PROCUREMENT SPECIFICATION MODEL DSC800 HYDRAULIC BOLLARD BARRICADE SYSTEM

Size: px
Start display at page:

Download "PROCUREMENT SPECIFICATION MODEL DSC800 HYDRAULIC BOLLARD BARRICADE SYSTEM"

Transcription

1 PROCUREMENT SPECIFICATION MODEL DSC800 HYDRAULIC BOLLARD BARRICADE SYSTEM SYNOPSIS This specification defines a CRASH TESTED - CRASH CERTIFIED - HIGH SECURITY BOLLARD BARRICADE SYSTEM DELTA Model DSC800. The basic system can consists of one or more vertical lift BOLLARDS together with a HYDRAULIC POWER UNIT, OPERATING CONTROLS, POWER CIRCUITS, OPERATING LOGIC, SAFETY AND ENVIRONMENTAL OPTIONS. The BOLLARD(S) may be specified with Standard or Custom Cast Outer Shells to match existing ARCHITECTURAL TREATMENTS or STYLES. 1.0 PATENT LICENSE. The CRASH CERTIFIED HYDRAULIC BOLLARD SYSTEM shall be fully licensed for manufacture under U.S. Patent Numbers: 4,576,508 and 4,715, SYSTEM CONFIGURATION 2.1 BOLLARD(S) STANDARD CONFIGURATION 2.1 BOLLARD ARRANGEMENT. The system shall have a total of Bollards arrayed in accordance with either or (specify the total number of Bollards in the system whether operated independently or in combination). Select either or to define the operating pattern of the Bollards within the system Single Bollards Individual Operated. Each individual Bollard shall be operated independently from any other Bollard within the system. Each Bollard shall have its own controls Multi Bollards Operating in Sets. Bollard system shall have sets (specify the number of sets). Each set shall consist of Bollards (specify the number of Bollards per set). Each set of Bollards shall have its own controls and operate independently from each other set within the system Construction. Bollard shall be a below grade assembly containing a heavy steel cylindrical weldment capable of being raised to an above grade position. The guard position shall present a formidable obstacle to approaching vehicles. Upon impact, forces shall be first absorbed by the weldment and then transmitted to the foundation of the unit Bollard Height. Height of the Bollard shall be 30 inches (762 mm) as measured from the top of the foundation frame to the top of the Bollard assembly Bollard Dimensions. Bollard shall be 6.63 inches (168 mm) in diameter Copyright 2001 Delta Scientific Corporation Page 1 of 8

2 2.1.6 Finish. The foundation and underside of the Bollard shall be asphalt emulsion coated for corrosion protection. The roadway plates shall have a non skid surface. The above grade portion of the Bollard shall be white and have yellow/black diagonal stripes (or alternately 2.2 BOLLARDS(S) WITH ARCHITECTURAL ENHANCEMENTS BOLLARD ARRANGEMENT. The system shall have a total of Bollards arrayed in accordance with either or (specify the total number of Bollards in the system whether operated independently or in combination). Select either or to define the operating pattern of the Bollards within the system Single Bollards Individual Operated. Each individual Bollard shall be operated independently from any other Bollard within the system. Each Bollard shall have its own controls Multiple Bollards Operating in Sets. Bollard system shall have sets (specify the number of sets). Each set shall consist of Bollards (specify the number of Bollards per set). Each set of Bollards shall have its own controls and operate independently from each other set within the system Construction. Bollard shall be a below grade assembly containing a heavy steel cylindrical weldment capable of being raised to an above grade position. The guard position shall present a formidable obstacle to approaching vehicles. Upon impact, forces shall be first absorbed by the weldment and then transmitted to the foundation of the unit Architectural Enhanced Outer Shells shall be cast from a free machining aluminum alloy and be free of cracks, uneven surface texture, excessive parting line offset or particle inclusions Bollard Diameter, with Architectural Enhancement in place shall not be greater than inches (260 mm) in diameter. (Refer to DELTA drawing for design envelope for enhancement) Bollard Height: shall be 30 inches (762mm) as measured from the top of the foundation frame to the top of the Bollard assembly Finish Steel Structure. The foundation and underside of the Bollard shall be asphalt emulsion coated for corrosion protection. The roadway plates shall have a non-skid surface. The above grade portion of the Bollard shall be finished with an industrial enamel primer Architectural Enhancement. Standard Aluminum Cast Outer Shells shall first be primed with an industrial enamel primer then finished with an industrial grade enamel. Highlight colors shall be of equivalent quality. Copyright 2001 Delta Scientific Corporation Page 2 of 8

3 Custom Architectural Enhancement Outer Shells shall be finished in accordance with customer instructions. 2.3 HYDRAULIC POWER UNIT (HPU) Hydraulic Circuit. Circuit shall incorporate the design concepts as described by U. S. Patent # 4,490,068 Re. 33,201. Unit shall consist of an electrically driven hydraulic pump which shall pressurize a high pressure manifold connected to a hydraulic type accumulator. Electrically actuated valves shall be installed on the manifold to allow oil to be driven to the up and/or down side of a double acting hydraulic cylinder to raise and lower the Bollard. The hydraulic circuit shall include all necessary control logic, interconnect lines and valves to override and lock out the normal speed control valve(s) for emergency fast operation of the Bollard(s) Main Power. The electric motor driving the hydraulic pump shall be fed from (specify actual site voltage, phase and frequency, i.e. 230/3/60). Motor shall be sufficiently sized for the expected number of barricade operations Power Off Operation. The accumulator shall be sized to allow three full cycle operations of a single Bollard in the event of a power outage. Enhanced power off capability can be selected as an option. The bi-directional control valves shall be manually operable in the event of a power outage Manual Operation. A hand pump shall be furnished to allow the Bollards to be raised manually in the event of a prolonged power interruption Construction. The hydraulic power unit and accessories shall be mounted and wired on an integral steel skid. The HPU shall fit in an envelope 60 inches W x 36 inches D x 60 inches H (1524 mm W x 914 mm D x 1524 mm H). The HPU shall be mounted indoors or in an optional weather resistant enclosure. 2.4 CONTROL AND LOGIC CIRCUITS The following circuits and control stations shall be furnished: Control Circuit. A control circuit shall be provided to interface between all Bollard control stations and the pneumatic power unit. This circuit shall contain all relays, timers and other devices necessary for the Bollard operation Voltage. The control circuit shall operate from a 120 volt, 50/60 Hz supply (optionally 240 volt, 50/60 Hz or 24 VDC). An internally mounted transformer shall reduce this to 24 VAC (24 VDC) for all external control stations Power Consumption. The control circuit power consumption shall not exceed 250 watts basic load, plus 200 watts for each Bollard in the system. Copyright 2001 Delta Scientific Corporation Page 3 of 8

4 Construction. The control circuit shall be mounted in a general purpose enclosure. All device interconnect lines shall be run to terminal strips. (The following control station(s) can be specified) Remote Control Panel. A remote control panel shall be supplied to control the Bollard operation. This panel shall have a key lockable main switch with "main power on" and "panel on" lights. Buttons to raise or lower each Bollard (or sets of Bollards) shall be provided. Bollard up and down indicator lights shall be included for each Bollard (or set). The emergency fast operate (EFO) feature shall be operated from a push button larger than the normal controls (optionally a covered toggle switch). The EFO shall also be furnished with EFO active light and reset button Voltage. The remote control panel shall operate on 24 VAC (optionally 24 VDC) Construction. The remote control station shall be a standard 19-inch electronics rack type surface mount panel with all devices wired to a terminal strip on the back (Option) Panel shall be equipped with a timer circuit to notify the operator via an annunciator "squealer" that the Bollard has been left in the down position for too long a time period. The time interval shall be customer selectable. (Select Control Panel instead of if Slave Panel is desired.) Remote Control Master Panel. A remote control master panel shall be supplied to control Bollard function. This panel shall have a key lockable main switch with "main power on" and "panel on" lights. Buttons to raise and lower each Bollard (or set) shall be provided. Bollard "up" and "down" indicator lights shall be included for each Bollard (or set). The emergency fast operate circuit (EFO) feature shall be operated from a push button larger than the normal controls (optionally a covered toggle switch). The EFO shall be furnished with EFO active light and reset button. The remote control master panel shall have a key lockable switch to arm or disarm the remote slave panel(s). An indicator light shall show if the slave panel is armed Voltage. The remote control panel shall operate on 24 VAC (optionally 24 VDC) Construction. The remote control station shall be a standard 19 inch electronics rack type surface mount panel with all devices wired to a terminal strip on the back (Option) Panel shall be equipped with a timer circuit to notify the operator via an annunciator "squealer" that the Bollard has been left in the down position for too long a time period. The time interval shall be customer selectable Remote Control Slave Panel. A remote control slave panel shall also be supplied to control the Bollard operation. This panel shall have a "panel on" light that is lit when enabled by a switch on the remote control master panel. Buttons to raise or lower each Bollard (or set) Copyright 2001 Delta Scientific Corporation Page 4 of 8

5 shall be provided. Bollard "up" and "down" indicator lights shall be included for each Bollard (or set). The emergency fast operate (EFO) feature shall be operated from a push button larger than the normal controls (optionally a covered toggle switch). When the slave panel EFO is pushed, an EFO "active" lamp will light and operation of the Bollard(s) will not be possible until reset at the master panel Voltage. The remote control panel shall operate on 24 VAC (optionally 24 VDC) Construction. The remote control station shall be a standard 19 inch electronics rack type surface mount panel with all devices wired to a terminal strip on the back (Option) Panel shall be equipped with a timer circuit to notify the operator via an annunciator "squealer" that the Bollard has been left in the down position for too long a time period. The time interval shall be customer selectable. The alarm is reset when the Bollards are returned to the up position. 3.0 ACCESSORY EQUIPMENT. Any or all of the following may be selected: 3.1 Auxiliary Emergency Fast Operate Circuit. A separate hydraulic circuit consisting of a pressure reserve source, operating controls logic and interconnects lines and valves shall be supplied. This circuit shall provide an available source of power to operate the Bollard(s) at emergency fast speed (as specified in 4.4.2), even after power off or manual operation or high frequency operation has depleted the normal reserve capacity. This system will operate in conjunction with and from normal EFO controls. 3.2 Electro-Mechanical Signal Gate. An electrically operated wood arm signal gate shall be supplied to alert vehicle drivers of the Bollard position. The gate operate shall interface with the Bollard at the control circuit. The control circuit shall close the gate at the Bollard "up" command and remain closed until the Bollard is fully lowered. The wood arm shall be foot ( 6, 8, 10 or 12 foot can be specified) long and be striped with reflective yellow/black tape. The gate assembly shall be mountable directly to the roadway surface. 3.3 Stop/Go Traffic Lights. Red/Green 8-inch traffic lights shall be supplied to alert vehicle drivers of the Bollard position. The green light shall indicate that the Bollard is fully down. All other positions shall cause the light to show red. Brackets shall be supplied to allow light(s) to be located on a (3.5 inch OD post) (wall) (3.5 inch OD post - back to back). The light operating voltage shall be 120 volts (alternately 240 volts), power consumption 40 watts per light. 3.4 Sump Pump. A self-priming sump pump shall be supplied to drain water collected in the Bollard foundation. The pump shall have the capacity to remove inches per minute of rainfall a distance of feet to customer supplied discharge drain. Pump operating voltage shall be 120/1/50-60 (alternately 240/1/50-60). 3.5 Safety Interlock Detector. A Bollard vehicle detector safety loop shall be supplied to prevent the Bollard from being accidentally raised under an authorized vehicle. The detector shall Copyright 2001 Delta Scientific Corporation Page 5 of 8

6 utilize digital logic have fully automatic tuning for stable and accurate long term reliability. The output of the detector shall delay any Bollard rise signal (except for EFO command) when a vehicle is over the loop. 3.6 Enhanced Power Off Capability. The hydraulic accumulator shall be sized to provide full cycle operations of a single Bollard (or sets of Bollards). 3.7 Weather Resistant HPU Enclosure. A lockable weather resistant enclosure shall be provided for the HPU. The design shall provide for easy access to the HPU for maintenance and emergency operation of the hydraulic system. Enclosure shall be provided with a corrosion resistant coating and shall be 60 inches W x 36 inches D x 60 inches H (1524 mm W x 914 mm D x 1524 mm H). 4.0 PERFORMANCE 4.1 EXPERIENCE. Bollard and auxiliary equipment shall be of proven design. Manufacturer shall have over 1700 Bollard type vehicle barriers in field operation for a minimum of 5 years with documented field experience for all major components and design features. 4.2 QUALIFICATION TESTS. Bollard design shall have successfully passed actual full scale crash tests conducted by a qualified independent agency Performance Evaluation. The Bollard shall have been certified by the United States Department of State to have a performance evaluation per D.O.S. Specification SD-SDT-0201 (Dated April 1985) of K4/L STOPPING CAPACITY Normal Operation. Bollard(s) shall provide excellent security and positive control of normal traffic in both directions by providing an almost insurmountable obstacle to non-armored or non-tracked vehicles The Bollard system shall be designed to stop a vehicle attacking from either direction High Energy Attack. Bollard(s) shall have been shown by certified dynamic non linear analysis to be capable of stopping and immobilizing non-armored or non-tracked vehicles with weight and velocity characteristics as defined in paragraph The Bollard system shall be designed to destroy the front suspension system, steering linkage, engine crankcase and portions of the drive train The Bollard shall be capable of stopping and destroying a vehicle(s) weighing: 15,000 pounds at 62 mph (66,7 kn at 100 kph) 30,000 pounds at 44 mph (133 kn at 71 kph). 4.4 SPEED OF OPERATION. Copyright 2001 Delta Scientific Corporation Page 6 of 8

7 4.4.1 Normal Operation. Each Bollard (or set) shall be capable of being raised or lowered in 3 to 15 seconds (customer adjustable) when operated at a repetition rate not greater than specified in paragraph 4.5. Bollard direction shall be instantly reversible at any point in its cycle from the control stations Emergency Fast Operation. Bollard shall rise to the guard position from fully down in 1.5 seconds maximum when the emergency fast operate button is pushed provided the system has not previously been exhausted by power off or manual operation or high speed cycle rates exceeding that specified in paragraph 4.5. Bollard shall remain in the up and locked position (normal up/down buttons inoperable) until the EFO condition is reset. (See 3.1 for auxiliary emergency fast operate system option.) 4.5 FREQUENCY OF OPERATION. Bollard shall be capable of (specify up to 200 cycles per hour) complete up/down cycles per hour. 5.0 ENVIRONMENTAL DATA (Please supply the following): Bollard shall operate satisfactorily under the following environmental conditions: 5.1 Extremes in temperature Yearly maximum drybulb temp f/c Yearly minimum drybulb temp f/c 5.2 Rainfall Yearly average inches Maximum expected hourly rate inches/hour 5.3 Snowfall Maximum expected hourly rate inches/hour Roadway will be (mechanically/manually/chemically) cleared. 6.0 QUALITY ASSURANCE PROVISIONS 6.1 Testing. Upon completion, the Bollard system will be fully tested in the manufacturer's shop. In addition to complete cycle testing to verify function and operating speeds, the following checks shall be made: Identification. A nameplate with manufacturer's name, model number, serial number and year built shall be located within the maintenance access area Workmanship. The Bollard and subsystems shall have a neat and workmanlike appearance Dimensions. Principal dimensions shall be checked against drawings and ordering information Finish. Coatings shall be checked against ordering information and shall be workmanlike in appearance. Copyright 2001 Delta Scientific Corporation Page 7 of 8

8 7.0 PREPARATION FOR SHIPMENT 7.1 The Bollard system shall be crated or mounted on skids as necessary to prevent damage from handling. The shipping container(s) shall be of sufficient structural integrity to enable the assembly to be lifted and transported by overhead crane or forklift without failure. 8.0 MANUFACTURER'S DATA 8.1 Drawings and installation data. The Bollard system drawings and installation, maintenance and operating manuals shall be sent to purchaser within 4 weeks of order. additional copies shall be supplied (1 copy supplied at no cost). 9.0 DISCLAIMER Please note - careful consideration must be devoted to the selection, placement and design of a Bollard installation. Just as in the case of any Barricade system, perimeter security device or security gate that blocks a roadway or drive, care must be taken to ensure that approaching vehicles as well as pedestrians are fully aware of the Bollards and their operation. Proper illumination, clearly worded warning signs, auxiliary devices such as semaphore gates, stop-go signal lights, audible warning devices, speed bumps, flashing lights, beacons, etc. should be considered. Delta has information available on many such auxiliary safety equipment not specifically listed herein. It is strongly recommended that an architect and or a traffic and or safety engineer be consulted prior to installation of a Bollard system. Delta will offer all possible assistance in designing the operating equipment, controls and the overall system but we are not qualified nor do we purport to offer either traffic or safety engineering information PROCUREMENT SOURCE The Model DSC800 Bollard Barricade System shall be purchased from: DELTA SCIENTIFIC CORPORATION West Avenue Stanford Valencia, California, 91355, USA Phone (661) FAX (661) info@deltascientific.com Copyright 2001 Delta Scientific Corporation Page 8 of 8

PROCUREMENT SPECIFICATION MODEL TT210 BOLLARD HYDRAULIC BARRICADE SYSTEM

PROCUREMENT SPECIFICATION MODEL TT210 BOLLARD HYDRAULIC BARRICADE SYSTEM PROCUREMENT SPECIFICATION MODEL TT210 BOLLARD HYDRAULIC BARRICADE SYSTEM 1.0 SCOPE The specification defines the procurement of a BOLLARD HYDRAULIC BARRICADE SYSTEM, Model TT210, consisting of (one, two,

More information

PROCUREMENT SPECIFICATION MODEL TT207S/FM PHALANX* SURFACE MOUNT HYDRAULIC BARRICADE SYSTEM

PROCUREMENT SPECIFICATION MODEL TT207S/FM PHALANX* SURFACE MOUNT HYDRAULIC BARRICADE SYSTEM PROCUREMENT SPECIFICATION MODEL TT207S/FM PHALANX* SURFACE MOUNT HYDRAULIC BARRICADE SYSTEM 1.0 SCOPE This specification defines the procurement of a PHALANX* HYDRAULIC BARRICADE SYSTEM, Model TT207S/FM,

More information

PROCUREMENT SPECIFICATION MODEL TT207S PHALANX* TYPE HYDRAULIC BARRICADE SYSTEM

PROCUREMENT SPECIFICATION MODEL TT207S PHALANX* TYPE HYDRAULIC BARRICADE SYSTEM 1.0 SCOPE PROCUREMENT SPECIFICATION MODEL TT207S PHALANX* TYPE HYDRAULIC BARRICADE SYSTEM This specification defines the procurement of a PHALANX* HYDRAULIC BARRICADE SYSTEM, Model TT207S, consisting of

More information

MODEL DSC2000 SYSTEM

MODEL DSC2000 SYSTEM MODEL DSC2000 SYSTEM MODULAR PHALANX TYPE BARRICADE SYSTEM This Procurement Specification defines a FULL SCALE CRASH TESTED AND CERTIFIED PHALANX TYPE COUNTER TERRORIST BARRIER SYSTEM - Model DSC2000.

More information

MODEL DSC501- K54 PHALANX TYPE BARRICADE SYSTEM

MODEL DSC501- K54 PHALANX TYPE BARRICADE SYSTEM MODEL DSC501- K54 PHALANX TYPE BARRICADE SYSTEM SYNOPSIS SECOND STRIKE CAPABILITY The DSC501 K54 Barricade System has been tested in full scale configuration and has demonstrated its ability to stop and

More information

MODEL DSC501 PHALANX TYPE BARRICADE SYSTEM HYDRAULICALLY OPERATED CRASH TESTED AND CERTIFIED MINIMUM DEPTH FOUNDATION CONFIGURATION

MODEL DSC501 PHALANX TYPE BARRICADE SYSTEM HYDRAULICALLY OPERATED CRASH TESTED AND CERTIFIED MINIMUM DEPTH FOUNDATION CONFIGURATION MODEL DSC501 PHALANX TYPE BARRICADE SYSTEM HYDRAULICALLY OPERATED CRASH TESTED AND CERTIFIED MINIMUM DEPTH FOUNDATION CONFIGURATION SYNOPSIS This Procurement Specification defines a FULL SCALE CRASH TESTED

More information

PROCUREMENT SPECIFICATION MODEL DSC720M 1M MANUAL BOLLARD BARRICADE SYSTEM

PROCUREMENT SPECIFICATION MODEL DSC720M 1M MANUAL BOLLARD BARRICADE SYSTEM SYNOPSIS PROCUREMENT SPECIFICATION MODEL DSC720M 1M MANUAL BOLLARD BARRICADE SYSTEM This specification defines a CRASH TESTED - CRASH CERTIFIED - HIGH SECURITY BOLLARD BARRICADE SYSTEM DELTA Model DSC720M.

More information

SYNOPSIS. This specification defines a CRASH TESTED - CRASH CERTIFIED - HIGH SECURITY BOLLARD BARRICADE SYSTEM DELTA Model DSC720 1M Hydraulic.

SYNOPSIS. This specification defines a CRASH TESTED - CRASH CERTIFIED - HIGH SECURITY BOLLARD BARRICADE SYSTEM DELTA Model DSC720 1M Hydraulic. PROCUREMENT SPECIFICATION MODEL DSC720 1M HYDRAULIC BOLLARD BARRICADE SYSTEM SYNOPSIS Over 20,000 Delta bollards have been installed in the past 24 years with hydraulic systems operating in areas as cold

More information

TYPE BARRICADE SYSTEM PROGRAMMABLE ELECTRO-MECHANICAL DRIVE SYSTEM CRASH TESTED AND CERTIFIED VERY HIGH SECURITY FULLY ENCLOSED BARRICADE,

TYPE BARRICADE SYSTEM PROGRAMMABLE ELECTRO-MECHANICAL DRIVE SYSTEM CRASH TESTED AND CERTIFIED VERY HIGH SECURITY FULLY ENCLOSED BARRICADE, MODEL DSC207S (EM) PHALANX TYPE BARRICADE SYSTEM PROGRAMMABLE ELECTRO-MECHANICAL DRIVE SYSTEM CRASH TESTED AND CERTIFIED VERY HIGH SECURITY FULLY ENCLOSED BARRICADE, SYNOPSIS This Procurement Specification

More information

PROCUREMENT SPECIFICATION MODEL SC3000S CRASH RATED CANTILEVER GATE SYSTEM WITH TT260 ELECTRO-MECHANICAL RACK AND PINION OPERATOR

PROCUREMENT SPECIFICATION MODEL SC3000S CRASH RATED CANTILEVER GATE SYSTEM WITH TT260 ELECTRO-MECHANICAL RACK AND PINION OPERATOR 1.0 SCOPE PROCUREMENT SPECIFICATION MODEL SC3000S CRASH RATED CANTILEVER GATE SYSTEM WITH TT260 ELECTRO-MECHANICAL RACK AND PINION OPERATOR This specification defines the procurement of a DELTA CRASH RATED

More information

PROCUREMENT SPECIFICATION DELTA MODEL DSC900 TRANSPORTABLE CRASH CERTIFIED RISING PLATE BARRIER SYSTEM

PROCUREMENT SPECIFICATION DELTA MODEL DSC900 TRANSPORTABLE CRASH CERTIFIED RISING PLATE BARRIER SYSTEM PROCUREMENT SPECIFICATION DELTA MODEL DSC900 TRANSPORTABLE CRASH CERTIFIED RISING PLATE BARRIER SYSTEM SYNOPSIS This Procurement Specification defines a CRASH CERTIFIED - TRANSPORTABLE BARRIER SYSTEM -

More information

PROCUREMENT SPECIFICATIONS DELTA MODEL DSC 1500 PORTABLE BEAM - CRASH CERTIFIED BARRIER SYSTEM

PROCUREMENT SPECIFICATIONS DELTA MODEL DSC 1500 PORTABLE BEAM - CRASH CERTIFIED BARRIER SYSTEM PROCUREMENT SPECIFICATIONS DELTA MODEL DSC 1500 PORTABLE BEAM - CRASH CERTIFIED BARRIER SYSTEM Copyright 2019 Delta Scientific Corporation Page 1 of 8 SYNOPSIS This Procurement Specification defines a

More information

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier

Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier Procurement Specification for a High Security Lift Arm Barrier (HSLAB) EB950 CR Armstrong High Security Lift Arm Barrier A. Requirement This document is to be used to specify the physical and operational

More information

Door Interlock System - For Invasion Stoppage

Door Interlock System - For Invasion Stoppage Door Interlock System - For Invasion Stoppage It is designed & manufactured State-of-the-art Door Interlock Based Access Systems for high security area- in fact any critical area that requires door access

More information

NMSB XX K12 Sliding Crash Gate

NMSB XX K12 Sliding Crash Gate NMSB XX K12 Sliding Crash Gate The Nasatka Maximum Security Barrier NMSB XX (pronounced 20) is a DOS listed K12 cantilevered sliding crash gate engineered for high-threat security facilities. The gate

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1

More information

Active Bollards An aesthetic solution to a complex need

Active Bollards An aesthetic solution to a complex need Active Bollards An aesthetic solution to a complex need Crash tested, Ross active bollards are designed to provide temporary or permanent security measures and are built to withstand violent impacts. Despite

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-34 71 13.19 (April 2008) ----------------------------- Preparing Activity: USACE Superseding UFGS-34 71 13.19 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Section A1. Vehicular Traffic Control. This Price Schedule is effective January 7, Date Page Comment

Section A1. Vehicular Traffic Control. This Price Schedule is effective January 7, Date Page Comment January 2019 PRICE SCHEDULE A 2.0 Section A1 This Price Schedule is effective January 7, 2019. Date Page Comment 1-2-19 All January, 2019 Price Schedule update. Specifications subject to change without

More information

Section A1. Vehicular Traffic Control. This Price Schedule is effective January 7, Date Page Comment

Section A1. Vehicular Traffic Control. This Price Schedule is effective January 7, Date Page Comment January 2019 PRICE SCHEDULE A 2.0 Section A1 This Price Schedule is effective January 7, 2019. Date Page Comment 1-2-19 All January, 2019 Price Schedule update. Specifications subject to change without

More information

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control Section A1 This Price Schedule is effective January 1, 2018. Date Page Comment 1-1-18 All January, 2018 Price Schedule update. 1-26-18 6, 7 Added 1601-180, 1601-181 Gray Housing and 1601-283 Gray arm hub

More information

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control Section A1 This Price Schedule is effective January 1, 2018. Date Page Comment 1-1-18 All January, 2018 Price Schedule update. 1-26-18 6, 7 Added 1601-180, 1601-181 Gray Housing and 1601-283 Gray arm hub

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control

January 2018 PRICE SCHEDULE A 2.0 Vehicular Traffic Control Section A1 This Price Schedule is effective January 1, 2018. Date Page Comment 1-1-18 All January, 2018 Price Schedule update. 1-26-18 6, 7 Added 1601-180, 1601-181 Gray Housing and 1601-283 Gray arm hub

More information

DEFENDERTM ANTI-RAM BOLLARDS PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM

DEFENDERTM ANTI-RAM BOLLARDS PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM DEFENDERTM ANTI-RAM BOLLARDS K4 PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM 866-467-2773 Section 1 Accreditation 1.01 Hydraulic bollard system 1.01.1 Designation High Security Fixed Bollard System

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

StopGate TM Barrier Arm GENERAL SPECIFICATIONS

StopGate TM Barrier Arm GENERAL SPECIFICATIONS StopGate TM Barrier Arm GENERAL SPECIFICATIONS I. GENERAL All StopGate Barrier Arms shall be designed and manufactured by Energy Absorption Systems, Inc., of Chicago, Illinois. II. DESCRIPTION OF SYSTEM

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

SENTINEL SHALLOW MOUNT ANTI-RAM WEDGE PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM

SENTINEL SHALLOW MOUNT ANTI-RAM WEDGE PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM SENTINEL SHALLOW MOUNT ANTI-RAM WEDGE PRODUCT DETAIL SPECIFICATION AMERISTARSECURITY.COM 866-467-2773 TM Section 1 Accreditation 1.01 Hydraulic Wedge Barrier system 1.01.1 Designation High Security Fixed

More information

Intelli-Park Series Barrier Arms. Intelli-Park 9. Intelli-Park 14. Intelli-Park 18. Intelli-Park 32

Intelli-Park Series Barrier Arms. Intelli-Park 9. Intelli-Park 14. Intelli-Park 18. Intelli-Park 32 Intelli-Park Series Barrier Arms Intelli-Park 9 Intelli-Park 14 Intelli-Park 18 Intelli-Park 32 06/2017 Features: The IntelliPark operators use a high quality PLC style microprocessor Features full system

More information

SHALLOW MOUNT ROAD BLOCKER/MODEL SHIELD

SHALLOW MOUNT ROAD BLOCKER/MODEL SHIELD /MODEL SHIELD Technical information: Solid steel construction with hot dib galvanized & RAL coating. Width: Height: Construction height: Electrical engine: Electrical system: Operating time: Operating

More information

Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24

Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24 Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24 2 Contents Contents Product Information and Specs. 3 Mechanical 3 Electrical, Line Connections 3 Electrical, Control Connections

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

APOLLO Gate Operators, Inc.

APOLLO Gate Operators, Inc. APOLLO Gate Operators, Inc. Model BA12 12 VOLT DC BARRIER ARM OPERATOR INSTALLATION MANUAL 0707 CONTENTS IMPORTANT SAFETY INSTRUCTIONS... 3 Applications... 4 Pre-Installation Checklist... 5 Operator Installation...

More information

Model 712 Cable Crash Beam Vehicle Barrier

Model 712 Cable Crash Beam Vehicle Barrier Installation and Operations Manual Model 712 Series Model 712 Cable Crash Beam Vehicle Barrier INSTALLATION MANUAL Corporate Office & Technical Support: 5900 S. Lake Forest Drive, Suite 230 McKinney, TX

More information

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

D. Operation and Maintenance Data. In addition to items specified in Division 1 Section Operation and Maintenance Data, include the following: SECTION 16211 - ELECTRICITY METERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Gate Operators, Inc. Model 7100UL Residential & Medium Duty Commercial Slide Gate Operator INSTALLATION MANUAL

Gate Operators, Inc. Model 7100UL Residential & Medium Duty Commercial Slide Gate Operator INSTALLATION MANUAL Gate Operators, Inc. Model 7100UL Residential & Medium Duty Commercial Slide Gate Operator INSTALLATION MANUAL 10-04-00 CONTENTS Safety Precautions... 2 Applications... 3 Pre-Installation Checklist...

More information

SOLAR HEATING SYSTEM

SOLAR HEATING SYSTEM SECTION 13600 SOLAR HEATING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07600 - Flashing and Sheet Metal. 2. 07900 - Joint Sealers. 3. 15260 - Thermal Insulation (Plumbing). 4. 15410 - Piping

More information

Owner s Manual. Model 9300 Vehicular Slide Gate Operator

Owner s Manual. Model 9300 Vehicular Slide Gate Operator Owner s Manual Model 9300 Vehicular Slide Gate Operator DoorKing, Inc. 120 Glasgow Avenue Inglewood, California 90301 U.S.A. Phone: 310-645-0023 Fax: 310-641-1586 www.doorking.com P/N 9300-065 Rev C 6/03

More information

MODEL 4X0E SERIES SLIDING GATE VEHICLE BARRIER

MODEL 4X0E SERIES SLIDING GATE VEHICLE BARRIER MODEL 4X0E SERIES SLIDING GATE VEHICLE BARRIER INSTALLATION MANUAL Headquarters & Tech Support: 5900 S Lake Forest Dr Suite 230 McKinney, TX 75070 Phone: (800) 367-0387 Fax: (972) 385-9887 E-mail: info@bb-armr.com

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

SECTION B1: MACHINE COMPONENTS

SECTION B1: MACHINE COMPONENTS SECTION B1: MACHINE COMPONENTS The machine portion of the Injected Metal Assembly system provides the means for: holding, heating and injecting the alloy; distributing and controlling electrical, pneumatic,

More information

TECHNICAL DATA SHEET AIRCRAFT GROUND POWER UNIT MODEL NO. B809D-1

TECHNICAL DATA SHEET AIRCRAFT GROUND POWER UNIT MODEL NO. B809D-1 COGNIZANT SERVICE: U.S.A.F. NATIONAL STOCK NUMBER: 6115-01-502-7927 OVERALL DIMENSIONS AND WEIGHT: Height: 63 Inches Length: 103 Inches Width: 66 Inches Weight (Dry): 4,372 Lbs. FUNCTIONAL DESCRIPTION:

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

SECTION LIFT ARM PARKING GATES

SECTION LIFT ARM PARKING GATES St. Anthony of Padua Catholic Church Phase I The Woodlands, Texas JRA Proj. No. 15004 Issued for Bidding - 1/20/2016 SECTION 11 12 33.13 LIFT ARM PARKING GATES PART 1 - GENERAL 1.01 SUMMARY A. Section

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

Packaged Pump Sets FOR DIESEL FUEL OIL APPLICATION. Packaged Pump Sets for Diesel/Fuel Oil Application Page 1

Packaged Pump Sets FOR DIESEL FUEL OIL APPLICATION. Packaged Pump Sets for Diesel/Fuel Oil Application Page 1 Packaged Pump Sets for Diesel/Fuel Oil Application Page 1 Packaged Pump Sets FOR DIESEL FUEL OIL APPLICATION Packaged Pump Sets for Diesel/Fuel Oil Application Page 2 Description Simplex SPS Series Packaged

More information

Parking Control Equipment Vehicle Fare Collection Roadway Construction Roadway Equipment

Parking Control Equipment Vehicle Fare Collection Roadway Construction Roadway Equipment 11 12 00 Parking Control Equipment 11 12 33 Parking Gates 11 12 33.13 Lift Arm Parking Gates 34 52 00 Vehicle Fare Collection 34 52 33 Vehicle Fare Gates 34 71 00 Roadway Construction 34 71 13.19 Vehicle

More information

STATEMENT OF WORK. Sinnemahoning State Park Cameron County, Pennsylvania

STATEMENT OF WORK. Sinnemahoning State Park Cameron County, Pennsylvania STATEMENT OF WORK Purchase of One (1) LP Gas (Propane) Standby Generator Set and One (1) Service Entrance Rated Automatic Transfer Switch For Delivery to Visitors Center Sinnemahoning State Park Cameron

More information

Installation and Maintenance Manual

Installation and Maintenance Manual Installation and Maintenance Manual Swing Gate Operator Model HL410-21 & HL410L-21 2 Contents Contents Parts & Components 3 Specifications & Capacities 4 Safety Information 6 Installer 6 End User 7 General

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

BOLLARDS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BRITISH PERIMETER SECURITY SPECIALISTS

BOLLARDS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BRITISH PERIMETER SECURITY SPECIALISTS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BOLLARDS BRITISH PERIMETER SECURITY SPECIALISTS Frontier Pitts Ltd., Crompton House, Crompton Way, Crawley, RH10 9QZ tel +44 (0)1293

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION

More information

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D

Pyrolance, LLC SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D SPECIFICATIONS FOR DIESEL ENGINE DRIVEN ULTRA HIGH PRESSURE PIERCING AND FIRE FIGHTING SYSTEM L 1000 W-D 1 SPECIFICATIONS FOR FIRE FIGHTING SYSTEM FIRE FIGHTING AND PIERCING SPECIFICATIONS Scope and General

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES

More information

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

MAG. FLB100 series Pedestrian Automatic Flap Barrier. General Description. Application. Features. Specification sheet. Date: April 2012, Revision: V1

MAG. FLB100 series Pedestrian Automatic Flap Barrier. General Description. Application. Features. Specification sheet. Date: April 2012, Revision: V1 Specification sheet FLB100 series Pedestrian Automatic Flap Barrier MAG Date: April 2012, Revision: V1 General Description MAG FLB101 and FLB102 is brand new product of MAG. Flap barrier, as the upgraded

More information

BOLLARDS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BRITISH PERIMETER SECURITY SPECIALISTS

BOLLARDS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BRITISH PERIMETER SECURITY SPECIALISTS GATES BARRIERS BLOCKERS BOLLARDS PEDESTRIAN FRONTIER PITTS SECURITY BOLLARDS BRITISH PERIMETER SECURITY SPECIALISTS Frontier Pitts Ltd., Crompton House, Crompton Way, Crawley, RH10 9QZ tel +44 (0)1293

More information

SAMPLE SPECIFICATIONS

SAMPLE SPECIFICATIONS SAMPLE SPECIFICATIONS CONTENTS PART 1 GENERAL...H1a-12 1.1 DEAERATOR SPECIFICATION...H1a-12 PART 2 PRODUCTS...H1a-12 2.1 HARDWARE...H1a-12 A. Deaerator...H1a-12 B. Make Up Valve and Controller...H1a-14

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

APOLLO Gate Operators, Inc.

APOLLO Gate Operators, Inc. APOLLO Gate Operators, Inc. Model 3500ETL/3600ETL Commercial Swing Gate Operator INSTALLATION MANUAL 01/08 CONTENTS IMPORTANT SAFETY INSTRUCTIONS. 3 Applications... 4 Pre-Installation Checklist... 5 Parts

More information

Installation/Owner s Manual 1601 / 1602

Installation/Owner s Manual 1601 / 1602 CFORMS TO ANSI/UL-325 CERTIFIED TO CAN/CSA C22.2 NO. 247 CLASS HP MODEL SERIAL 53382 VEHICULAR GATE OPERATOR DoorKing, Inc., Inglewood, CA Installation/Owner s Manual 60 / 602 Barrier Gate Operator Use

More information

MODEL B3X SERIES HYDRAULIC BOLLARD

MODEL B3X SERIES HYDRAULIC BOLLARD MODEL B3X SERIES HYDRAULIC BOLLARD INSTALLATION AND OPERATIONS MANUAL Corporate Office & Tech Support: 5900 S. Lake Forest Drive, Suite 230 McKinney, TX 75070 Phone: (972) 385-7899 Toll Free: (800) 367-0387

More information

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

UL 325 COMPLIANT CSI # Gate Operators. Gate-safe: during power outages, a magnetic lock releases a closed gate to permit emergency access.

UL 325 COMPLIANT CSI # Gate Operators. Gate-safe: during power outages, a magnetic lock releases a closed gate to permit emergency access. Model 75 Invisible UL 325 COMPLIANT CSI # 282 Gate Operators Model 75 Kits include: Swing Gate Operator The Model 75 hydraulic swing gate operator is designed specifically for underground installation

More information

ASVC2 OWNER S MANUAL. Vane Cutter PART # MACHINERY DIVISION

ASVC2 OWNER S MANUAL. Vane Cutter PART # MACHINERY DIVISION A S ASVC2 Vane Cutter PART # 43013 MACHINERY DIVISION OWNER S MANUAL -1- INTRODUCTION The ASVC2 Hollow Vane Cutting Machine was designed utilizing the best current technology to provide greater reliability.

More information

SECTION H4 BOILERMATE DEAERATORS

SECTION H4 BOILERMATE DEAERATORS SAMPLE SPECIFICATIONS PART 1 SECTION H4 BOILERMATE DEAERATORS GENERAL...H4-14 1.01 General...H4-14 PART 2 PRODUCTS...H4-14 2.01 Hardware...H4-14 A. Deaerator...H4-14 B. Make Up Valve and Controller...H4-15

More information

Regenerative power door operator for moderate to high traffic applications SERIES ADAEZ LOW ENERGY OPERATOR CATALOG

Regenerative power door operator for moderate to high traffic applications SERIES ADAEZ LOW ENERGY OPERATOR CATALOG Regenerative power door operator for moderate to high traffic applications 5800 SERIES ADAEZ CATALOG INTRODUCTION As one of the world s only regenerative power door operators, Norton s 5800 Series ADAEZ

More information

Model 712 Cable Crash Beam Vehicle Barrier

Model 712 Cable Crash Beam Vehicle Barrier Installation and Operations Manual Model 712 TABLE OF CONTENTS iii Model 712 Cable Crash Beam Vehicle Barrier OPERATIONS & MAINTENANCE MANUAL B&B ARMR Corporate Office & Technical Support: 5900 S. Lake

More information

ALVARADO (1029 mm) 25 (635 mm) 36.5 (927.1 mm)

ALVARADO (1029 mm) 25 (635 mm) 36.5 (927.1 mm) ALVARADO EDCX Bullnose Waist High Turnstile Technical Specifications Dimensions Unit Height: Unit Width: Unit Depth: 40.5 (1029 mm) 25 (635 mm) 36.5 (927.1 mm) Materials Cabinet: Formed and welded 14 gauge

More information

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual Series 386 Electrically Operated Non Automatic Switches J design 600 amps DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death. WARNINGisusedinthismanualtowarn

More information

SECTION 12 - CONSTRUCTION AREA TRAFFIC CONTROL TABLE OF CONTENTS

SECTION 12 - CONSTRUCTION AREA TRAFFIC CONTROL TABLE OF CONTENTS SECTION 12 - CONSTRUCTION AREA TRAFFIC CONTROL TABLE OF CONTENTS Section Page 12-1 GENERAL...12.1 12-2 FLAGGING...12.1 12-2.01 Flaggers...12.1 12-2.02 Flagging Costs...12.1 12-3 TRAFFIC-HANDLING EQUIPMENT

More information

KAVASS SECURITY TECH LIMITED

KAVASS SECURITY TECH LIMITED KAVASS SECURITY TECH LIMITED Tel:+86-571-88690663 Email: info@ikavass.com Web: www.ikavass.com Head office: 6th F, T5 EFC, 89# Lianchuang St.,Yuhang Dist., Hangzhou Zhejiang China. Factory: 46# Tianyang

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

INDEX COMPANY PROFILE. Based. Heald 800 (M800CR4) Roadblocker Test B Heald 1200 European Vehicle (HCR4M1200RB Test B

INDEX COMPANY PROFILE. Based. Heald 800 (M800CR4) Roadblocker Test B Heald 1200 European Vehicle (HCR4M1200RB Test B COMPANY PROFILE INDEX Based on the east coast of England, Heald have over 20 years experience in the field of high security barrier systems and a proven track record that is difficult to surpass. Sites

More information

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3) Door Control Board: Board 1Ø4 for PM/SSC 61111-149 (R3) 2000-08-31 2000, 1992 KONE Inc. Unpublished work. All rights reserved. No portion of this volume may be used or reproduced in any manner without

More information

Regenerative power door operator for moderate to high traffic applications SERIES ADAEZ LOW ENERGY OPERATOR CATALOG

Regenerative power door operator for moderate to high traffic applications SERIES ADAEZ LOW ENERGY OPERATOR CATALOG Regenerative power door operator for moderate to high traffic applications 5800 SERIES ADAEZ CATALOG INTRODUCTION As one of the world s only regenerative power door operators, Norton s ADAEZ Series is

More information

Electropneumatic Timing Relays Series 7000 Industrial

Electropneumatic Timing Relays Series 7000 Industrial DESIGN FEATURES Available in On-Delay, True Off-Delay, and On/Off-Delay. Timing from 0.1 seconds to 60 minutes, fully calibrated in linear increments. Oversize time-calibrated adjustment knobs, serrated

More information

Model 400. Opening a Whole New World: FAAC Swing Gate Systems SWEETS UL 325 COMPLIANT CSI # Gate Operators

Model 400. Opening a Whole New World: FAAC Swing Gate Systems SWEETS UL 325 COMPLIANT CSI # Gate Operators Look for us in SWEETS 2006 landscape architect directory and at: www.sweets.com Opening a Whole New World: FAAC Swing Gate Systems Model 400 The Model 400 is specifically designed for situations needing

More information

Declaration of Conformity

Declaration of Conformity Declaration of Conformity We, Manufacturer: Spartanics Ltd. 3605 Edison Place Rolling Meadows, Illinois 60008 Phone: 847-394-5700 Fax: 847-394-0409 USA ENGLISH declare under our sole responsibility that

More information

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates Issued 2005/06/01 Section 16239 Power Generation to 30 kw Page 1 of 7 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01355 Waste Management and Disposal..2 Section 01810 Commissioning..3 Section 03100 Concrete

More information

ROGERS MACHINERY COMPANY, INC

ROGERS MACHINERY COMPANY, INC KOBELCO KNW SERIES Sample Specifications ROGERS MACHINERY COMPANY, INC WATER-COOLED, OIL-FREE AIR COMPRESSOR Frame 00 20-50 HP 2110_00.doc Effective: 03/24/17 Supersedes: 10-11-13 Page 1 of 8 1. SPECIFICATION

More information

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600 MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES MV600 TABLE OF CONTENTS PART I GENERAL DESCRIPTION... PAGE 2 PART II FUNCTIONS... PAGE 2 PART III INSTALLATION... PAGE 3 PART IV INITIAL INSTALLATION

More information

Instruction Manual. Vibration Calibrators VC10 VC11 VC12 VC13

Instruction Manual. Vibration Calibrators VC10 VC11 VC12 VC13 Instruction Manual Vibration Calibrators VC10 VC11 VC12 VC13 Metra Mess- und Frequenztechnik Radebeul Meissner Str. 58 D-01445 Radebeul / Germany Tel. +49-351 8492104 Fax +49-351 8492169 Email: Info@MMF.de

More information

Model H/HB Heavy-Duty Industrial Drawbar Door Operator Safety, Installation and Service Manual

Model H/HB Heavy-Duty Industrial Drawbar Door Operator Safety, Installation and Service Manual Model H/HB Heavy-Duty Industrial Drawbar Door Operator Safety, Installation and Service Manual OSCO requires use of an electric edge or photoelectric control for pedestrian protection on all automatic

More information

StrongArmCRASH M30 ( K4) M50 ( K12) Patent Pending. Patent Pending

StrongArmCRASH M30 ( K4) M50 ( K12) Patent Pending. Patent Pending CRASH StrongArmCRASH TM M30 ( K4) Patent Pending M50 ( K12) Patent Pending StrongArmCRASHTM ULTIMATE HARDENED SECURITY StrongArm M30 & M50 take barrier arms to the extreme. These machines stop a 15,000

More information

(1032 mm) 30.5 (775 mm) 44 ( mm)

(1032 mm) 30.5 (775 mm) 44 ( mm) ALVARADO EDCX-EK Waist High Turnstile Technical Specifications Dimensions Unit Height: Unit Width: Unit Depth: 40.625 (1032 mm) 30.5 (775 mm) 44 (1117.6 mm) Materials Cabinet: Formed and welded 14 gauge

More information

MALSR APPROACH LIGHTING. Medium-Intensity Approach Lighting System WITH ELEVATED SEQUENCED FLASHERS AND STEADY BURNING LIGHTS

MALSR APPROACH LIGHTING. Medium-Intensity Approach Lighting System WITH ELEVATED SEQUENCED FLASHERS AND STEADY BURNING LIGHTS Medium-Intensity Approach Lighting System WITH ELEVATED SEQUENCED FLASHERS AND STEADY BURNING LIGHTS Compliance with Standards FAA: Uses Designed according to FAA-E-2325 The approach lighting system with

More information

ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG

ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG ARCHITECTURAL DOOR HARDWARE POWER SUPPLIES & TRANSFORMER CATALOG January 1, 2017 v3 West Coast Office (800) 544-4422 East Coast Office (800) 225-6737 intldoorclosers.com Index POWER SUPPLIES & TRANSFORMERS

More information

January 2007 Approval Guide Fixed Extinguishing Systems 5-57

January 2007 Approval Guide Fixed Extinguishing Systems 5-57 Fixed Extinguishing Systems 5-57 CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443 High Pressure System Equipment. Automatic Actuator. 1-026-02, -0250. Alarm. 1-003-0033, -0070, -0071,

More information

Sample Specifications 2110_KA.DOC KOBELCO KNW SERIES 1 OF 10 AIR-COOLED, OIL FREE AIR COMPRESSOR Frame 0, 1, HP

Sample Specifications 2110_KA.DOC KOBELCO KNW SERIES 1 OF 10 AIR-COOLED, OIL FREE AIR COMPRESSOR Frame 0, 1, HP KOBELCO KNW SERIES 1 OF 10 1. SPECIFICATIONS SCOPE 1.1 This specification covers the requirement for supply of a packaged oil-free rotary screw air compressor, Kobelco KNW Series model. 1.2 Any and all

More information

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker

More information

MODEL ELC-12/40-CVM-D BATTERY CHARGER

MODEL ELC-12/40-CVM-D BATTERY CHARGER NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING

More information