Galaxy PW kva. Installation manual. MGE UPS SYSTEMS D E V I P R O W E P O L E I B U P T E R R N T N I E U T H

Size: px
Start display at page:

Download "Galaxy PW kva. Installation manual. MGE UPS SYSTEMS D E V I P R O W E P O L E I B U P T E R R N T N I E U T H"

Transcription

1 M UPS SYSTMS alaxy PW 0-00 kv Installation manual R P R O V I R P O W L I R R U P T N T N I U T H -5083XU/H -

2 XU/H

3 ontents haracteristics eneral characteristics of alaxy PW UPSs... 4 UPS cubicles... 5 mpty battery cubicles... 5 lectrical parameters for selecting protective devices... 5 Normal source... 5 ypass source... 6 Recommended protection... 7 Protection upstream of alaxy PW... 7 Protection downstream of alaxy PW... 7 lectrical parameters for determining cable cross-sections... 7 Installation Positioning the cubicles... 9 loor load... 9 ubicle layout on a false floor or a normal floor... 9 Power-circuit wiring diagrams... 0 onnection of power circuits... UPS cubicle... attery cubicle... 5 onnection through the top... 6 xternal bypass cubicle 50 kv... 7 xternal bypass cubicle 360 kv... 8 xternal bypass cubicle 600 kv... 9 onnection of the hot-swap option... 0 alaxy PW cubicle with a built-in harmonic filter... 0 alaxy PW cubicle with a built-in bypass source isolation transformer... 0 ypass source isolation transformer in an auxiliary cubicle... THM filter... onnection of "Media ontacts " standard auxiliary circuits... 3 onnection to battery circuit breaker "Q"... 3 mergency power off... 3 onnections between cubicles (parallel-connected configurations)... 4 onnections between POZ boards... 4 onnections between MISI boards... 4 onnections between UPS cubicles and the external bypass... 5 Installation of communications options... 5 Installation of boards... 5 Passage of wires... 5 onnection of the battery "Temperature Monitor"... 6 onnections... 6 Installation of the "Temperature Monitor" in an M UPS SYSTMS empty battery cubicle... 7 "Temperature Monitor" installation in a battery room... 7 Link to an IM S/400 computer... 8 onnections... 8 onfiguration of the S/ onnection of the L indications unit (optional)... 9 inal installation steps... 9 ll products in the alaxy PW range are protected by patents. They implement original technology not available to competitors of M UPS SYSTMS. To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by M UPS SYSTMS. This document may be copied only with the written consent of M UPS SYSTMS. uthorised copies must be marked "alaxy PW installation Manual, N 5083XU" XU/H - 3

4 haracteristics eneral characteristics of alaxy PW UPSs UPS power rating in kv Normal input number of conductors 3 phases rated voltage and tolerances 380 V or 400 V or 45 V ± 0% (adjustable to ± 5%) rated frequency and tolerances 50 Hz or 60 Hz / ± 0% THI with THM filter < 4% power factor with THM filter up to 0,96 ypass input number of conductors 3 phases + neutral rated voltage and tolerances 380 V or 400 V or 45 V / ± 0% rated frequency and tolerances 50 Hz or 60 Hz / ± 0% Load number of conductors 3 phases + neutral Ph/Ph voltages 380 V or 400 V or 45 V (according to setting) Ph/N voltages 0 V or 30 V or 40 V (according to setting) voltage fluctuations ± % adjustable frequency and tolerances (on battery power) 50 Hz or 60 Hz ± 0,05 Hz synchronisation with bypass ± 0,5 Hz (adjustable from ± 0,5 Hz to ± Hz) voltage variation for 0 to 00% load step change ± % ((with battery) permissible overloads 50% for minute, 5% for 0 minutes Isc Ph/Ph (% of I rated) Isc Ph/N (% of I rated) THU Ph/Ph and Ph/N for linear load <,5% Ph/Ph, < % Ph/N THU Ph/Ph and Ph/N for non-linear load < % Ph/Ph, < 3% Ph/N (at 80% of Pn) () attery standard battery type gas-recombination sealed lead-acid battery UPS characteristics active power (kw) efficiency at 50% load (%) (values ± %) efficiency at 00% load (%) (values ± %) heat losses () in KW in cal./s storage temperature range -5 to +70 operating temperature range 0 to 35 (40 for 8 hours) relative humidity 95% maximum maximum operating altitude without derating < 000 meters noise level (d) dimensions (mm) width depth 85 height 400 or 900 ± ± 0 weight (kg) (3) recommended upstream earth-fault protection standards design I 46 product NV 5009 safety I 950, NV 5009 protection I 5 (cubicles 400 mm high = IP, cubicles 900 mm high = IP 0) electromagnetic compatibility I 6040, NV 5009 (): s per standards NV / I (): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system. (3): Not including any built-in options, such as harmonic filters or a bypass -source isolation transformer XU/H

5 haracteristics (cont.) UPS cubicles the cubicles are cooled by forced ventilation. The air enters via the doors and grids at the bottom and is discharged through the back, or through the roof for the 900 mm high cubicles (except the 60 and 00 kv units from which the air is discharged through the roof only, which means the cubicles can be positioned against the back wall). connections are made through the bottom. onnections through the top are available on option for all 900 mm high cubicles (except the 60 and 00 kv units). the connection cables may be run in three ways: in a trench running under the cubicles, under a false floor, on the floor under the cubicles, in the free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation; the cables for connections between: the battery and UPS cubicles (power and control cables); the bypass -source transformer in an auxiliary cubicle and the UPS cubicle can be supplied on option. Layout must comply with figures 5, 6 and 7. The other power cables for connections between cubicles are not supplied. only the wires for the intercubicle control connections between parallelconnected UPS units are supplied; the cubicle doors are secured by SOUTHO locks (key H75). mpty battery cubicles haracteristics of empty battery cubicles ubicle width ubicle height ubicle depth Maximum weight () in mm in mm in mm in kg ± ± ± ± () the indicated weights are for the empty cubicles, without the batteries because the total battery weight may vary widely. lectrical parameters for selecting protective devices Normal source The parameters given in the table opposite can be used to determine the required rating of the upstream protective circuit breaker on the normal input for one single-ups or parallel- UPS unit, a unit in economy mode or a frequency converter. Important: It is essential to choose the type of circuit breaker according to its breaking capacity and the prospective shortcircuit current at its place of installation (see Schneider lectric LV documentation). Note: or normal source power supply voltages of 380, 400 and 45 V, the normal source current is the same because it is a function of the voltage. lectrical parameters for the normal source Rated urrent normal source UPS Rated current In for unit: for 5% for 50% output with battery at start without battery () overload (3) overload (3) in kv of charge cycle () () the rated normal source currents (In) have been determined for a rated phase-to-phase voltage of 400 V, a battery with a 0 minute backup time at the beginning of its charge with 06 cells at Volts per cell (4 Volts) and full rated load with a power factor of 0.8. () The rated normal source currents (In) have been determined for a minimum float charging voltage of 43 V and full rated load with a power factor of 0.8. (3) the normal source currents given for an overload of 5% or 50% are maximum values. They have been determined for a battery with minimum float charging voltage and a load power factor of 0.8. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the values in the overload columns XU/H - 5

6 haracteristics (cont.) ypass source The parameters given in the table opposite can be used to determine the required rating of the upstream protective circuit breaker on bypass input. Important: It is essential to choose the type of circuit breaker for bypass input according to its breaking capacity and the prospective short-circuit current at its place of installation (see Schneider lectric LV documentation). This choice must also be made so as to protect the static-switch semiconductors with respect to the maximum permissible currents (see table opposite) and ensure discrimination between the UPS output fuses (see the fuse curves in figures and ) and the downstream protection devices. Remark: If the installation includes a transformer on the bypass input, allow for the inrush current caused by magnetisation of the transformer windings. lectrical parameters for bypass source (45 V) Rated UPS urrent bypass source () output in kv Rated current for 5% for 50% In overload overload () the bypass source currents have been determined for a rated phase-to-phase voltage of 400 V, a load power factor of 0.8 and for full rated load as well as overloads of 5% or 50%. When choosing the circuit breaker rating, use the "rated current" column and check that the circuit breaker tripping curves are compatible with the data in the overload columns. or a bypass source voltage of 380 V, multiply the currents indicated in this table by.09. or a bypass source voltage of 400 V, multiply the currents indicated in this table by.04. UPS output Maximum permissible current in kv 0 43 In for 0 ms 30 9 In for 0 ms 40 In for 0 ms 50 0 In for 0 ms 60 6 In for 0 ms 80 7 In for 0 ms 00 In for 0 ms 0 8 In for 0 ms 60 3 In for 0 ms 00 9 In for 0 ms alaxy PW kv t(s) alaxy PW kv t(s) I() I() ig. alaxy PW kv t(s) I() alaxy PW kv t(s) I() XU/H ig.

7 haracteristics (cont.) Recommended protection protection upstream of alaxy PW The information provided here is purely indicative, for a single-ups unit supplied by a 380 to 45 V, 50 to 60 Hz distribution system. heck that all the criteria mentioned in the previous section are taken into account (shortcircuit current and protection of the static-switch semiconductors on the bypass input). Ratings of recommended protection devices upstream of a single-ups unit (Merlin erin circuit breakers) Rated UPS ircuit breaker on normal ircuit breaker on bypass output input input in kv ircuit breaker ontrol unit ircuit breaker ontrol unit 0 NS 00N 3P TM 63 NS 00N 4P TM NS 00N 3P TM 63 NS 00N 4P TM NS 00N 3P TM 80 NS 00N 4P TM NS 00N 3P TM 00 NS 00N 4P TM NS 5 3P TM 5 NS 5 4P TM 5 80 NS 60N 3P TM 60 NS 60N 4P TM NS 50N 3P TM 00 NS 50N 4P TM 00 0 NS 50N 3P TM 50 NS 50N 4P TM NS 400N 3P STR 3 S NS 400N 4P STR 3 S 00 NS 400N 3P STR 3 S NS 400N 4P STR 3 S Protection downstream of alaxy PW These protection devices ensure discrimination for each of the alaxy PW output circuits. If the recommended downstream protection is not installed and a short-circuit occurs, the result may be a break longer than 0 ms on all the other output circuits. Ratings of recommended protection devices downstream of a single-ups unit (Merlin erin circuit breakers) Rated UPS ownstream circuit output breaker(s) in kv ircuit breaker ontrol unit 0 to 40 kv 60N to 60 kv 60N to 0 kv 60N 50 N to 00 kv N lectrical parameters for determining cable cross-sections this table has been drawn up for rated phase-to-phase source and load voltages of 400 V. or voltages of 380 V or 45 V, multiply the currents for the bypass source and the load by.05 and 0.96 respectively; the current values and cable crosssections for the normal source are given for full rated load with a power factor of 0.8 and a battery consuming its minimum float charging voltage. the battery current values and cable cross-sections have been determined for a battery at the end of discharging; the current values and cable sections for the bypass source and load are given for full rated load with a power factor of 0.8. or frequency converters, the parameters concerning the bypass source are not applicable. Parameters for cables for a single-ups unit Rated UPS Line currents absorbed in mps ross-sectional area of u cables in mm () output Normal source 400 V attery Normal source 400 V attery in kv with or bypass with or without battery bypass without battery () source and load source and load or x or x or x50 70 x or x50 70 x x x95 () The rated normal source currents (In) have been determined for a minimum float charging voltage of 43 V and full rated load with a power factor of 0.8. () the cable cross-sections are given for copper conductors (increase by 30% for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 00 m ( circuits) or 5 m ( circuits if cables not provided). or greater lengths, the cross-sections should be chosen to limit voltage drops to 3% () or % () XU/H - 7

8 haracteristics (cont.) The table opposite serves as an example for a parallel-connected installation comprising up to four UPS units. for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallelconnected UPS units, one being redundant, only UPS units are used to determine bypass source and load currents and cable crosssections); this table has been drawn up for rated phase-to-phase bypass source and load voltages of 400 V and full rated load with a power factor of 0.8. or voltages of 380 V or 45 V, multiply the indicated currents by.05 and 0.96 respectively, then modify the cable cross-sections accordingly, if necessary. The cable cross-sections in this table concern the parts illustrated in bold in the simplified diagram in figure 3, where: : normal source, : bypass source, : external bypass. Parameters for bypass source and load cables for a parallel UPS configuration Rated unit Number of Total UPS ypass able crossoutput parallel- rated output source or load section () in kv connected in kv line current in mm units in mps x x x x x x x x x x85 () cable cross-sections are given for copper conductors of the U000 R0V type (increase by 30% for aluminium conductors). They are calculated according to permissible temperature rise and allow for line voltage drops over a maximum length of 00 m. or greater lengths, the cross-sections should be chosen to limit voltage drops to 3%. alaxy alaxy alaxy 3 ig XU/H

9 Installation Positioning the cubicles prior to moving the cubicles to their final position, remove the packing material and the base panels which were shipped on top of the cubicle. The panels will be installed at the end of the installation procedure; after moving them to their installation location on their pallets, cubicles can be moved short distances using a forklift or pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 00 mm ±0 mm high openings; adjust the front foot pads to make the cubicle vertical and align the subsequent cubicles. loor loads See figure 4, where: : the rear panel of the cubicle, : the width of the cubicle, minus 39 mm (see page 5), : the four foot pads (diameter 40 mm), : the front panel of the cubicle. to determine the stresses applied by the cubicle on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (50 cm ). 69, , Note: ispose of packing materials in compliance with applicable legislation. ig. 4 ubicle layout on a false floor or a normal floor see figure 5 for a single-ups alaxy PW unit with a single battery cubicle; see figure 6 for a single-ups alaxy PW unit with several battery cubicles; see figure 7 for two parallel-connected alaxy PW units with battery and auxiliary cubicles. an overall clearance of 400 mm must be left above the entire surface of the cubicles for ventilation; in rooms with unrestricted access, install a fire-protection system under the UPS cubicle. 80 (*) 3 85 > Key for figures 5 to 7: : the width W of the cubicle (see the table in the haracteristics section on page 5), : the openings to be made for cables coming up through a false floor: 65 x 430 mm for 0 to 60 kv UPS, 00 x (L-60) mm for 80 to 00 kv UPS, : the position of a trench under the cubicles, if applicable, : front of cubicles : back of cubicles : the battery cubicle containing circuit breaker Q, : a second battery cubicle, 3: the UPS cubicle, 4: an auxiliary cubicle, if applicable. ig. 5 ig. 6 (*) : The alaxy PW 0 to 0 kv must be installed at a distance of at least 50 mm from a wall; alaxy PW 60 and 00 may be positioned against a wall; It is advised that, whenever possible, the units be installed at a distance of 400 mm from a wall, in order to facilitate their inspection during preventive maintenance ig XU/H - 9

10 Power-circuit wiring diagrams The single-wire diagrams for typical UPS installations are given in figures 8 to. The heavy lines represent the cables that must be connected (see the table in the previous chapter for the required cross-sectional areas of the cables). see figure 8 for a single-ups alaxy PW unit; see figure 9 for a two parallel alaxy PW units combined for redundancy. see figure 0 for a two parallel alaxy PW units combined for higher output; see figure for a alaxy PW frequency converter without a battery; Key for figures 8 and 9: : normal source, : bypass source, : the rectifier/charger module, : the inverter module, : the static-bypass module, : the battery cubicle next to the alaxy PW UPS cubicle, : any additional battery cubicles, : the equipotential-bonding connection between cubicles, : K3N contactor or output staticswitch module. alaxy PW single-ups unit Q Q + + alaxy PW ig. 8 alaxy PW parallel connection for redundancy Q + + Q alaxy PW Q + + Q alaxy PW ig XU/H

11 Key for figures 9 and 0: : normal source, : bypass source, : the rectifier/charger module, : the inverter module, : the static-bypass module, : the battery cubicle next to the alaxy PW UPS cubicle, : any additional battery cubicles, : the equipotential-bonding connection between cubicles, : K3N contactor or output staticswitch module. alaxy PW parallel connection for greater capacity Q + + Q alaxy PW Q + + Q alaxy PW ig. 0 alaxy PW frequency converter without a battery Q alaxy PW ig XU/H -

12 onnection of power circuits efore making connections, check that switches Q,,, and Q are in the "open" position. eneral: Remark. See page 4 for information on the supplied cables and wires. open the doors and remove the lower terminal shields (secured by screws to the cubicle chassis) of the UPS cubicles; connect the power cables; each cubicle must be earthed; all the cubicles must be interconnected for equipotential bonding, forming a mesh which is itself connected to the building structure and earthing electrode; the connection drawings hereafter show the cubicles with doors open and terminal shields removed. Important: or parallel UPSs with an external bypass unit, the power connections between each UPS cubicle and the external bypass unit must imperatively be of the same length. Outside the cubicles, separate the auxiliary wiring from the power cables. UPS cubicle See figure for 0 to 60 kv units, and figure 3 for 80 to 0 kv units, and figure 4 for 60 to 00 kv units. attery + and - cables are connected by lugs on 8 mm diameter pins for 0 to 0 kv units, or by lugs on mm diameter holes for 60 to 00 kv units. Normal/ypass input and load cables are connected by tunnel terminals to the 0 to 60 kv units, or by lugs on 0 mm diameter holes to the 80 to 0 kv units. levation of connections from ground for 0 to 60 kv units: normal/bypass input and load: 30 mm; battery: 80 mm. levation of connections from ground for 80 to 0 kv units: normal/bypass input and load: 340 mm; battery: 30 mm. levation of connections from ground for 60 to 00 kv units: normal/bypass input and load: 40 mm; battery: 40 mm XU/H

13 Key to figures and 3: : cross-sectional view of the cubicle, : front view of the cubicle, : front panel, : rear panel, : normal input connection, : bypass input connection, : load connection, : battery connection, : air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: rectifier/charger module, L: inverter module, M: static-bypass module, N: rack containing electronic boards, O: Media ontacts board, P: slot for communications boards, Q: U input fuses, R: US output fuses, S: TOI board (0 to 60 kv UPS) or RLI board (80 to 00 kv UPS), T: POZ board, U: MISI board, V: modem socket switch, W: trough (0 to 60 kv) or binding bar (80 to 00 kv) for fine wiring, X: fuses for overvoltage protection R circuit on bypass, Y: control-wire connection (auxiliary "Media ontacts " circuits and communications options). Notes: igure. Switch does not exist in parallel alaxy PW cubicles interconnected for greater capacity. igure 3. Switch and "X" (protection fuses) do not exist in parallel alaxy PW cubicles interconnected for greater capacity. The bypass source ("") connects to switch.,, ig. I J kv alaxy PW cubicle with built-in bypass -input isolation transformer (option) H H T R Q S Q L L N LLL3 L3 Q K, L, M N LLL3 K M N V O P N Y L L L L L3 L3 N LLL3 Y O P U V W H H L S M R Q U T W,, Q L L L3 N L L L3 N L L L3 X Y I J kv ig XU/H - 3

14 Key to figure 4: : cross-sectional view of the cubicle, : front view of the cubicle, : front panel, : rear panel, : normal input connection, : bypass input connection, : load connection, : battery connection, : air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: rectifier/charger module, L: inverter module, M: static-bypass module, N: rack containing electronic boards, O: Media ontacts board, P: slot for communications boards, Q: U input fuses, R: US output fuses, S: TOI board (0 to 60 kv UPS) or RLI board (80 to 00 kv UPS), T: POZ board, U: MISI board, V: modem socket switch, W: trough (0 to 60 kv) or binding bar (80 to 00 kv) for fine wiring, X: fuses for overvoltage protection R circuit on bypass, Y: control-wire connection (auxiliary "Media ontacts " circuits and communications options). Note: igure 4. Switch does not exist in parallel alaxy PW cubicles interconnected for greater capacity. The bypass source ("") connects to switch. H H K M N O P L T V S U M Q R W,,, Q LL L3 N LL L3 N LL L3 X Y I J kv ig XU/H

15 attery cubicle See figure 5. The battery cubicle shown is an example only, given that characteristics of these cubicles vary greatly from one cubicle to another. remove the cardboard covers and all the hooping (used only for transport); remove the terminal shield from the battery circuit breaker "Q" to make the connections to this circuit breaker; in the case of installations having several battery cubicles, the connections to be made between cubicles are indicated in the instructions accompanying the cubicles (or in the drawing file for complicated installations); in the case of a UPS with a power rating from 80 to 0 kv and connection via the top, the battery cubicle containing circuit-breaker Q cannot be connected to the UPS cubicle via the bottom. roof equipped with a cable gland can be installed on this battery cubicle in order to connect it directly via the top to the inverter cubicle. Please contact our after-sales service. Important: the cubicle is supplied with a fixture locking circuit breaker "Q"in the open position. o not remove this fixture before commissioning. ccidental closing of "Q" will power up the downstream circuits which could be hazardous for personnel and permanently damage the battery by deep discharge; connections between battery cubicles should be made in compliance with applicable regulations. Take all protective measures associated with working on live equipment and in particular use only qualified personnel equipped with gloves, protective goggles, insulated tools, etc. ables are connected to copper terminals by lugs. Note: The optional "Temperature Monitor" unit is located at the top in one of the battery cubicles. The cubicles not fitted with a battery circuit breaker include an additional shelf for battery cells. Key to figure 5: : cross-sectional view of the cubicle, : front view of the cubicle, : front panel, : rear panel, : cable ties to duckboard shelf, : cable exit through the bottom, : trough, if applicable, H: connection of exposed conductive parts to duckboard shelf, I: cable exit to battery connection point in UPS cubicle, J: cable exit to an additional battery cubicle, if applicable, K: cable ties to duckboard shelf, L: fixture locking circuit breaker "Q" in the open position. XR H Q + + I J K L ig XU/H - 5

16 onnection through the top (0 to 0 kv units) This type of connection is possible on 900 mm high cubicles. See figure 6. Key to figure 6: : cross-sectional view of the cubicle, : front view of the cubicle, : front panel, : rear panel, : normal input connection, : bypass input connection, : load connection, : battery connection, I: air outlet grid, J: passageway for cables exiting through the top (opening 460 x 97 mm with cable-gland plate), K: top view of the cubicle. Note: or 60 to 00 kv units, this option is not available because air is discharged through the top. However, it is possible to run normal/bypass input and load cables through an auxiliary cubicle (empty or containing an optional harmonic filter or bypass -input isolation transformer). In this case, the cables enter through the standard opening in the top and exit through the bottom of the cubicle. ig. 6,,, L+L- L3 L L L3 L L N L3 L L N J I K kv XU/H

17 xternal bypass cubicle 50 kv 50 kv 5,5 See figure 7. Key to figure 7: : bottom view of the unit, : front view of the unit, : passageway for cables (37 x 0 mm), : bypass input connection for the UPS units, : connections for auxiliary wiring indicating the position of the and switches, : connection for the UPS-unit outputs, : bypass input connection, H: load connection N L L L "MISI" + XM8 + XM9 N L L L3 H N L L L ,5 "MISI" + + XM8 XM9 N L L L3 750 "MISI" 3 "MISI" ,5 ig XU/H - 7

18 Installation (cont.) xternal bypass cubicle 360 kv See figure 8. Key to figure 8: : cross-section of cubicle, : cubicle front view, : front panel, : bypass input connection for the UPS units, : connection of the auxiliary position wires of switches "" and "", : connection of UPS load outputs, : bypass input connection, H: connection of load, I: air outlet grid, J: opening of 460 x 97 mm for cable insertion, K: fuses for overvoltage protection R circuit on bypass (to be replaced when the indicator light is on). L: top view of cubicle 900 N L L L3 N N L L L3 L L L3 K H H N L L L3 L J I "MISI" "MISI" + XM8 - + XM9 - + XM8 - + XM9-3 4 "MISI" 3 "MISI" kv ig XU/H

19 Installation (cont.) xternal bypass cubicle 600 kv See figure 9. Key to figure 9: : cross-section of cubicle, : cubicle front view, : front panel, : bypass input connection for the UPS units, : connection of the auxiliary position wires of switches "" and "", : connection of UPS load outputs, : bypass input connection, H: connection of load, I: air outlet grid, J: opening of 460 x 97 mm for cable insertion, L: top view of cubicle H H L J I "MISI" "MISI" + XM8 - + XM9 - + XM8 - + XM9-3 4 "MISI" 3 "MISI" kv ig XU/H - 9

20 onnection of the Hot Swap option The external bypass may be used to construct a bypass outside the UPS, thus making it possible to shutdown the UPS for maintenance purposes. The option may be used for single-ups units and redundant parallel UPSs. control-wire connections are not required between the bypass unit and the UPS unit(s); see figure 0 for the power-circuit connections of a single-ups unit and figure for the power-circuit connections of redundant parallel UPSs. Power cables for UPS-to-bypass connections are not supplied. ig. 0 Q alaxy PW Q + + alaxy PW cubicle with built-in bypass -input isolation transformer (0 to 60 kv UPSs) or this option, the cubicle is 900 mm high. This isolation transformer is installed in the top part of the cubicle. Power connections are not modified by this option (see figure ). Q Q + + alaxy PW Q + + Q alaxy PW ig. Q + + Q alaxy PW ig XU/H

21 H Mains isolation transformer in an auxiliary cubicle H Installation (cont.) H L The cubicle is 900 mm high. See figure 3 (0 to 0 kv units) and figure 4 (60 to 00 kv units). Key to figures 3 and 4: : cross-sectional view of the cubicle, : front view of the cubicle, : front panel, : rear panel, : bypass input connection (terminals,, or,, (+ 5%), : bypass input connection to UPS(s) - terminals n, a, b, c, : air inlets, H: air outlets, I: cable exit through the bottom, J: trough, if applicable, K: bypass input isolation transformer, L: passage of cables through the top, M: passageway for cables exiting through the top (opening 460 x 97 mm with cable-gland plate), N: air outlet grid, O: top view of the cubicle. I J kv O M N LL L3 75 NLL L3 K ig. 3 H L 05, LL L3 NLL L3 K I J kv O M N ig XU/H -

22 THM filter This option is installed on the normal input upstream of the alaxy PW UPS cubicle. The cubicle is 900 mm high. 0 to 0 kv units, width of auxiliary cubicle = 75 mm 60 to 00 kv units, width of auxiliary cubicle = 05 mm or THM-filter installation and connections, see manual No ig. 5 THM alaxy PW Key to figure 5: : normal input : bypass input : alaxy PW UPS cubicle : THM filter XU/H

23 onnection of "Media ontacts " standard auxiliary circuits See figure 6 below for information on connecting the auxiliary circuits to the three connectors on the "Media ontacts " board in the alaxy PW UPS cubicle. See the position of this board, marked "O" in figures to 4. recommended cable cross-section: mm ; the male connectors that fit the female connectors on the board (XR to XR5) are supplied; the contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest; contact breaking capacity: 50 V, 5. onnection to battery circuit breaker "Q" connect the cable from connector XR3 (pins to 8) on the "Media ontacts " board in the UPS cubicle to connector XR in the battery cubicle containing battery circuit breaker Q. mergency power off The UPS emergency shutdown function is generally wired to a "mushroomhead" type emergency-off button. Important: In the case of a complex installation with a number of units, there should be only one emergency shutdown pushbutton and this pushbutton must interrupt all the active conductors of all the units. or the same reason, it is essential for the pushbutton to open the upstream protective circuit breakers on the normal and bypass inputs. ach type of unit (single UPS, parallel UPS, frequency converter) must have an independent, volt-free contact connected to the emergency shutdown pushbutton. This pushbutton must therefore have as many contacts as there are units in the installation, as well as the contact or contacts required to open the upstream protective circuit breakers on the normal and bypass inputs. The emergency shutdown pushbutton turns off the rectifier/ chargers and inverters, opens the battery circuit breakers and activates a contact on the "Media ontacts " board (terminals to 3 on connector XR4). The emergency shutdown signal will be cleared when the emergency shutdown pushbutton contact has been reset. Media ontacts " board ig. 6 XR XR connector earth V 4V +V N N N V power supply + V temperature signal XR3 connector + V XR4 connector XR5 connector N N XR3 N N 0 XR4 output signals: general alarm output signals: load on inverter load on battery 0 XR5 input or output signals: emergency-shutdown button contact (jumper if not used) connection with optional electronic board for measuring battery temperature and/or harmonics filter temperature fault input or output signals: free auxiliary contact battery-room ventilation fault Q battery circuit-breaker opening command maintenance position complete system shutdown low-battery shutdown warning XR XR3 XR4 XR XR harmonic-filter cubicle XR terminal block battery cubicle XR terminal block thermal monitoring of the harmonics-filter inductor Q battery circuit-breaker closed Q battery circuit-breaker opening command -5083XU/H - 3

24 onnections between cubicles (parallel-connected configurations) These connections are made on the POZ board (marked T in figures to 4) and MISI board (marked U). "POZ" alaxy PW Important: Outside the cubicles, group the "POZ" inter-board and "MISI" interboard connections with the inter-cubicle auxiliary connections, and separate this assembly using power cables. onnections between POZ boards See figure 7. these connections are made using the cables () supplied; the purpose of the connection is to make a loop. onnector XM37 on the POZ board of one UPS unit must be connected to connector XM36 on the POZ board of the next UPS unit and so on until the first board is returned to. ig. 7 "POZ" alaxy PW "POZ" alaxy PW 3 XM37 XM36 XM37 XM36 XM37 XM36 onnections between MISI boards See figures 8, 9 and 30. these connections are made using the special cables () supplied; connectors XM5, XM6 and XM7 on the MISI board are used to transmit signals; connectors XM0, XM and XM on the MISI board are used to receive signals; connector XM5 is associated with connector XM0 for communication with one UPS unit; similarly, XM6 is associated with connector XM for communication with a second UPS unit and XM7 is associated with connector XM for communication with a third UPS unit; situation with two parallel UPS units: see figure 8; situation with three parallel UPS units: see figure 9; situation with four parallel UPS units: see figure 30. "MISI" alaxy PW "MISI" alaxy PW ig. 8 XM0 XM XM XM0 XM XM XM5 XM6 XM7 XM5 XM6 XM7 "MISI" alaxy PW "MISI" alaxy PW "MISI" alaxy PW 3 XM0 XM XM XM0 XM XM XM0 XM XM XM5 XM6 XM7 XM5 XM6 XM7 XM5 XM6 XM7 ig XU/H

25 "MISI" alaxy PW XM0 XM XM XM5 XM6 XM7 "MISI" alaxy PW XM0 XM XM XM5 XM6 XM7 "MISI" alaxy PW 3 XM0 XM XM XM5 XM6 XM7 "MISI" alaxy PW 4 XM0 XM XM5 XM6 XM7 XM ig. 30 onnections between UPS cubicles and the external bypass the recommended cross-sectional area of control wires is mm. Wires are not supplied; in non-redundant parallel UPS systems (increased output), the UPS units must be connected to the external bypass unit (see figures 7, 8 and 9): terminals and on connector XM8 of the MISI board of the UPS to terminals and on the external bypass for indications on the position of switch, terminals and on connector XM9 of the UPS to terminals 3 and 4 on the external bypass for indications on the position of switch. Installation of communications options Three slots are available on the "Media ontacts " board for communications options. See the position of these slots marked "P" in figures to 4. Installation of boards boards may be installed with the UPS on, without removing the protective covers; boards must be pushed to the end of the slots to ensure correct installation; board front plates must be screwed to the protective "Media ontacts " board cover. Passage of wires holes are provided in the support for the "Media ontacts " board for tying down the wires; the control wires must then be routed through the cableway marked "W" in figures to XU/H - 5

26 onnection of the battery "Temperature Monitor" onnections This unit must be connected to the XR connector on the remote indications "Media ontacts " board of the UPS cubicles. See the location of the "Media ontacts " board, marked "O" in figures to 4 in the ppendix. use a shielded cable made up of twisted telephone pairs with a conductor cross-section of at least 0. mm, not longer than 00 m in length; do not forget to connect the cable shield to ground pin on connector XR; in the case of a parallel UPS configuration, the connections between cubicles may be made by means of a shielded cable made up of or twisted telephone pairs. In this case, the total length of all the connecting cables must not exceed 00 m; a "Temperature Monitor" unit can be connected to several UPS cubicles only when the batteries of these cubicles are located in the same room at the same ambient temperature. onnection of the battery "Temperature Monitor" (single-ups unit) ig. 3 battery "Temperature Monitor" + XR XR + (unit shown open) shielded cable ( twisted telephone pairs) onnection of the battery "Temperature Monitor" (n parallel UPS units with batteries in same room) battery "Temperature Monitor" + XR XR + (unit shown open) shielded cable ( twisted telephone pairs) XR connector on "Media ontacts " board: V +V + earth power supply temperature signal XR connector on "Media ontacts " board in alaxy PW unit : N V +V + earth power supply temperature signal XR connector on "Media ontacts " board in alaxy PW unit : shielded cable ( or twisted telephone pairs) N + + temperature signal XR connector on "Media ontacts " board in alaxy PW unit n: earth earth temperature signal ig XU/H

27 Installation of the "Temperature Monitor" in an M UPS SYSTMS empty battery cubicle The "Temperature Monitor" unit is placed inside the battery cubicle housing circuit-breaker Q (see figure 33): open the unit cover; before fixing, break the self-cleavable seal on the base of the unit for insertion of the connecting cable; fix the unit on the plate using the selfadhesive sticker and a screw (nut and washer combination, diameter 4 mm, length 6 mm, not supplied); connect and put back the cover; the temperature sensor MUST be placed at the top of the cubicle to work properly; tie the connecting cable to the cubicle upright so that it does not pull on the unit. Installing the "Temperature Monitor" in a battery cubicle battery cubicle Q to UPS cubicle "Temperature Monitor" unit tie the cable to the cubicle upright ig. 33 "Temperature Monitor" installation in a battery room The "Temperature Monitor" should be secured against a wall or any vertical support. choose a location near the batteries and away from draughts which adversely affect the accuracy of temperature measurements; use the holes provided in the base plate to screw the unit to the vertical support (see figure 34); unless the connecting cable runs on the surface, break the knock-out in the unit base plate provided for cable entry, secure the cable by suitable means so that it does not pull on the unit. "Temperature Monitor" base dimensions du coffret : 75 x 75 x mm ig. 34 board oblong hole for fastening screw oblong hole for fastening screw knock-out for lateral cable entry -5083XU/H - 7

28 Link to an IM S/400 computer The alaxy PW can dialogue with an IM S/400 computer via this link in compliance with IM communications recommendations, thus enhancing the protection provided by your alaxy PW. The IM S/400 computer must be configured for the link. This document presents the physical connections required as well as the system values that must be modified on the S/400. or further information, consult the following IM documents: "Planning uide, ppendix " concerning physical connections; "ack-up and Recovery uide", chapter 7 "Power Loss Recovery" concerning configuration of the S 400. onnections connections are made to the female client connector XR5 on the "Media ontacts " board; the corresponding male connector is supplied; see figure 35 below for the wiring diagram. five-wire cable (not supplied) is required; on the S/400 side, use a 9 or 5-pin SU- connector, depending on the type of S/400. onfiguration of the S 400 ertain values on the S/400 must be configured to enable operation of the alaxy PW - S/400 link. The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss Recovery" of the "ack-up and Recovery uide" for the S/400. The values are the following: QUPSMSQ: UPS message queue; QUPSLYTIM: Uninterruptible power supply delay time; QPWRRSTIPL: Power restore IPL. onnection to the "Media ontacts " board "Media ontacts " remote indications board XR XR XR3 XR4 XR5 0 XR3 Note: the corresponding IM S/400 signal names are given in parentheses. XR4 0 0 XR5 XR5 connector output signals: load on inverter (ON) load on battery (utility failure) low-battery shutdown warning (low battery)) load on bypass (bypass active) XR common 0 V (system ground) male 9-pin SU- connector male 5-pin SU- connector alaxy PW IM S/400 ig XU/H

29 onnection of the L indications unit (optional) This unit connects to the XR4 and XR5 connectors (see the position of the board in the figures in the "connection of "Media ontacts " standard auxiliary circuits" section). or information on unit installation and details on connections to the unit, see the manual included with the L indications unit, document No the recommended cable crosssection is mm. inal installation steps fter making the connections: install the front and rear base plates of the cubicles, clipping them to the feet of the cubicles (unless the connecting cables are fed through these openings); refit the terminal shields of the terminal blocks, switches and circuit breakers XU/H - 9

30 XU/H

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41

More information

MGE Galaxy 5000 MGE Galaxy 5500 MGE Galaxy 6000 MGE Galaxy PW

MGE Galaxy 5000 MGE Galaxy 5500 MGE Galaxy 6000 MGE Galaxy PW Home Alarms Online Trend Statistics Rectifier Battery Inverter Bypass AC Bypass Output Set up Normal AC GALAXY 6000 400 kva SALLE IQ Q4S Load protected Q3BP QF1 0 Hour 50 Min. 100% 0 50% 15:24:32 30/05/2005

More information

MGE TM Galaxy TM 6000 : Specification guide. Single UPS, three-phase, 250 to 600 kva

MGE TM Galaxy TM 6000 : Specification guide. Single UPS, three-phase, 250 to 600 kva MGE TM Galaxy TM 6000 : Specification guide Single UPS, three-phase, 250 to 600 kva Contents 1 - UPS definition... C-3 1.1 - Purpose... C-3 1.2 - Brief description... C-3 2 - Operating principle... C-3

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

Standard specification Galaxy PWi, three-phase, 10 to 200 kva

Standard specification Galaxy PWi, three-phase, 10 to 200 kva Galaxy PWi, three-phase, 10 to 200 kva Contents 1 - UPS definition... 2 1.1 - Purpose... 2 1.2 - Brief description... 2 2 - Operating principle... 2 2.1 - Normal operation... 2 2.2 - Operation on battery

More information

Galaxy kva Installation manual FR/AA - Page 1

Galaxy kva Installation manual FR/AA - Page 1 www.mgeups.com Galaxy 7000 50-500 kva Installation manual T I B L E P O W E R P R O V I D E R U P E R R N T N I E U T H 40064FR/AA - Page Introduction Thank you for selecting an MGE UPS SYSTEMS product

More information

TECHNICAL DATA SHEET KVA UPS Systemss

TECHNICAL DATA SHEET KVA UPS Systemss Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_010-040_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

MASTERYS IP+ 10 to 80 kva

MASTERYS IP+ 10 to 80 kva MASTERYS IP+ 10 to 80 kva OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application. the information

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series

More information

MGE TM Galaxy TM 7000 GFC

MGE TM Galaxy TM 7000 GFC MGE TM Galaxy TM 7000 GFC Grid Frequency Converter (GFC) for Shore Connection solution 500 kva Performance 3 Phase Power Protection with high adaptability to meet the unique requirements of Shore Connection

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw

DELPHYS GP. Green Power 2.0 range 160 to 1000 kva/kw DELPHYS GP Green Power 2.0 range 160 to 1000 kva/kw OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application.

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TM SG Series 100 &120 PurePulse TM SG Series 60 & 80 PurePulse SGSE_060-120_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

POWER kva

POWER kva +44 (0)20 8868 3732 TECHNICAL DATA SHEET B9600 400-800kVA GENERAL INFORMATION UPS Type ON LINE - Doppia Conversione Nominal output power (Cos φ0,8) kva 400 500 600 800 Nominal output power (Cos φ1,0) kw

More information

MGE TM Galaxy TM 7000

MGE TM Galaxy TM 7000 MGE TM Galaxy TM 7000 Power efficiency for business continuity 160/200/250/300/400/500 kva > Performance 3 Phase Power Protection with high adaptability to meet the unique requirements of Medium to Large

More information

APC by Schneider Electric MGE GALAXY 5500 Uninterruptible Power Supply Guide Specifications 20 kva to 120 kva Single UPS, three-phase

APC by Schneider Electric MGE GALAXY 5500 Uninterruptible Power Supply Guide Specifications 20 kva to 120 kva Single UPS, three-phase APC by Schneider Electric MGE GALAXY 5500 Uninterruptible Power Supply Guide Specifications 20 kva to 120 kva Single UPS, three-phase THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION

More information

Green Power 2.0 MASTERYS GP

Green Power 2.0 MASTERYS GP Green Power 2.0 MASTERYS GP 60 to 120 kva/kw OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application.

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

GENERAL SPECIFICATION ELECTRICAL

GENERAL SPECIFICATION ELECTRICAL GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC) TECHNICAL DATA SHEET B9000 FXS 200-250 - 300kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE - Double Conversion Nominal output power (Cos φ0,8) kva 200 250 300 Nominal output power (Cos φ1,0)

More information

Product Specifications

Product Specifications Product Specifications Guide Specification for FirstLine 10Kva, 15Kva, and 20Kva Three-Phase, On-Line Uninterruptible Power Supply 4-15-10 301 Gaddis blvd, Dayton, OH 45403, USA Telephone: (866) 261-2257,

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

POWER kva

POWER kva TECHNICAL DATA SHEET B9000 FXS 60-80-100-125-160kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos φ 0,8) kva 60 80 100 125 160 Nominal output power

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

Master Plus kva

Master Plus kva Local Area Networks (LAN) ServerS Data Centers Telecommunication devices e-business (Servers Farms, ISP/ASP/POP) Industrial Processes Industrial PLCs Electromedical Devices Emergency Devices (lights/alarms)

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 10 20 30 kva 400 VAC CE Series 4 SGT4000_010-020-030 GE_01 Manufactured by: GE

More information

DEVICE STATE/BYPASSED FAILURE OVERLOAD

DEVICE STATE/BYPASSED FAILURE OVERLOAD Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated

More information

EFFEKTA Power Supplies

EFFEKTA Power Supplies EFFEKTA GENERAL INFORMATION UPS topology ON LINE - Double Conversion Classification VFI-SS-111 in accordance with IEC 62040-3 Nominal output power (Cos Ø 0,9) - kva 10 15 20 30 40 Nominal output power

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

MODULYS RM GP. Rack-mounted modular UPS system. Green Power 2.0 range up to 4 x 25 kw

MODULYS RM GP. Rack-mounted modular UPS system. Green Power 2.0 range up to 4 x 25 kw MODULYS RM GP Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw 19 OBJECTIVES The aim of these specifications is to provide the information required to prepare the system and installation

More information

MODULYS RM GP. Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw

MODULYS RM GP. Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw MODULYS RM GP Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw 9 OBJECTIVES The aim of these specifications is to provide the information required to prepare the system and installation

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

QUEENSLAND URBAN UTILITIES

QUEENSLAND URBAN UTILITIES DOCUMENT NO : EQUIPMENT NO : PREPRED : CHECKED : PPROVED : SHEET NO : 1 of 6 GENERL 1 Battery Charger DCC Inverters 3 DCDC Converters 4 System Design Life (other than batteries) Years 5 Battery Design

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

MGE Galaxy kva. Installation manual. Single UPS. Integrated Parallel UPS. Parallel UPS with SSC. Frequency converters

MGE Galaxy kva. Installation manual. Single UPS. Integrated Parallel UPS. Parallel UPS with SSC. Frequency converters MGE Galaxy 7000 60-500 kva Installation manual Single UPS Integrated Parallel UPS Parallel UPS with SSC Frequency converters Static-switch cabinet Introduction Thank you for selecting an APC by Schneider

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series 10 20 30 40 kva 400 Vac CE Series 5 GE Consumer & Industrial SA General Electric Company CH

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out) TECHNICAL DATA SHEET B8031 FXS 10 15 20 kva 3Ph(In) 1Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos 0.9) kva 10 15 20 Nominal output power (Cos 1.0) kw 9 13.5

More information

LV Capacitor CLMD03 Power Module Instruction manual

LV Capacitor CLMD03 Power Module Instruction manual LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...

More information

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Tender Paper TECHNICAL SPECIFICATIONS FOR 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Contents 1. General 2. Tender submission requirements 3. Environmental

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

Pulsar EXtreme CLA 1500C

Pulsar EXtreme CLA 1500C www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme CLA 500C Installation and user manual 503998EN/AA - Page Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.

More information

Technical Data Sheets

Technical Data Sheets Digit al Energy T M L P Seri es Di gi ta l Energy TM LP Series Digita l Energ y T M L P Se rie s GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply

More information

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out) TECHNICAL DATA SHEET B8033FXS 10 15 20 kva 3Ph(In) 3Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cosϕ 0.9) kva 10 15 20 Nominal output power (Cosϕ 1.0) kw 9 13.5

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

AME. Rectifier - Battery charger. Industrial applications: Key features:

AME. Rectifier - Battery charger. Industrial applications: Key features: Rectifier - Battery charger AME VRLA batteries, flooded battery or Ni/Cd with output voltage from 24, 48, 110, 220 Vdc up to 150A Industrial applications: Oil&Gas (Petrochemicals Offshore, Onshore, Pipelines);

More information

AIS 5000 UPS kva 480 V. Installation Manual

AIS 5000 UPS kva 480 V. Installation Manual AIS 5000 UPS 10-100 kva 480 V Installation Manual IMPORTANT! THIS DOCUMENT CONTAINS IMPORTANT SAFETY INSTRUCTIONS - PLEASE SAVE THESE INSTRUCTIONS! Contents Safety...1 IMPORTANT SAFETY INSTRUCTIONS - SAVE

More information

Manual for Inverter system type PCI05

Manual for Inverter system type PCI05 - 1- Manual for Inverter system type PCI05 SAFETY INSTRUCTIONS This manual must be read before installation, use or work on the product. This product contains dangerous voltages that when touched can cause

More information

MTPi2000C - 80 KW (RANGE)

MTPi2000C - 80 KW (RANGE) MTPi2000C - 80 KW (RANGE) TECHNICAL DESCRIPTION 1 GENERAL DESCRIPTION The MTPi2000C - 80 kw system is designed to convert AC mains voltage into 48 VDC and to supply telecom equipments with back up batteries.

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work Digital Energy Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91

More information

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL Local Area NETWORKS (LAN) ServerS DATA CENTRES TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)

More information

Master Plus kva

Master Plus kva LOCAL AREA NETWORKS SERVERS DATA CENTERS TELECOM MUNICATION DEVICES (Servers Farms, ISP/ASP/POP INDUSTRIAL PROCESSES INDUSTRIAL PLCS MEDICAL DEVICES EMERGENCY DEVICES ights/alarms Master Plus 100- kva

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION Electrical Energy Storage Tester EEST-511-S Semi-Automatic Charge-Discharge Battery Bench 1 channel 50 V / 100A (Ni-CD, Pb, Ni-Mh, Li-ion...) TECHNICAL DESCRIPTION To buy, sell, rent or trade-in this product

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,

More information

SAVER DSP SERIES. 3-10kVA USER MANUAL

SAVER DSP SERIES. 3-10kVA USER MANUAL . SAVER DSP SERIES. SINGLE PHASE IN SINGLE PHASE OUT 3-10kVA USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS 288713578 Important Notices Thank you for choosing Inform UPS Systems. This document provides

More information

PowerValue 11/31 T kva

PowerValue 11/31 T kva Technical Datasheet PowerValue 11/31 T 10-20 kva Classification IEC/EN 62040-3 VFI-SS-111 Working mode on-line double conversion Power rating 10-20 kva Paralleling up to 4 units (up to 80 kva) Output power

More information

ConceptpowerTM Modular kVA

ConceptpowerTM Modular kVA TECHNICAL SPECIFICATIONS ConceptpowerTM Modular 10-15-20-30-40kVA Uninterruptible Supply (UPS) Modular, n+1 redundant, three-phase On-line, Double-Conversion, VFI Classic-Line 10-40kVA Gemini-Line 10-30kVA

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TM SG Series 200-250 - 300 PurePulse CE S3 TM SG Series 160 PurePulse CE S3 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)

More information

Master MPS. Highlights kva kva. Three-phase/Three-phase. Three-phase/Single-phase

Master MPS. Highlights kva kva. Three-phase/Three-phase. Three-phase/Single-phase Local Area Networks (LAN) ServerS DATA CENTRES TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)

More information

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS NB 0811 - NB 1511 NB 0831 - NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS LEN.MAN.UPS.069 Rev.2.00/2002 CONTENTS Safety Instructions 1 Introduction 3 2.1 FEATURE 3 2.2 UPS modules 4 How the UPS works 5 3.1

More information

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC Manufacturer s declaration in accordance with 8- Frame Model catalogue reference 93PS-XX(20)-YY- 93PS-XX(40)-YY- Number of power modules (UPM) 1 1 or 2 Number of internal batteries 0 to 2 x 32 blocks 0

More information

Technical data sheets

Technical data sheets GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

AIS and 40 kva 400 V. Site Preparation and Installation Manual

AIS and 40 kva 400 V. Site Preparation and Installation Manual AIS 3100 20 and 40 kva 400 V Site Preparation and Installation Manual www.apc.com AIS 3100 20 and 40 kva 400 V Site Preparation and Installation Manual www.apc.com IMPORTANT SAFETY INSTRUCTIONS SAVE THESE

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification

Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification Liebert Hipluse U UPS;80-400kVA; 380/400/415V Detailed Specification Conformity And Standard General safety requirements for UPS EMC requirements for UPS Table 1-1 Conformity and standard Normative reference

More information

USER MANUAL MPS 1-5KW SERIES

USER MANUAL MPS 1-5KW SERIES USER MANUAL MPS 1-5KW SERIES Low Series Frequency Solar and Wind Power Charging Inverter CONTENTS 1 WWW.NEXTGENNRG.COM 1. Introduction... 3 2. Profile Structure 4 2.1. Working Principle 4 2.2.Product Features..5

More information

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W Page 1 / 7 Full operation without need of battery Two independent 48Vdc outputs for switching and control Local monitoring with 8 LEDs Remote monitoring with 4 alarm relays Monitoring and configuration

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33U Series / 10 20 30 40 50 60 kva 208 VAC UL Series 1 Date of issue: 11/05/2008 LPS33U_030-040_S1 GE_01

More information

Industrial Chargers and

Industrial Chargers and Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company imagination at work QUITO: Elia Liut N45-26 y Edmundo Chiriboga Telf:

More information

Single and Parallel Installation

Single and Parallel Installation Single and Parallel Installation Smart-UPS VT 10 40 kva 380/400/415 V with Batteries American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American

More information

Liebert Hipulse E Hi-Availability UPS Uninterruptible Power Supply. Installation and User Manual. 800 kva - 50/60 Hz

Liebert Hipulse E Hi-Availability UPS Uninterruptible Power Supply. Installation and User Manual. 800 kva - 50/60 Hz Power Quality Solutions Liebert Hipulse E Hi-Availability UPS Uninterruptible Power Supply 800 kva - 50/60 Hz EN Installation and User Manual SINGLE UNIT AND '1+N' (EXPANDABLE) Dear Customer, Please allow

More information

D.A.T. Single-phase Voltage Regulator. --o-- Complying with EDF specifications HM-76/99/047/B, of 10/10/ o-- Doc. : DAT\GUI-J13-UK\S230

D.A.T. Single-phase Voltage Regulator. --o-- Complying with EDF specifications HM-76/99/047/B, of 10/10/ o-- Doc. : DAT\GUI-J13-UK\S230 OPTIMALISATION, IMPROVMENT ELECTRICAL NETWORKS 1 7 2, a v e n u e d u M a r é c h a l L e c l e r c - 3 3 1 3 0 B E G L E S - P h o n e : + 3 3 ( 0 ) 5 5 6 4 9 4 9 4 8 F a x : + 3 3 ( 0 ) 5 5 6 4 9 7 6

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

Emergency lighting units EM converterled. EM converterled BASIC 90 V BASIC series

Emergency lighting units EM converterled. EM converterled BASIC 90 V BASIC series BASIC 90 V BASIC series Product description lighting Driver for manual testing For self-contained emergency lighting For modules with a forward voltage of 40 97 V SEV for output voltage < 120 V DC ow profile

More information

MODVAR Low voltage reactive power compensation modules Installation manual

MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal

More information

Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification:

Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification: Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification: 1 Capacity 5 ky A UPS system with APFC system 2 Input supply Suitable for400±15% Y, 3 phase, 50

More information

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER Chassis Inverter power Rated input Rated output Battery pack Safeties Environment Others Input Voltage Lower Limit Input Voltage Upper Limit Power Input Current Output Voltage Output accuracy Transient

More information

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V DC circuit supplementary protectors for feeders / distribution systems C60H-DC C curve DB123430 DB123525 DB405571 IEC 60947-2 PB107193-34.eps PB107194-34.eps The C60H-DC supplementary protectors are used

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Emergency lighting units EM converterled

Emergency lighting units EM converterled EM converter EM converter BASIC icd 50 V BASIC series Product description lighting Driver for manual testing For self-contained emergency lighting For modules with a forward voltage of 10 54 V SEV for

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

Technical specifications

Technical specifications KINGDOM OF SAUDI ARABIA THE SAUDI FUND FOR DEVELOPMENT ( SFD) ITB -207-7 Technical specifications Project name: Reconstruction, Furniture and Equipping of Three Schools Photovoltaic Solar System for Holly

More information

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...

More information

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/ Galaxy VX Technical Specifications 12/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this

More information

Emergency lighting units EM converterled. EM converterled BASIC 50 V BASIC series

Emergency lighting units EM converterled. EM converterled BASIC 50 V BASIC series BASIC 50 V BASIC series Product description lighting Driver for manual testing For self-contained emergency lighting For modules with a forward voltage of 10 52 V SEV for output voltage < 60 V DC ow profile

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information