Installation, Operation and Maintenance Instructions. SLS Series Single Phase Disconnector
|
|
- Arleen Harrell
- 6 years ago
- Views:
Transcription
1 Installation, Operation and Maintenance Instructions SLS Series Single Phase Disconnector
2 Contents Inspection, Preparation and Installation...4 Step 1. Mounting Bracket Installation...4 Step 2. Mounting Bracket to Cross Arm Installation...5 Operation...6 Maintenance Instructions Safety of Personnel Recommended Maintenance Interval of Outdoor Pole Mounted Single Phase Disconnector Frequent Operation or Adverse Atmospheric Conditions Routine Maintenance Inspection of SLS Disconnector Examination and Overhaul of SLS Disconnector Fasteners Insulators (Porcelain or Polymer) Contacts and Other Current-Carrying Components Pivot Point and Hinge Pins...9
3 Qualified Personnel Only The Single Phase Disconnector covered by this publication must be installed, operated and maintained by qualified personnel who are knowledgeable in installation, operation and maintenance of distribution switch equipment along with associated hazards. A qualified personnel is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. Read and keep these instructions Carefully read and understand these instructions before installing, operating and maintaining your ABB Single Phase Disconnector (SLS). For safe operation the appropriate Australian or International Standards should be applied. These instructions should be available for reference wherever SLSs are used. Keep these instructions in a location where you can easily retrieve and refer to them. Proper Application Only The equipment covered by this publication MUST be selected for a specific application within the specified rating shown in Plating name, attached to the contact blade. Notice The instructions covered in this publication are intended only for qualified personnel and do not substitute any adequate training and experience in safety procedures. Installation, Operation and Maintenance SLS Series 3
4 Inspection, Preparation and Installation Standard SLS series Single Phase Disconnector shipment includes: a Single phase base assembly, a mounting bracket and one kit of fasteners. Inspect disconnector ratings on name plate, attached to contact blade assemblies and ensure the unit is suitable for your application. Remove the above equipments from box and place them into scissor lifts. Step 1. Mounting Bracket Installation Attach mounting bracket to phase base assembly, using provided kit of fasteners ( One M12 Cup-head Bolt, One M12 Spring washer, One M12 Hex Nut). To prevent mounting bracket twisting during opening and closing operation ensure the mounting bracket fits in place properly. Mounting Bracket M12 Spring Washer M12 Hex Nut M12 Cup-head Bolt Single Phase Base Assembly 30 mounting assembly Underslung mounting assembly 1 4 SLS Series Installation, Operation and Maintenance
5 Underslung mounting assembly 2 Step 2. Mounting Bracket to Cross Arm Installation Attach mounting bracket to Cross Arm using a M20 Bolt and Nut. Note: Each Standard Single Phase disconnector assembly is completed with mounting bracket to suit 100mm x 100mm crossarms and to ensure a correct operation following timber shrinkage the underside of the mounting bracket have dimples/spikes protruding to bite into the timber. Mounting bracket to suit 150 mm* 150 mm fibreglass crossarm is also available. Do not use mounting bracket with dimples on fiberglass crossarm as it will damage the crossarm. Underslung mounting 1 Underslung mounting 2 30º mounting 1 30º mounting 2 Installation, Operation and Maintenance SLS Series 5
6 Operation Only qualified personnel should operate, inspect, or maintain a Single phase Disconnector unit. Qualified personnel should wear protective equipment such as rubber gloves, hard hat, safety glasses, flash-clothes, etc., in accordance with established Australian or International safety practices. After attaching the unit to cross arm as described in preceding section, insert the prong of a hookstick in the pull ring attached to contact blades assembly and pull the hookstick to fully open position. Ensure all fasteners are tightened properly, contact blades are set correctly, then repeat open and close the disconnector several times to ensure proper operation. 6 SLS Series Installation, Operation and Maintenance
7 Maintenance Instructions 1. Safety of personnel To establish safe working conditions for maintenance of Single phase disconnector the requirements stated in AS , IEEE Std.C , IEEE Std and other international standards should be complied with. 2. Recommended Maintenance Interval of Outdoor Pole Mounted Single Phase Disconnector Due to the widely varying conditions where Single Phase disconnector products are used it is not possible to provide a general recommendation for maintenance interval and maintenance period could vary greatly depending upon the environmental condition and frequency of operation of unit under normal and fault current. But generally for outdoor pole mounted Single Phase disconnectors where the atmospheric conditions of the site are reasonably clean and the disconnector is not subject to excessive pollution such as industrial or coastal areas and for normal distribution duties (e.g. opened and closed infrequently) the below maintenance intervals are recommended. a. (a) Inspect regularly with a maximum interval of 12 months. b. (b) Typically examine the unit at 5 year intervals but the intervals may vary and it should be based on experience gained from inspection and overhaul. c. (c) Overhaul should only be carried out when and to the extent that inspection, examination or diagnostic testing indicates it to be necessary. However a maximum interval of 15 years may be advisable. Note: The intervals quoted are given as a guide and are based on a three-stage maintenance policy of inspection, examination and overhaul. Where the policy is based on two stages, i.e. inspection and overhaul, the maximum advisable interval between overhauls should be reduced to 10 years. 2.1 Frequent operation or adverse atmospheric conditions For Single phase disconnectors which are frequently operated or situated in adverse atmospheric conditions (Polluted and coastal areas) the intervals between maintenance operations will be less than those stated above. 3. Routine Maintenance 3.1. Inspection of SLS Disconnector A general inspection of the SLS disconnector should be made and attention be given to general cleanliness of the unit. During this inspection, the condition of insulators, contacts and blades should be inspected for any sign of abnormality such as crack on insulators or severe discoloration, burning and pitting of contacts, contact blades and insulator pins Examination and Overhaul of SLS Disconnector Fasteners The switchgear should be inspected and checked for any defects and to ensure that all fasteners, pins and terminal connectors are secured and in good condition. Note: Refer to IEEE Std for detailed procedure of Insulators cleaning Insulators (porcelain or polymer) Insulators should be inspected for any breakage, cracks, burns, or contamination and also to ensure the surface is clean and free from excessive contamination such as salt deposits and road dust to avoid flashover as a result of the accumulation of foreign substances, cracked, broken or chipped insulators should be replaced to prevent flashover and extra consideration should be given to repair or replace any faulty or damaged components. Installation, Operation and Maintenance SLS Series 7
8 3.2.3 Contacts and other Current-Carrying Components The following recommendations apply to contacts: 1. Contacts should be examined for pitting, burning and misalignment to ensure that the contacts on the units in close position are held with adequate pressure. Badly pitted, burnt, or distorted contacts should be replaced and aligned and contact springs pressure should be checked and adjusted if necessary. It will be expected that the arcing contacts will show some signs of burning or discoloration but this will not cause any problem provided they are not damaged and the parts are in correct operational position. The condition and position of any arc resisting tips should be checked as the primary function of arcing tips are to carry the arc root and excessive burning or erosion of the part could cause problem and should be replaced. 2. Hinge contacts should be examined for any signs of overheating, burning, welding or other visible damage and replaced or repaired as necessary and if such damages on hinge contact. Fixed contacts or contact blades are found the cause should be investigated. 3. Slight discoloration or burning of bare copper or copper-alloy contacts are not a major problem but if necessary could be removed by suitable abrasive cloth or a fine file. The amount of plating and material removed from contacts should be kept to a minimum and if necessary the contacts should be replaced. It is important to maintain spring tension if the contact blades are repaired or replaced for correct operation of the unit. Mounting Bracket Insulator Insulator pin Insulator pin Terminal Fixed contact Pull ring Hinge contact Contact blades 8 SLS Series Installation, Operation and Maintenance
9 Hinge Contact Pre-Setting Hinge Contact Final Setting St/St Flat Washer St/St Nylock Nut 22 mm 18 mm St/St Spring Brass Spacer St/St Pressure Bolt Terminal Palm Jaw Contact Pre-Setting Jaw Contact Final Setting 22 mm 19 mm 4. When contact blades are repaired or replaced the below procedure shall be followed to ensure correct pressure and alignment of the components. In SLS series disconnector the constant pressure is maintained by means of stainless steel helical springs and contact force is factory set to a nominal of 200 N. On maintained contacts to obtain the correct contact pressure, the below pre-setting and final setting shall be performed: Notice Do not use any compound containing molybdenum disulphide as a lubricant, since it affects the electrical performance of the unit. Pre-setting: While pressure bolt spacer & stainless steel spring are in place, screw the stainless nylock Self-locking nut on to the bolt until a setting of 22 mm is obtained. Final setting: Using two open ended spanners of the correct size, hold the bolt head and tighten the nut until a final setting of 19 mm is obtained for the jaw contact and 18 mm for the hinge contact Pivot Point and Hinge Pins Contacts pivot point and hinge pins and pivot points should be inspected and lubricated with medium bodied general purpose grease e.g: Valvoline Valplex M or Ampol Jet-Lube Kopr-Kote. Installation, Operation and Maintenance SLS Series 9
10 Contact For more information please contact: Note Medium Voltage Products 1 Baupaume Road Moorebank, NSW 2170 Australia Phone: Fax: While care has been taken to ensure that the information contained in this document is correct, no responsibility can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at any time in the light of technical or other developments. Technical specifications are valid under normal operating conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for indirect or consequential damages. Technical data and design is subject to change and should be confirmed prior to ordering. SLS series instructions We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction in whole or in parts is forbidden without ABB s prior written consent. Copyright 2013 ABB. All rights reserved.
PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons
Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...
More informationGWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004
Installation Instructions Series I Encapsulated Current Limiting Fuse GWI 701-4 Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information
More informationInstallation, Operation, and Maintenance
S&C Regulator Bypass Switches Outdoor Distribution (14.4 kv through 25 kv) Type XL (Sequenced) and Type NL (Non-sequenced) Installation, Operation, and Maintenance Table of Contents Section Page Section
More informationInstallation and Operation
S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction
More informationCOOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN
Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION
More informationS&C Vista Underground Distribution Switchgear
S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section
More informationCOOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN
Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER
More informationCOOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN
Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationOBAE, OBAEXU, ON BOARD Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBAE, OBAEXU, ON BOARD Battery Chargers INTRODUCTION: The OBAE line of chargers are designed for the permanent installation on battery powered
More informationCutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com
MODEL : BANTAM C8 PART NO. : 602-325P SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@ PAGE - 1 - WARRANTY
More informationInstallation and Operation
S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Installation and Operation Table
More informationCOOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN
Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationCENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch
Instructions CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch CENTERLINE 2100 Motor Control Centers Introduction The intent of this publication is to provide field
More informationINSTRUCTION MANUAL. Pacific Self-locking Beam Trolleys Pacific Adjustable Angle Clamps Pacific Top Girder Clamps
INSTRUCTION MANUAL Pacific Self-locking Beam Trolleys Pacific Adjustable Angle Clamps Pacific Top Girder Clamps IMPORTANT Please read this instruction manual before using these products. This manual contains
More informationFigure 1. Kearney Type HX cutout.
Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2
More informationCOOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing
Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification
More informationJet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY
Jet Fans Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY All Leader Fan products are guaranteed to be free from defects of workmanship or material and to function satisfactorily when properly
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationVacuum Circuit Breaker (Vehicle)
Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationSM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety
SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com
More informationAPCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES
APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES Instruction D12043 June 2016 DeZURIK Instructions These instructions provide installation, operation and maintenance information for APCO CRF-100A Rubber
More informationMODEL 7100 PORTABLE PIN WELDER OPERATOR S MANUAL
Model 7100 Portable Pin Welder MODEL 7100 PORTABLE PIN WELDER OPERATOR S MANUAL Copyright: March 22, 2005 Revised: December 20, 2016 Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence,
More informationCOOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN
Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section
More informationBefore equipment use, please read this operation manual carefully. Serial Number: Date Purchased:
Pushed & Geared Trolleys OPERATION MANUAL This operation manual is intended as an instruction manual for trained personnel who are in charge of installation, maintenance, repair etc. Before equipment use,
More informationVacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C
Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationCutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com
MODEL : BANTAM C8 BANTAM C10 PART NO. : 602-325A 602-343A SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@
More informationGT-200 GATE VALVES PN16, Screwed end
Document No. : MD-QO-04-281 Date : 2009/07 /17 Version : 1.0 GT-200 GATE VALVES PN16, Screwed end USER MANUAL Modentic Industrial Corporation 14F-1,No.57Taya Rd.,Taichung,Taiwan,R.O.C. Email:modentic@ms9.hinet.net
More informationReplacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement
More informationPAGE 1 OF 5 HEALTH, SAFETY & ENVIRONMENTAL MANUAL PROCEDURE: S360 Overhead Cranes & Lifts Procedure REV 4.0 8/14/2012
PAGE 1 OF 5 PURPOSE: OVERHEAD CRANES AND LIFTS PROCEDURE The purpose of this procedure is to define the safety and training requirements for use of overhead cranes and lifts. Procedure: Definitions Designated
More informationINSTRUCTION MANUAL FOR THE THERMOCOUPLE ATTACHMENT UNIT (TAU)
INSTRUCTION MANUAL FOR THE THERMOCOUPLE ATTACHMENT UNIT (TAU) Model Number: 41756 (100 125Vac) 41757 (220 240Vac) Manufactured in the United Kingdom CONTENTS Chapter Page Specification 3 What the TAU does
More informationAVX. Operation and Maintenance Manual AVX 1200A A 15kV to 362kV. ALUMINIUM VERTICAL BREAK DISCONNECT SWITCH 15kV to 362kV 1200A A
Operation and Maintenance Manual AVX AVX AVX-1200 2000-15 362KV-E R00 1 TABLE OF CONTENTS 1 General Description...4 1.1 General...4 1.2 Contacts...5 1.3 Switch Base...5 1.4 Insulator Stack Bearing Assemblies...5
More informationMCset kv Medium voltage equipment
Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide
More informationCOOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN
Surge Arresters MN235004EN Effective December 2015 Supersedes S235-26-1 August 2012 COOPER POWER SERIES Surge arrester interchangeable fuse cutout combination installation instructions DISCLAIMER OF WARRANTIES
More informationIntroduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section
More informationPO Box 645, Stockton, Missouri, FAX superiorgearbox.com
I000-7000-D0447-A 4/7/05 1 SAFETY PRECAUTIONS CAUTION Please read this entire document prior to operating the gear drive. Gear drive failure and / or injury to operators may be caused by improper installation,
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationInstruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod
Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND
More informationUniSec Maintenance solutions
DISTRIBUTION SOLUTIONS UniSec Maintenance solutions ABB supports you to improve the reliability, safety and efficiency of your electrical equipment UniSec Maintenance solutions Table of contents 004 00
More informationEffective June 2016 New Issue
Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation
More informationOBE, OBEXU, ON BOARD Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBE, OBEXU, ON BOARD Battery Chargers INTRODUCTION: These chargers are designed for the permanent installation on battery powered vehicles
More informationPOWER PINNER HAND WELDER 7200 OPERATOR S MANUAL
POWER PINNER HAND WELDER 7200 OPERATOR S MANUAL Copyright: January 5, 2009 Revised: November 24, 2014 Serial No. 0901189 - Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence,
More informationTRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS
TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationInstruction manual. EK6 Earthing switch 36/40.5 kv
Instruction manual EK6 Earthing switch 36/40.5 kv Your safety first always! That s why our instruction manual begins with these recommendations: Only install switchgear and/or switchboards in enclosed
More informationFuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A
DISTRIBUTION SOLUTIONS Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A Efficient protection of voltage transformer circuits Extending the lifetime of installed electrical
More informationCOOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN
Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper
More informationGUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES
MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable
More informationCOOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions
Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation
More informationELB ELB
ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical
More informationIntroduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) Inspection Recommendations for Switchgear Equipped with Type AT-2 Source-Transfer Controls Table of Contents
More informationElgin Hydraulic Clutch-Brake ECB-240, Product Number FORM NO. L F FORM NO. L F-0704
Elgin Hydraulic Clutch-Brake ECB-20, Product Number 96225 FORM NO. L-20283-F-070 1 FORM NO. L-20283-F-070 In accordance with Nexen s established policy of constant product improvement, the specifications
More informationInnovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual
Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION
More information1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide
1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.
More informationCOOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN
Recloser Mountings MN280071EN Effective May 2017 Supersedes February 1997 (S280-85-5) KA662R tank-lifting windlass assembly and installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More informationCOOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN
Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF
More informationIGNITION COIL - 2.4L SPARK PLUG
TJ IGNITION CONTROL 8I - 13 IGNITION COIL - 2.4L DESCRIPTION - 2.4L The coil assembly consists of 2 different coils molded together. The assembly is mounted to the top of the engine (Fig. 21). REMOVAL
More informationPO Box 645, Stockton, Missouri, FAX superiorgearbox.com W D0446-A 4/1/05 1
W000-7000-D0446-A 4/1/05 1 SAFETY PRECAUTIONS CAUTION Please read this entire document prior to operating the gear drive. Gear drive failure and / or injury to operators may be caused by improper installation,
More informationEffective November 2016 Supersedes September 1998 (S )
Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES
More informationELB ES. Product Installation Instructions
ELB-25-210-ES 200A 25kV Class Loadbreak Elbow with Integral Jacket Seal for Copper Tape (CT) and Jacketed Concentric Neutral (JCN) cables Product Installation Instructions Safety Instructions When installing
More informationProduct Group Brochure. PS Range Capacitor Vacuum Switches
Product Group Brochure PS Range Capacitor Vacuum Switches Introduction ABB introduces the latest range of PS capacitor vacuum switches. Building on the proven PS switch design, new single phase and three
More informationEffective November 2016 Supersedes February 2012 (S )
Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling
More informationGROUNDSMASTER. 52 Recycler. for 120 Traction Unit. Model No & UP. Operator s Manual
FORM NO. 8-980 Rev A GROUNDSMASTER 5 Recycler for 0 Traction Unit Model No. 077 79000 & UP Operator s Manual IMPORTANT: Read this manual carefully. It contains information about your safety and the safety
More informationGeneral notes. Operating conditions
1 General notes Wöhner busbar systems and components are the result of expert development based on many years of experience. They have been exhaustively tested and hold many approvals. The correct selection
More informationType NR oil switch installation and operation instructions
Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION
More informationX-Tractor Series. Cutters INSTRUCTION MANUAL
INSTRUCTION MANUAL X-Tractor Series Cutters PRINTED IN USA 0305 PART NO. 159R141 Rev. 02 2005 Hale Products, Inc. Hale Products, Inc. reserves the right to make changes at any time, without notice or obligation,
More informationProduct Specifications for Phase Over Phase GOABS(r)
1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for
More informationOperations Manual. and. Seal Kit Replacement Guide
Operations Manual and Seal Kit Replacement Guide MANUFACTURED BY COLUSSI ENGINEERING PTY. LTD. TELEPHONE: (02) 9817 5433 FAX: (02) 9879 6753 53 College street, Gladesville, NSW 2111, Australia www.novapumps.com.au
More informationPlayscape Classics Routine Inspection
Playscape guidelines for playscape classics, including swings, slides, cableways, roundabouts, see saws, rockers, springies and climbers. Remove hazards, such as broken glass, litter, debris from trees
More information9120 EBCU Battery Charger MODELS: 9120EBCU96V 9120EBCU240V
USER GUIDE EBCU Battery Charger MODELS: EBCU96V EBCU240V www.powerware.com.au OMMEBCURev2.doc 1 Table of Contents List of Figures and Tables... 2 Safety Instructions... 3 1.0 Charger Features... 4 1.1
More informationABACO MACHINES OPERATION MANUAL STONE/STEEL/GLASS/WOODS LIFTER (ASSGWL20) ABACO MACHINES (USA)
ABACO MACHINES OPERATION MANUAL STONE/STEEL/GLASS/WOODS LIFTER (ASSGWL20) ABACO MACHINES (USA) 14508 S. Garfield Ave., Paramount, CA 90723, USA Tel : 310-532-0366 Fax : 310-532-99 Email : sales@abacomachines.com
More informationSIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3
SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious
More informationQPET, QPETXU Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S QPET, QPETXU Battery Chargers INTRODUCTION: The QPET line of chargers are designed for general purpose deep cycle batteries. They are an electronically
More informationElectrical Safety Program
Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and
More informationInstructions for Fitting, Operating and Maintenance Canopy Door RE / (St.: )
EN Instructions for Fitting, Operating and Maintenance Canopy Door 1 818 012 RE / (St.: 12.2010) 12.2010 ENGLISH Contents 1 Safety Instructions... 3 1.1 Qualified persons... 3 1.2 Symbols and signal words
More informationBEAM CLAMP INSTRUCTION MANUAL
BEAM CLAMP INSTRUCTION MANUAL Imported exclusively for the Global Lifting Group by Pacific Hoists Pty. Ltd. & Pacific Hoists Ltd. 2 SAFETY INSTRUCTIONS THE FOLLOWING SAFETY INSTRUCTIONS OUTLINE THE CARE
More informationInstruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:
Check out what else you can get from Martindale: 17th Edition Testers Accessories Calibration Equipment Continuity Testers Electricians Kits Environmental Products Full Calibration & Repair Service Fuse
More informationInstruction Manual. Single Acting, Pancake, Locking Collar Hydraulic Cylinders RPLC Series. Maximum Operating Pressure 700 bar
Single Acting, Pancake, Locking Collar Hydraulic Cylinders RPLC Series Maximum Operating Pressure 700 bar ABSOLUTE EQUIPMENT PTY LTD 2/186 Granite Street, GEEBUNG QLD 4034 Australia sales@absoluteequipment.com.au
More informationRadian Research, Inc. makes no warranty on the accuracy of the information contained in this Operations Manual and accepts no liability for its use.
About This Operations Manual makes no warranty on the accuracy of the information contained in this Operations Manual and accepts no liability for its use. The information contained in this Operations
More informationKD1E Range Potential Indicators
KD1E Range Potential Indicators Operating Instructions 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Limited Warranty & Limitation
More informationAttachment Solutions. Superlift System. Operators Manual
Attachment Solutions Superlift System Operators Manual TABLE OF CONTENTS Section I. General Information... 3 Section II. Safety... 3 Section III. Identification of Major Components... 5 Section IV. Setup...
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP
INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP The purpose of this manual is to aid in the proper installation and operation of the fans.
More informationINSTALLATION GUIDE AND USER MANUAL
Electric Vehicle Charging Station INSTALLATION GUIDE AND USER MANUAL Model: 30A EVoCharge EVSE Model Number: EV072-300-001A Product Safety Certification: UL and cul Listed Description: SAE J1772 AC Level
More informationINSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS
INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended
More informationMG GS Warranty Statement
MG GS Warranty Statement Warranty Period The warranty period commences on the date of first registration. MG covers your new MG GS for unlimited mileage up to 12 months, and for 80,000 miles between 13
More informationExample Maintenance Schedule 1. The attached document is an example of an acceptable maintenance schedule.
IRRIGATION TRAINING & RESEARCH CENTER California Polytechnic State University San Luis Obispo, CA 93407-0730 Phone: 805.756.2434 FAX: 805.756.2433 www.itrc.org Example Maintenance Schedule 1 The attached
More informationRaychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions
Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark
More informationIllinois State University. Electrical Safety Procedure
Illinois State University Electrical Safety Procedure Illinois State University Facilities Management Revision Date: May 2014 Illinois State University Facilities Management Electrical Safety Procedure
More informationS Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES
Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2
More informationOWNER S MANUAL PRODUCT CODE: 2006T
Jul-18 Product Code: 2006T OWNER S MANUAL PRODUCT CODE: 2006T HYDRAULIC PIPE BENDER 12,000KG Model Capacity Bending Die No of Attachments 12,000kg 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" 6 Made in China to
More informationModels P, P, P, , DANGER
Installation and maintenance guide Air filter Models 600104P, 600106P, 600108P, 600112, 600116 Date of issue January 2015 Form number 404646B Section G10 Page 31B DANGER Read manual prior to installation
More informationInstruction Manual. Single Acting Hydraulic Aluminium Pull Cylinders RAP Series. Maximum Operating Pressure 700 bar
Single Acting Hydraulic Aluminium Pull Cylinders RAP Series Maximum Operating Pressure 700 bar ABSOLUTE EQUIPMENT PTY LTD 2/186 Granite Street, GEEBUNG QLD 4034 Australia sales@absoluteequipment.com.au
More informationService Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A
Service Instructions Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Vibrating Feeders Models: F-T01-A and DF-T01-A Contents Page
More informationInstallation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv
S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Catalog Number Supplement R3
More informationCONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1
TECHNICAL SERVICE MANUAL industrial heavy duty motor speed pumps SERIES 4076 AND 4176 SIZES hle, ate and ale SECTION TSM 710.1 PAGE 1 of 8 ISSUE B CONTENTS Introduction....................... 1 Safety
More informationERD Electrically Released Brakes
ERD Electrically Released Brakes P-229 819-0453 Installation Instructions Warner Electric s ERD series spring set, electrically released brakes are designed to hold a load when the power to the brake is
More information