1 Installation Instructions Series I Encapsulated Current Limiting Fuse GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information & Precautions 3 3. Description 5 4. Installation 6 This information is transmitted by G&W Electric Co. and accepted by you subject to the following understanding and agreement: By accepting these instructions and any included drawings you agree that all rights to the drawing and information contained herein, as well as the proprietary and novel features of the subject matter, are reserved by G&W Electric Co. and that devices embodying such features or information derived from these disclosures will not be manufactured by you or disclosed to others without the expressed written consent of G&W Electric Co. These drawings and information contained herein are and remain the property of G&W Electric Co. and are not to be copied, reproduced or disclosed to others without the expressed written consent of G&W Electric Co Page 1 G&W ELECTRIC CO G&W Electric Co. PRINTED IN U.S.A.
2 SECTION 1. INTRODUCTION 1.1 General This document is intended to provide the user with necessary information to properly receive, inspect and install G&W s Series I Encapsulated Current Limiting Fuse. These instructions do not intend to cover all situations or contingencies in equipment, procedures or processes. If after reviewing the information contained herein, you should have any questions, please contact your G&W representative or call our customer service number. Read these Instructions Keep these Instructions How to Contact G&W Read and understand the contents of this document and follow all locally approved procedures and safety practices before installing, operating or maintaining this equipment. Be sure to read and understand the Safety Information in Section 2. This document is a permanent part of your G&W fuse record. Keep it in a safe location where it can be readily available and referred to, as necessary. By Phone: By Fax: Mail: Internet: , Monday through Friday, 8:00 AM to 5:00 PM Central Time webmail@gwelec.com 3500 W. 127 th Street, Blue Island, Illinois 60406, USA To find your local G&W Representative visit our Web site: Qualified Persons The equipment covered by this document is intended to be installed, operated and maintained by qualified persons who are trained in the installation, operation and maintenance of electric power distribution equipment along with the associated hazards. A qualified person has been trained and is competent: To de-energize, clear and tag circuits and equipment in accordance with established safety procedures To distinguish between live parts from non-live parts of the equipment In the proper use of insulated tools, wears protective equipment such as rubber gloves, hard hat, safety glasses, flash-clothes, etc. in accordance with established safety practices and is trained in the care of such equipment Is certified in rendering first aid, especially in the technique of removing a person in contact with a live circuit and in applying cardiopulmonary respiration. These instructions are intended only for qualified persons, and are not intended as a substitute for adequate training and experience in safety procedures for this type of equipment. 1.3 Shipment Inspection Examine the equipment carefully for any damage that may have occurred in transit. Remove packing as soon as possible after receiving the equipment. Examine the equipment carefully for any hidden damage that may have occurred in transit and was previously undetected. If damage is found, a claim should be filed at once with the transportation company. 1.4 Storage 2
3 Fuses not immediately installed should be kept in a clean, dry location. Insure that fuses are protected from potential physical or environmental damage. SECTION 2 SAFETY INFORMATION & PRECAUTIONS 2.1 Safety Alert Messages The following is important safety information. For safe installation and operation, be sure to read and understand all danger, warning and caution information. The various types of safety alert messages are described below: DANGER DANGER - Indicates an imminently hazardous situation, which if not avoided, will result in death or serious injury. - Indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury. CAUTION CAUTION - Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury. May also be used to alert against unsafe practices. 2.2 Following Safety Instructions Carefully read all safety messages in this manual and on your equipment. Keep safety signs in good condition. Replace missing or damaged safety signs. Keep your equipment in proper working condition. Unauthorized modifications to the equipment may impair the function and/or safety and affect equipment life. If you do not understand any part of these safety instructions and need assistance, contact your G&W representative or G&W customer service. CAUTION G&W Series I Encapsulated Current Limiting Fuses are not intended to prevent injury or death of people.. CAUTION G&W Series I Encapsulated Current Limiting Fuse is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. Ensure the fuse is rated for the intended application before it is installed. Failure to do so may result in serious damage to the equipment. Fuses should be installed and serviced only by personnel familiar with good safety practice and the handling of hi-voltage electrical equipment. 3
4 Fuses must be de-energized during maintenance. Visible break and adequate grounding must be provided before work proceeds. Failure to do so may result in serious injury or death. CAUTION Fault Indicators: When using fault-indicating devices on a test point, follow instructions provided with the indicator. 4
5 SECTION 3 DESCRIPTION 3.1 General G&W Series I Encapsulated Fuses are used to limit the system fault currents by use of a current limiting fuse element (conforming to Section 6 of ANSI/IEEE Std. C ). The fuses are provided with ANSI terminal connections (meet requirements of IEEE Standard No. 386) for compatible installation in underground cable systems by using 200A dead break, load break, and elbow inserts. The fuses are ruggedly constructed of electrical grade epoxy. The external semi-conducting coating meets grounded surface requirements of IEEE Std An optional stainless steel bracket can be used to mount the fuse. Brackets may be mounted to unistrut, vault walls or welded to an existing bracket system. 3.2 EQUIPMENT REQUIRED G&W Series I Fuse Instruction Sheet Support Bracket (For new installations) Tools - Torque Wrench 3.3 Identification of Components Parking Stand Ground Terminal Mounting Straps YYWEEK Serial # VOLTAGE F AMPS (indicated on outside surface) Semi conductive Tape Figure 1: Components 5
6 SECTION 4 INSTALLATION 4.1 NEW FUSE INSTALLATION (Figures 2 and 3 may be used as typical installations using G&W supplied bracket.) A terminal is provided for attaching a ground to the bracket Recheck to make sure that the semi-conducting surface of the fuse is in electrical contact with the Make sure that all existing grounding procedures are followed Mount the G&W fuse bracket using the mounting holes, making sure that necessary clearance (Refer to figure 2 and 3) are maintained (brackets may also be mounted to unistrut systems, vault walls or welded to an existing bracket system). The G&W bracket has provisions for ½ mounting hardware (mounting hardware is not included) Parking stands may be rotated by 90 increments to fit specified configuration Tightly mount the fuse using the two (2), stainless steel mounting straps and supplied hardware. Torque the fasteners to 65 ft-lbs (88 Newton-meter) The fuse must be mounted such that the semi-conducting surface is in electrical contact with the Remove the plastic protective caps from the ANSI terminals Install the dead break or load break inserts and elbows as specified by the cable accessory manufacturer. 4.2 FUSE REPLACEMENT Fuses must be de-energized during maintenance. Visible break and adequate grounding must be provided before work proceeds. Failure to do so may result in serious injury or death A terminal is provided for attaching a ground to the bracket Recheck to make sure that the semi-conducting surface of the fuse is in electrical contact with the Make sure that all existing grounding procedures are followed It may not be necessary to remove the mounting bracket when re-fusing. Follow the appropriate steps for the change below De-energize the system using the approved safety procedures Place the elbows on the parking stands Remove the stainless steel mounting straps Remove the fuse that has operated Inspect the new G&W Series I encapsulated Fuse Tightly mount the fuse using the two (2), stainless steel mounting straps and supplied hardware. Torque the fasteners to 65 ft-lbs. (88 Newton-meter) The fuse must be mounted such that the semi-conducting surface is in electrical contact with the Remove the plastic protective caps from the ANSI terminals Install the dead break or load break inserts and elbows as specified by the cable accessory manufacturer. 6
7 Figure 2: Typical horizontal vault installation Figure 3: Typical vertical vault installation 7
8 4.3 GROUNDING Fuses must be de-energized during maintenance. Visible break and adequate grounding must be provided before work proceeds. Failure to do so may result in serious injury or death. Make sure that the fuse is adequately grounded and the semi-conductive surface is in electrical contact with the bracket. Failure to properly ground the fuse assembly may lead to the presence of hazardous voltage, which can result in serious injury or death A terminal is provided for attaching a ground to the bracket Recheck to make sure that the semi-conducting surface of the fuse is in electrical contact with the Make sure that all existing grounding procedures are followed. 8
COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN
Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationS&C Vista Underground Distribution Switchgear
S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section
More informationCOOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN
Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES
More informationCOOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN
Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND
More informationCOOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.
Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling
More informationFigure 1. Kearney Type HX cutout.
Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2
More informationCOOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN
Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationCOOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing
Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification
More informationS Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES
Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2
More informationCOOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN
Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More informationEffective November 2016 Supersedes September 1998 (S )
Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES
More informationReplacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement
More informationCOOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN
Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER
More informationCOOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN
Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationCOOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN
Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationCOOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN
Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF
More informationEffective November 2016 Supersedes February 2012 (S )
Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling
More informationCOOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN
Voltage Regulators MN225064EN Effective March 2017 Supersedes October 2011 (S225-60-12) Testing a motor capacitor on a voltage regulator procedure instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES
More informationCOOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN
OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF
More informationCOOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )
Pad-mounted Switchgear MN285019EN Effective March 2017 Supersedes February 2007 (S285-10-6) COOPER POWER Type VFI fault interrupter with tri-phase control single-phase trip to three-phase trip conversion
More informationHigh-voltage primary bushings installation instructions
OEM Equipment Effective November 2013 Supersedes April 2013 S800-35-2 High-voltage primary bushings installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,
More informationInstallation and Operation
S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction
More informationCOOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN
Fault Indicators MN320005EN Effective March 2017 Supersedes December 2008 (S320-50-1) COOPER POWER SERIES S.T.A.R. type LVR faulted circuit indicator installation instructions DISCLAIMER OF WARRANTIES
More informationInstallation Instructions For Motor Control Center (MCC) Units
s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground
More informationEffective March 2015 Supersedes S August 2012
Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions
More informationCOOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions
Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper
More informationS Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards
Voltage Regulators QD8 Tap Changer Replacement Procedure Kit 57A63675100A Service Information S225-50-16 Contents General..................................... 1 Parts Supplied...1 Tools Required..............................
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable
More informationSM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety
SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com
More informationEffective June 2016 New Issue
Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation
More informationCOOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )
Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The
More informationInstruction and Installation Guide
Instruction and Installation Guide Type 2A Arc Resistant tiastar Motor Control Center www.usa.siemens.com/mcc DANGER Hazardous voltage. Will cause death or serious injury. Keep out. Qualified personnel
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section
More informationType NR oil switch installation and operation instructions
Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationType 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear
Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the
More informationFLEX CONNECTOR HEAT SHRINK SLEEVE INSTALLATION GUIDE
FLEX CONNECTOR HEAT SHRINK SLEEVE INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information
More informationPAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons
Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...
More informationCOOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN
Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION
More informationVacuum Circuit Breaker (Vehicle)
Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationSecoVac * Ground & Test Device
GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6
More informationCOOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN
Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION
More informationCOOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions
Deadbreak Apparatus Connectors MN650005EN Effective February 2015 Supersedes S600-10-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions
More informationNorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy
NorthStar TM brand Instruction Manual SLIM Tach SL56 1.125 Thru-Shaft Diameter Magnetoresistive Encoder Designed for GE Wind Energy Patent Pending *791-1061-00* Rev. B Page 2 Table of Contents Chapter/Paragraph/Illustration
More informationTrailer Jack. Model Assembly and Operating Instructions
Trailer Jack Model 37792 Assembly and Operating Instructions 3491 Mission Oaks Blvd., Camarillo, CA 93011 Copyright 1998 by Harbor Freight Tools. All rights reserved. No portion of this manual or any artwork
More informationTechnical Manual. DLM Module. This manual should remain with the unit.
Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this
More informationCOOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN
Recloser Mountings MN280071EN Effective May 2017 Supersedes February 1997 (S280-85-5) KA662R tank-lifting windlass assembly and installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More informationCOOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN
Reclosers MN280074EN Effective May 2017 Supersedes September 2009 (S280-90-6) Electronic control battery testing, charging, and replacement instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More informationSIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3
SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious
More informationCOOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN
Deadbreak Apparatus Connectors MN650004EN Effective February 2015 Supersedes S600-15-3 July 2014 COOPER POWER SERIES 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions DISCLAIMER
More informationSEALING DIP CAP INSTALLATION GUIDE
SEALING DIP CAP INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information contained
More informationANTI-SYPHON VALVE INSTALLATION GUIDE
ANTI-SYPHON VALVE INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information contained
More informationTJ lb Capacity Trailer Jack. 2-in-1 Combo With Swing Back Design. Assembly & Operating Instructions
TJ1500 1500 lb Capacity Trailer Jack 2-in-1 Combo With Swing Back Design Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information
More informationPMA INTAKE FILTER SCREEN INSTALLATION GUIDE
PMA INTAKE FILTER SCREEN INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationCOOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN
Reclosers MN280070EN Effective May 2017 Supersedes July 2014 (S280-80-23) COOPER POWER Dielectric grease application to recloser cable instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationS Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage
Voltage Regulators QD3T350 Reversing Stationary Contact Assembly Instructions Kit 5791822A02 Service Information S225-50-43 Contents General..................................... 1 Parts Supplied...............................
More informationFog Light Bracket Assembly. Unpacking the Kit
25500507 Rev. A0 0219 Safety Message to Installers of Warning Light Equipment People s lives depend on your proper installation and servicing of Federal Signal products. It is important to read and follow
More informationThis Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.
Reclosers CT Field Modification Kit KA906R1 Installation and Testing Instructions Service Information S280-80-13 This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers. Not
More informationInstallation and Operating Manual
Model u002 & u003 Installation and Operating Manual Ultrasonic Level Switch 60 Great Hill Road Naugatuck, CT 06770 ph: 203-729-6434 fax: 203-729-6696 www.innovativesensing.com Read this Manual Before Installing
More informationInstallation, Operation and Maintenance Instructions. SLS Series Single Phase Disconnector
Installation, Operation and Maintenance Instructions SLS Series Single Phase Disconnector Contents Inspection, Preparation and Installation...4 Step 1. Mounting Bracket Installation...4 Step 2. Mounting
More informationS Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.
Voltage Regulators QD3/T350 Main Movable Contact Assembly Kit Kit 5741325B04 Service Information S225-50-42 Contents General..................................... 1 Tools Required..............................
More informationCOOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN
Deadbreak Apparatus Connectors MN650003EN Effective February 2015 Supersedes S600-55-1 July 2014 COOPER POWER SERIES 600 A 35 kv class BT-TAP connector system installation instructions DISCLAIMER OF WARRANTIES
More informationCleaning Flooded Gear
S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationS Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.
Voltage Regulators QD8 Movable Contact Board Replacement Procedure Kit 5742895B01 Service Information S225-50-38 Contents General..................................... 1 Parts Supplied...............................
More informationTRAILER INSTALLATION INSTRUCTIONS
TRAILER INSTALLATION INSTRUCTIONS 8A000450 DuraMax 20,000 LB. CAPACITY Link Mfg. Ltd. 223 15th St. N.E. Sioux Center, IA USA 51250-2120 www.linkmfg.com QUESTIONS? CALL CUSTOMER SERVICE 1-800-222-6283 Refer
More informationManufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN
Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180 ST Series Service Tester Phase Identifier Operating Instructions ST500PGN REV. ED. 101229 CONTENTS Limitation of Warranty and Liability
More informationAssembly Instructions
Assembly Instructions SS-4000 Serial No. SB4-100000 and higher Madison Heights, Michigan 48071 800-SALTERS www.snowexproducts.com CUSTOMER COPY TrynEx International 2013 (REV A) F51067C 1 Table of Contents
More informationEffective May 2017 Supersedes December 2004 (S )
Reclosers MN280054EN Effective May 2017 Supersedes December 2004 (S280-15-10) COOPER POWER Types L, V4L, E, 4E, and V4E; KA785L10S, KA785L20S, KA785L30S, and KA785L40S Automation upgrade kit installation
More informationCOOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN
Reclosers MN280069EN Effective April 2017 Supersedes February 1982 (S280-80-19) COOPER POWER KA1169R Closing Coil Transfer-Switch Accessory Operation SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationSTEEL SIDE PANEL KIT. Model (FOR USE WITH MODEL FOLDABLE UTILITY TRAILER)
STEEL SIDE PANEL KIT Model 47423 (FOR USE WITH MODEL 42709 FOLDABLE UTILITY TRAILER) Set up and Operating Instructions (MODEL 42709 TRAILER and TARP NOT INCLUDED. TARP SOLD SEPARATELY. Shown for illustration
More informationOwner's/Installation Manual
Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationModel IPX-LPV2 Adjustable Mounting Kit for IMPAXX. and MicroPulse. Installation Instructions A Rev. A Printed in U.S.A.
Model IPX-LPV2 Adjustable Mounting Kit for IMPAXX and MicroPulse Installation Instructions 25500375A Rev. A0 0117 Printed in U.S.A. Limited Warranty This product is subject to and covered by a limited
More informationCAMBELT TENSION GAUGE
CAMBELT TENSION GAUGE Model 96557 Operating Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the product
More informationPremium Supply. Tilt Deck. Models PCK-TD PCK-PTD. Operator s Manual and Installation Instructions
Tilt Deck Models PCK-TD PCK-PTD Operator s Manual and Installation Instructions Premium Supply 2038 West Interstate 30 866-934-0777 Proud members of: and June 1, 2015 Table of Contents Introduction...
More informationHubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.
Line Post Sensors Product Instruction Manual Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications. 2018 Hubbell Incorporated
More informationGalaxy Receiving and Unpacking 09/
Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS
More informationFebruary 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION
February 28 th, 2018 UPDATE: Important Product Safety Bulletin Immediate Action Required INSTRUCTIONS FOR FIELD RISK MITIGATION Eaton Bussmann series CUBEFuse Indicating TCF DANGER: FAILURE TO WEAR APPROPRIATE
More informationU00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004
U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004 READ THIS MANUAL PRIOR TO INSTALLATION This manual
More informationMonicon Instruments Co., Ltd. CHR-1285/2485 CHR-1285/2485 BATTERY CHARGER
CHR-1285/2485 BATTERY CHARGER TEL:886-4-2238-0698 FAX:886-4-2238-0891 Web Site:http://www.monicon.com.tw E-mail:sales@monicon.com.tw Copyright 2007 Monicon Instruments Co., Ltd. All right reserved. Contents
More informationTUFFSTUFF FITNESS INTERNATIONAL OWNER S MANUAL
TUFFSTUFF FITNESS INTERNATIONAL OWNER S MANUAL Maintenance & Assembly Instructions IMPORTANT: KEEP THIS MANUAL FOR FUTURE REFERENCE NOTICE It is the Purchaser s/owner s obligation: 1. To disclose and post
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION
More informationAltivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit
Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit Instruction Bulletin 30072-453-27 Retain for future use. For Frame Sizes 2 5: ATV61H075M3, -HU15M3, -HU22M3, -HU30M3, -HU40M3,
More informationSERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES
SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED
More informationCOOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN
Fusing Equipment MN132024EN RTE EL-BAY-O-NET FUSE Re-Fusing Instructions Effective November 2016 Supersedes June 1991 (S240-72-1) COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationElectrical Safety Program
Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and
More informationOPERATOR S AND PARTS MANUAL PALLET FORKS. Part Number: MODEL NUMBER: Rev. 4
OPERATOR S AND PARTS MANUAL PALLET FORKS SERIAL NUMBER: Manual Number: OM642 Part Number: 75542 MODEL NUMBER: Rev. 4 800-456-7100 I www.paladinlcg.com 503 Gay Street, Delhi, IA 52223, United States of
More informationPremium Supply. Tilt Deck. Models PCK-TD PCK-PTD CTD-310-K. Operator s Manual and Installation Instructions
Tilt Deck Models PCK-TD PCK-PTD CTD-310-K Operator s Manual and Installation Instructions Premium Supply 2038 West Interstate 30 866-934-0777 Proud members of: and April 20, 2018 Table of Contents Introduction...
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationFLEX-ING TM DISPENSER HOSES INSTALLATION GUIDE
FLEX-ING TM DISPENSER HOSES INSTALLATION GUIDE The information in this publication is provided for reference only. While every effort has been made to ensure the reliability and accuracy of the information
More informationBlinkerBeam SL80 Controller User Guide
BlinkerBeam SL80 Controller User Guide TAPCO Traffic & Parking Control Company, Inc. SL80_guide_131119 Table of Contents Read Warnings, Cautions and Notes on next page Before Proceeding Testing Battery
More informationOwner s Manual & Safety Instructions
Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s
More informationWB-100B Walk-Behind Broadcast Spreader
Fisher Engineering 50 Gordon Drive, Rockland, Maine 04841-2139 www.fi sherplows.com 85102 February 1, 2019 Lit. No. 43587, Rev. 02 WB-100B Walk-Behind Broadcast Spreader Owner's Manual and Installation
More informationInstallation and Operation Manual
1645 Lemonwood Dr. Santa Paula, CA 93060 USA Toll Free: 1 (800) 253-2363 Tel: 1 (805) 933-9970 rangerproducts.com Ranger Floor Jack Installation and Operation Manual Manual Revision B July 2017 Manual
More informationCleaning Flooded Gear
S&C Manual Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationSAC Liquid Manure Flow Meter
LM300000 REV A 11/11/2009 QUALITY PEOPLE, QUALITY PRODUCTS SAC Liquid Manure Flow Meter Operation and Service Manual ASSEMBLY CALIBRATION OPERATION REPLACEMENT PARTS READ complete manual CAREFULLY BEFORE
More informationModels beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.
Models beginning with MO, MK, 7B, 6S, 6F or 5B The Mini Meter Product Description Technical Specifications Installation Instructions February 28 th, 2013 1. Product Description...2 1.1 General Description...2
More information1250 LB. CAPACITY MECHANICAL WHEEL DOLLY
1250 LB. CAPACITY MECHANICAL WHEEL DOLLY 67287 SET-UP AND OPERATING INSTRUCTIONS Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result
More information