Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Size: px
Start display at page:

Download "Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues"

Transcription

1 Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them Use simulation to compare different designs and maintenance strategies validate with measurements how to value pollution? Implement system changes again, validate with measurements 4/23/2008 Pollution-Resilent Electric Power System 2 1

2 Harmonic Voltage Distortion Pollution Rank #1, PQ Rank #3 Standard: IEEE 519 Metric: THD 95 ; level exceeded 5% of time limit at MV is 5.0% total, 3.0% any component 4/23/2008 Pollution-Resilent Electric Power System 3 Voltage Flicker 100 Step-wise Flicker 50 Voltage Magnitude (%) Time (s) Pollution Rank #2, PQ Rank #4 Standard: IEEE 1453 Metric: P ST ; short-term flicker coefficient planning limit is 0.9 4/23/2008 Pollution-Resilent Electric Power System 4 2

3 Transient Overvoltages Pollution Rank #3, PQ Rank #5 Standard: IEEE 1159 (plus EPRI reports) Metric: SATMORI 1.7 ; annual frequency of voltage transients at least 1.7 per-unit typical value of 1 per day? 4/23/2008 Pollution-Resilent Electric Power System 5 RMS Variations (Sags & Swells) (Similar to voltage flicker) Pollution Rank #4, PQ Rank #2 Standard: IEEE 1159 (plus EPRI reports) Metric: SARFI 70 ; annual frequency of sags to 70% voltage or below typical value of 20 4/23/2008 Pollution-Resilent Electric Power System 6 3

4 Momentary Interruptions (Sags below 10% voltage; followed by a voltage recovery transient when the fault clears) Pollution Rank #5, PQ Rank #1 Standard: IEEE 1366 Metric: MAIFI; frequency of interruptions up to 1 or 5 min typical value of 6 annually 4/23/2008 Pollution-Resilent Electric Power System 7 Benefits of Source Strength Reduce voltage sag magnitudes Absorb more harmonic current injection Reduce flicker magnitudes Note: these are probably what you think of as pollution No inherent effect on interruptions (aka reliability) or transients (another type of pollution) 4/23/2008 Pollution-Resilent Electric Power System 8 4

5 Source Effect on Sags Fault on Adjacent Feeder Downstream Fault V PCC 1 = Z A Z + Z S A V PCC 2 = Z A Z + Z + Z S F A 4/23/2008 Pollution-Resilent Electric Power System 9 Source Effect on Flicker & Harmonics Pst* TDD [%] Pst Lim Sk [MVA] S K P ST 2 kv = Z + Z = S S F N cf S K 4/23/2008 Pollution-Resilent Electric Power System 10 5

6 Source Effect Parallel Resonance Parallel Resonance of 5 MVA, 13.8-kV Capacitor MVA Transformer 12-MVA Transformer 200 Voltage (V) Frequency (H pu) 4/23/2008 Pollution-Resilent Electric Power System 11 How To Increase Source Strength Increase conductor sizes Increase substation transformer capacity Add a substation transformer Higher transmission voltage service Add a transmission line Express feeders (isolation from other load) Dedicated transformers (more isolation) 4/23/2008 Pollution-Resilent Electric Power System 12 6

7 Benefits of Sectionalizing Better interruption indices More RMS variations (they were interruptions before) No inherent impact on harmonics, flicker, or transients 4/23/2008 Pollution-Resilent Electric Power System 13 Permanent Fault Effect of Sectionalizing SARFI SAIFI SARFI SARFI SAIFI Temporary Fault SARFI MAIFI SARFI SARFI MAIFI 4/23/2008 Pollution-Resilent Electric Power System 14 7

8 Impact of Distributed Resources The effect is mixed, and benefits may accrue primarily to the DG owner Good Impacts: Higher source strength? Depends on interconnection Backup source may reduce long-term interruption indices Bad Impacts: Higher ground fault voltages on healthy phases May produce more flicker or harmonics 4/23/2008 Pollution-Resilent Electric Power System 15 DG Effect on Overcurrent Protection No Fuse Saving Loss of Sensitivity Sympathetic Tripping 4/23/2008 Pollution-Resilent Electric Power System 16 8

9 DG Impact on Reclosing Reclose Interval DG Must Disconnect Here DG has to disconnect early in the reclose interval, may lengthen to 2 5 seconds Dead time changes from instantaneous to momentary category of IEEE /23/2008 Pollution-Resilent Electric Power System 17 Reducing the Event Rate Helps both interruptions and RMS variations Upgraded lightning protection Arresters Overhead shield wires, with better grounding More insulation Vegetation management 4/23/2008 Pollution-Resilent Electric Power System 18 9

10 Other Measures Capacitor switching surge reduction Synchronous or zero-voltage control Preinsertion resistors Power electronic devices to reduce flicker or harmonics (STATCOM, DVAR, etc.) Passive harmonic filters PWM converters don t inject low-order harmonic currents 4/23/2008 Pollution-Resilent Electric Power System 19 Capacitor Switches Mitigation None 20-Ω Resistor Standard Inductor Enhanced-Duty Ind. Peak [p.u.] % >= 1.7 p.u /23/2008 Pollution-Resilent Electric Power System 20 10

11 2 No Mitigation g 1 Voltage (V pu) Time (ms) 4/23/2008 Pollution-Resilent Electric Power System 21 Pre-insertion Resistor Voltage (V pu) Time (ms) 4/23/2008 Pollution-Resilent Electric Power System 22 11

12 2 Pre-insertion Inductor y 1 Voltage (V pu) Time (ms) 4/23/2008 Pollution-Resilent Electric Power System 23 Why Do We Need PQ Simulation? Measurements take a long time Measurements are after the fact Simulation can be a virtual laboratory 4/23/2008 Pollution-Resilent Electric Power System 24 12

13 Stochastic Fault Application Rate (0.1 / mile / yr) Other Variables: Phases Involved Permanent? (20%) Resistance? (5 Ω) Each type makes a weighted contribution to MAIFI and SARFI 4/23/2008 Pollution-Resilent Electric Power System 25 Fault Analysis Flowchart Coil Pickup Contact Time dial Trip and Reset Times 100 Seconds Multiples of Pickup (M) 4/23/2008 Pollution-Resilent Electric Power System 26 13

14 Stochastic Load Variations 600 Power Time [s] Peak = MW 2% Level = MW 5% Level = MW Frequency Power [MW] % 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 4/23/2008 Pollution-Resilent Electric Power System 27 How Accurate Can This Be? Overcurrent device models are very good Utilities used these for decades They have been essential to protect life and property Voltage and current calculations are very good Utilities used these for decades They have been essential for equipment specification The greatest uncertainty lies in the number, types, and locations of faults, or the variation of harmonic and flicker injections Utilities do gather some statistics Benchmark over time with PQ measurements 4/23/2008 Pollution-Resilent Electric Power System 28 14

15 Conclusion You can t manage something unless you measure it Software tools need to produce figure-ofmerit outputs (SARFI, MAIFI, P ST, THD 95 ) How to assign value to the indices? EPRI software tools: PQ Planner (not used much) DSS (going open source!!) 4/23/2008 Pollution-Resilent Electric Power System 29 15

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems

CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements

More information

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History Early 1970 s Small Substation Transformers

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,

More information

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Breaker Technology Operational Advantages Development Schedule Dave Richardson, Ph.D.,P.E. Powell Power Electronic

More information

Copyright 2003 Advanced Power Technologies, Inc.

Copyright 2003 Advanced Power Technologies, Inc. Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design

More information

Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System

Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System A. INTRODUCTION This document outlines the technical requirements

More information

Sources, Effect, and melioration. Power Quality Problems. Asnil Elektro FT UNP

Sources, Effect, and melioration. Power Quality Problems. Asnil Elektro FT UNP Sources, Effect, and melioration of Power Quality Problems Asnil Elektro FT UNP Sources of Power Quality Problems Power Electrinic Devices Arcing Devices Load Switching Large Motor Starting Embedded Generation

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

ABB FACTS Grid connection of Wind Farms

ABB FACTS Grid connection of Wind Farms Christian PAYERL ABB FACTS Grid connection of Wind Farms May 28, 2010 Slide 1 ABB Power of Wind May 28, 2010 Slide 2 ABB FACTS 300 engineers, highly skilled in the following disciplines: Development Marketing

More information

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET) INTERNATIONAL International Journal of JOURNAL Electrical Engineering OF ELECTRICAL and Technology (IJEET), ENGINEERING ISSN 0976 & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances 29 Juli 2014 Page 1 Characteristics of the Project Parameter Detail

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS Prof. Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology Bombay OUTLINE Intoduction Grid

More information

Optimizing Emergency Power Systems for Health Care Applications

Optimizing Emergency Power Systems for Health Care Applications 2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan

More information

Power Systems Trainer

Power Systems Trainer Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,

More information

Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults

Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults Potential Negative Impact on Reliability of Distributed Generation under Temporary Faults Xuanchang Ran, Tianqi Hong Department of Electrical and Computer Engineering, New York University, Five Metro-tech

More information

Duke Energy Power Quality Today. Presented by: Kevin Little

Duke Energy Power Quality Today. Presented by: Kevin Little Duke Energy Power Quality Today Presented by: Kevin Little Who are We? US Franchised Electric & Gas 5 states: North Carolina, South Carolina, Indiana, Ohio and Kentucky 47,000 square miles of service area

More information

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The

More information

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

Using Hosting Capacity Methodology to Develop Simplified Screens for New Solar PV Interconnections

Using Hosting Capacity Methodology to Develop Simplified Screens for New Solar PV Interconnections Using Hosting Capacity Methodology to Develop Simplified Screens for New Solar PV Interconnections Jeff Smith, Matt Rylander EPRI Robert Broderick Sandia National Laboratory Barry Mather NREL 6 th International

More information

TD-2306B-001, Interconnecting Large 2-20MW Generation Systems. Employees involved with generation interconnection on electric distribution circuits.

TD-2306B-001, Interconnecting Large 2-20MW Generation Systems. Employees involved with generation interconnection on electric distribution circuits. SUMMARY The protection requirements for connecting new Distributed Generation (DG) have been modified to reduce the need for Direct Transfer Trip (DTT) schemes which are costly to employ and difficult

More information

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 2 August 2015 ISSN (online): 2349-784X Power System Stability Analysis on System Connected to Wind Power Generation with

More information

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1 Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1 A Guide for Iowa s Municipal Electric Utilities On the How the IEEE 1547 Distributed Generation Interconnection Standard Affects Solar

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

Targeted Application of STATCOM Technology in the Distribution Zone

Targeted Application of STATCOM Technology in the Distribution Zone Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008

IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008 IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008 Improving Power System Dynamic Performance in Laredo, TX Prepared by Paul Hassink (AEP) Paul Marken (GE) Rob O Keefe (AEP) Gerardo

More information

Distributed Generation

Distributed Generation Distributed Generation Presented by: Doug Fairchild & Chris Cooper 1 Agenda Hydro One Overview The state of DG in the Province of Ontario Technical Issues Operational Requirements Overview Control Room

More information

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device Australian Journal of Basic and Applied Sciences, 5(9): 1180-1187, 2011 ISSN 1991-8178 Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

More information

Small Generator Interconnection Program Interconnection Technical Requirements

Small Generator Interconnection Program Interconnection Technical Requirements General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator

More information

American Electric Power s Energy Storage Deployments

American Electric Power s Energy Storage Deployments American Electric Power s Energy Storage Deployments 1 2 American Electric Power : Company Profile The Evolution of the Electric Utility System Before Smart Grid: One-way power flow, simple interactions,

More information

The North Carolina solar experience: high penetration of utility-scale DER on the distribution system

The North Carolina solar experience: high penetration of utility-scale DER on the distribution system 1 The North Carolina solar experience: high penetration of utility-scale DER on the distribution system John W. Gajda, P.E. Duke Energy IEEE PES Working Group on Distributed Resources Integration 2 High

More information

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 01 July 2015 ISSN (online): 2349-784X Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC Ravindra Mohana

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection

More information

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies

Accidental Islanding of Distribution Systems with Multiple Distributed Generation Units of Various Technologies CIGRÉ-EPRI Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS Boston, MA, October 20-22, 2013 http : //www.cigre.org Accidental Islanding of Distribution Systems with Multiple Distributed Generation

More information

Presented By: Bob Uluski Electric Power Research Institute. July, 2011

Presented By: Bob Uluski Electric Power Research Institute. July, 2011 SMART DISTRIBUTION APPLICATIONS &THEIR INTEGRATION IN A SMART GRID ENVIRONMENT Presented By: Bob Uluski Electric Power Research Institute July, 2011 Key Smart Distribution Applications What are the major

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

PV Grid Integration Research in the U.S.

PV Grid Integration Research in the U.S. PV Grid Integration Research in the U.S. Barry Mather Ph.D. NREL- Power Systems Engineering Center HEPIA IEA PVPS Task 14 Utility Workshop Geneva, Switzerland March 31 st, 2014 NREL is a national laboratory

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

EPRI HVDC Research. Gary Sibilant, EPRI. August 30, 2011

EPRI HVDC Research. Gary Sibilant, EPRI. August 30, 2011 EPRI HVDC Research John Chan, Ram Adapa, Bernie Clairmont & Gary Sibilant, EPRI EPRI HVDC & FACTS Conference August 30, 2011 Presentation Contents 1. Team Members 2. Research Program Objective & Scope

More information

Self-Adaptive Relaying Scheme of Reclosers for Fuse Saving in Distribution Networks with DG

Self-Adaptive Relaying Scheme of Reclosers for Fuse Saving in Distribution Networks with DG 8 International Journal of Power and Energy Research, Vol. 1, No. 1, April 2017 https://dx.doi.org/10.22606/ijper.2017.11002 Self-Adaptive Relaying Scheme of Reclosers for Fuse Saving in Distribution Networks

More information

PHEV Design Impacts. Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010

PHEV Design Impacts. Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010 PHEV Design Impacts Jason Taylor Ph.D. South West Electric Distribution Exchange May 6 th, 2010 1 Annual Energy Usage Electrical Appliances Home Heating System Central Air Conditioning Refrigerator/Freezer

More information

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

Electric Power Delivery To Big Cities

Electric Power Delivery To Big Cities Problem Definition Electric Power Delivery To Big Cities a) Socio-economic incentives are a major factor in the movement of population to big cities b) Increasing demand of electric power has strained

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

4-Day Power System Analysis, Coordination, System Studies

4-Day Power System Analysis, Coordination, System Studies 4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our

More information

Item 1: Contents of the complete training & CV of the lecturer

Item 1: Contents of the complete training & CV of the lecturer Course DESIGN CONCEPTS + software SwitchgearDesign for SWITCHGEAR, SWITCHBOARDS, BUSDUCTS & SUBSTATIONS" Item 1: Contents of the complete training & CV of the lecturer Presented by Sergio Feitoza Costa

More information

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

Machine, Panel, and Plant Level Solutions

Machine, Panel, and Plant Level Solutions Machine, Panel, and Plant Level Solutions Mark Stephens, PE Manager Industrial Studies Electric Power Research Institute 942 Corridor Park Blvd Knoxville, Tennessee 37932 Phone 865.218.8022 mstephens@epri.com

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Testing Energy Storage Systems: From EVs to Utility Grid

Testing Energy Storage Systems: From EVs to Utility Grid Testing Energy Storage Systems: From EVs to Utility Grid Jonathan P. Murray Business Development Manager 2008 Bloomy Controls. All Rights Reserved Agenda Energy storage system landscape Electric vehicle

More information

Physical Design of a Volt/Var Implementation

Physical Design of a Volt/Var Implementation 1 Physical Design of a Volt/Var Implementation Hydro-Québec Distribution s approach Prepared by Bruno Fazio 2 Subjects Context Volt control Planning Control strategies and exploitation Var control Planning

More information

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,

More information

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems SECTION 9: ELECTRICAL POWER DISTRIBUTION ESE 470 Energy Distribution Systems 2 Introduction The Electrical Grid 3 Three main components to the electrical grid Generation ESE 450 Transmission Transmission

More information

Dynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West)

Dynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West) Dynamic Reactive Power Control By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West) Acknowledgement The author acknowledges with deep gratitude the experience

More information

Energy Security Electrical Islanding Approach and Assessment Tools. Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration

Energy Security Electrical Islanding Approach and Assessment Tools. Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration Energy Security Electrical Islanding Approach and Assessment Tools Dr. Bill Kramer Senior Research Engineer Distributed Energy Systems Integration Dr. Bill Kramer - 2 Electricity, Resources, & Building

More information

MEPPI Power Systems Engineering Division (PSED)

MEPPI Power Systems Engineering Division (PSED) Loss of Synchronous Generation Impacts and Mitigation MEPPI Power Systems Engineering Division (PSED) for EE500E Energy & Environment Seminar, University of WA, October 5, 2017 Agenda 1. An Active Industry

More information

34 th Hands-On Relay School

34 th Hands-On Relay School 34 th Hands-On Relay School Generation Track Overview Lecture Generator Design, Connections, and Grounding 1 Generator Main Components Stator Core lamination Winding Rotor Shaft Poles Slip rings Stator

More information

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid K. B. Mohd. Umar Ansari 1 PG Student [EPES], Dept. of EEE, AKG Engineering College, Ghaziabad, Uttar Pradesh, India

More information

Margarett Jolly DG Manager, Consolidated Edison Company of New York, Inc

Margarett Jolly DG Manager, Consolidated Edison Company of New York, Inc Margarett Jolly DG Manager, Consolidated Edison Company of New York, Inc Con Edison s Infrastructure Delivers Energy To New York City And Westchester 3.3 million electric customers 1.1 million gas customers

More information

Overview Overvoltage protection

Overview Overvoltage protection A P P L I C AT I O N N OT E 1.0 Overview Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge

More information

Large Scale Solar Integration

Large Scale Solar Integration Large Scale Solar Integration Experiences and Coming Changes in Distributed Energy Resource Interconnections October 26 th, 2017 Overview Background on Xcel Energy Expansion of Solar in Minnesota Changes

More information

An Integrated Grid Path for Solar. Thomas Key, EPRI Senior Technical Executive. ISES Webinar. April 22, 2016

An Integrated Grid Path for Solar. Thomas Key, EPRI Senior Technical Executive. ISES Webinar. April 22, 2016 An Integrated Grid Path for Solar Thomas Key, EPRI Senior Technical Executive ISES Webinar April 22, 2016 Changing Landscape: An Integrated Grid is a Better Grid Combined Heat & Power Demand Response Energy

More information

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS. SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS Róbert Riedlmajer TRNAVA 2007 Unit 14 - Fundamentals of power system protection

More information

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE Richa jain 1, Tripti shahi 2, K.P.Singh 3 Department of Electrical Engineering, M.M.M. University of Technology, Gorakhpur, India 1 Department

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

STOCHASTIC ESTIMATION OF FEEDER-SPECIFIC DISTRIBUTED GENERATION (DG) HOSTING CAPACITY

STOCHASTIC ESTIMATION OF FEEDER-SPECIFIC DISTRIBUTED GENERATION (DG) HOSTING CAPACITY STOCHASTIC ESTIMATION OF FEEDER-SPECIFIC DISTRIBUTED GENERATION (DG) HOSTING CAPACITY Estorque, L.K.L, REE, MSEE, Manila Electric Company (MERALCO), lklestorque@meralco.com.ph ABSTRACT The significant

More information

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Experience on Technical Solutions for Grid Integration of Offshore Windfarms Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow

More information

Experience and History

Experience and History Experience and History 1956 Battery no-break 1994 New Mfg Facility 500kVA System 1974 1000kVA System IC with Inner Rotor 1963 4x1600 MV System 1969 First Diesel CPS System (300 kva) 1992 2250kVA Dual Output

More information

Sensitivity Analysis of Photovoltaic Hosting Capacity of Distribution Circuits

Sensitivity Analysis of Photovoltaic Hosting Capacity of Distribution Circuits This accepted version article has been published in Proceedings of the 216 IEEE Power & Energy Society General Meeting, July 17-21, 216, Boston, MA. Sensitivity Analysis of Photovoltaic Hosting Capacity

More information

Technology Roadmap for zzzzzzzzz Grid Automation

Technology Roadmap for zzzzzzzzz Grid Automation IEEE Nashville Chapter Technology Roadmap for zzzzzzzzz Grid Automation November 2010 2010 by R. W. Beck, An SAIC Company. All Rights Reserved. Projected Expenditures 2010-2030 Substation Transmission

More information

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Product Selection & Application Guide Product Description GE's Thyristor Switched Harmonic Filter Banks (TSC), are custom designed

More information

Zone Selective Interlock Module. For GE Circuit Breakers

Zone Selective Interlock Module. For GE Circuit Breakers GE Zone Selective Interlock Module For GE Circuit Breakers Table of Contents 1. Introduction... 4 What is Zone-Selective Interlocking (ZSI)?...4 What is a Zone-Selective Interlock Module?...4 2. Description...

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

David Park, EPMV ABB South Africa / Africa Channel Partner event, 2016 ABB Africa Channel Partner event Medium Voltage Apparatus

David Park, EPMV ABB South Africa / Africa Channel Partner event, 2016 ABB Africa Channel Partner event Medium Voltage Apparatus David Park, EPMV ABB South Africa / Africa Channel Partner event, 2016 ABB Africa Channel Partner event Medium Voltage Apparatus Slide 1 Technical Session 10 Solutions for reliable power supply through

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

Transmission Problem Areas. Bulk power transfer over long distances Transmission Limitations/Bottlenecks have one or more of the following:

Transmission Problem Areas. Bulk power transfer over long distances Transmission Limitations/Bottlenecks have one or more of the following: Transmission Problem Areas Bulk power transfer over long distances Transmission Limitations/Bottlenecks have one or more of the following:» Steady-state stability limits» Transient stability limits» Power

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems Farid Katiraei *, Barry Mather **, Ahmadreza Momeni *, Li Yu *, and Gerardo Sanchez * * Quanta Technology, Raleigh,

More information

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION El Paso Electric Company System Operations Department System Planning Section August 2006 I. INTRODUCTION The

More information

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Clearing of transient faults in medium voltage networks

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE H U B B ELL L ABO R ATO R I E S CAPABILITY GUIDE INTRODUCTION Hubbell Power Systems, Inc. manufactures a wide variety of products for the electric utility, telecommunications, civil construction, transportation,

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information