power off). If no error has been present the last activated input is shown. The error code is reset by pressing the UP and DOWN button simultaneously when showing the parameter. Par. 2**: Motor running direction This parameter changes the motor direction without swapping the motor wires. Used when installing if the motor runs in the wrong direction. Par. 5**: Cycle counter Shows the no. Of cycle the doors has preformed. (1 cycle = one opening and one closing) Example: Shows in thousands: = Cycles. The cycle counter is reset by pressing the UP and DOWN simultaneously when showing the parameter. (Only when operator code is set.) Par: D** Slow opening position (In the end of the open cycle) Used if there is a danger for getting squeezed between the door and e.g. a wall when opening. This makes the door move slowly when the set position is reached. The frequency is set to the one in Par. 3 when this position is reached. Ver: Rights to changes reserved
12 5.3 Controller set-up Overview of door positions that is used internal in the controller: Figure 10 (Door positions) P4 P5 P3 P2 P1 P0 Reference position = 0 Parameter J set the actual operation mode. It can be set to the following modes: Value: Operation mode: Description: 1 Manual / Deadman mode Manual operation with low speed. Note that no end points are used. Note: default mode when product is new. 2 Set-up / Service - mode Used when installing door. Installation process for setting door positions. 3 Not used for sliding doors 4 Automatic mode with electrical test of safety edge before each closing. This mode is used after Set-up mode is completed. Then the door runs automatically with the positions set up in Set-up process. It is necessary to set a operator password to access all the parameters after power up. Set necessary parameters before running position set up. Quick setup. (Available on software version >) Setup procedure: 1. First make all electrical connections and power up the controller. Then try the motor direction by using the external membrane switches. (In manual operation mode J=1). Door must open when pressing UP and close when pressing DOWN. If it runs in wrong direction switch over 2 of the motor wires. If display shows E03 let go of the switch and then try again. Encoders counter direction is automatic changed. 2. Set parameter J = 30 (Auto installation mode) and store it with a short press at STEP/STORE. Press one more time at STEP/STORE to start the Setup. Display will show a flashing OPn. 3. Open door till it s open position with the internal UP / DOWN buttons. When position is found, store it with a press at STEP/STORE. 4. Now the display shows a flashing CLo. Close the door till it s closed position using the internal UP / DOWN buttons. When the position is found store it with a press STEP/STORE. Then the door starts to run a reference run to find its reference point. Display shows REF 5. The door is ready to operate when the reference point is found (Automatic mode) Continued Ver: Rights to changes reserved
13 Abort: Error: The automatic installation can be aborted by giving a STOP command. The display will show E15. Make a new installation from point no. 2. If the distance between P0 and P4 is shorter than the length of P1 is the default values for the positions used and the display shows E15. Make a new installation (Goto no. 2) Old installation process: 1. Checklist before running installation: Make sure to select operation mode J = 1 (Manuel mode). Try to move the door with manual run by pressing the UP or DOWN button at the front foil. Or press the STEP/STORE button and keep it pressed, then press the UP or DOWN button. The door should be able to move in the whole travel area without any mechanical problems. Check that the door opens when the UP button is used and closes when the down button is used. If not swap 2 of the motor wires or change the value of parameter 2** (Display shows E02). Note: Do not touch the terminal or wires before 5 min after switching off the mains supply. Check that the counter direction of the encoder. This is done by opening the door manually as in step 1 and 2. When the door opens the counter value in the display should increase. When the door closes it should decrease. If this is not the case swap the encoder A and B signal wires. See part MIG encoder. Adjust the photocells. This is done by setting the display readout 0** = 10. Now the display shows the signal strength. Adjust the photocells to a value as high as possible. It has to be at least 4. When the setting is done set the readout back to 12 (Par. 0** = 12). 2. Position installation / set-up: Set the operation mode to J = 2 (Installation / Service). If the display shows E13 are the parameters locked and you have to enter the operator code in Par. J. See part 5.2 Parameter setting. Press the STEP/STORE button and keep it pressed. Then press the down button shortly (The direction of the reference point This uses a mechanical reference at closed position). If you press at the wrong key the display shows E04. Choose opposite direction. Note: The motor only runs as long as the STEP/STORE key is pressed. When the door reaches its reference point is stops and the STEP/STORE buttons should be released. The display jumps to the parameter flashing 0 (Par. 0*). This is the position for Door Closed P0. See Figure 10 (Door positions). Now move the door to the closed position by using the UP or DOWN button. When the position is found save it with at short press at STEP/STORE. Press the STEP/STORE button shortly to go to the next position 1* (P1). The safety edge is turned off below this position. Note that this position must be set as close as possible to P0 to avoid personal danger. Move the door to the desired position with the UP or DOWN button and store the position with a press at STEP/STORE. Press the STEP/STORE button shortly to go to the next position 2* (P2). This is the position where the door changes speed when closing (Par. 2 -> Par. 3). This gives a steadily closing of the door. Move the door to the desired position with the UP or DOWN position and store it with a press at STEP/STORE. Press the STEP/STORE button shortly to go to the next position 3* (P3). This is the position for reduced opening (P3). This can be used for personal walk through at large doors. Move the door to the desired position and store it with a press at STEP/STORE. If not used just press STEP/STORE Press the STEP/STORE button shortly to go to the next position 4* (P4). This is the position for door fully open. Moved the door to the desired position with the UP or DOWN button. Store the position with a press at STEP/STORE. Ver: Rights to changes reserved
14 The controller now jumps to Par. J Operation mode. Set the operation mode to J = 4 for automatic mode and save it with a pres son STEP/STORE. Now press the STEP/STORE until normal readout is shown. Now the door is ready to Automatic / Normal operation. But first it needs to make a reference run. Giving the controller a standard open or close command does this. Now test the door functions: open, close, safety edge, ect. When this is done reset the controller by pressing the UP and DOWN button for 10 sec in normal readout (Or remove mains supply) This lock up the parameters, so that the user can t make any dangerous changes to the parameters. Then parameters can t be change without first entering the operator code. Ver: Rights to changes reserved
15 6 Fault description 6.1 Error codes Frequency inverter part Display: Problem: UU OU OH OC1 OC2 OC3 OC4 OC5 50,5 Mains voltage too low Mains voltage too high Controller is overheated Current too high. Over 190% Shortly Current too high. 150% in more than 30 sec. Current too high while accelerating. Current too high while DC braking. Peek current too high Solution: Check mains supply. Maybe too high impedance. Controller might be defect. Check mains supply. Deceleration maybe too fast. Use a controller with integrated brake chopper. Check the placement of the controller. Must not be placed in direct sunlight. Controller defect. Mechanical overload Controller or drive might be too small. Acceleration Par. 7 may be too high. Try to decrease the value to solve the problem. Par. H* too high. Decrease the value for Par. H*. Short Circuit in controller. Check motor cables and motor. Controller defect. Display flashes Normal current is more than 100%. Controller power stage is too small Door Controller part Display: Problem: Solution: Operation mode: Mechanical overload Check if door is blocked. Stop and shows error. E01 MIG encoder defect Open or close command resets the error. (Slip too high) Note that a encoder with high pulse count must be used if low frequencies is used. E02 E03 E04 E05 E06 E07 E08 E09 Wrong encoder count direction. Only showed when J=2 No pulses from encoder Only at installation mode J=2 Wrong direction Reference switch Reference switch position Try to decrease Par. C. Motor or encoder needed to be changed. Wrong direction. See parameter 2**. Check the encoder cable or encoder. Wrong direction chosen regarding to reference point. Choose direction of reference point. Press the button in direction of the reference switch. Check the cable for defects. Check if Par. 8** is set correct. Reference switch has moved since last run. Please check mechanical mounting. (Moved more than 15 x Par. D). Wrong function NO/NC regarding to placement. Mechanical overload or Par. B set too low Increase time for travel time in Timer 5 (Par. 6*) Travel time limit exceeded Safety edge test failed Safety edge test failed. Check connections. (Check Par. 7** to see if correct function is chosen) Safety edge connection fault Check safety resistors and connections. *Deadman mode with error code in display *Deadman run with error code in display (Only when J=2) Stop with error code *Deadman mode with error code in display * Deadman mode with error code in display Open or close command *Deadman mode when closing and normal open speed. Reset controller. * Deadman mode with error code in display Ver: Rights to changes reserved
16 E10 E12 E13 SCDmini TSm01.3 Sliding doors Safety edge activated If error comes unexpected check connection and try New command to adjust position in Par. 1*. Torque limit The load while opening was too high. New command Parameters locked The operator code has not been entered. Parameters locked. Enter operator code in Par. J Note: It is not possible to reset all errors with a new OPEN / CLOSE command. It is necessary to reset the controller if a critical error is present. This is done by pressing the UP and DOWN button until the display turns off.! *Warning: There is no endpoint / safety edge supervision when controller run is deadman mode. The operator must supervise the door movement Input diagnostic: Use the display readout below to detect fault reason. If an input is activated for more than 1 sec a message is shown in the display. Displ. Input: Terminal: Fault: J 11 Open NO Terminal no: 11 - Normally: 0V Button or cable to this input J 12 J 13 J 14 J 15 J 17 J 19 J 21 REF ABL Close NO Terminal no: 12 - Normally: 0V Button or cable to this input ½ Open NO Terminal no: 13 - Normally: 0V Button or cable to this input Flip/Flop NO Terminal no: 14 - Normally: 0V Button or cable to this input Stop NC Terminal no: 15 - Normally: 24V Button or cable to this input OFF NC Terminal no: 17 - Normally: 24V Button or cable to this input Photocell transmitter Terminal no: 19 Photocell receiver Terminal no: 21 Reference run needed Set an OPEN/CLOSE command to start a reference run. Receiver can t see transmitter Broken cables. If photocell is not used connect transmitter to receiver. Mains power interrupted Fire signal activated NC Terminal nr. 8 Normally 24V Check external fire signal UPS UPS - Power NC Terminal nr. 9 Normally 24V UPS emergency power input active. Check external equipment. FAN Fan not connected Plug for fan Below buttons Plug or Fan defective Relay status: The segments in the green display is used for relay status in normal readout (Not showing a parameter) Green dot. Powerrelay K0 activated Upper left green segment. K1 activated Ver: Rights to changes reserved
17 7 Technical data Door controller: Type: Max motorpower (kw) Output current Mains supply Output voltage Fuse (Max) SCDmini 750 0,75 3 x 4A 1 x 230V/50-60Hz 3 x 0-230V 13A SCDmini x 7A 1 x 230V/50-60Hz 3 x 0-230V 16A Integrated 24V supply: Start-up current max 500mA Continuous: 250mA / 6W MIG encoder: Supply voltage Output signal Signal levels Max output frequency VDC 2 channel A,B with 90 phase shift Uhigh > 6 V / Ulow < 1.5 V 20 khz at max rotation speed MIG og motor: Type Name: Pulse count: Motor size: Type no: MIG Size: 80 0,75KW 6 poles 400/690V T80 CB6 B14 400/690 0,75KW MIG Size: 90 1,5KW 6 poles 400/690V T90 LB6 B14 400/690 1,5KW Please note that it is recommended to use MIG encoders with high pulse count when no gearbox is used. (50 pulses pr. Rev). Photocell: Function: Type no.: Range: Transmitter DOT.T15 (Dansk Opto Teknik) Receiver DOT.R15 RFC (Dansk Opto Teknik) Max. 10 meters Safety edge: Supplier: Gelbau Type No: Terminated with 8K2 Ohm resistor Mounting: Controller must be placed in surroundings where temperature is between 0 and 40 degrees. Do not mount the controller in direct sunlight. 163,5 mm +40 C 0 C 163,5 mm Ver: Rights to changes reserved
18 8 Declaration of Conformity A EC Declaration of Conformity Manufacturer: Speed-Tech A/S Address: Nybrovej 97 DK-2820 Gentofte Phone: Fax: Herewith declares that: Electronic door control unit, type: SCD750mini, SCD1500mini, SCD And Is in conformity witch the provisions of the Council Directive 89/336/EEC of 3 May 1989 on the Approximation of the laws of the Member States relating to electromagnetic compatibility (EMC) Is in conformity witch the provisions of the Council Directive 73/23/EEC of 19 February 1973 on the harmonization of the laws of Member States relating to electrical equipment designed for use within certain voltage limits, latest change in 93/68 /EEC. And furthermore declares that the following (parts/clauses of) harmonized standards have been applied: EN :2005 EN :2002 EN :2002 Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods. Electromagnetic compatibility (EMC) - Part 6-3: Generic standards Emission standard for residential, commercial and light-industrial environments. Electromagnetic compatibility (EMC) - Part 6-2: Generic standards Immunity for industrial environments EN :2003 Industrial, commercial and garage doors and gates - Product standard Part 1: Products without fire resistance or smoke control characteristics EN 12445:2001 EN 12453:2001 Industrial, commercial and garage doors and gates - Safety in use of power operated doors - Test methods Industrial, commercial and garage doors and gates - Safety in use of power operated doors - Requirements EN :2003 Household and similar electrical appliances - Safety - Part 2-103: Particular requirements for drives for gates, doors and windows Name: René Jørgensen, Engineering Manager Date: Gentofte d. 14 Oktober 2005 Signature: Ver: Rights to changes reserved
19 B EC Declaration of Conformity for Components Directive, 98/37/EC, Annex II, B Manufacturer: Speed-Tech A/S Address: Nybrovej 97 DK-2820 Gentofte, Denmark Phone: Fax: Herewith declares that Electronic door control unit, type: - SCD750mini, SCD1500mini, SCD Is intended to be incorporated into a door system to constitute machinery covered by Directive 98/37/EC - Does therefore not in every respect comply with the provisions of this directive And that the following (parts/clauses of) harmonized standards have been applied: EN 954-1:1999 Safety of machinery - Safety-related parts of control systems Part 1: General principles for design.kategori 2 EN 418:1994 EN 1037:1998 Safety of machinery - Emergency stop equipment, functional aspects - Principles for design. Safety of machinery - Prevention of unexpected start-up And futhermore declares that it is not allowed to put the control unit into service until the hole door-system into which it is to be incorporated or of which it is to be a component has been found and declared to be in conformity with the provisions of Directive 98/37/EC and with national implementing legislation i.e. as a whole, including the machinery referred to in this declaration. Name: René Jørgensen, Engineering Manager Date: Gentofte d. 14 Oktober 2005 Signature: Ver: Rights to changes reserved
MS-1 SPEED COMMANDER DOOR CONTROL INSTALLATION MANUAL. issue 1
CONTENTS 2 INTRODUCTION 3 MODEL IDENTIFICATION 4 1PH INTERNAL PANEL LAYOUT 5 3PH INTERNAL PANEL LAYOUT 6 BASIC WIRING & INSTALLATION PROCEDURE 8 LIMIT SWITCHES AND ENCODERS 9 PARAMETER SETTING 10 SAFETY
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationElectrical operating instructions
en Electrical operating instructions Door control panel TS 958 Software 1.0 - (Design and functions subject to change) 51171324 - c 03.2007 OPERATING INSTRUCTIONS Page SAFETY DIRECTIONS...4 INSTALLATION
More informationc-go 24V/6A 24V/8A 24V/12A
c-go 24V/6A 24V/8A 24V/12A Battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Quick start guide... 4 4. Operation... 4 5. Problem solving... 6 6. Specifications...
More informationOPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets
Art. nr. 40200261 OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets WHISPERPOWER BV Kelvinlaan 82 9207 JB Drachten Netherlands Tel.: +31-512-571550 Fax.: +31-512-571599
More informationTTT802 Gearshift Controller, Part # R1N-S (Standard), -P (Paddleshift)
First, Sign and Date Bln 2009-03-9 Updated, Sign and Date Bln 200-04-29 (0) User Manual TTT802 Gearshift Controller Firmware for R--N-2- TTT802 Gearshift Controller, Part # 2-620-9-RN-S (Standard), -P
More informationHIB Enclosed Inverter User Guide
HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit
More informationECONOMISER SERIES E2T USER MANUAL
TURBO S.R.L. Electronic Control Systems for Dust Collectors e-mail: info@turbocontrols.it web: www.turbocontrols.it TEL. ++39 (0)362 574024 FAX ++39 (0)362 574092 ECONOMISER SERIES E2T USER MANUAL 24/06/2014
More informationCS300FU SYSTEM. Pro-Line OPERATING INSTRUCTION
CS300FU OPERATING INSTRUCTION Pro-Line EN 1. Contents 1. Contents 2 2. Information in this document 2 3. General safety instructions 3 4. Overview of products 4 5. Frequency Converter 6 6. Initial Operation
More informationCONTROL UNIT BIOS2. Manual for installation. Programmable Control board for wings gates.
Programmable Control board for wings gates www.remotecontrolgates.co.uk Manual for installation Compatible from firmware version BIOS2BT02 CONTROL UNIT BIOS2 1. Introduzione The control unit BIOS2 is particularly
More informationElectrical operating instructions
en Electrical operating instructions Door control panel TS 961 Software 2.6 (Design and functions subject to change) 51171292 - f 02.2013 OPERATING INSTRUCTIONS Page SAFETY DIRECTIONS...4 INSTALLATION
More informationDYNEO Synchronous motors with permanent magnets-drive Commissioning
Synchronous motors with permanent magnets-drive NOTE LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments.
More informationINSTRUCTION INVERTER COMPACT FOR SLIDING GATES /R0 10/11/2017
INSTRUCTI INVERTER COMPACT FOR SLIDING GATES 6-1622616 /R0 10/11/2017 2 / 20 3 / 20 1. INTRO The control unit INVERTER COMPACT is integrated in the motor KALOS XL. It is a device suitable for operating
More informationIntelli-Feed Controller User s Manual Intelli-Feed Digital Tachometer and Hourmeter
Intelli-Feed Controller User s Manual Intelli-Feed Digital Tachometer and Hourmeter Part #: 9047 Table of Contents: Table of Contents 2 Intelli-Feed TM User Interface 3 Equipment Diagnostic Indicators
More informationOperating Instructions for Roll-Up Door Operators / MDF
Operating Instructions for Roll-Up Door Operators / MDF GB Roll-Up Door Operator / MDF / Rev. 0.0 1 1. Contents 3. General safety instructions 1. Contents 2 2. Key to symbols 2 3. General safety instructions
More informationEC DECLARATION OF CONFORMITY
EC DECLARATION OF CONFORMITY Manufacturer : Address: Declares that: FAAC S.p.A. Via Benini, 1-40069 Zola Predosa BOLOGNA - ITALY 844 T control board, conforms to the essential safety requirements of the
More informationGate & Door Controller with LCD and Intelligent Technology
2nd Edition Gate & Door Controller with LCD and Intelligent Technology 24Sv1 and 12Sv1 Motor Controllers Setup and Technical information for single motor controller for gates & doors Includes latest Intelligent
More informationDoor Control Panel TS 960. instructions. (Design and functions subject to change) /
Electrical operating Operating instructions Door Control Panel TS 960 GB (Design and functions subject to change) 51171098 / 10.2002 OPERATING INSTRUCTIONS PAGE SAFETY DIRECTIONS...4 FUNCTION OVERVIEW...6
More informationDKG-114 MANUAL AND REMOTE START UNIT
DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More informationOperating Instructions for Control CS 300
Operating Instructions for Control CS 00 GB CS 00 Gate Controls / Rev.A 5.5 . Contents. General safety instructions. Contents. Key to symbols. General safety instructions 4. Overview of products 5. Initial
More informationMANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax Article no. F21009201 IBC control Made in Sweden TABLE OF CONTENTS Installation instructions 2 Mounting 2 Safety instructions 3 Manufacturer's
More informationOperating Instructions for Control CS 300
Operating Instructions for Control CS 00 GB CS 00 Gate Controls / Rev. 5.5 . Contents. General safety instructions. Contents. Key to symbols. General safety instructions 4. Overview of products 5. Initial
More informationParker AC10 Frequency Inverter (to 22kW) Easy Start Guide
Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide CAUTION: 1)Do not re-set while the motor is rotating 2)Perform parts replacement after discharge is finished 3)Do not connect output terminals
More informationInstallation & instruction manual
Installation & instruction manual KPC-200 KPC-100 strip cutter Continence of this manual. Manufacturers declaration Page 3 Safety instructions.. Page 4 Installations guide.. Page 5 Electrical installation..
More informationUSER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT
Quadri di Manovra per Ascensori Lifts Control Panels PELAZZA PEPPINO S.r.l. 20063 CERNUSCO SUL NAVIGLIO (MI) ITALY Via Ponchielli, 6/8 Tel. 02/92.31.694 Fax 02/92.42.706 Tel. 02/92.42.706 Web Site: www.pelazza.com
More informationElectrical operating instructions
en Electrical operating instructions Door control panel TS 981 FT Software 2.1 - (Design and functions subject to change) 51171393 - f 06.2014 OPERATING INSTRUCTIONS Page SAFETY DIRECTIONS...4 INSTALLATION
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationMerih DDCA60 Operation and User Manual I Merih Asansör A.Ş.
1. WARNINGS! CAUTION This manual contains user guidelines for Merih DDCA60 hardware version v1.05 and software version v1.03. This document will be updated with differences result from version differences.
More information1. WARNINGS CAUTION BEFORE FIRST USE GENERAL NOTE. Merih DDCA60 Operation and User Manual I Merih Asansör A.Ş.
1. WARNINGS! CAUTION This manual contains user guidelines for Merih DDCA60 hardware version v1.05 and software version v1.03. This document will be updated with differences result from version differences.
More informationTECHNICAL MANUAL AND ELECTRONICAL MODULE REGULATION VVVF-4 +
TECHNICAL MANUAL AND ELECTRONICAL MODULE REGULATION VVVF-4 + 8 CABIN DOORS DESCRIPTION OF SWITCHES The unit may be programmed using the DIL switches on the front of the unit. If any change is made to any
More informationQuick Start Guide of CV50- ControlVIT Series
❶ Safety precautions Do not refit the inverter unauthorizedly; otherwise fire, electric shock or other injury may occur. Please install the inverter on fire-retardant material and keep the inverter away
More informationDocumentation. RM-BV4 Micro DP. Filter control
Documentation RM-BV4 Micro DP Filter control Contents 1 Safety instructions... 3 2 Device description... 3 3 Installation... 4 4 Installation... 5 4.1 Connection of the differential pressure measuring
More informationCompact Heat Meters. Features. -A Pulsed output. -B M-Bus output. Accessories. UK Sales Tel: International Tel:
Compact Heat Meters Features Compact design Simple operation Pulsed output Measures heating or cooling Specification Product Codes Water Meter Temp. range 10 to 90 C Nominal pressure 16bar Installation
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationTROUBLESHOOTING TP. Index
TROUBLESHOOTING TP Index E1 POWER CUT DETECTED... 2 E2 LOCK ERROR... 3 E3 DRAINAGE FAILURE / WATER IN TUB... 6 E4 MAXIMUM WATER LEVEL REACHED... 6 E5 FAULT WATER INLET... 6 E6 HEATING FAULT... 6 E7 MAXIMUM
More informationContinental Hydraulics Installation Manual CEM-AA-A
Continental Hydraulics Installation Manual CEM-AA-A Description: This power amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to proportional
More informationElectrical Operating Instructions
Electrical Operating Instructions Door Control Panel TS 958 Software 1.2 - (Design and functions subject to change) 51171324 - f 01.2010 Northern Sales & Distribution Centre The Door Centre, Discovery
More informationCHAPTER 7 ERROR MESSAGE AND TROUBLESHOOTING
CHAPTER ERROR MESSAGE AND TROUBLESHOOTING VFD-V Series The AC drive has a comprehensive fault diagnostic system that includes various alarms and fault messages such as over-voltage, low-voltage and over-current.
More informationMulti-Mover Charger for model L25
Multi-Mover Charger for model L25 Important safety instruction. Keep these instructions. This manual contains important instructions for the safety of the user and the operation of the device. 1. SYMBOLS
More informationUniversal Wireless Dashboard Y-Dash + Android App Y-Dash GT. User Manual Firmware version 1.6 Software version 2.28 Hardware version 1.
Universal Wireless Dashboard + Android App GT User Manual Firmware version 1.6 Software version 2.28 Hardware version 1.3 Page 2 is an electronic microprocessor based device that collects analog and digital
More informationEC DECLARATION OF CONFORMITY
A100 EC DECLARATION OF CONFORMITY (DIRECTIVE 2006/42/EC) Manufacturer: Address: Declares that: FAAC S.p.A. Via Benini, 1-40069 Zola Predosa BOLOGNA - ITALY A100 COMPACT automation is built to be incorporated
More informationM u l t i P o w e r. CM MultiPower. Installation and Operating Manual
M u l t i P o w e r CM MultiPower Installation and Operating Manual Index 1. Introduction of the 4HS submersible pumps range... 3 2. Safety Instructions... 4 3. CM MP installation... 5 3.1 Electric wiring...
More informationc-go 12V/10A 12V/20A Power supply and battery charger Instruction manual
c-go 12V/10A 12V/20A Power supply and battery charger GB Instruction manual 1 Index 1. Product description... 2 2. Safety advices... 3 3. Mounting and installation... 4 4. Operation... 5 5. Problem solving...
More informationV200 USER MANUAL SWING GATE OPENER. 100kg 1.5m. 100kg 1.5m
V200 USER MANUAL SWING GATE OPENER 100kg 1.m 100kg 1.m Content Important Safety Advice... Content of the Kit... Connection Diagram... Installation Guide... Actuator... Control box... AC cable wiring...
More informationSMS PRODUCT CATALOGUE
SMS PRODUCT CATALOGUE CONTENTS 1 TAKEDO 3VF-NXP - LIFT INVERTER Page 3 2 TAKEDO 3VF-V20 - OPEN LOOP LIFT INVERTER Page 6 3 TAKEDO ENERGY - DYNAMIC BRAKING REGENERATIVE UNIT Page 7 4 HYDROVERT VVVF FOR
More informationMagnetek DSD 412 Drive
DRIVE STARTUP MANUAL Magnetek DSD 412 Drive Induction Motor Installation www.smartrise.us 2601 Fair Oaks Blvd., Sacramento, CA 95864 916.457.5129 Magnetek DSD 412 Drive EQUIPMENT/SETTINGS VERIFICATION
More informationCENTROIDTM. AC Brushless Drive. Product Spec Sheet
4 Axis, up to 2 KW motors Brake Output for each axis Overtemp and Overcurrent Protection All-software Configuration Self-cooled Fiber Optic Control CENTROIDTM AC Brushless Drive Product Spec Sheet AC Brushless
More informationPKS-FD Servo System
PKS-FD123-01 Servo System FEATURES 24-70VDC of 0.32 Nm Power Ratings up to 100 Watts 2,500 PPR Incremental Encoder Maximum Speed of 6500 RPM IP65 for Body, IP54 Shaft Seal Brake Option Available Position,
More informationHGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology
HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951
More informationIBC control. MicroMax MANUAL. With adjustable boost function and threshold value. Since Set of EMC-glands as an option
Made in Since 1983 S w e d e n MANUAL Set of EMC-glands as an option CONTROL UNIT FOR ROTARY HEAT EXCHANGER MicroMax Article no. F21009301 With adjustable boost function and threshold value IBC control
More informationAutomatic Sliding Door Retrofit Drive Assembly. Installation Manual DoorControlsUSA.com
Automatic Sliding Door Retrofit Drive Assembly Installation Manual 800-437-3667 DoorControlsUSA.com TABLE OF CONTENTS pg. 1. COMPONENTS 2 2. HEADER PREPARATION 2 3. DOOR PREPARATION 2 4. MOTOR AND CONTROLLER
More informationMANUAL. MiniMax V / VK
MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MiniMax V / VK Revised 2014-10-07 Version 1.3.1 F21037901GB Declaration of Manufacturer The manufacturer s assurance of the agreement of the product with
More informationElectrical Operating Instructions
Electrical Operating Instructions Door Control Panel TS 970 Software 4.5 - (Design and functions subject to change) 51171271 - i 01.2012 Northern Sales & Distribution Centre The Door Centre, Discovery
More informationKNC-PKS-FD S-AAK-DKH
KNC-PKS-FD123-02 - Servo System FEATURES 24-70VDC of 90 oz-in Power Ratings up to 200 Watts 2,500 PPR Incremental Encoder Maximum Speed of 6000 RPM IP65 for Body, IP54 Shaft Seal Brake Option Available
More informationEDG6000 Electronic Digital Governor
INTRODUCTION GAC s digital governor is designed to regulate engine speed on diesel and gaseous fueled engines. When paired with a GAC actuator the EDG is a suitable upgrade for any mechanical governor
More informationFLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER
FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when
More information224-EN WIRELESS CONTROLLER INSTALLATION & INTERFACE GUIDE. Guide No. 224-EN USING AS REPLACEMENT CONTROLLER
INSTALLATION & INTERFACE GUIDE USING AS REPLACEMENT CONTROLLER Confirm software version on existing controllers See Parameter 80 If Parameter 80 is 18 or lower change Parameter 54 to 1 Guide No. Contents
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More informationOpen Chassis Star-Delta Starter User Guide
Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...
More informationINTELLIGENT FLANGE STRÖTER. Magnetic pulse generator
INTELLIGENT FLANGE STRÖTER agnetic pulse generator Incremental magnetic pulse generator addons to drive systems is now possible in an easy and economical way both in new and existing installations. The
More informationINSTALLATION GUIDE Table of Contents
CT-3100 Automatic transmission remote engine starter systems. What s included..2 INSTALLATION GUIDE Table of Contents Door lock toggle mode..... 4 Notice...2 Installation points to remember. 2 Features..2
More informationSYSDrive Frequency Inverter
SYSDrive Frequency Inverter T V/f control T PID control T Standard LED, optional LCD operator T Fieldbus options: DeviceNet T 7 configurable digital inputs T 3 configurable digital outputs T Low audible
More informationAssembly and Operating Instructions
BECK-O-TRONIC 6 Version: Centronic en Assembly and Operating Instructions Door control unit Important information for: Fitters / Electricians / Users Please forward accordingly! These instructions must
More informationPCT-3001 plus. Display LCD
PCT3 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS DESCRIPTION Pressure controller for refrigeration systems capable to control suction (compressors) and discharge (fans) pressures. It is possible
More informationInstallation, Operation and Maintenance Manual
Document 47681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
More informationNortoft Electronic A/S, Sejrupvej 38, DK 7323 Give. Program Rain User Manual
Nortoft Electronic A/S, Sejrupvej 38, DK 7323 Give. www.nortoftelectronic.com Program Rain 10-12 Features: Speed regulation Pre- and post-irrigation 4 different speeds Clock Start time is adjustable Stop
More informationOPERATING INSTRUCTIONS FOR SLIDING DOOR RETROFIT CONTROLLER DC-02
OPERATING INSTRUCTIONS FOR SLIDING DOOR RETROFIT CONTROLLER DC-02 1. INTRODUCTION 2. SAFETY INSTRUCTIONS 3. SPECIFICATION 4. OPERATING INSTRUCTIONS AND CONTROL FUNCTIONS 5. SET UP PROCEDURE 6. CONNECTIONS
More informationDatasheet PDCSY-MW-CHM. Technical Overview. Features. Product warranty and total quality commitment. General Information.
Datasheet Compact Heat Meters Technical Overview Heat energy is calculated by using a matched pair of high accuracy sensors to measure the difference between the forward and flow temperatures. The amount
More informationDigital Diesel Control Remote control panel for GENVERTER GV4 and GV7i
OPERATING MANUAL Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i Art. nr. 40200801 WHISPER POWER BV ENGLISH: PAGE 1 Kelvinlaan 82 9207 JB Drachten NEDERLANDS: PAGINA 41 Netherlands
More informationMitsubishi. VFD Manuals
Mitsubishi VFD Manuals Mitsubishi D700 VFD Installation Mitsubishi FR-D700 VFD User Manual Mitsubishi D700 Parallel Braking Resistors VFD Wiring Diagram - Apollo Mitsubishi VFD to Interpreter Mitsubishi
More informationInstallation, Operation and Maintenance Manual
Document 473681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,
More informationUSER GUIDE Digital Thermostat GUIDE D UTILISATION Thermostat digital Bedienungsanleitung Termostato digital 50-72
BT D-01 1 2 USER GUIDE GB Digital Thermostat 4-25 GUIDE D UTILISATION F Thermostat digital 26-49 Bedienungsanleitung D Termostato digital 50-72 GUÍA DE USUARIO ES Termostato digital 74-97 GUIA DO UTILIZADOR
More informationKelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.
Kelly HSR Opto-Isolated Series Motor Controller with Regen User s Manual HSR72601 HSR72801 HSR12401 HSR12601 HSR12901 HSR14301 HSR14501 HSR14701 Rev.3.3 Dec. 2011 Contents Chapter 1 Introduction... 2 1.1
More informationRoll Up Door Operator
INSTRUCTIONS & OWNERS MANUAL Roll Up Door Operator 2 INDEX Preparation before installation 4. Terms and definitions 5. Pictures & names of parts 6. Mounting the weight bar 7. Installing the operator 7.
More informationDC-Motor Controller. User Manual
Jægergårdsgade 152/05A DK-8000 Aarhus C DENMARK WWW.WAHLBERG.DK Forside DC-Motor Controller User Manual Firmware V4.00 Product content 1 Controller box - for controlling a DC-motor. 1 PowerCON TRUE1 female
More information2-PHASE STEPPING MOTOR DRIVER FE Z5 DISPENSE
2-PHASE STEPPING MOTOR DRIVER FE Z5 DISPENSE For Diaphragm Dosing Pumps FEM 1.02_.55 / FEM 1.09_.55 Controller board package, without pump: ID 160536 Operating and Installation Manual It is important to
More informationHGM1750 Genset Security Module USER MANUAL Smartgen Technology
HGM1750 Genset Security Module USER MANUAL Smartgen Technology CONTENT 1. SUMMARY... 4 2. PERFORMANCE AND CHARACTERISTICS... 5 3. SPECIFICATION... 7 4. OPERATION... 8 5. PROTECTION... 9 6. PARAMETER RANGE
More informationSliding Gate Operator User's Manual
Sliding Gate Operator User's Manual SL600AC. Products introduction Please read the instructions carefully before proceeding. MCU is supplied to control the gate operator. Keypad / single button interface.
More informationFunctions and Displays
Functions and Displays No. 4125 (12V/220V only - Euro-Connector) No. 4127 (12V/220V only - GB-Connector) No. 4129 (12V/110V only US/Japan-Connector) Dear Customer, thank you for purchasing this LRP product.
More informationOvervoltage Suppression F7 Drive Software Technical Manual
Overvoltage Suppression F7 Drive Software Technical Manual Software Number: VSF11015X, Drive Models: CIMR-F7UXXXXXX-062, CIMR-F7U40750F-145. Document Number: TM.F7SW.062, Date: 09/17/2010, Rev: 10-09 This
More informationSPEEDRIVE INSTRUCTIONS MANUAL
EN SPEEDRIVE INSTRUCTIONS MANUAL Safety warning. The following symbols shown beside a paragraph represent danger warnings associated to the failure to comply with the corresponding instructions. DANGER!
More informationDC POWER SUPPLY ALIMENTATION C.C.
DC POWER SUPPLY ALIMENTATION C.C. ISO-TECH IPS 303A 201-3424 ISO-TECH IPS 601A 201-3446 SAFETY TERMS AND SYMBOLS These terms may appear in this manual or on the product: WARNING. Warning statements identify
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More information1 EASY COMMISSIONING GUIDE FRONIUS PV-SYSTEM CONTROLLER
1 EASY COMMISSIONING GUIDE FRONIUS PV-SYSTEM CONTROLLER Reading this document does not substitute for user s reference to CIRCUTOR CDP-DUO user-guide. 1.1 Scope Using Fronius grid-tie inverters in remote
More informationInstruction of Solar Charge Controller. User s Manual
Instruction of Solar Charge Controller User s Manual 12V/24V 30A Dear Users: Thank you for selecting our product. Please read this manual carefully before you use this product. 0 The controller is for
More informationRM B. Features. Drive Model Number Scheme. A RM6 Product Series
Features RM6 series are suitable for constant and variable torque loads (mixer, conveyor, fan, pump, etc.) Overload capacity with 150% drive s rated output current for 1 min can sustain heavy load conditions
More informationOperator systems for garage doors Comfort 260, 270, 280 speed
GB Operating instructions Last updated: 02.2014 Operator systems for garage doors Comfort 260, 270, 280 speed Table of Contents 1. General safety instructions...3 1.1 Intended use...3 1.2 Target group...3
More informationPowerView PV380-R2 Mechanical Configuration
PowerView PV380-R2 Mechanical Configuration Operations Manual *Products covered in this document comply with European Council electromagnetic compatibility directive 2004/108/EC and electrical safety directive
More informationDKG-317 MANUAL AND REMOTE START UNIT
Tel: +54-11-4629-600 Fax:+54-11-4627-3500 http://www.cramelectro.com DKG-317 MANUAL AND REMOTE START UNIT FEATURES Manual starting and stopping Engine control Generator protection Built in alarms and warnings
More informationSliding Gate Operator User's Manual
Sliding Gate Operator User's Manual PY800AC/PY00AC. Products introduction Please read the instructions carefully before proceeding. MCU is supplied to control the gate operator. Keypad / single button
More informationInstallation, Operation and Maintenance Manual
Document 473681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,
More informationExplanation 1 Input External Switch 2 Input Hipot Safety Switch
on the 1100H+ The 1100H+ has capability, which allows you to set up the tester to control external devices with tester functions. You can also use an input on the tester to start a test. For example, the
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationPorte 150 Users Manual Swing Gate Opener 24V DC
Porte 150 Users Manual Swing Gate Opener 24V DC for residential use only Signal Light Push-button Control Box 14 Contents 1. Important Safety Information 2. Product Description and Application 2.1 Application
More informationTECHNICAL CATALOG NEPTIS INVERS/INVERS-B ELECTRO-MECHANICAL OPERATOR FOR AUTOMATIC SWING DOORS, WITH SINGLE/DOUBLE LEAF
NEPTIS INVERS/INVERS-B ELECTRO-MECHANICAL OPERATOR FOR AUTOMATIC SWING DOORS, WITH SINGLE/DOUBLE LEAF FOR SAFETY EXITS IN SMOKE EXHAUSTION SYSTEMS TECHNICAL CATALOG Automatic Door Solutions NEPTIS INVERS/INVERS-B
More informationDevices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB
Kelly KEB Brushless Motor Controller User s Manual Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 KEB EB72 72331 KEB72450 KEB EB72 72451 KEB72600 KEB
More informationABB component drives ACS150, 0.5 to 5 Hp
ABB component drives ACS150, 0.5 to 5 Hp Technical Catalog BUSINESS PROFILE INDUSTRIES PRODUCTS APPLICATIONS EXPERTISE PARTNERS SERVICES Contents Choice 1: Simply contact your local ABB drives sales office
More informationGLM SERIES CONTROL Users Manual Rev:
GLM SERIES CONTROL Users Manual Rev: 808062 Connecting Power Page 2 Motor Terminal Wiring Diagrams Page 3 Getting Started / Setup Page 4 1. Obstruction Detection Devices Page 4 2. Checking Power and Direction
More information