UNIT 6: BATTERIES, UPS AND CABLES
|
|
- Lewis Ellis
- 5 years ago
- Views:
Transcription
1 UNIT 6: BATTERIES, UPS AND CABLES 6.1 Batteries Introduction i. Definition of Batteries: Stores chemical energy in cells and converts them into electrical energy in the form of direct current (D.C); Process is known as electrochemical reaction. ii. Functions of Batteries: Provides a mobile source of power for equipment in places where there is no permanent electrical supply; When connection to a permanent power supply is not practical, e.g torchlights; Temporary back up for permanent electrical systems in the form of UPS (Uninterrupted power supply). Symbol of Battery on Single Line Diagrams 1
2 6.1.2 How Batteries Work i. Battery consists of: Positive electrode (Cathode); Negative electrode (Anode); Electrolyte. ii. Working Process: When wired with a load in a circuit, the negative electrodes will have the tendency to travel to the cathode; In the process, this is stopped by the electrolyte as it contains negative ions; The electrodes are then forced to enter the wiring circuit to enter the cathode. This generates electric current to the load and depletes the positive electrodes; When positive electrodes are depleted, electricity generation stops; Some batteries can be recharged (By replenishing the positive electrodes and reducing negative electrodes). Diagram illustrating the working principle of battery. Diagram illustrating the charging of battery. 6.2 Uninterruptible Power Supply (UPS) Why UPS? i. Essential services are usually connected to a generator electricity supply. ii. In the event of a power failure, the generator will kick in to supply auxiliary power supply for a brief span of time to allow time for main electricity supply to recover. iii. Shortcomings of generator power: Short time interval between power trip and generator to kick in (Usually between 8 10 secs); While this span of time is minimal, there are sensitive systems within the building proper which cannot tolerate this time lapse. iv. Examples of sensitive systems include: Hospital equipment, fire alarm systems, security systems, server equipment, etc. v. UPS helps to bridge this time lapse by continuing to supply electricity to these equipment during a power outage. vi. May operate independently or together with generator power. 2
3 6.2.2 Types of Generator-UPS Configurations i. Static Electronic Converter-Inverter Unit: Connected to batteries. Converts DC current to AC current. A.C power from electric mains for battery charging; ii. Alternator coupled to A.C (Alternating Current) synchronous motor: Connected to two sources of electricity supply (one of which is electricity mains); iii. Alternator coupled to D.C (Direct Current) motor: Connected to electricity mains (via rectifier) and main battery tank; iv. Alternator coupled to diesel generator and A.C synchronous motor (To electricity mains). Generator UPS Set Up Main Components of Static UPS System UPS Single Line Diagram 3
4 Main components of a typical Static UPS: Rectifier/Charger; Inverter; Battery; Static Transfer Switch; Bypass Switch. Provides precise AC Power to Support Equipment and other sensitive systems. a) UPS module: To provide precise AC Power; Houses Rectifier/Charge unit, inverter unit; Other accessories: Control logic, synchronizing equipment, protective devices, etc. 1. Rectifier/Charger Unit: Converts A.C power to D.C power for battery charging; 2. Inverter Unit: Converts D.C power from battery or rectifier/charger unit to A.C Power. Only A.C Power can be used to supply critical load. Rectifier/Charger Unit Inverter Unit b) Battery: Stored energy source; Heavy industry battery for standby power service; Must have sufficient capacity to provide power to inverter to sustain critical load for stated time period. c) Static Transfer Switch: Designed to minimize disruption to critical load by bypassing UPS system immediately should malfunction of UPS system occurs. Normally opened switch; Operates parallel to the mechanical bypass switch; When UPS malfunction occurs, static transfer switch receives signal from UPS module and closes immediately to complete bypassing of UPS system. Industrial Strength Battery Static Transfer Switch d) Battery Disconnect Circuit Breaker: Used to terminate electrical supply to and from battery. Disconnected when: Battery reaches minimum discharge levels; Signaled by UPS module. e) Disconnect Switch for Static Transfer Switch: For disconnecting Static Transfer Switch if it malfunctions. 4
5 6.2.4 How UPS Operates i. Normal Operating Conditions: a) CB1, Input CB, output switch, CB2, disconnect switch for Static Transfer Switch and CB3 are closed; b) Power from input AC power supply flows in one direction to critical load (Red arrow). ii. iii. Failure of AC Power Supply (Power Trip/Failure): Battery supplies power straight to inverter, with no disruption to inverter output supplying critical load (See red arrow); Restoration of AC Power Supply: a) Power supply restored to normal (See (i)); b) Restored AC Power Supply is used to charge batteries with no disturbance to inverter output (See blue arrow). 5
6 iv. UPS Fault a) Monitor of UPS Module: Detects UPS fault, sends signal to static transfer switch; b) Static transfer switch closes instantaneously. CB1 and Input CB will open. Electricity flows via the bypass line through the static transfer switch towards critical load (See Red Arrow); c) Mechanical bypass switch closes, static switch opens. Power supply is then maintained through mechanical bypass switch (See blue arrow) Auxiliary Components of Static UPS System 6
7 i. Reactor: To reduce current ripple acceptable to both battery and inverter. ii. Output filter: To reduce harmonic content (Voltage fluctuation) of inverter output to acceptable levels of critical load. Harmonic Content in Voltage Form iii. Input Harmonic Filter: Installed in rectifier; Ensure distorted harmonic currents do not flow back to the source. Harmonic Content in Current Form Input Harmonic Filter Single Line Diagram Back Up Generator for UPS Systems i. Problem with Static UPS Using Batteries only: Insufficient power to last a long time should power failure be prolonged. ii. For longer duration of power backup, standby generator is required. iii. When standby generator is connected: Once there is power failure, batteries will supply power for a brief period of time to stand in temporarily for the generator; Standby generator will take some time (Possibly 10 secs or more) to kick in. Single Line Diagram showing Genset Connected to Static UPS 7
8 6.2.7 Maintenance of UPS Systems i. Why maintenance? Planned Maintenance: Minimize failure of back up power should the main electrical supply line fail; Corrective Maintenance: Carried out when UPS Systems fail. ii. Maintenance Procedures: 1. Remove all input and output power (i.e Isolating) connection to UPS system; 2. Discharge and ground all capacitors in inverter/charger 3. Inspect parts for overheating and damage; 4. Inspect all terminals for loose connections or burnt insulation; 5. Check for liquid contamination (E.g spilling of battery electrolytes); 6. Inspect and clean all intake and excess openings; 7. Check for liquid continuation in batteries and overall battery condition; 8. Check and calibrate voltage output and efficiency as per manufacturers specification; 9. Connect back to UPS; 10. Check output voltage and frequency under load; 11. Simulate power failure, check for proper system operation. 6.3 Cables i. Definition of Cables: Insulated electrical conductors, held together by a sheath, designed to carry electricity from source to electrical loads. ii. Basic components of cables: Electrical Conductors: Conducts Electricity; Insulation: Protects users from electric shock; Protective Jacket/Sheath: Protects damage to insulation and conductor. iii. Types of Cables: Polyvinyl Chloride (PVC) Cable; Thermosetting/Cross-Setting (XLPE) Cable; Rubber Cable; Fire Resistant (FR) Cable; Low Smoke Zero Halogen (LSOH) Cable; Neoprene Cable. Cross Section of an Armored Cable 8
9 iv. Method of cable installation: Conduit and trunking; Cable Tray; Underground cable trench. PVC Trunking Steel Cable Tray Steel type Galvanized GI Electrical Conduit Laying of Underground Cable in Trench Types of Cable and Insulation i. PVC Insulated Cable: For normal appliance use, e.g connection to power point; Ease of handing for termination and jointing purposes due to the absence of sheath protection; Disadvantage: Restricted by 70 degrees Celsius maximum temperature. This restricts its usage up to only 600V/1000V. Cross Section of a PVC Cable ii. XLPE Insulated Cable: Operates up to 90 degrees Celsius; Application: From 600/1000V to 32kV; Advantages: Better electrical, thermal and thermal properties; Ease of handling for termination and jointing. 9
10 iii. iv. Rubber Cable: Cable protected by outer layer of tough rubble sheath: Operated up to 85 degrees Celsius; Application: For use in applications requiring extreme toughness protection against mechanical hazards; Disadvantage: Rigid and inflexible for installation purposes. Fire Resistant Cable: Made of fire resistant material for conductor, insulator and sheath; Application: For use in locations with extreme fire hazards, e.g oil refineries. Cross Section of a Rubber Cable Cross Section of a Fire Resistant Cable v. Low Smoke Zero Halogen (LSOH) Cable: Used for cable jacketing of cables; Made of thermoplastic or thermoset compounds. Advantages: Emits little smoke and no halogen when exposed to high heat source or fire; Environmentally friendly as it does not release toxic gases under high heat conditions; Lighter, so overall cable system weight is reduced. Applications: Used in locations with poor ventilation, e.g aircrafts; Locations where fire hazard is high and there is high occupancy load, e.g Factories. In these facilities smoke can impede occupants from evacuating buildings. LSOH Cable Jacketing Cross Section of LSOH Cable Jacketing 10
11 vi. Neoprene Cable: Used for cable jacketing of cables; Advantages: Flexibility over wide temperature ranges; High resistance to degradation; High burning point (260 degrees Celsius), giving it fire retardant properties; Flat construction allows for space saving advantages. Applications: Extreme environments, such as shipyards, warehouses, steel mills, etc. Neoprene Flat Cable vii. Armored Cables: Additional steel taper layer/steel wires for mechanical protection of cables. Can serve as return path for earth currents. Applications: Typically for underground installations and cable trenches when installing PVC or XLPE cables. Comes in: DSTA (Double Steel Taped Armored) and SWA (Steel Wire Armored) Types. Cross Section of Steel Wire Armored Cable Cross Section of Double Steeled Tape Wire Armored Cable 11
12 Tutorial Questions 1) Batteries are used in many portable and non-portable devices. i. Briefly define batteries, the function of batteries and the circumstances whereby batteries are used (5 marks). ii. Explain, with the help of a simple diagram, how an ordinary dry cell battery works (15 marks). 2) Generators and UPS systems are typical installations in buildings. i. Explain why generators are used and the shortcomings of generators (4 marks). ii. Explain the shortcoming(s) of the UPS system as a standalone back-up power supply and recommend a solution to overcome the problem (3 marks). iii. Maintenance of UPS systems are viable to the operational quality of these systems. List down the types of maintenance plans which are required (2 marks); List down the maintenance procedures which are typically carried out during the maintenance regime for UPS systems (11 marks). 3) Cables are part and parcel of electrical installation works. i. List the major components of a cable and explain their basic functions (3 marks). ii. List down the propert(ies) of the PVC insulated cable and its application, and the disadvantage(s) of using a PCV insulation cable for cable installation works (3 marks). iii. List down the types of cable installations options available(3 marks). iv. List down the advantages of using the Low Smoke Zero Halogen (LSOH) Cable and its applications (5 marks). v. Briefly explain the use of the neoprene cable and list down the advantages of using neoprene cables for cable installation works. List down the applications of the neoprene cable (6 marks). 12
E-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationModel ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase
Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible
More informationULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)
white paper ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS) Electricity, flowing continuously through the grid, is something that most of today s amenities rely on. For any electrical device to
More informationBackup Generation Application
Backup Generation Application For connection of non-parallel generation between Menard Electric Cooperative s Electric system and standby generation that will operate with a manual or automatic transfer
More informationChapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar
Chapter 6 Batteries Types and Characteristics Functions and Features Specifications and Ratings 2012 Jim Dunlop Solar Overview Describing why batteries are used in PV systems. Identifying the basic components
More informationNB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS
NB 0811 - NB 1511 NB 0831 - NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS LEN.MAN.UPS.069 Rev.2.00/2002 CONTENTS Safety Instructions 1 Introduction 3 2.1 FEATURE 3 2.2 UPS modules 4 How the UPS works 5 3.1
More informationNYY-J Cable. Dungannon Electrical Wholesale Tel: Page 1 of 10
NYY-J Cable Application: A VDE approved, solid conductor, black PVC jacketed, 600/1kV power and control cable. These power cables are designed for energy supply cable ducts, power station, industry and
More informationUser Manual Rittal PMC UPS 6kVA
User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...
More informationGENERAL SPECIFICATION ELECTRICAL
GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.
More informationis the UK subsidary of Tele-Fonika Kable S.A., with offices and a warehouse centrally located in Leicestershire.
is the UK subsidary of Tele-Fonika Kable S.A., with offices and a warehouse centrally located in Leicestershire. We are a major supplier of housewiring, low voltage, power and fire resistant cables for
More information18-I73E CAT REF.
& www.terasaki.co.jp 1-I73E CAT REF. TABLE OF CONTENTS General 1-1 Introduction 1- General 1-3 Selection Chart 1- Ratings and Specifications -1 Air Circuit Breakers for DC350V-00V - Moulded Case Circuit
More informationMaintaining the operating temperature of the battery at 20 C to 25 C will maximize its service life and efficiency.
5.1.3 Reliability In most cases, the reliability of a VLA is better than VRLA cells given similar environments. VLA batteries are also more robust to environmental conditions such as temperature and ripple
More informationFR-N1X1G1. Low voltage - Energy, cabling, signalling and control
Low voltage - Energy, cabling, signalling and control FR-N1X1G1 Construction: NF C 32-323 NF C 32-323/1 Fire propagation: NF EN 60332-3-24 NF C 32-070 C1 IEC 60332-3-24 C Flame propagation: NF EN 60332-1-2
More informationUNISONIC TECHNOLOGIES CO., LTD UC5301
UNISONIC TECHNOLOGIES CO., LTD UC5301 SWITCHED-CAPACITOR VOLTAGE INVERTERS DESCRIPTION The UTC UC5301 is an unregulated charge-pump voltage inverter. It can be used to generate a negative supply from positive
More informationCourse Semester Subject Code Subject Name B.E EEE(M) V UAEE507 MARINE ELECTRICAL TECHNOLOGY UNIT-I
Course Semester Subject Code Subject Name B.E EEE(M) V UAEE0 MARINE ELECTRICAL TECHNOLOGY 0 What is Megger? Mention the Uses of Megger How the smoke detecters are working? What is the use of OCR in generator?
More information15-I73E CAT REF.
& www.terasaki.co.jp 5-I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers
More informationPyrohalon. Cables, halogen-free, fire-retardant. Pyrohalon PLUS Fire-resistant cables, halogen-free, fire-retardant
Pyrohalon Cables, halogen-free, fire-retardant www.oktechnology.ru w Pyrohalon PLUS Fire-resistant cables, halogen-free, fire-retardant Disappointing statistics Fire is a great disaster that often cause
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More information14-I73E CAT REF.
& www.terasaki.co.jp -I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers
More informationUSER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4
USER S MANUAL ON-LINE 1K/2K/3KVA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. UPS OPERATION...... 12 6. TROUBLE
More information600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables (2-5 Cores)
www.caledonian-s.co.uk www.addison-s.com 600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables (2-5 Cores) FTX400 1RZ1-R (CU/XLPE/LSZH 600/1000V Class 2) FTX400 1RZ1MZ1-R (CU/XLPE/LSZH/SWA/LSZH
More informationDuracell Battery Glossary
Duracell Battery Glossary 1 Duracell Battery Glossary AB Absorption Alloy Ambient Humidity Ambient Temperature Ampere-Hour Capacity Anode Battery or Pack Bobbin C-Rate (also see Hourly Rate) Capacity Capacity
More informationPower & Control Cables. U o. /U 0.6/1 kv - IEC
Power & Control Cables U o /U 0.6/1 kv - IEC 60502-1 2 KERPEN GmbH & Co. KG 07.2005 Printing errors excepted. Subject to alteration List of Contents Introduction Page B1 Construction Page B3 Use Page B4
More informationOn Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual
On Line UPS LUC 1000E / LUC 2000E / LUC 3000E User Manual Save This Manual Please read this manual carefully prior to storage, installation, wiring, operation and maintenance of the UPS. This manual contains
More informationGLOSSARY: TECHNICAL BATTERY TERMS
GLOSSARY: TECHNICAL BATTERY TERMS AB5 Absorption Alloy Ambient Humidity Ambient Temperature Ampere-Hour Capacity Anode Battery or Pack Bobbin C-Rate (also see Hourly Rate) Capacity Capacity Retention (or
More informationInstallation Operation Parts
OWNER S MANUAL BATTERY BACKUP SUMP Installation Operation Parts For further operating, installation or maintenance assistance, Call 98-8-05 PRINTED IN U.S.A. M-8 (/9) RULES FOR SAFE INSTALLATION AND OPERATION
More informationAcme NonStop Power. FNC Cell Technology Sealed fiber nickel-cadmium battery systems For commercial, military and space systems.
Acme Aerospace Inc., manufactures power supplies and high-performance, sealed FNC batteries for military and commercial aerospace, as well as industrial and satellite/ space applications. Acme NonStop
More informationSECTORFLEX CABLE CATALOGUE
SECTORFLEX CABLE CATALOGUE SAVING SPACE AND TIME R & D + i SERVING OUR CUSTOMERS PRESENTATION One of the largest companies in the sector worldwide. General Cable is a leading company in the manufacture
More informationIT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES
SUBCOURSE IT 0335 EDITION B US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES INTRODUCTION TO CELLS AND BATTERIES Subcourse Number IT0335 EDITION B US ARMY INTELLIGENCE CENTER FORT HUACHUCA,
More informationIT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES
SUBCOURSE IT 0335 EDITION B US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES INTRODUCTION TO CELLS AND BATTERIES Subcourse Number IT0335 EDITION B US ARMY INTELLIGENCE CENTER FORT HUACHUCA,
More informationSYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test)
ANNEXURE I SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) Paper I & Paper II for General Category of S.C.C. Examination Paper I & Paper
More informationSupercapacitor Based Power Conditioning System for Power Quality Improvement in Industries
Supercapacitor Based Power Conditioning System for Power Quality Improvement in Industries T. Barath, E. Anand Issack, M. Ragupathi, Gummididala V. S. Pavankumar, EEE Department Abstract-- Transmission
More informationGUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES
MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More informationWinter 2016 Conference
Winter 2016 Conference * Reference: 7x24 International Conference, Spring 2012, Comparison of UPS Alternative Energy Storage Technologies, Syska Hennessy Group, BB&T 3/3/2016 We Will Discuss: What Is A
More informationMGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications
MGL Avionics AvioGuard Fault protected, wide input range, isolated, DC to DC converter for avionics applications General The MGL Avionics AvioGuard is a fault protected DC to DC converter. It is able to
More informationFR-3S Fire Resistant Cables
FR-3S Fire Resistant Cables APPLICATION This cable is suitable use in fire extinguishing systems to operate sprinklers, control panels, exit lights in high-rise buildings, hotels, hospitals, sub-ways and
More informationUSER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4
USER S MANUAL PowerWalker VFI 1000 / 3000VA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION......... 2 3. SYSTEM DESCRIPTION......... 4 4. CABLE CONNECTION......... 7 5. OPERATION...... 8 6. TROUBLE
More informationElectricity Unit Review
Science 9 Electricity Unit Review Name: General Definitions: Neutral Object Charge Separation Electrical Discharge Electric Current Amperes (amps) Voltage (volts) Voltmeter Ammeters Galvanometer Multimeter
More informationTECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS
Tender Paper TECHNICAL SPECIFICATIONS FOR 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Contents 1. General 2. Tender submission requirements 3. Environmental
More informationEdgeLED TM Range. Installation and Operating Instructions EdgeLED TM RANGE INSTALLATION NON-EMERGENCY LUMINAIRES PRE INSTALLATION
EdgeLED TM Range THIS FITTING SHOULD NOT BE USED IN AREAS EXCEEDING 25 C AMBIENT AIR TEMPERATURE This fitting must be installed by a qualified electrician and wired in accordance with the latest edition
More informationBS 6724 Armoured Power Cables, 600/1000V
BS 6724 Armoured Power Cables, 600/1000V Application These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The
More information10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph
VEGA INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY 10 20KVA 3Ph/1Ph 10 120KVA 3Ph / 3Ph - 6 pulse SCR rectifier - IGBT inverter - Power output transformer - Low and stable ripple on battery for the highest battery
More informationPower & Control Cables
The Quality Connection Power & Control Cables U o /U 0.6/1 kv - IEC 60502-1 2 The Quality Connection www.leoni-industrial-projects.com The LEONI Group Cable expertise for the most various industrial markets.
More informationGUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL
1.1 SUMMARY Liebert APM UPS GUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL Liebert APM UPS, 15-45 kva and 15-90 kva Scalable This specification
More informationHOTLINE ELECTRICAL TRADING
HOTLINE ELECTRICAL TRADING (L.L.C) P.O.Box: 235152 Dubai, UAE. Tel ; +971-4-3455173 Email:-manuel@hletllc.com I www.hletllc.com Company Profile Hotline Electrical Trading L.L.C is a trading company dealing
More informationAcme NonStop Power. FNC Cell Technology
Acme NonStop Power................................................................................................................ FNC Cell Technology Sealed fiber nickel-cadmium battery systems For commercial,
More informationTower Electronic Systems
3300 UPS Instruction Manual AUGUST 2005 CONTENTS 1.0 INTRODUCTION 1.1 General description 3 1.2 UPS building blocks 3 1.2.1 Boost converter 3 1.2.2 Inverter 3 1.2.3 Static transfer switch 3 1.2.4 Battery
More informationTOSHIBA G , 750kVA
SOCIAL INFRASTRUCTURE SYSTEM GROUP POWER ELECTRONICS DIVISION UPS 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (855) 803-7087 FACSIMILE: (713) 896-5212 TOSHIBA G2020 500, 750kVA
More informationPhosphate-base Lithium-ion Battery Pack Model:LFP V 1350Ah Product Specifications Lithium Energy Solution 1/8
Phosphate-base Lithium-ion Battery Pack Model:LFP1350-48 48V 1350Ah Product Specifications Lithium Energy Solution 1/8 1. Product overview LFP1350-48 Products are mainly for customized development of high
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More information600/1000V XLPE Insulated PVC Sheathed Power Cables (Multicore)
600/1000V XLPE Insulated PVC Sheathed Power Cables (Multicore) FGD400 1RV-R (CU/XLPE/PVC 600/1000V Class 2) Outdoor Cabling Earth Conductor Earth Conductor APPLICATION The cables are mainly used in power
More informationStandard specification Galaxy PWi, three-phase, 10 to 200 kva
Galaxy PWi, three-phase, 10 to 200 kva Contents 1 - UPS definition... 2 1.1 - Purpose... 2 1.2 - Brief description... 2 2 - Operating principle... 2 2.1 - Normal operation... 2 2.2 - Operation on battery
More informationValcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual
Valcom Failsafe Unit 1620ESv2 SERIES Operation and Maintenance Manual Table of Contents Section Title Page 1. - Introduction.. 2. - Unpacking the Failsafe unit. 3. - Installation 3.1 - Auto / Timed UPS
More informationQUEENSLAND URBAN UTILITIES
DOCUMENT NO : EQUIPMENT NO : PREPRED : CHECKED : PPROVED : SHEET NO : 1 of 6 GENERL 1 Battery Charger DCC Inverters 3 DCDC Converters 4 System Design Life (other than batteries) Years 5 Battery Design
More informationTest Stations and Pipe-to-Soil Potential Measurements
Test Stations and Pipe-to-Soil Potential Measurements Period #7 Practical Applications Course 2017 Mark James NACE CP II #5619, NACE CIP I #37041 1 Introduction Test Stations Wire Connection to Pipe Pipe-to-Soil
More informationBattery Storage Systems
Battery Storage Systems Agenda System Components Applications How to Size Batteries System Components Basic battery theory Electro-chemical reaction Two dissimilar metals Positive electrodes Negative electrodes
More informationNew Safety Rules for Large Scale Photovoltaic Systems, Energy Storage Systems, and Microgrids
October 10, 2016 New Safety Rules for Large Scale Photovoltaic Systems, Energy Storage Systems, and Microgrids New Safety Rules for Large Scale Photovoltaic Systems, Energy Storage Systems, and Microgrids
More informationPowerware Master Modbus
Powerware Master Modbus Map 164201391 Rev D This document describes the format of the data contained in the Modbus messages. Not all registers apply to all UPS modules. Please consult the individual UPS
More informationCentral Battery Systems
Central battery system based emergency lighting is ideal for medium to large installations. For projects where central control and testing is desirable, a central battery system is a viable and cost effective
More informationChapter 3. Direct Current Power. MElec-Ch3-1
Chapter 3 Direct Current Power MElec-Ch3-1 Overview Batteries Safety Precautions Marine Storage Battery Charging Systems Battery Utilization MElec-Ch3-2 Batteries Cells and Battery Battery Chemistry Primary
More informationUsers Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B
Users Manual Defender 1 8.0KW to 14.0KW Online Lighting Inverter Technical Manual #018-0102-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail:
More informationBUTTON CELL CR2450S BRIEF SPECIFICATION
BUTTON CELL CR2450S BRIEF SPECIFICATION Model: CR2450S Nominal Voltage: 3V Nominal Capacity:550mAh Standard Discharge with load: 15KΩ Weight: 6.8g Stainless steel container ISO9001 Certified UL Certified
More informationpart three electrical installations
part three electrical installations Cleat Hitch Faulty electrics, or poorly installed electrical systems, can be a real hazard and could place you and others at risk. This part of the Standards aims to
More informationDUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL
72-7570 DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL Table of Contents Specification 1 Safety 3 EMC 4 Installation 5 Connections 5 Operation 6 Maintenance 8 Specification General specifications
More informationApplication Guidelines
This document provides basic guidelines for application development using aerogel capacitors, also known as supercapacitors. If questions arise during your development process and are not answered in this
More informationEmergi-Lite EMEX central power supply solutions
Emergi-Lite EMEX central power supply solutions Reliable central back up power Available for AC/AC and AC/DC power supply systems Exceptional overload performance Entire modular build for quick and simple
More informationSAVER DSP SERIES. 3-10kVA USER MANUAL
. SAVER DSP SERIES. SINGLE PHASE IN SINGLE PHASE OUT 3-10kVA USER MANUAL UNINTERRUPTIBLE POWER SUPPLY UPS 288713578 Important Notices Thank you for choosing Inform UPS Systems. This document provides
More informationIlluminator Series CR NEMA 3R
Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the
More informationMANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel
MANUAL CONGRATULATIONS on the purchase of your new CTEK professional battery management unit. This unit is part of a range of professional battery chargers from CTEK SWEDEN AB. It represents the latest
More informationLIST OF PUBLISHED STANDARDS
Report : 08-0-6 Page o : Of 5 LST OF PUBLSHED STDRDS Total Count: 78 umber SS umber pproved mendment SBS/TC 066 SS 97:07 7.0 Electric cables - mpregnated paper-insulated 07-0-7 metal-sheathed cables for
More informationPower Inverter. User s Manual. Diamond Series CPD1200EILCD
Power Inverter Diamond Series CPD1200EILCD User s Manual 2 TABLE OF CONTENTS 1 IMPORTANT SAFETY INSTRUCTIONS..4 2 INSTALLATION....5 2-1 Unpacking...5 2-2 Product Overview & Outlook..5 2-3 Power Requirements
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More informationAqua SnakeEye. OA-09 Extended Life NiMH Battery. Operators Manual
Aqua SnakeEye OA-09 Extended Life NiMH Battery Operators Manual Rev. 1.2 Table of Contents I. Introduction II. Part List III. Getting Started IV. Ready for Use V. Trouble Shooting VI. Specifications I.
More informationExperience and History
Experience and History 1956 Battery no-break 1994 New Mfg Facility 500kVA System 1974 1000kVA System IC with Inner Rotor 1963 4x1600 MV System 1969 First Diesel CPS System (300 kva) 1992 2250kVA Dual Output
More informationStudy on the Performance of Lithium-Ion Batteries at Different Temperatures Shanshan Guo1,a*,Yun Liu1,b and Lin Li2,c 1
7th International Conference on Mechatronics, Computer and Education Informationization (MCEI 217) Study on the Performance of Lithium-Ion Batteries at Different Temperatures Shanshan Guo1,a*,Yun Liu1,b
More informationSurabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality
Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100
More informationFortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting
More information1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8
Contents : 1. INTRODUCTION...1 2. IMPORTANT SAFETY INSTRUCTIONS...2 3. SYSTEM DESCRIPTION...4 3.1 Front Panel...4 4. CONNECTION AND OPERATION...6 5. TROUBLESHOOTING...8 6. MAINTENANCE...9 6.1 Operation...9
More informationSEMI, manufacturer of superior quality electrical flexible conduit and fittings systems. Over Braided Liquid Tight Conduit ( YF-705 )
Over Braided Liquid Tight Conduit ( YF-705 ) Trade Size I.D. (mm) O.D. (mm) Min Bending MIN. MAX. MIN. MAX. Meters/Coil YF-70503 3/8" 12.3 12.8 18.5 19.0 75 50 YF-70504 1/2" 15.7 16.3 21.8 22.3 95 50 YF-70506
More informationThe introduction of Lead Crystal Battery
The introduction of Lead Crystal Battery (1). Brief Introduction of Lead Crystal Battery Lead crystal battery is based on an in-depth study of both lead acid batteries and gel batteries features and defects,
More informationLiebert. FP 50Z kva
Liebert FP 50Z 5 250 kva Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online faster and at a lower cost when search and social
More informationBuilding & Infrastructure Cables DELIVERING ENERGY
Building & Infrastructure Cables DELIVERING ENERGY Keystone Cable is a Leading Singaporebased Cable Manufacturer and Supplier. Keystone Cable Market Reach Established since 1990, Keystone Cable has an
More informationSINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /1 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More informationLithium battery charging
Lithium battery charging How to charge to extend battery life? Why Lithium? Compared with the traditional battery, lithium ion battery charge faster, last longer, and have a higher power density for more
More informationXLB Series Power Supply Application Notes
XLB Series Power Supply Application Notes Introduction The XLB series short arc lamp power supplies are designed to ignite and properly power Xenon short arc lamps ranging in power from 100 watts to over
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More information9. Effects of an electric current
Leaving Cert Physics Long Questions 2017-2002 9. Effects of an electric current Please remember to photocopy 4 pages onto one sheet by going A3 A4 and using back to back on the photocopier Contents Ordinary
More informationMachine, Panel, and Plant Level Solutions
Machine, Panel, and Plant Level Solutions Mark Stephens, PE Manager Industrial Studies Electric Power Research Institute 942 Corridor Park Blvd Knoxville, Tennessee 37932 Phone 865.218.8022 mstephens@epri.com
More informationMKN-DSP SERIES - THREE PHASE
Output Power Factor 0.9 MKN-DSP SERIES - THREE PHASE Double conversion True On-Line UPS 3 Phase Input - 3 Phase Output 10 KVA 15 KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA Model for: 208/120 V 220/127 V /
More informationLi-ion Cylindrical Battery Specification. SHIBA Li-ion Battery Typical Capacity: 2000mAh Total Page: 10
Li-ion Cylindrical Battery Specification MODEL : SHIBA Li-ion Battery Typical Capacity: 2000mAh Total Page: 10 1 P a g e Table of Content 1. Scope...3 2. Initial Dimension...3 3. Specification...4 4. General
More informationDual Power. Protection. Protection
54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result
More informationLED Emergency Luminaires
LED Emergency Luminaires THIS FITTING SHOULD NOT BE USED IN AREAS EXCEEDING 25 C AMBIENT AIR TEMPERATURE This fitting must be installed by a qualified electrician and wired in accordance with the latest
More informationSectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications
Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History Early 1970 s Small Substation Transformers
More information& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL
72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com
More information