ELB ELB

Size: px
Start display at page:

Download "ELB ELB"

Transcription

1 ELB ELB A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical power system accessories, failure to follow applicable personal safety requirements and written installation instructions could result in fire or explosion and serious or fatal injuries. As Tyco Electronics has no control over field conditions which influence product installation, it is understood that the user must take this into account and apply his own experience and expertise when installing product. Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling high-voltage electrical equipment. De-energize and ground all electrical systems before installing product. Conductive cap Insulating plug Stud Optional test point Elbow Power distribution and transmission products must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Read and understand the contents of these instructions before installation and follow all locally approved procedures and safety practices before installing or operating this equipment Lug adapter Fig. 101 These instructions cannot cover all details or variations in the equipment, procedures, or processes described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, please contact your Tyco Electronics sales representative. These instructions are not intended to supersede or replace existing safety and operating procedures. Upon receipt of a product, inspect it thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately or contact your Tyco Electronics representative. Customer Service For 24 hour customer service, call Grounding and Sealing applications Tyco Electronics recommends sealing elbow s bottom end and cable area. Sealing kit for CN, JCN, and copper tape cable types not included. Tyco Electronics sealing kit (ELB GRD1, GRD2, or GRD3) or equivalent is recommended. General Information The Tyco Electronics ELB and ELB kV class 600A elbows are used to terminate highvoltage cable on deadfront apparatus transformers and switchgear or make separable splice or junction connections. They are fully shielded, fully submersible and are interchangeable with all other manufacturers that certify compliance with IEEE standard

2 Installation Instructions 1. Check kit Check kit components to insure proper fit with the cable diameter dimensions, conductor size, and mating products. Suggested Installation Equipment (not supplied with kit) preparation tools, lint-free cloths Non-conducting abrasive cloth, 120 grit or finer Connector(s) and installation tools 2. Cut cable Position the cable so that it is parallel to the apparatus faceplate and is located in the final assembled position with enough slack to allow movement of elbow to insulated parking bushing. Cut cable 1-3/4 (45mm) from the centerline of the mating bushing. C L 1-3/4 (45mm) Cut Fig. 102 Choose the cable type (Choice 1 below or Choice 2: Copper Tape Shield on page 7, step 18) and follow the directions given. Choice 1: Jacket Concentric Neutral or Concentric Neutral cable 3. Prepare cable If using an elbow sealing kit - review the instructions before starting the elbow cable prep to avoid redundant steps. If jacketed neutral cable, remove outer jacket 13 (330mm) from end of cable. If unjacketed neutral cable, bind neutral wires using red marking tape at 15 (380mm). Fold back neutral wires allowing enough extra length to connect to ground and allow elbow movement to insulated parking bushing. Tape the ends of the concentric neutral wires down to cover sharp edges. Remove semi-con shield 10-1/2 (267mm) from the end of the cable with a straight, smooth, squared cut. Do not cut or nick the. Wrap two turns of marking tape 1 (25mm) from end of semi-con shield. This will be a guide for the cable adapter location. Gray mastic for elbow seal (if applicable) Concentric neutral wires Semi-con 2-1/2" (63mm) 13 (330mm) 10-1/2" (267mm) 1" (25mm) Fig Remove 4-3/8-4-5/8 ** (111mm-118mm) ** If using a ShearBolt connector, refer to conductor strip lengths in ShearBolt packaging. Remove exposing conductor between 4-3/8 and 4-5/8 (111mm and 118mm). Bare conductor Fig

3 5. Chamfer and clean Remove sharp edge of by chamfering the end of the cable at a 45 0 angle, approximately 1/4 (6mm) back. Thoroughly clean the with a solvent dampened cloth, wiping from conductor toward cable semi-con shield. Ensure that all traces of conductive residue are removed. If using a jacket sealing device park it on the cable now. Follow instructions in the jacket sealing kit after elbow assembly is complete /4 (6mm) Chamfer Fig Lubricate and install cable adapter Lubricate exposed cable with silicone grease always working toward cable semi-con shield. Lubricate Lubricate Lubricate inside inside of cable adapter. Install cable adapter, small end first, over cable using a twisting motion until it is flush adapter with the edge of the tape marker. Fig Ensure position of cable adapter The cable adapter has a step molded into the cable entrance. When sliding the cable adapter on you should feel a positive stop when the step in the adapter meets the step in the semicon of the cable. The positive stop should be felt at the same location as the tape mark. DO NOT slide adapter past this step. If you suspect you have slid the adapter past the step, pull adapter off and reinstall cable adapter. When you are certain that the adapter is in the correct position, secure cable adapter in position by wrapping five half lapped layers of PVC tape over the small end of Semicon step Slide adapter Note: When using ShearBolt lug, some may extend beyond the top of the cable adapter. Adapter PVC tape step adapter the cable adapter and over the marking tape. Fig Install connector (Compression or ShearBolt lug) Compression Lug: Copper conductor: Remove protective cap and fully insert conductor into compression lug. Aluminum conductor: Prepare aluminum conductor by wire brushing just prior to insertion into connector. Remove protective cap and fully insert conductor into compression lug. Connector must be fully seated on cable conductor. Align flats of lug and bushing before crimping. Start crimps at the lug end 1/2 (13mm) below shoulder of compression connector and work down. Crimp the compression lug following the crimping instruction supplied with the lug. Wipe all excess inhibitor from connector and cable adapter surfaces. ( ) Lug Place first crimp here Parallel flats Fig

4 ShearBolt Lug: Copper conductor: Fully insert conductor into ShearBolt lug. Aluminum conductor: Prepare aluminum conductor by wire brushing just prior to insertion into connector. Fully insert conductor into ShearBolt lug. Connector must be fully seated on cable conductor. Align flats of lug and bushing before installation. Install ShearBolt lug per instructions packaged with lug. Thoroughly clean the connector to remove any installation residue. 9. Check dimension The distance from the end of the lug to the cable adapter after installation should be between 6-1/2 to 7-1/2 (165mm 190mm). Otherwise redo assembly. The following steps for JCN will be illustrated using a compression lug but the same applies for a ShearBolt lug. Bolt shearing squence 1 2 Lug 1/2" (13mm) Check dimension after installation 6-1/2 to 7-1/2 ( mm) Fig. 108sb Parallel flats Fig. 109jcn 10. Install elbow on cable and evenly lubricate the entire surface of cable adapter with silicone grease. Lubricate inside the cable entrance of the elbow wiping 360º around the entire surface and at least 2 (50mm) deep. If test point elbow is used, ensure that test point is facing towards installer. Push elbow onto cable adapter until lug eye is centered in the 600A interface. Ensure that the cable adapter does not move while installing the elbow. and Lubricate Optional test point facing installer 2 Elbow and Lubricate inside surface 2 (50mm) Fig Verify dimension 2 (52mm) maximum Make sure the gap between the cable jacket cutback and the end of the elbow does not exceed 2 (50mm). Fig. 1025j 12. cable from the elbow grounding eye to the cable jacket cutback using an approved solvent capable of removing silicone grease. Make sure all grease is removed from bottom of elbow. If using an elbow seal, install now, before connecting elbow to bushing. Fig. 1026j 4

5 13. Assemble elbow on bushing and lubricate the entire mating surfaces of bushing and elbow interfaces. Push elbow onto apparatus bushing. If a test point elbow is used, ensure that the test point is facing the installer. and lubricate mating surfaces Fig Prepare insulating plug Carefully hand tighten the threaded stud into the insulating plug or mating part. and lubricate the mating surfaces of insulating plug and elbow interface. Insulating plug Stud and lubricate mating surfaces Fig Install insulating plug Push plug into the elbow and tighten to apparatus bushing using a torque wrench and 1 socket. Tighten plug clock-wise exerting 55 ft-lbs (75 N-m) of torque. The insulating plug provides a capacitive test point for detecting system voltage. The ELB elbow has an integral capacitive test point on the body. Follow VOLTAGE TEST directions on page 12. Apply torque 55ft-lbs ELB optional test point Fig

6 16. Install conductive cap and lubricate inner surface of conductive cap with lubricant supplied. Push cap onto insulating plug until it snaps into place. Conductive cap and lubricate inside surface Fig Ground system Connect the grounding eye of the elbow with a minimum #14AWG copper drain wire to cable s concentric neutral wires or to a common ground point. Installation is complete. See page 12 for additional information. Ground copper braid Fig. 115j 6

7 Choice 2: Copper Tape Shield 18. Prepare cable Sealing kit for CN, JCN, and copper tape shield types not included. Tyco Electronics sealing kit (ELB GRD1, GRD2, or GRD3) or equivalent is recommended. If using an elbow sealing kit - review the instructions before starting the elbow cable prep to avoid redundant steps. Remove outer jacket 14 (356mm) from end of cable. Remove semi-con shield 10-1/2 (267mm) from the end of the cable with a straight, smooth, squared cut. Do not cut or nick the. Wrap two turns of marking tape 1 (25mm) from end of semi-con shield. This will be a guide for the cable adapter location. Copper tape shield Semi-con 3-1/2" (89mm) 1-1/2" (38mm) 14 (356mm) 10-1/2" (263mm) 1" (25mm) Fig Install ground braid (included with grounding kit) (1) Lay the ground braid on the cable with the solder block aligned with the jacket cutback and the short end of the braid over the exposed copper tape shield. Ground braid Moisture block Spring clamp (2) Attach the braid to the tape shield by placing two wraps of the spring clamp over the braid. (3) Fold the short end of the braid back over the spring clamp wraps as shown. Continue to wrap the remaining clamp over the braid. Tighten clamp by twisting it in the direction it is wrapped and secure with the copper foil tape provided Fig Remove ** If using a ShearBolt connector, refer to conductor strip lengths in ShearBolt packaging. 4-3/8-4-5/8 ** (111mm-118mm) Remove exposing conductor between 4-3/8 and 4-5/8 (111mm and 118mm). Bare conductor Fig Chamfer and clean Remove sharp edge of by chamfering the end of the cable at a 45 0 angle, approximately 1/4 (6mm) back. Thoroughly clean the with a solvent dampened cloth, wiping from conductor toward cable semi-con shield. Ensure that all traces of conductive residue are removed. If using a jacket sealing device park it on the cable now. Follow instructions in the jacket sealing kit after elbow assembly is complete Bare conductor 1/4 (6mm) Chamfer Fig. 105CT 7

8 22. Lubricate and install cable adapter Lubricate exposed cable with silicone grease always working toward cable semi-con shield. Lubricate inside of cable adapter. Install cable adapter, small end first, over cable using a twisting motion until it is flush with the edge of the tape marker. Lubricate Lubricate inside adapter Fig. 106CT 23. Ensure position of cable adapter The cable adapter has a step molded into the cable entrance. Slide adapter When sliding the cable adapter on you should feel a positive stop when the step in the adapter meets the step in the semicon of the cable. The positive stop should be felt at the same location as the tape mark. DO NOT slide adapter past this step. If you suspect you have slid the adapter past the step, pull adapter off and reinstall cable adapter. When you are certain that the cable is in the correct position, secure cable adapter in position by wrapping five half lapped layers of PVC tape over the small end of the cable adapter and over the marking tape. Semicon step Adapter step PVC tape adapter Fig. 107CT 24. Install connector (Compression or ShearBolt lug) 1/2" (13mm) Compression Lug: Copper conductor: Remove protective cap and fully insert conductor into compression lug. Aluminum conductor: Prepare aluminum conductor by wire brushing just prior to insertion into connector. Remove protective cap and fully insert conductor into compression lug. Lug Place first crimp here Parallel flats Fig. 108CT Connector must be fully seated on cable conductor. Align flats of lug and bushing before crimping. Start crimps at the lug end 1/2 (13mm) below shoulder of compression connector and work down. Crimp the compression lug following the crimping instruction supplied with the lug. Wipe all excess inhibitor from connector and cable adapter surfaces. Bolt shearing squence 1 2 ShearBolt Lug: Copper conductor: Fully insert conductor into ShearBolt lug. Aluminum conductor: Prepare aluminum conductor by wire brushing just prior to insertion into connector. Fully insert conductor into ShearBolt lug. Connector must be fully seated on cable conductor. Align flats of lug and bushing before installation. Install ShearBolt lug per instructions packaged with lug. Lug 1/2" (13mm) Parallel flats Fig. 108CTSB 8

9 25. Check dimension The distance from the end of the lug to the cable adapter after installation should be between 6-1/2 to 7-1/2 (165mm 190mm). Otherwise redo assembly. The following steps for copper tape shield will be illustrated using a compression lug but the same applies for a ShearBolt lug. Check dimension after installation 6-1/2 to 7-1/2 ( mm) Fig. 109CT 26. Install elbow on cable Optional test point facing installer and evenly lubricate the entire surface of cable adapter with silicone grease. Lubricate inside the cable entrance of the elbow wiping 360º around the entire surface and at least 2 (50mm) deep. If test point elbow is used, ensure that test point is facing towards installer. Push elbow onto cable adapter until lug eye is centered 2 Elbow in the 600A interface. Ensure that the cable adapter and and does not move while installing the elbow. Lubricate Fig. 110 Lubricate inside surface 2 (50mm) 27. Prepare cable and install elbow 3-1/4 (83mm) maximum Prepare rest of cable and install elbow per manufacturer s instructions. Make sure the gap between the cable jacket cutback and the end of the elbow does not exceed 3-1/4 (83mm). Fig cable from the elbow grounding eye to the cable jacket cutback using an approved solvent capable of removing silicone grease. Make sure all grease is removed from bottom of elbow. If using an elbow seal, install now, before connecting elbow to bushing. Fig

10 29. Assemble elbow on bushing and lubricate the entire mating surfaces of bushing and elbow interfaces. Push elbow onto apparatus bushing. If a test point elbow is used, ensure that the test point is facing the installer. and lubricate mating surfaces Fig. 111CT 30. Prepare insulating plug Hand tighten the threaded stud into the insulating plug or mating part. and lubricate the mating surfaces of insulating plug and elbow interface. Insulating plug Stud and lubricate mating surfaces Fig. 112CT 31. Install insulating plug Push plug into the elbow and tighten to apparatus bushing using a torque wrench and 1 socket. Tighten plug clock-wise exerting 55 ft-lbs (75 N-m) of torque. The insulating plug provides a capacitive test point for detecting system voltage. The ELB elbow has an integral capacitive test point on the body. Follow VOLTAGE TEST directions on page 12. Apply torque 55ft-lbs ELB optional test point Fig. 113CT 10

11 32. Install conductive cap and lubricate inner surface of conductive cap with lubricant supplied. Push cap onto insulating plug until it snaps into place. Conductive cap and lubricate inside surface Fig. 114CT 33. Ground system Connect grounding eye of the elbow with a min. #14AWG copper drain wire. Connect ground to braid or a common ground point. Installation is complete. See page 12 for additional information. Fig

12 Capacitive Voltage Test The Tyco Electronics ELB elbow is provided with an integral capacitive test point on the body. Both the ELB and ELB elbow kits contain an insulating plug that has a test point as noted in steps 15 and 31. Complete the following steps to use the test point: Remove test point cap with a hotstick. Rather than pulling directly in line with the test point assembly. PEEL OFF AT AN ANGLE. Test point Using a suitable sensing device, determine if the cable is energized. Use only voltage indicating instruments specifically designed for capacitive test points. Use of conventional voltage sensing devices may provide a false No Voltage indication. The test point must be dry and free of contaminants when checking for voltage. Test point To prevent serious or fatal injury treat the elbow as energized until the No Voltage test point indication is confirmed by other means. After voltage detection has been made, clean and lubricate the inside surface of the test point cap with silicone grease and replace it on the test point with a hot stick. Fig. 116 The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. However, Tyco Electronics Corporation has no control over the field conditions which influence product installation. It is the user s responsibility to determine the suitability of the installation method in the user s field conditions. Tyco Electronics only obligations are those in Tyco Electronics standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products. TE (logo) and Tyco Electronics are trademarks. Other trademarks used are the property of their respective owners. Copyright Tyco Electronics Corporation. All Rights Reserved. 12

ELB ES. Product Installation Instructions

ELB ES. Product Installation Instructions ELB-25-210-ES 200A 25kV Class Loadbreak Elbow with Integral Jacket Seal for Copper Tape (CT) and Jacketed Concentric Neutral (JCN) cables Product Installation Instructions Safety Instructions When installing

More information

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions Raychem CSJA 1521 Cold-Shrinkable Splice for single core polymeric insulated (XLPE-EPR) cables up to 15kV for tape, wire, Unishield, LC shield, JCN, and flat strap neutral cable UniShield is a trademark

More information

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions Deadbreak Apparatus Connectors MN650005EN Effective February 2015 Supersedes S600-10-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

More information

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF

More information

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN Deadbreak Apparatus Connectors MN650004EN Effective February 2015 Supersedes S600-15-3 July 2014 COOPER POWER SERIES 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions DISCLAIMER

More information

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN Deadbreak Apparatus Connectors MN650003EN Effective February 2015 Supersedes S600-55-1 July 2014 COOPER POWER SERIES 600 A 35 kv class BT-TAP connector system installation instructions DISCLAIMER OF WARRANTIES

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

Installation Instructions

Installation Instructions 517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Deadbreak Elbow Applicable Current Ratings 600A (Aluminum) 900A (Copper) Applicable Catalog Prefix 35kV

More information

3M Cold Shrink QT-III Silicone Rubber Termination

3M Cold Shrink QT-III Silicone Rubber Termination 3M Cold Shrink QT-III Silicone Rubber Termination For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable 7673-S-8(S)-TOW/WOT Instructions IEEE Std. No. 48 Class 1 Termination 69 kv Class, 350

More information

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles IS---K656CY,CH,I Page 1 of 6 CONTENTS: Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars,

More information

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series 3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series For 3-Conductor Copper Tape Shield Cables without Ground Wires Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN For Jacketed Concentric Neutral (JCN) Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350 kv BIL IEC 60840 72,5

More information

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions

Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Cold Shrink - Silicone Rubber QTII(X)4S-32H Series Cable Termination Instructions Class I Indoor Termination Voltage Designation: 12/20(24) kv Kit Contents: 1 HeatShrinkBreakoutBootAssembly 3 HeatShrinkBindingSleeves

More information

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit 3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit With High-K Stress Relief For 3-Conductor Copper Tape Shield Cables with or without Ground Wires 7600-T-3RJS Series Instructions

More information

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN

Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN 3 Cold Shrink Silicone Rubber Termination QT-III 7672-S-8-JCN Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class 350 kv BIL IEC 60840 72,5 kv Kit Contents: 1 Silicone Rubber Lug Seal Insulator

More information

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN Loadbreak Apparatus Connectors MN650014EN Effective January 2016 Supersedes S500-110-1 April 2015 COOPER POWER SERIES Fused loadbreak elbow connector installation instructions DISCLAIMER OF WARRANTIES

More information

3M Cold Shrink Splice Kit QS-III 5536A

3M Cold Shrink Splice Kit QS-III 5536A 3M Cold Shrink Splice Kit QS-III 5536A for UniShield, Wire Shielded, Longitudinally Corrugated (LC), and Tape Shielded (Ribbon Shielded) Cable or Transitions to Concentric Neutral (CN)/Jacketed Concentric

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-TOW/WOT For Tape-Over-Wire (TOW) or Wire-Over-Tape (WOT) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

Effective November 2016 Supersedes February 2012 (S )

Effective November 2016 Supersedes February 2012 (S ) Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling

More information

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits 3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits With High-K Stress Relief For 3-Conductor Type G (Ground Wire), Copper Tape Shield, Armored Cables 7600-S-3G Series Instructions IEEE Std.

More information

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination 3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination Instructions IEEE Std. No. 48 Class 1 Termination CAUTION Working around energized electrical systems may

More information

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC 3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8-Tape/LC For Tape Shield or Longitudinally Corrugated (LC) Shielded Cable Instructions IEEE Std. No. 48-1996 Class 1 Termination 69 kv Class, 350

More information

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) 3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TOW/WOT (RW) for Tape Over Wire and Wire Over Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325

More information

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW)

3M Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8-TS (RW) 3M Cold Shrink Skirted Termination Kit QT-III 7672-S-8-TS (RW) for Tape Shielded Cable Instructions Class 1 Termination IEC 60840 72,5 kv 69 kv Class 325 kv BIL CAUTION Working around energized systems

More information

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES

More information

(K),(M)430TB/G Up to 36 kv

(K),(M)430TB/G Up to 36 kv IS90722-ENG - 430TB/G-45 25 June 2009 - Revision 8A - Supersedes edition of 25 November 2008 Page 1 of 10 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation

More information

(K),(M),(P)489TB/G Up to 42 kv

(K),(M),(P)489TB/G Up to 42 kv IS91374-ENG - 489TB/G-45/S 22 October 2012 - Revision 1 - Supersedes edition of 4 May 2012 Page 1 of 9 CAUTION : Read instructions thoroughly and completely prior to beginning installation. Installation

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief 7642-S-2, 7642-S-2(L) For Jacketed Concentric Neutral (JCN) and Concentric Neutral (CN) Cable Instructions IEEE Std.

More information

QT-III Cold Shrink Silicone Rubber

QT-III Cold Shrink Silicone Rubber QT-III Cold Shrink Silicone Rubber 7600-T-3RJS Series 3/C Cabinet Termination Instructions Kit Contents: 3ÑSilicone Rubber Phase Re-jacketing Sleeve Assembly 3ÑCold Shrink Silicone Rubber Termination Assembly

More information

HVS S 15kV Class

HVS S 15kV Class Product HVS-3-1580S 15kV Class Transition Splice for 3/C to 3/C Extruded Dielectric (Poly/EPR) Power Cables Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 PII-54864, Rev

More information

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254. 3 Loadbreak Elbows 200 Amp 5-15 kv Industrial pg. 252 Loadbreak Elbows 200 Amp 25 kv Industrial pg. 254 Loadbreak Elbows 200 Amp Industrial pg. 255 Loadbreak Elbows Accessories 3 Loadbreak Elbows 3M 200

More information

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN Fault Indicators MN320005EN Effective March 2017 Supersedes December 2008 (S320-50-1) COOPER POWER SERIES S.T.A.R. type LVR faulted circuit indicator installation instructions DISCLAIMER OF WARRANTIES

More information

Cold Shrink QS T Trifurcating Transition Splice Kit

Cold Shrink QS T Trifurcating Transition Splice Kit Cold Shrink QS2012-13-3T Trifurcating Transition Splice Kit Instructions IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice Cable Size Range Requirements PILC 500 kcmil Conductor Size (240 mm 2

More information

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526

Product Installation Instructions. Raychem Corporation Electrical Products 8000 Purfoy Road Fuquay-Varina, NC 27526 Product HVS Series Cable Splice Shim Kit for 1/C Extruded Dielectric (Poly/EPR) Power Cables: Metallic Tape, Wire Shield, UniShield, LC Shield, Lead Sheath or Concentric Neutral URD Cables UniShield is

More information

High-voltage primary bushings installation instructions

High-voltage primary bushings installation instructions OEM Equipment Effective November 2013 Supersedes April 2013 S800-35-2 High-voltage primary bushings installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables)

Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Motor Lead Pigtail or V-Stub Splice 5380 Series For 5/8 kv Non-Shielded and Shielded Feeder Cables (Tape, Wire or UniShield Cables) Instructions Kit Contents 3 Lug Covers 3 Cold Shrink Terminations 12

More information

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable 7685-S-8 Instructions IEEE Std. No. 48 Class 1 Termination 35

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kit 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief 3M Cold Shrink QTIII Silicone Rubber Skirted Termination Kit With HighK Stress Relief For Jacketed Concentric Neutral

More information

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits

3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits 3M Cold Shrink QT-II Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Instructions IEEE Std. No. 48 Class 1 Termination 8 kv Class, 95 kv BIL:

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit

3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit 3M Cold Shrink QT-III Silicone Rubber Indoor Tubular Termination Kit With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7622-T-110, 7624-T-110, 7625-T-110, 7626-T-110 Instructions

More information

Installation Instructions

Installation Instructions 517 Lyons Ave, Irvington, NJ 07111 Phone: 973-371-1771 Fax: 973-371-4304 Installation Instructions Series Cold Shrink R-800 Appli Ftener Type G Style Appli Housing Sizes O, P, & Q Appli Catalog Prefix

More information

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K)

IS94012-ENG - AFN February Revision 6 - Supersedes edition of 28 January and / or. 3 x Stress control mastic, type MFC (Hi-K) IS94012-ENG - AFN 20-45 5 February 2013 - Revision 6 - Supersedes edition of 28 January 2013 Page 1 of 7 CAUTION: Read instructions thoroughly and completely prior to beginning installation. Installation

More information

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief

3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief 3M Cold Shrink QT-III Silicone Rubber Indoor Termination Kits With High-K Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7621-T-95, 7622-T-95, 7624-T-95, 7625-T-95 Instructions IEEE Std.

More information

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4

3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 3M Cold Shrink QT-lll Silicone Rubber Skirted Termination Kit 7692-S-4, 7693-S-4, 7694-S-4, 7695-S-4, 7696-S-4 With High-K Stress Relief For Tape Shielded, Wire Shielded and UniShield Cable Instructions

More information

INSTALLATION PRODUCTION TESTS

INSTALLATION PRODUCTION TESTS Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate

More information

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits 3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits With High Ampacity Ground Connection and High-K Stress Relief For Tape Shield, Wire-Over-Tape Shield and Longitudinally Corrugated (LC) Shield

More information

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50 Deadbreak Apparatus Connectors 600 A 35 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-50 General The Cooper Power Systems 600 A, 35 kv Class Bol-T Deadbreak Connector is used to terminate

More information

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit Instructions for Shielded and Belted PILC Cable IEEE Std. 404-1993 15 kv Class 110 kv BIL Completed Splice UniShield Wire Shielded Longitudinally

More information

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards Voltage Regulators QD8 Tap Changer Replacement Procedure Kit 57A63675100A Service Information S225-50-16 Contents General..................................... 1 Parts Supplied...1 Tools Required..............................

More information

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief)

Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Cold Shrink Silicone Rubber Termination QT-III (With High-K Stress Relief) Instruction Sheet IEEE Std. No. 48 1990 Class 1 Termination 5/8.7 kv Class 95 kv BIL Kit Contents: 3 Hi K, Tracking Resistant,

More information

Installation Instructions LINK---C

Installation Instructions LINK---C IS---LINK---C Page 1 of 10 Installation Instructions LINK---C DEADBREAK CAM LINK OPERABLE CONNECTOR SYSTEM The is a 600 amp, connector designed to: 1.) provide a fully shielded, fully submersible hot stick

More information

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector

More information

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate

More information

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief

3M Cold Shrink QT-lll Silicone Rubber Indoor Tubular Termination Kits With High-K Stress Relief 3M Cold Shrink QTlll Silicone Rubber Indoor Tubular Termination Kits With HighK Stress Relief For Tape Shield, Wire Shield and UniShield Cable 7693T150, 7695T150, 7696T150 Instructions IEEE Std. No. 48

More information

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is

More information

Effective June 2016 New Issue

Effective June 2016 New Issue Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation

More information

Effective March 2015 Supersedes S August 2012

Effective March 2015 Supersedes S August 2012 Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions

More information

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors Catalog Data CA650063EN Supersedes 500-10-7C November 2011 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

600 A 35 kv class BT-TAP deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal Loadbreak Connectors Catalog Data CA650062EN Supersedes June 2015 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class T-OP II deadbreak connector Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,

More information

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connector CA650099EN Supersedes 500-28-7C November 2011 COOPER POWER SERIES 200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition General Eaton

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Effective May 2017 Supersedes December 2004 (S )

Effective May 2017 Supersedes December 2004 (S ) Reclosers MN280054EN Effective May 2017 Supersedes December 2004 (S280-15-10) COOPER POWER Types L, V4L, E, 4E, and V4E; KA785L10S, KA785L20S, KA785L30S, and KA785L40S Automation upgrade kit installation

More information

600 A 25 kv class BT-TAP deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector Deadbreak Connectors Catalog Data CA650001EN Supersedes January 2015 600 A 25 kv class BT-TAP deadbreak connector COOPER POWER SERIES General Eaton terminates high-voltage underground cable to transformers,

More information

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers. Reclosers CT Field Modification Kit KA906R1 Installation and Testing Instructions Service Information S280-80-13 This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers. Not

More information

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

3M Mechanical Shearbolt Connectors, QCI Series

3M Mechanical Shearbolt Connectors, QCI Series M Mechanical Shearbolt Connectors, QCI Series Data Sheet November 2011 Description Connector Contents M Mechanical Shearbolt Connectors, QCI Series are designed to cover a wide range of conductor sizes

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition Loadbreak Connectors CA650101EN Supersedes 500-29-7C November 2011 COOPER POWER SERIES 200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

More information

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot. Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling

More information

Installation Instruction EPP /92

Installation Instruction EPP /92 E L E C T R I C A L P R O D U C T S. D I V I S I O N Installation Instruction EPP 0275 8/92 Terminations for Screened Single Core Plastic and Rubber Insulated Cables 7.2 kv to 36 kv without Armour Before

More information

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation

More information

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN Reclosers MN280070EN Effective May 2017 Supersedes July 2014 (S280-80-23) COOPER POWER Dielectric grease application to recloser cable instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S ) Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The

More information

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series 3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series Data Sheet March 2011 Description 3M Cold Shrink 1/C Transition Splice Kits QS-III, 5510A-1T-PILC Series (which includes 5513A-1T-PILC,

More information

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.) Molded Rub ber Products 600 A 35 kv Class Separable Splices Electrical Ap pa ra tus 700-31 General Cooper Power Systems 600 A, 35 kv Class Deadbreak Separable Splices are used to splice two, three or four

More information

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination

Instructions. Quick Term II 2047MT 74. Quick Term II. Silicone Rubber Termination Instructions Quick Term II Silicone Rubber Termination IEEE Std. No. 48 1990 Class 1 Termination 46 kv Class 250 kv BIL ÁÁ ÁÁ Kit Contents 1 High-K, 8 Skirted Silicone Rubber Termination 1 4 Skirt Silicone

More information

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2

More information

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts Deadbreak Connectors Catalog Data CA650007EN Supersedes March 2015 COOPER POWER SERIES 600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts General Eaton connects and assembles

More information

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage. Voltage Regulators QD8 Movable Contact Board Replacement Procedure Kit 5742895B01 Service Information S225-50-38 Contents General..................................... 1 Parts Supplied...............................

More information

High Voltage Joints and Terminations up to 72,5 kv 145 kv

High Voltage Joints and Terminations up to 72,5 kv 145 kv High Voltage Joints and Terminations up to 72,5 kv 145 kv 3M Cold Shrink Termination Kits QT-III and Joint Kits are designed to provide high reliability and save you time and money. They install quickly

More information

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief)

Instructions. Quick Term II 2047MT 56. 3M Quick Term II. Silicone Rubber Termination (with High-K Stress Relief) Instructions Quick Term II Silicone Rubber Termination (with High-K Stress Relief) IEEE Std. No. 48 990 Class Termination 5 kv Class 50 kv BIL Kit Contents Hi K Silicone Rubber Termination Scotch 70 Silicone

More information

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable 3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable Data Sheet September 2010 Description 3M Cold Shrink 3-Conductor

More information

600 A 35 kv class separable splices

600 A 35 kv class separable splices Splices Catalog Data CA650050EN Supersedes 700-31 March 2009 COOPER POWER SERIES General Eaton s Cooper Power series 600 A, 35 kv Class deadbreak separable splices are used to splice two, three or four

More information

Installation instruction PEM1150ENG

Installation instruction PEM1150ENG Installation instruction PEM1150ENG 2008-08 USHJ630 SCREENED SEPARABLE BACK CONNECTOR 630 A FOR 1 CORE PLASTIC CABLES 12-24 kv ENGLISH 2/8 USHJ630 PEM1150ENG 2008-08 GENERAL INFORMAT ION - Check that the

More information

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A 3M Cold Shrink QS-III Inline Splice Kits 15 kv Data Sheet June 2014! CAUTION Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

C Power Connection Kit

C Power Connection Kit 1548-4000C Power Connection Kit For use with Dekoron 2700 Family of Heating Cables Installation Instructions Kit Description The Dekoron 1548-4000C electrical connection kit distirbuted by Heat-Line is

More information

Installation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour

Installation Instruction EPP /02. Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour R Installation Instruction EPP-0778-11/02 Terminations for Screened Single Core Polymeric Insulated Cables up to 24 kv without Armour Type: IXSU-F / OXSU-F Tyco Electronics Raychem GmbH Energy Division

More information

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Voltage Regulators QD3/T350 Main Movable Contact Assembly Kit Kit 5741325B04 Service Information S225-50-42 Contents General..................................... 1 Tools Required..............................

More information

Effective May 2017 Supersedes January 2003 (S )

Effective May 2017 Supersedes January 2003 (S ) Reclosers MN280068EN Effective May 2017 Supersedes January 2003 (S280-80-13) CT field modification kit KA906R1 installation and testing instructions COOPER POWER This kit is for use with types RE, RVE,

More information