Sentron SMP Switchboards

Size: px
Start display at page:

Download "Sentron SMP Switchboards"

Transcription

1 8 SWTBOARDS Sentron SMP Switchboards onstruction Details Simplified system design. A typical SMP switchboard consist of a floor mounted, wall supported service section, and a distribution section. The wireway can also be added where required by the local utility or if additional cable termination space is required. Wireways are modular to allow flexibility The wireway is available in 2 depths to suit customer needs. Wireway has split front doors as standard with optional hinged doors. The lug pads are standard NMA hole pattern and accept up to 5 mechanical lugs or 6 compression lugs. Service ntrance Sections house a variety of equipment. b Service ntrance Sections. Service sections can be fed directly from overhead by cable. Service entrance sections equipped for bottom feed will accept cable from underground directly into the service section. b Utility Metering n addition to the main device, the service section contains utility metering provisions. old metering provisions (T s on the load side of the main device) are furnished. The T s are provided by the utility company. The compartment will be built to utility company standards, with hinged doors and provisions for utility metering equipment. b User Metering The service section provides space for the Siemens Digital Meter with remote display, and it s associated components. b Main protective device The MB is mounted individually so that it can be located quickly in an emergency. SMP switchboards will accommodate different types of main circuit breakers. Selection depends on the characteristics of your individual electrical system. Distribution Sections have ample wiring room and front accessibility. Generous top or bottom gutters have been created by locating the bus-link in the top or bottom of the distribution section, so there s ample room to run cables into the distribution section and make connections. Standard bolted covers allow complete access to load conductors. Future flexibility comes standard in the Siemens SMP switchboard. The distribution section can accommodate any combination of panel mounted devices, including MBs and fusible disconnect switches. Operating temperatures are in accordance with SA Standards Bus bars are available in standard tin-finished aluminum or optional silver-finished copper. Standard bus is sized on the basis of heat rise criteria, in accordance with SA 22.2 #31. All bus bars are sized to limit heat rise to above an ambient temperature of 40. onstruction Bus-Link onnections are accessible from the front. The Bus-Link can be bolted from the front of the switchboard. ach bus-link is attached by grade five bolts to assure solid joints between sections, and to maintain full bus ampacity through the joint. To make installation and servicing of the bus-link easier, all phase and neutral busses are stacked one above the other. able Terminals Screw mechanical connectors (lugs) are provided as standard equipment. 8-2 Siemens anada Limited Power Product atalogue 2014

2 SMP Switchboard ntroduction Whether the design is for a 240V A, 400 ampere system; a 600V A, 1 A ampere system; or something in between, Siemens Sentron Switchboards should be considered. very aspect of design has been aimed at improving layout convenience, reducing installation costs, and minimizing the impact and cost of system changes. These switchboards provide the space saving construction and service flexibility necessary in systems for light industrial plants, retail strip malls, and commercial buildings. Service entrance sections of the SMP accepts a wide range of Sentron Molded ase ircuit Breakers as main disconnect devices. The SMP switchboard is designed for special configurations. t can be equipped with incoming and outgoing cable/conduit connections, supplied with metering and other special features. The distribution sections of all Sentron Switchboards are designed with improved wiring space and greater accessibility. They re also designed for easier installation and maintenance. onveniently located bus-link without compromising useful wiring gutter space, and standard bolted gutter covers offer complete access to load conductors. Front accessibility to bus and protective devices makes adding or replacing circuit breakers or switches quick and easy. SMP Switchboard Features and Ratings b Main bus rated up to 1 ampere. b Rear of all sections aligned so that switchboard can be floor mounted and secured against the wall. b Front connected and front accessible. b Main devices individually mounted. Molded ase Breaker: amps. b Branch Devices panel mounted. Molded ase Breaker: 15 1 amps fixed. Quick-Make Quick-Break Fusible Switch: A SMP Specifications (Table 1) nclosure Type Dimensions Main or Distribution Wireway Volts SMP Switchboard MA 1 Dripshield (option) 38 W x 90 x Dp 24 W x 90 x Dp or.5 Dp 600V Max Amperes 400-1A Bus Type Bus Bracing nterrupting apacity ntry Main Device Branch Devices (Unit Space) Metering Devices Other Options Aluminum (tin plated) opper (silver finished) optional 50 KA KA (optional) Main and Distribution Section Dimensions (Table 2) Switchboard Type 50 KA KA (optional) able only (top or bottom) MB 400-1A b 80% Rated b % Rated (option) 52.5 in Main with Distribution Section, or 22.5 in MUD Section, or 60 in Distribution Section General Siemens Digital Meter with Remote Display SADU (option) Feeder Breakers Only SPD Units Sill hannels (1.5 ) Lifting ooks Access Revised 02/19/2015 Dimensions - nches (mm) W D SMP Front 90 (2286) 38 (9) (324) 600 Volts A Maximum 1 Ampere Mains 1 Ampere Maximum Branch SA Short ircuit Rating,000A R Maximum SA ertified To: AN/SA-22.2 No. 31-M89 SA File #LR (49454) 8 SWTBOARDS a Only available as a Wireway. Siemens anada Limited Power Product atalogue

3 8 SWTBOARDS Sentron SMP Switchboards Protective Devices - Molded ase ircuit Breakers Standard Breakers are designed for commercial, industrial, institutional and other heavy duty applications. They are rated up to 600V A and 0V D. Their interrupting ratings are higher than normal duty breakers. igh nterrupting Breakers are designed for heavy duty applications where the interrupting requirements exceed the ratings of heavy duty breakers. They are rated up to 600V A. urrent Limiting Molded case breakers incorporate the exclusive -T- blow-apart interruption principle. They meet the SA requirements for current-limiting breakers. urrent-limiting circuit breakers can limit the let-through 2 t to a value less than the 2 t of one-half cycle wave of the symmetrical prospective current without any fusible elements when operating within their current-limiting range. Main Breaker Selection (Table 3) (KA) Max Ampere Breaker atalogue Rating Type Number 240V 480V 600V Available Trip Values XD6 X, 2, 0, 300, 0, 400 D6 6, 2, 0, 300, 0, 400 D6, 2, 0, 300, 0, 400 D6, 2, 0, 300, 0, 400 SD6 S, 300, 400 SD6 S, 300, 400 SD6 S, 300, 400 LXD6 LX 450, 500, 600 LD6 L6 0, 300, 0, 400, 450, 500, 600 LD6 L 0, 300, 0, 400, 450, 500, 600 LD6 L 450, 500, 600 SLD6 SL 300, 400, 500, 600 SLD6 S6 300, 400, 500, 600 SLD , 400, 500, 600 MD6 M6 50 MD6 M 50 MD6 M SMD6 SM , 700, 800 SMD6 S , 700, 800 SMD , 600, 800 ND6 N , 900, 0, 1 1 ND6 N , 900, 0, 1 ND6 N 900, 0, 1 SND6 SN , 0, 1 SND6 S , 900, 0, 1 SND6 800, 900, 0, (6) 10.0 (4) 8. (210) 7.9 (201) (193) (299) 13.4 (341) (227) 13.0 (330) 12.0 (305) 13.0 (330) Selection Branch Breaker Gutter Dimensions For 38 W Distribution Section (Table 5) A B D F G K M A B D F 3.75 (95) 3.75 (95) 5.00 (127) 5.00 (127) 5.00 (127) 3.75 (95) (4) (4) 8-4 Siemens anada Limited Power Product atalogue 2014

4 Branch ircuit Breaker Selection a (Table 4) Selection Breaker Type Available Trip Value Ampere Ratings Mounting eight - nches (mm) Max Rating (KA) Twin Single Gutter f 240V 480V 600V BL 15, 20, 30, 40, 50, 60, 70, 80, 90, 3.75 (95) A 10 BLF (GF) 15, 20, 30, 40, 50, (95) A 10 BL (GF) 15, 20, (95) A 10 BL 15, 20, 30, 40, 50, 60, 70, 80, 90, 3.75 (95) A 22 BL (GF) 15, 20, 30, 40, 50, (95) A 22 BQD6 e 15, 20, 30, 40, 50, 60, (95) A D2 15, 20, 30, 40, 50, 60, 70, 80, 90, 3.75 (95) 3.75 (95) B D4 15, 20, 30, 40, 50, 60, 70, 80, 90,, 110, (95) 3.75 (95) B D6 15, 20, 30, 40, 50, 60 70, 80, 90,, 110, 1 D6 15, 20, 30, 40, 50, 60, 70, 80, 90, 110, 1 Q2 Q2 Q2- FXD6 FD6 FD6 XD2 XD6, D6 D6 D6 SD6 SD6 SD6 LXD6, LD6 LD6 LD6 SLD6 SLD6 SD6 LMD6 LMD6 MD6 MD6 MD6 SMD6 SMD6 SMD6 ND6 ND6 ND6 SND6 SND6 SND6 Breaker Type 60, 70, 80, 90,, 1,, 175,, 2 60, 70, 80, 90,, 1,, 175,, 2 60, 70, 80, 90,, 1,, 175,, 2 70, 80, 90,, 1,, 175,, 2, 0 70, 80, 90,, 1,, 175,, 2, 0 70, 80, 90,, 1,, 175,, 2, 0, 2, 0, 300, 0, 400, 2, 0, 300, 0, 400, 2, 0, 300, 0, 400, 300, 400, 300, 400, 300, 400, 300, , 500, 600 0, 300, 0, 400, 450, 500, , 500, , 400, 500, , 400, 500, , 400, 500, , 700, , 700, , 600, , 900, 0, 1 800, 900, 0, 1 800, 900, 0, 1 800, 0, 1 800, 900, 0, 1 800, 900, 0, 1 Available Trip Value Ampere Ratings 3.75 (95) 3.75 (95) B 3.75 (95) 3.75 (95) B 3.75 (95) 3.75 (95) F 3.75 (95) F 10 (4) 10 (4) 10 (4) 10 (4) 10 (4) 10 (4) 10 (4) 10 (4) D D G M M K K Max Rating (KA) Mounting eight - nches (mm) Twin Single Gutter (mm) 240V 480/277V 480V 600/347V 600V NGB 15, 20,, 30,, 40, 50, 60, 70, 80, 90,, 110, (95) 13.98" (5) 14 NB B NDG LDG NFG LFG 15, 20,, 30,, 40, 50, 60, 70, 80, 90,, 110, 1 15, 20,, 30,, 40, 50, 60, 70, 80, 90,, 110, 1 50, 60, 70, 80, 90,, 110, 1, 50, 60, 70, 80, 90,, 110, 1,, 110, 1,, 175,, 2, 0, 110, 1,, 175,, 2, (95) (295) 5.00 (127) (276) 5.00 (127) (276) NG 0, 300, 0, (158.75) 6. (158.75) 13.42" (341) SWTBOARDS Space includes housing frame plate with blank cover plate. Provision includes all necessary mounting hardware, less circuit breaker, and includes housing frame cover plate with breaker handle opening. 1 to 6 poles may be mounted in 3.75 (95) of unit space Accessories such as shunt trips on three pole breakers require 6. (159) of unit space. Ground fault is not available on branch Sensitrip breakers. e Also 10KA at 600Y/347 Volts. f Refer to Table 5 for layout dimensions. Siemens anada Limited Power Product atalogue

5 Protective Devices - Fusible Disconnects Selection Fuse Selection The Proper Fuse Type for the Application is Selected Using the Following Parameters: b Voltage Requirements b onductor Ampacity b orsepower Requirements b Maximum Available RMS Fault urrent b SA Fuse lass Maximum VB P Ratings (Table 6) Volts Amp 3 Phase Single Phase Rating Branch Switch onnectors (Table 10) d Switch Ampere Rating Wire and able Range 30 (1)#14 #4 AWG (u or Al) 60 (1)#14 #4 AWG (u or Al) (1)#10 #1/0 AWG (u or Al) (1)#6 AWG-0kcmil (u or Al) 400 (1)#1/0 AWG-750 MM OR (2)#1/0 AWG-0 MM (u or Al) 600 (1)#1/0 AWG-750 MM OR (2)#1/0 AWG-0 MM (u or Al) Branch Switch Gutter Dimensions Maximum VK P Ratings (Table 9) For 38W Distribution Section (Table 8) Volts Amp 3 Phase Single Phase 7.5" (191) 6." (159) Rating /30A VK Switch " (191) 6." (159) /60A VK Switch 7.5" (191) /A VK Switch 7.5" (191) Gutters (Table 12) nd Gutters Side Gutters Ampere Minimum - Minimum - Rating nches (mm) nches (mm) (305) 7.9 (201) (305) 7.9 (201) 5.0" (127) /A VK Switch 10.0" (4) 10.0" (4) 30/30A VB Switch 7.5" (191) 10.0" (4) 10.0" (4) /A VB Switch 7.5" (191) 8.0" (203) 9." (2) 60/60A VB Switch 7.5" (191) /A VB Switch 10.0" (4) 400A thru 600A VB Switch 15.0" (381) Branch Switches 600V Maximum (Table 11) Rating Max Fusing Mounting eight Ampere Voltage 38 W 30/30A & 60/60A (VK) e 600V lass,, R 6. (159) /A (VK) e 600V lass,, T 7.5 (190) /A (VK) e 600V lass,, T 10.0 (4) 30/30A & 60/60A (VB) 600V lass 7.5 (190) /A (VB) 600V lass 7.5 (190) /A (VB) 600V lass R,, T 10.0 (4) 400A & 600A (VB) 600V lass,r,,t 15.0 (381) Switch Accessories (Table 13) Fuse Pullers (VK) at. No. 30 or 60 Amp FP2 Amp FP3 Amp FP4 8 SWTBOARDS SA Fuse lasses (Table 14) nterrupting lass Amperes Volts (A) Ratings 2 t, p (Let-Thru) ircuits Standard ode 1-600A 0 and 600V 10,000A Less than or less 10,000A available K a Fast Acting 1-600A 0 and 600V 50,000A Feeder circuits (One time) or less Fast Acting 1-600A 600V or less To,000A p and 2t-Low Feeder circuits and Time Delay (motor load small %) Motor circuits RK1 Fast Acting 1/10-600A 600V or less To,000A 2t-Slightly > Feeder circuits and Time Delay 0V or less p-slightly > Motor circuits RK5 Fast Acting 1/10-600A 600V or less To,000A 2t- > RK-1 Feeder circuits and Time Delay 0V or less p- > RK-1 Motor circuits Moderate 2-600A 600V or less To,000A 2t- < RK-5 Motor circuits (FORM ) Delay p- < RK-5 T Fast Acting 1-600A 300 and 600V To,000A 2t-Low Non-motor loads or less p-low L Fast Acting A 600V or less To,000A 2t-Low Feeder circuits and Time Delay p-low motor loads Motor circuits Fuse clips do not prohibit the use of lass type fuse in switch. Refer to Siemens for single phase and D horsepower requirements. Ratings are based on UL test procedure. d onnector range applies to VB Switches only. 5 Not suitable for use in distribution space in main section. 8-6 Siemens anada Limited Power Product atalogue 2014

6 Replacement or Modification omponents for ircuit Breakers or Fusible Switches g onnecting Strap Kits For Use With ircuit Breakers n Distribution Sections dh (Table 15) eight - atalogue Breakers nches (mm) Number BQ, BQ, B BL, BL, BL 3.75 (95) 6BL2 c D2, D4, D6, 3.75 (95) D (95) 662 c D (95) 6L2 Q2, Q2, Q2-6Q2 FXD6, FD6, FD6 6F62 FD6 6LF1 XD2, XD6, D2, D6, D6 662 SD6, SD6 D6, SD6 6L1 LXD6, LD6, LD6, SLD6, SLD6 6LL61 LD6 6LL1 SLD6 6SL61 MD6, MD6, 10 (4) MD6, SMD6 10 (4) 6M61 These are aluminum connectors. f copper is required please add suffix (95) plate accommodates six 1-pole breakers. 10 (4) plate accommodates eighteen 1-pole breakers. onnector kits also accommodate S5, F2, DP Panelboards, FRS, F and F distribution interiors or DP6/SPP6 Series Panels. Special onstruction, Additions and Accessories When required, special constructions or additions to standard Switchboards may be specified for all factoryassembled Switchboards. Listed below are those available for Type SMP Switchboards. 1. nclosure Type 38 nclosure MA Types Type 1 (ndoor or Drip-proof) Type 1A (Front Gasketed) 2. Wireway Options These connectors are available in copper only. f Blank (ircuit Breaker or Switch) over Plates can also be used in F and F distribution interiors or DP6/SPP6 Series Panels. g Please refer to the Siemens Speedfax for detailed circuit breaker or switch information. Selection 10. ircuit Breaker Accessories andle Blocking Device Blocks handle in either the ON or OFF position. Available for: 24 W x 90 x Dp inged Door MD6, MD6, MD6, SMD6, Door overs ND6, ND6, ND6, SND6 MN6BL 24 W x 90 x.5 Dp inged Door Door overs Padlocking Device - Padlocks in OFF 3. Painted Finish position. Available for: Touch-Up Paint (ASA61, Light Grey) Breaker Type at. Number 12 oz. aerosol can, at. # TUP-61 BL, BL, BL, ND6, ND6, ND6 10 (4) QLD3 BQ, BQ, BQ, B6, BQXD SND6, SND6, 10 (4) 6N61 SND6 10 (4) 4. Miscellaneous Accessories One pole, BL, BLF, B, BAF PLD1 onnecting Strap Kits For Use With ircuit Nameplate - laminated and engraved Two-pole, BL, BLF, and B PLD2 Breakers in S5 and SPP6 Series Panels 5. Bus-Link (One Set Per Panel) Q2, Q2, Q2- L9419 eight atalogue Breaker Type Mounting BQD, QD BQDPLD (mm) Number Ampere Unit Space Occupied in MUD - D4, D6, D4, D6 D2PL NGB 3.75 Rating nches (mm) (95) D SNBD j onsult Factory FXD6, FD6, FD6, FD6 FD6PL1 NB, B 3.75 XD6, D6, D6, D6, SD6, D6PL (95) D SBD j 6. Grounding of SMP Switchboard LXD6, LD6, LD6, LD6, SLD6 NDG, DG, LDG 5.00 (127) D SDGD j MD6, MD6, MD6, SMD6, MN6PLD Non-nsulated quipment Ground Bus ND6, ND6, ND6, SND6 NFG, FG, LFG 5.00 ncluding Ground Lug (127) D SFGD j ontinuous Solid opper Ground andle xtensions - For replacement NG, G, LG 6. (158.75) D SG2D j (optional) (one extension shipped with breaker) NG, G, LG 6. (158.75) S SG1D j 7. Main Bus Breaker Type at. Number onnecting Strap Kits For Use With VB, VK or P MD6, MD6, MD6, SMD6, X11 Standard Main bus and Neutral bus are Switches in Distribution Sections dh (Table 16) ND6, ND6, ND6, SND6 tin plated aluminum or silver finished Rating VB Switch VK Switch P Switch copper (option). Amperes at. No. at. No. at. No. Ground Fault Sensing Relay Kit 30/30 N/A VK6-57 N/A 8. Lugs quipment Protection (30 ma) 60/60 VB6-71 VK6-57 N/A For Main Device and Neutral For Use with Number atalogue Number / N/A VK6-58 N/A For Main Breakers please see SpeedFax Breaker Types of Poles Description VB6-71 N/A N/A section #6 D4, D6, See breaker section Neutral - please consult factory D4 1, 2, 3 of this catalogue. / N/A VK6-72 N/A VB6-71 VK6-71 i N/A VB6- N/A N/A 800 N/A N/A F6162DAN Blank over Plates For Distribution Switch or ircuit Breaker f (Table 17) For use with SMP Switchboards. eight - atalogue nches (mm) Number 1. (32) 6FPB (64) 6FPB (95) 6FPB (127) 6FPB (4) 6FPB (381) 6FPB15 9.SPD Modules Sentron TPS3 05 KA KA KA 0KA 300KA Options: Surge ounter Remote Monitor Breaker Type at. Number BL, BL, BL, QL1 Q2, Q2, Q2- QS1 BQD, QD, NGG BQDBD D4, D6, D4, D6 2BL FXD6, FD6, FD6, FD6 FD6B1 XD6, D6, D6, D6, SD6, D6BL LXD6, LD6, LD6, LD6, SLD6 Shunt Trip on Main and Branches at. Description Number BL, BQD6 (branch only) See breaker section Q2, Q2, Q2, D2, D4, D4 (branch only) of this All others through 1A catalogue. h Mounting kits include connector straps and covers (breakers or switches are not included). i Refer to Siemens for units equipped with auxiliary switches. j onsult Sales for mounting in F/F Switchboards. Siemens anada Limited Power Product atalogue SWTBOARDS

7 8 SWTBOARDS Sentron SMP Switchboards A. Scope Furnish and install, as shown on the plans, a secondary distribution switchboard, as specified herein, for the system indicated below: 120/208V 3-phase 3-wire 347/600V 4-wire 600V B. onfiguration The switchboard enclosure shall be of bolted construction: MA 1 indoor. MA 1 with dripshield (optional). MA 1 with Front Gasketed (optional). Switchboard shall be bolted together to form one metal enclosed rigid switchboard. Switchboard shall include all protective devices and equipment as listed on drawings with necessary interconnections, instrumentation and control wiring. All groups of control wires leaving the switchboard shall be provided with terminal blocks with suitable numbering strips. The switchboard shall have space or provisions for future expansion as noted on the plans. Switchboard shall be constructed and certified in accordance with SA standards and shall be Siemens type (SMP) or approved equal. ndividual sections shall be front accessible, not less than (324) deep, and the rear of all sections shall align. Distribution sections shall be designed to accommodate the intermixing of Molded ase Breakers and Fusible Disconnects in the same distribution interior.. Bus Requirements The bus shall be tin-finished aluminum silver-finished copper (option) of sufficient size to limit the temperature rise to. The bus shall be braced for 50,000 or,000 (option) amperes symmetrical and supported to withstand mechanical forces exerted during short circuit conditions when directly connected to a power source having the indicated available short circuit current. D. ncoming Service Overhead or Underground Service: able ntry This section shall be bussed and sealable per local utility requirements. Screw-type mechanical lugs, compression lugs to terminate, aluminum, copper cable, shall be kcmil, and cables per phase. Main breaker standard aluminum mechanical lugs suitable for aluminum or copper. (No wireway). Metering Service Section The service section shall be designed for the system parameters indicated in section A above. The metering service section shall have a Utility Metering compartment per utility requirements. User metering as indicated below and as shown on plans. Main (service) section: Siemens Digital metering with remote display current transformer(s) /5 or suitable rating Branch circuits (Sensitrip only): SADU Meter Display (option) Ground fault Protection (3-Phase, 4-Wire): Furnish and install on the service equipment and/or switchboard a Ground Fault protection system and indication equipment as specified herein and as shown on drawings in accordance with Section All new Ground Fault Protection and ndication equipment shall be factory installed, wired and tested by the switchboard manufacturer. F. Switchboard SMP Guide Specification The complete switchboard shall be finished with light grey, ASA-61 paint. ach switchboard main section shall have a metal nameplate permanently affixed to it, listing the following information: b Name of manufacturer b System voltage b Ampacity b Type b Manufacturer s shop order number and date b ach section of switchboard shall bear a SA certification mark and a short circuit rating label. The switchboard shall be per the arrangement below. F1. Switchboard Type Panel-Mounted, Front Accessible. Switchboard shall be of Siemens SMP type, or approved equal. ndividual sections shall be front accessible, floor mounted rear supported, not less than (324) deep, and rear, of all sections shall align. ncoming line termination, main device connection and all bolts used to join current-carrying parts shall be installed so as to permit servicing from the front only so that no rear access is required. The branch devices shall be front removable and panel mounted with line and load side connections front accessible. G. Main Protective Devices The main protective device, to be installed in the main device section, shall be as indicated below: G1. Molded ase ircuit Breaker Molded case circuit breaker shall be of the quick-make, quick-break, trip-free, (standard) (igh nterrupting) (urrent Limiting) (solid state Sensitrip ) type. t shall be frame (3-pole) (240V) (600V) breaker with a trip current rating of: 400A, 600A, 800A, 0A a, Ground fault protection required, per section when the current is O 0A at 600 volts. Specification 1 A a of an interrupting capacity of not less than amperes RMS symmetrical at the system voltage. The following accessory options are to be included: Shunt trip Ground fault relay Long time (Sensitrip only) Long time delay (Sensitrip only) Short time (Sensitrip only) Short time delay (Sensitrip only) ntegral ground fault (Sensitrip only) Other (list). Branch Protective Devices (Select as necessary) All molded case circuit breakers, and fusible disconnect units used as a protective device in a branch circuit will meet the requirements of the appropriate paragraph below 1. Molded ase ircuit Breaker Molded case circuit breakers shall be of quick-make, quick-break, trip-free (thermal magnetic type) (current limiting) (solid state) with frame, trip and voltage rating, either 2-pole or 3-pole, as indicated on the plans. All breakers shall have an interrupting capacity of not less than amperes RMS symmetrical at the system voltage. All breakers shall be removable from the front of the switchboard without distributing adjacent units. The switchboard shall have space or provisions for future units shown on the plans. 2. urrent Limiting ircuit Breaker urrent limiting circuit breakers shall provide inverse time delay, instantaneous circuit protection, and also limit the letthrough 2 t to a value less than 2 t of one-half cycle wave of the symmetrical prospective current without any fusible elements. Breakers shall have an interrupting capacity of not less than ampere RMS symmetrical at the system voltage. 3. Fusible Disconnect Fusible disconnects shall be quick-make, quick-break units utilizing the double-break principle of circuit rupturing to minimize arcing and pitting and shall conform to the ratings shown on the plans. ach disconnect shall have an individual door over the front, equipped with a voidable interlock that prevents the door from being opened when the switch is in the ON position unless the interlock is purposely defeated by activation of the voiding mechanism. All disconnects shall have externally operated handles. Disconnects shall be equipped with lass (standard), lass R rejection type, lass L (standard), lass T fuse holders as indicated on the plans suitable for application on system with amperes symmetrical available fault current. 8-8 Siemens anada Limited Power Product atalogue 2014

8 Fault-urrent alculation on Low- Voltage A Systems n order to determine the maximum interrupting rate of the circuit breakers in a distribution system it is necessary to calculate the current which could flow under a three-phase bolted short circuit condition. For a three-phase system the maximum available fault current at the secondary side of the transformer can be obtained by use of the formula: l sc = kva x KV x 3 x % Z l sc = Symmetrical RMS amperes of fault current. kva = Kilovolt-ampere rating of transformers. KV = Secondary voltage in kilovolts. %Z = Percent impedance of primary line and transformer. Application ntegrated quipment Short ircuit Ratings The term ntegrated quipment Short ircuit Rating refers to the application of series connected circuit breakers in a combination that allows some breakers to have lower individual interrupting ratings than the available fault current. This is permitted as long as the series combination has been tested and certified by UL & SA. Series ratings must be specified on order at time of entry. For more information on series ratings please consult your local Siemens sales representative. Normal load and Fault urrents of Three Phase Transformers (Table ) Trans- Maximum 208 Volts, 3 Phase 240 Volts, 3 Phase 480 Volts, 3 phase 600 Volts, 3 Phase former Short-ircuit Rated Short-ircuit urrent Rated Short-ircuit urrent Rated Short-ircuit urrent Rated Short-ircuit urrent Rating Kva Load RMS Symmetrical Amps. Load RMS Symmetrical Amps. Load RMS Symmetrical Amps. Load RMS Symmetrical Amps. 3 Phase Available ontin- Trans- 50% om- ontin- Trans- % om- ontin- Trans- % om- ontin- Trans- % om- Kva and from uous former Motor bined uous former Motor bined uous former Motor bined uous former Motor bined imped- Primary urrent, Alone Load urrent, Alone Load urrent, Alone Load urrent, Alone Load ence % a System Amps Amps Amps Amps % Unlimited % Unlimited % Unlimited % Unlimited SWTBOARDS Short circuit currents are calculated with impedences and kva shown in this table. Short circuit current contributions are calculated on the basis of motor characteristics that will produce four times normal current. 50% motor load contribution is assumed for 208V and % motor load contribution is assumed for 240V, 480V and 600V. This Table has been prepared to list the symmetrical RMS fault current which is available at the secondary terminals of the transformer. Siemens anada Limited Power Product atalogue

Section 8. Switchboards. Contents. Sentron SMP, FCI, FCII Switchboards Type SMP. Selection Construction Details Specification Type FCI, FCII

Section 8. Switchboards. Contents. Sentron SMP, FCI, FCII Switchboards Type SMP. Selection Construction Details Specification Type FCI, FCII Section Switchboards Contents Sentron SMP, FCI, FCII Switchboards Type SMP Features Selection Construction Details Specification Type FCI, FCII Features Selection Construction Details Specifications Protective

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1

GE 8000-Line Motor Control Centers Mains, Feeders, Incoming Lines C-1 GE 8000-Line -1 Mains, coming Lines MAINS GENERAL Main units consist of an externally operable circuit disconnect, either a fusible switch or a circuit breaker. Sizes by ampere rating, short-circuit rating,

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

Application guide. Tmax Link OEM UL 891 Switchboard Program

Application guide. Tmax Link OEM UL 891 Switchboard Program Application guide Tmax Link OEM UL 891 Switchboard Program 04 Tmax Link Overview 04 Standards 04 UL File Extension Process Overview 05 Electrical Data 05 Technical Data 05 Ambient Conditions 08 Circuit

More information

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description .5 Types PRL1a, 2a, a, E, 4 and Column Modifications s Types PRL1a, 2a, a, E, 4, Column Modifications Selection Guide Modifications Alphabetical Index Modification Item Contents Types PRL1a, 2a, a, E,

More information

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim Applications The CDP panels provide protection for lightning and power distribution circuits in the commercial and industrial establishments. The circuit breakers thermomagnetic trip allows for momentary

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Boxes C " wide, 5 3 4" deep. C " wide, 5 3 4" deep. Branch Breaker Side Gutters. Type Breaker (inches) C1 BL, BLH, HBL C2 BQD 3.

Boxes C  wide, 5 3 4 deep. C  wide, 5 3 4 deep. Branch Breaker Side Gutters. Type Breaker (inches) C1 BL, BLH, HBL C2 BQD 3. Circuit Breaker / Column Type Type C1 240 Volts AC Mains Branch UL Short Circuit Rating 200,000 IR Branch Breaker Symmetrical Interrupting Rating Based on Underwriters Test Procedure Type C2 480Y/277 Volts

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

GE 8000-Line Motor Control Centers

GE 8000-Line Motor Control Centers GE 8000-Line -1 ENCLOSURE TYPES TYPE 1 General Purpose, Indoor Intended for use indoors, primarily to prevent accidental contact of personnel with the enclosed equipment, in areas where unusual service

More information

Lighting Panelboards. P2 Panelboards

Lighting Panelboards. P2 Panelboards Lighting Panelboards P2 Panelboards Features Flexibility is the hallmark of the P2 panel. This panel offers a wide array of factory-assembled options to meet virtually any lighting panel application. The

More information

Panelboards Circuit Breaker / Lighting and Distribution

Panelboards Circuit Breaker / Lighting and Distribution Circuit Breaker / Lighting and Distribution 480Y/277 Vac Maximum 600Y/ 347 Vac (CSA only) Maximum 400 Ampere Mains 400 Ampere Maximum Branch UL Short Circuit Rating 200,000 A. @ 240 Vac / 100,000 A. @

More information

Multi-Pak Group Control

Multi-Pak Group Control Multi-Pak Grouping.1 Product....................................... Application.................................... Features Enclosures........................................... V-T-2 V-T-2 V-T-2 Feeder

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Table of Contents TPS NQ & AQ Series Overview 2 Switchboard Technical Data 3-5 Panelboard Technical Data 5-11 1 Tier Power

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

Selection and application guide

Selection and application guide Selection and application guide Integrated Power Systems Switchboards www.usa.siemens.com/switchboards Integrated Power Systems Switchboards Contents General Product Information 2-3 General Layout Information

More information

I-Line Circuit Breaker Panelboards Catalog 2110CT9701R02/ Class 2110

I-Line Circuit Breaker Panelboards Catalog 2110CT9701R02/ Class 2110 I-Line ircuit Breaker Panelboards atalog 2110T9701R02/16 2016 lass 2110 ONTENTS Description............................................ Page Product Description.................................... Page

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com J QMB Panel boards Switchboards 200,000A. short circuit rating QMB Fusible Switches Throughout our complete line of 30-SOOA. ULiisted QMB fusible switches, we've combined timeproven Square D safety switches

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

WARREN COUNTY, N.Y. M/E REFERENCE

WARREN COUNTY, N.Y. M/E REFERENCE SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE

More information

PANELBOARDS C1/C2 SECTION 6

PANELBOARDS C1/C2 SECTION 6 SECTION 6 C1/C2 PANELBOARDS Page General Specifications 6-2 Box Sizing 6-2 Gauge Steel Boxes 6-2 Fronts 6-2 Main Breaker Connectors 6-2 Main Lug Connectors 6-2 Selection 6-3 6-5 Main Lugs Only C1 and C2

More information

Molded Case Circuit Breakers Reference Guide

Molded Case Circuit Breakers Reference Guide Molded Case Circuit Breakers Plug-In Breakers Panelboard Breakers QT QP, QPP QPH, QPPH HQP, HQPP HQPPH QPJ BL BLH HBL BQD, BQD NGB NEB HEB Page 1-25 1-27, 1-29 1-27, 1-29 1-24, 1-29 1-24, 1-29 1-29 -18-18

More information

For Options, Modifications and Accessories, see pages Discount Schedule A6

For Options, Modifications and Accessories, see pages Discount Schedule A6 Main and Feeder Units Bulletin 191F and 191M Outgoing Feeder Lug Compartment (FLUG) and Incoming Main Lug Compartment (MLUG)................................................. The Bulletin 191M and 191F

More information

Specialty Service Entrance Switchboards. Selection and Application Guide

Specialty Service Entrance Switchboards. Selection and Application Guide Specialty Service Entrance Switchboards Selection and Application Guide Power! As the heart of every business complex it has to be reliable. As part of your business, it has to be economical too.you get

More information

type P1 Lighting and Power Distribution Panelboards Overview P1 Panelboards

type P1 Lighting and Power Distribution Panelboards Overview P1 Panelboards type P Lighting and Power Distribution Panelboards Specifications Main Breaker: 400A Maximum Main Lugs only: 400A Maximum Voltages: 480Y/277V AC Maximum 250V DC Maximum 3Ø3W, 3Ø4W, Ø3W, Ø2W General P panelboards

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers 600V Circuit Breakers Sentron MD Breakers 480V 600V MD, SMD6 50KAIC 25KAIC HMD, SHMD6 65KAIC 50KAIC CMD, SCMD6 100KAIC 65KAIC Sentron ND Breakers ND, SND6 50KAIC 25KAIC HND, SHND6 65KAIC 50KAIC CND, SCND6

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers Type SND6 Molded Case Circuit Breakers SND 1200A Frame Digital Solid State Sentron Sensitrip III Series Type SHND6 Current Limiting Type SCND6 Blue Label Black Label Red Label Catalog Current Price SND69800A

More information

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller Number: 5344-1.1.311 Rev. 8 Portable Mine Power Centres Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller SCOPE This specification covers general material and design

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers Molded Case Circuit Breakers LMD 800A Frame Sentron Series Type LMXD6 Non-Interchangeable Trip (Assembled Circuit Breaker without Lugs) Blue Label Continuous 2-Pole (3 Pole Width) 3-Pole Current Rating

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

PANELBOARDS SECTION 1

PANELBOARDS SECTION 1 SECTION 1 P1 PANELBOARDS Description Page General Information 1-2 Selection and Application 1-2 Application 1-3 1-6 Main Breaker Panel Size Selector 1-3 Main Breaker Selection 1-3 Main Lugs Size Selector

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Quik-Spec Coordination Panelboard Specifications

Quik-Spec Coordination Panelboard Specifications Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Ampere Connectors Suitable for Copper or Aluminum 800 (3) - #3/0 AWG-500 Kcmil 1000 (4) - #3/0 AWG-500 Kcmil 1200 (4) - #3/0 AWB-500 Kcmil

Ampere Connectors Suitable for Copper or Aluminum 800 (3) - #3/0 AWG-500 Kcmil 1000 (4) - #3/0 AWG-500 Kcmil 1200 (4) - #3/0 AWB-500 Kcmil Panelboards Type P5 Panelboards Features The P5 panel is the largest footprint distribution panel in the Siemens panel family. Even though it is our largest panel type, the P5 panel is still a space saver

More information

QO and QOU Miniature Circuit Breakers QOU Miniature Circuit Breakers

QO and QOU Miniature Circuit Breakers QOU Miniature Circuit Breakers QO and Miniature ircuit reakers Miniature ircuit reakers lass 720 / Refer to atalog 0730T9801 Low mpere Miniature ircuit reakers unit mount miniature circuit breakers (cable-in/cable-out) are ideal for

More information

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

POWER PRODUCT Meter Centres Contents

POWER PRODUCT Meter Centres Contents POWER PRODUCT Meter Centres Contents General Specifications - Catalogue Numbering System - 40V Meter Centre Overview - Features & Benefits -3 Procedure -5 Switches and Tap Boxes -6 Meter Stacks -7 Socket

More information

Contents. 4 Loadcentres

Contents. 4 Loadcentres POWER PRODUCT Contents Application and Description -2 Product Offering and Specification Guide -3 Product Features and Customer Benefits - ing System -5 EQL & SEQ Single phase EQL with main lug -6 SEQ

More information

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3

Introduction. P1 Panelboards. P1 Feature Overview. Contents. Siemens Panelboards Introduction to P1 Panelboards 1. General Specifications 3 Introduction P1 Panelboards P1 Feature Overview Key Panelboard Features Lighting and Appliance Applications Power Panelboard Applications Convertible From Top Feed to Bottom Feed and Vice Versa Change

More information

SECTION ELECTRIC DISTRIBUTION

SECTION ELECTRIC DISTRIBUTION SECTION 16400 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary General Conditions and other Division

More information

Panelboards. Type P3 Panelboards. General. Revised 04/15/14. Features

Panelboards. Type P3 Panelboards. General. Revised 04/15/14. Features 11 Panelboards Features Another innovation from Siemens is the P3 panel. It is a smaller, footprint distribution panel to fit a large number of applications that require more (or larger) branch devices

More information

Bussmann series Quik-Spec Coordination Panelboard

Bussmann series Quik-Spec Coordination Panelboard Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers 600V Circuit Breakers Sentron MD Breakers 480V 600V MD, SMD6 50KAIC 25KAIC HMD, SHMD6 65KAIC 50KAIC CMD, SCMD6 100KAIC 65KAIC Sentron ND Breakers ND, SND6 50KAIC 25KAIC HND, SHND6 65KAIC 50KAIC CND, SCND6

More information

PlexPower Fused Factory Sealed Panelboard with Bus Bar Up to 30 Amps. Stainless Steel Enclosures

PlexPower Fused Factory Sealed Panelboard with Bus Bar Up to 30 Amps. Stainless Steel Enclosures Applications The PlexPower panelboard provides indoor and outdoor protection and control of electrical circuits in hazardous environments such as: Petroleum plants Chemical plants Refineries Wastewater

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant Applications Protection and control of electrical equipment and circuits such as lighting and heat tracing in hazardous locations or in damp, wet or corrosive conditions. D2P Series designed for use in

More information

QO and QOU Miniature Circuit Breakers QO Circuit Breaker Accessories

QO and QOU Miniature Circuit Breakers QO Circuit Breaker Accessories QO and Miniature ircuit reakers QO ircuit reaker ccessories lass 1130 / Refer to atalog 0730T9801 IRUIT RKRS ccessories for Use with QO and QO Miniature ircuit reakers Handle ttachments escription at.

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

A. This section includes unit capacitors for power factor correction.

A. This section includes unit capacitors for power factor correction. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Solar Power Switchgear & Energy Storage Renewable Energy Systems 7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH

More information

SECTION DISTRIBUTION AND GROUNDING

SECTION DISTRIBUTION AND GROUNDING SECTION 16400 DISTRIBUTION AND GROUNDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Furnishing and installation of a complete electrical distribution and grounding system. B. Furnish and install motor control

More information

22.000A IR. Catalog Number. Price $

22.000A IR. Catalog Number. Price $ Full Size (" per Pole) with INSTA-WIRE -Pole Plug-In (V AC) Type MP-T Type MP-HT Type MP-MT Continuous Current Rating @ C 5 25 35 5 0.000A IR Catalog Number MP5 MP MP25 MP MP35B MP MP5B MP MPB MPB List

More information

Modular Metering. Canadian Version

Modular Metering. Canadian Version Modular Metering Canadian Version Meter Centres and Tenant Breakers...2 Industrial Multi-Metering...3 Main Service Modules...4 Main Terminal Boxes...7 Main Circuit Breakers...8 Main Fusible Switches...9

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

XP Series Pre-Wired Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof System

XP Series Pre-Wired Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof System NEC/ Applications Protection and control of electrical apparatus and circuits in hazardous environments, either indoor or outdoor. Designed for Class I, Division 2 areas where flammable gases or vapors

More information

QMB Fusible Panelboards

QMB Fusible Panelboards Catalog 4620CT9601R04/09 2009 Class 4620 CONTENTS Description............................................. Page Overview.............................................. Page 3 QMB Switches..........................................

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

Molded Case Circuit Breakers

Molded Case Circuit Breakers SMD 800A Frame Digital Solid State Sentron Sensitrip III Series Selection Type SMD6 Type SHMD6 Current Limiting Type SCMD6 Blue Label Black Label Red Label Catalog Current List SMD69600A 600 SMD69700A

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less. PART 1: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other

More information

Engine Generator Circuit Breakers

Engine Generator Circuit Breakers Engine Generator Circuit Breakers Product Description............................................. 2 Application Description........................................... 2 Standards and Certifications......................................

More information

4.5. Switchboards. Contents Description Instant Service Switchboards Product Selection...

4.5. Switchboards. Contents Description Instant Service Switchboards Product Selection... .5 Type 1 Indoor Product Description Eaton s Instant are designed as stocked units to provide fast delivery to match the needs of the construction market. Suitable for use as service entrance equipment,

More information

Loadcentres. 4 Loadcentres. Product Offering and Specificaton Guide. Description. Application

Loadcentres. 4 Loadcentres. Product Offering and Specificaton Guide. Description. Application Product Offering and Specificaton Guide Application Main lug loadcentre, b Phase 3 W /V, to 0A, / - 0/80 circuits b 3 Phase W /8V, 00 to 5A, - circuits Main Breaker loadcentre, b Phase 3 W /V, to 0A, /

More information

Model 6 Motor Control Centers Catalog 8998CT9701R07/ Class 8998

Model 6 Motor Control Centers Catalog 8998CT9701R07/ Class 8998 Catalog 8998CT9701R07/09 2009 Class 8998 CONTENTS Description............................................. Page Product Description.......................................... 7............................

More information

New York City Apartment Metering Meter Sockets / Load Centers

New York City Apartment Metering Meter Sockets / Load Centers s New York City Apartment Metering Meter Sockets / Load Centers Selection and Application Guide Bulletin RPSA-S0001 Before You Begin... System Parameters Mounting: Indoor only Input: 208Y/120V AC, 3 Phase,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Type MP-T Type MP-HT Type MP-MT

Type MP-T Type MP-HT Type MP-MT CIRCUIT BREAKERS 2 Circuit Breakers Full Size (1 per Pole) with INSTA-WIRE 1-Pole Plug-In (120V AC) Type MP-T Type MP-HT Type MP-MT Continuous 10,000A IR 22,000A IR 65,000A IR Current Rating Catalog List

More information

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7 Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

Switchgear. Low Voltage

Switchgear. Low Voltage January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................

More information

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units -22 2 Amperes January 1 Vol. 1, Ref. No. [0488] Table -. FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Max. Cont. Ampere Rating @ 40 C 600V AC Maximum, 0V DC 277V AC Maximum,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information