Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Size: px
Start display at page:

Download "Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor"

Transcription

1 > 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper presents the results of analyses ab transient stability enhancement using both devices-the fault current limiter and the thyristor controlled braking resistor. Following a major disturbance in power system, the fault current limiter operates for limiting of the fault current, enhancement of the transient stability and suppression of the turbine shaft torsional oscillation, and then the thyristor controlled braking resistor operates with the objective of fast control of generator disturbances. The effectiveness of both devices has been demonstrated by considering 3LG (three-phase-to-ground) fault at 1 fault points in a two-machine infinite bus system. The simulation results indicate a significant transient stability enhancement and damping shaft torsional oscillations. Index Terms Fault current limiter, power system transient stability, thyristor controlled braking resistor, turbine shaft torsional torque I. INTRODUCTION ITH the increasing demand for electric power, power W systems are becoming larger and more interconnected. As a consequence, the fault current increase, and transient stability problems become more serious. Consequently, in order to maintain the stability of power system, replacement of substation equipment or changes in the configuration of the system will be needed, and this ultimately leads to decreased operational flexibility and lower reliability. The use of Fault Current Limiters (FCLs) is being evaluated as one element necessary to limit the fault current and enhance the power system transient stability [1]-[3]. FCL is a device that limits the fault current by generating an impedance when a fault occurs. In addition, the limiting impedance generated to limit fault currents proves helpful in increasing generator put degraded by a fault, thus providing stabilization. However, as FCLs installed in series with transmission lines can be just operated during the period from the fault occurrence to the fault clearing, they cannot control the generator disturbances after the clearing of fault. M.Yagami is with the Department of Electrical and Electronic Engineering, Hokkaido Institute of Technology, Sapporo, JAPAN ( yagami@hit.ac.jp). J.Tamura is with the Department of Electrical and Electronic Engineering, Kitami Institute of Technology, Kitami, JAPAN ( tamuraj@mail.kitami-it.ac.jp). The Braking Resistor (BR) is also known as a very effective device for transient stability control. It can be viewed as a fast load injection to absorb excess transient energy which arises due to system disturbances. Besides, with the recent development of power electronics technology, replacing the circuit breaker with the semiconductor device is becoming feasible. Several thyristor-based control techniques [4],[5] have been proposed in the literature for the switching of BR. Since the thyristor controlled braking resistor (TCBR) can control the accelerating power in generators with flexibility, the power system stability is enhanced more than that of the use of BR controlled by mechanical device. However, as BR is installed in parallel with the transmission lines, BR cannot be operated before the clearing of faults. From these viewpoints, in this paper, we have proposed the use of both devices-fcl and TCBR for the purpose of a significant transient stability enhancement. If both devices-fcl and TCBR operate at the same bus, the stabilization control scheme can be carried continuously and with flexibility for a long duration (i.e., FCL operates from the fault occurrence instance to the fault clearing, and then TCBR operates dynamically until the generator disturbance becomes small). Through the simulation results, the effectiveness of the use of both devices on transient stability enhancement is demonstrated. This paper also presents the effectiveness of the use of both devices on suppression of the turbine shaft torsional oscillations. Simulations are performed using EMTP/ATP. II. POWER SYSTEM MODEL The power system model used for the simulation is shown in Fig. 1. It consists of two generators, an infinite bus, transformers and double-circuit transmission lines. The generator parameters are listed in Table I [6]. Both the generators and neutral points on the transformers Y-sides are connected directly. Only the leakage inductance of transformers is considered; the magnetizing inductance is neglected. The line constants in the diagram are given in terms of RjX (jb/) per circuit. The TCBR with a conductance value of G TCBR is connected to the Y-side of the transformer, Tr.1, through the thyristor switching circuit. The FCL is installed in at the same bus. The turbine shaft system is represented by a /7/$5. 7 IEEE 38 PowerTech 7

2 > 57 < (P/Q=/.35) (P/Q=1.9/.1) G1 j65 FCL 17j.144 (j373) 38j.16 (j53) F1 F11 F1 F9 j586 (P/V=1./) G Tr.1 PI Controller Device G ( ) TCBR G TCBR F1 64j.3 3LG (j765) F (P/Q= 1.5/) F3 F4 j.17 (j44) Tr.3 4 F8 78j.34 (j895) F7 F6 34j.184 (j395) F5 j576 (P/Q=.9/.3) Infinite bus Tr. Turbine Shaft System HP IP LPA LPB GEN EXC HP: High-Pressure Turbine IP: Intermediate-Pressure Turbine LPA, LPB: Low-Pressure Turbine GEN: Generator EXC: Exciter 5Hz, 1MVA BASE Fig. 1. Power system model. r a X l X d X q X d X q X d r a X l X d X q X d X q X d G1 G G1 HP Turbine LP Turbine LPA Turbine LPB Turbine Generator Exciter G HP Turbine LP Turbine LPA Turbine LPB Turbine Generator Exciter TABLE I GENERATOR PARAMETERS Rating (MVA) X q X T d T q T d T q H X q X T d T q T d T q H Rating (MVA) TABLE II TURBINE SHAFT PARAMETERS Inertia constant (s) Spring constant (pu T/rad) Inertia constant (s) Spring constant (pu T/rad) AVR Vs GOV m - Vso S m Efdo 6-mass-point model as shown in Fig. 1, with the parameters given in Table II [7]. The models of AVR and governor are shown in Fig.. In the simulation study, it has been considered that the three-lines-to-ground (3LG) fault occurs at.1 sec at some of the 1 fault points shown in Fig. 1 (F1 to F1). The circuit breakers on the faulted line are opened at. sec and reclosed at sec. It is assumed that the circuit breakers clear the line when the current through it crosses the zero level. III. MODELING OF FCL A variety of FCLs with various approaches to limiting current have been developed and tested. The FCL conceived of in this paper consists of a detector, a controller, and a limiting resistance, all common hardware found in an FCL of any type. Fig. 3 shows the changes over time for the limiting resistance created in an FCL. It is assumed that the limiting resistance value is pu (based on G1 rating), and the fault detection time and starting time of limiting resistance are msec and 1 msec respectively [1]. Namely, FCL starts to operate at.1 1S Po -4. Fig.. AVR and governor models Efd P 39

3 > 57 < 3 sec, and then the limiting resistance increases linearly from pu to pu within 1 msec. Although the effect of enhancement of transient stability is changed depend on the limiting resistance value, pu is the most effective value on the transient stability enhancement which is determined based on the results of simulation using various limiting resistance values. Limiting Resistance IV. MODELING OF TCBR As shown in Fig.1, the generator speed deviation,, and the desired conductance value of BR, G, are selected as the input and put respectively. Following a fault in power system, the rotor speed deviation,, of the generator is measured, and then the desired conductance value, G, is determined by PI controller. PI controller is designed based on control rules as follows: (1) If is large, G is determined so that the power dissipated in BR becomes also large, () If is small, G is determined so that the power dissipated in BR becomes also small, and (3) If is less than 1 pu, G is zero ( =18 degree). For the fast control of the generator disturbances, we have tuned the controller parameters by trial and error method. Firing-angle,, for the thyristor switch is calculated from the put of the PI controller (i.e., G ). The desired power consumption determined by G and the real power consumption determined by G TCBR are equal and hence firing-angle,, can be calculated from the following power equation. V GTCBR 1 Fault detection time sin Starting time Fig. 3. Limiting resistance characteristics. Where V is the rms value of the generator terminal bus voltage and G TCBR is specified to pu. However, the firing-angle,, cannot be directly calculated from eq.(1) since it includes a trigonometric function. So, in this simulation, firstly by using eq.(1), a set of different values of G is calculated for the values of firing-angle ranging from to 18 degrees with a step V G (1) of degrees. Then by using the linear interpolation technique, firing-angle,, is determined. V. SIMULATION RESULTS A. Limitation of Fault Current Fig. 4 shows the 3-phase current flowing into the Y-side of the transformer, Tr.1, during 3LG fault at point F1. In case of no devices, the fault currents rise up significantly and DC component in the a- and c-phase currents decreases slowly (The fault occurrence time corresponds to nearly the maximum terminal voltage for phase b at generator G1, and hence hardly any DC component is included in the b-phase current.) On the other hand, in case of with the both devices of FCL and TCBR, the fault currents are limited and the DC component decreases rapidly by the limiting resistance of FCL. Current Current (a) phase 'a' phase 'b' phase 'c' (b) With FCL and TCBR Fig phase current at Y-side of Tr.1 (fault point F1). phase 'a' phase 'b' phase 'c' B. Enhancement of Transient Stability Fig. 5 shows the load angle responses of both generators in 4

4 > 57 < 4 the case of fault point F1. In case of with devices, the load angle swings of both generators are restrained more than that of no devices. This is because the difference between the mechanical input power and the electrical put power in the generator is decreased due to absorption of the real power by FCL or TCBR. In case of with FCL, the first waves of load angle swings are restrained effectively. However, FCL can be just operated during the period from the fault occurrence to the fault clearing, it cannot restrain the load angle swings after the clearing of fault. The load angle swings are also effectively restrained in case of with TCBR. In particular, the load angle of generator G1 becomes almost constant after the second wave. However, as TCBR starts to operate after the clearing of fault, the first wave of load angle swing is not restrained so much. Finally, in case of with both devices of FCL and TCBR, the load angle swings are restrained effectively for the overall duration of simulation. From these responses, it is clear that the use of both devices of FCL and TCBR makes the system stable quickly more than the use of any of these devices. 1 To evaluate the transient stability in all fault points, we have used the stability index, W c, given by T d Wc Wtotal dt / system base power () dt where W total is the summation of kinetic energy of each generator and T is the simulation time selected to 7 sec. By using W total, we can evaluate the transient stability of overall power system, taking each generator power rating into account. Fig. 6 shows the total kinetic energy of both generators in case of fault at point F1. W total (J).6x1 9.6x1 9 8x1 9 6x x1 9 Load angle (deg) 6 4 (a) G1 With FCL With TCBR Fig. 6. W total (fault point F1). W c is the integrated variation of the energy exchanged between the generator rotor and the system; thus, the lower the value of the parameter, the smaller the transient swing, and the better the overall system stability. Fig. 7 shows the stability index, W c, for each fault point. As can be seen, the both devices-fcl and TCBR can effectively enhance the power system transient stability for all fault points. 1 5 Load angle (deg) 8 6 With FCL With TCBR W c (s) (b) G Fig. 5. Load angle responses (fault point F1) Fault point Fig. 7. W c at each fault point. 41

5 > 57 < 5 C. Suppression of Turbine Shaft Torsional Oscillation In reality, a steam turbine-generator rotor has a very complex mechanical structure consisting of several predominant masses (such as rotors of turbine sections, generator rotor, couplings, and exciter rotor) connected by shafts of finite stiffness. Therefore, when the generator is perturbed, torsional oscillations occur between different sections of the turbine-generator rotor. The certain electrical system disturbance can significantly reduce the life expectancy of turbine shafts [8]. Therefore, sufficient damping is needed to reduce turbine shaft torsional oscillations. Fig. 8 shows the turbine shaft torque responses of generator G1 for fault point F1. In case of with devices, the torque oscillations are effectively restrained. In particular, the use of both devices-fcl and TCBR is effective. Fig. 9 shows the maximum shaft torque of generator G1 for each fault point. As can be seen, the maximum shaft torque is restrained for almost all fault points. From these responses, it can be said that FCL and TCBR are effective devices for damping the turbine shaft torque oscillations. (a) HP-IP (b) IP-LPA HP-IP IP -L P A LPA-LPB LPB-G EN (a) -.5 (b) With FCL Maximum torque (c) LPA-LPB (d) LPB-GEN Turbine shaft torque -.5 (c) With TCBR Fault point Fig. 9. Maximum torque at each fault point. - (d) With FCL and TCBR -.5 Fig. 8. Turbine shaft torque responses (fault point F1). VI. CONCLUSION In order to enhance the power system transient stability and damp the turbine shaft torsional oscillations, the use of both devices-fault current limiter and thyristor controlled braking resistor is proposed in this paper. If both devices operate at the same bus, the stabilization control scheme can be carried continuously and with flexibility from the fault occurrence instance, thus the transient stability is enhanced effectively. The effectiveness of both devices is demonstrated by simulation considering three-lines-to-ground fault in a two-machine infinite bus system. Simulation results clearly 4

6 > 57 < 6 indicate the significant enhancement of the transient stability and suppression of turbine shaft torsional oscillations. REFERENCES [1] IEE Japan, State-of-the art and trends in fault current limiting technologies, IEEJ Report, no.79, [] E. Leung, Superconducting fault current limiters, IEEE Power Engineering Review, pp.15-3, Aug.. [3] M. Sjostrom, R.Cherkaoui and B.Dutoit, Enhancement of power system transient stability using superconducting fault current limiters, IEEE Trans. Applied Superconductivity, vol.9, no., pp , [4] H.Jiang, J.Dorsey, and T.Habetler, A cost effective generator brake for improved generator transient response, IEEE Trans. Power Systems, vol.9, no.4, pp , [5] M.H.Ali, T.Murata, and J.Tamura, An analysis of the fuzzy logic controlled braking resistor for transient stability improvement in multi-machine power system, IEEJ Trans. PE. vol.14, no.4, pp , 4. [6] Y.Sekine, Transient Analysis Theory of Power System, Ohmu Press, 1989 [7] IEEE subsynchronous resonance task force of the dynamic system performance working group power system committee, First benchmark model for computer simulation of subsynchronous resonance, IEEE Trans. Power Apparatus System, vol. PAS-96, no.5, pp , [8] P.Kundur, Power system stability and control, McGraw-Hill,

Investigation of Transient Recovery Voltage Across a Circuit Breaker with Presence of Braking Resistor

Investigation of Transient Recovery Voltage Across a Circuit Breaker with Presence of Braking Resistor Australian Journal of Basic and Applied Sciences, 5(5): 231-235, 2011 ISSN 1991-8178 Investigation of Transient Recovery Voltage Across a Circuit Breaker with Presence of Braking Resistor 1 Amir Ghorbani,

More information

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 2 August 2015 ISSN (online): 2349-784X Power System Stability Analysis on System Connected to Wind Power Generation with

More information

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The

More information

IEEE Transactions on Applied Superconductivity, 2012, v. 22 n. 3, p :1-5

IEEE Transactions on Applied Superconductivity, 2012, v. 22 n. 3, p :1-5 Title Transient stability analysis of SMES for smart grid with vehicleto-grid operation Author(s) Wu, D; Chau, KT; Liu, C; Gao, S; Li, F Citation IEEE Transactions on Applied Superconductivity, 2012, v.

More information

Performance Analysis of Transient Stability on a Power System Network

Performance Analysis of Transient Stability on a Power System Network Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere

More information

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Journal of American Science 2015;11(11)   Integration of wind Power Plant on Electrical grid based on PSS/E Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity

More information

Advance Electronic Load Controller for Micro Hydro Power Plant

Advance Electronic Load Controller for Micro Hydro Power Plant Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman

More information

ECEN 667 Power System Stability Lecture 19: Load Models

ECEN 667 Power System Stability Lecture 19: Load Models ECEN 667 Power System Stability Lecture 19: Load Models Prof. Tom Overbye Dept. of Electrical and Computer Engineering Texas A&M University, overbye@tamu.edu 1 Announcements Read Chapter 7 Homework 6 is

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 17, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC Int. J. of P. & Life Sci. (Special Issue Engg. Tech.) Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC Durgesh Kumar and Sonora ME Scholar Department of Electrical

More information

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Raju Pandey, A. K. Kori Abstract FACTS devices can be added to power transmission and distribution systems at appropriate

More information

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment 2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in

More information

Overview of Flexible AC Transmission Systems

Overview of Flexible AC Transmission Systems Overview of Flexible AC Transmission Systems What is FACTS? Flexible AC Transmission System (FACTS): Alternating current transmission systems incorporating power electronic-based and other static controllers

More information

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen) Technical Paper: Low voltage ride-through testing of wind turbine converters at ABB helps wind turbines meet the requirements of IEC 61400-21 more quickly (by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka

More information

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor 1 Chaudhari Krunal R, 2 Prof. Rajesh Prasad 1 PG Student, 2 Assistant Professor, Electrical Engineering

More information

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran Effect of Increasing the Grounding Grid Resistance of a Ground System at a Substation on the Safety and Transient Overvoltage on the Interior Equipments M. Bashir M.Sc student, Student Member, IEEE Ferdowsi

More information

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 01 July 2015 ISSN (online): 2349-784X Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC Ravindra Mohana

More information

Simulation of Voltage Stability Analysis in Induction Machine

Simulation of Voltage Stability Analysis in Induction Machine International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 6, Number 1 (2013), pp. 1-12 International Research Publication House http://www.irphouse.com Simulation of Voltage

More information

Review paper on Fault analysis and its Limiting Techniques.

Review paper on Fault analysis and its Limiting Techniques. Review paper on Fault analysis and its Limiting Techniques. Milap Akbari 1, Hemal Chavda 2, Jay Chitroda 3, Neha Kothadiya 4 Guided by: - Mr.Gaurang Patel 5 ( 1234 Parul Institute of Engineering &Technology,

More information

INDUCTION motors are widely used in various industries

INDUCTION motors are widely used in various industries IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 6, DECEMBER 1997 809 Minimum-Time Minimum-Loss Speed Control of Induction Motors Under Field-Oriented Control Jae Ho Chang and Byung Kook Kim,

More information

ANFIS CONTROL OF ENERGY CONTROL CENTER FOR DISTRIBUTED WIND AND SOLAR GENERATORS USING MULTI-AGENT SYSTEM

ANFIS CONTROL OF ENERGY CONTROL CENTER FOR DISTRIBUTED WIND AND SOLAR GENERATORS USING MULTI-AGENT SYSTEM ANFIS CONTROL OF ENERGY CONTROL CENTER FOR DISTRIBUTED WIND AND SOLAR GENERATORS USING MULTI-AGENT SYSTEM Mr.SK.SHAREEF 1, Mr.K.V.RAMANA REDDY 2, Mr.TNVLN KUMAR 3 1PG Scholar, M.Tech, Power Electronics,

More information

International Journal of Emerging Technology and Innovative Engineering Volume 2, Issue 4, April 2016 (ISSN: )

International Journal of Emerging Technology and Innovative Engineering Volume 2, Issue 4, April 2016 (ISSN: ) International Journal of Emerging Technology and Innovative Engineering Volume 2, Issue 4, April 2016 (ISSN: 2394 6598) Date of Publication: 25.04.2016 TRANSIENT FREE TSC COMPENSATOR FOR REACTIVE LOAD

More information

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) Nazneen Choudhari Department of Electrical Engineering, Solapur University, Solapur Nida N Shaikh Department of Electrical

More information

Statcom Operation for Wind Power Generator with Improved Transient Stability

Statcom Operation for Wind Power Generator with Improved Transient Stability Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 3 (2014), pp. 259-264 Research India Publications http://www.ripublication.com/aeee.htm Statcom Operation for Wind Power

More information

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Abstract: G. Thrisandhya M.Tech Student, (Electrical Power systems), Electrical and Electronics Department,

More information

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG C.Nikhitha 1, C.Prasanth Sai 2, Dr.M.Vijaya Kumar 3 1 PG Student, Department of EEE, JNTUCE Anantapur, Andhra Pradesh, India.

More information

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink Satvinder Singh Assistant Professor, Department of Electrical Engg. YMCA University of Science & Technology, Faridabad,

More information

Analysis on natural characteristics of four-stage main transmission system in three-engine helicopter

Analysis on natural characteristics of four-stage main transmission system in three-engine helicopter Article ID: 18558; Draft date: 2017-06-12 23:31 Analysis on natural characteristics of four-stage main transmission system in three-engine helicopter Yuan Chen 1, Ru-peng Zhu 2, Ye-ping Xiong 3, Guang-hu

More information

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation 822 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 3, JULY 2002 Adaptive Power Flow Method for Distribution Systems With Dispersed Generation Y. Zhu and K. Tomsovic Abstract Recently, there has been

More information

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line Nitin goel 1, Shilpa 2, Shashi yadav 3 Assistant Professor, Dept. of E.E, YMCA University

More information

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,

More information

Real Time Transient Stability Simulator of Large Scale Multi-Machine Power System in Matlab/Simulink Environment

Real Time Transient Stability Simulator of Large Scale Multi-Machine Power System in Matlab/Simulink Environment Real Time Transient Stability Simulator of Large Scale Multi-Machine Power System in Matlab/Simulink Environment T. Hiyama, Senior member, IEEE, Y. Tsukawaki, nonmember, M. Kawakita, nonmember Abstract--A

More information

Influence of Parameter Variations on System Identification of Full Car Model

Influence of Parameter Variations on System Identification of Full Car Model Influence of Parameter Variations on System Identification of Full Car Model Fengchun Sun, an Cui Abstract The car model is used extensively in the system identification of a vehicle suspension system

More information

Forced vibration frequency response for a permanent magnetic planetary gear

Forced vibration frequency response for a permanent magnetic planetary gear Forced vibration frequency response for a permanent magnetic planetary gear Xuejun Zhu 1, Xiuhong Hao 2, Minggui Qu 3 1 Hebei Provincial Key Laboratory of Parallel Robot and Mechatronic System, Yanshan

More information

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION International Journal of Latest Research in Science and Technology Volume 3, Issue 1: Page No.68-74,January-February 2014 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 POWER QUALITY IMPROVEMENT

More information

Low Speed Control Enhancement for 3-phase AC Induction Machine by Using Voltage/ Frequency Technique

Low Speed Control Enhancement for 3-phase AC Induction Machine by Using Voltage/ Frequency Technique Australian Journal of Basic and Applied Sciences, 7(7): 370-375, 2013 ISSN 1991-8178 Low Speed Control Enhancement for 3-phase AC Induction Machine by Using Voltage/ Frequency Technique 1 Mhmed M. Algrnaodi,

More information

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,

More information

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device Australian Journal of Basic and Applied Sciences, 5(9): 1180-1187, 2011 ISSN 1991-8178 Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

More information

THE EFFECT OF DISTURBANCES IN THE ELECTRICAL POWER SYSTEM ON TORQUE MOMENTS OF THE HIGH-POWER TURBINE SET SHAFT

THE EFFECT OF DISTURBANCES IN THE ELECTRICAL POWER SYSTEM ON TORQUE MOMENTS OF THE HIGH-POWER TURBINE SET SHAFT THE EFFECT OF DISTURBANCES IN THE ELECTRICAL POWER SYSTEM ON TORQUE MOMENTS OF THE HIGH-POWER TURBINE SET SHAFT The results presented in this paper have been obtained through research co-financed by the

More information

FEASIBILITY STYDY OF CHAIN DRIVE IN WATER HYDRAULIC ROTARY JOINT

FEASIBILITY STYDY OF CHAIN DRIVE IN WATER HYDRAULIC ROTARY JOINT FEASIBILITY STYDY OF CHAIN DRIVE IN WATER HYDRAULIC ROTARY JOINT Antti MAKELA, Jouni MATTILA, Mikko SIUKO, Matti VILENIUS Institute of Hydraulics and Automation, Tampere University of Technology P.O.Box

More information

Semi-Active Suspension for an Automobile

Semi-Active Suspension for an Automobile Semi-Active Suspension for an Automobile Pavan Kumar.G 1 Mechanical Engineering PESIT Bangalore, India M. Sambasiva Rao 2 Mechanical Engineering PESIT Bangalore, India Abstract Handling characteristics

More information

Wind Farm Evaluation and Control

Wind Farm Evaluation and Control International society of academic and industrial research www.isair.org IJARAS International Journal of Academic Research in Applied Science (2): 2-28, 202 ijaras.isair.org Wind Farm Evaluation and Control

More information

Examples of Electric Drive Solutions and Applied Technologies

Examples of Electric Drive Solutions and Applied Technologies Examples of Electric Drive Solutions and Applied Technologies 2 Examples of Electric Drive Solutions and Applied Technologies Atsushi Sugiura Haruo Nemoto Ken Hirata OVERVIEW: Hitachi has worked on specific

More information

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis

More information

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load,,, ABSTRACT- In this paper the steady-state analysis of self excited induction generator is presented and a method to calculate

More information

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller Vidya S 1, Dr. Vinod Pottakulath 2, Labeeb M 3 P.G. Student, Department of Electrical and Electronics Engineering,

More information

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier Performance of DC Motor Supplied From Single Phase AC-DC Rectifier Dr Othman A. Alnatheer Energy Research Institute-ENRI King Abdulaziz City for Science and Technology- KACST P O Box 6086, Riyadh 11442,

More information

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING A.ANBARASAN* Assistant Professor, Department of Electrical and Electronics Engineering, Erode Sengunthar Engineering College, Erode, Tamil Nadu, India

More information

A Model of Wind Turbine s Flexibility Shaft

A Model of Wind Turbine s Flexibility Shaft Advanced Materials Research Online: 2014-06-18 ISSN: 1662-8985, Vols. 953-954, pp 384-388 doi:10.4028/www.scientific.net/amr.953-954.384 2014 Trans Tech Publications, Switzerland A Model of Wind Turbine

More information

The 1,400-MW Kii-Channel HVDC System

The 1,400-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System 114 Hiroyuki Nakao Masahiro Hirose Takehisa Sakai Naoki Kawamura Hiroaki Miyata Makoto Kadowaki Takahiro Oomori Akihiko Watanabe OVERVIEW:

More information

Reactive Power Management Using TSC-TCR

Reactive Power Management Using TSC-TCR Reactive Power Management Using TSC-TCR Kumarshanu Chaurasiya 1, Sagar Rajput 1, Sachin Parmar 1, Prof. Abhishek Patel 2 1 Student, Department of Electrical Engineering, Vadodara institute of engineering,

More information

Implementation of FC-TCR for Reactive Power Control

Implementation of FC-TCR for Reactive Power Control IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 5, Issue 5 (May. - Jun. 2013), PP 01-05 Implementation of FC-TCR for Reactive Power Control

More information

Study on Analysis Model for Transient Phenomena of Brushless Synchronous Generator

Study on Analysis Model for Transient Phenomena of Brushless Synchronous Generator IEEJ Journal of Industry Applications Vol.3 No.6 pp.414 421 DOI: 10.1541/ieejjia.3.414 Paper Study on Analysis Model for Transient Phenomena of Brushless Synchronous Generator Daisuke Hiramatsu a) Member,

More information

Computer Aided Transient Stability Analysis

Computer Aided Transient Stability Analysis Journal of Computer Science 3 (3): 149-153, 2007 ISSN 1549-3636 2007 Science Publications Corresponding Author: Computer Aided Transient Stability Analysis Nihad M. Al-Rawi, Afaneen Anwar and Ahmed Muhsin

More information

INVESTIGATION OF THE IMPACT OF SWITCHING A HEAVILY LOADED TRANSMISSION LINE ON OPERATION OF A POWER PLANT WITH TURBINE-GENERATOR UNITS

INVESTIGATION OF THE IMPACT OF SWITCHING A HEAVILY LOADED TRANSMISSION LINE ON OPERATION OF A POWER PLANT WITH TURBINE-GENERATOR UNITS Investigation of the Impact of Switching a Heavily Loaded Transmission Line on Operation of a Power Plant with Turbine-generator Units INVESTIGATION OF THE IMPACT OF SWITCHING A HEAVILY LOADED TRANSMISSION

More information

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant Vu Minh Phap*, N. Yamamura, M. Ishida, J. Hirai, K. Nakatani Department of Electrical and Electronic Engineering,

More information

DESIGN AND ANALYSIS OF PRE- INSERTION RESISTOR MECHANISM

DESIGN AND ANALYSIS OF PRE- INSERTION RESISTOR MECHANISM DESIGN AND ANALYSIS OF PRE- INSERTION RESISTOR MECHANISM Bhavik Bhesaniya 1, Nilesh J Parekh 2, Sanket Khatri 3 1 Student, Mechanical Engineering, Nirma University, Ahmedabad 2 Assistant Professor, Mechanical

More information

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE 1 AUNG KYAW MIN, 2 YAN AUNG OO 1,2 Electrical Engineering, Department of Electrical Power Engineering,

More information

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT Prof. Chandrashekhar Sakode 1, Vicky R. Khode 2, Harshal R. Malokar 3, Sanket S. Hate 4, Vinay H. Nasre 5, Ashish

More information

Real And Reactive Power Saving In Three Phase Induction Machine Using Star-Delta Switching Schemes

Real And Reactive Power Saving In Three Phase Induction Machine Using Star-Delta Switching Schemes Real And Reactive Power Saving In Three Phase Induction Machine Using Star-Delta Switching Schemes Ramesh Daravath, Lakshmaiah Katha, Ch. Manoj Kumar, AVS Aditya ABSTRACT: Induction machines are the most

More information

Modeling and Simulation of Five Phase Inverter Fed Im Drive and Three Phase Inverter Fed Im Drive

Modeling and Simulation of Five Phase Inverter Fed Im Drive and Three Phase Inverter Fed Im Drive RESEARCH ARTICLE OPEN ACCESS Modeling and Simulation of Five Phase Inverter Fed Im Drive and Three Phase Inverter Fed Im Drive 1 Rahul B. Shende, 2 Prof. Dinesh D. Dhawale, 3 Prof. Kishor B. Porate 123

More information

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application Issue #WP102: Technical Information from Cummins Generator Technologies Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application White Paper Ram Pillai

More information

Volume II, Issue VII, July 2013 IJLTEMAS ISSN

Volume II, Issue VII, July 2013 IJLTEMAS ISSN Different Speed Control Techniques of DC Motor: A Comparative Analysis Virendra Singh Solanki, Virendra Jain, Anil Kumar Chaudhary Department of Electrical and Electronics Engineering,RGPV university,

More information

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation Computation of Sensitive Node for IEEE- 4 Bus system Subjected to Load Variation P.R. Sharma, Rajesh Kr.Ahuja 2, Shakti Vashisth 3, Vaibhav Hudda 4, 2, 3 Department of Electrical Engineering, YMCAUST,

More information

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID ROHIT GAJBHIYE 1, PRALAY URKUDE 2, SUSHIL GAURKHEDE 3, ATUL KHOPE 4 1Student of Graduation, Dept. of Electrical Engineering, ITM College of engineering,

More information

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM Ms. Dipali A. Umak 1, Ms. Trupti S. Thakare 2, Prof. R. K. Kirpane 3 1 Student (BE), Dept. of EE, DES s COET, Maharashtra,

More information

Modelling and Simulation of DFIG with Fault Rid Through Protection

Modelling and Simulation of DFIG with Fault Rid Through Protection Australian Journal of Basic and Applied Sciences, 5(6): 858-862, 2011 ISSN 1991-8178 Modelling and Simulation of DFIG with Fault Rid Through Protection F. Gharedaghi, H. Jamali, M. Deisi, A. Khalili Dashtestan

More information

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller Bulletin of Electrical Engineering and Informatics ISSN: 2302-9285 Vol. 5, No. 3, September 2016, pp. 271~283, DOI: 10.11591/eei.v5i3.593 271 Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM

More information

Analysis of Grid Connected Solar Farm in ETAP Software

Analysis of Grid Connected Solar Farm in ETAP Software ABSTRACT 2017 IJSRSET Volume 3 Issue 3 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Analysis of Grid Connected Solar Farm in ETAP Software Komal B. Patil, Prof.

More information

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM Volume II, Issue XI, November 13 IJLTEMAS ISSN 78-54 PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING K.B. Porate, Assistant Professor, Department of Electrical Engineering, Priyadarshini

More information

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect PAPER Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect Minoru KONDO Drive Systems Laboratory, Minoru MIYABE Formerly Drive Systems Laboratory, Vehicle Control

More information

Enhancement of Power System Stability Using Thyristor Controlled Series Compensator (TCSC)

Enhancement of Power System Stability Using Thyristor Controlled Series Compensator (TCSC) Enhancement of Power System Stability Using Thyristor Controlled Series Compensator (TCSC) Pooja Rani P.G. Research Scholar in Department of Electrical Engg. MITM, Hisar, Haryana, India Mamta Singh Assistant

More information

A Comparative Analysis of Speed Control Techniques of Dc Motor Based on Thyristors

A Comparative Analysis of Speed Control Techniques of Dc Motor Based on Thyristors International Journal of Engineering and Technology Volume 6 No.7, July, 2016 A Comparative Analysis of Speed Control Techniques of Dc Motor Based on Thyristors Nwosu A.W 1 and Nwanoro, G. C 2 1 National

More information

Grid Stability Analysis for High Penetration Solar Photovoltaics

Grid Stability Analysis for High Penetration Solar Photovoltaics Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department

More information

Battery Charger for Wind and Solar Energy Conversion System Using Buck Converter

Battery Charger for Wind and Solar Energy Conversion System Using Buck Converter Battery Charger for Wind and Solar Energy Conversion System Using Buck Converter P.Venkatesan 1, S.Senthilkumar 2 1 Electrical and Electronics Engineering, Ganesh College of Engineering, Salem, Tamilnadu,

More information

Control Scheme for Grid Connected WECS Using SEIG

Control Scheme for Grid Connected WECS Using SEIG Control Scheme for Grid Connected WECS Using SEIG B. Anjinamma, M. Ramasekhar Reddy, M. Vijaya Kumar, Abstract: Now-a-days wind energy is one of the pivotal options for electricity generation among all

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

Fault Rid Through Protection of DFIG Based Wind Generation System

Fault Rid Through Protection of DFIG Based Wind Generation System Research Journal of Applied Sciences, Engineering and Technology 4(5): 428-432, 212 ISSN: 24-7467 Maxwell Scientific Organization, 212 Submitted: September 14, 211 Accepted: October 15, 211 Published:

More information

Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap

Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap American Journal of Applied Sciences 6 (8): 1526-1530, 2009 ISSN 1546-9239 2009 Science Publications Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap 1 Luiz Augusto Pereira

More information

Robust Control Technique for Grid-connected Power Conditioner

Robust Control Technique for Grid-connected Power Conditioner Hitachi Review Vol. 63 (2014), No. 8 483 Featured Articles Robust Control Technique for Grid-connected Power Conditioner Hikaru Meguro Kazuya Tsutsumi Masaya Ichinose Tomomichi Ito Akira Kikuchi OVERVIEW:

More information

Technical Explanation for Inverters

Technical Explanation for Inverters CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor

More information

Soft Start for 3-Phase-Induction Motor

Soft Start for 3-Phase-Induction Motor Soft Start for 3-Phase-Induction Motor Prof. Vinit V Patel 1, Saurabh S. Kulkarni 2, Rahul V. Shirsath 3, Kiran S. Patil 4 1 Assistant Professor, Department of Electrical Engineering, R.C.Patel Institute

More information

Development of Feedforward Anti-Sway Control for Highly efficient and Safety Crane Operation

Development of Feedforward Anti-Sway Control for Highly efficient and Safety Crane Operation 7 Development of Feedforward Anti-Sway Control for Highly efficient and Safety Crane Operation Noriaki Miyata* Tetsuji Ukita* Masaki Nishioka* Tadaaki Monzen* Takashi Toyohara* Container handling at harbor

More information

Flywheels and Power System Stability

Flywheels and Power System Stability 1 Flywheels and Power System Stability Michael Breuhl, Horacio Silva, and Dr.Hector Pulgar-Painemal Abstract The study looks at impact of flywheels on a power system. This study looks at the effect of

More information

ANN Peak Load Shaver.

ANN Peak Load Shaver. ANN Peak Load Shaver. ANN Peak Load Shaver. ANN Based Electricity Load Forecasting By: Ameya Deoras [1] For short term operations and long term planning for utilities, accurate forecasts are critical.

More information

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach DC Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach F. Akhter 1, D.E. Macpherson 1, G.P. Harrison 1, W.A. Bukhsh 2 1 Institute for Energy System, School of Engineering

More information

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme 1 A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme I. H. Altas 1, * and A.M. Sharaf 2 ihaltas@altas.org and sharaf@unb.ca 1 : Dept. of Electrical and Electronics

More information

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Performance Evaluation of Composite Islanding and Load Management System using Real Time Digital Simulator Sachin Srivastava, Meera K.S, R.S. Shivakumara Aradhya and Sunil Verma Abstract A Composite Islanding

More information

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3 IJSRD International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 23210613 Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3 1 M.E. student 2,3 Assistant Professor 1,3 Merchant

More information

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience

Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Dynamic Study of Bonaire Island Power System: Model Validation and Project Experience Y. Sun 1, 2,*, W. G. Kuijpers 3, E. C. W. de Jong 1,2, and H. Pustjens 3 1 Electrical Energy System, Eindhoven University

More information

Silencers. Transmission and Insertion Loss

Silencers. Transmission and Insertion Loss Silencers Practical silencers are complex devices, which operate reducing pressure oscillations before they reach the atmosphere, producing the minimum possible loss of engine performance. However they

More information

Clutch Damper High Cycle Fatigue

Clutch Damper High Cycle Fatigue Abstract Clutch Damper High Cycle Fatigue KD Wang LUK Incorporated Kalyan Bairavarasu LUK Incorporated The clutch damper of the manual transmission system is prone to vibration related fatigue damage when

More information

IMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW

IMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW International Journal of Electrical Engineering & Technology (IJEET) Volume 8, Issue 2, March- April 2017, pp. 01 07, Article ID: IJEET_08_02_001 Available online at http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=8&itype=2

More information

The Influence of Different Storage Technologies on Large Power System Frequency Response

The Influence of Different Storage Technologies on Large Power System Frequency Response The Influence of Different Storage Technologies on Large Power System Frequency Response Atia Adrees, Member, IEEE, Jia Song and Jovica V Milanović, Fellow, IEEE School of Electrical and Electronic Engineering

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Passive Vibration Reduction with Silicone Springs and Dynamic Absorber

Passive Vibration Reduction with Silicone Springs and Dynamic Absorber Available online at www.sciencedirect.com Physics Procedia 19 (2011 ) 431 435 International Conference on Optics in Precision Engineering and Nanotechnology 2011 Passive Vibration Reduction with Silicone

More information

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS Farhad Shahnia Saeed Tizghadam Seyed Hossein Hosseini farhadshahnia@yahoo.com s_tizghadam@yahoo.com hosseini@tabrizu.ac.ir Electrical and

More information

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode International Journal for Research in Engineering Application & Management (IJREAM) Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode 1 Soumitra S. Kunte,

More information