Zone 1. Zone 3. Zone 2. PROBLEM 1 (40 points) Fixed Load Auction (No transmission limits considered):

Size: px
Start display at page:

Download "Zone 1. Zone 3. Zone 2. PROBLEM 1 (40 points) Fixed Load Auction (No transmission limits considered):"

Transcription

1 EE5721 Practice Final Exam PROBLEM 1 (40 points) A power system consists of three zones. Each zone will be represented by a single generator and a single load on a single bus as shown below: GA GC LA LC Zone 1 GB Zone 3 LB Zone 2 The generators are labeled GA, GB and GC and the loads are labeled LA, LB and LC. The schedule of generation and load in this system is determined by an auction. We shall consider two variations of input data for the auctions. In the first, load will be considered fixed in that it will be satisfied (that is, the load is supplied) no matter what the generator s sell prices are (assuming that the transmission system and the generators have adequate capacity to meet the load). The second auction will consider the load to be variable in that the load shall submit a willingness to pay price to purchase blocks of energy. If the price of energy is below the load s willingness to pay price it is satisfied (again assuming that there is sufficient transmission and generation capacity). If the price of energy from the generators is above the load s willingness to pay price - then the load is not satisfied (that is, the load block is not supplied). Fixed Load Auction (No transmission limits considered): Generators submit blocks of energy for sale with a price for each block. The power exchange arranges all the generator sell blocks from lowest price to highest price. The load is summed for the entire system. It then starts the process of finding a clearing price as follows: Step down the generation bids block by block, until there is sufficient generation to meet the load, then stop. The last block of generation may be completely used of it may only be partially used. The generation price for this last block of energy is the clearing price for the entire auction.

2 EE5721 Practice Final Exam Problem 1 Part A) Loads are fixed, and the generation blocks and prices are given in the table below. Note that each generation block is labeled GA1, GA2,..., GC5. We shall assume that the transmission system capacity is adequate for any transfer of power from any zone to any other zone. Find the clearing price for this auction. Indicate which blocks of generation are actually sold. Calculate the flows on the transmission paths from zone 1 to zone 2 and from zone 2 to zone 3. Generator: GA Generator: GB Generator: GC Block Block Price Block Block Price Block Block Price Number MW $/MWh Number MW $/MWh Number MW $/MWh GA GB GC GA GB GC GA GC GA GC GC Load: LA Load: LB Load: LC 300 MW 600 MW 450 MW Data for Problem 1 Part A Variable Load Auction (No transmission limits considered): Generators submit blocks of energy for sale with a price for each block. Loads submit bids to purchase blocks of energy with a price or willingness to pay for each block. The power exchange arranges all the generator sell blocks from lowest price to highest price and arranges the load purchase blocks from highest price down to lowest price. It then starts the process of finding a clearing price as follows: 1) Match the lowest sell price for a generator block to the highest purchase price for a load block. If the selling price of the generation block is below the purchasing price of the block of load then the load block is satisfied. The clearing price is the price of the generation block. 2) Match the next highest sell price for a generator block to the next lowest purchase price for a load block. If the sell price of generation is below the purchase price for load, the load is satisfied and the clearing price for the entire auction now becomes the generation sell price of this most recently sold block of generation. 3) Continue, block by block, until the sell price for a generator block is greater than the purchase price for a load block - then stop. The generation block price for the last match where generator sell price is below load purchase price is the clearing price for the entire auction.

3 EE5721 Practice Final Exam PROBLEM 1 Part B) The Generator Blocks and their prices (same as in part A) and the Load Blocks and their prices are given below: Generator: GA Generator: GB Generator: GC Block Block Price Block Block Price Block Block Price Number MW $/MWh Number MW $/MWh Number MW $/MWh GA GB GC GA GB GC GA GC GA GC GC Load: LA Load: LB Load: LC Block Block Price Block Block Price Block Block Price Number MW $/MWh Number MW $/MWh Number MW $/MWh LA LB LC LA LB LC LB LC LB Data for Problem 1 Part B Note that now both the generation and load blocks are each given an identifier. Find the clearing price for this auction assuming that there are no limits on the power that can be transmitted over the interconnections between zones. Identify which blocks of each generator are sold and which blocks of each load are satisfied. Identify which blocks of load go unsatisfied and explain why. Finally, calculate the flows on the transmission paths from zone 1 to zone 2 and from zone 2 to zone 3. Auctions with Transmission Limits When transmission limits are imposed, the same matching procedure as on the previous pages is used, however, each time a block of generation is matched to a block of load the transmission flows are calculated for the addition of the sale of that block. If a transmission limit is hit, then the matching procedure will only sell as much of that block as will make the transmission path go to its limit. At that point the system is split into two separate auctions - one auction matches unfilled load in the zone(s) on one side of the congested path to unused generation in the same zone(s), the second auction matches unfilled load to unused generation on the remainder of the network located on the other side of the congested path.

4 EE5721 Practice Final Exam Problem 1 Part C Assume that the transmission path from zone 1 to zone 2 is limited to only 100 MW flow in either direction while the transmission path from zone 2 to zone 3 is still unlimited. What is the clearing price in each zone and what are the transmission flows, if the loads are fixed (same block and price data as Problem 1 Part A). Problem 1 Part D Assume again that the transmission path zone 1 to zone 2 is limited to only 100 MW in either direction while the transmission path from zone 2 to zone 3 is still unlimited. What is the clearing price in each zone and what are the transmission flows, if the loads are variable (same block and price data as Problem 1 Part B).

5 Solution for Parts A and B, no transmission limits Part B Solution, with variable load Part A solution, all loads fixed Gen Asking Prices Load Bids Fixed Load Variable Load Cum MW Cum MW Clearing Price Difference Clear Price GB LB GA LA GA LC GB LA GA LB GC LC GA LB GC LB GC * LC GC GC Part C Solution with transmission limits fixed loads Gen Asking Prices Load Blocks Clear Price Transmission GB LB GB LB GB LB GA LA GA LA GA LA GA LA GA LA GA LA GB LB GB LB GB LB GA LB GA LB clear price zone A GA not sold GC LC GC LC GC LC GA not sold GA not sold GA not sold GC LC GC LC GC LC GC LC GC LC GC LC GC LB GC LB GC LB GC LB Clear price zone B&C Final Flows GC not sold GC not sold

6 Part D Solution with transmission limits Variable loads Gen Asking Prices Load Bids Transmission Difference Clearing Price GB LB GB LB GB LB GA LA GA LA GA LA GA LC GA LC Zone A GA LA GA LA GA LA Zone A Clearing Price GA not sold GA not sold GA not sold GA not sold Zones B & C GB LC GB LB GB LB GC LB GC LC GC LC GC LC Zones B&C Clear Price GC not sold* LB not satisfied* GC not sold* LB not satisfied* GC not sold LB not satisfied GC not sold LB not satisfied GC not sold LB not satisfied GC not sold LB not satisfied GC not sold LC not satisfied GC not sold LC not satisfied GC not sold LC not satisfied GC not sold GC not sold * Never said what to do if gen price equals load price, above assumes these not sold, if you assume they are sold then the clear price is still but LB3 gets 100 (not 0) and GC2 sells 150 (not 50).

7 PROBLEM 2 Given the following network: Bus 1 Bus 2 Bus 3 m2 m3 m12 θ 1 = 0 m23 The network is to be modeled with a DC power flow with line reactances as follows: (assume 100 MVA base) x 12 = 0.15 pu x 23 = 0.2 pu The meters are all of the same type with a standard deviation of σ = 0.05 pu for each. The measured values are: m12 = 2.46 pumw m2 = 1.58 pumw m23 =.684 pumw m3 = 1.74 pumw 1) Find the phase angles which result in a best fit to the measured values. 2) Find the value of the residual function J. 3) Calculate estimated generator output the generator, the estimated load at each load, and the estimated power flow on each line. 4) Are there any errors in the measurements? If you think so explain which meters are apt to be in error and why. 5) If in part 4 a measurement error was found, remove that measurement and resolve for the angles, flows, and residual J.

8 H = θ θ = 2 = θ The four measurements calculated using the values of theta estimate are: m12 = m2 = m23 = m3 = These result in a residual ot J = The individual errors for each measurement are: m12 error = m2 error = m23 error = m3 error = Dropping the m3 measurement due to its large error: θ θ = 2 = θ Measured quantities are: m12 = m2 = m23 = The resulting residual is J = The errors are: m12 error = m2 error = m23 error = The large drop in J indicates that this is a much better estimate.

9 PROBLEM 3 Four generators G1, G2, G3 and G4 are located at a large oil refinery. Ggnerators G1 and G2 are connected together on one bus and G3 and G4 are connected to another bus. The buses are connected together with a short tie line. The refinery draws a load of 2000 MW as shown below: P ref GOV P ref GOV G1 G3 P ref GOV P ref G2 GOV G4 LOAD The parameters for the four generators are: G1 and G2: 500MVA, R1 = 0.05 G3: 1000MVA, R2 = 0.02 G4: 200MVA, R3 = 0.01 where the values for R1, R2, R3 and R4 are all in per unit referenced to their generator s MVA as base. When you solve the problem, change all generator MW s, the load MW and the R values to a common system base of 100 MVA. At time t = 0 all four generators are supplying power to the load and the frequency is at 60 Hz. Assume the generators supply the following: P1 and P2 = 450 MW, P3 = 950 MW and P4 = 150 MW. Just after t=0 the load drops suddenly from 2000 to 1500 MW. Assuming no Automatic Generation Control action (no LFC) - only governor action. a) What is the steady state frequency reached after the load drop? b) How much power flows on the tie line and in what direction? b) What is the new MW output of each generator after the frequency reaches a stable value? Now assume that G1 and G2 and their bus are controlled by an Automatic Generation Control (AGC) system. What is the Area Control Error (ACE) when the frequency stabilizes (assume = 1000MW/Hz and that the tie schedule is 1100 MW. B f

10 Convert to common base: Rnew 1 = ( 0.05) = 0.01 Similarly: R2=0.01, R3 = 0.002, and R4 = β = = β f = load f = pu = 0.333Hz new frequency is pu = Hz P -1 1 = f = -100*(.00555)= pu=-55.5MW R 1 Similarly: delp2=-55.5 MW, delp3=-277mw, delp4 = -111 MW

11 New Generation is: Pnew 1 = = and P2new = 394.5, P3new=673, and P4new = 39 the tie flow goes to 712 MW from right to left. By the convention of interchange being positive going out, this means the schedule is now negative 712 MW and the original schedule was negative 1100 MW ACE = ( (-1100))-1000( 0.333) = 55

POWERWORLD SIMULATOR. University of Texas at Austin By: Mohammad Majidi Feb 2014

POWERWORLD SIMULATOR. University of Texas at Austin By: Mohammad Majidi Feb 2014 POWERWORLD SIMULATOR University of Texas at Austin By: Mohammad Majidi Feb 2014 AGENDA Contingency Analysis OPF SCOPF Examples 2 START CONTINGENCY ANALYSIS Open case B7SCOPF from the Program Files/PowerWorld/Simulator/Sample

More information

Steady-State Power System Security Analysis with PowerWorld Simulator

Steady-State Power System Security Analysis with PowerWorld Simulator Steady-State Power System Security Analysis with PowerWorld Simulator S3: Techniques for Conditioning Hard-to-Solve Cases 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com

More information

ECE 740. Optimal Power Flow

ECE 740. Optimal Power Flow ECE 740 Optimal Power Flow 1 ED vs OPF Economic Dispatch (ED) ignores the effect the dispatch has on the loading on transmission lines and on bus voltages. OPF couples the ED calculation with power flow

More information

Ancillary Services. Horace Horton. Market Overview Course. Senior Market Trainer, Market Training, NYISO. March 8, Rensselaer, NY 12144

Ancillary Services. Horace Horton. Market Overview Course. Senior Market Trainer, Market Training, NYISO. March 8, Rensselaer, NY 12144 Ancillary Services Horace Horton Senior Market Trainer, Market Training, NYISO Market Overview Course March 8, 2018 Rensselaer, NY 12144 1 Ancillary Services Objectives At the end of this session attendees

More information

Ancillary Services. Horace Horton Senior Market Trainer, Market Training, NYISO. New York Market Orientation Course (NYMOC)

Ancillary Services. Horace Horton Senior Market Trainer, Market Training, NYISO. New York Market Orientation Course (NYMOC) Ancillary Services Horace Horton Senior Market Trainer, Market Training, NYISO New York Market Orientation Course (NYMOC) June 5-8, 2018 Rensselaer, NY 12144 1 Ancillary Services SESSION OBJECTIVES: attendees

More information

Fall 1997 EE361: MIDTERM EXAM 2. This exam is open book and closed notes. Be sure to show all work clearly.

Fall 1997 EE361: MIDTERM EXAM 2. This exam is open book and closed notes. Be sure to show all work clearly. NAME: STUDENT NUMBER: Fall 1997 EE361: MIDTERM EXAM 2 This exam is open book and closed notes. Be sure to show all work clearly. 1. 10 points - Mechanical and Electrical Energy Relationships: A dc motor

More information

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS OVERVIEW Interconnected systems Generator scheduling/dispatching Load-generation balancing Area Control Error (ACE) Load

More information

Steady-State Power System Security Analysis with PowerWorld Simulator

Steady-State Power System Security Analysis with PowerWorld Simulator Steady-State Power System Security Analysis with PowerWorld Simulator using PowerWorld Simulator 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com

More information

Convergence bidding. RUC tier 1 obligation uplift ISO PUBLIC 2015 CAISO

Convergence bidding. RUC tier 1 obligation uplift ISO PUBLIC 2015 CAISO Convergence bidding RUC tier 1 obligation uplift Module objective Evaluate what triggers the residual unit commitment (RUC) tier 1 uplift obligation when participating in convergence bidding Identify key

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

d / cm t 2 / s 2 Fig. 3.1

d / cm t 2 / s 2 Fig. 3.1 7 5 A student has been asked to determine the linear acceleration of a toy car as it moves down a slope. He sets up the apparatus as shown in Fig. 3.1. d Fig. 3.1 The time t to move from rest through a

More information

Tutorial. Running a Simulation If you opened one of the example files, you can be pretty sure it will run correctly out-of-the-box.

Tutorial. Running a Simulation If you opened one of the example files, you can be pretty sure it will run correctly out-of-the-box. Tutorial PowerWorld is a great and powerful utility for solving power flows. As you learned in the last few lectures, solving a power system is a little different from circuit analysis. Instead of being

More information

ELECTRIC CURRENT. Name(s)

ELECTRIC CURRENT. Name(s) Name(s) ELECTRIC CURRT The primary purpose of this activity is to decide upon a model for electric current. As is the case for all scientific models, your electricity model should be able to explain observed

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 Short Circuit

More information

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2 BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor > 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper

More information

Non-BM Balancing Services Volumes and Expenditure

Non-BM Balancing Services Volumes and Expenditure Non-BM Balancing Services Volumes and Expenditure Contents 1 Introduction... 2 1.1 What are Balancing Services or Ancillary Services?... 2 1.2 What are Balancing Mechanism (BM) and Non-Balancing Mechanism

More information

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011 EE 742 Chap. 7: Wind Power Generation Y. Baghzouz Fall 2011 Overview Environmental pressures have led many countries to set ambitious goals of renewable energy generation. Wind energy is the dominant renewable

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Study Performed by El Paso Electric Company System Planning Section - 1 I.

More information

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) Nazneen Choudhari Department of Electrical Engineering, Solapur University, Solapur Nida N Shaikh Department of Electrical

More information

SSE Guide to the Energy Industry. Guide

SSE Guide to the Energy Industry. Guide SSE Guide to the Energy Industry Guide Understanding energy costs Non-commodity costs (NCCs) are increasing. It is therefore important to understand how they are calculated and how they can affect your

More information

VOLTAGE STABILITY CONSTRAINED ATC COMPUTATIONS IN DEREGULATED POWER SYSTEM USING NOVEL TECHNIQUE

VOLTAGE STABILITY CONSTRAINED ATC COMPUTATIONS IN DEREGULATED POWER SYSTEM USING NOVEL TECHNIQUE VOLTAGE STABILITY CONSTRAINED ATC COMPUTATIONS IN DEREGULATED POWER SYSTEM USING NOVEL TECHNIQUE P. Gopi Krishna 1 and T. Gowri Manohar 2 1 Department of Electrical and Electronics Engineering, Narayana

More information

Power System Economics and Market Modeling

Power System Economics and Market Modeling Power System Economics and Market Modeling M5: Security Constrained Optimal Power Flow 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Figure 4.1.1: Cartoon View of a DC motor

Figure 4.1.1: Cartoon View of a DC motor Problem 4.1 DC Motor MASSACHUSETTS INSTITUTE OF TECHNOLOGY Department of Electrical Engineering and Computer Science 6.007 Applied Electromagnetics Spring 2011 Problem Set 4: Forces and Magnetic Fields

More information

Decision on Merced Irrigation District Transition Agreement

Decision on Merced Irrigation District Transition Agreement California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS El Paso Electric Company System Operations Department System Planning

More information

IEEE SESSION COMPUTER AIDED SMART POWER GRID

IEEE SESSION COMPUTER AIDED SMART POWER GRID IEEE SESSION COMPUTER AIDED SMART POWER GRID GEN_1 t.giras@ieee.org GEN_2 LOAD_1 LOAD_2 1 HIGH SMART GRID LEVEL LOW SMART POWER GRID TECHNOLOGY HISTORY MIT NETWORK ANALYZER 1940 ANALOG DISPATCH ACE SCADA

More information

California Independent. System Operator. Market Overview and Design Construct

California Independent. System Operator. Market Overview and Design Construct California Independent Market Overview and Design Construct Kyle Hoffman 916-608-1127 khoffman@caiso.com The ISO Vision Preferred Provider of Superior Electric Transmission Services Ensure reliable transmission

More information

Dynamic Scheduling NI A F S NI S. Where:

Dynamic Scheduling NI A F S NI S. Where: Dynamic Scheduling FERC Order 888 defines dynamic scheduling: which is the electronic transfer of the time-varying electricity consumption corresponding to a load or the time-varying generation associated

More information

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation Computation of Sensitive Node for IEEE- 4 Bus system Subjected to Load Variation P.R. Sharma, Rajesh Kr.Ahuja 2, Shakti Vashisth 3, Vaibhav Hudda 4, 2, 3 Department of Electrical Engineering, YMCAUST,

More information

Frequency Quality in the Nordic system: Offshore Wind variability, Hydro Power Pump Storage and usage of HVDC Links

Frequency Quality in the Nordic system: Offshore Wind variability, Hydro Power Pump Storage and usage of HVDC Links Frequency Quality in the Nordic system: Offshore Wind variability, Hydro Power Pump Storage and usage of HVDC Links by Atsede G. Endegnanew Hossein Farahmand Daniel Huertas-Hernando SINTEF Energy Research

More information

Proposed Solution to Mitigate Concerns Regarding AC Power Flow under Convergence Bidding. September 25, 2009

Proposed Solution to Mitigate Concerns Regarding AC Power Flow under Convergence Bidding. September 25, 2009 Proposed Solution to Mitigate Concerns Regarding AC Power Flow under Convergence Bidding September 25, 2009 Proposed Solution to Mitigate Concerns Regarding AC Power Flow under Convergence Bidding Background

More information

Flexible Ramping Product Technical Workshop

Flexible Ramping Product Technical Workshop Flexible Ramping Product Technical Workshop September 18, 2012 Lin Xu, Ph.D. Senior Market Development Engineer Don Tretheway Senior Market Design and Policy Specialist Agenda Time Topic Presenter 10:00

More information

Hybrid Wind Solar Generator

Hybrid Wind Solar Generator Jerry Bell Resource Adequacy Planning Department Planning Committee December 14th, 2017 How did this concept arise? Wind units rarely use their full inverter capability If wind units capacity factors in

More information

Transient Stability Analysis with PowerWorld Simulator

Transient Stability Analysis with PowerWorld Simulator Transient Stability Analysis with PowerWorld Simulator 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Transient Stability Basics Overview

More information

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller Vidya S 1, Dr. Vinod Pottakulath 2, Labeeb M 3 P.G. Student, Department of Electrical and Electronics Engineering,

More information

RATE 765 RENEWABLE FEED-IN TARIFF

RATE 765 RENEWABLE FEED-IN TARIFF NORTHERN INDIANA PUBLIC SERVICE COMPANY Original Sheet No. 104 TO WHOM AVAILABLE Sheet No. 1 of 12 This Rate Schedule is a voluntary offer available to any Customer that operates within the Company s service

More information

PSO project EaseWind Enhanced ancillary services from Wind Power Plants. Anca D. Hansen DTU Wind Energy

PSO project EaseWind Enhanced ancillary services from Wind Power Plants. Anca D. Hansen DTU Wind Energy PSO project EaseWind Enhanced ancillary services from Wind Power Plants Anca D. Hansen DTU Wind Energy Background PSO project EaseWind (2011-2014) Enhanced Ancillary Services from Wind Power Plants Partners:

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

Review of Upstate Load Forecast Uncertainty Model

Review of Upstate Load Forecast Uncertainty Model Review of Upstate Load Forecast Uncertainty Model Arthur Maniaci Supervisor, Load Forecasting & Energy Efficiency New York Independent System Operator Load Forecasting Task Force June 17, 2011 Draft for

More information

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW-

P. SUMMARY: The Southeastern Power Administration (SEPA) establishes Rate Schedules JW- This document is scheduled to be published in the Federal Register on 08/29/2016 and available online at http://federalregister.gov/a/2016-20620, and on FDsys.gov 6450-01-P DEPARTMENT OF ENERGY Southeastern

More information

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2014

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2014 UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2014 FACULTY OF SCIENCE AND ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING TITLE OF PAPER: POWER SYSTEM ANALYSIS AND OPERATION COURSE

More information

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3 IJSRD International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 23210613 Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3 1 M.E. student 2,3 Assistant Professor 1,3 Merchant

More information

Power Grid & Blackouts. Prof. Ramzy R. Obaid

Power Grid & Blackouts. Prof. Ramzy R. Obaid Power Grid & Blackouts Prof. Ramzy R. Obaid With many thanks and appreciation to Professor Mohamed A. El Sharkawi Power System The electric power systems in the North America and Europe are probably the

More information

Feasibility Study for the Q MW Solar Project

Feasibility Study for the Q MW Solar Project Feasibility Study for the Q171 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC

More information

Energy Storage Interconnection Initiative

Energy Storage Interconnection Initiative Energy Storage Interconnection Initiative Stakeholder Call November 25, 2014 Agenda Time Agenda Item Speaker 10:00-10:10 Introduction, Stakeholder Process Tom Cuccia 10:10-10:30 Applying the GIDAP to energy

More information

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER EXPERIMENT CALIBRATION OF PHASE ENERGY METER THEORY:- Energy Meters are integrating instruments used to measure the quantity of electrical energy supplied to a circuit in a given time. Single phase energy

More information

Feasibility Study Report

Feasibility Study Report Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014

More information

Merger of the generator interconnection processes of Valley Electric and the ISO;

Merger of the generator interconnection processes of Valley Electric and the ISO; California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric

More information

Introduction to PowerWorld Simulator: Interface and Common Tools

Introduction to PowerWorld Simulator: Interface and Common Tools Introduction to PowerWorld Simulator: Interface and Common Tools I10: Introduction to Contingency Analysis 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com

More information

Energy Economics. Lecture 6 Electricity Markets ECO Asst. Prof. Dr. Istemi Berk

Energy Economics. Lecture 6 Electricity Markets ECO Asst. Prof. Dr. Istemi Berk Energy Economics ECO-4420 Lecture 6 Electricity Markets Asst. Prof. Dr. Istemi Berk istemi.berk@deu.edu.tr 1 Electricity Markets An Introduction Electricity secondary energy source generated from different

More information

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Journal of American Science 2015;11(11)   Integration of wind Power Plant on Electrical grid based on PSS/E Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity

More information

PROCESS SYSTEMS OPPORTUNITIES IN POWER GENERATION, STORAGE AND DISTRIBUTION

PROCESS SYSTEMS OPPORTUNITIES IN POWER GENERATION, STORAGE AND DISTRIBUTION PROCESS SYSTEMS OPPORTUNITIES IN POWER GENERATION, STORAGE AND DISTRIBUTION Masoud Soroush Department of Chemical and Biological Engineering Drexel University Donald J. Chmielewski Department of Chemical

More information

Optimal Power Flow (DC-OPF and AC-OPF)

Optimal Power Flow (DC-OPF and AC-OPF) Optimal Power Flow (DC-OPF and AC-OPF) DTU Summer School 2018 Spyros Chatzivasileiadis What is optimal power flow? 2 DTU Electrical Engineering Optimal Power Flow (DC-OPF and AC-OPF) Jun 25, 2018 Optimal

More information

Power Consump-on Management and Control for Peak Load Reduc-on in Smart Grids Using UPFC

Power Consump-on Management and Control for Peak Load Reduc-on in Smart Grids Using UPFC 1 Power Consump-on Management and Control for Peak Load Reduc-on in Smart Grids Using UPFC M. R. Aghaebrahimi, M. Tourani, M. Amiri Presented by: Mayssam Amiri University of Birjand Outline 1. Introduction

More information

Renewable Energy System Tariffs and Pricing

Renewable Energy System Tariffs and Pricing Renewable Energy System Tariffs and Pricing National Association of Regulatory Utility Commissioners Energy Regulatory Partnership Program with The National Commission for Energy State Regulation of Ukraine

More information

SOLENOID VALVES AND PNEUMATIC VALVES

SOLENOID VALVES AND PNEUMATIC VALVES A S E R I E S Catalogue 001 Directly operated solenoid valves Series A / way, 3/ way monostable, stable (with magnetic memory) Ports M5, G1/8, cartridge ø 4 The Series A solenoid valves are of the directly

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 17, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

SERVICE PROCEDURE. Revision 1 updated Table 1 to include old / new part number combination C91 / C92.

SERVICE PROCEDURE. Revision 1 updated Table 1 to include old / new part number combination C91 / C92. SERVICE PROCEDURE G-08506 R1 MARCH 2009 SUBJECT: SAFETY RECALL (U.S.) IDM FUSE BLOCK on certain INTERNATIONAL 3200, 3300, and IC Bus BE, CE, HC, RE models built 9/21/01 thru 12/31/07 with an INTERNATIONAL

More information

EEEE 524/624: Fall 2017 Advances in Power Systems

EEEE 524/624: Fall 2017 Advances in Power Systems EEEE 524/624: Fall 2017 Advances in Power Systems Lecture 6: Economic Dispatch with Network Constraints Prof. Luis Herrera Electrical and Microelectronic Engineering Rochester Institute of Technology Topics

More information

Distributed Energy Resources

Distributed Energy Resources Distributed Energy Resources WECC Data Subcommittee Rich Hydzik, Avista (ERSWG/DER Subgroup Lead) June 29, 2018 Why Are We Concerned About DER? Concern about changing generation fleet Large coal fired

More information

IMPACT OF MARKET RULES ON ENERGY STORAGE ECONOMICS

IMPACT OF MARKET RULES ON ENERGY STORAGE ECONOMICS IMPACT OF MARKET RULES ON ENERGY STORAGE ECONOMICS [Eric Cutter, Energy and Environmental Economics, 415-391-5100, eric@ethree.com] [Lakshmi Alagappan, Energy and Environmental Economics, 415-391-5100,

More information

CUSTOMER/ TWIN ARROWS PROJECT

CUSTOMER/ TWIN ARROWS PROJECT A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 41. Procurement Of RMR Generation... 2 41.1 Procurement Of Reliability Must-Run Generation By The CAISO... 2 41.2 Designation Of Generating Unit As Reliability Must-Run Unit... 2 41.3

More information

Column Name Type Description Year Number Year of the data. Vehicle Miles Traveled

Column Name Type Description Year Number Year of the data. Vehicle Miles Traveled Background Information Each year, Americans drive trillions of miles in their vehicles. Until recently, the number of miles driven increased steadily each year. This drop-off in growth has raised questions

More information

DATA SHEET NTC thermistors, accuracy line. BCcomponents

DATA SHEET NTC thermistors, accuracy line. BCcomponents DATA SHEET 2322 640 6... N thermistors, accuracy line Supersedes data of April 1995 File under BCcomponents, BC02 1998 Sep 04 FEATURES Accuracy over a wide temperature range High stability over a long

More information

The Gambia National Forum on

The Gambia National Forum on The Gambia National Forum on Renewable Energy Regulation Kairaba Hotel, The Gambia January 31 February 1, 2012 Tariff and Price Regulation of Renewables Deborah Erwin Public Service Commission of Wisconsin

More information

Pumped storage for balancing wind power fluctuations in an isolated grid

Pumped storage for balancing wind power fluctuations in an isolated grid Wind Power to the Grid EPE Wind Energy Chapter 1 st seminar Delft University of Technology, 8-9 March 008 Pumped storage for balancing wind power fluctuations in an isolated grid Jon Are Suul, Professor

More information

Physics 2048 Test 2 Dr. Jeff Saul Fall 2001

Physics 2048 Test 2 Dr. Jeff Saul Fall 2001 Physics 2048 Test 2 Dr. Jeff Saul Fall 2001 Name: Group: Date: READ THESE INSTRUCTIONS BEFORE YOU BEGIN Before you start the test, WRITE YOUR NAME ON EVERY PAGE OF THE EXAM. Calculators are permitted,

More information

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances

Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances Ukujima Photovoltaic Park 400 MW Stable Integration of a 400MW Photovoltaic Farm into the Japanese Power System Challenges and Chances 29 Juli 2014 Page 1 Characteristics of the Project Parameter Detail

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

Every Friday, Bart and Lisa meet their friends at an after-school club. They spend the afternoon playing Power Up, a game about batteries.

Every Friday, Bart and Lisa meet their friends at an after-school club. They spend the afternoon playing Power Up, a game about batteries. Battery Lab NAME Every Friday, Bart and Lisa meet their friends at an after-school club. They spend the afternoon playing Power Up, a game about batteries. The object of the game is to arrange battery

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY Short Circuit Analysis System Operations Department System Planning Section March 2001 I. Introduction XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

More information

Generation Capacity Design for a Microgrid for Measurable Power Quality Indexes

Generation Capacity Design for a Microgrid for Measurable Power Quality Indexes 1 Generation Capacity Design for a Microgrid for Measurable Power Quality Indexes Q. Fu, A. Solanki, L. F. Montoya, Student Members, IEEE, A. Nasiri, Senior Member, IEEE, V. Bhavaraju, Senior Member, IEEE,

More information

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection

More information

Evaluation of a Gearbox s High-Temperature Trip

Evaluation of a Gearbox s High-Temperature Trip 42-46 tlt case study 2-04 1/13/04 4:09 PM Page 42 Case Study Evaluation of a Gearbox s High-Temperature Trip By Vinod Munshi, John Bietola, Ken Lavigne, Malcolm Towrie and George Staniewski (Member, STLE)

More information

Evaluating Losses in Electrical Equipment Focus on Transmission Utilities. CNY Engineering Expo 2016 Syracuse, New York Arthur C. Depoian P.E.

Evaluating Losses in Electrical Equipment Focus on Transmission Utilities. CNY Engineering Expo 2016 Syracuse, New York Arthur C. Depoian P.E. Evaluating Losses in Electrical Equipment Focus on Transmission Utilities CNY Engineering Expo 2016 Syracuse, New York Arthur C. Depoian P.E. Contents Introduction Present Value of ongoing energy costs

More information

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS

ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS MIL-STD-1539 (USAF) 1 AUGUST 1973 MILITARY STANDARD ELECTRICAL POWER, DIRECT CURRENT, SPACE VEHICLE DESIGN REQUIREMENTS FSC 1810 Electrical Power, Direct Current, Space Vehicle Design Requirements MIL-STD-1539

More information

Phys 202A. Lab 7 Batteries, Bulbs and Current

Phys 202A. Lab 7 Batteries, Bulbs and Current Phys 202A Lab 7 Batteries, Bulbs and Current Name Objectives: To understand how a voltage (potential difference) results in a current flow through a conductor. To learn to design and wire simple circuits

More information

Frequently Asked Questions New Tagging Requirements

Frequently Asked Questions New Tagging Requirements Frequently Asked Questions New Tagging Requirements Q: Are there new E-tagging requirements related to the new fifteen minute market FERC Order No. 764 fifteen minute scheduling implemented on May 1, 2014?

More information

TransWest Express Project

TransWest Express Project TransWest Express Project Phase One--Feasibility Study Final Study Report November 2006 A subsidiary of Pinnacle West Capital Corporation Executive Summary On October 21, 2005 Arizona Public Service Company

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

Can Vehicle-to-Grid (V2G) Revenues Improve Market for Electric Vehicles?

Can Vehicle-to-Grid (V2G) Revenues Improve Market for Electric Vehicles? Can Vehicle-to-Grid (V2G) Revenues Improve Market for Electric Vehicles? Michael K. Hidrue George R. Parsons Willett Kempton Meryl P. Gardner July 7, 2011 International Energy Workshop Stanford University

More information

SUGGESTED SOLUTION IPCC MAY 2017EXAM. Test Code - I M J

SUGGESTED SOLUTION IPCC MAY 2017EXAM. Test Code - I M J SUGGESTED SOLUTION IPCC MAY 2017EXAM COSTING Test Code - I M J 7 1 4 5 BRANCH - (MULTIPLE) (Date : 05.03.2017) Head Office : Shraddha, 3 rd Floor, Near Chinai College, Andheri (E), Mumbai 69. Tel : (022)

More information

Chapter 21 Electric Current and Direct- Current Circuits

Chapter 21 Electric Current and Direct- Current Circuits Chapter 21 Electric Current and Direct- Current Circuits Menu Electric Current Resistance and Ohm s Law Energy and Power in Electric Circuits Resistors in Series and Parallel HW # 5 Pg. 754 759: # 7, 8,

More information

Performance Analysis of Transient Stability on a Power System Network

Performance Analysis of Transient Stability on a Power System Network Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere

More information

Contingency Analysis

Contingency Analysis Contingency Analysis Power systems are operated so that overloads do not occur either in real-time or under any statistically likely contingency. This is often called maintaining system security Simulator

More information

The Coefficient of Determination

The Coefficient of Determination The Coefficient of Determination Lecture 46 Section 13.9 Robb T. Koether Hampden-Sydney College Tue, Apr 13, 2010 Robb T. Koether (Hampden-Sydney College) The Coefficient of Determination Tue, Apr 13,

More information

GC0101 Mod Title: EU Connection Codes GB Implementation Mod 2

GC0101 Mod Title: EU Connection Codes GB Implementation Mod 2 Stage 01: Modification Proposal Grid Code GC0101 Mod Title: EU Connection Codes GB Implementation Mod 2 Purpose of Modification: This modification (2/4) will set out within the Grid Code the following

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

Repairing your vehicle

Repairing your vehicle Repairing your vehicle Estimating procedure Depreciation Recycled parts The claims process The first step to repairing your vehicle is to report your Autopac claim by telephone: In Winnipeg: 204-985-7000

More information

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach DC Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach F. Akhter 1, D.E. Macpherson 1, G.P. Harrison 1, W.A. Bukhsh 2 1 Institute for Energy System, School of Engineering

More information

APIFLO-M series Series

APIFLO-M series Series APIFLO-M series Series Horizontal Multistage Pump According to API610 Capacity: up to 650m 3 /h (50Hz) up to 780 m 3 /h (60Hz) Head: up to 1200m (50Hz) up to 1728 m (60Hz) Pressure: APIFLO-M: up to 25

More information

Voting Draft Standard

Voting Draft Standard page 1 of 7 Voting Draft Standard EL-V1M4 Sections 1.7.1 and 1.7.2 March 2013 Description This proposed standard is a modification of EL-V1M4-2009-Rev1.1. The proposed changes are shown through tracking.

More information

Docket No. ER June 2018 Informational Report Energy Imbalance Market Transition Period Report Idaho Power Company

Docket No. ER June 2018 Informational Report Energy Imbalance Market Transition Period Report Idaho Power Company California Independent System Operator Corporation August 21, 2018 The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 Re: California

More information

694 Electric Machines

694 Electric Machines 694 Electric Machines 9.1 A 4-pole wound-rotor induction motor is used as a frequency changer. The stator is connected to a 50 Hz, 3-phase supply. The load is connected to the rotor slip rings. What are

More information