TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

Size: px
Start display at page:

Download "TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS"

Transcription

1 INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1

2 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description Features Inspection Storage Installation Precautions INSTALLATION 2.1 General Cable and Circuit Breaker Ratings Wiring Layout and Connections Battery Requirements and Precautions Battery Connection OPERATING PROCEDURES 3.1 Initial Startup Transfer Load to Inverter Transfer Load to Reserve Manual Bypass Mode Isolate Load TROUBLE SHOOTING 4.1 General Problems Alarms Status Description of Alarms MAINTENANCE 5.1 Preventative Maintenance Battery Maintenance SPECIFICATIONS UPS SERVICE HISTORY 12 September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 2

3 1 I N T R O D U C T I O N 1.1 GENERAL DESCRIPTION The Tower Series of Uninterruptible Power Supplies, UPS, provide low noise, reliable and continuous power to an external load. The load is protected against input transients, i.e. sudden voltage or current fluctuations, and the output frequency is controlled to within specified parameters. In the event of a power failure the UPS will continue to maintain the load demands for a period which is dependent on the degree of loading and the size of the installed reservoir battery. In the event of UPS failure, the load will be automatically transferred to the reserve mains supply. The unit can then be connected into Manual Bypass mode for repairs to the unit if required. Provided that the mains supply is reliable, the load will thus never be without a source of power. The Double Conversion UPS units are also available from Tower, the manufacturers, however these will not be featured as only the Single conversion-on-line units are covered in this manual. 1.2 FEATURES. UPS Systems Power Range Display Alarm card Serial Ports 3KVA, 5KVA, 8KVA, 10KVA, 15KVA, or 20KVA. 230V, 50Hz single phase output. Liquid crystal type (LCD). Remote alarms monitoring. Interface to Server / PC for automatic shutdown and monitoring of units parameters. See note. Advanced power switching and digital diagnostics. Ergonomic, low noise and compact design. Note: The remote alarms and interface to a computer server is an optional extra. Should the latter be desired, an interface card and a RS232 cable together with the software would have to be installed at a nominal fee. 1.3 INSPECTION Inspect the unit on arrival for any damages that may have occurred during transit. If so, report these immediately to the supplier and retain the packaging for inspection by the supplier and Transport Company. Note: The unit has undergone thorough factory testing and inspections. 1.4 STORAGE If the unit is not to be installed immediately it would be advisable to keep it stored in the original packing materials, in normal temperatures, i.e. between -10 C and 50 C and protected from any moisture whatsoever. If the unit is not to be utilised for a long period it would be advisable to contact the battery supplier concerning battery shelf life periods. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 3

4 1.5 INSTALLATION PRECAUTIONS The following factors should be considered to determine a suitable location for your unit: Protection against excessive temperature and humidity. Protection against moisture. Ease of access. Its position relative to the critical load for ease of electrical reticulation. Adequate ventilation clearance. A close proximity of the Battery Cabinet to the UPS unit where applicable. Potential expansion, e.g. additional battery cabinet. 2 I N S T A L L A T I O N 2.1 GENERAL The following information concerning the required circuit breakers and cable cross sectional area should be adhered to. Table 1 outlines these ratings as laid down by the electrical wireman s code. 2.2 CABLE AND CIRCUIT BREAKER RATINGS. The recommended input circuit breaker and input and output cable sizes are listed in Table 1. The input circuit breaker must have a D curve response and should be mounted in the existing distribution board. The UPS must not be connected via an EARTH LEAKAGE breaker on the input supply. All cable sizes are rated for a maximum distance of 50 meters. Table 1. UPS Rating KVA Input Amps Recommend Circuit Breaker Input cable Cross sec.area Output Amps Output cable Cross sec.area 3KVA 11A 20A 1 pole 2.5mm 2 13A 2,5mm 2 5KVA 18A 25A 1 pole 4mm 2 22A 4mm 2 8KVA 28A 40A 1 pole 6mm 2 35A 6mm 2 10KVA 36A 50A 1 pole 10mm 2 43A 10mm 2 15KVA 53A 80A 1 pole 16mm 2 65A 16mm 2 20KVA 71A 100A 1 pole 25mm 2 87A 25mm 2 NOTE: The input and output cables should have two cores plus an earth respectively. 2.3 WIRING LAYOUT AND CONNECTIONS The wiring details are shown in Figure 1. Ensure that all cables are secure and the length adequate to allow sufficient movement of the unit for access when servicing. Figure 1 Terminal block wiring layout. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 4

5 Figure 2 Key Description 1 Rotary Switch 3 5 KVA units only * 2 Battery Fuses 3 CB1 AC Input 4 Terminal Block 5 Alarms Relay Card 6 Input & Output Cables 7 Chassis Earth Point * 8 20 KVA units use OUTPUT & BYPASS Isolators. INVERTER STATUS MESSAGE ALARM OFF ON INPUT OUTPUT VOLTAGE OUTPUT AMPS FREQ. Hz BATTERY VOLTAGE CANCEL Inverter ON/OFF switch LCD Display Alarms Cancel Button Figure 3 September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 5

6 2.4 BATTERY REQUIREMENTS AND PRECAUTIONS. The four battery trays were designed to house a maximum of 2 parallel banks of 32, batteries. A minimum of 32 batteries are required for normal operation of your unit. Each tray houses 16, 7A/H batteries. An additional external battery cabinet can house 3 parallel banks of 32, 7A/H batteries. This would allow for extended time during a power failure. Other available battery options include using 32, 12A/H batteries or 2 parallel banks of 32, 12A/H batteries if an external cabinet is employed. Battery links and interconnecting cables are supplied with your unit.! Care should be exercised when installing the batteries. The following should be considered: Do not short out the battery terminals. Do not drop the batteries. Ensure the polarity connections are correct. Ensure that the battery interconnections are connected securely. Ensure that the interconnecting cables are not pinched underneath trays. High DC voltage is dangerous and is potentially lethal. Batteries should only be installed by qualified personel. Battery life expectancy is reduced when exposed to temperatures above 28 C September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 6

7 2.5 BATTERY CONNECTION F1 F2 F3 Fuses Top Tray Back of UPS unit Bottom tray Figure 4: 2. The batteries should be connected as shown above. CB1 F1 + F2 - F3 AC INPUT hager TRANSFER BYPASS NORMAL ISOLATE LOAD Figure 5: CB1 (AC Input) Battery Fuses Rotary Switch 3 & 5 KVA units only September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 7

8 3 O P E R A T I N G P R O C E D U R E S 3.1 INITIAL STARTUP: (Refer to figure 2 and figure 3) Ensure the INVERTER KEY Switch is in the OFF position and the Battery Fuses are OPEN. For the 3-5KVA units, place the Rotary Switch in the TEST position. For the 8-20KVA units, close the BYPASS Switch (SW2) and open the OUTPUT ISOLATE Switch (SW1). Close the AC input circuit breaker. Depress ALARM Cancel button to reset the hooter. The LCD will activate and after a brief period analog values and status alarms will be displayed. Turn the INVERTER KEY Switch to the ON position. The unit will start up when synchronized to the reserve (mains) in approximately 20 seconds. The sound of a closing relay contact will be heard and the fan will commence spinning. The DC voltage on LCD will rise to 432V and the UPS output voltage will indicate 230V with a frequency of 50Hz. Above these values the NO ACTIVE ALARMS message should appear. Check for correct polarity at the top of the fuses before closing. Close the DC input fuses (Battery fuses, F1, F2 & F3). 3.2 TRANSFER LOAD TO INVERTER: Turn the INVERTER KEY Switch to the OFF position and confirm INVERTER IN STANDBY / LOAD ON BYPASS is displayed on the LCD. For 3-5KVA units, place the Rotary Switch to the NORMAL position. For 8-20KVA units, Close the OUTPUT ISOLATE Switch (SW1) and open the BYPASS Switch (SW2) Turn INVERTER KEY Switch to the ON position. After approximately 20 seconds depress ALARM CANCEL button to silence hooter if required. The display should now read NO ACTIVE ALARMS together with the units input and output parameter values. The unit is now operating in the normal mode. 3.3 TRANSFER LOAD TO RESERVE: Ensure that the status, NO ACTIVE ALARMS is displayed. If LOSS OF PHASE LOCK alarm is displayed the load will loose power if the next step is performed. Do not proceed. Turn the INVERTER KEY Switch to the OFF position. The LCD will display the status INVERTER IN STANDBY LOAD ON BYPASS. For 3-5KVA units, place the Rotary Switch in the BYPASS position. For 8-20KVA units, close the BYPASS switch (SW2) and open the OUTPUT ISOLATE switch (SW1). The load is presently fed from the detour supply, i.e. raw mains. Open the DC fuses (F1, F2 & F3). Open the input circuit breaker (CB1). After approximately 1 minute the internal capacitors will discharge completely and the display will switch off. The unit may now be serviced or cleaned in this state. To switch the unit on again, refer to the INITIAL STARTUP procedures. 3.4 MANUAL BYPASS MODE: Perform the TRANSFER LOAD TO RESERVE procedure. The unit is placed in this state if a fault has occurred within the unit or the load conditions have changed. Depress the ALARMS CANCEL button to confirm an actual fault condition or otherwise. 3.5 ISOLATE LOAD: (3 & 5 KVA Units Only) This is a position on the Rotary Switch on the 3-5KVA units. The load will loose its source of power in this state. This position should be evaded unless a fault condition developes in the load,e.g. short circuit. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 8

9 4 T R O U B L E S H O O T I N G 4.1 GENERAL PROBLEMS The Tower range has been designed for maximum efficiency and reliability. This will be realized as long as the unit is operated within the specifications listed on the last page. The temperature is a major factor affecting the tolerances of the electronic components and also influences the lifespan of the batteries. It is important then that the units internal fan is always in working order. In the unlikely event of a failure occurring, it would not be wise to close circuit breakers that had tripped. Investigate the alarm status on the LCD, check for obvious causes and contact your service centre for advice. 4.2 ALARMS STATUS The LCD indicates the current alarm status of the UPS. 4.3 DESCRIPTION OF ALARMS A L A R M HIGH DC SHUTDOWN BATTERY DISCHARGING DC CRITICAL LOW DC SHUTDOWN INVERTER IN STANDBY INV. VOLTS OUT OF LIMITS INVERTER OVERLOAD OVER CURRENT STOP INVERTER LOCKOUT E X P L A N A T I O N DC voltage exceeded trip point (+20% of normal battery voltage).the over-voltage condition was present for longer than 15 seconds. The DC voltage has dropped below the float of 432V DC value. This indicates that the Inverter is drawing from the batteries and not from the charger. The DC voltage has decreased to a value approaching the Inverter switch-off point. The DC voltage has dropped below the low DC trip point. The Inverter is off. It will restart automatically when the condition that caused it to switch off e.g.low DC SHUTDOWN returns to normal. The Inverter output voltage is out of tolerance.( +10% or 10% ) The load demands on the Inverter exceeded 120% of its capacity. The condition was prevalent for longer than 15 seconds. The Inverter switched off due to excessive load current demands. ( Load current exceeded 300% for a period greater than 40ms ). After 5 unsuccessful attempts to start the Inverter within a time frame of 250 seconds, the LOCK OUT mode is reached. The Inverter will remain off and the load will source to the mains supply via the Static Switch. (Static bypass mode ). INPUT OUT OF LIMITS The MAINS source voltage is out of tolerance.( +/- 15% ) LOAD ON BYPASS ON OFF/DETOUR SWITCH OFF The Critical Load is fed from the reserve source via the Static Switch. The Inverter Key Switch is in the OFF position. FREQ OUT LIMITS The frequency of the reserve source is out of tolerance. ( +/- 2% ). LOSS OF PHASELOCK SINE ERROR CHARGER FAIL OVER TEMPERATURE SUPERVISION STOP The inverter is not able to lock in phase with the reserve source. The instantaneous value of the Inverter output voltage deviated from the limits by more than 15%. The load will be switched to the reserve source if it is present. The charger source has been interrupted. The unit has shut down due to excessive internal temperatures. The Inverter has switched off due to an excessive current demand detected in the IGBT Bridge. A fault condition has occurred and the Inverter will not restart. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 9

10 NO ACTIVE ALARMS No alarm conditions exist, the unit is functioning normally. 5 M A I N T E N A N C E 5.1 PREVENTATIVE MAINTENANCE To ensure continuous reliable operation of and to protect your unit from potential component failure and premature battery incapacity, it is advisable to have the unit serviced. This should be done at least anually but preferably every six months. The following checks may be carried out on a monthly basis : 1. Switch the unit OFF. ( See Operating Procedures ). 2. Ensure that ventilation slots and openings are not blocked.( Avoid placing the unit in confined spaces unless there is adequate ventilation ). 3. Check that the unit is not covered in excessive dust. If necessary remove the covers and blow the unit out. 4. Ensure that the unit remains free of moisture. 5. Check all cables to ensure that they are secure and in good condition. 6. Switch the unit ON. ( See Operating Procedures ) 7. Switch off the input mains supply by opening CB1. 8. Check that the UPS continues to supply the load and the NO ACTIVE ALARMS status is being displayed. (See battery maintenance below if the unit fails at this point.) 9. The unit is now operating on batteries. No additional alarms should be encountered. 10. Reset CB1 after a period of approximately 5 minutes. Depress the ALARMS CANCEL to clear the hooter if required. 11. Check the LCD for the following parameters: Input voltage : V (Rms value) Output voltage : Frequency : 50Hz Output current : 230V Rms (Inverter voltage) Within the specified limit.e.g. < 23A for the 5KVA unit. Battery voltage : 432V DC. ( All Single conversion On Line units ) 5.2 BATTERY MAINTENANCE It is crucial that the units battery back up is monitored and kept maintained. Steps 7 and 8 above will give an indication of the state of charge of the batteries. If the Inverter switches off during this test it indicates that either an individual battery has failed or the entire bank may be due for replacement, or an open circuit condition exists. The following may be checked quarterly: 1. Isolate the batteries from the UPS by opening the fuses F1, F2 and F3. 2. Remove the cabinet side panels and blow out the trays with a blower. 3. Check and ensure that all battery interconnections are tightly secured, and free of corrosion. 4. Check the main battery cable connections to the UPS. 5. Replace and secure all cabinet side panels. The anticipated life of the batteries is between 3 to 5 years depending on the number of discharges and the ambient temperatures. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 10

11 6 S P E C I F I C A T I O N S INPUT 3KVA 5KVA 8KVA 10KVA 15KVA 20KVA Voltage 230V±15% 230V±15% 230V±15% 230V±15% 230V±15% 230V±15% Frequency 50Hz±4% 50Hz±4% 50Hz±4% 50Hz±4% 50Hz±4% 50Hz±4% Current 11A 18A 28A 36A 54A 68A Power 2.22KW 3.7KW 5.92KW 7.4KW 11.1KW 14.8KW OUTPUT Voltage 230V rms 230V rms 230V rms 230V rms 230V rms 230V rms Voltage stability static 1% 1% 1% 1% 1% 1% Voltage stability dynamic <3% <3% <3% <3% <3% <3% Frequency 50Hz 50Hz 50Hz 50Hz 50Hz 50Hz Waveform Sine Sine Sine Sine Sine Sine Harmonic distortion(linear loads) 3% 3% 3% 3% 3% 3% Inverter overload 200% 15sec 200% 15sec 200% 15sec 200% 15sec 200% 15sec 200% 15sec Bypass overload 1000% 0.1s 1000% 0.1s 1000% 0.1s 1000% 0.1s 1000% 0.1s 1000% 0.1s Efficiency (input-output) 95% 95% 95% 95% 95% 95% 0.7 pf 13A 22A 35A 43A 64A 87A BATTERY N o of 12V blocks 32 x 7A/H 32 x 7A/H 32 x 7A/H 32 x 7A/H 32 x 7A/H 32 x 7A/H Max N o of banks in cabinet Float voltage 432V 432V 432V 432V 432V 432V Battery discharging 384V 384V 384V 384V 384V 384V Shutdown imminent 345V 345V 345V 345V 345V 345V Low DC off 335V 335V 335V 335V 335V 335V Autonomy 0.7 pf (2 banks) 50min 30 min 20 min 12 min 8min 4min GENERAL Weight of UPS with 1 set of batteries 120kg 150kg 165kg 180kg 215kg 230kg Dimensions of UPS units and extended battery cabinets. L - 660mm H - 850mm W - 370mm Weight of battery cabinet with 3 sets of batteries Ambient temperature Noise level PROTECTION (ALL RANGES ) Input AC circuit breaker 300kg C 90% maximum humidity 1 meter Input DC circuit breaker / fuses. Electronic overload. Electronic over current. Electronic Transistor supervision. A l l u n i t s c a r r y a o n e y e a r f a c t o r y w a r r a n t y. September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 11

12 7 S E R V I C E H I S T O R Y Commissioned By : Commissioned Date: Service Date Serviced By Next Service Date Notes: September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 12

Tower Electronic Systems

Tower Electronic Systems 3300 UPS Instruction Manual AUGUST 2005 CONTENTS 1.0 INTRODUCTION 1.1 General description 3 1.2 UPS building blocks 3 1.2.1 Boost converter 3 1.2.2 Inverter 3 1.2.3 Static transfer switch 3 1.2.4 Battery

More information

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4 USER S MANUAL PowerWalker VFI 1000 / 3000VA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION......... 2 3. SYSTEM DESCRIPTION......... 4 4. CABLE CONNECTION......... 7 5. OPERATION...... 8 6. TROUBLE

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION... CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. INVERTER OPERATION... 11 6. TROUBLE SHOOTING GUIDE....... 16 7.

More information

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4 USER S MANUAL ON-LINE 1K/2K/3KVA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. UPS OPERATION...... 12 6. TROUBLE

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Defender 1 8.0KW to 14.0KW Online Lighting Inverter Technical Manual #018-0102-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail:

More information

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,

More information

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Cobra Plus Stand-By Lighting Inverter Technical Manual #018-0110-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail: techsupport@dspmanufacturing.com

More information

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System POWER TROLLEY 8 Model: SINE 1548 Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System Version 07 CONTENTS Page 1. INTRODUCTION... 1 2. USING THE POWER TROLLEY.... 2 3. BATTERY BACKUP

More information

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9 USER MANUAL 1 CONTENTS 1. INTRODUCTION... 1 2. SAFTY INSTRUCTION... 3 3. CABLE CONNECTION... 4 4. SYSTEM DESCRIPTION... 5 5. OPERATION... 9 6. TROUBLE SHOOTING GUIDE... 25 7. OPERATION MODES..... 27 8.

More information

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Technical Specifications Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Sentinel PRO CONTENTS 1. GENERAL DESCRIPTION... 2 1.1. Main features of the UPS unit... 3 1.2. Standard Versions...

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

Technical data sheets

Technical data sheets GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company

More information

Technical Specification SENTINEL PRO

Technical Specification SENTINEL PRO Technical Specification SENTINEL PRO Contents 1 GENERAL DESCRIPTION... 3 1.1 Main features of the UPS unit... 4 1.2 Standard Versions... 4 1.3 ER Versions for extended autonomy... 4 2 SENTINEL PRO SERIES

More information

TECHNICAL DATA SHEET KVA UPS Systemss

TECHNICAL DATA SHEET KVA UPS Systemss Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800

More information

PowerValue 11/31 T kva

PowerValue 11/31 T kva Technical Datasheet PowerValue 11/31 T 10-20 kva Classification IEC/EN 62040-3 VFI-SS-111 Working mode on-line double conversion Power rating 10-20 kva Paralleling up to 4 units (up to 80 kva) Output power

More information

EFFEKTA Power Supplies

EFFEKTA Power Supplies EFFEKTA GENERAL INFORMATION UPS topology ON LINE - Double Conversion Classification VFI-SS-111 in accordance with IEC 62040-3 Nominal output power (Cos Ø 0,9) - kva 10 15 20 30 40 Nominal output power

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SVT20KX Highlights On-line double-conversion topology, VFI operation

More information

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual DC AC POWER INVERTER LIV 10 / LIV 20 / LIV 30 User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the Power Inverter. This

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous

More information

MKN-DSP SERIES - THREE PHASE

MKN-DSP SERIES - THREE PHASE Output Power Factor 0.9 MKN-DSP SERIES - THREE PHASE Double conversion True On-Line UPS 3 Phase Input - 3 Phase Output 10 KVA 15 KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA Model for: 208/120 V 220/127 V /

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01

More information

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 MODEL NUMBER: AL-84111 Specifications OUTPUT Output Volt Amp Capacity (VA) 2200 Output kva Capacity

More information

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS MODEL NUMBER: S3M60KX Highlights Best-in-class footprint and power density minimize space requirements for up to 60kVA

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT20K Highlights On-line double-conversion topology, VFI operation

More information

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS CENTRALIZED Battery System BS-EN-50171 Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS 10KVA-40KVA The systems running

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 10 20 30 kva 400 VAC CE Series 4 SGT4000_010-020-030 GE_01 Manufactured by: GE

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

Standby Power Systems

Standby Power Systems Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to

More information

Low Frequency Inverter. User Manual

Low Frequency Inverter. User Manual Pure Sine Wave 220-240V 50-60Hz Low Frequency Inverter User Manual For LK/LW series Power Star inverters only, models: LK2000, LK2000-24, LK3000, LK3000-24, LK3000-48, LK6000-24, LK6000-48 1. Safety precautions

More information

Onfiniti. 1 Phase UPS

Onfiniti. 1 Phase UPS Onfiniti 1 Phase UPS Today's business continuity demands a cost-effective power protection solution, for ensuring Power Continuity and Power Quality with optimal Total Cost of Ownership (TCO). The UPS

More information

USER MANUAL. Power GUARD UPS. Uninterruptible Power System

USER MANUAL. Power GUARD UPS. Uninterruptible Power System USER MANUAL Power GUARD UPS Uninterruptible Power System IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Power GUARD that should be followed during

More information

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC Manufacturer s declaration in accordance with 8- Frame Model catalogue reference 93PS-XX(20)-YY- 93PS-XX(40)-YY- Number of power modules (UPM) 1 1 or 2 Number of internal batteries 0 to 2 x 32 blocks 0

More information

Phase Modular Finally the benefits of Modular ups are for all

Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 The MUST 30/120 is an uninteruptible power supply, three phase input/ output, ranging from 15 kva to 120 kva

More information

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000 User Manual V1.1 OptiFlex 1100 / OptiFlex 2000 Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation

More information

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS NB 0811 - NB 1511 NB 0831 - NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS LEN.MAN.UPS.069 Rev.2.00/2002 CONTENTS Safety Instructions 1 Introduction 3 2.1 FEATURE 3 2.2 UPS modules 4 How the UPS works 5 3.1

More information

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF Manuel d installation Installation manual Part. LE05733AA-07/12-01 GF Index 1 Introduction 18 2 Conditions for use 19 3 Installation 20 4 Visual and acoustic warning signals 22 5 ups diagnostic software

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

Three Phase UPS Systems Range: 10 to 500kVA

Three Phase UPS Systems Range: 10 to 500kVA Three Phase UPS Systems Range: 10 to 500kVA Three Phase UPS Systems Hitachi Hi-Rel Power Electronics Pvt. Ltd. is in the business of Industrial UPS Systems since 1987 and has rich experience in supplying

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series 10 20 30 40 kva 400 Vac CE Series 5 GE Consumer & Industrial SA General Electric Company CH

More information

Pulsar Evolution 1500 / 1500 Rack 1100 / 1100 Rack 800 / 800 Rack 500 Rack

Pulsar Evolution 1500 / 1500 Rack 1100 / 1100 Rack 800 / 800 Rack 500 Rack www.mgeups.com MGE UPS SYSTEMS Pulsar Evolution 1500 / 1500 Rack 1100 / 1100 Rack 800 / 800 Rack 500 Rack Installation and user manual S T O P Y O U N O W L L W I N G I T H N O 34007117EN/AB - Page 1 Page

More information

U n i n t e r r u p t i b l e P o w e r S y s t e m

U n i n t e r r u p t i b l e P o w e r S y s t e m SMART ON-LINE UPS User s Manual U n i n t e r r u p t i b l e P o w e r S y s t e m Smart On-Line UPS 2KVA ~ 20KVA 20KVA Exhaust hole (16)Main breaker (12)Heat exhaust hole (15)Telephone (Rj11) or network

More information

Aurora Single Phase Emergency Lighting Inverters

Aurora Single Phase Emergency Lighting Inverters Aurora Single Phase Emergency Lighting Inverters True Sine Wave On-Line Single Phase Emergency Lighting Inverters AURORA Series Emergency Lighting AC Inverters are among the most reliable systems available

More information

Sine Wave Solar UPS. Owner s Manual. Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology.

Sine Wave Solar UPS. Owner s Manual. Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology. Sine Wave Solar UPS Owner s Manual KSU 1024S, KSU 2048S Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology. Please read this guide carefully before installing the product.

More information

Solar Hybrid Inverter SP Brilliant Series

Solar Hybrid Inverter SP Brilliant Series User Manual Solar Hybrid Inverter SP Brilliant Series Version: 1.5 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System

More information

User Manual 1KVA-5KVA INVERTER / CHARGER

User Manual 1KVA-5KVA INVERTER / CHARGER User Manual 1KVA-5KVA INVERTER / CHARGER Version: 1.7 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III 1. SCOPE A. The Central Lighting Inverter shall be a solid-state three phase system designed to provide

More information

User Manual Rittal PMC UPS 6kVA

User Manual Rittal PMC UPS 6kVA User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...

More information

SAVER DSP SERIES. 3-10kVA USER MANUAL

SAVER DSP SERIES. 3-10kVA USER MANUAL . SAVER DSP SERIES. SINGLE PHASE IN SINGLE PHASE OUT 3-10kVA USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS 288713578 Important Notices Thank you for choosing Inform UPS Systems. This document provides

More information

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0 User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER Version: 1.0 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

Technical Data Sheets

Technical Data Sheets Digit al Energy T M L P Seri es Di gi ta l Energy TM LP Series Digita l Energ y T M L P Se rie s GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33U Series / 10 20 30 40 50 60 kva 208 VAC UL Series 1 Date of issue: 11/05/2008 LPS33U_030-040_S1 GE_01

More information

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual On Line UPS LUC 1000E / LUC 2000E / LUC 3000E User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the UPS. This manual contains

More information

TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT

TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters

More information

Series. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Rack Mount. Your Tailored Power Solutions Provider TM

Series. On-line, Single-phase Parallel Redundant UPS System.   6 and 10 kva Rack Mount. Your Tailored Power Solutions Provider TM Series 6 and 10 kva Rack Mount On-line, Single-phase Parallel Redundant UPS System n Power range and runtime scalability n Full-time Digital Signal Processor Control n LCD/LED mimic panel n Easy-to-set

More information

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL

INDUSTRIAL PROCESSES TELECOM- MUNICATIONS DEVICES EMERGENCY DEVICES INDUSTRIAL Local Area NETWORKS (LAN) ServerS DATA CENTRES TELECOM- MUNICATIONS DEVICES e-business (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCs ELECTRO- MEDICAL DEVICES EMERGENCY DEVICES (Lights/Alarms)

More information

Powerware Master Modbus

Powerware Master Modbus Powerware Master Modbus Map 164201391 Rev D This document describes the format of the data contained in the Modbus messages. Not all registers apply to all UPS modules. Please consult the individual UPS

More information

The Power of Reliability INSTRUCTION MANUAL

The Power of Reliability INSTRUCTION MANUAL The Power of Reliability INSTRUCTION MANUAL SAFETY & WARNINGS Read this manual carefully and understand all Warnings and Cautions before connections are made to the Inverter. If unsure about any aspects

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series

More information

User Manual Solar Charge Controller 3KW

User Manual Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...

More information

Uninterruptible Power System

Uninterruptible Power System USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency UPS 1 st Edition Uninterruptible

More information

Delta UPS - Ultron Family. HPH Series, Three Phase 20/30/40/60 kva 208V. User Manual. The power behind competitiveness

Delta UPS - Ultron Family. HPH Series, Three Phase 20/30/40/60 kva 208V. User Manual.   The power behind competitiveness EPO NORMAL BATTERY BYPASS FAULT ESC ON OFF EPO NORMAL BATTERY BYPASS FAULT ESC ON OFF The power behind competitiveness Delta UPS - Ultron Family HPH Series, Three Phase 20/30/40/60 kva 208V User Manual

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

ConceptpowerTM Modular kVA

ConceptpowerTM Modular kVA TECHNICAL SPECIFICATIONS ConceptpowerTM Modular 10-15-20-30-40kVA Uninterruptible Supply (UPS) Modular, n+1 redundant, three-phase On-line, Double-Conversion, VFI Classic-Line 10-40kVA Gemini-Line 10-30kVA

More information

Series. Full Three Year Warranty. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Tower. Your Tailored Power Solutions Provider TM

Series. Full Three Year Warranty. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Tower. Your Tailored Power Solutions Provider TM Series 6 and 10 kva Tower On-line, Single-phase Parallel Redundant UPS System n Power range and runtime scalability n Full-time Digital Signal Processor Control n LCD/LED mimic panel n Easy-to-set user

More information

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3 User Manual 5KVA/5KW INVERTER / CHARGER Version: 1.3 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

Industrial Chargers and

Industrial Chargers and Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines

More information

Uninterruptible Power System

Uninterruptible Power System USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency AVR Protection Compact

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Phoenix Inverter

Phoenix Inverter Manual EN Handleiding NL Manuel FR Anleitung DE Manual ES Appendix Phoenix Inverter 12 250 12 375 12 500 12 800 24 250 24 375 24 500 24 800 48 250 48 375 48 500 48 800 1. Safety instructions WARNING: ELECTRIC

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS 40, 60, 80 kva (three phase input and output) GENERAL DATA Output Rated Power kva 40 60 80 Output Power Factor 0.8 Topology Technology Construction Parallel Configuration Redundant

More information

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

Power Inverter. User s Manual. Diamond Series CPD1200EILCD Power Inverter Diamond Series CPD1200EILCD User s Manual 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5 2-2 Product Overview & Outlook..5 2-3 Power Requirements

More information

TLE Series UPS 400/500 kw With eboost Technology

TLE Series UPS 400/500 kw With eboost Technology TLE Series UPS 400/500 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical power

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT40K Highlights On-line double-conversion topology, VFI operation

More information

User Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller

User Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller User Manual 4KVA/ 5KVA INVERTER / CHARGER With MPPT Controller CONTENTS ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91

More information

Pulsar Evolution 2200/3000/3000 XL

Pulsar Evolution 2200/3000/3000 XL www.mgeups.com Pulsar Evolution 2200/3000/3000 XL Installation and user manual MGE UPS Systems 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www.mgeups.com IMPORTANT

More information

User Manual. PF0.9 1K/2K/3K Online UPS. Uninterruptible Power Supply System. Version: 1.3

User Manual. PF0.9 1K/2K/3K Online UPS. Uninterruptible Power Supply System. Version: 1.3 User Manual PF0.9 1K/2K/3K Online UPS Uninterruptible Power Supply System Version: 1.3 Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation...

More information

USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply

USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply www.eaton.com/dxups USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply CONTENTS 1.Brief introduction 1 1.1 System and model description 1 1.2 Description of commonly used symbols

More information

USER S MANUAL SOLAR POWER INVERTER KW-6KW

USER S MANUAL SOLAR POWER INVERTER KW-6KW USER S MANUAL ------SOLAR POWER INVERTER------ 1KW-6KW Appliances--------------------------------------------- Content Content Content... 1 1 Figures of unit... 2 2 Specification... 3 3 Front panel...

More information

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER CONTENTS ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture... 2 Product Overview...

More information

Installation and user manual. 5SC 500i 5SC 750i 5SC 1000i 5SC 1500i ENGLISH. Copyright 2013 EATON All rights reserved.

Installation and user manual. 5SC 500i 5SC 750i 5SC 1000i 5SC 1500i ENGLISH. Copyright 2013 EATON All rights reserved. ENGLISH Installation and user manual 5SC 500i 5SC 750i 5SC 1000i 5SC 1500i Copyright 2013 EATON All rights reserved. Service and support: Call your local service representative Certification Standards

More information

1. Important Safety Warning

1. Important Safety Warning Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation... 1 1-5. Maintenance, service and faults... 2 2. Installation and

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

TLE Series UPS 160/200/225/250 kw with eboost Technology

TLE Series UPS 160/200/225/250 kw with eboost Technology TLE Series UPS 160/200/225/250 kw with eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical

More information

Master DIALOG INDUSTRY RANGE

Master DIALOG INDUSTRY RANGE Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs Emergency devices (lights/alarms) Electro-medical devices Telecommunication devices Industrial applications

More information

USER'S GUIDE. WiseHP11 SINGLE PHASE HIGH PRECISION AVR SERVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

USER'S GUIDE. WiseHP11 SINGLE PHASE HIGH PRECISION AVR SERVO-MOTOR AUTOMATIC VOLTAGE STABILIZER USER'S GUIDE WiseHP11 SINGLE PHASE HIGH PRECISION AVR SERVO-MOTOR AUTOMATIC VOLTAGE STABILIZER LEN.MAN.STA.145 Rev.5.00/2010 CONTENTS 1. SAFETY INSTRUCTIONS 1 2. INTRODUCTION 2 3. FRONT PANEL AND INSIDE

More information

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC) TECHNICAL DATA SHEET B9000 FXS 200-250 - 300kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE - Double Conversion Nominal output power (Cos φ0,8) kva 200 250 300 Nominal output power (Cos φ1,0)

More information

3 Uninterruptible Power Systems

3 Uninterruptible Power Systems S4K2U and S4K2U-5 Industrial On-Line UPS The true on-line (double conversion) protection offered by the S4K2U Industrial UPS series eliminates a wider range of potential power problems (spikes, surges

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software User Manual Thank you for purchasing the Defender 650/1200/1600. It is designed to provide safe and reliable power protection to your precious electronics equipment. Before you start using the product,

More information