1 ELECTRICITY COMMISSION PLANNING AND STUDY DEP. BAGHDAD, REPUBLIC OF IRAQ Annex A SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 61410/11kV REVISION YEAR 2001

2 DISTRIBUTION TRANSFORMERS 1- SCOPE OF THE TENDER : Tenderer are invited for the design, manufacture, testing and supply of a 11000/416 volt,oil immersed copper winding outdoor type (Directly under the sun) transformers to be supplied complete with all necessary fittings, accessories offload tap changer, insulating oil and spare parts... etc. The transformer is to be hermetically sealed (without conservator tank)bolted cover with bushing insulators on both H.T and L.T sides for the following rating : 100, 250, 400, Box type for rating 630 and 1000 KVA. And a valid ISO 9001 certificate. 2- GENERAL REQUIREMENTS : The transformers shall be of first class quality and design for continuous satisfactory operation as continuity of supply is of prime consideration. the design shall be allow all necessary precaution for the safety of operation and maintenance personnel. the transformers shall operate satisfactorily under variations of load, voltage or short circuit or other conditions which may occur on the system provided that these variations are within the assigned rating of the apparatus. All the equipment shall be designed to obviate the risk of accidental short circuit. 2-1 Climatic Conditions : The materials used shall be suitable for the following climatic conditions prevailing at the site: Ambient temperature: Highest maximum (in the shade) +55C for about 6 hrs a day. Lowest minimum 10C Maximum yearly average+30c Maximum daily average +40C Sun Temperature: Black objects under direct sunshine attain a temperature of 80 C Air humidity : Maximum 92% at 40 C Minimum 12% Yearly average 44%

3 2-1-4 Sand storm: In general the atmosphere is dusty which may result in a layer of dust being deposited on all exposed surfaces. Also fine dust particles may penetrate even through minute openings. 2-2 Altitudes From sea level up to (1000m) 2-3 System Data: High voltage side:- Nominal voltage Short circuit level Frequency Highest system voltage system Low voltage side:- Nominal voltage: 416/240 volts s ystem Short circuit level Volts 25 KA at volts 50 HZ volts 3- phase,3-wire with neutral isolated but provision is made for earthling through an earthling resistance of 21.1 ohms to limit the earth fault current to 300 Amp. phase,4-wire neutral solidly earthed. According to the short circuit level of H.T side and the rated power of the transformer 2-4 Standards: All the equipments shall be in accordance with the latest issue of the international Electro technical commission (IEC specification). 2-5 Deviation: The tenderer shall particularly mention in his tender all deviations from the specification described in these tender specification. 2-6 Schedules: The tender shall duly fill in the schedules A&B of guaranteed technical particulars, prices, delivery and deviations attached to this specification. Incomplete tenders are liable to rejection.

4 2-7 Guarantee: The tenderer shall confirm than the transformer guaranteed against all defects arising from faults design, materials and workmanship, for a period of (12) months from commissioning or (18) months from arrivals, whichever period expires earlier. 3- system composition The transformer shall operate in distribution systems where most of the net work is overhead lines and comprising partly underground cable. 4- TECHNICAL SPECIFICATION The transformers shall be copper winding. Hermetically sealed of the blolted cover and should have the following characteristics:- Rated outputs ONAN. 100, 250, 400, 630, and 1000 KVA. Duty.step-down, outdoor bushing type for 100,250,400,Box type for 630 & 1000 KVH. Type wound, 3-phase Rated voltage at no load. H.V. 11kv L.V- 416 volt. System frequency 50HZ Interphase Connection H.V. Delta L.V- star with neutral brought out. Vector relation ship Dyn 11 Type of Cooling. ONAN Temperature rise ( i ) 45 C in top oil by thermometer (ii) 50 C in winding by resistance. Off circuit tapings five tapping for 2.5% - 5% on the H.T winding for off circuit operation externally. The machine must be of the robust and definite position type with a click indicating position arrived during tap changing. System Highest Voltage.. H.V side 12 kv Terminal arrangement of transformers:- The 11 kv side terminal is to be a clamp type with eyebolt and nut suitable for conductors up to 150 mm 2 copper. The low voltage terminal are to be flat bar type with holes suitable for compression type thimble the sizes of L.V side: For 100 KVA transformer 4x1x70 mm 2 copper. For 250 KVA transformer 6x1x mm 2 copper For 400KVA transformer 7x1x150 mm 2 copper For 630 KVA transformer 11x1x240 mm 2 copper For 1000 KVA transformer 14x1x240 mm 2 copper

5 Terminal arrangement of outdoors transformers must be brown colored bushing insulator mounted on the top cover of transformer for both H.T. and L.T, with arcing horn on H.T.bushing for outdoor transformer only. Neutral bushing should distinguished from phase bushing, - For box-type transformer a suitable iron box cover the top bushings. 5- Fittings and Accessories: - Terminal marking plate. - Tapping switch. - Valves 3 / 4 B.S.P fitted on cover and bottom of tank, switch cocks. - Thermometer pocket. - Lifting lugs. - Pressure relief valve. - Earthling terminal on tank. - Rating and diagram plate to be chromium plated of the engraved type. - Skid mounting to be vertical with the length of the transformer. - Oil level indicator, to be of mechanical type located on the top cover of transformer to avoid oil leakage, covered by metallic envelop. 6- painting A primary coat shall be applied immediately after cleaning all ungalvanized metallic parts thoroughly. An oil and weather resistant type second coat shall then be applied and the transformer finished in aluminum paint. 7- insulating oil The transformer is to be shipped with first filling of oil which shall be SHELL DIALA (B). 8- loss evaluation The tolerance permitted is +10% of the evaluated guaranteed total losses mentioned in the offer. Any transformer with total losses more than + 10% will be rejected. For transformer with total losses within +5% of the evaluated guaranteed losses, no variation to the contract price shall be made, for transformers where the total losses between 105% to 110% of the total evaluated guaranteed losses, the contract price shall be reduced by the cost of the difference between the total losses and the 105% of the total evaluated guaranteed losses according to the following values. Iron losses 1800 USD per kw. Copper losses 600 USD per kw. For any transformer with total losses less than 100% of the guaranteed losses, no variation to the contract price shall be made.

6 9-1 Inspection: 9- Test The material shall be subjected to inspection and test by our inspectors or international inspector at any time during manufacture. The manufacture shall provide all inspection facilities for the said inspection and inspection shall be made at the place of manufacture or at international testing facilities. The inspector shall have the right of rejecting any portion of the material at any time during manufacture if it dose not meet with the requirements of this specification in all particulars. He shall have the right of overseeing the packing and shipping of all material to be supplied. 9-2 Test at manufacture work: Test at manufacture s work shall comprise type tests if required and routine tests. a-type tests The type test prescribed shall be carried out on one unit of each capacity 1- Test of temperature rise clause 41 of IEC 76/ Full wave impulse-voltage withstand test clause test 45 of IEC 76/ Cost of these tests to be borne by the manufacturer. b- Routine tests Each transformer shall be subjected to all the routine tests specified in section twelve of IEC 76/ Test reports: Five copies of the test reports will be mailed within 8 days after the tests have taken place. These reports will indicate: - The results of the tests. - The calculation of performance of the items. - The guarantee figures to show that each apparatus performs the conditions of the specification within the guaranteed limits. 9-4 Test Certificates: The tenderer shall furnish the Electricity Commission (EC) with 6 copies of test certificates. No equipment shall be shipped without obtaining the (EC) inspector prior approval of the certificates.

7 9-5 Witnessing tests: Unless otherwise agreed to, all tests at factory shall be witnessed by an authorized representative of our (EC). The cost of travelling & accommodation of required authorized engineers to witness the test at the place of manufacture for required days, to be on tenderer account. 10- Drawing, Instruction Book And Litreature document to be submitted with the tender: The following documents shall be submitted by the tenderer along with his tender:- a- full and technical specification of transformer including schedule A&B of guaranteed technical particulars. b- An outline drawing showing the plan, front and side elevation of the transformers, dimensions, terminals, equipment, and all accessories of the transformers. c- Catalogues of the manufacturer for transformers. d- Valid ISO-9001 certificate of the manufacture r for transformers. e- Test certificate for identical transformers. f- Reference list of manufactured and exported transformers. g-incomplete tenders are liable to rejection Document to be furnished by the successful tenderer: Within a period of 4 months from the date of award of the contract, the successful tenderer shall furnish the (EC) with the following documents:- a- 24 sets of prints on paper on all drawings. b- 24 copies of all instruction books and technical maintenance of the transformer, OFF Load tap changing gear and other ancillary equipments. c- 24 copies of instruction for erection of the equipment. d- 24 copies of spare parts list with catalogue number Language: The language to be used in the drawings and instruction book shall be English Dimension: Due to the space requirement in our system it is important for the participants in this tender to make sure that the dimension of each type of the

8 required transformers to be as small as possible the following table is indicative as a maximum for each single dimension:- Table of Dimension Transformer KVA Length MM Width MM Height MM Approval of drawings: The successful tenderer shall prepare and submit to the (EC) all necessary drawings complete with explanations in due time and obtain approval of the same before commencing manufacture. Failure to comply with this clause shall make the equipment or parts or parts there of liable to rejection. 11- Packing The supplier will pack or protect the goods in the most appropriate manner. He will be responsible for any loss or damage arising from careless packing or protection up to the place of final destination after completion of the inspection and tests at the factory, each item shall be packed for export shipment. All parts provided for shipping purposes only and which are to be removed at the time of erection shall be conspicuously tagged. The method of packing shall be such as to protect all the items against excessive corrosion of dampness, and shall afford adequate protection against breakage or other injury, or loss due to breakage of cases or crates from the time the items leaves the factory until finally installed at the substation during which time, the apparatus will travel by rail by a long sea voyage again by rail or truck to the site of the substation. The equipment will also undoubtedly stand on wharves and in the open during and in between periods of transportation and will thereby be exposed to heavy rain, hot sun, humid climate and sudden changes of temperature. Owing to the numerous handlings, the containers should be very strong also extra ordinary care should be given to the packing of the equipment and especially the items having insulating material to prevent the injury due to moisture, from sources external to the packing or from excessive condensation with the packing.

9 12- Spare parts and special tools for each rating 12-1 Spare parts: 1- H.T / L.T winding. 3% 2- H.T bushing with it s accessories. 10% 3- L.T bushing with it s accessories. 10% 4- Tap changer. 3% 5- Pressure relief valve. 2% 6- Oil level indicator. 10% 7- Cover gasket 10% Unit price per set and per piece for each item are required Special tools: All special tools required for maintenance of transformer shall be included in the scope of supply. An itemized list of special tools together with prices shall be submitted with the tender.

10 SCHEDULE ((A)) SCHEDULE OF THE GUARANTEED PERFORMANCE AND OTHER TECHNICAL PARTICULARS (TO BE COMPLETED BY THE TENDERER) Unit KVA KVA KVA KVA KVA Tr. Tr. Tr. Tr. Tr. 1- Name of manufacturer. 2- Country of origin. 3- Standard on which performance data is based. 4- Continuous maximum rating for the specified. Temperature rise and ambient temperature ( valid clause 5 (1) ONAN rating-(kva) 5- Rated temperature rise ( C ) a- Oil by thermometer. b- Winding by resistance 6- Hottest spot temperature-(c). 7- No-load voltage ratio at normal tap & vector relationship> 8- Exciting current referred to H.V. and 50 c/s and at.. (Amps) a- 90% rated voltage. b- 100% rated voltage. c- 110% rated voltage. 9- Power factor of exciting current at100% rated voltage and 50 HZ.. (%). 10- Iron losses at 50 HZ and at.. (kw). a- 90% rated voltage. b- 100% rated voltage. c- 110% rated voltage. 11- Copper losses at full load (O.N.rating) and at 75 C (kw) 12- Total losses.. (kw). 13- Resistance voltage at full load and at 75 C (%). 14- Reactance voltage at full load and at 75 C... (%) 15- Impedance voltage at full load 75 C... a- At normal tap. b- At highest tap. c- At lowest tap. 16- Resistance of H.V. winding per phase at 20 C -(ohms). 17- Resistance of L.V. winding per phase at 20 C -(ohms). 18- regulation at full load at 75 C a- 1.0 power factor. b- 0.8 P,F lagging. 19- Efficiency at 75 C -(%) a- 100% load b- 75% load

11 c- 50% load d- 25% load 20- Calculated thermal time constant -(Hrs). 21- Maximum flux density at normal voltage and frequency and at normal ratio - (KI/sq.cm) a- core b- yoke 22- Maximum flux density at 110% voltage and frequency and at normal voltage and frequency and at normal ratio a-core b- Yoke 23- Insulation of a-core bolts b- Core bolts washer c-side plates d- Core laminations 24- Current destiny in windings Amps/sq.cm. a- H.V. winding b- L.V. winding 25- Insulation on copper 26- insulation strength of winding. a- Impulse full wave -(kv) ( I ) H.V. (I I ) L.V. b- Impulse chopped wave -(kv) ( I ) H.V. (I I ) L.V. c- Applied voltage test. -(kv) d- Induced voltage test. -(kv) 27- Insulation strength of terminals. a- Over voltage test -(kv) b- Minimum wet withstand voltage. -(kv) c- Minimum impulse withstand. -(kv) d-minimum puncture or oil-immersed withstand voltage. -(kv) 28- Type of core 29- Tap changer a- Manufacturer b- Type c- Step of one tap in per cent of rated voltage 30- Thickness of transformer tank (mm) a-sides b-bottom c-corrugated radiators

12 (i) (ii) 31- Weights and dimensions a-net weight of core b-net weight of copper H.V. L.V. c-net untanking weight of -(Kg) -(Kg) (i) Core -(Kg) (ii) Frame -(Kg) (iii) Coil -(Kg) d- Volume of insulating oil -(IMP.Gall) e- Net weight of insulating oil -(Kg) f- Total weight of transformer less oil -(tons) g- Weight of the largest shipping package -(tons) h- Crane lift for untanking core and coils -(m) i- Crane lift for removal of bushings -(m) j- Dimensions of transformer -(m) (i) (ii) (iii) (iv) Under base to top most point Under base to bushing mounting flanges Overall breadth Overall length k- Overall shipping dimensions of tee largest package. 32- Noise level..db.

13 SCHEDULE B OIL CHABACTERISTICS TABLE (TO BE COMPLETED BY THE TENDERER) NO. DESCRIPTION UNIT SPECIFICATIONS 1. MAKER S NAME 2. REFERENCE NAME OF OIL 3. SLUDGE VALUE 0% 4. FLASH POINT (CLOSED) C 5. POUR POINT C 6. VISCOSITY AT 21 CST 7. ELECTRIC STRENGTH(BREAKDOWN KV VOLTAGE) 8. ACIDITY(NEUTRALIZATION VALUE) -TOTAL mg/koh/g -INORGANIC 9. SAPONIFICATION VALUE mg/koh/g 10. COPPER DISCELERATION 11. CRACKLE 12. SPECIFIC GRAVITY 13. SULFER CONTENT 14. DIELECTRIC DISSIP ATION FACTOR (tend)

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35 Ministry of Electricity Planning and Studies Office Baghdad Iraq Specification No. D-02 TECHNICAL SPECIFICATION OF 33/11KV MOBILE SUB-STATION 1 10MVA 1 16MVA REVISION YEAR 2001 YEAR 2009

36 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA 1. GENERAL 1.1 SCOPE OF WORK: Tenderers are invited for the design, manufacture, testing and commissioning, of trailer mounted 33/11.5 KV 10 MVA and 16 MVA mobile substations to be supplied complete with all necessary fittings accessories according to attached single line diagrams. spare parts and a valid ISO 9001 certificate for power transformer and (33KV, 11KV) switchgear i.e circuit breakers and their switchboard, to be submitted with tender documents, otherwise the offer will be rejected. 1.2 STANDARDS The applicable standard to design the equipments and accessories shall be the latest IEC recommendation. 1.3 SCHEDULES The tenderer shall duly fill in the schedules of guaranteed technical particulars, prices, delivery time schedules and deviations attached to this specification. Incomplete tenders will be rejected. 2. General Requirements: The materials shall be of first class quality and designed for continuous satisfactory operation as continuity of supply is of prime importance and to operate satisfactorily under variation of load, voltage and short circuit or other conditions which may occur on the system provided that these variations are within the assigned rating of the apparatus. The materials used shall be suitable for the following climatic conditions: 2-1 Ambient temperature: Highest maximum (in the shade) 55 C for about 6 hours a day Lowest minimum (-10) C Maximum yearly average (+30) C Maximum daily average (+40) C 2.2 Sun Shine temperature: Black objects under direct sunshine attain a temperature of 80 C 2.3 Air humidity: Maximum 92% at 40 C Minimum 12% Yearly average 44% 2.4 Altitudes: From sea level up to (1000m) 2.5 Sand storm: The equipments shall be suitable for outdoor installations and subjected to frequent sand storms and heavily polluted atmospher. (1-21)

37 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA 3. TECHINCAL REQUIREMENT 3.1 System Data a- 33 KV system Nominal voltage Highest system voltage System Short circuit level b- 11 KV system Nominal voltage Highest system voltage System Short circuit level volts volts 3- phase, 3 wire,50hz 25 KA r.m.s at volts volts volts 3-phase,3 wire with neutral earthed through an earthing resistance of 21.1 ohm to limit earth fault current to 300Amps. 25 KA r.m.s at volts c-l.t.system Nominal voltage 416 volts + 6%, -10% System 3- phase, 4 wire with neutral solidly earthed Short circuit level 35 KA r.m.s at 400 volts 4. GENERAL SPECIFICATION OF THE SUBSTATION : 4.1 The substation is to include the 33 kv switchgear, 33/11.5 KV transformer, 11 kv switchgear, 33 kv &11 kv cables on drums, with all necessary accessories to complete in working condition. 4.2 The 33 kv & 11 kv switchgear is to be contained in an outdoor kiosk and the transformer to be of outdoor type. Mobile substation maximum height 4.5 meter. 4.3 The kiosk type is to be sheet steel with double layers, rock wool or any alternative of thermally insulating material in between roof and walls for thermal insulation to with stand the local ambient conditions. Kiosks to be air-conditioned. 4.4 The complete unit must be transportable as a single unit. The structure should be fixed to a rigid frame and base ensuring successful operation and transportation. 4.5 The trailer should be according to the relevant international standard and it is to be coupled to a truck. The trailer should be made steel framed, reinforced, complete with all necessary equipment (such as rear light, breaks, flashers, wheels. etc). The trailers have to be designed for heavy road conditions to prevent the damage of substation equipment during transportation. The trailer should be low-bed type with three axles for maximum permissible load. One axle in front to support the trailer It should be designed with suitable connection to 6x4 tractor (tractor is out of scope) Four number of heavy lifting jacks. Two spare tires. 4.6 Station fire extinguisher shall be of the portable type using suitable chemicals for the electrical fire extinguishers. The size shall be determined by the tenderer to suit the type of the equipment. 4.7 Normal indoor and outdoor lighting & sockets 4.8 In case of internal arc fault a safety diaphragm to relief the pressure caused by the arc outside the kiosk. Degree of protection between compartments should be IP40 in the switchgear. 5. INSTRUMENT AND PROTECTION TRANSFORMERS : 5.1 CURRENT TRANSFORMER: In general the instrument and protection current transformer must comply with the IEC and dry type. Three secondary winding of the CT s for 33 & 11 kv circuit one for over current and earth fault protection and the other for measurement shall be designed for rated (2-21)

38 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA current of 5 AMP. The third shall be designed for differential protection with rated current of 1 AMP. Of special class with suitable accuracy class and a saturation factor protecting the instrument in case of short circuit in the main installation, and the protective CT shall ensure correct operation up to the maximum fault current which can be attained or any developed C.T to fulfill the above requirements. 5.2 VOLTAGE TRANSFORMER : In general the voltage transformers must comply with the IEC And dry type. The secondary voltage shall be 110 Volts between phases. The PT should be of suitable accuracy class and protected by means of easily accessible fuses on H.T side and M.C.B on L.T side The voltage transformers used for earth fault indication and metering shall be of three single phase double wound (star/ star) type with a tertiary winding connected in open delta the secondary star winding shall be used for visual indication of earth fault and for metering, the open delta winding for operating an audible alarm or trip of earth fault on the 11 kv side. 6. INSTRUMENTS AND RELAYS : All indicating instruments must be water and dust proof designed for tropical climate and capable of continuous operation at full load current as well by fault current. All relays shall be of ELECTRONIC type. Relays shall be of withdrawable type to carry out routine tests in service. and for early replacement. Additional protection relay without auxiliary supply or supplied through capacitor storage unit shall be added to operate the protection when there is no D.C supply in the substation. 7. PROTECTION RELAYS: 7.1 ALL panels shall be provided with over current and earth fault relay (2 O/C + 1E /F) of IDMTL type as follows:- Time range 0 3 sec. Current setting for O/C % In Current setting for E/F 5-40% In Instantaneous element %(when required) 7.2 Under voltage relay on the 33kv side to trip the 33kv C. B. in case of supply voltage failure. Earth fault alarm relay self rest of two normally open contact for local and remote alarm should be connected to the open delta winding of V.T on the 11kv side. 7.3 Transformer Neutral point. this protection shall be definite time earth fault relay connected to the C. T. of the neutral earthing resistor to make trip of 33kv C.B, in case of earth fault 7.4 Differential protection for the transformer. 8. SWITCHGEAR: 8.1 The switchgear shall comply with IEC 60289, completely metal- clad type with suitable air insulated bus bar covered by proper insulation assigned for indoor installation equipped with vacuum type circuit breaker. The switchgear shall be provided with suitable interlocks and adequate safety devices to prevent access to the live compartment. 33 KV and 11Kvcircuit breakers to be withdrawable type. A set of metal shutters shall be provided to cover all live parts. Shutters shall open automatically by positive drive initiated by the movement of circuit breaker carriage. The circuit breaker should be fixed with suitable fixation facility in test position during transportation of mobile substation in order to protect the plug and socket isolating devices. 8.2 CIRCUIT BREAKER OPERATING MECHANISM:- Circuit breaker operating mechanism shall be of the spring powered stored energy. Each equipment shall be provided with visual indicating device to show the circuit breaker "Open" or "closed" it shall operative when the circuit breaker is in the "service" "isolated" and "earthed" positions. (3-21)

39 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA It shall be possible to complete the closing tripping indication and interlock circuits when the circuit breaker is isolated. Locking facilities shall be provided so that the circuit breaker can be locked in each position. The closing mechanism shall be provided with electrical release coils and shall be of "trip free" type. It shall be possible to charge the mechanism spring with circuit breaker ineither the "open" or the "closed" position. In normal operation the recharging of the operating spring shall be commenced immediately and automatically upon completion of the circuit breaker closure. A visual mechanical indicating device shall be provided to indicated the state of the spring " spring charged" when the spring is in condition to close the C.B and "spring free" when the spring not in a condition to close the C.B. The mechanism shall be fitted with local manual spring release preferably by push botton, shrouded to prevent inadvertent operation. The mechanism shall be suitable for motor and hand rewinding (motor should be for a system of 220 V A.C) and shall be suitable for remote control for both closing and opening operations. 9. TRANSFORMER: 9.1 TRANSFORMER SPECIFICATION The transformer and its associated equipment shall comply with the latest issue of IEC6076. It should be as slim as possible to suit the requirement of the substation. The transformer shall have the following characteristics: a) Rated output power (ONAN) 10 MVA, 16MVA b) Duty Step Down, Outdoor service c) Type Core, double wound 3- phase, box type d) Rated voltage at no load H.V 33 kv L.V 11.5 kv e) System frequency 50 Hz f) Interface connection H.V- Delta L.V- star with neutral brought out Through 15 kv outdoor bushing and arrester of 7.3 KV g) Vector group Dyn 11 h) Type of cooling ONAN i) Temperature rise 45 C in top oil by thermometer 50 C in winding by Resistance j) Impedance voltage 7-10% at 75 C and at principal tapping k) System highest voltage H.V 36 kv L.V - 12 kv l) Terminal arrangement Suitable for switchgear connection m) Taps On- load on H.V. side for variation in equal steps from + 7.5% to 10% n) Oil characteristics To be confirmed 9.2 ON LOAD TAP CHANGER: The tap changer is to comply with IEC recommendation. Each transformer shall be equipped with on load tap changer suitable for the rated current of the transformer (+ 20 % over load) on-load tap changer of modern design and robust construction of MR type VACUTAB (machine - fabrick ReinHausen of West Germany). The current breaking contacts shall be contained in a separate oil tank. The tap changer shall be easily accessible so that it could be inspected and if necessary removed without having to remove the cover of main tank. The mechanism derive shall be (ED) type, designed to be controlled through push buttons. In addition to manual operation by means of a suitable operating handle. necessary interlock shall be provided to prevent simultaneous operation of manual and electric drive. The tap changer motor shall be designed for 3 - phase, 416 volt A.C. supply the tap changing process once initiated must be completed even in case of power failure to the driving mechanism. (4-21)

40 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA It shall not be possible for the tap changer to be left in an intermediate position. The tap changer control circuit should be provided with protective device against short circuit when the tap changer is in operation. (To prevent operation of tap changer during short circuit ). The mechanism, fuses, relays and control equipment shall be housed in a suitable weather proof metallic cabinet mounted on the transformer. 9.3 FITTINGS AND ACCESSORIES: The following fittings and accessories shall be provided: a. Conservator to be provided with filter cap and drain valve and a shut off valve between the conservator and transformer tank. b. Oil level gauges marked to indicate normal level at 20 C one at each side of the conservator one for transformer oil and the second for the tap changer oil. c. Explosion vent, double diaphragm type, with port hole type oil level gauge. With one contact for tripping. d. Dial type thermometer to indicate top oil temperature with maximum reading pointer and 2 sets of contacts suitable for alarm and trip. e. Winding temperature indicator to indicate the hottest spot temperature of the winding with maximum reading indication and two sets of contacts for alarm and trip. f. Drain valve plug g. Dehydrating breather for each part of conservator h. Buchholz relay, double float type and flap with alarm and trip contacts and test terminal block. i. Gas relay for OLTC with trip contact j. Manhole of adequate size to permit internal inspection of the transformer. k. Air release plugs on the top of the necessary transformer parts l. Two nos.. filter valves with caps. m. Rating and terminal plate to be chromium plated n. Two nos. Grounding pads. o. Lifting and jacking lugs p. Water proof metallic junction box to house all terminals, controls, etc q. Alarm and signaling relays for all control and protection equipment of the transformer. All these devices shall be mounted on the 33 kv switchgear panel or on transformer control board. 9.4 PAINTING A primary coat shall be applied immediately after cleaning all ungalvanized metallic parts thoroughly. An oil and weather resistance type second coat shall then be applied and the transformer finished in aluminum metallic paint. 9.5 INSULATING OIL The transformer shall be supplied with first filling of oil. The insulating oil shall be SHELL DIALA (B) or BP Energol JS-V/JS-A no other Oil will be acceptable 9.6 TESTING OF TRANS PORMER In addition to the routine test which shall be carried out on the power Transformer. A type test of temperature rise, and impulse withstand voltage test must be carried out on one transformer test should be carried out by KEMA or CESI or EDF of France. 9.7 LOSS EVALUATION The tolerance permitted is + 10% of the evaluated guaranteed total losses mentioned in the offer. Any transformer with losses more than + 10% will be rejected for transformers with total losses within + 5% of the evaluated guaranteed losses, no variation to the contract price shall be made. For transformers where the total evaluated losses between + 5% to + 10% of the total guaranteed losses, the contract price shall be reduced by the cost of the difference between the total evaluated costs of losses and the 105% of the total evaluated losses according to the following values:- Iron losses 1800 USD per kw. copper losses 600 per kw. (5-21)

41 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA for any transformer with total losses less than 100% of the guaranteed losses, no variation to the contract price shall be made 9.8 COMPENSATION FOR EXCESSIVE TEMP ERATURE RISE If the transformer C.M.R. output must be reduced by n% to maintain the rise of temperature of any part of the transformer within the guaranteed limits, the compensation shall represent twice times n % of the corresponding F.O.B. price of the transformer. 10. DC SUPPLY:- Two kinds of DC supply are required: - The first is the main DC supply for control and protection is to use (110 V) DC system consist of nickel - cadmium alkaline type battery set of (55) ampere - hour, and battery charger of (20) Amp Current rating, of floating operating mode able to supply the control and protection circuit load and at the same time to charge the battery. the R.M.S ripple voltage on the DC side shall be less than 1% of the mean DC voltage. On the front of the charger housing shall include the following: - Operating on/off switch with red and green lamps respectively. DC voltmeter indicating charger or battery voltage with selector switch. DC Ampere meter to indicate the total output current. the second emergency DC supply is to use a capacitor storage units instead of the main DC in case of low or failure of DC voltage of battery and battery charger set. the charging of these capacitors shall be from the auxiliary transformer through rectifier, and this supply is to feed all protection and tripping circuit of 33kv and 11kv C.B including protection circuit of transformer tripping relay DC DISTRIBTION BOARD Consist of necessary MCCB and MCB s with suitable current ratings and sufficient number to fulfill all requirement of the DC distribution. DC under voltage and earth fault relay & indicators to be provided. voltage & current meters are required. (6-21)

42 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA 11. CONNECTION The required arrangements regarding the connection between the substation with the network and transformer with the switchgear shall be as follows: KV CONNECTION The incoming connection to the 33 kv isolator shall be by a flexible single core cable with one end to be permanently connected to the incoming side of the isolator, or be connected after rewound the cable so the box to be of air insulated and easily worked. The other end to be of clamp for over head line connection operated from the ground by the telescopic insulating rod (the rod is to be part of the S/S) KV CONECTIONS : The outgoing feeders of the 11 KV switchgear shall be connected to the line as for the 33KV side TRANSFOMER CONNECTION The connection between transformer with H.T & L.T switchgear shall be single core cables. All the connection & live parts to be protected against direct touch so that the connection to the transformer on 33KV and 11KV sides shall be through plug in termination CABLES The 33&11kv cables are to be of flexible type EPR single core copper conductor and according to IEC recommendation: The 33kv cable for incoming to be sq mm cross section EPR type of 30 meter length with suitable clamps. The 11 kv cable for outgoing to be sq mm cross section EPR type of 50 meter length for each feeder. For transformer connection the cables to be sq mm XLPE TYPE ON 33KV SIDE AND sq mm XLPE type on 11kv side for 16 MVA mobile substation and Sq. mm. XLPE type for 10 MVA substation. Each cable has to be mounted on moving drum with arrangement for the connection on the side of the switchgear. the drum to be mounted on a stand fixed to the trailer with easy movable action for pulling & rewinding the cable. 12. EARTHING THE NEUTRAL POINT OF THE TRANSFORMER:- The neutral point of the 11 kv side of the transformer to be earthed through an earthing resistance of 21.1 OHM. 11KV 300 AMP rated current 30 sec-rated time. The housing of the resistance should include 11KV 400 AMPS on load isolator and 7.3 KV arrester. Detailed design specification, descriptions, catalogues, methods of mounting to be submitted with the offer which include : Anticorrosion methods for resistor plates. Temp. rise curves The effect of the mechanical stresses on the resister during faults. The resistor shall be equipped with /5 A CT and E/F relay to be provided 13. AUXILIARY SUPPLY 13.1 AUXILIARY TRANSFORMER:- An auxiliary transformer of (33/0.416) KV voltage and 50 KVA rating Oil immersed hermetically sealed to be supplied completed with all necessary fitting such as off load tap changer, pressure relief valve and mechanical oil level indicator. to be protected by 33kv switch fuse combination with suitable 33kv, 5Amp HRC fuses. The switch must be open automatically when each fuse has blown AC DISTRIBUTION BOARD Consist of necessary MCCB and MCB s with suitable current ratings of sufficient number to fulfill all requirements of the AC distribution. AC under voltage and earth fault relays and indicators to be provided. Voltage & current meters are required. (7-21)

43 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA 14. DRAWINGS AND INSTRUCTION BOOKS : 14.1 The following document shall be submitted in three copies with the tender documents, in English language. Technical literature giving full description of the trailer truck, transformer & switchgear offered with all details of the S/S and their contents. Also outlined drawings with dimensions showing the front side and top elevation of the trailer substation. Single line diagram to show the connection of all equipment of the S/S in detail Complete description of all equipments, Relays, C.Ts, P.Ts, C.Bs, transformer, batteries, battery charger etc Catalogues of the manufacturer for mobile s/s. Valid ISO 9001 certificate of the manufacturer of 33KV & 11KV C.Bs, 33KV & 11KV switch gears 33/11.5 KV power transformer Type test certificates of identical equipments. Reference list of manufacturer and exported mobile s/s. Incomplete tenders are liable to rejection 14.2 The document to be furnished by the successful tendrer in English language include five copies of the following drawing within two months from the date of the order. Schedule of the anticipated shipping dates. Installation drawings. Out lined drawings of the S/S, and single line diagram Sectional elevation of all part of S/S General arrangement and schematic diagram of all equipment One set of reproducible print (velograph ) tracing cloth etc of all approved drawings Two copies of final as built drawings for each s/s. NOTE : It must be noted that all drawings are subjected to approval before manufacturing BEFORE SHIPMENT : All instructions for maintenance, testing and commissioning of all relays and equipment s, shall be supplied. 15. PACKINGS The supplier will pack or protect the goods in the most appropriate manner. He will be responsible for any loss or damage arising from careless packing or protection unto the place of final destination After completion of the inspection and tests at the factory each item shall be packed for export shipment. All parts provided for shipping purposes only and which are to be removed at the time of erection shall be conspicuously tagged.the method of packing shall be such as to protect all of the items against excessive corrosion or dampness, and shall afford adequate protection against breakage or other injury, or loss due to breakage of cases or crates from the time leaves the factory until finally inst. allied during which time the apparatus will travel by rail, by a long sea voyage again by rail or truck to the site of the stores. The apparatus will also undoubtedly stand on wharves and in the open during and in between periods of transportation and will there be exposed to heavy rains, hot sun, humid climate and sudden changes of temperature. Owing to the numerous handling, extra ordinary care should be given to the packing of the equipment and especially the item having insulating material to prevent the injury due to moisture from sources external to the packing or from excessive condensation with the packing. 16. INSPECTION The material shall be subject to inspection and test by our inspectors at any time during manufacturing. (8-21)

44 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA The manufacture shall provide all inspection facilities for the said inspection and testing. All testing and inspection shall be made at the place of manufacture. The inspector shall have the right of rejecting any portion of the material at any time during manufacture if it does not meet with the requirements of this specification in all particulars. He shall have the right of overseeing the packing and shipping of all materials to be supplied. 17. Test at manufacturer s work. Manufactures work shall comprise type tests and routine tests, and a complete invitation ( full accommodation and traveling cost ) of four engineers for two weeks on the manufactures account for witnessing the tests. A. TYPE TEST :- These tests are in general, those detailed in the IEC standards which pertain to the equipment being tested equipment type test approve the general design of the equipment. the manufacturer may submit test certificates of tests which have been carried out on identical equipments. The inspector after referring to the COE may accept such certificate in lieu of the specified type test or to reject them. The type test prescribed shall be carried out in all cases where such certificates are not available or are rejected. The type test shall be carried out according to the IEC standards. certified test certificates issued by KEMA or any other qualified laboratory after agreement with the purchaser for type tests carried out on identical equipment will be accepted in lieu. B. routine test : The routine test shall be carried out on all equipment according to latest IEC standards :- 18. guarantee:- The tender shall confirm that mobile substations against defects arising from faults in design, materials and workmanship, for a period of (12) months from commissioning or (18) months from delivery whichever period expires earlier. 19. spare parts:- The tenderers are requested to give spare list sufficient for five years operation with unit price for each item, and also see spare parts list. to submit unit price per piece and per set ( if necessary). Itemized prices for recommended spare parts indicated in a list attached. 20. technical specification :- The required technical specification of the main equipment s are listed in tables. the tenderer is required to fill tables fully. any values are site rating values. (9-21)

45 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA SCHEDULE "A" SCHEDULE OF GUARANTEED PERFORMANCE AND OTHER TECHNICAL PARTICULARS The schedule is to be fully completed by the tenderer to provide detailed characteristics of the equipment and materials offered, which shall be guaranteed. This is an important point which shall be taken into consideration during tender analysis. TRANSFORMERS: # Description Unit Specification offered 1 Name of manufacturer 2 Country of origin 3 Standard on which performance data is based 4 Continuous maximum rating for the specified temperature rise and ambient temperature ( vide class 5(1)-(KVA) a. ONAN rating 5 Rated temperature rise a- Oil by thermometer C b- Winding by resistance C 6 Hottest spot temperature 7 No-load voltage ratio at normal tap 8 Exciting current referred to H.V.50 HZ Amp. a- 90% rated voltage b- 100% rated voltage c- 110% rated voltage 9 Power factor of exciting current at 100% rated voltage and 50 Hz 10 Iron losses at 50 Hz and at kw a- 90% rated voltage b- 100% rated voltage c- 110 % rated voltage 11 Cupper losses at full load (ONAN) rating at 75 C Kw 12 Total losses Kw 13 Resistance voltage at full load and at 75º C % 14 Reactance voltage of full load and at 75º C % 15 Impedance voltage at full load and at 75 ºC % a- At normal tap b- At highest tap c- At lowest tap 16 Resistance of H.V. winding per phases at 20ºC Ohm 17 Resistance of L.V winding per phase at 20º C Ohm 18 Regulation at full load 75º C a- 1.0 power factor b- 0.8 P.F lagging 19 Efficiency at 75º C % a- 100% load b- 75% c- 50% d- 25% 20 Calculated thermal time constant (ONAN) Hrs 21 Maximum flux density at normal voltage and (KI/ eq.cm) frequency and at normal ratio a- Core b- Yoke 22 Maximum flux density at 110% voltage and (KI/ eq.cm) (10-21)

46 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA # Description Unit Specification offered Frequency and at normal ratio a- Core b- Yoke 23 Insulation of a- core bolts b- core bolts washers c- side plates d- core laminations 24 Current density in windings A/cm 2 a- H.V. winding b- L.V. winding 25 Insulation on copper 26 Insulation strength of winding H.V L.V KV H.V L.V a- Impulse full wave b- Impulse chopped wav c- Applied voltage test d- Induced voltage test kv 27 Insulation strength of terminals 33kV 11kV a- over voltage test b- Minimum impulse withstand voltage c- Minimum impulse withstand voltage d- Minimum puncture or oil-immersed withstand voltage 28 Type of core 29 Tap changer a- manufacturer b- type c- time required for one tap change d- no. of steps e- Step of one tap in percent of rated voltage % 30 Dimensions of tap-changer control panel cm 31 Thickness of transformer tank mm a- sides b- bottom 32 Weights and dimensions Kg H.V L.V a- Net weight of core b-net weight of copper c- Net untanking weight of core, frame and coil d- Volume of insulating oil (Imp-gall) e- Net weight of insulating oil f- Total weight of transformer less oil Tons g- Weight of the largest shipping package Tons h- Crane lift for untanking core and coils M i- Crane life for removal of bushings M j- Dimensions of transformer M I- Under base to tap most point II- Under base to bushing mounting flange III- Overall breadth IV- Overall length k- Overall shipping dimensions of the largest package 33 Noise level at a distance of 3 meters db (11-21)

47 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA TECHNICAL SPECIFICATION FOR INDOOR CIRCUIT BREAKER # Description Unit specification offered 11kV 33kV 1 Make 2 Type 3 Normal rated voltage V 4 Normal current rating A 5 Breaking capacity a-symmetrical KA(r.m.s) b- symmetrical MVA b-asymmetrical KA(r.m.s) 6 Making capacity KA peak 7 Rated short time current 1 sec 8 Capacitive breaking current A 9 Capacitive making current A 10 Certification for the above capacities a- Name of certifying authority b- Number of certificates issued by the Authority a copy of which is enclosed with the tender 11 Impulse voltage withstand 1.2/50 wave K.V crest 12 Standard 1 min.50 Hz withstand K.V(r.m.s) voltage 13 temperature rise of main contacts continuous operation at rated current 14 Opening time a- Without current msec b- At 100% breaking current msec 15 Total break time msec 16 Making time msec 17 Type of closing mechanism 18 Power at normal voltage for shunt trip w coils 19 Minimum clearance in air a- between phases mm b- between live part & earth mm 20 weight of complete circuit breaker kg (12-21)

48 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA TECHNICAL SPECIFICATION OF CURRENT TRANSFORMERS # Description Unit 1 make 2 Impulse voltage withstand (1.2/50 wave) KV(peak) 3 I min.power frequency withstand voltage KV.(r.m.s) 4 Rated short time current (3 sec) K.A(r.m.s) 5 Temperature rise of windings on C continuous operation at rated current & output 6 For feeder circuit: a- Type b- Accuracy class c- Transformation ratio d- Current ratio error % e- Phase displacement min 7 For transformer circuit: a. Over current & instrument 1- Type 2- Accuracy class 3- Transformation ratio 4-Current ratio error 5-Phase displacement b. Differential 1- Type 2- Accuracy class 3- Transformation ratio 4- Correction C.T. ratio 5-Current ratio error 6-Phase displacement 8 For metering transformer circuit 1- Type 2- Accuracy class 3- Transformation ratio 4-Current ratio error 5-Phase displacement 9 For metering Auxiliary Transformer circuit 1- Type 2- Accuracy class 3- Transformation ratio 4-Current ratio error 5-Phase displacement specification offered 11kV 33kV (13-21)

49 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA TECHNICAL SPECIFICATION OF THE VOLTAGE TRANSFORMER # Description Unit specification offered 11kV 33kV 1 make 2 type 3 rated output VA 4 Rated frequency Hz 5 Number of phases (3 phase/single phase) 6 Transformer ratio 7 Accuracy class 8 Ratio error % 9 Phase displacement min 10 Temperature rise limit at rated primary C voltage 11 Rated voltage factor (1,9 for 8 hrs ) 12 Fuse protection a- Rated primary side A b- Rated secondary side A 13 Insulation level A a- Impulse withstand voltage KV(peak) b- I min. power frequency withstand KV(r.m.s) voltage 14 Dimensions a- Length mm b- Width mm c- Heigh mm TECHNICAL SPECIFICATION FOR THE SWITCHGEAR # Description Unit specification offered 11kV 33kV 1 make 2 type 3 Bus Bar a- Normal current rating A b- Temperature rise on continuous operation C at normal current c- Cross sectional area mm 2 d- Insulation of Bus Bar e- Maximum working temperature of busbar C insulation f- Bus bar joints insulation g-- Minimum clearance between phases mm h- Minimum clearance between phases & kv earth 4 Service voltage kv 5 Highest voltage kv 6 Impulse withstand voltage K.V(peak) 7 1 Min. power frequency withstand voltage K.V(r.m.s) 8 Dimension a- length mm b- width mm c- height mm (14-21)

50 Technical Specification of 33/11 kv Mobile Sub-Station for 1 10 & 1 16 MVA SCHEDULE (B) OIL CHARACTERISTICS TABLE (TO BE COMPLETED BY THE TENDERER) # DESCRIPTION UNIT SPECIFICATION 1. MAKERS NAME 2. REFERENCE NAME OF OIL 3. SLUDGE VALUE % 4. FLASH POINT (CLOSED) C 5. POUR POINT C 6. VISCOSITY AT 21 C CST 7. ELECTRIC STRENGTH (BREAK DOWN KV VOLTAGE) 8. ACIDITY (NEUTRALIZATION VALUE) MG/ KOH/G - TOTAL - INORGANIC 9. SAPONIFICATION VALUE MG/ KOH/G 10. COPPER DISCELERATION 11. CRACKLE 12. SPECIFIC GRAVITY 13. SULFER CONTENT 14. DIELECTRIC DISSIPATION FACTOR (15-21)

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026 TECHNICAL PERTICULAR FOR 1.6 MVA 6.6/0.433 KV SERVICE TRANSFORMER 1.00.00 GENERAL 1.01.00 Service SERVICE 1.02.00 Make ASHOK/VOLTAMP/DANKE/CGL 1.03.00 Type CORE 1.04.00 Location OUTDOOR 1.05.00 Specification

More information

Technical Specification of GECOL. Packaged Transformers

Technical Specification of GECOL. Packaged Transformers GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

TGK Prefabricated Substation Technical Data

TGK Prefabricated Substation Technical Data TGK Prefabricated Substation Technical Data Ref Item Data 1 General Technical 1.1 Frequency (Hz) 50 1.2 Transformer Rating (kva) 315/750 1.3 Transformer Primary Voltage (kv) 11 1.4 Transformer Secondary

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

General Specification and Technical Requirement of 45 MVA 132/33kV Mobile Substation

General Specification and Technical Requirement of 45 MVA 132/33kV Mobile Substation General Specification and Technical Requirement of 45 MVA 132/33kV Mobile Substation MINISTRY OF ELECTRICITY, REPUBLIC OF IRAQ - 1 - Contents MOE/45 MVA,132/33 KV/Mobile Substation Part-1 General Specification

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

Distribution transformers Efficiency over life-cycle

Distribution transformers Efficiency over life-cycle Distribution transformers Efficiency over life-cycle ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

31-SDMS-01 REV. 03 SPECIFICATIONS FOR

31-SDMS-01 REV. 03 SPECIFICATIONS FOR 31-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE DISTRIBUTION PANEL This specification is property of SEC and subject to change or modification without any notice CONTENTS Clauses: Page No. 1.0 SCOPE

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES

More information

TRANSFORMERS UP TO 750 kv

TRANSFORMERS UP TO 750 kv Electric Co. Ltd. TRANSFORMERS UP TO 750 kv CONTENTS General... 2 Products... 3 Construction...4 Magnetic core... 4 Windings...5 Frame structure... 6 Connections...6 Tap changer and motor drive...7 Tank...

More information

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date: 10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may

More information

MEDIUM POWER TRANSFORMER

MEDIUM POWER TRANSFORMER MEDIUM POWER TRANSFORMER MEDIUM POWER TRANSFORMER FROM 3,15 TO 31,5 MVA HIGHEST VOLTAGE FOR MATERIAL 72,5kV GENERAL CHARACTERISTICS Three phase oil-immersed naturally cooled type ONAN medium power transformers.

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : : DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : FOREWORD : Even though 11KV Drop Cut Fuse Cut Outs are widely used for protection / isolation of distribution transformers, their quality

More information

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.

More information

Section V DC Nickel Cadmium Alkaline BATTERY

Section V DC Nickel Cadmium Alkaline BATTERY Section - 7 TECHNICAL SPECIFICATION OF 110V DC Nickel Cadmium Alkaline BATTERY TECHNICAL SPECIFICATIONS & REQUIREMENTS OF 110V DC Nickel Cadmium Alkaline Battery 7. 1 GENERAL This section of the document

More information

7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION

7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION 92 Section VI. Schedule of Requirements 7.0 Technical Guarantee Specification of 60MV, 132/33 Mobile Substation TECHNICL DT SCHEDULE 60MV, 132/33 MOBILE SUBSTTION ITEM DESCRIPTION UNITS REQUIRED GURNTEED

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The

More information

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2 BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002

More information

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable

More information

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch 1. Scope:- This specification covers manufacturing, testing and supply of 11KV 200Amp. 50Hz Air Break switches for outdoor installation

More information

SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. The networks are mainly of outdoor type. The basic parameters are set out below:

SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. The networks are mainly of outdoor type. The basic parameters are set out below: SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. A. SYSTEM INFORMATION A-1 System Conditions The networks are mainly of outdoor type. The basic parameters are set out below: Nominal system voltage between

More information

Metal Clad VCBs ~ Mk1

Metal Clad VCBs ~ Mk1 Metal Clad VCBs ~ Mk1 DUVI 150/40 ROLL ON FLOOR VCBs Range: 6kV, 00A, 1.5kA, 12kV, 150A, 40kA ( 4A000A Bus-Bars ) ` Widest range for MV (up to 6kV) Distribution Networks Megawin make metal clad VCB Panels

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

COMPACT SUBSTATION GUIDE

COMPACT SUBSTATION GUIDE COMPACT SUBSTATION GUIDE Certificate Number FM35831 1 The substation is a compact enclosure consisting of MV switchgear, a transformer and an LV switchboard located in three separate compartments which

More information

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum

More information

(A Government Company) CENTRAL WORK SHOP KOTHAGUDEM

(A Government Company) CENTRAL WORK SHOP KOTHAGUDEM The Singareni Collieries Company Limited (A Government Company) CENTRAL WORK SHOP KOTHAGUDEM-507101 Vendor meet for supply, erection & commissioning of 3T capacity induction melting furnace on Trunkey

More information

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement. INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side

More information

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear. Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear www.siemens.com/energy Technology s Contents Application Page Benefits 2 Typical uses 2 and 3 Technical

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION SECTION - III TECHNICAL SPECIFICATION OF AB SWITCH & HG FUSE NESCO : TN/ 17427/14.11.11-1 - 1. 33 KV 200 Amp 3 Pole HG Fuse (Horizontal Mounting Type) Quantity 15 Sets Technical Specification 1. SCOPE:

More information

PART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS

PART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS PART C: GUARANTEED TECHNICAL PARTICULARS OF 33 KV, 2x5/6.67 MVA RURAL TYPE SUB-STATION MATERIALS C.8.1: TECHNICAL PARTICULARS AND GUARANTEES OF 33/11KV, 5 /6.67 MVA POWER TRANSFORMER (To be filled up by

More information

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. DRAFT SPECIFICATION NO : RDSO/PE/SPEC/D/PS/0010-99 (REV. 0 ) SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. 0. FOREWORD 0.1 This specification covers manufacturing and

More information

43-SDMS-01 SPECIFICATIONS FOR

43-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3

More information

with Vacuum Circuit Breaker HAF

with Vacuum Circuit Breaker HAF M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS 1 TABLE OF CONTENTS ABOUT SVEL GROUP CAST-RESIN TRANSFORMERS ACCESSORIES AND OPTIONAL EQUIPMENT ENCLOSURE AND HOUSING TESTS AND QUALITY

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected. Issued: January 2013 Copyright by ZPUE Katowice S.A. All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

West Bengal State Electricity Distribution Co. Ltd.

West Bengal State Electricity Distribution Co. Ltd. West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 240 Kvar

TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 240 Kvar SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION OF ELECTRICITY PEDE TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 240 Kvar Eng. Kazem Abd Al-Hamid Eng. Ali

More information

TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 140 Kvar

TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 140 Kvar SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION OF ELECTRICITY PEDE TECHNICAL SPECIFICATIONS for LOW VOLTAGE CAPACITOR BANKS 140 Kvar Eng. Kazem Abd Al-Hamid Eng. Ali

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information