WELCOME AND INTRODUCTORY REMARKS
|
|
- Susanna Miles
- 5 years ago
- Views:
Transcription
1 WELCOME AND INTRODUCTORY REMARKS Robust Power Workshop , Per Lamell, F
2 SAFETY FIRST Please note where the nearest emergency exits, fire extinguishers, gathering place and defibrillators are. 2
3 AGENDA The Office Nuclear Power in Sweden Forsmark NPP Major event at Forsmark NPP OPC event at F3 May 30, 2013 Fukushima The future for Forsmark NPP An introductory conclusion 3
4 PARTICIPANT FROM FKA NEEA OFFICE NEE Electrical Engineering 50 employed 46 consultants NEEA Electrical Analysis and Plant Engineering (Portfolio investment) Johan Berg NEES System Design Engineering Electrical NEEE Component Design and Documentation Electrical 1 NEEI Component Design and Documentation Electrical 2 Project Sponsor Electrical Analysis Coordination of Electrical Design Maintenance with Electrical Design 4
5 HISTORY OF NUCLEAR POWER IN SWEDEN Research and education (Heavy water, Swedish nuclear weapon program) R1 started July located at KTH 27 meter down in bedrock 300 kw -> 1 MW (AB Atomenergi) R0 Studvik when critical 1959 was a so-called zero-power reactor R2 in Studvik started 1960 (-2005) 1963 first electricity produced R3 in Ågesta (to -73), provided the suburb Farsta (Stockholm) with district heating (Vattenfall and AB Atomenergi) R4 in Marviken outside Norrköping (no operation, oil power plant) 1972 operation of Sweden's first commercial nuclear power plant, Oskarshamn 1 (ASEA-Atom - Merger of the Asea nuclear power department and AB Atomenergi's technical department) 5
6 HISTORY OF NUCLEAR POWER IN SWEDEN CONT. NET POWER Ringhals NPP RAB (Main owner: Vattenfall AB) R1 (BWR, 865 MW, in op. 1976, planning to close 2020) R2 (PWR, 865 MW, in op. 1975, planning to close 2019) R3 (PWR, 1064 MW, in op. 1981) R4 (PWR, 1130 MW, in op. 1983) Forsmark NPP FKA (Main owner: Vattenfall AB) F1 (BWR, 984 MW, in op. 1980) F2 (BWR 1120 MW, in op. 1981) F3 (BWR, 1167 MW, in op. 1985) Oskarshamn NPP OKG (main owner: Uniper/EON) O1 (BWR, 473 MW, in op. 1972, shut down 2017) O2 (BWR, 638 MW, in op. 1974, shut down 2015) O3 (BWR, 1400 MW, in op. 1985) Barsebäck NPP (main owner: Uniper/EON) B1 (BWR, 600 MW, in op. 1975, shut down 1999 in decom.) B2 (BWR, 600 MW, in op. 1977, shut down 2005 in decom.) 6
7 FORSMARK PLANT AND VILLAGE 7
8 FORSMARK SITE Forsmark 1 Forsmark 2 Forsmark 3 Gasturbine 70 kv Switchyard: FT kv for F3 Switchyard: FT kv for F1 and F2 Switchyard: ÄT66-70kV 8
9 MAJOR EVENTS IN FORSMARK Loss of external power and loss of power supply from 2 of 4 diesel generators Forsmark 1 (July 25, 2006) Lightning strike tripped all eight main circulation pumps at Forsmark 2 (June 13, 2008) Lightning strike causing voltage transient in station AC net Forsmark 3, (July 13, 2012 ) Loss of two phases of the external grid during outage shutdown with loss of decay heat removal (May ) 9
10 LOSS OF EXTERNAL POWER AND LOSS OF POWER SUPPLY FROM 2 OF 4 DIESEL GENERATORS FORSMARK 1 (JULY 25, 2006) Unit breaker open X 400 kv 13:20:20 -> 13:42:01 70 kv M Gas turbine X Plant generator 6 kv 500 V A XM Diesel 654A V AC C M Diesel 654A V AC R101.A11 656T101.A11 655R101.A11 656T101.A11 Turbine 655B R102 K1 K1 T1 T8 Blocking XX Blocking X Blocking 655R B101 T8 655R R T1 4 Q29 Q29 T9 656T kva 0,5/0,5 kv T9 656T kva 0,5/0,5 kv Q2 Q2 500 V 655R102.A23 656A T101.A V AC 655R102.A23 656A T101.A V AC
11 LIGHTNING STRIKE TRIPPED ALL EIGHT MAIN CIRCULATION PUMPS AT FORSMARK 2 (JUNE 13, 2008) Normal operation Voltage disrupt DC busbar ESF MCP (Main Circulation Pump) (Energy storage Flywheel) I max 11
12 LIGHTNING STRIKE CAUSING VOLTAGE TRANSIENT IN 662.WD1 STATION AC NET FORSMARK 3, (JULY 13, 2012 ) 677.TD1.A TD1.T1 677.TD1.A UD11.U1 671.BD11.B1.B4 677.UD1 677.UD2.A11.A11 System boarder Safety 677.UD1.U1 643.WD1 660 V AC 671.WA1 677.UD2.U1 671.UD12.U1 677.TD2.T1 677.TD2.A TD2.A11 Non-safety 677.TD1.A UD1 677.UD2.A TD2.A22.A WD1.W1 677.WD2.W1 380 V AC loaded loaded unloaded unloaded A-sub: Unaffected 677UC1 677UB2 Faulty Degraded thyristor module thyristor module 677UD1 och 677UD2 Faulty thyristor module 12
13 LOSS OF TWO PHASES OF THE EXTERNAL GRID DURING OUTAGE SHUTDOWN WITH LOSS OF DECAY HEAT REMOVAL (MAY ) Connected to F2 70 kv switchyard was disconnected Outage for about 10 days 400 kv Residual heat removal pumps trip Phase unbalance protection trip motors - Byron 2 January Byron 1 February 28 Unit breaker: T31-D400-S open (maintenance) T31-E400-S initial closed Important! The generator step-up transformer has a Y0-Δ (400 kv/20.5 kv) coupling. EDG failed to start Simulating of the fault case U L1-L2= 102%, L2-L3= 57% och L3-L1= 78% which gives a mean value of 79%. L1 L2 L3 13
14 TESTING OF THE VOLTAGE REGULATOR SETTINGS AND LIMITER Voltage and current signal to the voltage regulator and limiter 2013 the second year of using of the testing procedure 2012 connected to standby power 70 kv Three phase testing equipment connected 30 May 2013 Connection terminals for an updated testing procedure Current signal to the overload 14 and negative sequence protection
15 RELAY PROTECTION THAT ACTIVATED THE OPENING OF THE UNIT BREAKER AT 400 KV SWITCHYARD AVR Trip Overload Trip signal to open the generator breaker (already open) Trip Negative sequence Step 1. Trip signal to open the unit breaker Trip Negative sequence Step 2. Trip signal to open the generator 15 breaker (already open)
16 MAIN CONTROL ROOM First impression of the event at the control room: The light in the control room was lower Operators heard sounds that was identified as typical of motors running on unbalance voltage. Unit breaker at the 400 kv switchyard signaled both on and off position. Several alarms occurred both from: the switchyard from objects that had tripped due to phase unbalance (rectifiers and induction machines driven objects) residual heat removal pump stopped 16
17 RESTORE OF THE POWER SYSTEM Start EDG and start loading objects in B-train 10:15 Reset of Overload protection (phase unbalance protection) on pumps RHR restored in one train after 17 min Start EDG and start loading objects in A-train 10:18 Start EDG and start loading objects in C-train 10:26 Start EDG and start loading objects in D-train 10:36 All safety trains restored after 35 min Restoration of offsite power 10:44 The offsite power restored 22:00 The parallel 400 kv unit breaker was restored and EDG stopped Compensatory measure 03:07 following day One EDG running on it s own train 17
18 FUKUSHIMA DAIICHI ACCIDENT, MARCH 11,
19 A TOOL BOX OF MITIGATING ACTIONS Design Process Integral testing Electric separation Unbalance protection Transient overvoltage protection (surge arresters) Analysis (simulation) of postulated disturbances V&V Transient registration Supervision Compensatory measures during operation Island operation of DG during lightning and electrical maintenance No major electrical work until the lid is off (decay heat, availability of water) Specific plan during challenging plant modifications Classic approach Analysis of disturbances Reverse approach What 19 can we withstand?
20 ELECTRIC SEPARATION TOOL BOX Feed of one or two trains from standby network Both non-safety and safety busbar Only safety busbar Active protection trigger happy Feed from different locations in the grid (only applicable in some plants) Filter MG-set (or static) Separate between safety and non-safety Separate sensitive equipment (UPS) Electronic switch to be or not to be? Rectifier as a barrier Breaker before rectifier w or w/o automatic restart Cooperation with vendors How to specify at procurement? 20
21 FORMARK PLANNING HORIZON Our mission - Ensure safe and stable long-term operation Investments (target approx MEUR) More focus on maintenance 21
22 AN INTRODUCTORY CONCLUSION Robust power supply system is one of the most essential aspects for safety at nuclear power plants worldwide. This workshop shall discuss the recent progress in achieving a better understanding of "new" electrical phenomena that occurred recently, like Open Phase Conditions. This understanding will lead to improved countermeasures and to an upgraded defence-in-depthconcept. The results of our meeting shall contribute to the progress for a more reliable power supply system in the near future. Welcome! 22
23 QUESTIONS? 23
24 THANKS 24
Erik Sandqvist Principal Engineer Power Systems WSE 12.1_Bl23 rev 1,
Traditional NPP electric power systems and modern equipment - sensitivity to net disturbances The original design and the introduction of modern equipment Erik Sandqvist Principal Engineer Power Systems
More informationLESSONS LEARNED FORSMARK EVENT Presented To IEEEE
LESSONS LEARNED FORSMARK EVENT Presented To IEEEE Thomas Koshy Member of the Task Group on Forsmark Chief of Mechanical & Electrical Engineering Office of Research, USNRC Thomas.Koshy@nrc.gov 1 Agenda
More informationThe IAEA does not normally maintain stocks of reports in this series.
IAEA-TECDOC- The IAEA does not normally maintain stocks of reports in this series. However, microfiche copies SAFETY ASPECTS OF STATION BLACKOUT AT NUCLEAR POWER PLANTS IAEA, VIENNA, 1985 IAEA-TECDOC-332
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More information2015 WDC Disturbance and Protection Standards Overview
NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationGrounding Of Standby & Emergency Power Systems
July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due
More informationHawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER
1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationService and Rehabilitation Electrical Power Systems
Service and Rehabilitation Electrical Power Systems From water to wire 3 ANDRITZ HYDRO Electrical Power System Modernization and rehabilitation International technology group ANDRITZ is a globally leading
More informationSurabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality
Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100
More informationForsmark 12. S3K Applications. Thomas Smed US User Group Meeting Arizona, October 2008
Forsmark 12 S3K Applications Thomas Smed US User Group Meeting Arizona, October 2008 Introduction It is well-known that we have vast experience in providing S3R (and RAMONA) to training simulators It may
More informationTransient Analysis for Simulator Validation. Jeffrey A. Borkowski 2008 US Users Group Meeting Tempe, Arizona October
Transient Analysis for Simulator Validation Jeffrey A. Borkowski 2008 US Users Group Meeting Tempe, Arizona October 22-24 2008 Advanced Training Simulator Models Engineering-grade model core model S3R
More informationAppendix A. Power Management System Test Guidelines
Appendix A Power Management System Test Guidelines The MTS DP Committee wants to thank Don Wilkes of Minden Engineering Company for his authorship of this appendix to the Test Guidelines Table of Contents
More informationCSNI Draft Report DEFENCE IN DEPTH OF ELECTRICAL SYSTEMS AND GRID INTERACTION. Final DIDELSYS Task Group Report
CSNI Draft Report DEFENCE IN DEPTH OF ELECTRICAL SYSTEMS AND GRID INTERACTION Final DIDELSYS Task Group Report 1 2 Forward The July 2006 Forsmark-1 event identified a number of design deficiencies related
More informationSolar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011
Solar Development in New Jersey, and PV Impacts on the Distribution System Carnegie Mellon Conference on the Electricity Industry - March 9, 2011 Jim Calore Public Service Electric & Gas Co. Overview This
More informationREDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION
REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi
More informationPOWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011
POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL
More informationCabo Verde s new Renewable-Energy-Friendly Grid Code
Cabo Verde s new Renewable-Energy-Friendly Grid Code Bernd Weise DIgSILENT GmbH International Workshop on Renewable Energy Development in Macaronesia and West Africa Praia, Cabo Verde, May 30-31, 2016
More informationSouthern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management
Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements
More informationModular Standardized Electrical and Control Solutions for Fast Track Projects
Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive
More informationTREAT Startup Update
Resumption of Transient Testing Program TREAT Startup Update John D. Bumgardner Director, Resumption of Transient Testing Program December 5 th, 2018 1 Facility Location 2 Nuclear Fuels Development Requires
More informationThe Strategic reserve - why and how? Joakim Cejie Miljö- och energidepartementet
The Strategic reserve - why and how? Joakim Cejie Miljö- och energidepartementet Agenda The history behind it Generation adequacy- the current situation recent activities The current system size period
More informationMargarett Jolly DG Manager, Consolidated Edison Company of New York, Inc
Margarett Jolly DG Manager, Consolidated Edison Company of New York, Inc Con Edison s Infrastructure Delivers Energy To New York City And Westchester 3.3 million electric customers 1.1 million gas customers
More informationPower Systems Trainer
Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,
More informationIntegration of Smart Grids and Renewables Achievements in Sweden
Integration of Smart Grids and Renewables Achievements in Sweden Dr Magnus Olofsson ISGAN Workshop Yokohama, 8 March 2016 In Summary Governmental Actions on Smart Grid Four cases: Smart Grid Gotland Increased
More informationB. HOLMQVIST Nuclear Fuel Division, ABB Atom AB, Vasteras, Sweden
I Iflllll IPIBM1I IHtl!!!! Blini Vllll! «! all REDUCTION OF COST OF POOR QUALITY IN NUCLEAR FUEL MANUFACTURING XA0055764 B. HOLMQVIST Nuclear Fuel Division, ABB Atom AB, Vasteras, Sweden Abstract Within
More informationVattenfall Capital Markets Day 2009
Vattenfall Capital Markets Day 2009 Presentation by: Helene Biström Senior Executive Vice President Head of Business Group Pan Europe Amsterdam, 23 September 2009 Contents Overview Business Group Pan Europe
More informationEvaluation of a Gearbox s High-Temperature Trip
42-46 tlt case study 2-04 1/13/04 4:09 PM Page 42 Case Study Evaluation of a Gearbox s High-Temperature Trip By Vinod Munshi, John Bietola, Ken Lavigne, Malcolm Towrie and George Staniewski (Member, STLE)
More informationAPR1400 Electric System Design. KHNP KEPCO E&C November 29, 2017
APR1400 Electric System Design KHNP KEPCO E&C November 29, 2017 Contents 1. Introduction 2. Offsite Power System Design 3. Onsite Power System Design Auxiliary Power System DC & IP System Onsite Power
More informationABB Power Cables Service Turnkey Cable Repairs Three Reference Cases
ABB Power Cables Service, ABB Power Cables Service Turnkey Cable Repairs Three Reference Cases July 16, 2013 Slide 1 ABB Power Cables Service Success Repair Story Wind Farm, United Kingdom, March 2012
More informationBasics of Paralleling
Basics of Paralleling Revised: February 1, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Discuss basic paralleling control functions to gain a better understanding
More informationSeabrook Substation Reliability Improvement Project
New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationEnergy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director
Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th Alex Bettencourt Managing Director National Association Made Up of Entire Industry Utilities Industry Academia / R&D
More informationDouble earth fault in a PSP during back to back launching sequence
Double earth fault in a PSP during back to back launching sequence Jean-Louis DROMMI EDF Hydro Engineering Center, France Pump Storage Scheme, back to back launching Electricité de France Hydro Department
More informationAppendix G Examples and Recommended Methods
Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600
More informationEH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map
EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids
More informationUniversal Interconnection Technology Technology Roadmap Workshop. Associated Barriers to Distributed Generation
Universal Interconnection Technology Technology Roadmap Workshop Associated Barriers to Distributed Generation 7/25-26/2002 1 DG System Topics System Coordination Issues Present Day UIT System Issues Power
More informationHVDC. TMT&D provides the best and most economical HVDC system.
HVDC TMT&D HVDC TMT&D provides the best and most economical HVDC system. In 1955, TMT&D started the development of HVDC and is the leading HVDC supplier in Japan. TMT&D has continued to develop HVDC technology
More informationGRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS
GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS Prof. Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology Bombay OUTLINE Intoduction Grid
More informationCurrent Status of Fukushima Daiichi Nuclear Power Station & Lessons Learned from Experiences of the Great East Japan
These materials may contain sensitive information from TEPCO or other companies. Therefore, the usage of these materials outside of their intended goal is prohibited, alongside the showing or publication
More informationJames Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists
James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N. 010 848 389 trading as Power Drive Systems Generator Control Specialists 48A Ainsdale Street Telephone: 0500 800 225 P.O. Box 30 West Chermside, Qld
More informationTransformer oils - Production, performance and in-service behaviour
Transformer oils - Production, performance and in-service behaviour Johan Grövik Nynas AB TRANSFORM Partner Nynas Nynas AB founded 1928 Swedish based company Approximately 850 employees Turnover 2 billion
More informationDISTURBANCES IN THE EUROPEAN NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL SYSTEMS
Journal of ELECTRICAL ENGINEERING, VOL. 62, NO. 3, 2011, 173 180 REVIEWS - LETTERS - REPORTS DISTURBANCES IN THE EUROPEAN NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL SYSTEMS Alexander Duchac Marc Noël
More informationABB FACTS Grid connection of Wind Farms
Christian PAYERL ABB FACTS Grid connection of Wind Farms May 28, 2010 Slide 1 ABB Power of Wind May 28, 2010 Slide 2 ABB FACTS 300 engineers, highly skilled in the following disciplines: Development Marketing
More information2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited
More informationShunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian
Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission
More informationDESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)
DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN) -A.R. Subraaanian -R.A.A. Palani -J. Thomson A new 3.3 K.V. 4200 KVAR auto switching capacitor bank has been installed
More informationDISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase
PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More information2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT
41-348.11C SA-1 Generator Differential Relay - Class 1E 2.0 CONSTRUCTION The type SA-1 relay consists of: Restraint Circuit Sensing Circuit Trip Circuit Surge Protection Circuit Operating Circuit Amplifier
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationMEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices
MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect
More informationELECTRIC TRACTION.
ELECTRIC TRACTION www.koncar.hr MODERNISATION ELECTRIC TRACTION VEHICLES Company KON AR - ELECTRIC VEHICLES Inc. upgrades electric locomotives, electric multiple unit and electric tramcars. Upgrading proceedings
More informationSGT5-8000H/SCC5-8000H 1S. First experience of Commercial Operation at Irsching 4. Russia Power Moscow, March
SGT5-8000H/SCC5-8000H 1S First experience of Commercial Operation at Irsching 4 Russia Power Moscow, March 5 2012 Armin Städtler R&D Program Manager 8000H 8000H Overview Validation Status Summary Fig.
More informationT-Line Generator Control, Protection and Monitoring
T-Line Generator Control, Protection and Monitoring» Control. Monitor. Protect. SELCO T-Line The SELCO T-line offers a complete range of system components for generator control, protection and power monitoring.
More informationISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT
ISLANDING SCHEME FOR STATION DURING GRID BLACK-OUT By Girija Shankar Sharma, M.Tech (Power System), DGM (O&M-Opn), NTPC-Rihand, E-mail: gssharma@ntpc.co.in Presentation Points System Description and Grid
More informationDevelopment of Emergency Train Travel Function Provided by Stationary Energy Storage System
150 Hitachi Review Vol. 66 (2017), No. 2 Featured Articles III Development of Emergency Train Travel Function Provided by Stationary Energy System Yasunori Kume Hironori Kawatsu Takahiro Shimizu OVERVIEW:
More informationPCS AC POWER LINE CONDITIONERS. PCS H SERIES - THREE PHASE - 6 to 500 kva H - THREE PHASE SERVO ELECTRONIC DESIGN. AC - THREE PHASE - 6 TO 500 kva
PCS H - THREE PHASE - 6 to 500 kva POWER CONDITIONING PROTECTION against voltage fluctuations and line disturbances - ensuring a CLEAN supply. FEATURES Automatic Voltage Regulation Step less automated
More informationDesigning and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues
Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them
More informationProtective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON
21, rue d Artois, F-75008 PARIS B4-70 CIGRE 2016 http : //www.cigre.org Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON VILES Consulting
More informationBreakout Session 1 Report-out presentations
Breakout Session 1 Report-out presentations www.oe.energy.gov U.S. Department of Energy National 1000 Academy Independence of Engineering Ave., -SW BMED Washington, DC 20585 9/6/2011 1 Technical Topic
More informationLife Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic
Life Needs Power, Hannover Messe 2017 Inertia in Future Electrical Power Systems Challenges and Solutions Dr. Ervin Spahic siemens.com/energy-management Motivation Challenge of reduced synchronous generators
More informationControl System for a Diesel Generator and UPS
Control System for a Diesel Generator and UPS I. INTRODUCTION In recent years demand in the continuity of power supply in the local distributed areas is steadily increasing. Nowadays, more and more consumers
More informationExpect More From An Energy Storage Solution BATTERY FREE DC ENERGY STORAGE FOR UPS BILL WOLFE NORTHEAST REGIONAL MANAGER
Expect More From An Energy Storage Solution BATTERY FREE DC ENERGY STORAGE FOR UPS BILL WOLFE NORTHEAST REGIONAL MANAGER DC Energy Storage - ReGen Energy Re-cycle Markets / Applications Energy Re-cycling
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationExpected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)
Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li
More informationHope Creek Variable Frequency Drive
Hope Creek Variable Frequency Drive 2018 Power Plant Simulation Conference Houston, TX January 14-18, 2018 Hope Creek Variable Frequency Drive Simulation John Stone Senior Engineer - CORYS Presentation
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationPPHVC Power Quality Solutions. ABB PQC-STATCON Benefits and advantages
PPHVC Power Quality Solutions ABB PQC-STATCON Benefits and advantages Reasons for investing in power quality Poor power quality costs Sector Financial loss per incident Semi-conductors production(*) 3
More informationC PER. Center for Advanced Power Engineering Research C PER
Center for Advanced Power Engineering Research C PER 2017 Summer Research Planning Workshop Energy Storage Technologies and Application Roadmap Presented By: Johan Enslin Zucker Family Graduate Education
More informationStatic frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids
Static frequency converter couples US paper mill s 2-Hz and 0-Hz electricity grids Before 0 Hz was adopted as the standard frequency for electricity distribution in the USA, power companies across the
More informationBreaker failure relay REB 010
Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970138) Features Local redundant protection when the circuit breaker does not operate The technique with microprocessors
More informationMedium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.
Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution
More informationPOWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012
POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 PREPARED BY: Electricity System Operations Planning and Performance DATE: 5 June 2012 FINAL
More informationULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)
white paper ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) Electricity, flowing continuously through the grid, is something that most of today s amenities rely on. For any electrical device to
More informationHealth Monitoring of Rotating Equipment from Torsional Vibration Features
College of Engineering Health Monitoring of Rotating Equipment from Torsional Vibration Features Martin W. Trethewey Department of Mechanical and Nuclear Engineering Penn State University April 13, 2007
More informationPARALLELING SWITCHGEAR
ONBOARD VS TRADITIONAL IEEE Central Tennessee PARALLELING SWITCHGEAR Dustin Sperber Application Engineer Manager Nixon Power Services Objective for todays meeting: To examine the latest technology in paralleling
More informationSYSTEM EARTHING & PROTECTIVE EARTHING
Training Title SYSTEM EARTHING & PROTECTIVE EARTHING Training Duration 5 days Trainnig Dates & Venue System Earthing & Protective Earthing 5 02 06 June $3,750 Abu Dhabi, UAE In any of 5 star hotel. The
More informationWorld Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants
World Class Power Solutions Rectifiers For Stationary Battery Systems in Nuclear Power Plants General 2 1.1 Application Electronically controlled rectifier assemblies are used in conjunction with suitable
More informationProtection with distributed generation, experience with the Mont-Soleil wind farm project
Protection with distributed generation, experience with the Mont-Soleil wind farm project Florian Romanens IEEE Workshop 28 April 2011 Kursaal Bern Content BKW FMB Energie AG Mont-Soleil project Overview
More informationPower Conditioning of Microgrids and Co-Generation Systems
Power Conditioning of Microgrids and Co-Generation Systems Nothing protects quite like Piller piller.com Content 1 Introduction 3 2 Basic requirements of a stable isolated network 3 3 Requirements for
More informationCigre SC B4 Activities Towards HVDC Grids. HVDC Grid Workshop Belgium
Cigre SC B4 Activities Towards HVDC Grids Bjarne Andersen Chairman of Cigre Study Committee B4 HVDC and Power Electronics HVDC Grid Workshop Belgium 2014 1 Contents Why build HVDC Grids? Types of HVDC
More informationPQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads
PQC-STATCON PPHVC-Power Quality Solutions Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads Contents What is poor power quality? Reasons for investing
More informationU n i n t e r r u p t i b l e P o w e r S y s t e m
SMART ON-LINE UPS User s Manual U n i n t e r r u p t i b l e P o w e r S y s t e m Smart On-Line UPS 2KVA ~ 20KVA 20KVA Exhaust hole (16)Main breaker (12)Heat exhaust hole (15)Telephone (Rj11) or network
More informationBeyond Design Basis Analysis:
Executive Beyond Design Basis Analysis: Developments in UK s Approach and Perspective IAEA International Expert s Meeting on Severe Accident Prof. Ali Tehrani Principal Inspector Nuclear Safety March 2014
More informationDG SYNCHRONIZING &AMF PANEL
A 80, Sector 80, Phase 2, Noida 201305, Utter Pradesh, India DG SYNCHRONIZING &AMF PANEL Clients Bharat Petroleum Corp.Ltd PROJECT- DG Synchronization panel with AMF function. Design BY:- Errection By
More informationOutage dates (duration): March 2, 1993 to April 20, 1994 (1.1 years) Reactor age when outage began: 11.7 years
Sequoyah Unit 1 Soddy-Daisy, TN Owner: Tennessee Valley Authority Reactor type: Pressurized water reactor Commercial operations began: July 1, 1981 Outage dates (duration): March 2, 1993 to April 20, 1994
More informationUNIT 6: BATTERIES, UPS AND CABLES
UNIT 6: BATTERIES, UPS AND CABLES 6.1 Batteries 6.1.1 Introduction i. Definition of Batteries: Stores chemical energy in cells and converts them into electrical energy in the form of direct current (D.C);
More informationElectrical Test of STATCOM Valves
21, rue d Artois, F-75008 PARIS 619 CIGRE 2016 http : //www.cigre.org Electrical Test of STATCOM Valves Baoliang SHENG 1, Christer DANIELSSON 1, Rolf NEUBERT 2, Juha TURUNEN 3, Yuanliang LAN 4, Fan XU
More information3.2. Current Limiting Fuses. Contents
.2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse
More information3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.
41-348.1H Type SA-1 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are
More informationAPPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION
APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION Work Order No: File Reference: 16/2/1 This application form for the connection of small scale embedded generation is for small
More informationUnit Protection System for Pumped-Storage Power Stations
Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve
More informationPLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION
PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH
More informationFeatures of PSEC Educational Programs
Power Systems & Energy Course 2018 These intensive four-week programs are designed to strike the necessary balance between energy systems engineering theory and relevant, real-world applications. With
More informationUSER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4
USER S MANUAL PowerWalker VFI 1000 / 3000VA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION......... 2 3. SYSTEM DESCRIPTION......... 4 4. CABLE CONNECTION......... 7 5. OPERATION...... 8 6. TROUBLE
More informationThe Swedish Government Inquiry on Smart Grids
The Swedish Government Inquiry on Smart Grids Math Bollen Athens, Greece, 18 December 2010 Smart grid inquiry What are smart grids? Why do we need smart grids? State of deployment and development Conclusions
More information