Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A
|
|
- Moris Daniels
- 6 years ago
- Views:
Transcription
1 WATTS INDUSTRIES, INC. Technical Data SD 4512A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY PRINTED IN U.S.A. SD 4512A/9806 T124/T134 PILOT FRONT VIEW 2 1 /16 F 5 7 /8 2 3 /8 T124/T134 PILOT SIDE VIEW PILOT DIMENSION TYPE F T /8" T /4" 13 7 /8 1 3 /8 TYPE T124 & T134 TEMPERATURE PILOT The combination of a Spence Type T124 or T134 with a Spence Type E or Type C main valve produces a steam pressure reducing valve and temperature regulator in a single pilotoperated valve. Steam pressure on the heater is modulated in proportion to temperature and load variations. Pressure control provides fast, accurate adjustment of heat transfer rate to demand requirements. This pilot is primarily intended for use on instantaneous heaters. By combining both temperature and pressure control in one pilot, unusually close regulation of temperature is achieved through the anticipation of fast load changes. An additional benefit of this pilot is that pressure reduction and temperature control can be provided with a single regulator. For pressures not to exceed 20 psi, the T134 should be used. For pressures between 20 and 125 psi, the T124 should be used. RATINGS (Maximum Inlet Conditions) Construction Pressure (Temperature) Cast Iron PSIG...(450 F) Cast Bronze PSIG...(450 F) Cast Steel PSIG...(750 F) TEMPERATURE RANGES 20 to 120 F 150 to 300 F 300 to 400 F 50 to 150 F 170 to 270 F 330 to 430 F 70 to 170 F 250 to 350 F 400 to 500 F 120 to 220 F 290 to 390 F THERMOSTAT ASSEMBLY Standard Thermostat Assemblies and Wells: Stainless Steel Bronze Flexible tubing and capillary are available to 50 feet. OPTIONS Thermostat Well Dial Thermometer THERMOSTAT Adjustment Indicator Integral Mount Body 1" NPT 5 /8" 20 1 /2" Style #700 bronze bulb with 10 feet of brass flexible tubing will be furnished unless otherwise specified. For other bulb styles, see SD9501.
2 OPERATING PRINCIPLE The regulator is operated by its initial steam pressure. The main valve is normally closed, being held so by initial pressure on the disc and by an internal main spring. The pilot is opened by compressing the pressure limit spring. When steam is turned on, it flows to the pilot through the connecting nipple and union (see Fig. 1). At the No. 8B tee on the pilot outlet, the flow divides. One branch is connected to bleedport No. 4A and the other to restriction elbow No. 5A and the underside of the main valve diaphragm. Bleedport No. 4A restricts the flow, builds pressure under the diaphragm and opens the main valve. Restriction No. 5A steadies the operation of the regulator. Steam flowing to the heater creates a rising delivery pressure which feed back through the control pipe to the underside of the pilot diaphragm. As the pressure on this diaphragm approaches a balance with the thrust of the pressure limit spring, the pilot throttles. This, in turn, allows the main valve to assume a position where just enough steam flows to maintain the set maximum delivery pressure. As the temperature of the heated medium rises, vapor pressure is generated in the thermostat bulb and transmitted to the pilot temperature diaphragm. When the vapor pressure becomes sufficient to over-balance the combined thrust of the temperature adjusting and pressure limit springs, the regulator throttles to maintain the set temperature. RECOMMENDED INSTALLATION FIGURE 1 2
3 INSTALLATION PLANNING Locate the regulator in a horizontal pipe. Prevent water hammer and erratic operation by providing a trap ahead of the regulator. Avoid damaging effects of scale and dirt in pipelines by using a strainer to protect the regulator. Provide a three valve bypass to facilitate inspection of the regulator without interrupting service. The preferred thermostat position is horizontal. When vertical or slanting, the tip end of the bulb must point downward. Locate the thermostat as close to the heater outlet as practical. Expose the entire length of the bulb to the active flow leaving the heater. If the pressure rating of the heater or connected equipment is less than the initial steam pressure, provide a safety valve. Hot water and similar liquid systems require a relief valve to prevent dangerous overpressure due to expansion. Instantaneous heaters, when operated on intermittent demand (as in domestic water heating), require the following conditions for best temperature regulation. a. Constant forced recirculation of fluid through the heater. b. Omission of thermostat well to reduce temperature lag. Use of a thermostat compatible with the heated medium is preferred over the use of a standard thermostat installed in a well which is compatible with the heated medium. When the use of a well is unavoidable, an appropriate heat transfer medium should be installed between the well and the thermostat. MAIN VALVE Flush the piping system thoroughly to clear it of welding beads, scale, sand, etc. Mount the main valve with diaphragm chamber down and arrow on body pointing in the direction of flow. Screwed end valves should be mounted in unions. FIGURE 3 PILOT Mount the pilot on either side of the main valve by means of 1/4" nipple and union provided. Make this connection the the 1/4" pipe tap at the inlet side of the main valve as shown in Figure 2. Screw No. 4A bleedport fitting into the 1/8" pipe tap at the outlet side of the main valve body. Note bleed orifice in this fitting vital to operation of regulator. Screw No. 8B tee into 1/8" pipe tap in pilot. Select tap facing downstream. Screw No. 5A elbow containing restriction orifice into 1/8" pipe tap on underside of main valve diaphragm chamber. If the initial pressure or pressure drop is less than 15 psi, a No. 5B open elbow without orifice. Connect tubing bends as illustrated in Fig. 2. Valves with condensation chamber are fitted up according to Figure 3. CONTROL PIPE (if required) FIGURE 2 Use 1/4" pipe for this line which connects the pilot pressure diaphragm chamber (Fig. 2) to the desired point of pressure control. On instantaneous heaters with steam in shell (Fig. 1), tap the control pipe into the shell. Otherwise, enter the delivery steam pipe at point of entrance to heater. Pitch the control pipe away from the pilot and avoid water pockets. Insulation may be applied to the upper portion (globe and flanges) of the main valve. Do not insulate the diaphragm chamber or any part of the pilot (Fig. 1). 3
4 START-UP AND SETTING Best temperature control will result when the delivery pressure setting is the lowest steam pressure capable of sustaining the desired temperature at maximum load. The following adjustments should be made under full load conditions or as near to such as possible. Close bypass, open 1/4" control pipe valve and turn up the temperature adjusting wheel (Fig. 1) until 1/2" of thread is exposed. Back off pressure adjusting screw to remove all compression from pressure limit spring. Crack open the outlet stop valve. Crack open the inlet stop valve, blow down strainer and then slowly open the inlet valve wide. Slowly turn up the pressure adjustment. When steam begins to flow, gradually open the outlet stop valve. Continue delivery pressure adjustment until heater output temperature is 5 F above required. If the temperature adjustment made at the beginning of this procedure limits this operation, set the adjusting wheel a little higher. Lower the temperature adjusting wheel until the desired operating temperature is reached. If the adjustment is made at partial load, the temperature will sag under heavier loads. When maximum load occurs, increase the pressure setting just enough to restore the temperature to normal. TROUBLE SHOOTING FAILURE TO OPEN OR SAGGING DELIVERY PRESSURE 1. Adjusting spring on pilot may have been tampered with. 2. Initial pressure may be down due to partially closed supply valve, clogged strainer or other obstruction. 3. Bleedport may have been omitted and an open coupling substituted. 4. Orifice in No. 5A restriction elbow may be plugged. 5. Control pipe may be plugged. Most likely points of obstruction are at shutoff valve and entrance to delivery main. 6. Make sure heater is properly trapped and free of condensate. 7. Pilot or main valve diaphragm may be broken. Check for leakage around stem between lever and diaphragm on pilot. Check the main valve with air pressure in diaphragm chamber before dismantling. 8. Leak in the thermostat bulb may allow heated fluid pressure if sufficiently high to back up into the thermal system to hold pilot closed. FAILURE TO CLOSE OVERHEATING 1. Adjusting spring on pilot may have been tampered with. 2. By-pass may be leaking. 3. Thermostat located too far from instantaneous heater outlet. 4. Thermostat may be kinked or broken or have lost it s fill. Alternately warm and cool thermostat 10 F above and below it s set point. If thermostat is operative, the pin between the lever and pressure diaphragm will become loose and snug as the temperature stem on opposite end of the lever moves up and down. 5. A lift of condensate to a hot well may require more pressure in heater than the heated medium. Arrange drainage of the heater by gravity or install a pump to lift condensate. 6. Main valve or pilot may be held open by foreign matter. To determine which valve leaks: a. Close inlet stop valve and 1/4" control valve. b.remove bleedport bend so pilot will exhaust to atmosphere. c. Remove all compression from pressure adjusting spring. If steam issues from the end of the bleedport bend on the pilot, there is an obstruction between it s seat and disc. Steam blowing back from the bleedport on the downstream side of the valve indicates that the main valve disc is held open by foreign matter. Leakage of either valve requires dismantling. See dismantling and valve grinding for instructions. ERRATIC TEMPERATURE CONTROL 1. Thermostat installed too far from heater outlet. 2. Improper trapping or erratic discharge of trap. 3. Lift of condensate to hot well may require more pressure than that called for by the medium flowing through the heater. Arrange to drain condensate by gravity or lift it with a pump. 4. Sticky check valve in return line. 5. Poor circulation through heater. Constant circulation should be employed. 6. Valve too large for the heater or heater too large for the load. 7. Valve installed too far from heater. 4
5 DISMANTLING MAINTENANCE (Brackets refer to item number) THERMOSTAT REPLACEMENT 1 - Remove diaphragm nuts (4) and lift off top works and diaphragms. 2 - Remove the blind flange bolts (7) and take off the blind flange (26). Remove the screen (46) and gasket. 3 - Hold the pusher plate (41) with a socket wrench and remove stem nuts (25). The disc (24) will drop off. Lift out the stem (22) and valve spring (43). ASSEMBLY 1 - Reassemble the pilot in the reverse of the procedure described above. 2 - Take particular care that diaphragm screw (37) and cowl bracket (19) are centered on diaphragm flange of the pilot body (44). Misalignment can cause erratic performance. 3 - When replacing diaphragms, apply sealing compound (Copaltite or equal ) sparingly to the shoulder of the diaphragm screw (37). For steel pilot only, apply sealing compound to the diaphragm flange of the pilot body. SEAT, DISC AND STEM REPLACEMENT 1 - Examine the seat and disc sealing surfaces for nicks or other signs of damage by pipeline debris. If sealing surfaces are damaged, they must be replaced. 2 - When seat, disc or stem is replaced, the sealing surfaces must be lapped. Lap sparingly using 500 grit lapping compound and light pressure. Heavy grinding may cause galling, wide sealing surfaces and a grooved disc, all of which tend to produce leakage. After the sealing surfaces are lapped in, disassemble and clean all parts. 3 - Remove the seat ring (23) from the body with a socket wrench. Clean the body threads of old sealing compound using a wire brush. Apply new sealing compound (Copaltite or equal) sparingly to the threads and shoulder of the new seat ring. Let stand until tacky before assembling into the pilot body. 4 - Lap in joint between new stem (22) and disc (24). 5 - Apply lapping compound to the disc, place it on the stem and secure with a stem nut (25). Slip the stem into it s normal position and lap the disc to seat joint. The stem is slotted for rotation with a screwdriver. 6 - Screw on the pusher plate (41), omitting the valve spring. Hold the disc on the seat and adjust the pusher plate until dimension (C=11/64") is obtained (Fig. 4). 7 - Remove stem nut, being careful not to disturb the pusher plate adjustment and lift stem out the top of the pilot. Grind off stem projection B flush with upper surface of pusher plate. 8 - Reinsert stem in the pilot with disc and a stem nut attached. Check dimension c and, if correct, lock the position by prick punching the thread at several points. Work carefully to avoid bending the stem. 9 - Scrape away burrs raised by prick punching. Upper surface must be smooth and flat. 10 -Check that valve travel is A=3/64". This need not be exact. Stem should move smoothly. Binding indicates a bent stem Remove stem nut a disc and withdraw stem. Install stem with valve spring, disc and both stem nuts in place. 1 - Cool the thermostat bulbs of original and replacement elements below the low end of their temperature range (See range tag on flexible tubing). Maintain bulbs at this temperature during replacement process. 2 - Back off temperature adjusting wheel (14) to within a turn or two of the barrel nut (1). Back off pressure adjusting screw (20) to remove all compression from spring. This will allow temperature diaphragm plate (7) to remain seated in correct alignment on balls (10) after disengagement of thermostat assembly. Unless pilot is upright, balls will fall out of position. 3 - Remove diaphragm nuts (8) and detach thermostat assembly from pilot. Similarly, detach shipping plate from replacement thermostat. When removing diaphragm nuts, be sure cowl assembly (29) does not turn in threaded joint at barrel nut (1). If movement is observed, reset position as per instructions for temperature stem position adjustment below. 4 - Install replacement thermostat on pilot and install shipping plate on original thermostat. Tighten bolts evenly. FIGURE 4 TRAVEL SETTING TEMPERATURE STEM ADJUSTMENT The temperature stem adjustment is factory set and locked by a barrel nut (1). If the setting is accidentally disturbed, readjust as follows: 1 - Remove thermostat assembly per instructions above. 2 - Clamp a flat bar to the cowl (29) so that the pressure plate (7) is flush with the cowl s pinch ring. 3 - Loosen cowl bracket set screw (30) and turn cowl assembly (29) up about one turn. Remove putty from barrel nut set screw (1), loosen set screw and back off barrel nut about one turn. 4 - Crack inlet stop valve or apply shop air to the pilot inlet. Turn up pressure adjusting screw (20) until flow issues from pilot outlet tee. Rotate the cowl assembly (29) down until flow stops. 5 - Lock this adjustment with the cowl bracket s set screw (30). Turn down the barrel nut (1) to jam against cowl bracket and lock with it s set screw (5). 6 - Reinstall the thermostat assembly
6 T124 BODY T134 SIDE VIEW FRONT VIEW 6
7 COMPOSITION DISC ADJUSTMENT INDICATOR When ordering parts, it is essential that the pilot type, service and serial number be stated. Select part by item number, but order by part number. Specify complete part number when ordering. ITEM NO. PART NAME MATERIAL PART NO. REMARKS 1 Barrel Nut Aluminum Set Screw, Pivot Pin Steel Cotter Pin Steel Diaphragm Nut Steel T124 Diaphragm Nut Steel T134 5 Diaphragm Bolt Steel T124 Diaphragm Bolt Steel T134 6 Pipe Plug Ledloy Iron, Steel Pipe Plug Brass Bronze 7 Temperature Plate Ledloy Temp. Diaphragm Nut Steel Temp. Diaphragm Bolt Steel Temp. Plate Ball Steel Temp. Spring Button Ledloy Temperature Spring Oil Temp. Stl Thrust Bearing Steel Handwheel Cast Iron Set Screw, Barrel Steel Spring Button, Upper Ledloy Pressure Spring Oil Temp. Stl T124 Pressure Spring Oil Temp. Stl T Spring Button, Lower Ledloy Cowl Bracket Cast Iron Iron T124 Cowl Bracket Cast Iron Iron T134 Cowl Bracket Ductile Iron Bronze, Steel T124 Cowl Bracket Ductile Iron Bronze, Steel T Adjusting Screw 416 St. Stl Stem Bushing 203 PB * Stem 303 St. Stl Standard Stem 303 St. Stl Composition Disc 23* Seat Ring 420 FH St. Stl Standard Seat Ring 303 St. Stl Composition Disc 24* Disc 440 CH Standard Disc Brass, Hycar Composition 25* Stem Nut Steel Steam Service Stem Nut Brass Water Service 26 Blind Flange Cast Iron Iron Blind Flange Cast Steel Steel Blind Flange Cast Bronze Bronze 27 Blind Flange Bolt Steel Iron, Bronze Blind Flange Bolt Steel Steel 28 Temp. Plate Center Ledloy Cowl Steel Cowl Pin Steel Barrel Aluminum Temperature Stem Aluminum Pivot Pin 416 St. Stl Set Screw, Press. Stem Steel Lever Steel T124 Lever Steel T Pressure Stem 416 St. Stl * Diaphragm Screw Ledloy T124 Diaphragm Screw Ledloy T134 38* Pressure Plate Ledloy T134 39* Diaphragm 301 St. Stl * Floating Plate Iron T134 41* Pusher Plate Ledloy * Vacuum Spring 302 St. Stl T134 43* Valve Spring Inconel T124 Valve Spring Inconel T Body Cast Iron Iron T124 Body Cast Iron Iron T134 Body Cast Steel Steel T124 Body Cast Steel Steel T134 Body Cast Bronze Bronze T124 Body Cast Bronze Bronze T124 45* Gasket Non-asbestos Iron, Bronze Gasket Flexitalic Steel 46* Screen 301 St. Stl Steam Service Screen 301 St. Stl Water Service 47* Diaphragm Nut Ledloy T Adj. Indicator Plate Aluminum Adj. Indicator Pointer Aluminum *These parts furnished in Repair Kit
Technical Data TYPE A SERIES AIR ADJUSTED PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4011 OPERATING PRINCIPLE
Technical Data SD 4011 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE A SERIES AIR ADJUSTED PILOT PRINTED IN U.S.A. SD 4011/9504 Type A or A83 (wt 6 lb) Type A53 or A 85
More informationTYPE E Main Valve Sizes 3 /8 through 12
Technical Data SD 3001E PRINTED IN U.S.A. SD 3001E/9709 SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 A B TYPE E MAIN VALVE FACE TO FACE DIMENSIONS C D E DIMENSIONS (inches)
More informationINSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION
30/8.5.1 INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION VKP PILOT OPERATED PRESSURE REDUCING VALVE 12501 Telecom Drive, Tampa, Florida 33637 1. Introduction The Class VKP pilot-controlled steam
More informationDO NOT INSULATE BELOW THIS LINE. * For sizes 1/2" to 1 1/2" add 2 1/2" to 'C' dimension.
428 Jones Boulevard Limerick Airport Business Center Pottstown, PA 19464 Phone: (610)495-5131 ax: (610)495-5134 www.watsonmcdaniel.com PAGE 28 INSTRUCTION PART NO. 2315400 C.R.3500 REV. 10 SIZE C B CENTER
More informationMAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P
MANUAL NUMBER P-EFS-1 MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P TRAC Regulator Company Inc. 160 South Terrace Avenue Mount Vernon, New York USA 10550-2408 Phone: (914)
More informationTechnical Data PRESSURE (PSI) DIMENSIONS inches AND WEIGHTS pounds
Technical Data SD 8010A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 PRINTED IN U.S.A. SD 8010A/0103 G 5" ACTUATOR REMOVAL CLEARANCE F 1/4 NPT A INTIMIDATOR TYPE J CONTROL
More informationIdeal Installation. I & M Mark 67 (1/2 6 ) Control Line. Installation & Maintenance Instructions for Mark 67 Pressure Regulators
I & M Mark (/ ) 0 Wasson Road Cincinnati, OH 0 USA Phone --00 Fax -8-00 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark Pressure Regulators Warning: Jordan Valve
More informationIdeal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS
I & M Mark 80 370 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-87-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 80 Temperature Regulator
More informationIdeal Installation. I & M Mark 80. Bulb Installation PROTECT VALVES WITH LINE STRAINERS
I & M Mark 80 370 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-87-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 80 Temperature Regulator
More informationMercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.
SECTION 23 22 13 STEAM AND CONDENSATE PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification
More informationI & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting
I & M 8000 Series 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 lowflow@richardsind.com www.lowflowvalve.com Installation & Maintenance Instructions for 8000 Series Low
More informationTYPE ET14 TEMPERATURE REGULATOR CAST IRON, BRONZE or STEEL CONTROLS 20 to 500 F
TYPE ET14 TEMPERATURE REGULATOR CAST IRON, BRONZE or STEEL CONTROLS 20 to 500 F Temperature Regulation for Batch Process Storage Heaters (Water, Fuel Oil or Chemical) Air Heating TYPE ET14 TEMPERATURE
More informationI & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )
I & M Mark 8 Series 0 Wasson Road Cincinnati, OH 4509 USA Phone 5-5-5600 Fax 5-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (-/ - ) Warning:
More informationI & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )
I & M Mark 8 Series 30 Wasson Road Cincinnati, OH 4509 USA Phone 53-533-5600 Fax 53-8-005 info@richardsind.com www.jordanvalve.com Installation & Maintenance Instructions for Mark 8 Control Valves (/ -
More informationSTYLE J COMBINATION PRESSURE AND TEMPERATURE REGULATOR
STYLE J COMBINATION PRESSURE AND TEMPERATURE REGULATOR MIL-V-19772A and MIL-DTL-19772B TYPE IV SERIES 100 (BRONZE) and 150 (STEEL) SUITABLE FOR SHIPBOARD SERVICE TRAC Regulator Company Inc. 160 South Terrace
More informationTechnical Data SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 1520 SERIES 2000 DIRECT & REVERSE ACTING
Technical Data SD 520 PRINTED IN U.S.A. SD 520/98 SPENCE ENGINEERING COMPANY, INC. 50 COLDENHAM ROAD, WALDEN, NY 2586-205 SERIES 2000 DIRECT & REVERSE ACTING DIRECT & REVERSE ACTING DIMENSIONS inches (mm)
More informationCONTROL VALVES SINGLE PORTED CLASSES DL, DDL, DOS, DDOS
12501 Telecom Drive, Tampa Florida 33637 Installation, Operation and Maintenance 10/1.5.1 Rev. 0 CONTROL VALVES SINGLE PORTED CLASSES DL, DDL, DOS, DDOS TABLE OF CONTENTS INSTALLATION...2 VALVE POSITION...2
More informationMaintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10"
IOM-F-860_880V INSTALLATION, OPERATION, MAINTENANCE Maintenance Manual Reduced Pressure Assembly Models 860 & 880V 2 1 /2" 10" 860 880V Standard Configuration 880V Vertical Configuration INDEX Vandalism..............................................
More informationCUSTOM COMBINATION AIR VALVE
INSTALLATION / OPERATION / MAINTENANCE CUSTOM COMBINATION AIR VALVE INTRODUCTION This manual will provide you with the information to properly install and maintain this valve to ensure a long service life.
More informationI & M Mark 708ME. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & Motor Actuator
I & M Mark 708ME 3170 Wasson Road Cincinnati, OH 45209 USA Phone 513-533-5600 Fax 513-871-0105 info@richardsind.com www.lowfl owvalve.com Installation & Maintenance Instructions for Mark 708 & Motor Actuator
More informationSECTION VALVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:
More informationDKLO D1 & D4 CONTROL VALVE Sizes ½ through 4 ANSI CLASS 125/250 TABLE OF CONTENTS
12501 Telecom Drive, Tampa Florida 33637 Installation, Operating and Maintenance Instructions Supplement 10/5.5.2 Rev. 1 DKLO D1 & D4 CONTROL VALVE Sizes ½ through 4 ANSI CLASS 125/250 TABLE OF CONTENTS
More informationINSTRUCTION MANUAL INTERNAL GEAR PUMP TITAN G-4124A SERIES=> FLANGED TITAN G-124A SERIES => FLANGED MODELS:
INSTRUCTION MANUAL INTERNAL GEAR PUMP TITAN G-4124A SERIES=> FLANGED TITAN G-124A SERIES => FLANGED MODELS: G-H, G-HL, G-K, G-KK, G-L, G-LQ, G-LL, GLS, G-Q, G-QS 1 Contents Maintenance Thrust bearing adjustment
More informationINSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL MODEL 4D-200 REDUCED PRESSURE PRINCIPLE (RPZ) & MODEL 4D-700 REDUCED PRESSURE DETECTOR ASSEMBLY (RPDA) BACKFLOW PREVENTERS 2 ½ 10 Conbraco Industries Inc.
More informationPRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY
PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been
More informationTechnical Data P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP SD 9952B
Technical Data SD 9952B SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NEW YORK, 12586-2035 P3 PISTON POWER PUMP NON-ELECTRIC CONDENSATE PUMP Pressures To 250 PSIG (20.7 barg) Temperatures
More informationPressure Relief Valve Maintenance Manual
Technical Manual 1098T Pressure Relief Valve Maintenance Manual Farris Engineering Division of Curtiss-Wright Flow Control Corporation TABLE OF CONTENTS - Manual Revision 0 Introduction & Safety Tips...
More informationCrispin Valves Operating Guide. Crispin
Crispin Valves Operating Guide Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick, PA 18603 1-800-AIR-VALV T: (570) 752-4524 F: (570) 752-4962 www.crispinvalve.com sales@crispinvalve.com
More informationI & M Mark 708. Ideal Installation. Start-Up Procedure. Installation & Maintenance Instructions for Mark 708 & 14M Actuator and Motor Valve
I & M Mark 708 370 Wasson Road Cincinnati, OH 509 USA Phone 53-533-5600 Fax 53-87-005 info@richardsind.com www.lowflowvalve.com Installation & Maintenance Instructions for Mark 708 & M Actuator and Motor
More informationINSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS 377 Float Cage / 326L & 322L lever Valves TABLE OF CONTENTS Overview... Cover General Information... Cover Operation... 4 Installation...4-6 Maintenance...
More informationInstallation, Operation & Maintenance Instructions
Installation, Operation & Maintenance Instructions 377 Float Cage / 326L & 322L lever Valves TABLE OF CONTENTS Overview... Cover General Information... Cover Operation... 4 Installation...4-6 Maintenance...
More informationSTYLE B THERMOSTATIC TEMPERATURE REGULATOR
STYLE B THERMOSTATIC TEMPERATURE REGULATOR MIL-V-19772A and MIL-DTL-19772B TYPE I (3-WAY) / TYPE II CLASS 1 / TYPE II CLASS 2 WITH MANUAL OVERRIDE and OVERHEAT PROTECTION SUITABLE FOR SHIPBOARD SERVICE
More informationTypes 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators
Instruction Manual Form 5116 Types 1808 and 1808A July 2010 Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators! Warning Failure to follow these instructions or to properly install
More informationANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood TABLE OF CONTENTS 1. General valve description and start-up... 1 2. Main valve maintenance... 1 3. Pilot maintenance... 5 4. Pilot
More informationTECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc
Page 1 TI595CD A Watts Industries Co. TECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc VALVE DESCRIPTION TABLE OF CONTENTS The Powers #11 Regulator is a self-actuating
More informationCP400 Series Commercial/Industrial Pressure Loaded Pressure Reducing Regulators
CP400 Series Commercial/Industrial Pressure Loaded Pressure Reducing Regulators September 2014 P1182 typical type cp400 regulator P1522 P1410 Typical type CP403 Regulator WITH INTEGRAL TRUE-MONITOR PROTECTION
More informationLIL GATOR TYPE VLG CONTROL VALVE SIZES ½ THROUGH 2
12501 Telecom Drive, Tampa Florida 33637 Installation, Operating and Maintenance Instructions Supplement 10/1.5.2 Rev. 1 LIL GATOR TYPE VLG CONTROL VALVE SIZES ½ THROUGH 2 TABLE OF CONTENTS OPERATING PRINCIPLE...5
More informationArmstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance
Armstrong Double Duty 6 Steam Trap/Pump Combination Installation and Maintenance 119 Overview Warning: This bulletin should be used by experienced personnel as a guide to the installation and maintenance
More informationFloat Dynamic Steam Trap J10
172-65237MA-01 (J10) 12 June 2015 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Float Dynamic Steam Trap J10 Copyright 2015 by TLV CO., LTD. All rights reserved
More informationCla-Val. Service Training Manual. Simple solutions plus learning with a purpose
Cla-Val Service Training Manual Simple solutions plus learning with a purpose 5 Application Series Section General Identify What Valve You Have 5-1 Rate of Flow 40 Series 5-2 Pressure Relief 50 Series
More informationRev 0 Page 83. Series W91/94 Self-Operating Temperature Regulator. Installation, Operation & Maintenance Instructions
2440300 Rev 0 Page 83 Series W91/94 Self-Operating Temperature Regulator Installation, Operation & Maintenance Instructions Installation, Operation & Maintenance Manual TABLE OF CONTENTS Principles of
More informationPilot-Operated Regulators
Fisher Controls Instruction Manual Type 1098-EGR & 1098H-EGR Pilot-Operated Regulators R May 1987 Form 5084 Contents Introduction................................... 2 Scope of Manual..............................
More information3" & 4" Cast Iron Self-Priming Centrifugal Pump Instruction Manual
12 3" & 4" Cast Iron Self-Priming Centrifugal Pump Instruction Manual 333 & 444 Series Read these instructions and the instructions covering operation of the pump drive unit. Do not operate the gas engine
More informationTechnical Instructions
IS-P-595DB Double Seat - Balanced Valve - Bronze (Type DB) or Stainless Steel Trim (Type DS) Technical Instructions Description The Powers #11 Double Seat Balanced Valve Regulator (Bronze or Stainless
More informationSECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING
SUNY GENESEO 220523-1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationHIGH PRESSURE CONTROL VALVE PISTON BALANCED
PISTON BALANCED All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been made to ensure their accuracy, they are not to be
More informationSECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING
SECTION 220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationType EZR Relief Valve or Backpressure Regulator
Instruction Manual Form 5476 Type EZR Relief May 2012 Type EZR Relief Valve or Backpressure Regulator Introduction Scope of the Manual W7347 This instruction manual provides installation, startup, shutdown,
More informationType 289P Pilot-Operated Relief Valve
Instruction Manual D102680X012 Type 289P July 2017 Type 289P Pilot-Operated Relief Valve Figure 1. 1 NPT Type 289P Pilot-Operated Relief Valve Figure 2. 2 NPT Type 289P Pilot-Operated Relief Valve Introduction
More informationOperating & Maintenance Manual For Steam Conditioning Valve
For Steam Conditioning Valve 1 Table of Contents 1.0 Introduction 3 2.0 Product description 3 3.0 Safety Instruction 4 4.0 Installation and Commissioning 5 5.0 Valve Disassembly 6 6.0 Maintenance 6 7.0
More informationIron Horse ED Series Pressure Regulator
REGULATORS Applications Pressure Regulation for Steam Distribution Single Point or Multiple Use Applications Pressure Control for Steam Plants District Heating Systems Single Stage Reduction Stations Two
More informationS203 Series Relief Monitor Regulators
Instruction Manual Form 2216 S203 Series December 2008 S203 Series Relief Monitor Regulators W2109 Figure 1. Type S203 Relief Monitor Regulator! Warning Fisher regulators must be installed, operated, and
More informationA. This Section includes general duty valves common to several HVAC piping systems.
SECTION 23 05 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationIndustrial Turbo Meters, Sizes 2" through 6"
Industrial Turbo Meters Sizes 2" through 6" TUR-UM-00530-EN-19 (October 2014) User Manual Industrial Turbo Meters, Sizes 2" through 6" User Manual CONTENTS Scope of the Manual 5 Specifications 5 Product
More informationINSPECTION & MAINTENANCE BULLETIN ARI 1301/1302 1" Plug Type Angle Valves
INSPECTION & MAINTENANCE BULLETIN ARI 1301/1302 1" Plug Type Angle Valves Item # Description Item # Description 1 Body 12 Washer 2 Packing Retainer 13 Bushing 3 Packet Set 14 Bolt 4 Jam Nut 15 Yoke 5 Stud
More informationTorqueflite Manual/Automatic Valve Body
TCI 122400 Torqueflite Manual/Automatic Valve Body This valve body can be installed in a few hours by carefully following directions. Read all instructions first to familiarize yourself with the parts
More informationAir Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.
172-65177M-02 (TATSU2) 7 August 2013 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Air Trap TATSU2 Copyright 2013 by TLV CO., LTD. All rights reserved 1 Contents
More informationSentinel 250 Fire Hydrant
Maintenance Instructions manual table of contents PAGE Sentinel 250 Fire Hydrant Inspection and Lubrication 2 Rotating Hydrant to Face Desired Direction 3 Installing Extension Section 3-6 Restoring Service
More informationSECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING
SECTION 22 05 23 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Valves, General 2. Gate Valves 3. Balancing Valves 4. Ball Valves 5. Swing Check Valves 6. Backflow Prevention Assemblies 7. Pressure
More informationTypes 92CT and 92CTP Temperature Regulators for Steam, Water, and Air
Instruction Manual Form 5630 Types 92CT and 92CT April 2000 Types 92CT and 92CT Temperature Regulators for Steam, Water, and Air W7652 W7651 Figure 1. Type 92CT Temperature Regulator Figure 2. Type 92CT
More informationOperating and Maintenance Manual for Type S Flowmeters. M101 Rev. B Type S Flowmeters: 5 8, 3 4 and 1 with 157 & 600 Series Registers
Operating and Maintenance Manual for Type S Flowmeters M101 Rev. B Type S Flowmeters: 5 8, 3 4 and 1 with 157 & 600 Series Registers TABLE OF CONTENTS Installation & Operation... Page 1 Calibration...
More informationTITAN FLOW CONTROL, INC.
PREFACE: TITAN FLOW This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI)Full Body Swing Check Valves. To ensure efficient and safe
More informationLEVEL CONTROLS 313 IOM
LEVEL CONTROLS 313 IOM 313 OVERFLOW TRAP INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS Overview...Cover General Information...Cover Installation...4 Operation...4 Maintenance...4
More informationIMOI 2010 Rev 0
FOREWORD The following instructions are offered as a reference aid to the valve user when installing, maintaining or operating Williams Gate, Globe and Swing Check valves. This document, consisting of
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM)
INSTALLATION, OPERATION AND MAINTENANCE MANUAL (IOM) IOM-1088 03-16 Model 1088 Vacu-Gard Blanketing Valve ISO Registered Company SECTION I I. DESCRIPTION AND SCOPE The Model 1088 Vacu-Gard is a tank blanketing
More informationMODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions
MODEL 106/206-PG POWER OPERATED GLOBE VALVE Sizes 1/2" to 8" (106-PG) 3" to 10" (206-PG) Installation, Operating and Maintenance Instructions DESCRIPTION: This valve is the basic component used for most
More informationSECTION VALVES PART 1 - GENERAL
1.01 RELATED DOCUMENTS SECTION 15100 VALVES PART 1 - GENERAL A. The work in this section includes the furnishing and installation of all control valves and accessories shown on the construction plans and
More informationfor ½" thru 2" 800 lb. Piston Lift Check Valves with Resilient Seat Option
Manual No. 800-PC Issued: March 31, 2004 INSTRUCTION MANUAL for ½" thru 2" 800 lb. Piston Lift Check Valves with Resilient Seat Option Flowserve Corporation Flow Control Division 1900 S. Saunders Street
More information4 - Way Control 4 - Way Control 4 - Way Control with lock
INSTALLATION / OPERATION / MAINTENANCE 1. DESCRIPTION MODEL 0-02 (Full Internal Port) Powertrol Valve This manual contains information for installation, operation and maintenance of the Cla-Val Co. 0-02
More informationSECTION VALVES PART 1 -GENERAL
SECTION 1571 0 VALVES PART 3- EXECUTION General Shut-off Valves Balancing Valves Drain Valves RELATED WORK Section 15430- Plumbing Specialties Section 15450- Plumbing Equipment PART 1 -GENERAL SCOPE This
More informationOPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE
OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE INDEX SERIES 2500 DUCTILE IRON RESILIENT WEDGE GATE VALVE OPERATION and MAINTENANCE MANUAL. OPERATION AND MAINTENANCE Operation,
More informationMAINTENANCE MANUAL. Covering Models: Series (1/4-10 ) S Series (1/4-1 ) Series (3-10 )
BFMM4000 1-09 MAINTENANCE MANUAL Covering Models: 40-200 Series (1/4-10 ) 40-200S Series (1/4-1 ) 40-700 Series (3-10 ) REDUCED PRESSURE PRINCIPLE (RPZ) BACKFLOW PREVENTERS 1/4" - 10" AND REDUCED PRESSURE
More informationwalton TEMPERATURE CONTROL SYSTEMS Pneumatically Operated (Rotary)
walton TEMPERATURE CONTROL SYSTEMS Pneumatically Operated (Rotary) WALTON ENGINEERING CO. LTD. 61 London Road St Albans Hertfordshire AL1 1LJ England Telephone +44 (0)1727 855616 Fax +44 (0)1727 841145
More informationSteam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions
INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-8-002-US October 2016 Steam/Water Washdown Units Safety and Operation Installation and Maintenance Instructions These instructions should be read by the Company
More informationOperation and Maintenance Manual
BM / BMA Hydrometers ½ Operation and Maintenance Manual i This manual is intended for use by the users of this equipment. The information contained herein is the property of the Arad Ltd. Dalia and may
More informationM-5000TG/5700TG Steam and Cold Water Mixing Unit
M-5000TG/5700TG Steam and Cold Water Mixing Unit Installation, Operating and Maintenance Instructions Last Updated: August, 2014 Strahman Valves, Inc. USA Headquarters 2801 Baglyos Circle Bethlehem, PA
More informationEngineering Standard. Fig 707 Safety Relief Valve Installation and Maintenance Instructions
ES/707/0/003 ES/707/0/003 June 2007 Engineering Standard Fig 707 Safety Relief Valve Installation and Maintenance Instructions Sharp Street, Worsley, Manchester M28 3NA: Tel +44 (0) 161 790 7741 Fax +44
More information161 Series Pilots for Pilot-Operated Pressure Reducing Regulators
Instruction Manual D03232X02 6 Series August 208 6 Series Pilots for Pilot-Operated Pressure Reducing Regulators! WARNING Failure to follow these instructions or to properly install and maintain this equipment
More informationFIREFLO - MODEL F-06 INSPECTION, INSTALLATION & MAINTENANCE MANUAL. Item No.s/Description
FIREFLO - MODEL F-06 INSPECTION, INSTALLATION & MAINTENANCE MANUAL Item No.s/Description Item No. Description Material Specification HYDRANT Qty. Req d Item No. Description Material Specification 1 Operating
More informationMark 5108 Series. Back Pressure Regulating Valves Mark 5108 Series. Back Pressure Regulating Valves. Valve Features. Operation
Mark 5108 Series Back Pressure Regulating Valves In many liquid piping systems, it is vital that line pressure is maintained within relatively narrow limits. The Mark 5108 is designed to do just that.
More informationSelf-Operating Temperature Regulators
Self-Operating Temperature Regulators Remote Bulb for Heating, Cooling, Mixing and By-Pass Applications Powers # Regulators With Powers # Self-Operating Temperature Regulators, you no longer need external
More informationINSTRUCTIONS Installation - Operation - Inspection - Maintenance 4" - 16" ROSS MODEL - 30AWR FIGURE 29 SINGLE ACTING ALTITUDE VALVE
SINGLE ACTING ALTITUDE VALVE INSTRUCTIONS Installation - Operation - Inspection - Maintenance 4" - 16" ROSS MODEL - 30AWR FIGURE 29 SINGLE ACTING ALTITUDE VALVE GLOBE FLAT SEAT STYLE ROSS VALVE Mfg. Co.,
More informationSECTION (15110) - GENERAL DUTY VALVES FOR PLUMBING PIPING
SECTION 22 05 23 (15110) - GENERAL DUTY VALVES FOR PLUMBING PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Valves. B. Related Sections: 1.02 REFERENCES 1. Section 22 05 53 (15075) Identification
More informationPressure Reducing Valve Type 2114/2415
Pressure Reducing Valve Type 2114/2415 Fig. 1 Type 2114/2415 1. Design and principle of operation The Type 2114/2415 Pressure Reducing Valve consists of the Type 2114 Valve and the Type 2415 Actuator.
More informationType EZR Relief Valve or Backpressure Regulator
Instruction Manual Form 5476 Type EZR Relief October 2015 Type EZR Relief Valve or Backpressure Regulator W7347 Figure 1. Type EZR Relief Valve or Backpressure Regulator Introduction Scope of the Manual
More informationMaintenance Manual Double Check and Double Check Detector Assemblies Series 850, 856, 870V & 876V 2 1 /2" - 10" (65 250mm)
IOM-F-DC/DCDA INSTALLATION, OPERATION, MAINTENANCE Maintenance Manual Double Check and Double Check Detector Assemblies Series 850, 856, 870V & 876V 2 1 /2" - 10" (65 250mm) Series 850 Series 876V Table
More informationInstruction Manual & Parts List For H/G323FXFSX-500_ & 800_ Pumps With Flowserve Type BX Cartridge Seal
TM Instruction Manual & Parts List For H/G323FXFSX-500_ & 800_ Pumps With Flowserve Type BX Cartridge Seal WARNING This Special Instruction Manual and General Instructions Manual, CA-1, should be read
More informationFire Engine Dump Valve
Fire Engine Dump Valve INSTRUCTIONS Installation - Operation - Inspection - Maintenance 1-3" ROSS MODEL - 20WR-D Fire Engine Dump Valve Serial #S ROSS VALVE Mfg. Co., Inc. 6 OAKWOOD AVENUE, TROY, NY 12180
More informationW91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer
Design & Operation W91 Non-Indicating W94 Dial Thermometer Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company CAPILLARY
More informationThese instructions are applicable to the following models: ARI 1118 ARI 1148
INSPECTION & MAINTENANCE BULLETIN ARI 1118 & 1148 Safety Relief Valve These instructions are applicable to the following models: ARI 1118 ARI 1148 Only AAR class F facilities are certified to recondition,
More informationThese instructions are applicable to the following models: ARI 1108 ARI HP1108
INSPECTION & MAINTENANCE BULLETIN ARI 1108 & HP1108 Safety Relief Valve These instructions are applicable to the following models: ARI 1108 ARI HP1108 Only AAR class F facilities are certified to recondition,
More informationAPT10-2 Automatic Pump Trap
6120050/3 IM-P612-18 ST Issue 3 APT10-2 Automatic Pump Trap Installation and Maintenance Instructions 1. General safety information 2. Product information 3. Installation Closed loop steam systems only
More informationM-5000TG/5700TG Steam and Cold Water Mixing Unit
M-5000TG/5700TG Steam and Cold Water Mixing Unit Installation, Operating and Maintenance Instructions Last Updated: October, 2012 Strahman Valves, Inc. USA Headquarters 2801 Baglyos Circle Bethlehem, PA
More informationLOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED
DIAPHRAGM BALANCED All Rights Reserved. All contents of this publication including illustrations are believed to be reliable. And while efforts have been made to ensure their accuracy, they are not to
More informationTable of Contents Visual Inspection and Neutralizing... 3 Disassembly
1 Table of Contents Visual Inspection and Neutralizing... 3 Disassembly... 3... 4... 4 Cleaning... 4 Inspection... 4 Reconditioning of Valve Seats... 5 Lapping Procedures... 5 Lapping Blocks... 5 Lapping
More informationInstructions for Installation, Operation, Care and Maintenance
Bulletin 407 Rev. T Model E Alarm Check Valve Bulletin 407 Rev. T Instructions for Installation, Operation, Care and Maintenance 4 (100 mm), 6 (150 mm), 8 (200 mm) Sizes With Model E3 Trim Listed by Underwriters
More informationBaumann Mikroseal Control Valve
Instruction Manual 81000 Valve Baumann 81000 Mikroseal Control Valve Contents Introduction... 1 Scope of Manual... 1 Safety Precautions... 2 Maintenance... 3 Installation... 3 Air Piping... 4 Flow Direction...
More informationTILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: FAX:
TILLOTSON LTD., CLASH INDUSTRIAL ESTATE, TRALEE, CO. KERRY, IRELAND PHONE: +353 66 7121911 FAX: +353 66 7124503 e-mail: sales@tillotson.ie SERIES SERVICE MANUAL INTRODUCTION The gasoline engine industry
More informationseries 5100 GAS/PNEUMATIC DRIVEN INJECTION PUMP DESCRIPTION APPLICATIONS
TEXSTEAM Pumps series 5100 GAS/PNEUMATIC DRIVEN INJECTION PUMP Series 5100 LP Wt. 45 pounds Microswitch Option Available DESCRIPTION The 5100 Series performs accurately because (1) the head is designed
More information980 B Wheel Loader S/n 89P1 & Up Volume 1 of 2
Caterpillar Service Manual 980 B Wheel Loader S/n 89P1 & Up Volume 1 of 2 Service Manual THIS IS A MANUAL PRODUCED BY JENSALES INC. WITHOUT THE AUTHORIZATION OF CATERPILLAR OR IT S SUCCESSORS. CATERPILLAR
More information