SECTION 8 SAMPLE EXAMPLE
|
|
- Barbra Johnson
- 6 years ago
- Views:
Transcription
1 SECTON 8 SMPLE EXMPLE PROBLEM #1: hospital facility in California is located in Seismic Zone 4, 5 km from a Seismic Source Type. The soil prile in the region is Type S D. The hospital building is a 6-story, steel framed structure with floor construction consisting 3½ 3000 psi Normal Weight Concrete on 3 20ga composite decking and anchorage will be made with expansion anchors that satisfy the 8:1 embedment to diameter ratio. Equipment items at the top 1/3 the building are to be investigated for seismic anchorage. nchorage a 4 dia. uninsulated Sch. 40 water filled pipe will be investigated. Design Procedure: Complete STEPS in SECTONS 1 through 7. Obtain factors required to generate seismic forces (these are independent the component being anchored). SECTON 1 - REVEW SESMC BRCNG REQUREMENTS ND CRTER to determine if bracing is required. SECTON 2 - DETERMNTON %g Step 1 - Per SEOR: Zone 4 Soil Prile Type S D Seismic Source Type 5 km from Seismic Source Steps 2 & 3 - Refer to Table 2-3 (pg. 2-3 Manual) to determine %g Building mportance Factor = 1.5 Pipe is not vibration isolated ap = Per Rp = 3.0 STEP 3 Pipe is near ro level therefore top 1/3 building Per Table 2-3: Soil Prile = S D C a =.44 N a =.44 x 1.2 =.53 Seismic Source Type = 5 km from Seismic Source %g = 6 ap = Rp = Top 1/3 building Step 4 - Go to SECTON 3. NOTE: This SMPLE EXMPLE is followed by a Sample Submittal. s the user proceeds through this SMPLE EXMPLE, a number in a box like this directs the user to a SMPLE SUBMTTL page marked by a box with the same number. The Sample Submittal Form is marked with 1 Box 1 and should be filled in as each Section is completed. Begin filling in the Submittal Form (Box 1), back circle the applicable information on Section 1 & 2 pages (Boxes 2 & 3), and insert the applicable Section s (Boxes 1, 2 & 3) into the Submittal Package. 2 P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-1
2 SECTON 8 SMPLE PROBLEM 4-Way Sway Brace (Typ.) (Transverse & Longitudinal at same location) 2-Way Sway Brace 4 Uninsulated Sch. 40 Water Pipe 40 ft. max. 40 max. B. Determine nchorage for specific components. nvestigate the anchorage required for 4 dia. uninsulated Sch. 40 water filled pipe. SECTON 3 - DETERMNTON HORZONTL ERTHQUKE LOD & BRCE SZE Step 1 - %g = 6 Tables are provided in various increments, therefore use the next highest %g Table. (Use %g = 1.25) Per the ndex on 3-2, the Earthquake Load / Brace Size Table for Uninsulated Sch. 40 Pipe (Water Filled) at 1.25 %g is on Step 2 - Locate the row for 4 pipe in the first column Table Step 3 - Scan across the row to find the Horizontal Earthquake Load (Fps) and Brace Size for the applicable brace spacing at a 30 o angle from vertical. 40 spacing Fps = 590 lbs Brace Size = spacing Fps = 1180 lbs Brace Size = 36 4 Back circle the applicable information on the Section 3 page (Box 4), and insert the applicable Section 3 into the Submittal Package. Step 4 - Go to SECTON 4. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-2
3 SECTON 8 SMPLE PROBLEM SECTON 4 - SELECTON BRCE SSEMBLY W/ NCHORGE Step 1 - Find the Brace Selection Table in SECTON 4 corresponding to the type structure the anchorage will be attached to. (ttachment will be made to the underside a floor system consisting 3 1/2" concrete on 3 metal decking. Concrete is 3000 psi Normal Weight and expansion anchors will be used.) Brace Selection Table for 3000 psi, NW concrete on 4-7 is selected. Step 2 - n the table on 4-7, find column heading for anchorage orientation / loading condition that applies. Refer to the headings on 4-4 to determine which column to use. ttachment will be made to underside slab, therefore the values in the middle columns will be used (Orientation #2). Step 3 - Steps 4,5 - Locate the column values for a 30 o angle from vertical. Scan down the column to find an anchorage method with a Horizontal Load capacity that exceeds that which was determined in SECTON 40' Transverse Spacing (1) 5/8 4 embed: 727# llowable > 590# Fps (Section 3) Brace size 80' Longitudinal Spacing (2) 5/8" 4" embed: 1333# llowable > 1180# Fps (Section 3) Brace size - 36 NOTE: The 2001 CBC requires that Rp = 1.5 when shallow concrete anchors are used. Shallow anchors have less than 8:1 ratio anchor embedment to diameter. f a shallow concrete anchor from the Table must be used to satisfy the load requirement at this stage, it will be necessary to return to Section 2 to re-select the %g according to the ap/rp and then repeat the Steps in Sections 3 & 4 for the higher load requirements. f a concrete anchor satisfying the 8:1 ratio is not available, more cost effective solution would be returning to Section 3, selecting a shorter brace spacing, which would result in lower loads, and repeating the Steps in Section 4 with the selection anchors that maintain the 8:1 ratio. See continuation this example on 8-4 for embedment and P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-3
4 SECTON 8 SMPLE PROBLEM Steps 4, ft. Spacing For the 5/8" HKWB, a 5" embedment is needed to satisfy the 8:1 ratio or the load must be increased by changing to ap = / Rp = 1.5 per Note 2 in Section 2 and the Steps in SECTONS 2, 3 & 4 repeated. However, a 5" embedment can be achieved with this floor system. Therefore, use a 5/8 HKWB at 5" embedment. The 8:1 ratio is now satisfied. Per table on 4-7: 5/8 5" embed: 775 lbs llowable > 590 lbs Fps (Section 3) NOTE: depth, (2) 3/8 anchors utilizing the Sling ssembly on 7-10 could be used. This would require a 3 embedment to maintain the 8:1 ratio and the allowable load carrying capacity would be ft. Spacing For the 5/8" HKWB, a 5" embedment is again needed to satisfy the 8:1 ratio or the load must be increased by changing to ap = / Rp = 1.5 per Note 2 in Section 2 and the Steps in SECTONS 2, 3 & 4 repeated. However, a 5" embedment can be achieved with this floor system. The 8:1 ratio is now satisfied. Per table on 4-7: (2) 5/8 5" embed: 1333 lbs llowable > 1180 lbs Fps (Section 3) NOTE: f there is no anchorage in the Section 4 Table that can satisfy the Fps from Section 3, return to Section 3 and reduce brace spacing and/or increase the brace angle to reduce the Fps to achievable loads in the Section 4 Tables. 5 5 Back circle the applicable information on the Section 4 page (Box 5), and insert the applicable Section 4 into the Submittal Package. Steps 6 - Go on to SECTON 5. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-4
5 SECTON 8 SMPLE PROBLEM SECTON 5 - DETERMNTON ROD STFFENER REQUREMENT Step 1 - Step The hanger rod size is assumed as 5/8 dia. and, based on available ceiling space, the maximum length hanger rod is assumed as 36 long. RS1 rod stiffeners are required in accordance with the RS Rod Stiffener Detail and spaced in accordance with Table 5-2. For a brace spacing 40 ft. in the Transverse direction and 80 ft. in the Longitudinal direction, the Horizontal Load (Fps) per Section 3 is 590 lbs. for the Transverse Brace and 1180 lbs. for the Longitudinal Brace. Referring to Table 5-2 for 30 o brace angle from vertical and for 5/8 dia. hanger rod, a rod stiffener with a RS1 clip spacing 36 o.c. maximum (max. Fps = 638 lbs.) will be adequate for the Transverse Brace. RS1 clip spacing 18 o.c. maximum (max. Fps = 1889 lbs.) will be adequate for the Longitudinal Brace. Back circle the applicable information on the Section 5 pages (Boxes 6, 7 & 8), and insert the applicable Section 5 into the Submittal Package. Steps 6 - Go on to SECTON 6. SECTON 6 - LOCTONS FOR SESMC SWY BRCE NSTLLTON Step 1 - Step 2 - Locate Transverse braces at Max. 40 ft. spacing and at changes direction. Locate Longitudinal braces at Max. 80 ft. spacing and at changes direction. nsert spacing information on the Section 6 pages (Box 9), and insert this into the Submittal Package. 9 Steps 3 - Go on to SECTON 7. SECTON 7 - SWY BRCE COMPONENTS, NSTLLTON NSTRUCTONS ND DETLS Step 1 - nstall braces at Transverse Brace locations per the Transverse Sway Brace Detail for Un-insulated Pipe & Conduit on 7-11 and at Longitudinal Brace locations per the Longitudinal Sway Brace Detail for Un-insulated Pipe & Conduit on 7-12, using the Loos & Co., nc. components, tools and installation instructions on s 7-2 through nsert the applicable Details from Section 7 s (Boxes 10,11,12 into the Submittal Package. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-5
6 SECTON 8 SMPLE EXMPLE PROBLEM # 2: Many projects in California utilize 3¼ Lightweight concrete on 3 x 20ga metal deck. Since this construction is common, this Manual has incorporated Quick Select tables in Section 3 (Tables 3-2a to 3-2q) to allow the user to quickly determine an adequate brace size, spacing and anchorage for the component in question. To illustrate refer to the Sample Example on 8-1 and use the Quick Select Tables to determine the necessary bracing requirements. The only difference is that the construction is 3¼ Lt. Wt. Concrete on 3 x 20ga metal deck. nchorage will be made with expansion anchors that can maintian an 8:1 ratio embedment. Design Procedure: Complete STEPS in SECTONS 1 through 7. Obtain factors required to generate seismic forces (these are independent the component being anchored). SECTON 1 - REVEW SESMC BRCNG REQUREMENTS ND CRTER to determine if bracing is required. SECTON 2 - DETERMNTON %g Step 1 - Per SEOR: Zone 4 Soil Prile Type S D Seismic Source Type 5 km from Seismic Source Steps 2,3,4 - Refer to Table 2-3 (pg. 2-3 Manual) to determine %g Building mportance Factor = 1.5 Pipe is not vibration isolated ap = Per Rp = 3.0 STEP 3 Pipe is near ro level therefore top 1/3 building 2 Per Table 2-3: Soil Prile = S D C a =.44 N a =.44 x 1.2 =.53 Seismic Source Type = 5 km from Seismic Source %g = 6 ap = Rp = 3.0 Top 1/3 building 3 Begin filling in the Submittal Form (Box 1), back circle the applicable information on Section 1 & 2 pages (Boxes 2 & 3), and insert the applicable Section s (Boxes 1, 2 & 3) into the Submittal Package. Step 5 - Go to SECTON 3. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-6 5/15/04
7 SECTON 8 SMPLE PROBLEM 4-Way Sway Brace (Typ.) (Transverse & Longitudinal at same lacation) 2-Way Sway Brace 4 Uninsulated Sch. 40 Water Pipe 40 ft. max. 40 max. B. Determine nchorage for specific components. nvestigate the anchorage required for 4 dia. uninsulated Sch. 40 water filled pipe. SECTON 3 - DETERMNTON HORZONTL ERTHQUKE LOD & BRCE SZE Step 1 - %g = 6 Tables are provided in various increments, therefore use the next highest %g Table. (Use %g = 1.25) Per the ndex on 3-2, the Quick Select Earthquake Load / Brace Size / %g is on 3-2e. Step 2 - Locate the row for 4 pipe in the first column Table 3-2e. Step 3 - Step 4 - Scan across the row to find the Horizontal Earthquake Load (Fps) and Brace Size for the applicable brace spacing at a 30 o angle from vertical. Transverse Brace 40 spacing Fps = 661 lbs 4a Brace Size = 36 nchorage per Note Below Table = Double 5/8 Kwik Bolt Longitudinal Brace 80 spacing Fps = 1321 lbs Brace Size for 30 o at 80 ft. spacing is un-achievable. increased. We have the option reducing brace spacing to 50 o.c. using a brace angle 30 o or brace spacing to 80 o.c. using brace angle 45 o. For this example, use 50 spacing at 30 o brace angle. 40 spacing Fps = 826 lbs Brace Size = 36 nchorage per Note Below Table = Double 5/8 Kwik Bolt Back circle the applicable information on the Section 3 page (Box 4a), Section 4 4-3, Section 5, 6 & 7 pages (Boxes 6-12), and insert the applicable Section 3 through 7 s into the Submittal Package. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 8-7
8 OSHPD PRE-PPROVED SESMC SWY BRCNG SUBMTTL FORM CBLEWRE DVSON NDUSTRL BLVD. NPLES, FL FX : Pre-Stretched, Color Coded, Break Strength Certified Project Name: ddress: City, State: Contractor Name: ddress: City, State: Submittal Prepared by: Date: Phone: ( ) GENERL NCHORGE CRTER nchorage for: Per Record (SEOR) Seismic Zone Soil Prile. Elevation: Seismic Source Type - Distance Structure: C a nchorage these components will be per Loos & Co., nc. OSHPD Pre-pproved Package OP (See attached applicable Tables and Details) SECTON 1 ap = Rp = SECTON 2 Table %g = SECTON 3 Table Transverse Longitudinal Max. Brace Spacing: Min. Brace ngle: Fps (Service): Brace Size: SECTON 5 Table Hanger Rod: Dia. Max. Length (in) Rods Exceed Max. Un-Stiffened Rod Criteria: Stiffener Required for Rods Exceding Maximum Un-Stiffened Rod Criteria. Transverse Longitudinal Min. Brace ngle: Max. Clip Spacing: Max. Fps : SECTON 4 Table Structure: _ Fastener Orientation: Required nchorage: Transverse Longitudinal Fastener Qty.: Fastener Type: Fastener Dia.: Embedment: Fastener Capacity (lbs): SECTON 6 SECTON 7 (See ttached Details) (See ttached Details) NOTE: Copies the Pre-pproval details (this submittal) must be on the job prior to starting the installation the component or system.
9 OSHPD PRE-PPROVED SESMC SWY BRCNG SUBMTTL FORM 1 CBLEWRE DVSON Pre-Stretched, Color Coded, Break Strength Certified Project Name: 901 NDUSTRL BLVD. NPLES, FL FX : Contractor Name: ddress: City, State: ddress: City, State: Submittal Prepared by: Date: Phone: ( ) GENERL NCHORGE CRTER nchorage for: Per Record (SEOR) Seismic Zone Soil Prile. Elevation: Seismic Source Type - Distance Structure: C a nchorage these components will be per Loos & Co., nc. OSHPD Pre-pproved Package OP (See attached applicable Tables and Details) SECTON 1 ap = Rp = SECTON 2 Table %g = SECTON 3 Table Transverse Longitudinal Max. Brace Spacing: Min. Brace ngle: Fps (Service): Brace Size: SECTON 5 Table Hanger Rod: Dia. Max. Length (in) Rods Exceed Max. Un-Stiffened Rod Criteria: Stiffener Required for Rods Exceeding Maximum Un-Stiffened Rod Criteria. Min. Brace ngle: Max. Clip Spacing: Max. Fps : SECTON 4 Table Structure: Fastener Orientation: Required nchorage: Transverse Longitudinal Fastener Qty : Fastener Type: Fastener Dia.: Embedment: Fastener Capacity (lbs): SECTON 6 SECTON 7 (See ttached Details) (See ttached Details) NOTE: Copies the Pre-pproval details (this submittal) must be on the job prior to starting the installation the component or system.
10 SECTON 2 DETERMNTON %g 2 1. SECTON 2 - DETERMNTON %g TO BE USED N HORZONTL ERTHQUKE LOD REQUREMENT FOR BRCED COMPONENT. STEP 1 - Obtain the seismic factors necessary to determine the %g from the Record, which should be on the contract documents. NOTE: f the contract documents indicate the %g to be used, go directly to SECTON 3. f the Record (SEOR) has given the value C a, go directly to STEP 2 this SECTON. The seismic factors required to determine the value C a are : Seismic Zone 3 a. Soil Prile; S, S B, S C, S D, S E or S F Seismic Zone 4 a. Soil Prile; S, S B, S C, S D, S E or S F b. Seismic Source Type (Zone 4 only);, B or C c. Near Source Factor (Zone 4 only); N a STEP 2 - Tables are provided on page 2-2, 2-3 & 2-4 for determining the %g to be used. The Tables for Zone 3 are found on 2-2. The Tables for Zone 4 are found on 2-3 or 2-4. Find the Table for the applicable Seismic Zone and use the portion the Table under the heading for the applicable Note below. Note 1: ap =, Rp = 3.0 Non-vibration isolated equipment braced above center gravity, pipes, ducts & conduit and anchored to steel, wood or concrete w/ concrete anchors maintaining embedment ratio 8:1. Note 2: ap =, Rp = 1.5 Non-vibration isolated equipment braced above center gravity, pipes, ducts & conduit and anchored to concrete w/ shallow concrete anchors. Note 3: ap = 2.5, Rp = 3.0 Non-vibration isolated equipment braced below center gravity, pipes, ducts & conduit and anchored to steel, wood or concrete w/ concrete anchors maintaining embedment ratio 8:1. Note 4: ap = 2.5, Rp = 1.5. Non-vibration isolated equipment braced below center gravity, pipes, ducts & conduit and anchored to concrete w/ shallow concrete anchors. Equipment that is Vibration solated and anchored to steel, wood or concrete w/ concrete anchors, other than expansion anchors, maintaining embedment ratio 8:1. Note 5: ap = 1.3, Rp = 3.0 Emergency power supply, essential communications equipment, battery racks, fuel tanks and components with non-ductile material (cast iron, no-hub and plastic pipe) and anchored to steel, wood or concrete w/ concrete anchors maintaining embedment ratio 8:1. Note 6: ap = 1.3, Rp = 1.5 Emergency power supply, essential communications equipment, battery racks, fuel tanks and components with non-ductile material (cast iron, no-hub and plastic pipe) and anchored to concrete w/ shallow concrete anchors. Note 7: ap = 2.5, Rp = 1.5 Equipment that is Vibration solated and anchored to steel, wood or concrete w/ shallow or expansion anchors. (Table includes 1.3 increase Fp formulas per 2001 CBC Table 16-O footnote 14.) STEP 4 - Under the subheading indicating the vertical portion the building to which the braced component is anchored (Bottom 1/3., Middle 1/3. or Top 1/3.), find the %g value in the row for the applicable C a value based on the Seismic factors or provided by the SEOR. STEP 5 - Go to Section 3 and select the seismic load/brace size for the %g and type component being braced. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 2-1
11 SESMC ZONE 4 %g TBLE 2-3 See example page 2-4a 3 SOL PRLE S S B S C S D S E S F Ca FORMUL.32N a.40n a.40n a.44n a.36n a Occupancy Category Component/Equipment mportance Factor p = 1.5 SESMC SOURECE TYPE B C B C B C B C B C Near Source Factor DSTNCE TO NEREST SESMC SOURCE < 2 km 5 km > 10 km < 2 km > 2 km ny Distance < 2 km 5 km > 10 km < 2 km > 2 km ny Distance < 2 km 5 km > 10 km < 2 km > 2 km ny Distance < 2 km 5 km > 10 km < 2 km > 2 km ny Distance < 2 km 5 km > 10 km < 2 km > 2 km ny Distance N a Ca CTUL Note 1 (pg 2-1) Note 2 (pg 2-1) Note 3 (pg 2-1) Note 4 (pg 2-1) ap = Rp = 3.0 ap = Rp = 1.5 ap = 2.5 Rp = 3.0 ap = 2.5 Rp = 1.5 Bot 1/ Mid 1/ Top 1/ Soil condition not suitable for most construction. Consult Record. Bot 1/ Mid 1/ Top 1/ Bot 1/ Mid 2/ Top 1/ Top 1/ Mid 1/ Top 1/ P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 2-3
12 SECTON 3 DETERMNTON ERTHQUKE LOD & BRCE SZE 4 UNNSULTED SCH. 40 STEEL PPE - WTER FLLED HORZONTL ERTHQUKE LOD (Fps in lbs. ) and BRCE SZE Nominal Water BSED ON HORZONTL LOD FCTOR (%g ) 1.25 Pipe Filled CCORDNG TO BRCE SPCNG and BRCE NGLE FROM VERTCL Table 3-39 Size Weight 10 ft. Spacing 20 ft. Spacing 30 ft. Spacing 40 ft. Spacing 50 ft. Spacing 60 ft. Spacing 70 ft. Spacing 80 ft. Spacing ( in. ) ( lbs./f t. ) Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) / / / / / / / X X X X X X X X X X X X X X X X X 5299 X X X X X X X X X X X 5305 X X X X 6189 X X X X 7074 X X X X X X X X X X X X 6149 X X X X 7174 X X X X 8199 X X X X X X X X X X X X 6348 X X X X 7617 X X X X 8887 X X X X X X X X X X X X X 6154 X X X X 7693 X X X X 9231 X X X X X X X X X X X X X X X X X X 7328 X X X X 9160 X X X X X X X X X X X X X X X X X X X X X 7475 X X X X 9966 X X X X X X X X X X X X X X X X X X X X P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 3-39
13 SECTON 3 DETERMNTON ERTHQUKE LOD & BRCE SZE 4a Table 3-2e QUCK SELECT TBLE FOR LL TYPES PPE HORZONTL LOD (Fps) w/ BRCE SZE/NCHORGE BSED ON HORZONTL LOD FCTOR (%g ) 1.25 CCORDNG TO BRCE SPCNG and BRCE NGLE FROM VERTCL Nominal Water for nchorage in Pipe Filled 3 1/4 " 3000 psi SND-LGHTWEGHT Concrete on 3" METL DECK ( w/ 8:1 Embedment Ratio ) Size* Weight 10 ft. Spacing 20 ft. Spacing 30 ft. Spacing 40 ft. Spacing 50 ft. Spacing 60 ft. Spacing 70 ft. Spacing 80 ft. Spacing ( in ) ( lbs/f t ) Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Horiz. Brace Size Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle Load By ngle ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) ( lbs. ) X X X X X X X X X X X X X X X X X X X X 3506 X X X X 4007 X X X X X X X X X X X 3741 X X X X 4489 X X X X 5238 X X X X 5986 X X X X X X X X X X 4029 X X X X 5036 X X X X 6043 X X X X 7050 X X X X 8057 X X X X X X X X X X 4099 X X X X 5124 X X X X 6149 X X X X 7174 X X X X 8199 X X X X X X X X X 4468 X X X X 5957 X X X X 7446 X X X X 8936 X X X X X X X X X X X X X X X X X X X 5078 X X X X 6348 X X X X 7617 X X X X 8887 X X X X X X X X X X X X X 4616 X X X X 6154 X X X X 7693 X X X X 9231 X X X X X X X X X X X X X X X X X 5496 X X X X 7328 X X X X 9160 X X X X X X X X X X X X X X X X X X X X X X X 7475 X X X X 9966 X X X X X X X X X X X X X X X X X X X X NOTES: in the Table above indicates a Size 12 brace with a SNGLE 1/2 dia. x 5½ long (4 embedment) Hilti Kwik Bolt- anchor in the Table above indicates a Size 18 brace with a SNGLE 5/8 dia. x 6 long (5 embedment) Hilti Kwik Bolt- anchor in the Table above indicates a Size 36 brace with a DOUBLE 5/8 dia. x 6 long (5 embedment) Hilti Kwik Bolt- anchor. (Use Cable Load Doubler Sling ssembly on 7-10 for Double anchor.) 4. Refer to Table 4-3 in Section 4 for description Orientation # 2 the anchor and allowable horizontal loads. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 3-2e
14 SECTON 4 nchorage in 3000 psi NORML WEGHT Concrete 5 NOTE: When 2 fasteners are required, use the Cable Load Doubler Sling ssemby shown on P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 4-7
15 SECTON 5 DETERMNTON ROD STFFENER REQUREMENT 1. SECTON 5 - DETERMNTON ROD STFFENER REQUREMENT 6 STEP 1 - Provide a rod stiffener on the hanger rod nearest the seismic sway brace in accordance with the RS1 Detail below with installation instructions on 5-3 and go on to SECTON 6. NOTE: rod stiffener is not required, if the length hanger rod itself and the applied horizontal load do not exceed the Rod Stiffener Clip Spacing and associated llowable Horizontal Load shown in Table 5-1 or 5-2. For Example: f the brace angle from vertical is 45 o and the horizontal seismic load does not exceed 1,465 lbs., a ½ dia. rod that does not exceed 18 in length would not require a rod stiffener. HNGER ROD SWY BRCE 1 Sch. 10 or 40 pipe Rod Stiffener RS1 ROD STFFENER CLPS SWY BRCE B STRUCTURE B Braced Pipe or Other Component RS1 ROD STFFENER DETL RS1 ROD STFFENER The Detail to above depicts the installation a pipe type rod stiffener using RS1 Rod Stiffener Clips, which must be located and spaced as shown on this detail and installed in accordance with the details on 5-3. The Maximum Dimension is 3. See Table 5-1 and Table 5-2 for the Maximum B Dimension, which varies according to the Maximum llowable Horizontal Load (Fps from Section 3). NOTE: The llowable Fps values in Table 5-1 and Table 5-2 are based on hanger rods meeting the material strength requirements STM 36. TBLE 5-1 MX. LLOWBLE HORZONTL LOD (Fps from Section 3 in lbs.) on rods at length satisfying kl/r =200 between clips BRCE NGLE 3/8 x 24 ROD 1/2 x 33 ROD 5/8 x 41 ROD 3/4 x 50 ROD 7/8 x 59 1 x 68 FROM MX. LENGTH MX. LENGTH MX. LENGTH MX. LENGTH MX. LENGTH MX. LENGTH VERTCL 30 o - 44 o 128 lbs. 314 lbs. 504 lbs. 747 lbs lbs lbs. 45 o - 59 o 199 lbs. 487 lbs. 781 lbs lbs lbs lbs. 60 o - 90 o 387 lbs. 712 lbs lbs lbs lbs lbs. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf /3/05
16 TBLE 5-2 MXMUM LLOWBLE HORZONTL FORCE (Fps from Section 3 )for THREDED HNGER RODS WTH RS1 ROD STFFENERS CCORDNG TO RS CLP SPCNG MXMUM Fps (lbs.) CCORDNG TO HNGER ROD D. (in.) 3/8 1/2 5/8 3/4 7/8 1 BRCE NGLE FROM VERTCL 30 o - 44 o 45 o - 59 o 60 o - 90 o SECTON 5 DETERMNTON ROD STFFENER REQUREMENT MXMUM RS1 ROD STFFENER SPCNG B DMENSON , ,879 1, ,615 1, ,502 2,068 1, ,664 3,028 2,196 1, NOTE: The Tabulated Values in Table 5-1 and 5-2 do not account for the weight the braced component (Wp) in fsetting the vertical compression force on the hanger rod. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike ,667 2,346 1,936 1, ,131 3,635 2,999 2,229 1,458 1,013 6,048 5,321 4,391 3,263 2,135 1,483 4,050 3,688 3,232 2,688 2,055 1,442 1, ,273 5,713 5,006 4,164 3,183 2,233 1,641 1,256 9,185 8,365 7,329 6,096 4,660 3,270 2,402 1,839 5,685 5,287 4,789 4,202 3,520 2,763 2,041 1,562 1,234 8,807 8,190 7,419 6,509 5,466 4,281 3,161 2,420 1,912 12,894 11,991 10,862 9,530 8,003 6,268 4,628 3,543 2,800 7,517 7,085 6,549 5,921 5,206 4,405 3,509 2,692 2,127 1,723 1,424 11,645 10,974 10,145 9,172 8,065 6,823 5,436 4,170 3,295 2,669 2,206 17,049 16,068 14,853 13,429 11,808 9,990 7,959 6,105 4,824 3, , NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 5-2
17 SECTON 5 RS1 ROD STFFENER CLP NSTLLTON DETLS 8 Rod Stiffener Pipe Hanger Rod RS1 PLN VEW Rod Stiffener Pipe Hanger Rod PLN VEW RS1 ELEVTON STEP 1: Position the RS1 against the rod stiffener pipe opposite the hanger rod. ELEVTON STEP 2: Snap the RS1 over the rod stiffener pipe. PLN VEW PLN VEW ELEVTON STEP 3: nsert the RS1 bolt with flat washers and lock nut through the holes in the RS1 that correspond to the hanger rod diameter. ELEVTON STEP 4: Tighten the locknut until the two ends the RS1 close as shown. P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf /3/05
18 SECTON 6 LOCTONS FOR SESMC SWY BRCE NSTLLTON 9 1. SECTON 5 - LOCTONS FOR SWY BRCE NSTLLTON STEP 1 - f the component being braced is piece equipment suspended by hangers at each its 4 corners (VV Box, HU, transformer, etc.), locate one seismic sway brace cable assembly (selected in SECTON 4) at the point connection each hanger rod at each the 4 corners the equipment. Go to Details on 7-22 or 7-23 in SECTON 7. STEP 2 - f the component being braced is piece equipment suspended by hangers at both ends (inline pumps, etc.), locate two seismic sway brace cable assemblies (selected in SECTON 4) at the point connection both hanger rods at both ends the equipment. Go to Detail on 7-24 in SECTON 7. STEP 3 - Each run braced piping, conduit, ducts, cable trays, etc., between changes in direction greater than 5 ft., shall be provided with a minimum two transverse braces and one longitudinal. n addition transverse and longitudinal bracing shall be provided at intervals not exceeding the maximum spacing limitation established in SECTON 3. Go to applicable Details in SECTON 7. NOTE: Sections piping, conduit, ducts, cable trays, etc. that are less than 5 ft. in length between changes direction, are not required to have this additional bracing. Transverse and longitudinal bracing for one run piping, conduit, ducts, cable trays, etc. may also act as transverse and longitudinal bracing for adjacent runs at 90 o changes direction, if the brace is located within 24 the change in direction. t vertical fsets, locate a transverse and a longitudinal brace on both the high and low sides the vertical fset as shown below. S = MXMUM BRCE SPCNG DETERMNED N SECTON 3 STEP 3 NOTE S S S 1/3 S 1/3 S MX. MX. STRGHT RUNS HORZONTL FSETS STEP 3 NOTE = TRNSVERSE SWY BRCE 2-Way Brace (Model or B) = LONGTUDNL SWY BRCE VERTCL FSETS 2-Way Brace (Model or B) = 4-WY (TRNSVERSE & LONGTUDNL) SWY BRCE (Model C) EXMPLE RECOMMENDED SWY BRCE LOCTONS P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf 6-1
19 SECTON 7 DETLS BRCED COMPONENTS 10 SESMC WRE ROPE/CBLE TM SSEMBLES FOR BRCES NOTES: 1. nstall cable assemblies with a minimum angle the cable from the vertical plane per Section 3 & 4 Selection Tables. Hanger Rod w/ Rod Stiffener per Section 5 2. nchorage the cable assemblies to the structure to be per Section 3 & 4 Selection Tables. 3. Tighten cables to be in a straight line after installation without lifting the braced component. 4. fter tightening cables to be in a straight line on vibration isolated components, loosen each cable 1/4 at oval sleeves before crimping. Cable ssembly to Structure per Sections 3 & 4 (Typ.) PLN VEW Uninsulated Pipe or Conduit djustable Clevis Hanger Hanger Rod w/ Hanger Rod w/ Rod Stiffener 6 max. Rod Stiffener per Section 5 per Section 5 Cable ssembly to Structure per Sections 3 & 4 (Typ.) djustable Clevis Hanger END VEW Cable Connection to Component per Detail on 7-4 Uninsulated Pipe or Conduit SDE VEW TRNSVERSE SWY BRCE DETL FOR UN-NSULTED PPE & CONDUT Uninsulated Pipe or Conduit P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf /3/05
20 SECTON 7 DETLS BRCED COMPONENTS 11 SESMC WRE ROPE/CBLE TM SSEMBLES FOR BRCES NOTES: 1. nstall cable assemblies with a minimum angle the cable from the vertical plane per Section 3 & 4 Selection Tables. Hanger Rod w/ Rod Stiffener per Section 5 2. nchorage the cable assemblies to the structure to be per Section 3 & 4 Selection Tables. 3. Tighten cables to be in a straight line after installation without lifting the braced component. 4. fter tightening cables to be in a straight line on vibration isolated components, loosen each cable 1/4 at oval sleeves before crimping. Cable ssembly to Structure per Sections 3 & 4 (Typ.) PLN VEW Uninsulated Pipe or Conduit Cable ssembly Hanger Rod w/ to Structure per Rod Stiffener Sections 3 & 4 6 max. per Section 5 (Typ.) djustable Clevis Hanger Hanger Rod w/ Rod Stiffener per Section 5 Cable Connection to Component per Detail B on 7-4 djustable Clevis Hanger END VEW Uninsulated Pipe or Conduit SDE VEW LONGTUDNL SWY BRCE DETL FOR UN-NSULTED PPE & CONDUT Uninsulated Pipe or Conduit P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf /3/05
21 SECTON 7 DETLS BRCED COMPONENTS 12 SESMC WRE ROPE/CBLE TM SSEMBLES FOR BRCES NOTES: 1. nstall cable assemblies with a minimum angle the cable from the vertical plane per Section 3 & 4 Selection Tables. 2. nchorage the cable assemblies to the structure to be per Section 3 & 4 Selection Tables. 3. Tighten cables to be in a straight line after installation without lifting the braced component. 4. fter tightening cables to be in a straight line on vibration isolated components, loosen each cable 1/4 at oval sleeves before crimping. Cable ssembly to Structure per Sections 3 & 4 (Typ.) PLN VEW Hanger Rod w/ Rod Stiffener per Section 5 Uninsulated Pipe or Conduit djustable Clevis Hanger Hanger Rod w Hanger Rod w/ Rod Stiffener 6 max. Rod Stiffener per Section 5 per Section 5 Cable ssembly to Structure per Sections 3 & 4 (Typ.) djustable Clevis Hanger END VEW Cable Connection to Component per Detail C on 7-4 Uninsulated Pipe or Conduit (only the two cables in foreground shown for clarity) SDE VEW 4-WY SWY BRCE DETL FOR UN-NSULTED PPE & CONDUT (for locations where Transverse & Longitudinal bracing coincide) Uninsulated Pipe or Conduit P P R O V E D Fixed Equipment nchorage OP /01/04 G R ET S E L C L FO R N STT E nthony Pike NDUSTRL BLVD. NPLES, FL FX : CBLEWRE DVSON Loos & Co., nc nwar Yusuf /3/05
22
SEISMIC RESTRAINTS Multi-Directional Bracing For Electrical Conduit, Cable Tray And Mechanical Piping Systems
SEISMIC RESTRAINTS Multi-Directional Bracing For Electrical Conduit, Cable Tray And Mechanical Piping Systems SYSTEMS THAT MAKE SENSE INTRODUCTION INTRODUCTION What is Seismic Bracing? Seismic forces are
More information229 B-Line series Pipe Hangers & Supports
accessories offered in this section are designed to reduce installation time. wide range of types and sizes are available for various applications. Materials For maximum loading design, Carbon Steel, Forged
More informationMidwest Roadside Safety Facility
22860 900" D D 914 36" 1000 39 3/8" SOIL AND TARMAC CUT-OUT CONCRETE TARMAC BRIDGE DECK B PLAN VIEW C A C 15 20 [3/4"] Deck Gap BRIDGE DECK A 3900 153 1/ Impact 30V 45720 1800" 34290 13" 11430 4" RAIL
More informationStandard Installation Fire Damper Models: 319, 319(SS), D39
Standard Installation Fire Damper Models: 319, 319(SS), D39 Page 1 or 6 APPLICATION This fi re damper is intended to restrict the passage of fl ame. The standard installation requires that the damper is
More informationMIDDLE SECTION REPRESENTS "BLADE SIZE" (EXAMPLE: 24 = 24/32" [3/4"] 48 = 48/32" [1 1/2"]) REPRESENTS NUMBER OF BLADES PER 12" WIDE PANEL WG WB
HOW TO READ PRODUCT "SKU" : FIRST TWO LETTERS REPRESENT "PRODUCT TYPE" MIDDLE SECTION REPRESENTS "BLADE SIZE" (EXAMPLE: 24 = 24/32" [3/4"] 48 = 48/32" [1 1/2"]) REPRESENTS NUMBER OF BLADES PER 12" WIDE
More informationTO BE USED FOR MAINTENANCE MICHIGAN DEPARTMENT OF TRANSPORTATION. 2 3/16" x 2 3/16" x 10 Ga. 12" 15.5" 1 1/2" x 1 1/2" x 12 Ga.
2 3/16" x 2 3/16" x 10 Ga. TOP VIEW 18" 1" 7/16" Hole 1 1/2" x 1 1/2" x 12 Ga. two sides only steel tubing 1 1/2" x 1 1/2" x 12 Ga. @ 18" long steel angle 15.5" 12" TRAFFIC 3/8" Hex head grade 5 steel
More informationPipe/Conduit Clamps & Hangers
Our beam attachments and pipe supports offered in this section are designed to provide supports without drilling or welding. complete selection of beam clamps, pipe clamps, rollers, supports and accessories
More informationInstallation Instructions Capacity 10,000 lbs. (100 Series Lift)
Installation Instructions Capacity 10,000 lbs. (100 Series Lift) IMPORTANT Reference ANSI/ALI ALIS, Safety Requirements for Installation and Service of Automotive Lifts before installing lift. OPERATING
More informationRittling Econoline Enclosures
Hydronic Heating Fan Coils Radiant ceiling systems Water Source Heat Pumps Rittling Econoline Enclosures Submittal Data, English Language, IP Units Submittal data Project Job number Architect Performance
More informationInstallation Instructions
Installation Instructions 2-Post Capacity 12,000 lbs. OPERATING CONDITIONS Lift is not intended for outdoor use and has an operating ambient temperature range of 41-104 F (5-40 C) IMPORTANT Reference ANSI/ALI
More informationEccentric Collar Ball CONTENTS. Bearing
CONTENTS Specialty Tapered Features / Benefits Type C...B11-2 Special Duty, Hinged Cap.......................................... B11-3 ll Steel...B11-4 Specifications Type C...B11-5 Special Duty, Hinged
More informationVertex Plus, Vertex V60, Solus & Cardio Camera Site Planning Document
Vertex Plus, Vertex V60, Solus & Cardio Camera Site Planning Document 9347-0101 Rev B Sec 1: Room Requirements...1-1 Sec 2: Room Layouts...2-1 Sec 3: Anchor Details...3-1 Sec 4: Gantry Cables...4-1 Sec
More informationRobinson. Principals Meier Peter Robinson, S.E. Juilly & Associates Kurt Ruhland, S.E.
Structural Engineers Robinson Principals Meier Peter Robinson, S.E. Juilly & Associates Kurt Ruhland, S.E. Senior Structural Engineer Paul L. Juilly, S.E. Corporate Consultant L.F. Robinson, S.E. Structural
More informationSECTION HVAC POWER VENTILATORS
SECTION 233423 HVAC POWER VENTILATORS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationWeb: Elk Grove, Califimiia I 8401 L1guna Palms Way. Modification or Addition to Improvement Standards and Details
Phone: 9166837111 Fax: 916691 168 Web: wwwelkgrovecityorg Elk Grove, Califimiia 95758 EK 8401 1guna Palms Way GROVE - PROUD HmGE BRGHT FUTURE- Modification or ddition to mprovement Standards and Details
More informationInstallation STUD JOIST A237R SPECIFICATIONS. Width Height Depth Weight Max. Spacing between Mounts Max. Load
WILREP LTD. 08 13 48 13 SPECIAL CONSTRUCTION 14 manufactured sound & vibration control components Installation A237R SPECIFICATIONS Width Height Depth Weight Max. Spacing between Mounts Max. Load FURRING
More informationPipe Hangers. 47 B-Line series Pipe Hangers & Supports
Pipe hangers offered in this section are designed to support insulated or non-insulated pipe allowing for vertical adjustment and limited movement in the piping system. Materials arbon Steel, Malleable
More informationPipe Hangers. Pipe Hangers. Pipe Hangers & Supports
Pipe hangers offered in this section are designed to support insulated or non-insulated pipe allowing for vertical adjustment and limited movement in the piping system. Materials arbon Steel, Malleable
More informationDETAIL 'A' INTERIOR INSTALLATION. OVERALL ISOMETRIC VIEW (unless noted otherwise) 300C CARRIER 12 GA HANGER WIRE, BY OTHERS, NOT BY HUNTER DOUGLAS
3 " NOM. 316 G, ER V RO N HA. TYP SEE DETAILS A1.7 THROUGH A1.10 FOR FIXTURE OPENING RECOMMENDATIONS IE ARR XC 12 GA HANGER WIRE, BY OTHERS, NOT BY HUNTER DOUGLAS SEE DETAIL A1.2 A "M 1'-0 300C PANEL SPLICE
More informationInstallation Instructions Capacity 10,000 lbs. DP10 (200 Series Lift)
Installation Instructions Capacity 10,000 lbs. DP10 (200 Series Lift) IMPORTANT Reference ANSI/ALI ALIS, Safety Requirements for Installation and Service of Automotive Lifts before installing lift. OPERATING
More informationTELETOM PREINSTALLATION MANUAL
TELETOM PREINSTALLATION MANUAL MANUAL ORGANIZATION SAFETY CONTENTS SECTION 1 INTRODUCTION...1-1 DESCRIPTION...1-1 PRE-INSTALLATION RESPONSIBILITIES...1-2 BERCHTOLD RESPONSIBILITIES...1-2 OWNER RESPONSIBILITIES...1-3
More informationIndex ADDITIONAL ANCILLARY ITEMS 342 OFFSET PIPE CLAMP 115A SLING ROD CAGE PIPE ROLLER 362 ADJUSTABLE SUPPORT ROLLER CHAIR
ITIONL NILLRY ITEMS 1 Index 145 115 SLING RO GE 154 34 OFFSET PIPE LMP 31 PIPE ROLLER 11 EM LMP 348 JUSTLE PEESTL SUPPORT 13 3 JUSTLE SUPPORT ROLLER HIR 3 14 117 EM LMP 15 347 & 383 HOL OWN LMPS 35 SUPPORT
More informationInnerlynx Type UL Fire Rated 3Hour Fire Stop ADVANCE PRODUCTS & SYSTEMS, INC. ISO-9001 CERTIFIED COMPANY - FM
Innerlynx Type UL Fire Rated 3Hour Fire Stop ADVANCE PRODUCTS & SYSTEMS, INC. ISO-9001 CERTIFIED COMPANY - FM53705 www.apsonline.com Why choose Innerlynx? offer 21 different sizes for all pipe diameters
More informationToyota Prado 150 Backbone - RTPB1
Fit Time: 1.5 Hours Layout: IMPORTANT INFORMATION Maximum carrying capacity: Suitable Suitable On Road Cargo Off Road Cargo Pioneers On Road & Off Road Cargo Allowance Pioneers Allowance Allowance Static
More informationWIDE SPAN SHELVING PAGE 1 OF 10
WIDE SPAN SHELVING PAGE 1 OF 10 I N S T A L L A T I O N I N S T R U C T I O N S PAGE 2-3 PARTS IDENTIFICATION NOTE! This publication is intended to be a generic installation instruction for Madix Wide
More informationHANGERS, STRUT, AND FITTINGS SUBMITTAL
HANGERS, STRUT, AND FITTINGS SUBMITTAL Prepared By: Submitted by: Enter Company Name INTERNATIONAL SEISMIC APPLICATION TECHNOLOGY A Division of Tomarco Contractor Specialties Enter Project Name 4848 Northam
More informationfischer Bolt anchor FAZ II
fischer Bolt anchor FAZ II The power anchor for highest demands NEW Bolt anchor FAZ II For highest demands Powerful and flexible The distinctive edge holds the expansion clip in position even with reinforcement
More informationInstallation Information 2009 Model 300 Dumbwaiter
Installation Information 2009 Model 300 Dumbwaiter 3/17/09 Introduction This new model of Matot Dumbwaiter has several features that we hope you find are beneficial. Precision extruded rail sections provide
More informationWedgy Attachment Solutions
Innovation Since 1977 Introduction - Table of Contents Designed and Engineered by Professionals for Professionals Labor Saving Attachment Solutions Wedgy Attachment Solutions STEEL METAL Wedgys work because
More informationCADDY SEISMIC SWAY BRACING
DDY SEISMI SWY RING Page 214 Page 215 Page 215 Page 215 TP0 TP5 TP5G TP5 Page 216 Page 216 Page 217 Page 217 TP230 TP230G TP235 TP240 Page 218 Page 219 Page 0 TP280 S55 DDY EZ RE 213 DDY SEISMI SWY RING
More informationMechanical System Hanger
D U C T M A T E U.S. Patent No. 7,222,824 Mechanical System Hanger Seismic Tested & Conforms to ICC Code Guidelines EG284 May be used on a variety of mechanical systems Steel Cable & Clutcher mechanism
More informationToyota Prado 120 Backbone - RTPB2
Toyota Prado 120 Backbone - RTPB2 Fit Time: 1.5 Hours Layout: IMPORTANT INFORMATION Maximum carrying capacity: Suitable Pioneers On Road Cargo Allowance Off Road Cargo Allowance Static Allowance Roof Allowance
More informationKINETICS Pipe & Duct Seismic Application Manual
KINETICS Pipe & Duct Seismic pplication Manual KSCU & KSCC SEISMIC RESTRINT CBLE KIT CPCITIES MODEL KSCU RESTRINT CBLE SSEMBLY SPECIFICTIONS MODEL GRIPPLE CONNECTOR TYPE WIRE ROPE DIMETER (mm [in.]) B
More information[1200mm] 5" [125 mm] 2 3/4" [70mm] [2600mm] [450mm]
MIN 9'-10 1/2" [3010mm] 9'- CR 8'-6"MIN [2825mm] 6'-0" 12" S [2550mm] CR [1800mm] ON SIDE PLN "" 8'-8" CR 2 [2600mm] 6'-0" CR [1800mm] 2 FRONT ND RER S [55mm] 8'-6" [2550mm] [55mm] [125 mm] 2 [70mm] 6
More informationSECTION AXIAL HVAC FANS
SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationSTREAMLINED SOLAR CHECKLIST Owner Name:
STREAMLINED SOLAR CHECKLIST Owner Name: Address: DEPARTMENT OF PUBLIC WORKS AND PLANNING ALAN WEAVER, DIRECTOR This checklist must be completed by the contractor or an authorized agent of the contractor
More informationINTERIOR INSTALLATION
HOOK ON CROSS CONNECTOR CLAMP AT ALL INTERSECTIONS OF S 4-1 4" PANEL 1/2" x 1-1/2" 16 GA CR CHANNEL PRIMARY AT 48" O.C. MAX SPACING, TYPICAL. PANEL 1 1 2 " 12 GA HANGER WIRE, BY OTHERS, NOT BY HUNTER DOUGLAS.
More informationPVC & CPVC Copper Tubing. Insulated Pipe Steel Conduit. Plastic Conduit SDR-35. Dual Containment Glass Pipe
Why choose Innerlynx? Innerlynx offer 21 different sizes for all pipe diameters ranging from 1. Innerlynx are made from synthetic rubbers with industrial strength UV and ozone resistant plastic or all
More informationORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and C-to-C dimension. C - C LOAD lb.
Fig. 2110 www.pipingtech.com/fig2110 Sway Strut with 4 of Adjustment Engineered spring supports option 1 option 2 ORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and
More informationPipe hanger solutions
Product catalog Middle East offering Pipe hanger solutions for commercial and industrial applications B00 series B00 - Standard clevis hanger Pipe will not pinch when installing. 5 swing in either direction
More informationInstallation Instructions X-Force UTV Lift (000 Series) Capacity 2,275 lbs (1,035 kg)
Installation Instructions X-Force UTV Lift (000 Series) Capacity 2,275 lbs (1,035 kg) Read entire manual before assembling, installing, operating, or servicing this equipment. LP20640 IN20793 September
More informationInstallation, Operation, & Maintenance Manual
Installation, Operation, & Maintenance Manual IMPORTANT! DO NOT DESTROY Free Standing Steel Work Station Bridge Crane Gorbel Customer Order No. / Serial No. Gorbel Dealer Date Month Year This page intentionally
More informationCATALOGUE PIPE SUPPORTS
CTOGUE B R T IN SIN C E 1 9 2 4 G 90 YERS ST E RU CE T PIPE SUPPORTS O F PIPE SUPPORTS - PICTORI INEX PIPE SUPPORTS The Unistrut pipe support systems covers an extensive range of hangers, pipe clips, pipe
More informationDuct System for a Server or Switch Cabinet Mounted Cisco 4900M (CNLTD21B2)
Duct System for a Server or Switch Cabinet Mounted Cisco 4900M (CNLTD21B2) Panduit Corp. 2012 INSTALLATION INSTRUCTIONS 4900M Duct (Installed in Net-Access Cabinet.) Switch Cabinet Application Server Cabinet
More informationAPPENDIX D. D.1 Macalloy Bars. Approximate safe working loads (kn) Appendix D - Proprietary Components (1/9) Stainless steel architectural ties
Appendix D - Proprietary Components (1/9) APPENDIX D D.1 Macalloy Bars Bar dia. mm Stressing ties Stainless steel stressing ties Stainless steel architectural ties High strength Tie rods grades precision
More informationMECHANICAL INSTALLATION PROCEDURES for Custom Grids and Support Framing
CosaTron Mechanical Installation Instructions MECHANICAL INSTALLATION PROCEDURES for Custom Grids and Support Framing BECAUSE CLEAN AIR MATTERS General The CosaTron Custom Grids are located within the
More informationElectrical Accessories
complete system of top quality, time saving products, designed for surface metal raceways, lighting and cable supports. Innovative designs offer many installation advantages. -Line s surface raceways are
More informationInstallation, Operation and Maintenance Manual
Document 474916 HBS Series Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or
More informationSPO15, SPO18 I N S T A L L A T I O N I N S T R U C T I O N S
SPO15, SPO18 Sprinter SPO15 (3A0 Lifts) Capacity 11,000 lbs. Standard SPO15 (300 Series Lifts) Capacity 15,000 lbs. Standard SPO18 (300 Series Lifts) Capacity 18,000 lbs. SPO15 (31A0 Lifts) Capacity 14,300
More information4.5 COMPOSITE STEEL AND CONCRETE
4.5 COMPOSITE STEEL AND CONCRETE 4.5.1 RULES OF THUMB 4.5 Composite Steel and Concrete (1/11) Typical starting point Overall concrete depth 130mm (Grade 30) Depth of profiled decking 60mm Size beam with
More informationTG/RB/2M/Web Rev.12/1/16. Pipe Hangers & Devices
TG/RB/2M/Web Rev.12/1/16 Pipe Hangers & Devices Pipe Welcome Hangers to PHD & Devices Manufacturing PHD Manufacturing, Inc. was founded in 1972 by a group of industry veterans with strong management, financial,
More informationRETRACTED SIDE MINIMUM. 4 1/4 in. [108.0 mm] CP-493 HANGER (WITHOUT TRIGGER) RETRACTED SIDE CP-007 CLIP ACTIVATED SIDE MINIMUM. [108.
TYPE CC-NRB CATCH N CLOSE CROWDERFRAME POCKET DOOR KIT INSTRUCTION SHEET FOR NARROW DOORS 18 in [457 mm] TO LESS THAN 26 in [660 mm] WIDE ONLY ACTIVATED SIDE CC-493 HANGER (WITH TRIGGER) SEE RIGHT (COMPLETE
More informationReference Data. Schedule 40 Steel Pipe Data. Schedule 80 Steel Pipe Data
Schedule 40 Steel Pipe Data Maximum Recommended Pipe Size Pipe O.D. Thickness Weight of Pipe Filled With Water Span* Hanger Rod Ft. Meter Sizes 3/8" (10).675 (17.1).091 (2.3).6 (.9).7 (1.0) 7 (2.13) 3/8"-16
More informationReliance BlastMax Blast Resistant Curtain Wall Wet Glazed
Reliance BlastMax Blast Resistant Curtain Wall Wet Glazed Table of Contents (Drawing numbers ie H9601 used as CAD detail reference only ) Elev-RcwStrMax-Wet-Glz-TwnSpn H9601-Head-at-Vision H9602-Typical-Horizontal
More informationResilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator
Worldwide ontacts www.tyco-fire.com Resilient-Seated Gate Valves with Vertical or ross Wall Post Indicator General Description TYO Resilient-Seated Gate Valves with Vertical and ross Wall Indicators are
More informationResilient-Seated Gate Valves with Vertical or Cross Wall Post Indicator
Worldwide ontacts www.tyco-fire.com Resilient-Seated Gate Valves with Vertical or ross Wall Post Indicator General Description TYO Resilient-Seated Gate Valves with Vertical and ross Wall Indicators are
More informationProduct Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm
Product Data 42BH System Fan Coil 800 to 4000 Cfm Satisfy All Your Design Requirements with Carrier s Versatile 42BH Fan Coil Unit A selection of 6 sizes covers capacities from 800 to 4000 cfm Choice of
More informationVALVE INSERTION WHEN YOU ARE UNDER PRESSURE TO INSTALL A VALVE IN AN OPERATING LINE VALVE INSERTION PAGE QV-2
www.romac.com 1-800-426-9341 WHEN YOU RE UNDER PRESSURE TO INSTLL VLVE IN N OPERTING LINE PGE QV-2 4", 6" or 8" installations in cast iron, ductile iron, /C and some classes of PVC pipe Uses modern resilient
More informationELECTRICAL ACCESSORIES FOR 1 5 8" (41 MM) WIDTH SERIES CHANNEL
ELECTRICL CCESSORIES FOR 5 8" (4 MM) WIDTH SERIES CHNNEL Page Electrical Fittings Receptacles Fixture Hangers ccessories and Connectors Junction Boxes In-Channel Joiners Swivel Hangers Cable Entrance Tubing
More information3.0 RAIL-FREE RACKING. Utilizes EcoFasten Solar s patented technology
3.0 RAIL-FREE RACKING Utilizes EcoFasten Solar s patented technology Document Date: 05.08.2018 Contents Pg. 1... Assets of Design Features System Components Pg. 2... Rock-It 3.0 Mount Assembly Rock-It
More informationPART NUMBER POLE DIAMETER RANGE CARTON QTY " to 5" " to 6 3 4" " to 7 3 4" " to 8 3 4" 10
PH1 Offset Pole Band Bands Single Double Offset Pole Bands are used for dead-ending, guying, and mounting secondary racks on metal poles, pipe masts, or conduit. Each Pole Band Assembly contains two 1
More informationGRATE-LOCK PRODUCT SPECIFICATIONS. GRATE-LOCK Plank with Grip or Smooth Surface. 1-1/2", 2-1/2", 3" (4" special order)
QUALITY HOLE PRODUCTS PLANK GRATING McNICHOLS Quality Plank Grating includes a variety of channel configuration choices and walkway styles. Plank Grating is a one-piece construction product that is lightweight
More informationCENTERLINE GLASS RAILING - NEW! 2.5 Post System Mechanical/Welded Combo Accepts 7/16 and 9/16 Glass Tested and Engineered System
CENTERLINE 2.5 Post System Mechanical/ Combo Accepts 7/16 and 9/16 2.5 Post 28-60-735 Round Top Cap 28-63-700 Intermediate Rail Option - 28-63-720 Alternate Radius Top Cap - 28-63-710 Option 2.5 Rail Post
More informationTO BE USED AS A GUIDE ONLY
Granor Potstay Fixed GRANOR SERVICEABILITY ULTIMATE ROT'N POT BEARING POT BEARING ATTACH'T POT POT POT TYPE LIMIT STATE LIMIT STATE BOTTOM PLATE TOP PLATE BOLTS BRG BRG STRUCTURAL (SLS) (ULS) OVERALL DIMENSIONS
More informationIDS ILLINOIS, LLC. 2000/2500 DEVICE & OPERATOR
IDS ILLINOIS, LLC. 2000/2500 DEVICE & OPERATOR INSTALLATION MANUAL 922 Geneva Street Shorewood, IL 60404 PH: 815/730-0050 FX: 815/730-0057 IDS ILLINOIS, LLC. Quick List Quick Reference for Installation
More informationLifting height 5.5" - 72" with adapters " Height overall 165" Width between columns 122" Drive through 109" Width overall 151.
Model Number TP12KC-D Capacity 12,000 lbs. Lifting height 5.5" - 72" with adapters 79.625" Height overall 165" Width between columns 122" Drive through 109" Width overall 151.125" Arm extension 37.5" -
More informationTypical Specifications for ECP Helical Torque Anchors
Chapter 4 Typical Specifications for ECP Helical Torque Anchors ECP Helical Torque Anchors New Construction Piles 73 Helical Torque Anchor Underpinning With Foundation Bracket 79 ECP Helical Torque Anchor
More informationfsfdfsdfsdfssfsf OMNI DIFFUSER
fsfdfsdfsdfssfsf OMNI DIFFUSER Architectural Ceiling Diffusers diffusers OMNI The Titus OMNI diffuser satisfies architectural as well as engineering criteria. Its strong, clean, unobtrusive lines harmonize
More informationSECTION CENTRIFUGAL HVAC FANS
SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationInternal Joist Mount: ACC120. extension column. Cathedral Ceiling Adapter: ACC556. Mounts to cathedral or vaulted ceilings 120 (+60 ) of adjustment
Ceiling Plates Ceiling Plate: CMJ470(W), CMJ480(W), CMJ490(W) Internal Joist Mount: ACC120 Round Ceiling Plate: ACC570(S)(W), ACC571 Mounts to wood joists or structural concrete ceiling (requires concrete
More informationGP Lam LVL. Grade Thickness Depth , , , , , 149, 169, 189, 249 (209and 229 by special order) 2.
GP Lam LVL Grade Thickness Depth 2.0E 1 3 49, 3 1 29 7 1 49, 9 1 49, 9 1 29, 11 1 49, 11 7 89, 149, 169, 189, 249 (209and 229 by special order) 1.5E 1 3 49 7 1 49, 9 1 49, 9 1 29, 11 1 49, 11 7 89, 149,
More informationSection 8 AMERICAN. Flanged Pipe
Section 8 AMERICAN Flanged Pipe The principal standards covering Flanged Pipe are ANSI/AWWA C115/A21.15 and ANSI/AWWA C110/A21.10. These and other standards are referenced throughout this Section either
More informationINSTALLATION OF OFF-THE-FLOOR FIXTURES
6 Closet Carriers INSTALLATION OF OFF-THE-FLOOR FIXTURES Many factors, including cost, material, labor required, space, handling and others must be thoroughly evaluated when planning an installation. With
More informationLimit Switch D4D- N. Small, Economical Switch Featuring a Positive Opening Mechanism and Conforming to the CE Mark
Limit Switch Small, Economical Switch Featuring a Positive Opening Mechanism and Conforming to the CE Mark Features positive opening mechanism (NC contacts only) that opens contacts, thus preventing faulty
More informationSECTION PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
More informationFINAL REPORT CATHODIC PROTECTION EVALUATION. 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to South Texas Water Authority
FINAL REPORT CATHODIC PROTECTION EVALUATION 42-Inch Water Transmission Pipeline Contract 1 Station 0+00 to 50+00 South Texas Water Authority Prepared for: South Texas Water Authority P.O. Box 1701 Kingsville,
More informationVALVES, FIRE HYDRANTS, AND APPURTENANCES
VALVES, FIRE HYDRANTS, AND APPURTENANCES PART 1 - GENERAL 1.01 SECTION INCLUDES A. Butterfly Valves B. Gate Valves C. Tapping Valve Assemblies D. Fire Hydrant Assemblies E. Flushing Devices (Blowoffs)
More informationGB-250. Submittal Specifications Installation Application Specific Details
GREASE INTERCEPTOR TECHNICAL DATA Submittal Specifications Installation Application Specific Details 68" (1,727 mm) 13½" (343 mm) 51½" (1,308 mm) 38" (965 mm) SUBMITTAL 33½" (851 mm) STANDARD: 4" plain
More informationU.S. PATENT NO.: US 7,765,771 TECHNICAL GUIDE SUPERIOR ENGINEERED FLOOR FRAMING SYSTEM
U.S. PATENT NO.: US 7,765,771 TECHNICAL GUIDE SUPERIOR ENGINEERED FLOOR FRAMING SYSTEM SUPERIOR ENGINEERED JOIST SYSTEMS JoistRite is a specially designed, patented, cold-formed steel section that has
More informationWESTERN SPECIFIER. Technical Data for PWI Joists, PWLVL Headers, Beams, Rim Board, Stud, and Dimension
E N G I N E E R E D W O O D WESTERN SPECIFIER Technical Data for PWI Joists, PWLVL Headers, Beams, Rim Board, Stud, and Dimension P R O D U C T S JOIST DIMENSIONS 9½ LVL FLANGE PWI JOIST SERIES JOIST DIMENSIONS
More informationAlpha System ADAPTABLE KEWAUNEE LABORATORY FURNITURE. encouraging new discovery
Alpha System ADAPTABLE LABORATORY FURNITURE KEWAUNEE encouraging new discovery Alpha 6 partition modules with Kemresin worktops. Minneapolis, Minnesota Alpha 6 partition modules with Alpha overhead service
More informationACCESS DOORS. Model Model Model Model Model
MODEL 0840-6 PLENUM CCESS DOOR Nailor Model 0840-6 ultra-low leakage plenum access door provides easy access to larger plenums and equipment housings and is suitable for use in high, medium or low pressure
More informationStandard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)
Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Page 1 of 6 APPLICATION These dynamically rated fire/smoke and fire s are intended to restrict
More informationIntroduction. Features. Intelligent Technologies Motor Control Center Structures
Intelligent Technologies Technical Data New Information Description Page Intelligent Technologies General............................................. 2 s.......................................................
More informationUTILITY CROSSING DETAIL
6" OF CSBC COMPACTED TO A FIRM AND UNYIELDING CONDITION. NOTE: - SILT FENCE SHALL CONFORM TO 8-01.3(9)A - SILT FENCES SHALL BE INSTALLED ALONG CONTOUR WHENEVER POSSIBLE. - POST SPACING MAY BE INCREASED
More informationStandard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2
Reprinted Feb 2013 APPLICATION These dynamically rated fire/smoke and smoke dampers are intended to restrict the passage of smoke. The dynamically rated fire/smoke dampers are also intended to restrict
More informationunderfloor 49 UFC UFC 50 FAS P 50 UFCN 51 UC C DF 54 UFS 55 UFFS 56 UFS Cablofil cable management UNDER FLOOR SUPPORT CLAMP kit
underfloor 49 UFC 550 UNDER FLOOR SUPPORT CLAMP kit 49 UFC UNDER FLOOR SUPPORT CLAMP 50 FAS P FAS PROFILE 50 UFCN UNDER FLOOR CLAMP 51 UC 50 CABLE TRAY STANDOFF 51 C 50 UNDER FLOOR ATTACHMENT 52 fas l
More informationMaximum Span Tables. for Joists and Rafters. MSR Lumber. for Performance. Figure provided courtesy of the American Forest & Paper Association
Maximum Span Tables for Joists and Rafters MSR Lumber for Performance Figure provided courtesy of the American Forest & Paper Association 2 MSRLumber Producers Council Span Tables Purpose and Introduction
More informationLab Specialty Products Technical Information TECHNICAL INFORMATION WEIGHTS & DIMENSIONS
Lab Specialty Products Technical Information TECHNICL INFORMTION WEIGHTS & DIMENSIONS Contact Spears for any Information not found. Page 569 Lab Ball s Sample Engineering Specification ll thermoplastic
More informationInstallation Instructions Vanishing Lid Bracket
-800-447-88 www.coverpools.com Installation Instructions Vanishing Lid WARNING FOR YOUR SAFETY This product must be installed and serviced by a contractor who is licensed and qualified in pool equipment
More informationHAMPTON INN AND SUITES
SUITES, /7/08 5:0:0 PM Z:\808 Montpelier Garage\0. REVIT FILES\808 - Montpelier Parking Garage - 0--8.rvt ADD ADDITIONAL A/C AIR CONDITION(ING) AT ACOUSTIC TILE ADJ ADJUSTABLE AFF ALUM ABOVE FINISH FLOOR
More informationSECTION METAL ATHLETIC SPORT LOCKERS
SECTION 10 50 13 - METAL ATHLETIC SPORT LOCKERS PART 1 GENERAL 1.1 SECTION INCLUDES A. DESCRIPTION: Furnish and install factory-assembled Heavy-Duty MIG-Welded Metal Lockers, complete, as shown and specified
More informationSeries 36-WW COMBINATION AIR VALVES DATA AND SIZING WASTEWATER SERVICE. (Single Body Style) Installation. Specifications. Purchase Specification
Series -WW COMINTION IR S DT ND SIZING WSTEWTER SERVICE (Single ody Style) Stainless Steel T Trim Standard Stainless Steel Floats Guaranteed Fully Ported s - No Restrictions Engineered For Drip Tight Seal
More informationBulletin BX-512H. Bell & Gossett. Series HSC-S Pumps Technical Bulletin. Bell & Gossett. Part of the. Equipment Selection Programs
Bulletin BX-1H Bell & Gossett Series HSC-S Pumps Technical Bulletin Part of the Bell & Gossett Equipment Selection Programs TABLE OF CONTENTS Useful Pump Formulas...............................................
More information2507 (IBC 2006 ONLY) 3054 (IBC 2006 ONLY) Supreme Framing System Product Catalog
12 0 2 / 2009IANT C B I PL COM 2507 (IBC 2006 ONLY) 3054 (IBC 2006 ONLY) R Supreme Framing System Product Catalog Supreme Framing System The Benefits of Supreme Framing System Speak for Themselves What
More informationfischer Bolt anchor FAZ II The power anchor for highest demands.
fischer Bolt anchor FAZ II The power anchor for highest demands. Bolt anchor FAZ II For highest demands. Powerful and flexible. The distinctive holds the expansion clip in position even with reinforcement
More informationINSTALLATION INSTRUCTIONS FOR FORD 4WD SUPER DUTY F COIL SPRING SUSPENSION SYSTEM
INSTALLATION INSTRUCTIONS FOR 2008-10 FORD 4WD SUPER DUTY F250-350 6 COIL SPRING SUSPENSION SYSTEM Requires the following parts (sold separately) for a complete installation: KIT PART NUMBER (6860) REQUIRES
More informationSpring hangers, spring supports
Spring hangers, spring supports 2 spring Spring hangers, supports PRODUCT 2 GROUP Spring hangers, spring supports Contents Page Field of application...2.1 Overview of spring hangers and spring supports...2.3
More information2) Mark wall at 5 10 for center line of bottom bolt-hole in wall brackets on transition box side of floor.
IN-BAY INSTALLATION 1) Set up transit or level to determine highest point on the floor. From this point establish a level line from which to mark the bracket height on the walls. 2) Mark wall at 5 10 for
More informationModels: DC Electric Vibrators. Operating Instructions CEG CEG CEG CEG CEG
DC Electric Vibrators Operating Instructions Global External 12-Volt DC Electric Vibrators Intermittent Use Only Models: CEG-1800-12 CEG-2200-12 CEG-2800-12 CEG-3600-12 CEG-4200-12 INDUSTRIAL ELECTRIC
More information