INSTALLATION, OPERATION and MAINTENANCE MANUAL for FLOTEC SENSOR

Size: px
Start display at page:

Download "INSTALLATION, OPERATION and MAINTENANCE MANUAL for FLOTEC SENSOR"

Transcription

1 di Wika Italia Srl Sas Via G. Borghisani, PIEVE S. GIACOMO (CR) ITALY Tel.: Fax: euromisure@euromisure.it IM-FLO-E-10/02 Pagine Documento Document Pages 16 IM INSTALLATION, OPERATION and MAINTENANCE MANUAL for FLOTEC SENSOR Mod. S-730 Mod. S-750 Mod. S-755 Mod. F-730 Mod. F-750 / F-780 Mod. F-755 / F-785 Mod. EM-730 Mod. EM-750 / EM-780 Mod. EM-755 / EM-785

2 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 2 IM INDEX 1) Scope 2) General Description of the FLOTEC Device 3) Operating Limitations 4) Selecting Mounting Location 4.1 Straight Run Requirements 4.2 Relation to Readout Device 4.3 Pulsation & Vibration 4.4 Position in the Pipe Liquid Flow Measurement Air / Gas Flow Measurement Steam / Vapor Flow Measurement 5) Installation Instruction 5.1 Model S with Coupling, Gland, Packing and Threaded Ferrule FLOTEC Model S-730 and S-750 (without opposite support) FLOTEC Model S-755 (with opposite support) 5.2 Model F with Flanged Mounting Nozzle FLOTEC Model F-730, F750 and F-780 (without opposite support) FLOTEC Model F-755 and F-785 (with opposite support) 5.3 Model EM with Flanged Mounting Nozzle Extractable Type FLOTEC Model EM-750 and EM-780 (without opposite support) FLOTEC ;Model EM-755 and EM-785 (with opposite support) 6) Insertion / Extraction System for Extractable Type FLOTEC ( EM Model) 6.1 Insertion of the FLOTEC Sensor 6.2 Extraction of the FLOTEC Sensor 7) Meter Connection and Location 7.1 General Requirements 7.2 Requirements for Liquid 7.3 Requirements for Air and Gas 7.4 Requirements for Steam 8) Purging 8.1 Periodic Purging 9) Maintenance 10) Interchangeability 11) Troubleshooting Guide 11.1 Questionable Accuracy 11.2 Low Signal 11.3 Spiking Signal

3 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 3 IM 1) SCOPE This manual describes the general functioning principles and the essential safety requirements for the handling, the installation, the use and the maintenance of the standard FLOTEC shown on page 1 and codified as per follow description : Mounting type: S: Coupling with gland, packing and threaded ferrule F: Flanged mounting nozzle EM: Flanged mounting nozzle extractable type under process condition. Series: 73: suitable for small pipe diameter, low-stress conditions 75: suitable for medium pipe diameter, medium-stress conditions 78: suitable for large pipe diameter, high-stress conditions Application of opposite support (if required): Suffix 0 (Model type xx0): without opposite support Suffix 5 (Model type xx5): with opposite support (Not Applicable for Series 73) The choice of the applicable model is based on the vibration / frequency due to the process conditions. The high capacity FLOTEC models (F-790 and F-795), suitable for strongest process conditions are not in the scope of this manual. 2) GENERAL DESCRIPTION OF THE FLOTEC DEVICE The FLOTEC is based on the classical Pitot tube rule, but the average upstream velocity (and as consequence the average upstream pressure) is taken from 4 different pressure taps (dynamic) located in defined positions on the upstream edge of the square-bar of the FLOTEC. While the static pressure tap (downstream pressure) is located on the downstream edge of the square-bar of the FLOTEC, in the centre of the pipe line diameter. The difference between the dynamic and static pressure taps is the measured Dp of the device. Like all the others flow measurement, the applicable equation for the FLOTEC is the follow: Q Fm Dp Gf where Q is the volumetric flow rate, Fm is a correction factor for dimensional units which includes a discharge coefficient to correct for the characteristics of the construction, Dp is the pressure difference between the measured upstream and downstream pressures, Gf is the density of the fluid. The condition necessary to obtain an accurate flow rate measurement is to have stable flow rate, pressure and temperature states. 3) OPERATING LIMITATIONS Structural limitations based on differential pressure are included in the here below Graph 1, for temperatures up to 93 C. For higher operating temperatures, reduce the maximum allowable differential pressure (Dp) by 3% each 38 C from 93 C to 400 C. These values are applicable for AISI 316 / AISI 316L (Stainless Steel) FLOTEC sensor material only.

4 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 4 IM 4) SELECTING MOUNTING LOCATIONS Correct location of the FLOTEC in the pipeline is important because disturbance in flow by pipe layout may affect the accuracy of measurement. The following standard practices should be reviewed before selecting a mounting location : 4.1 Straight Run Requirements Table 1 here below shows recommended approach and depart values in terms of straight pipe diameters for normal industrial metering work. For laboratory or high accuracy work, add 25% to the values shown. Use of recommended straight pipe lengths of uniform diameter upstream and downstream in sures that flow measurements will be made in flow with fully-developed characteristics. Straightening vanes may be used to reduce the length of straight pipe required in many cases. Table 1 1) Exceptions : Field experience has proven that FLOTEC produces a repeatable signal even in pipes with less than the recommended upstream and downstream straight pipe. In such cases, FLOTEC is an effective flow sensor for control and other applications where repeatability is the most important factor. 2) Pos.6 includes gate, globe, plug, and other throttling valves that are only partially opened. If valve is to be fully open, use values shown on Pos. 4 or 5. Control valves should be located after FLOTEC element.

5 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 5 IM Table 1 - Upstream and Downstream straight run pipe requirement (multiple of internal pipe diameter D) 4.2 Relation to Readout Device The distance between the meter (Dp transmitter) and the FLOTEC should be as short as possible. If the distance from meter to sensor is under 50 feet (15 m), 1/4 " OD tubing is satisfactory. For each additional 50 feet (15 m), use tubing 1/8" larger in size.

6 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 6 IM 4.3 Pulsation & Vibration Avoid the location of the FLOTEC in pulsating flow. This may result in "noisy" signal problems. Vibration can also distort the output signal and compromise structural limits of the FLOTEC. Mount the FLOTEC in a secure, stable run of pipe to obtain optimum signal output. 4.4 Position in the Pipe FLOTEC may be installed in any plane of the pipe ( horizontal, vertical, 45, or any angle in-between). However, for trouble free operation, consideration must be given to the type of fluid and the secondary instrumentation LIQUID FLOW MEASUREMENT For vertical pipes, the FLOTEC can be installed in any position of the 360 circumference of the pipe. For horizontal pipes, it is suggested to install the FLOTEC into the bottom side (see Fig.1) so that the instrument connections are below the pipe center line. This will keep the instrument lines full of liquid and encourage air or gas that may be in the instrument tubing to find its way to the sensor and thus into the flowing fluid. For liquid applications is necessary to vent the trapped air (or gas) in the instrument before to do a flow measurement. In case of big dimensions pipe and/or underground applications the FLOTEC must be mounted vertically AIR / GAS FLOW MEASUREMENT On vertical pipes, the FLOTEC may be installed in any position of the 360 circumference of the pipe. For horizontal pipes, the FLOTEC should be installed so the instrument connections are above the pipe center line (see Fig.2). This is to prevent moisture or condensation from entering the connecting lines. In case of big dimensions pipe and/or underground applications the FLOTEC must be mounted vertically. Fig. 1 Installation of FLOTEC in horizontal pipe for LIQUID Fig. 2 Installation of FLOTEC in horizontal pipe for AIR / GAS

7 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 7 IM STEAM / VAPOR FLOW MEASUREMENTS On vertical pipes, the FLOTEC may be installed in any position of the 360 circumference of the pipe, with the instrument connections on the same horizontal plane (see Fig.3). FLOTEC for vertical steam lines must be manufactured with instrument connections at right angle to flow direction. For horizontal pipes, install the FLOTEC in the above side of the pipe (see Fig.4). Steam flow measurement requires special consideration for successful operation (see Para 7.4). Fig. 3 Installation of FLOTEC in vertical pipe for STEAM Fig. 4 Installation of FLOTEC in horizontal pipe for STEAM 5) INSTALLATION INSTRUCTIONS 5.1 MODEL S WITH COUPLING, GLAND, PACKING AND THREADED FERRULE FLOTEC Model S-730 and S-750 (without opposite support) sketch No. 1 2 / 3 / ) Drill or burn a 35 mm hole in pipe for furnished mounting coupling. 2) Install threaded ferrule (without gland) on mounting coupling to protect threads during welding.

8 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 8 IM 3) Tack weld mounting coupling to the pipe and align it so it is perpendicular to and intersects the pipe axis. A convenient way to do this is to insert a short piece of 1" diameter stock into the mounting coupling and use it as leverage for alignment. 4) Complete welding 5) Remove threaded ferrule from mounting coupling and slide it onto FLOTEC along with the gland. The short-tapered end of gland should be pointing toward the probe tip so that it goes into the mounting coupling installed in the pipe. Place the packing into the coupling. 6) Insert the FLOTEC along with the threaded ferrule and the gland into the mounting coupling on the pipe. Align the flow arrow on the FLOTEC with the direction of flow and the flats on the FLOTEC head parallel to the pipe axis. Be sure the FLOTEC is touching the back side of the pipe. Tighten the compression nut to 250 lbs. ft. (340 Nm) torque. Approximately one full thread is left exposed under the nut. Use of a 2 to 3 ft. (60 to 90 mm) wrench is normally required. It may be necessary to hold the head of the FLOTEC with a wrench to keep it from rotating while tightening the threaded ferrule. To obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE FLOTEC Model S-755 (with opposite support) sketch No. 2 / 3 / 4 5 / ) Repeat the operations from 1 to 3 as per FLOTEC Model S-730 and S-750 instructions (5.1.1). 2) Locate position for opposite support coupling by putting a piece of soft wire or string around the pipe. Measure halfway (180 ) around the pipe from mounting coupling and mark center for opposite support coupling. 3) Drill or burn a 35 mm hole at mark for opposite support coupling. 4) Tack opposite support coupling in place. Check for correct alignment by inserting FLOTEC through mounting coupling and opposite support coupling. Remove FLOTEC and complete welding for both coupling. 5) Remove threaded ferrule from mounting coupling and slide it onto FLOTEC along with the gland. The short-tapered end of gland should be pointing toward the probe tip so that it goes into the mounting coupling installed in the pipe. Place the packing into the coupling. 6) Insert FLOTEC along with threaded ferrule and gland into mounting coupling and through to the opposite support coupling. 7) Screw hex plug into opposite support coupling and guide FLOTEC into it. Use pipe thread compound on it and tighten hex plug until it is secure. 8) Push FLOTEC until it touches bottom of hex plug. Align the flow arrow on the FLOTEC with the direction of flow and the flats on the FLOTEC head parallel to the pipe axis. Tighten the compression nut to 250 lbs. ft. (340 Nm) torque. Approximately one full thread is left exposed under the nut. Use of a 2 to 3 ft. (60 to 90 mm) wrench is normally required.

9 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 9 IM It may be necessary to hold the head of the FLOTEC with a wrench to keep it from rotating while tightening the threaded ferrule. To obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE 5.2 MODEL F WITH FLANGED MOUNTING NOZZLE FLOTEC Model F-730, F-750 and F-780 (without opposite support) The flanged nozzle could be supplied by Euromisure or supplied by piping and in this case the Customer have to give to Euromisure the following informations, mandatory to design in the correct way the FLOTEC: - DN, Rating and the facing type of flanges (RF, FF, RTJ etc.) - The exact height of the nozzle (from flange facing surface to the external surface of the pipe) - The internal diameter of the nozzle have to be 1.3/8 (35 mm) minimum for FLOTEC Models F-730, F- 750 and F-755 and 2.3/8 (60 mm) minimum for FLOTEC Model F-780 and F-785. The flanged nozzle supplied by Euromisure have not a fix distance from the flange facing surface to the external face of the pipe. Usually is 150mm, but it depend from the type of nozzle (weldolet and flange type, or coupling, pipe and flange type) or from the thickness of insulation (the Customer have to inform Euromisure if it is applicable or not) sketch No. 1 / ) If the mounting nozzle is supplied by Euromisure, drill or burn a 35 mm hole for Mod. F-730 and F-750, or 60 mm for Mod. F-780 in pipe. 2) Tack weld mounting nozzle (attention to the position of the holes for bolts) to the pipe and align it so it is perpendicular to and intersects the pipe axis. 3) Complete welding. 4) Insert the FLOTEC into the flanged nozzle (attention to the position of the flow arrow shown on the FLOTEC head) and complete with gaskets and fix with bolts and nuts (this operation is valid also for the FLOTEC with mounting nozzle NOT supplied by Euromisure). to obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE.

10 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 10 IM FLOTEC Model F-755 and F-785 (with opposite support) sketch No. 2 / ) Repeat the operations 1 & 2 as per FLOTEC Model F-730, F-750 & F-780 instructions (5.2.1). 2) Locate position for opposite support nozzle by putting a piece of soft wire or string around the pipe. Measure halfway (180 ) around the pipe from mounting nozzle and mark center for opposite support nozzle. 3) Drill or burn a 35 mm hole for Mod. F-755 or 60 mm hole for Mod. F-785 at mark for opposite support nozzle. 4) Tack opposite support nozzle (attention to the position of the holes for bolts) to the pipe and align it so it is perpendicular to and intersects the pipe axis. The blind flange (and its centering pipe, gaskets and bolts and nuts) have to be mounted on the opposite flanged support. Check for correct alignment by inserting FLOTEC through mounting nozzle and opposite support nozzle. Remove FLOTEC and complete welding for both nozzle. 5) Insert the FLOTEC into the flanged nozzle (attention to the position of the flow arrow shown on the FLOTEC head) and check that the end part of the FLOTEC go into the opposite flanged support. Complete with gaskets and fix with bolts and nuts (this operation is valid also for the FLOTEC with mounting nozzle NOT supplied by Euromisure). To obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE 5.3 MODEL EM WITH FLANGED MOUNTING NOZZLE EXTRACTABLE TYPE FLOTEC Model EM-750 and EM-780 (without opposite support) 1) Repeat the operations from 1 to 4 as per FLOTEC Model F-730, F-750 and F-780 instructions (5.2.1). To obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE FLOTEC Model EM-755 and EM-785 (with opposite support) 1) Repeat the operations from 1 to 4 as per FLOTEC Model F-755 and F-785 instructions (5.2.2). To obtain a good measurement you must respect the tolerance indicated at Para 9-TROUBLESHOOTING GUIDE

11 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 11 IM 6) INSERTION / EXTRACTION SYSTEM FOR EXTRACTABLE TYPE FLOTEC ( EM MODEL) The extractable FLOTEC model, is a flanged mounting nozzle model with the extraction system to insert / extract the FLOTEC under process condition. For safety, the extractable FLOTEC model is NOT applicable if one or more of the following conditions happens in the process: - Lethal fluid - Toxic fluid - Easily flammable fluid - Acids or other fluids that could be dangerous in general for the operator - Operating pressure higher than 200 Bar - Operating temperature higher than 300 C The extraction system is applicable for the following FLOTEC model: EM-750 and EM-780: flanged model without opposite support EM-755 and EM-785: flanged model with opposite support 6.1 INSERTION OF THE FLOTEC SENSOR 6.1 sketch No. 1 / 2 / 3 / 4 5 / 6 7 / 8 / 9 1) Check that the blow-out bleed valve mounted on the packing seat is fully closed 2) Unscrew and lift up the anti-squirt cap 3) Loosen the packing gland without remove it 4) Fully open the isolation valve (usually 1.1/2 ball valve type). Be carefully, because during this operation some fluid may exit from the packing gland; in this case tighten the packing gland till the leakage finished. If necessary, for the operator safety, during the tighten of the packing gland re-close temporarily the isolation valve and re-test again the packing gland seal. 5) Re-screw the anti-squirt cap on its original position and check that the isolation valve is fully open. 6) Turn the hand wheel till the lock-washer welded on the threaded rod (highlighted in red color) reach its end limit (inserted position) 7) Unscrew and lift up the anti-squirt cap 8) Tighten the packing gland 9) Re-screw the anti-squirt cap on its original position.

12 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 12 IM 6.2 EXTRACTION OF THE FLOTEC SENSOR 6.2 sketch No. 1 / 2 / / 6 / 7 / 8 / 9 / 10 1) Unscrew and lift up the anti-squirt cap 2) Loosen the packing gland without remove it. Be carefully, because during this operation some fluid may exit from the packing gland; in this case tighten the packing gland till the leakage finished. 3) Re-screw the anti-squirt cap on its original position 4) Turn the hand wheel till the green band painted on the threaded rod reach its end limit (extracted position). Warning!! Don t close the isolation valve if the green band have not yet reach its end limit, to avoid to damaged seriously the seal of valve against the FLOTEC, not yet completely extracted 5) Only when the point 4) is completed, fully close the isolation valve (usually 1.1/2 ball valve type). 6) Open the blow-out bleed valve to discharge the residual pressure and fluid from the extension nipple of the FLOTEC. Is possible to connect the bleed valve with a discharge tank at site. 7) Unscrew and lift up the anti-squirt cap 8) Tighten the packing gland 9) Re-screw the anti-squirt cap on its original position 10) Close the blow-out bleed valve

13 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 13 IM 7) METER CONNECTION AND LOCATION 7.1 GENERAL REQUIREMENTS Following is a checklist of general instrument practices for meter connecting tubing. Refer to installation instructions provided by the secondary instrument manufacturer to cover all contingencies of your application. 1) Connecting tubing must have a slope of least one inch per foot (25 mm each 300 mm) and must be supported over its entire length to prevent sagging. 2) The two connecting lines should be run close together to maintain equal temperatures. CAUTION : Be sure nylon or rubber lines are kept away from hot lines or other heat sources. 3) Run tubing in protected areas such as conduit, channels, I-beams or angles, against walls or ceilings. Protect horizontal runs near the floor or under work areas with steel sheeting for kick plates. 4) Run tubing where it will be accessible for maintenance. On long runs, tubing should be tagged every 30 to 40 feet (900 to 1200 mm) for easy identification. 5) Tubing must be absolutely airtight. If vibration is expected, set up a periodic inspection procedure for checking all joints for leakage. 7.2 REQUIREMENTS FOR LIQUID Trapped air in the piping system is responsible for the majority of problems associated with liquid flow measurement. Differential pressure must be transmitted from the FLOTEC to the secondary instrumentation through a solid head of non compressible liquid. Installation of the instrumentation below the FLOTEC is preferred for liquid service (see Fig. 5 and 6). Fig. 5 - LIQUID IN HORIZONTAL LINE Fig. 6 - LIQUID IN VERTICAL LINE For horizontal line, when is not possible to mount the FLOTEC under the pipe, it can be mounted above, but in this case a periodic vent of the system is necessary, to avoid the presence of air or gas that could be modify the flow measurement. 7.3 REQUIREMENTS FOR AIR and GAS Differential pressure must be transmitted from the FLOTEC to the secondary instrument without change due to leakage or trapped liquid. For dry air or gas, the secondary instrument may be mounted either below or above the FLOTEC. For wet or dirty air or gas flow, the secondary instrument should be mounted above the FLOTEC, or settling traps should be installed in the connecting lines (see Fig. 7 and 8).

14 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 14 IM Fig. 7 AIR / GAS IN HORIZONTAL LINE Fig. 8 AIR / GAS IN VERTICAL LINE 7.4 REQUIREMENTS FOR STEAM Differential pressure must be transmitted from the FLOTEC to the secondary instrument but the steam must not enter on the transmitter. Fill the system with cool water before pressurizing the system, using a tee connection installed after the valves mounted on the FLOTEC head. The installation of a condensing pot for each pressure tap instead of a tee is suggested. For steam in vertical pipe, the position of the head have to be rotate of 90 respect to the other standard installation, because the head of the FLOTEC have to be perpendicular to the pipe to have the two pressure taps at the same height (see Fig. 9 and 10). Fig. 9 STEAM IN HORIZONTAL LINE Fig. 10 STEAM IN VERTICAL LINE 8) PURGING FLOTEC have been used successfully for measuring flow of very contaminated fluids without purging. Conditions requiring purging are variable, and if the applications is questionable, use without purging and plan to use purging as a back-up. 8.1 PERIODIC PURGING Periodic or intermittent purging is the simplest purging method and should be considered first for contaminated flow measurement. To do this, install an air or steam line to the instrument lines and periodically blow through the element to force out contamination.

15 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 15 IM 9) MAINTENANCE The FLOTEC is virtually maintenance-free. Anyway it should be cleaned in the follow way: 1) Remove the element 2) Flush completely 3) Hand-clean with soft wire brush 4) Rod interpolating and static tubes with a soft wire brush For the extractable type model, lubricate each month the threaded rod and its seats. 10) INTERCHANGEABILITY Each FLOTEC is designed for a particular line size and type installation. The FLOTEC may be inter-changed among different pipes if the pipe size and installation are identical (Internal pipe diameter, thickness of the pipe and heights of the mounting/opposite nozzle). This provides great flexibility, especially when a Flo-Tap FLOTEC is used. The same FLOTEC may be used with different fluids. For example, the same FLOTEC may be used to measure liquid or gaseous propane, air, water or steam, always if the pipe size and installation are identical. The re-calculation of DP to flow conversion is the only adjustment required. FLOTEC is not recommended for two phase(liquid/vapor or liquid/gas) flow measurement 11) TROUBLESHOOTING GUIDE FLOTEC operates on natural scientific principles. No moving parts are used in the design, and wear has negligible effect on accuracy. If installed correctly, FLOTEC will provide a correct flow indication if there is flow in the pipe. To resolve a discrepancy, interpretation of the FLOTEC, signal and other components of the flow system should be examined closely QUESTIONABLE ACCURACY 1) FLOTEC installation : Insure that the FLOTEC flow arrow is pointing directly downstream. FLOTEC accuracy will be influenced by installation misalignment. To insure meeting stated accuracies, alignment must be within the limits shown here below (see Fig. 11). Fig. 11 FLOTEC INSTALLATION MISALIGNMENT LIMITS 2) Pipe Size : The FLOTEC may have been designed for a different pipe size from that in which it is being used. Measure pipe ID and compare with size printed on identification tag attached to the FLOTEC.

16 Sas di Wika Italia Srl IM-FLO-E-10/02 Pagina / Page 16 IM 3) Insufficient straight run : If the FLOTEC is installed in less than recommended straight run pipe length, accuracy may be affected (see Para Table 1 for straight run requirements). 4) Calculations : The calculation for a particular FLOTEC may be in error. Re-check the calculation or graph used for conversion. Changes in operating temperature or pressure are critical on air, gas or steam applications. Re-check the actual operating temperature and pressure compared to the values used in the calculation LOW SIGNAL 1) Leaks : Check for leaks in the instrument piping. Repair and seal all leaks. 2) Contamination / Plugging : Remove FLOTEC and check for contamination. Clean the FLOTEC as shown on Para 9 - MAINTENANCE. If removal is not practical, back-flush through instrument lines or through cleanout ports (plugged with 1/8 NPT on top side of the FLOTEC head) SPIKING SIGNAL 1) Pulsating Flow : If FLOTEC is installed in this condition, the signal will reflect the flow condition with a spiking signal. If unable to relocate, mechanical pressure snubbers in the instrument lines or electronic damping may alleviate this problem. 2) Two-Phase (Liquid/Vapor) Flow : Two-phase or alternating-phase flow will cause an erratic spiking signal. FLOTEC is a head measuring device and will not accurately measure two-phase flow.

User Guide IM/TORBAR-EN Rev. D. Averaging pitot tubes

User Guide IM/TORBAR-EN Rev. D. Averaging pitot tubes User Guide IM/TORBAR-EN Rev. D Torbar The Company We are an established world force in the design and manufacture of measurement products for industrial process control, flow measurement, gas and liquid

More information

Rosemount 585 Annubar Flanged Flo-Tap Assembly

Rosemount 585 Annubar Flanged Flo-Tap Assembly Quick Installation Guide 00825-0200-585, Rev AA Flanged Flo-Tap 585 Annubar Rosemount 585 Annubar Flanged Flo-Tap Assembly Start Step 1: Location and Orientation Step 2: Weld Mounting Hardware Step 3:

More information

Annubar Flowmeter Series

Annubar Flowmeter Series Annubar Flowmeter Series Section 2 Installation Safety Messages................................. page 2-1 Installation Flowchart and Checklist................ page 2-2 Mounting.......................................

More information

Rosemount 285 Annubar Pak-Lok Assembly

Rosemount 285 Annubar Pak-Lok Assembly Quick Installation Guide 0025-0100-02, Rev AA Pak-Lok 25 Annubar Rosemount 25 Annubar Pak-Lok Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Weld Mounting Hardware

More information

Rosemount 485 Annubar Flanged Assembly

Rosemount 485 Annubar Flanged Assembly Quick Installation Guide 00825-0100-809, Rev DB Flanged 85 Annubar Rosemount 85 Annubar Flanged Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Assemble and Check

More information

Rosemount 485 Annubar Pak-Lok Assembly

Rosemount 485 Annubar Pak-Lok Assembly Quick Installation Guide 00825-0300-809, Rev EA Pak-Lok 85 Annubar Rosemount 85 Annubar Pak-Lok Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Weld Mounting Hardware

More information

Rosemount 485 Annubar Threaded Flo-Tap Assembly

Rosemount 485 Annubar Threaded Flo-Tap Assembly Quick Installation Guide 00825-0500-809, Rev DB Threaded Flo-Tap 85 Annubar Rosemount 85 Annubar Threaded Flo-Tap Assembly Step 1: Location and Orientation Step 2: Weld Mounting Hardware Step 3: Install

More information

The Annubar Flowmeter Series

The Annubar Flowmeter Series Reference Manual The Annubar Flowmeter Series Model 3095MFA Mass ProBar Model 3051SFA ProBar Model 485 Annubar Primary www.rosemount.com Reference Manual Annubar Flowmeter Series The Annubar Flowmeter

More information

Scope. Applicability. Caution. I & M CV3000 Series. Storage. Installation & Maintenance Instructions for Marwin CV3000 Series Three Piece Ball Valves

Scope. Applicability. Caution. I & M CV3000 Series. Storage. Installation & Maintenance Instructions for Marwin CV3000 Series Three Piece Ball Valves I & M CV3000 Series 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 marwin@richardsind.com www.marwinvalve.com Installation & Maintenance Instructions for Marwin CV3000 Series

More information

The 285 Annubar Primary Element Series

The 285 Annubar Primary Element Series The 285 Annubar Primary Element Series www.rosemount.com Rosemount 285 285 Annubar Primary Element Series NOTICE Read this manual before working with the product. For personal and system safety, and for

More information

IFOA Integral Flow Orifice Assembly

IFOA Integral Flow Orifice Assembly Instruction MI 022-333 July 2007 Introduction IFOA Integral Flow Orifice Assembly The IFOA integral flow orifice assembly is used in conjunction with a Foxboro electronic or pneumatic differential pressure

More information

V400D VERIS Verabar (Double Rod) Installation and Maintenance Manual

V400D VERIS Verabar (Double Rod) Installation and Maintenance Manual V400D VERIS Verabar (Double Rod) Installation and Maintenance Manual 168-EN Please read and save these instructions Contents General Safety Information...3 Product Information...3 Section 1: Scope...3

More information

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators

Ideal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators I & M Mark (/ ) 0 Wasson Road Cincinnati, OH 0 USA Phone --00 Fax -8-00 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark Pressure Regulators Warning: Jordan Valve

More information

KB Series self averaging pitot flowmeter for gas, liquids and steam flows

KB Series self averaging pitot flowmeter for gas, liquids and steam flows process measurement solutions K Series self averaging pitot flowmeter for gas, liquids and steam flows Data sheet IP371 Advantages of the K series Description Patented square sensor design - reliable accuracy

More information

Low Profile Insertion Vortex

Low Profile Insertion Vortex Low Profile Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 24 Heavy Duty & Maintenance Free

More information

High Lift Flange Weld/Test Plug (3/4"-8") - Technical Specifications

High Lift Flange Weld/Test Plug (3/4-8) - Technical Specifications EXPANSION SEAL TECHNOLOGIES DC8055 11/98 REV 4 03/05 High Lift Flange Weld/Test Plug (3/4"-8") - Technical Specifications Flange Size Ansi Flange Class Pipe Schedule Part Number Plug OD Seal to Pipe Pipe

More information

SmartCone Differential Pressure Flow Meter User Manual

SmartCone Differential Pressure Flow Meter User Manual SmartCone Differential Pressure Flow Meter User Manual Page 1 Table of Contents Section 1 - SmartCone Introduction... 4 1.1 Introduction... 4 1.2 SmartCone - Meter Components... 4 1.3 Principles of Operation...

More information

5000/6000 SERIES BALL VALVES INSTALLATION - MAINTENANCE MANUAL

5000/6000 SERIES BALL VALVES INSTALLATION - MAINTENANCE MANUAL Date: August 2011 / Page 1 of 6 5000/6000 SERIES BALL VALVES INSTALLATION - MAINTENANCE MANUAL DESIGN The design features three piece construction and a free floating ball allowing ease of maintenance

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Intelligent Flow Measurement Your Sole Source for Badger Differential Producers Worldwide 6 Blackstone Valley Place, Lincoln RI 02865-1162 Ph: 401 334 1170 Fx: 401 334 1173 Em: solutions@wyattflow. Installation,

More information

V200D VERIS Verabar (Double Rod) Installation and Maintenance Manual

V200D VERIS Verabar (Double Rod) Installation and Maintenance Manual V200D VERIS Verabar (Double Rod) Installation and Maintenance Manual 173-EN Please read and save these instructions Contents General Safety Information...3 Product Information...3 Section 1: Scope...3

More information

Averaging Pitot Tube Flowmeter Catalogue ED IN AUSTRALIA

Averaging Pitot Tube Flowmeter Catalogue ED IN AUSTRALIA Averaging Pitot Tube Flowmeter Catalogue ED IN AUSTRALIA WHAT IS A TORFLOW? TheTORFLOW is a multiport self-averaging flow meter with a design based on the classical pitot tube concept of fluid flow measurement.

More information

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL

FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL FRP BALL VALVES TABLE OF CONTENTS MAINTENANCE AND INSTALLATION INSTRUCTIONS 1. 2. 2.1 2.2 2.3 2.4 GENERAL...Page 1 HANDLING...1 Receiving and Storing...1

More information

Model 1000 Vortex Meter

Model 1000 Vortex Meter Model 1000 Vortex Meter Installation and Instruction Manual Table of Contents General Information... 1 1-1 General... 1 1-2 Principles of Operation... 1 1-3 Sensor Operation... 1 1-4 Calibration Factor...

More information

To ensure proper installation, digital pictures with contact information to before startup.

To ensure proper installation,  digital pictures with contact information to before startup. Check List for Optimal Filter Performance? There should be no back-pressure on the flush line. A 1 valve should have a 2 waste line, and 2 valve should have a 3 waste line. Do not use rubber hosing or

More information

[DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary. Document No:

[DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary. Document No: Three-Piece ball valve EA-307 Series PED Category I, II EA-307 User Manual English Version [DRAFT VERSION] For use for company in Europe who will place the product on the market. Please amend which necessary.

More information

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A WATTS INDUSTRIES, INC. Technical Data SD 4512A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 4512A/9806 T124/T134 PILOT FRONT VIEW 2 1 /16 F 5 7 /8 2 3

More information

DVG/AF Variable Geometry Desuperheater

DVG/AF Variable Geometry Desuperheater Instruction Manual D101616X012 DVG/AF Desuperheater DVG/AF Variable Geometry Desuperheater Contents Introduction............................... 1 Scope of Manual.......................... 1 Description...............................

More information

ORIFICE PLATE flow meters

ORIFICE PLATE flow meters ORIFICE PLATE flow meters 1 Differential pressure and pressure loss When a throttle element is interposed in a closed passage of fluid in piping, a difference is produced between the pressure upstream

More information

Hot Tap Insertion Vortex

Hot Tap Insertion Vortex Hot Tap Insertion Vortex Product Features The same insertion meter can measure Steam, Gases or Liquids. Standardize on an insertion bar that can measure line sizes 2 48 Heavy Duty & Maintenance Free Design

More information

TYPE E Main Valve Sizes 3 /8 through 12

TYPE E Main Valve Sizes 3 /8 through 12 Technical Data SD 3001E PRINTED IN U.S.A. SD 3001E/9709 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 A B TYPE E MAIN VALVE FACE TO FACE DIMENSIONS C D E DIMENSIONS (inches)

More information

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE

Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE Technical Data SD 4011 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE A SERIES AIR ADJUSTED PILOT PRINTED IN U.S.A. SD 4011/9504 Type A or A83 (wt 6 lb) Type A53 or A 85

More information

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP

Welker Sampler. Installation, Operation, & Maintenance Manual. Model GSS-4HP Installation, Operation, & Maintenance Manual Welker Sampler Model GSS-4HP The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES FLS F6.60 MAGMETER FLOW SENSOR The new F6.60 and F6.63 are flow meters without moving mechanical parts which can be applied for the measurement of dirty liquids so long as they are conductive and homogeneous.

More information

Quick Start Guide , Rev AB June Rosemount 585 Annubar Flanged Assembly

Quick Start Guide , Rev AB June Rosemount 585 Annubar Flanged Assembly Quick Start Guide 00825-0100-585, Rev AB Rosemount 585 Annubar Flanged Assembly Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 585 Annubar Assembly. It does not provide instructions

More information

Accutubes. Accuracy True double averaging design +1% of rate accuracy +0.1% repeatability Tested and certified by independent flow labs

Accutubes. Accuracy True double averaging design +1% of rate accuracy +0.1% repeatability Tested and certified by independent flow labs s Meriam s Flow Sensors are lab-tested and field-proven flow elements perfect for gas, liquid or steam service. With thousands in use worldwide, the continues to be the right choice when ease of installation,

More information

ROOTS Meters Series B3 Meter Models 8C175-56M175

ROOTS Meters Series B3 Meter Models 8C175-56M175 ROOTS Meters Series B3 Meter Models 8C175-56M175 Refer to IOM-B3 for Complete Instructions IS:B3 3.03 RECEIVING, HANDLING AND STORAGE ROOTS rotary positive displacement gas meters are precision measurement

More information

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work?

Exercise 4-1. Flowmeters EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Rotameters. How do rotameter tubes work? Exercise 4-1 Flowmeters EXERCISE OBJECTIVE Learn the basics of differential pressure flowmeters via the use of a Venturi tube and learn how to safely connect (and disconnect) a differential pressure flowmeter

More information

ACCUTUBE Madison Avenue Cleveland, Ohio (216) FAX (216) web site:

ACCUTUBE Madison Avenue Cleveland, Ohio (216) FAX (216) web site: ACCUTUBE 10920 Madison Avenue Cleveland, Ohio 44102 (216) 281-1100 FAX (216) 281-0228 e-mail: meriam@meriam.com web site: www.meriam.com - 1 - ACCUTUBE INSTALLATION INSTRUCTIONS File No. 957:440-15 CONTENTS

More information

T-Bar Bonnet. Monoflanges STANDARD OPTIONS. O.S.&Y. Bonnet (firesafe) Gas Solution Bonnet. Anti-Tamper Bonnet

T-Bar Bonnet. Monoflanges STANDARD OPTIONS. O.S.&Y. Bonnet (firesafe) Gas Solution Bonnet. Anti-Tamper Bonnet T-Bar Bonnet Gas Solution bonnet with non-rotating Metal Stem Tip The Gas Solution bonnet protects the internal and external threads. Moreover, the bonnet thread is less subject to wear, since it is not

More information

26 Series Stainless Steel 2-way Ball Valves

26 Series Stainless Steel 2-way Ball Valves 1-800-899-0553 26 Series Stainless Steel 2-way Ball Valves Users Manual Installation, Operation, & Maintenance 1. General Precaution 1.1. Material Section Material deterioration is determined by the contained

More information

When installing the screwed end, socket weld & flanged end valves the following respective procedures shall be followed for better performance.

When installing the screwed end, socket weld & flanged end valves the following respective procedures shall be followed for better performance. 1. Storage LARSEN & TOUBRO LIMITED Page 1 of 5 1.1. All valves are to be stored in fully open position, in order to protect the sphere surface and soft valve seats. 1.2. Before shipping, the inlet and

More information

T5 Flare Gas Transducer

T5 Flare Gas Transducer GE Measurement & Control Flow T5 Flare Gas Transducer (Standard and Extended Velocity Range) Installation Guide 916-117 Rev. D November 2014 GE Measurement & Control T5 Flare Gas Transducer (Standard

More information

COMMERCIAL. BV & BVM Series Installation Instructions 06/29/15

COMMERCIAL. BV & BVM Series Installation Instructions 06/29/15 COMMERCIAL Bray Controls Commercial Division 13788 West Road, Suite 00A Houston, Texas 77041 BCDSales@Bray.com Phone: 1-888-41-79 Fax: 1-888-41-70 www.braycommercialdivision.com BV & BVM Series Installation

More information

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life!

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life! Instructions and operation manual for butterfly valves This manual is intended to support the users of Herberholz butterfly valves type HRD/HRA, RD/RA, LDKE/LDKF for installation, operation and maintenance

More information

INSTALLATION MANUAL XMT MAGNETOSTRICTIVE LEVEL PROBE

INSTALLATION MANUAL XMT MAGNETOSTRICTIVE LEVEL PROBE INSTALLATION MANUAL XMT MAGNETOSTRICTIVE LEVEL PROBE INDEX INDEX... 2 REVISION INDEX... 2 INTRODUCTION... 3 GENERAL WARNINGS... 3 DESCRIPTION... 4 MAIN COMPONENTS... 5 MECHANICAL INSTALLATION... 6 INSTALLATION

More information

JUMO flowtrans DP R. Meter run R01 and orifice plate R02. Applications. Brief description. Special features. Customer benefits.

JUMO flowtrans DP R. Meter run R01 and orifice plate R02. Applications. Brief description. Special features. Customer benefits. Page 1/8 JUMO flowtrans DP R and orifice plate R02 Applications For the flow measurement of single-phase aggressive and non-aggressive gases, steam, and liquids In nominal widths up to DN 40 designed as

More information

Pressure Reducing Valve Type 2114/2415

Pressure Reducing Valve Type 2114/2415 Pressure Reducing Valve Type 2114/2415 Fig. 1 Type 2114/2415 1. Design and principle of operation The Type 2114/2415 Pressure Reducing Valve consists of the Type 2114 Valve and the Type 2415 Actuator.

More information

Ver Trunnion Ball Valve INSTALLATION, OPERATION AND MAINTENANCE MANUAL FBV/IOM/BA02

Ver Trunnion Ball Valve INSTALLATION, OPERATION AND MAINTENANCE MANUAL FBV/IOM/BA02 Ver. 2008 Trunnion Ball Valve INSTALLATION, OPERATION AND MAINTENANCE MANUAL FBV/IOM/BA02 TABLE OF CONTENTS 1 APPLICATIONS...2 1.1 Applications...2 1.2 Performance Specifications...2 2 APPLICABLE STANDARDS...2

More information

Model 5000 Vortex Meter

Model 5000 Vortex Meter Model 5000 Vortex Meter Installation and Instruction Manual Table of Contents General Information... 1 1-1 General... 1 1-2 Principles of Operation... 1 1-3 Sensor Operation... 1 1-4 Calibration Factor...

More information

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual Before installation these instructions must be fully read and understood Important Before valves are installed or used the following actions are recommended. 1. Valves/parts have to be inspected and thoroughly

More information

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF VERSION UF-5xx d INSTALLATION MANUAL ISO 9001:2008 CONTENTS Page INTRODUCTION... 3 1. SAFETY INSTRUCTIONS... 4 2. MOUNTING PREPARATION... 4 3. MOUNTING REQUIREMENTS...

More information

Installation, Operation and Maintenance Manual for AlL Pressure seal Bonnet/Cover Class 600, 900, 1500 & 2500 Cast steel Gate, Globe & Check Valves

Installation, Operation and Maintenance Manual for AlL Pressure seal Bonnet/Cover Class 600, 900, 1500 & 2500 Cast steel Gate, Globe & Check Valves Installation, Operation and Maintenance Manual for AlL Pressure seal Bonnet/Cover Class 600, 900, 1500 & 2500 Cast steel Gate, Globe & Check Valves AUDCO INDIA LIMITED Chennai India AIL REF. No: IOM/PS/001

More information

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood 4. Ozone: storage rooms should not contain any equipment generating ozone. E.g. lamps, electric motors. IMPORTANT Before valves

More information

MANIFOLDS VALVE. Mfg & Exp. : Valves & Fittings. A Trusted Name in Valves and Fittings ISO 9001:2008 COMPANY. Catalogue No.

MANIFOLDS VALVE. Mfg & Exp. : Valves & Fittings. A Trusted Name in Valves and Fittings ISO 9001:2008 COMPANY. Catalogue No. A Trusted Name in Valves and Fittings Mfg & Exp. : Valves & Fittings MANIFOLDS VALVE ISO 9001:2008 COMPANY Pressure Ratings: 6,000 PSI/10,000 PSI NPT, ISO/BSP, Threads 2-,3- and 5-valves Instrument manifolds

More information

I & M MK96 & MK96C. Ideal Installation. Start-Up. Maintenance PROTECT VALVES WITH LINE STRAINERS

I & M MK96 & MK96C. Ideal Installation. Start-Up. Maintenance PROTECT VALVES WITH LINE STRAINERS **VIP** If you purchased your MK96 or MK96C Valve, or any stem repair component for this valve, after 9/7/08 - please see **VIP** assembly instruction change on page, middle-right, section. I & M MK96

More information

Crispin Valves Operating Guide. Crispin

Crispin Valves Operating Guide. Crispin Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com

More information

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION:

DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: DELTA O-RING CARTRIDGE SEAL ASSEMBLY AND INSTALLATION INSTRUCTIONS INTRODUCTION: These instructions are provided to familiarize the user with the seal and its use. The instructions must be read carefully

More information

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting I & M 8000 Series 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 lowflow@richardsind.com www.lowflowvalve.com Installation & Maintenance Instructions for 8000 Series Low

More information

Operating Procedures for 4 to 24 Double Block and Bleed Test and Isolation Plugs

Operating Procedures for 4 to 24 Double Block and Bleed Test and Isolation Plugs EST Group DC2693 03/16 Rev 3 05/17 Page 1 of 13 Operating Procedures for 4 to 24 Double Block and Bleed Test and Isolation Plugs WARNING Pressure testing is inherently dangerous. Strict adherence to these

More information

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood HAZARD POTENTIALS disregarding of instructions improper use of product insufficiently qualified personnel Valve application to be

More information

Flow Control Valve IOM 770-U

Flow Control Valve IOM 770-U IOM 770-U Flow Control Valve (Sizes 1½-14"; DN40-350) Description The Model 770-U Flow Control Valve is a hydraulically operated, diaphragm actuated, control valve that maintains pre-set maximum flow,

More information

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters Table of Contents Page 1. Principle of Operation...2 2. Installation Planning......2 3. Installation...3 3.1 Safety Considerations...

More information

Purging Air From Divider Block Lubrication Systems

Purging Air From Divider Block Lubrication Systems FROST ENGINEERING SERVICE Purging Air From Lubrication Systems A D I V I S I O N O F G E C S E Y S A L E S & S E R V I C E DESCRIPTION Divider block lubrication systems operate correctly only when all

More information

2.- HANDLING OF VALVES BEFORE ASSEMBLY 3.- FITTING THE VALVE TO THE REST OF THE ASSEMBLY 5.- PERIODICAL INSPECTION OF THE VALVE AND MAINTENANCE

2.- HANDLING OF VALVES BEFORE ASSEMBLY 3.- FITTING THE VALVE TO THE REST OF THE ASSEMBLY 5.- PERIODICAL INSPECTION OF THE VALVE AND MAINTENANCE Page 1 of 16 CONTENTS 1.- INTRODUCTION 2.- HANDLING OF VALVES BEFORE ASSEMBLY 3.- FITTING THE VALVE TO THE REST OF THE ASSEMBLY 4.- OPERATION OF A BALL VALVE 5.- PERIODICAL INSPECTION OF THE VALVE AND

More information

Series Base mounted pump. Installation and operating instructions

Series Base mounted pump. Installation and operating instructions Series 4030 Installation and File No: 40.80 Date: june 25, 2015 Supersedes: 40.80 Date: october 10, 2009 contents General 4 Inspection 4 Installation - Series 4030 base mounted Pump 4 1.0 Location 4 2.0

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Type 5282 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating instructions contain

More information

OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE

OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE INDEX SERIES 2500 DUCTILE IRON RESILIENT WEDGE GATE VALVE OPERATION and MAINTENANCE MANUAL. OPERATION AND MAINTENANCE Operation,

More information

Quick Start Guide , Rev FB June Rosemount 485 Annubar Flanged Flo-Tap Assembly

Quick Start Guide , Rev FB June Rosemount 485 Annubar Flanged Flo-Tap Assembly Quick Start Guide 00825-000-809, Rev FB Rosemount 85 Annubar Flanged Flo-Tap Assembly Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 85 Annubar. It does not provide instructions

More information

Serie Ekoflux S. Flanged balancing valve. Application fields. Regulation. Ekoflux.S_GB_22/04/2015 HEATING CONDITIONING

Serie Ekoflux S. Flanged balancing valve. Application fields. Regulation.   Ekoflux.S_GB_22/04/2015 HEATING CONDITIONING Serie Ekoflux S Flanged balancing valve Ekoflux.S_GB_/0/0 Application fields CONDITIONING HEATING www.brandoni.it Serie Ekoflux S The valves in the series EKOFLUX balance the flow in main circuits or single

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Type 5282 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation Contents 1 Operating Instructions... 2 2 Authorized use...

More information

INSTALLATION & MAINTENANCE MANUAL

INSTALLATION & MAINTENANCE MANUAL INSTALLATION & MAINTENANCE MANUAL 3-WAY/4-WAY/5-WAY MULTI-PORT BALL VALVES T TEFLON PARTS - 1. Seat x 5 pcs. 2. Joint Gasket x 5 pcs. 3. Retainer Seal x 5 pcs. 4. Thrust Washer x 1 pc. 5. O-Ring x 1 pc

More information

Y690A Series Pressure Reducing Regulators

Y690A Series Pressure Reducing Regulators Instruction Manual Form 5463 Y690A Series February 2009 Y690A Series Pressure Reducing Regulators! Warning Fisher regulators must be installed, operated, and maintained in accordance with federal, state,

More information

SECTION METERS AND GAGES FOR HVAC PIPING

SECTION METERS AND GAGES FOR HVAC PIPING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. 1.2 SUMMARY A. This

More information

TX 115/215 Hot-tap Insertion Turbine Instructions

TX 115/215 Hot-tap Insertion Turbine Instructions TX 115/215 Hot-tap Insertion Turbine Instructions General Information These hot tap versions of the proven TX insertion flow sensors are designed to install or be serviced without depressurizing the pipe.

More information

Pressure Relief Valve Maintenance Manual

Pressure Relief Valve Maintenance Manual Technical Manual 1098T Pressure Relief Valve Maintenance Manual Farris Engineering Division of Curtiss-Wright Flow Control Corporation TABLE OF CONTENTS - Manual Revision 0 Introduction & Safety Tips...

More information

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE

DEFENDER SERIES. 5 Gallon, Double Walled, Field Replaceable Spill Container Model Series INSTALLATION, OPERATION, & MAINTENANCE DEFENDER SERIES 5 Gallon, Double Walled, Field Replaceable Spill Container Model 705-550 Series INSTALLATION, OPERATION, & MAINTENANCE Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel:

More information

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS

PACKING, HANDLING, TRANSPORTING AND STORING MOTORS PACKING, HANDLING, TRANSPORTING AND STORING MOTORS Make sure that the shaft of the motor is not loaded in any way and is protected from knocks. Axial loads or shocks may easily damage the bearings inside

More information

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Date of Issue: 04 August 2010 Page 1 of 27 QF 80: Issue 2 WARNING! BEFORE ANY INSTALLATION AND MAINTENANCE WORK CAN COMMENCE ENSURE THE VALVE AND SURROUNDING

More information

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been

More information

Eurovacuum Installations and Operating manual EVD Series Vacuum pumps Models: EVD-6 to EVD-90. Double Stage Oil Lubricated Rotary Vane Vacuum Pump

Eurovacuum Installations and Operating manual EVD Series Vacuum pumps Models: EVD-6 to EVD-90. Double Stage Oil Lubricated Rotary Vane Vacuum Pump Eurovacuum Installations and Operating manual EVD Series Vacuum pumps Models: EVD-6 to EVD-90 Double Stage Oil Lubricated Rotary Vane Vacuum Pump Eurovacuum EVD-Series Double Stage Oil Sealed Rotary Vane

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

Butterfly valves Figure 56 Installation & Maintenance Instructions

Butterfly valves Figure 56 Installation & Maintenance Instructions KEYSTONE Please read these instructions carefully This symbol indicates important messages and safety instructions. Hazard potentials: disregarding of instructions improper use of product insufficiently

More information

The Multivariable Air Flow Meter

The Multivariable Air Flow Meter The Multivariable Air Flow Meter Model MVC10A/MVC10F OVERVIEW The Multivariable Mass Flow Meter model MVC10A/ MVC10F, a compact has all function necessary to measure nitrogen (N 2 ) gas, carbon dioxcide

More information

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual ACRIS PFA LINED BALL VALVES WWW.AMRESIST.COM Table of Contents Safety Instructions - Definition of Terms............................................2 Introduction..............................................................2

More information

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL Before installation these instructions must be fully read and understood Intended valve use The valve is intended to be used only in applications within the pressure/temperature limits indicated in the

More information

NEECO INDUSTRIES INC. INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY

NEECO INDUSTRIES INC. INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY INSTRUCTION MANUAL 7 1/16 10K SLAB GATE BODY INTRODUCTION The NF-700 type gate valves provided by Neeco Industries are full-bore through conduit non-rising stem manually (w/ball screw) operated valves.

More information

EZH and EZHSO Series. Pressure Reducing Regulators. EZH and EZHSO Series. Introduction. Scope of the Manual. Product Description !

EZH and EZHSO Series. Pressure Reducing Regulators. EZH and EZHSO Series. Introduction. Scope of the Manual. Product Description ! Instruction Manual D103077X012 EZH and EZHSO Series November 2017 EZH and EZHSO Series Pressure Reducing Regulators TYPE PRX/120 TYPE PRX/120-AP Figure 2. PRX Series Pressure Reducing Pilots Figure 1.

More information

Instrumentation Ball Valves

Instrumentation Ball Valves Rev. 0-2016 Ball Valve Main Components: 1. Obturator or closure member: part of the valve positioned in the flow stream to allow or prevent the flow (ball or tip); 2. Stem: part which connects the obturator

More information

DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL

DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL DYNAFLUID 2000 STEAM & WATER MIXING VALVE INSTALLATION & OPERATING MANUAL LILLY ENGINEERING COMPANY 217 CATALPA STREET P.O. BOX 173 ITASCA, ILLINOIS 60143 630-773-2222 FAX: 630-773-3443 www.lillyengineering.com

More information

UNA 13 UNA 15 UNA 15 Stainless Steel Design. Installation Instructions Steam Traps UNA 13, UNA 15

UNA 13 UNA 15 UNA 15 Stainless Steel Design. Installation Instructions Steam Traps UNA 13, UNA 15 UNA 13 UNA 15 UNA 15 Stainless Steel Design Installation Instructions 810604-01 Steam Traps UNA 13, UNA 15 1 Contents Important Notes Page Use... 7 Safety note... 7 Danger... 7 Explanatory Notes Scope

More information

V500 and V510 VERIS Verabar Installation and Maintenance Manual

V500 and V510 VERIS Verabar Installation and Maintenance Manual V500 and V510 VERIS Verabar Installation and Maintenance Manual 167-EN Please read and save these instructions Contents General Safety Information...3 Product Information...3 Section 1: Scope...3 Purpose

More information

SERIES DESUPERHEATERS

SERIES DESUPERHEATERS 3-4000 SERIES DESUPERHEATERS 2 3-4000 SERIES DESUPERHEATERS PARCOL 3-4000 series desuperheaters are used to reduce the steam temperature by directly water injection inside the superheated steam flow. The

More information

FLEXIBLE COUPLINGS RU-STEEL Annex Atex 95

FLEXIBLE COUPLINGS RU-STEEL Annex Atex 95 FLEXIBLE COUPLINGS RU-STEEL Annex Atex 95 Index: 1 Coupling s Choice 2 Assembly and Alignment 3 Simultaneous Alignment Check 4 Coupling s Guard 5 Check Intervals 6 Extraordinary Malfunctions, Causes and

More information

Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters

Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters 8000A/8300/9300A/9100A/9200A SERIES S Perfect for municipal water & wastewater applications 1.6 to 900 mm (1/16 to 36

More information

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions. Please read these instructions carefully

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions.  Please read these instructions carefully KEYSTONE Please read these instructions carefully This symbol indicates important messages and safety instructions. Hazard potentials: disregarding of instructions improper use of product insufficiently

More information

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM INSTRUCTION MANUAL Anchor Darling 1878 Swing Check Valves Sizes 1/2 through 2 Installation Operation Maintenance FCD ADENIM0006-00 Table of Contents 1.0 Physical Description and Operation of Equipment

More information

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 ) I & M Mark 8 Series 0 Wasson Road Cincinnati, OH 4509 USA Phone 5-5-5600 Fax 5-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (-/ - ) Warning:

More information

Engineered Valves For Pipeline Service Application

Engineered Valves For Pipeline Service Application Page 1 TRUNNION MOUNTED BALL VALVES TM SERIES Engineered Valves For Pipeline Service Application Valves for oil & gas pipelines and other industrial applications Flanged or Butt Weld ANSI Class 150 thru

More information

The Multivariable Air Flow Meter

The Multivariable Air Flow Meter No. SS2-MVC200-0100 OVERVIEW The Multivariable Mass Flow Meter AIRcube, a compact has all function necessary to measure nitrogen (N 2 ) gas, carbon dioxcide (CO 2 ) gas and air. The model MVC10A/MVC10F

More information

GLASS LEVEL GAUGES. Reflex Transparent Bicolour

GLASS LEVEL GAUGES. Reflex Transparent Bicolour GLASS LEVEL GAUGES Reflex Transparent Bicolour INDEX Page General Information...3 Types, Material Schedules and Applications...4-5 Reflex Level Gauges type BR14-G11 & GP11...6 type BR12-G11, G12, GP11

More information