HMM Series Mechanical Heat Meters
|
|
- Lenard Carr
- 5 years ago
- Views:
Transcription
1 Mechanical Heat Meters Important: Retain these instructions These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. Contents 1 Unpacking Storing...1 Installation Disposal Unpacking Installation Instructions TG Storing 5 C (41 F) 90 C (194 F) H O %RH Installation! This installation guide is intended for trained personnel and does not include basic working steps. 1 Dimensions H H h Nominal Flow Rate (m /h) DN Thread on meter (inch) G / 4 B G / 4 B G 1 B L (mm) Coupling thread (inch) R 1 / 2 R 1 / 2 R / 4 H (mm) DN15 and DN20 Versions L L Nominal Flow Rate (m /h) DN Thread on meter (inch) G 1 1 / 4 B G 1 1 / 4 B G 2 B L (mm) Coupling thread (inch) R 1 R 1 R 1 1 / 2 H (mm) h (mm) DN25 and DN40 Versions Heat Meters TG20116 Issue 4, 28/05/201 1
2 Installation (continued) 2 Mounting Requirements a b 5 C (41 F) 90 C (194 F) 0 %RH 90 %RH H O 2 Mounting Install according to EN144-6 Medium Water without additives Damaging meter seal voids warranty Do not disconnect internal battery! Temperature sensor cables must not be shortened or changed in any way. Note that the temperature sensors are marked with coloured labels: red for high temperature and blue for low temperature. The meter should be located according to instructions given on the front label. IEC HMM/H/1.5/MOD HMMHT heatmeter heat calibrated 2010 M DE-07-M1004-PTB00 Hydrometer Type 447 kwh p I s inst place: low temp. environmental class: E1+M1 q : ΔΘ: 1,5m /h k k accuracy class: q : Θ C C 0,06m /h q: 5 Pt500 DN15 q : Θ C 0,06m /h : C... PN16/PS16 e.g. inst. place: low temp. For heating only, the meter is mounted in the return pipe (low temp.). The low temp. (blue) sensor is mounted in the sensor body and the free high temp. (red) sensor should be mounted in the forward pipe. forward high temp. red probe return blue probe low temp. arrow on housing indicates direction of flow For heat/cool or cool meters, the meter is mounted in the forward pipe (high temp.). The low temp. (blue) sensor is always free and should be mounted in the return pipe. For DN15 and DN20 versions the high temp. (red) sensor is mounted in the sensor body. For DN25 and DN40 versions the high temp (red) sensor is free and should be mounted in the forward pipe. return blue probe low temp. forward high temp. red probe arrow on housing indicates direction of flow 2 Heat Meters TG20116 Issue 4, 28/05/201
3 Installation (continued) Mounting (continued) This symbol indicates that the HMM/HC models are fully encapsulated for reliable protection against condensation on the integrator board. Protection class: IP68. The sensors may either be mounted in ball valve or adapter, or in a pocket: Either mount temperature sensor in ball valve or adapter Fixing Kit O -ring Note that the sensor fixing kit (HMAC/SENSORFIXKIT) is not required if mounting the sensor in a pocket. The fixing kit is only required if mounting in a ball valve or adapter. split screw mounting pin One fixing kit is provided with DN15/20 meters (only one is needed for these as the other sensor is already fitted in the body of the unit). Two fixing kits will be required to be purchased separately for DN25/40 meters if using ball valves or adapters. A B C D 1. For ball valve only, close the ball valve and unscrew the plug screw from the ball valve. 2. For ball valve or adaptor place an O-ring on the mounting pin (A). The second O-ring is spare.. Insert the O-ring into the hole of the ball valve or adapter with the mounting pin using turning movements (B). 4. Position the O-ring in its final position using the other end of the mounting pin (C). 5. Place the two halves of the plastic screw around the temperature sensor. Press the two halves together so that the two studs on one half of the plastic screw fit into the holes on the other half (D). 6. Insert the temperature sensor with the plastic screw into the ball valve or adaptor and tighten the plastic screw by hand. 7. Check for leaks. Or mount temperature sensor in pocket L1 Sensor pocket for DN15/20 (HMAC/POCKET4MM) L1 = 4 mm, D1 = G 1 / 2 B D1 Sensor pocket for DN25/40 (HMAC/POCKET50MM) L1 = 50 mm, D1 = G 1 / 2 B screw 1. Mount pocket in pipe. 2. Insert probe as far as bottom of pocket and tighten screw.. Fill pocket with thermally conductive oil. 4. Seal pocket. Heat Meters TG20116 Issue 4, 28/05/201
4 Installation (continued) 4 Check Meter 1. Ensure that the volume measuring component is filled with liquid. 2. Check the operation of the meter by pressing the button on the front panel and viewing the display. display IEC HMM/H/1.5/MOD HMMHT heatmeter heat calibrated 2010 M DE-07-M1004-PTB00 Hydrometer Type 447 kwh p I s inst place: low temp. environmental class: E1+M1 q : ΔΘ 1,5m /h : k k accuracy class: q : Θ 5 90 C 0,06m /h q: C... Pt500 DN15 q : Θ C 0,06m /h : C... PN16/PS16 red pushbutton Data Sheet TA Connect a b Meter Brown not used m cable supplied; connect plug so that green core is on left green () white () brown (not required) 4 Heat Meters TG20116 Issue 4, 28/05/201
5 Installation (continued) 5 Connect (continued) c Either IQ/XNC with Driver 9 Way D plug RS485 RTS/EN CTS/EN RS22 9 Way D socket 6 RTS7 CTS (held high) 5 RS22/ Converter (e.g. TWP) Meter 1 Meter n RS22 The Trend RS22/ converters, TWP, TWP20, have straight through RS22 connections as shown, but some converters may require a / crossover connection. The Trend TWP converters may also be connected by a straight 9 Way D socket to 9 Way D plug cable. The meter connection is polarity independent. Use standard 2-wire telephone cable to wire the bus. Note that the cabling for an system requires no specified cable routing or network (e.g. star, series, etc.) d Or EMIC/MBA The EMIC/MBA can connect to a maximum of between 8 and 2 meters depending on its version. The adjacent diagram shows the physical connections. The Supervisor, IQ controller, EINC, and EMIC are connected to the Ethernet bus. The EMIC is connected to its meters using the BUS). The HMM meter takes the measurements and these are read by the EMIC using BUS protocol. The EMIC stores this data in memory and calculates further measurements. Trend system devices can then read the measurements from the EMIC using Trend network communications. The EMIC is a member of the internetwork, and its firmware simulates a Lan with each meter represented as a virtual outstation (e.g. a virtual IQ Controller). A supervisor (e.g 96) can connect to the EMIC by way of a vcnc (virtual Comunications Node Controller) in an EINC (or xtend/einc L, or IQ). In the above diagram, the Supervisor connects to the EINC s Lan using a supervisor mode vcnc. The INCs, Internetwork Node Controllers (EINC s, EMIC s, and IQ s) construct an internetwork. The supervisor can communicate across the internetwork to obtain the meter readings from a vos (virtual outstation). A vos can send Sensor High and Low alarms to the supervisor either through the EINC s vcnc in supervisor mode if the supervisor is permanently connected or through a EINC vcnc set to alarm mode if the supervisor is not permanently connected. The IQ controller is able to send Inter-Contoller Communications to the EMIC (e.g. to obtain meter readings). The IC Comms cannot be attribute comms so are limited to simple Data To and Data From comms. Heat Meters TG20116 Issue 4, 28/05/201 5
6 q : p q : I q : s q Installation (continued) 6 Configure Meter (if required) kwh USB to RS22 Hydro-Set software unit label 6 RTS 7 CTS Way D socket (held high) 5 IEC HMM/H/1.5/MOD HMMHT heatmeter heat calibrated 2010 M DE-07-M1004-PTB00 Hydrometer Type 447 inst place: low temp. environmental class: E1+M1 1,5m /h ΔΘ: k k accuracy class: 0,06m /h Θ : 5 C C Pt500 DN15 0,06m /h Θ : 0 C C PN16/PS16 RS22/ Converter (e.g. TWP) secondary address e.g Address meter IQ/XNC with BUS driver user meter secondary address (meter serial number). EMIC/MBA uses the meter s primary address (default =1). Meter 1 Meter n RS22 RS22 Hydro-Set User Manual TE Set baud rate to 2400 (or 00 for long distances) Meter auto-detects baud rate Data: 8 bits, 1 stop bit, even parity Hydro-Set configuration software is available free from product-download/by-categories.html (then select Select a partner - Hydrometer, Select category - Software, Select a product - HYDRO-SET, and in Download overview click HYDRO-SET software). It runs under Windows XP (v 1.51_b60 or greater runs under Windows 7). Page Parameter Default Change if Current Values Primary Address 1 If primary address clash on causes problems (Must change if there is more than one meter connected to the EMIC/MBA, do not change for IQ/ XNC with BUS driver) Secondary Address xxxxxxxx Fixed Reading Date Values Reading Date 1 (next) Set up reading date to record energy (kwh) 6 Heat Meters TG20116 Issue 4, 28/05/201
7 100?40 V RS485 OK 24 V A 0 V 24 V P RTS/EN CTS/EN RS P 0 P 0 P 0 P 0 P 0 P Installation (continued) 7 Configure IQ/XNC/SER (if used) SET Ethernet Hub Router Either Hub RS22 RS22/ Converter (e.g. TWP) Meter 1 Meter n SET Or Standard Ethernet cable XCITE/XA crossover adaptor - order separately IQ/XNC Driver Data Sheet TA201111, IQ/XNC Driver Manual TE HMM Communications Manual TE20114 a b c d e Run SET. (This may include drivers or the drivers may have to be downloaded from PartnerNet). Load Driver Solution. Set up strategy/tcl interface (addresses/communications settings). Define meter data map size (max. for HMM meter is 16 values which requires 17 stores). Download strategy to IQ. 8 Configure EMIC/MBA (if used) EMIC/MBA Data Sheet (TA201146) EMIC/MBA (TG201147) EMIC Manual (TE201084) either 100 m (109 yds) max. Ethernet hub or switch e.g: EDS205 5 port unmanaged switch available from Trend standard Ethernet cable Cat 5e twisted pair EMIC or direct connect web browser only (not 96) standard Ethernet cable - see above XCITE/XA crossover adaptor order separately (XCITE/XA/5 pack of 5) Heat Meters TG20116 Issue 4, 28/05/201 7
8 100?40 V RS485 A P 0 P 0 P 0 P 0 P 0 P 0 OK P V 0 V 24 V RTS/EN CTS/EN RS22 9 Check System e.g. 96 Energy Flow Ethernet Hub Router Hub RS22 RS22/ Meter 1 Converter (e.g. TWP) Meter n 4 Disposal WEEE Directive: At the end of their useful life the packaging, product, and battery should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn. Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com 201 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes. Trend Control Systems Limited Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0) Fax:+44 (0) Trend Control System USA th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) Fax:(425) Heat Meters TG20116 Issue 4, 28/05/201
EM-MPO/400. Multi-parameter Electricity Meter. Installation Instructions. Important: Retain these instructions. Mounting Requirements H O 2
I V E I V E I V E Multi-para Electricity Meter Important: Retain these instructions Contents 1 Unpacking...1 2 Storing...1 3 Installation...1 4 Disposal...8 1 Unpacking I V E G2118 2 Storing -25 C -23
More informationUS-S/FFL. Ultrasonic energy meters. Function. Flexible design. Connection. Mounting. High reliability
Revision 2017-08-15 Ultrasonic energy meters Flanged ultrasonic energy meters, intended for heating or cooling. Size DN25 DN100 Nominal flow 3.5 60 m³/h For horizontal or vertical mounting No data loss
More informationCompact Heat Meters. Features. -A Pulsed output. -B M-Bus output. Accessories. UK Sales Tel: International Tel:
Compact Heat Meters Features Compact design Simple operation Pulsed output Measures heating or cooling Specification Product Codes Water Meter Temp. range 10 to 90 C Nominal pressure 16bar Installation
More informationSeries 500. Liquid Level Transmitters. Instruction Manual
Series 500 Liquid Level Transmitters Instruction Manual Contents Section Content Page 1 Introduction 1.1 General Overview 3 1.2 Mounting Options 3 2 Installation Notes 2.1 Transmitters 4 2.1.1 Model 510
More informationEW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS
EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS Application PRODUCT DATA Static compact heat meter with electronic measurement, consisting of electronic energy integrator
More informationRAY MECHANICAL COMPACT METER. 4 MID approved class 2 from DN 15mm qp 0,6m3/h up to DN 40mm qp 10m3/h
APPLICATION is a fully electronic multi-jets compact heat meter or compact heat and cooling meter with impeller scanning for recording energy and volume data. is equipped with 2 temperature sensors. is
More informationDatasheet PDCSY-MW-CHM. Technical Overview. Features. Product warranty and total quality commitment. General Information.
Datasheet Compact Heat Meters Technical Overview Heat energy is calculated by using a matched pair of high accuracy sensors to measure the difference between the forward and flow temperatures. The amount
More informationSonoMeter 30 Energy Meters
SonoMeter 30 Energy Meters Description MID examination certificate no.: LT-1621-MI004-020 The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption
More informationSHARKY 775 COMPACT ENERGY METER ULTRASONIC
APPLICATION The ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. FEATURES 4 Approval for ultrasonic meter with dynamic
More informationSonoMeter 30 Energy Meters
SonoMeter 30 Energy Meters Description The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption in heating and cooling applications for billing
More informationRAY COMPACT ENERGY METER MECHANICAL
APPLICATION Fully electronic compact heat meter or compact cooling and heat meter with impeller scanning for recording energy and volume data. Highly accurate recording of all billing data in a heating
More informationWSTH/WPTH. Woltmann type combined energy meter. Measuring distance. Function. Connection. High reliability. Mounting.
Woltmann type combined energy meter Flanged Woltmann flow meters for large nominal flows, intended for flow measurements in large plants, such as those found in district heating systems. Size DN50 DN300
More informationALM-Inline. Accurate Lambda Meter V1.1.2 COPY RIGHTS ECOTRONS LLC ALL RIGHTS RESERVED.
ALM-Inline Accurate Lambda Meter V1.1.2 COPY RIGHTS ECOTRONS LLC ALL RIGHTS RESERVED Http://www.ecotrons.com Note: If you are not sure about any specific details, please contact us at info@ecotrons.com.
More informationObserve all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.
Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary
More informationHeat Meter Integrator
Heat Meter Integrator Features Simply operation Integral wall and DIN-rail mounting bracket Pulsed or M-Bus output options Measures heating or cooling and heat/cooling Specification Product Codes Temperature
More informationProduct Overview. Product Identification. Amps One CT Two CTs Three CTs
AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationInstallation and Programming Manual Part: Building Network Interface Card Product: 4100ES
Installation and Programming Manual Part: Building Network Interface Card 4100-6047 Product: 4100ES Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
More informationPLUS PLUS & PRO. Installation manual
PLUS PLUS & PRO Installation manual Safety warnings Manual for Maxem Plus and Pro Energy Manager. Publication Date: May 15, 2017 Questions or improvements If you see any errors or defects, if you have
More informationEW130 Series Multijet Water Meters DN15 40 FOR COLD AND WARM POTABLE WATER APPLICATIONS
EW10 Series Multijet Water Meters DN15 0 FOR COLD AND WARM POTABLE WATER APPLICATIONS CONTENTS PRODUCT DATA Fig. 1. EW100BM / EW101BM Contents... 1 General... 2 Application... 2 Features... 2 Design...
More informationSilvertel. 1. Features. 2. Description. IEEE802.3at compliant. Maximum 30 Watt Output Power. High efficiency DC/DC converter
Silvertel V.0 May 2009. Features Pb IEEE802.3at compliant Maximum 30 Watt Output Power High efficiency DC/DC converter Wide adjustable output voltage range 500Vdc isolation (input to output) Input voltage
More informationMetering systems 0578EN January 2014 Thermal energy meters, ultrasounds type for use in a boiler room GE552-1 series
Version A Version B GE552-1 Description The GE552-2 meters are thermal energy meters with double register and ultrasound,. They enable the measurement of energy used for heating and air-conditioning. They
More informationBYD Battery-Box HV User Manual Battery-Box H 5.1/6.4/7.7/9.0/10.2/11.5
Battery-Box H 5.1/6.4/7.7/9.0/10.2/11.5 Version 5.0 Contents 1 General Information... 2 1.1 Validity... 2 1.2 Application... 2 1.3 Intended Use... 2 1.4 Definition... 2 1.5 Identifying The Product... 3
More informationInfocal 9 Energy calculator for heating and cooling applications
Installation Guide Infocal 9 Energy calculator for heating and cooling applications www.danfoss.com 2 Danfoss Energy Meters 2018.08 VU.IG.N2.02 1. Installation 1.1. Preparation Only qualified personnel
More information362 Clamp Meter. Users Manual
362 Clamp Meter Users Manual PN 3622678 August 2010, Rev. 1, 4/13 2010, 2013 Fluke Corporation. All rights reserved. Printed in China. Specifications are subject to change without notice. All product names
More informationFuse state indicator MEg72. User manual
Fuse state indicator MEg72 User manual MEg Měřící Energetické paráty, a.s. 664 31 Česká 390 Czech Republic Fuse state indicator MEg72 User manual Fuse state indicator MEg72 INTRODUCTION The fuse state
More informationBK BK J93 MA BK MA BK MN93-BK MN193-BK MR193-BK SL261-BK SR193-BK
n 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com COMPATIBLE CURRENT PROBES & SENSORS FOR POWER QUALITY METERS 193-24-BK 193-36-BK
More informationSuperstatic 440. Static Heat- and Cooling Meter. Application
Superstatic 440 Static Heat- and Cooling Meter Application Design The Superstatic 440 is a static heat- and cooling meter according to standard EN1434 class 2 based on the fluid oscillation principle,
More informationDatasheet PDCSY-MW-U. Technical Overview. Features. Product warranty and total quality commitment.
Datasheet Ultrasonic Flow Sensors & Integrator Technical Overview Ultrasonic flow sensors have no moving parts in the volume flow, this makes them almost wear free and noiseless. They measure the flow
More informationSerial adapter 1.0 V10 Fadec to serial comunications
Serial adapter 1.0 V10 Fadec to serial comunications Users Guide. Torrent d en Puig, 31. 08358, Arenys de Munt, Barcelona,Catalonia,Spain E-mail: info@xicoy.com. Fax: +34 933 969 743 web: www.xicoy.com
More informationSensoStar C. Installation and Operating Instructions Heat Meter Calculator Heat/Cooling Meter Calculator Cooling Meter Calculator
Installation and Operating Instructions Heat Meter Calculator Heat/Cooling Meter Calculator Cooling Meter Calculator SensoStar C DE-18-MI004-PTB037 (MID heat) DE-18-M-PTB-0049 (national German cooling)
More informationINTECH Micro 2300-RTD6
INTECH Micro 2300-RTD6 6 Channel RTD Input Station Overview. The Intech Micro 2300 Series is a system of modular I/O Remote Stations, that add an even lower cost option to Intech s already extensive intelligent
More informationzelsius Installation and operating manual All that counts EnergyMetering
EnergyMetering zelsius Installation and operating manual Electronic compact heat meter M-Bus and 2 inputs/outputs optional Coaxial measuring capsule 2" q p 0.6/1.5/2.5 m³/h All that counts General information
More informationzelsius Installation and operating manual All that counts. EnergyMetering
EnergyMetering zelsius Installation and operating manual Electronic compact heat meter with single jet flow sensor M-Bus and 2 inputs/outputs optional qp 0.6/1.5/2.5 m³/h All that counts. General information
More information9142-B-P-156/AF. User s Guide. Field Metrology Well. Distribution is limited to DoD and U.S. DoD contractors only.
9142-B-P-156/AF Field Metrology Well User s Guide Distribution is limited to DoD and U.S. DoD contractors only. May 2013 2013 Fluke Corporation. All rights reserved. Specifications are subject to change
More informationSuperstatic 440. Static Heat Meter, Static Cooling Meter. Application
Superstatic 440 Static Heat Meter, Static Cooling Meter Application Design The Superstatic 440 is a static heat or cooling meter according to standard EN1434 class 2 based on the fluid oscillation principle,
More informationUSERS MANUAL MCD REMOTE OPERATOR
USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3
More informationDusty / Dusty Ex. Low-Cost Broken Bag Detection. Operating Instructions. SWR engineering Messtechnik GmbH
EN Dusty / Dusty Ex Operating Instructions Low-Cost Broken Bag Detection SWR engineering Messtechnik GmbH CONTENTS Page 1. Introduction.............................................................. 3 1.1
More informationCCIE Routing & Switching Hardware Specification
CCIE Routing & ing Lab Topology CCIE Routing & ing Hardware Specification Internetwork Expert s CCIE Routing & ing Lab Workbook Volume II uses the same hardware specification that is used in the actual
More informationPSU EN54-4 Power Supplies
PSU EN54-4 Power Supplies Ordering: Models, Sales Order Parts: PSU MXP-549 : 1.5A PSE in 7Ah enclosure MXP-550 : 3.0A PSE in 17/18Ah enclosure MXP-550D : 3.0A PSE in 25Ah enclosure MXP-551 : 5.0A PSE in
More informationInfocal 9 Energy calculator for heating and cooling applications
Installation & User Guide Infocal 9 Energy calculator for heating and cooling applications www.danfoss.com 2 Danfoss Energy Meters 2017.03 VUIGN102 1. Installation 1.1. Preparation Only qualified personnel
More informationModule B Module C FOR THE WEATHER CONTROLLER MULTI-MIX INSTALLATION MANUAL REVISION: 1.0_EN
Module B Module C FOR THE WEATHER CONTROLLER MULTI-MIX INSTALLATION MANUAL REVISION: 1.0_EN 05-2018 ELECTRIC DEVICE UNDER VOLTAGE! Before any action related to the power supply (cables connection, device
More informationDT304. Digital Temperature Logger INSTRUCTION MANUAL
Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 - TestEquipmentDepot.com DT304 INSTRUCTION MANUAL Digital Temperature Logger TABLE OF CONTENTS Introduction..........................................1
More informationThe 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.
1 Elmdene International Ltd Tel: +44 (0)23 9269 6638 3 Keel Close, Interchange Park, Fax: +44 (0)23 9266 0483 Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk STANDBY 220V AC POWER SYSTEM IDEAL
More informationInstallation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount
Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount Important Safety Messages Read the instructions carefully to become familiar with the equipment before
More informationENERGY MANAGER. Installation Manual
ENERGY MANAGER Installation Manual Safety Information Manual for Maxem Home Energy Manager. Publication Date: November 1, 2016 Questions or improvements If you see any errors or defects, if you have ideas
More informationCLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16
User Manual CLA-VAL Europe www.cla-val.ch cla-val@cla-val.ch 1 - LIN072UE - 04/16 Table of Contents 1 Introduction... 3 1.1 Precautions Before Starting... 3 1.2 Troubleshooting... 3 1.3 General Disclaimer...
More informationCORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS
Date of last update: Apr-15 Ref: D7.8.4/0112-0415/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors...
More informationDigital-Control and Programmable DC Power Supply Models: , , , & User Manual
Digital-Control and Programmable DC Power Supply Models: 72-2535, 72-2540, 72-2545, 72-2550 & 72-10480 User Manual Page 19/05/16 V1.0 Safety Symbols This chapter contains important safety instructions
More informationUser Manual Pocket Pro, Pro + ph
User Manual Pocket Pro, Pro + ph DOC022.52.80394 1 Specifications Specification Dimensions (W x D x H) Enclosure rating Weight Specifications are subject to change without notice. Details 37 x 30 x 170
More informationMXL Strada / Pista Plug and Play kit for Kawasaki ZX-10 R
INSTALLATION DOCUMENTATION 1/03/2006 P&P KIT Installation procedure for MXL Strada / MXL Pista Kawasaki ZX6R-ZX6RR - 2003-2004-2005 kit Version 1.02 Kawasaki ZX10R 2003-2004-2005 MXL Strada / Pista Plug
More informationZT-USB Series User Manual
ZT-USB Series User Manual Warranty Warning Copyright All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the date of delivery
More informationEnglish. Instruction and operation manual S 110. Power Meter
English Instruction and operation manual S 110 Power Meter Dear Customer, thank you for choosing our product. The operating instructions must be read in full and carefully observed before starting up the
More informationDominion PX. Quick Setup Guide. Before You Begin. Mounting Zero U Models Using L-Bracket. Zero U Size. 1U and 2U Size
Dominion PX Quick Setup Guide Thank you for purchasing the Dominion PX intelligent power distribution unit (PDU). The intended use of the Raritan Dominion PX is distribution of power to information technology
More informationInstallation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount
Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount Important Safety Messages Read the instructions carefully to become familiar with the equipment before attempting to install, operate,
More informationApplication Engineering Europe
Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for
More informationPROVA 1011 Solar System Analyzer
PROVA 1011 Solar System Analyzer CE CAT II 1000V, CAT III 300V Features: I-V curve test for solar system. Max. solar system power (Pmax) search by Auto-scan: 1000V, 12A (12000W capability). The analyzer
More informationMOTOR CONTROLLER SPECIFICATION
MOTOR CONTROLLER SPECIFICATION APACHE 120 / 240V 1. Scope This specification defines the basic characteristics for a motor controller Apache 120 / 240V, originally develop for laundry applications. This
More informationBattery-Powered Flow Transmitter
Data Sheet SS/AMAS/E Issue 3 Battery-Powered Flow Transmitter AquaMaster Explorer Widest flow range, highest accuracy measures minimal night and peak day flows Optional integral multi-speed, multichannel,
More informationINSTALLATION USER MANUAL
INSTALLATION & USER MANUAL DYNAMIC LOAD MANAGEMENT -PREMIUM- This document is copyrighted, 2016 by Circontrol, S.A. All rights are reserved. Circontrol, S.A. reserves the right to make improvements to
More informationJUMO thermocor. Portable measuring system for AMS2750 and CQI-9. Brief description. Block diagram. Special features. JUMO thermocor.
Page 1/8 JUMO thermocor Portable measuring system for AMS2750 and CQI-9 Brief description The JUMO thermocor is a high-precision documenting test device with 12 analog inputs for thermocouples. The use
More informationFeatures and Benefits. Certifications
iologik 4000 Series Modular remote I/O Features and Benefits I/O expansion without a backplane Active communication with MX-AOPC UA Server Supports SNMP v1/v2c Easy configuration with Modular ioadmin utility
More information5 kv and 10 kv Insulation Resistance
S1-552/2 and S1-1052/2 5 kv and 10 kv Insulation Resistance Testers n CAT IV 600 V n Mains or battery powered n Digital/analogue backlit display n Variable test voltage from 50 to 5000 or 10,000 V n Automatic
More informationBK BK A BK MA BK MA BK J93 MN93-BK MN193-BK MR193-BK SL261-BK SR193-BK
n COMPATIBLE CURRENT PROBES & SENSORS FOR POWER QUALITY METERS 193-24-BK 193-36-BK A196-24-BK MA193-10-BK MA193-14-BK J93 MN93-BK MN193-BK MR193-BK SL261-BK SR193-BK E N G L I S H User Manual Copyright
More informationOPERATIONS MANUAL CR Thermoreactor
OPERATIONS MANUAL CR 2200 Thermoreactor CR 2200 Note For the most recent version of the manual, please visit www.ysi.com. Contact Copyright YSI 1725 Brannum Lane Yellow Springs, OH 45387 USA Tel: +1 937-767-7241
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationHeat / Chill Meter PolluCom M Installation and Operating Instructions. PolluCom M. Installation and Operating Instructions. M H 1210 INT, Page 1
PolluCom M Installation and Operating Instructions M H 1210 INT, Page 1 The compact meter PolluCom M is suitable for the measurement of energy consumption in heating or chilling plants filled with the
More information27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2
1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:
More informationJUMO thermocor. Portable measuring system for AMS2750 and CQI-9. Brief description. Block diagram. Special features. JUMO thermocor.
sales@jumo.co.uk info.us@jumo.net Page 1/8 JUMO thermocor Portable measuring system for AMS2750 and CQI-9 Brief description The JUMO thermocor is a high-precision documenting test device with 12 analog
More informationUser Manual Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More informationMRXBOX-VSC Visual System User Control Installation and Maintenance
MRXBOX-VSC Visual System User Control Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU 1.0 INTRODUCTION The MRXBOX-VSC is a user control from the Ecosmart
More informationSupercal 539. Compact thermal energy meter
Supercal 539 Compact thermal energy meter Application Electronic, battery-powered compact thermal energy meter intended to record heat consumption in autonomous heating systems or combined heating/cooling
More informationBT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet
BT508/BT510/BT520/BT521 Battery Analyzer Safety Sheet Go to www.fluke.com to register your product, download manuals, and find more information. A Warning identifies conditions and procedures that are
More informationPQube 3 Modbus Interface
PQube 3 Modbus Interface Reference manual Revision 1.9 Modbus Interface Reference Manual 1.9- Page 1 Table of Contents 1. Background... 3 2. Basics... 3 2.1 Registers and Coils... 3 2.2 Address Space...
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationContent 1. Laserline series 3
FT LASERLINE Series TECHNICAL DATA SHEET FT LASERLINE Series 1. Laserline series Content 1. Laserline series 3 2. Connectors 4 3. Control system 4 4. Options 5 4.1 Automatic flow control 5 4.2 FT communication
More informationInstruction Manual. Q Series 2 Motor Control Modules - OEM
A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230
More informationMXL Pista / MXL Strada PLUG & PLAY KIT FOR SUZUKI GSX R
INSTALLATION DOCUMENTATION 9/11/2004 KIT MOTO Installation procedure for the Suzuki GSX-R- 2003-2004 kit Vers. 1.00 Suzuki GSX R 2003-2004 600 750 1000cc MXL Pista / MXL Strada PLUG & PLAY KIT FOR SUZUKI
More informationEnglish. Instruction and operation manual S 430. Pitot tube flow sensor
English Instruction and operation manual Pitot tube flow sensor Dear Customer, thank you for choosing our product. The operating instructions must be read in full and carefully observed before starting
More informationWSTH/WPTH. Woltmann type combined energy meter. Woltmann flow meters for large nominal flows combined with calculator and temperature sensors.
revision 04 2015 Woltmann type combined energy meter Woltmann flow meters for large nominal flows combined with calculator and temperature sensors. The WSTH and WPTH meters are designed for flow measurements
More informationl The Battery Tester is designed for measuring the l AC four-terminal method to measure the internal
Certificate of Calibration We hereby certify that this product has been calibrated and found to be in accordance with the applicable SPECIFICATIONS and STANDARDS. Accuracies of the standard equipment used
More informationIFX-M4-03 IFX-M4-03_D_E_2017_05_REV.0
IFX-M4-03 IFX-M4-03_D_E_2017_05_REV.0 Table of contents PRINCIPLE... 4 HOW TO ORDER... 4 TECHNICAL DATA... 5 Table 1.1... 6 Table 1.2... 7 Table 1.3... 7 Straight pipelines lengths... 7 Conveying liquid...
More informationGetting started with
PART NO. CMA113 MADE IN CHINA 1. Measuring CAT II 2. Max. voltage 250V ~ 3. Max. current 71 Amp Getting started with Electricity consumption & Solar PV generation monitoring single phase, for homes fitted
More informationCurrent transformers. Current transformers
Current transformers Current transformers Moulded case current transformer Moulded case CT, class 1 and 0.5 / 5 A Increased reliability Both halves of the housing overlap rather than butting up against
More informationMVN Rotary Valve Actuators FOR CONTROL BALL VALVES VBG (DN15 TO DN32)
MV Rotary Valve ctuators FOR COTROL LL VLVES VG (D5 TO D) PPLICTIO MV m Control Valve Rotary Valve ctuators are used with the VG -way and the VG -way Control all Valves to control hot and chilled water
More informationEazipole Cordless. Installation & Set Up Instructions. Electric Blinds & Curtains
Eazipole Cordless Installation & Set Up Instructions Electric Blinds & Curtains Pole Installation - Deciding The Best Position Points to consider when planning the installation of your pole It may be easiest
More informationUser Manual for the RAMK Rotational Absolute Magnetic Kit Encoder
VISHAY MCB www.vishay.com Variable Resistors By Frederic Bourget and Emmanuel Lemelle INTRODUCTION The purpose of this user manual is to define the precautions for unpacking, mounting, and using RAMK encoder
More informationReadStar & CapStar Range Torque Readouts & Torque Testers. Crane Electronics Inc The force in torque management
ReadStar & CapStar Range Torque Readouts & Torque Testers Crane Electronics Inc The ReadStar range enables the measurement and collection of torque data. The ReadStar range comprises ReadStar II, ReadStar
More informationUniversity of Delaware
25 05 00_ENERGY AND WATER METERING REQUIREMENTS APPLICATION All energy utilities and water shall be metered at the individual building level (at a minimum) and meters shall be connected to UD Energy ing
More informationUser Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software
User Manual Thank you for purchasing the Defender 650/1200/1600. It is designed to provide safe and reliable power protection to your precious electronics equipment. Before you start using the product,
More informationEPAS Desktop Pro Software User Manual
Software User Manual Issue 1.10 Contents 1 Introduction 4 1.1 What is EPAS Desktop Pro? 4 1.2 About This Manual 4 1.3 Typographical Conventions 5 1.4 Getting Technical Support 5 2 Getting Started 6 2.1
More informationFlex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No
Flex current clamps A 1179 A 1257 A 1395 User Manual Version 1.6; Code No. 20 751 167 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul Tel.: +386 1 75 58 200 Fax: +386 1 75 49 226 E-mail:
More information1 EASY COMMISSIONING GUIDE FRONIUS PV-SYSTEM CONTROLLER
1 EASY COMMISSIONING GUIDE FRONIUS PV-SYSTEM CONTROLLER Reading this document does not substitute for user s reference to CIRCUTOR CDP-DUO user-guide. 1.1 Scope Using Fronius grid-tie inverters in remote
More informationHoneywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION
Honeywell VV, VP, VB & MS SERIES FOR VQ400M CLASS A VALVES PRODUCT HANDBOOK APPLICATION The VV Series class A vent valves are intended to be used in combination with the VQ400M series combination valve.
More informationMXL Pista / MXL Strada KIT FOR SUZUKI GSX R
INSTALLATION DOCUMENTATION 1/03/2006 Bike KIT Installation Manual: MXL kit for Suzuki GSX-R K5-K6 Version 1.02 Suzuki GSX R K5-K6 750cc 1000cc MXL Pista / MXL Strada KIT FOR SUZUKI GSX R 2005-2006 The
More informationEmergency lighting units EM LED Light Engines
EM readyapply SELFTEST W EM readyapply Product description LED emergency module suitable for direct installation in ceilings Complete set with integrated electronics, LED module, heat sink, optics and
More informationBERMAD Waterworks. Insertion Flow Meter Device (IFM)
IFM-MUT1222PRV BERMAD's IFM-MUT1222-PRV SENSOR is designed for measuring the flow rate of valves sized DN80 to DN600 (3-24 ). This document describes the installation process of the sensor. For larger
More informationHeating / Cooling Meter PolluCom E Installation and Operation Instructions
Our compact meter PolluCom E is used for measuring energy consumption in plants carrying water as heating or cooling liquid. These installation and operation instructions specify how to install and operate
More informationUSER MANUAL. Revision 1.0.1
9ABCDEF08 NMEA2000 EXHAUST MULTIFUNCTION GAS TEMPERATURE DISPLAY Part MODULE Numbers: & PROBE3345 USER Part Numbers: MANUAL 4510 USER MANUAL 1234567 Revision 1.0.1 Revision History 1 1 Introduction 3
More information