Installation & Operation Manual - Model AV3000

Size: px
Start display at page:

Download "Installation & Operation Manual - Model AV3000"

Transcription

1 Airflow Control Valve U.S. Patent # 6,991,177 Distributed by: Manufactured by: Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT USA 600 Pepper Street, Monroe, CT USA For Service, Call Tek-Air Systems at Contents of this Manual are Subject to Change Without Notification AV3000 MANUAL-TEKAIR-JULY 2010.DOC

2 LIMITED WARRANTY Tek-Air Systems, Inc. having its principal place of business at 41 Eagle Road, Danbury, CT USA ("Manufacturer") warrants its AccuValve, Model AV3000 product (the "Products") as follows: 1. Limited Warranty. Manufacturer warrants that the Products sold hereunder will be free from defects in material and workmanship for a period of thirty-six (36) months from the date of purchase. If the Products do not conform to this Limited Warranty during the warranty period (as herein above specified), Buyer shall notify Manufacturer in writing of the claimed defects and demonstrate to Manufacturer satisfaction that said defects are covered by this Limited Warranty. If the defects are properly reported to Manufacturer within the warranty period, and the defects are of such type and nature as to be covered by this warranty, Manufacturer shall, at its own expense, furnish, replacement Products or, at Manufacturer's option, replacement parts or services for the defective Products. Shipping and installation of the replacement Products or replacement parts shall be at Buyer's expense. 2. Other Limits. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Manufacturer does not warrant against damages or defects arising out of improper or abnormal use of handling of the Products; against defects or damages arising from improper installation (where installation is by persons other than Manufacturer), against defects in products or components not manufactured by Manufacturer, or against damages resulting from such non-manufacturer made products or components. Manufacturer passes on to Buyer the warranty it received (if any) from the maker thereof of such non-manufacturer made products or components. This warranty also does not apply to Products upon which repairs have been affected or attempted by persons other than pursuant to written authorization by Manufacturer. This warranty also does not apply to any product provided by the buyer and mounted by the Manufacturer to Products. 3. Exclusive Obligation. THIS WARRANTY IS EXCLUSIVE. The sole and exclusive obligation of Manufacturer shall be to repair or replace the defective Products in the manner and for the period provided above. Manufacturer shall not have any other obligation with respect to the Products or any part thereof, whether based on contract, tort, strict liability or otherwise. Under no circumstances, whether based on this Limited Warranty or otherwise, shall Manufacturer be liable for incidental, special, or consequential damages. 4. Other Statements. Manufacturer's employees or representatives' ORAL OR OTHER WRITTEN STATEMENTS DO NOT CONSTITUTE WARRANTIES, shall not be relied upon by Buyer, and are not a part of the contract for sale or this limited warranty. 5. Entire Obligation. This Limited Warranty states the entire obligation of Manufacturer with respect to the Products. If any part of this Limited Warranty is determined to be void or illegal, the remainder shall remain in full force and effect. Contents of this Manual are Subject to Change Without Notification Page ii

3 TABLE OF CONTENTS LIMITED WARRANTY...ii TABLE OF CONTENTS...iii SECTION 1 - INTRODUCTION... 1 SECTION 2 - SPECIFICATIONS... 3 SECTION 3 MODEL CODE DESCRIPTION... 4 SECTION 4 PHYSICAL DIMENSIONS & WEIGHTS... 5 SECTION 5 - INSTALLATION... 6 SECTION 6 WIRING... 9 SECTION 7 OUTPUT CONFIGURATION SECTION 8 TEK-AIR CONTROLLER DIRECT INPUT SECTION 9 MAINTENANCE APPENDIX ACTUATOR TECHNICAL DATA SHEETS Contents of this Manual are Subject to Change Without Notification Page iii

4 SECTION 1 - INTRODUCTION 1.1 Description The AV3000 airflow control valve - AccuValve - incorporates high accuracy airflow sensing with a revolutionary but simple design. The AccuValve divides the airflow into two equal chambers using an airfoil shaped compression section. Each chamber is comprised of a vortex shedding airflow sensor, a modulating control blade and a static regain section. As air enters the chambers it accelerates and compresses, creating a laminar zone optimum for measuring airflow velocity. The vortex shedding airflow sensors provide a digital pulse train to the airflow transmitter which is directly proportional to the air flow velocity in each chamber of the AccuValve. The AccuValve transmitter provides an extremely accurate and repeatable analog output signal representing volumetric airflow which is compatible with all major BMS DDC controllers. 1.2 AV3100 Major Components Identified Airflow Transmitter Drive Shaft Electric Actuator Access Cover Valve Housing Round AccuValve Follower Shaft Modulating Control Blades Linkage Airflow Sensor Static Regain Section Compression Section Airflow Outlet View Airflow Inlet View Contents of this Manual are Subject to Change Without Notification Page 1

5 1.3 AV3200 Major Components Identified AV and -24 Linkage Airflow Transmitter Drive Shaft Electric Actuator Access Cover Airflow Sensor Center Compression Section Side Compression Section Airflow Inlet View Follower Shaft Center Regain Section Housing Modulating Control Blades Airflow Outlet View Side Regain Section AV and -48 Airflow Transmitter Actuator #1 Actuator #2 Airflow Inlet View Airflow Outlet View Contents of this Manual are Subject to Change Without Notification Page 2

6 SECTION 2 - SPECIFICATIONS AIRFLOW ACCURACY: +/- 5% of Reading SPEED OF RESPONSE: ~ 2 sec, full open to full closed using Actuator Options 1-5. SHUT OFF LEAKAGE: AV3100: < 2% FS, Optional Tight Shut-off -S < 0.5% FS AV3200: < 5% FS OPERATING PRESSURE: 0.3 wc to 3.0 wc ENVIRONMENTAL: Temperature Air stream -20 to 140 deg. F Ambient 25 to 125 deg. F Humidity 0 to 95% RH non-condensing TRANSMITTER ELECTRICAL: Input Power 24 VAC +/- 20% 50/60 Hz, 2.5 VA Max. or 24 VDC +/- 20%, 75mA Max. Power source must include a circuit breaker and be current limited to 8 amps maximum and grounded on the (-) side. Output Signal Configurable Using Jumpers JP1 and JP4: DC Voltage Output: 0-10 v or 2-10 v DC milliamp Output: 0-20 ma or 4-20 ma Electromagnetic Compatibility EMC Directive 2004/108/EC Low Voltage Directive 2004/108/EEC EN :2006 FCC Part 15 (Note 1) Product Safety IEC/EN/UL/CSA :2001 CAN/CSA-C22.2 No (Note 2) ACTUATOR ELECTRICAL: Reference Appendix VALVE MATERIALS OF CONSTRUCTION: Sheet Metal Parts Shafts Airflow Sensors OPERATING RANGE: Valve Model Available in Galvanized Steel, 304SS or 316SS All models use 316SS shafts Polycarbonate Plastic, UL94-V0 Min. Flow Max. 0.3 wc DP Max wc DP Transmitter Full Scale Range CFM CMH CFM CMH CFM CMH CFM CMH AV3100-L AV AV AV AV AV AV AV AV NOTES: 1. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user s own expense. This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. 2. This product has been tested to the requirements of CAN/CSA-C22.2 No , second edition, including Amendment 1, or later version of the same standard incorporating the same level of testing requirements. Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. Contents of this Manual are Subject to Change Without Notification Page 3

7 SECTION 3 MODEL CODE DESCRIPTION Model Code Examples: 1. AV Dia. Galvanized Valve with 0-10v Fail Last Position actuator. 2. AV S 8 Dia. 304SS Valve with 2-10v Fail Open/Closed actuator and Tight Shut-off option. 3. AV SI 10 Dia. Galvanized Valve with 0-10v Fail Last Postion actuator with Tight Shut-off and Insulation options. Contents of this Manual are Subject to Change Without Notification Page 4

8 SECTION 4 PHYSICAL DIMENSIONS & WEIGHTS 4.1 Round Sizes 12 (305mm) H L D Valve Model D L H Weight in. mm in. mm in. mm lbs. kg AV3100-L AV AV AV AV Rectangular Sizes mm H L W Valve Model W L H Weight in. mm in. mm in. mm lbs. kg AV AV AV AV Note: All dimensions are to the outside and have a tolerance of +/-.062 (1.6mm). Contents of this Manual are Subject to Change Without Notification Page 5

9 SECTION 5 - INSTALLATION 1. Read all instructions completely before installing the valve. NOTE: Wear eye protection, protective gloves and clothing suitable for working with sheet metal which may have sharp edges. 2. Verify the tag number located on the valve label matches the HVAC schedule. 3. Select optimum mounting location for the valve. NOTE: The AccuValve does not require straight inlet duct runs to operate properly, however it s always best to locate any duct device away from transitions and bends to minimize impact on system static pressure. 4. Allow a minimum clearance of 14 inches (356 mm) unobstructed access to the transmitter, actuator and valve access cover. 5. To support the weight of the valve, install duct hangers within 12 inches (305 mm) of valve connections. NOTE: Reference Section 4 for valve weights. 6. After the duct section is properly supported to carry the weight of the valve, install valve into the duct in accordance with the Airflow Direction Label located on the side of the valve. Position valve so the transmitter, actuator and access cover are easily accessible. NOTE: The AccuValve is not position sensitive. It can be installed in any plane or rotational axis without having impact on the factory calibration. 7. Reference the appropriate diagram provided in this section for installation details. NOTE: Screws, nuts, fasteners, duct sealant, hangers, companion flanges and gaskets are NOT provided by Tek-Air.. Secure Using Sheet Metal Screws Duct Support 14 (356mm) Minimum Clearance For Access Apply Duct Sealant Round Valve Installation Standard Slip-Fit Valve - Using Sheet Metal Screws Contents of this Manual are Subject to Change Without Notification Page 6

10 14 (356mm) Minimum Clearance For Access Draw Band Round Valve Installation Standard Slip-Fit Valve - Using Draw Band 3/8 bolts, lock-washers and nuts Duct Support Gasket 14 (356mm) Minimum Clearance For Access Round Valve Installation Option F (Flanges) Contents of this Manual are Subject to Change Without Notification Page 7

11 Rectangular Valve Installation Standard Slip Fit Using Sheet Metal Screws Rectangular Valve Installation Option F (Flanges) In addition to supporting the duct within 12" of each end of valve, a Mounting Strut is provided with the 12x36 and 12x48" valves. Position the valve so the Mounting Strut is below the valve and supported from above on both ends of the strut. NOTE: Do NOT position the valve below the Mounting Strut or valve may fall causing serious injury or death. Support Hanger Mounting Strut 14" (356mm) Minimum Clearance Additional Requirements for Installing 12X36 and 12x48 Valves Contents of this Manual are Subject to Change Without Notification Page 8

12 SECTION 6 WIRING 6.1 Transmitter Wiring Loosen the transmitter cover thumb-screw, lift and remove cover. NOTE: Reference the label on the inside of cover for identifying connection points. Thumb Screw Remove the Power and Signal connectors from board and route cables through the strain relief fitting located on the side of the enclosure. NOTE: For installations requiring conduit, the plastic strain relief fitting can be removed and replaced with a.875 (22.2mm) conduit fitting Land the wires to the appropriate connector terminals, secure connector screws and reinstall the connectors to their respective locations. NOTE: Reference job-specific wiring diagrams for details of connections to field devices. If transformer is used to power multiple devices, polarity must be maintained. Cable Entry Pull a few inches of cable into the enclosure, insert the ratcheting strain relief over cable and push down until snug. Strain Relief Strain Relief Fitting Input Power (X4) Output Signal (X2) NOTE: Ratcheting Strain Relief can be removed by inserting snap ring pliers with.040 tips into two holes on the part and spread open Reinstall the cover and secure by tightening thumb screw. 6.2 Actuator Wiring The AccuValve can be provided with various actuators depending on the application. The wiring for each type of actuator is similar, however reference the Appendix at the end of this manual for instructions specific to the actuator model provided for your project. Contents of this Manual are Subject to Change Without Notification Page 9

13 6.3 Field Wiring Schematics The following diagrams are intended to be used as examples for connecting the AccuValve AV3000 to Field Devices. Reference the inside of transmitter cover for identification of connectors. NOTE: Use AWG Shielded Cable Typical wiring between the AccuValve and DDC Control Panel Controller with Common I/O & Power Ground Typical wiring between AccuValve and Tek-Air Fume Hood Controller. Contents of this Manual are Subject to Change Without Notification Page 10

14 6.3.3 Typical wiring between AccuValve and Tek-Air SmartLab Controller equipped with the AccuValve Direct Input board Typical wiring between AccuValve and Tek-Air SmartLab Controller using the SmartLab s Powered Analog Input (AI-3 or AI-4). Contents of this Manual are Subject to Change Without Notification Page 11

15 SECTION 7 OUTPUT CONFIGURATION Each AccuValve is tested and calibrated in the factory and performance is verified to ensure accuracy. The transmitter Full Scale Range is set per the table in Section 2 and the Analog Output Signal has been configured to provide either Voltage (0-10v or 2-10v) or Current (0-20mA or 4-20mA) by using Jumpers JP1 and JP4. The factory default transmitter output is 2-10v unless specified otherwise at the time of placing order. If desired, the Output Signal can be reconfigured in the field by setting Jumpers JP1 and JP4 as shown below. AV3000 Transmitter Desired Output Jumper Positions Signal JP4 JP1 4 to 20mA 2-3 OFF 2 to 10 v 1-2 OFF 0 to 20mA 2-3 ON 0 to 10 v 1-2 ON Transmitter pictured is configured for 2-10v output: JP4 is set 1-2 and JP1 is OFF. Contents of this Manual are Subject to Change Without Notification Page 12

16 SECTION 8 TEK-AIR CONTROLLER DIRECT INPUT 8.1 Overview The Tek-Air SmartLab (SLC2000) and Fume Hood (FVC2000) Controllers can be ordered from the factory with an AccuValve Direct input board installed. This board enables a direct connection between the AV3000 transmitter and Tek-Air Controller using the VorTek Direct input, which is normally reserved for the VT4000 probe. The picture to the right shows a SmartLab Controller with an AccuValve Direct Input board installed Fume Hood Controller Applications: All FVC2000 applications utilizing the AV3000 must use the AccuValve Direct input board to connect the AV3000 to the FVC controller. If the Fume Hood Controller does not include the AccuValve Direct input board, the controller will not have the ability to read the airflow volume signal provided by the AV SmartLab Applications: Because the SmartLab Controller includes other analog inputs in addition to the VorTek Direct input, the AccuValve Direct input board is not always required for SmartLab applications. The AccuValve Direct input board is only required for utilizing the SLC2000 VorTek Direct input. 8.2 Field Wiring Refer to Section 6 for field wiring instructions. AccuValve Direct 8.3 AV3000 Transmitter Configuration In order for the AV3000 Transmitter to operate properly with the AccuValve Direct Input Board the transmitter output jumpers must be configured for 2-10 v operation and the Transmitter Full-Scale Range must remain set to the factory default values as shown below. Transmitter Valve Model Full 10 v CFM CMH AV3100-L AV AV AV AV AV AV AV AV Contents of this Manual are Subject to Change Without Notification Page 13

17 8.4 Fume Hood Controller Configuration Standard calibration constants for the FVC VorTek Direct input have been derived for each AV3000 transmitter range. Using the FVC2000 Configuration Tool, set the three VorTek parameters as show below for the given size valve. FVC2000 Config. Tool Parameter AV3100-L8 AV AV AV AV AV AV AV AV CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH Vortek Span FPM Coef Bias FPM Vortek Area Vortek Input Sq. F Channel After these parameters are saved to the FVC Controller, the VorTek Direct input will provide the properly scaled CFM value for the AV3000 transmitter to which it is connected. If it is necessary to adjust the airflow calibration in the field, the Vortek Coef Span FPM parameter can be modified. 8.5 SmartLab Controller Configuration Standard calibration constants for the SLC VorTek Direct input have been derived for each AV3000 transmitter range. Using the SmartLab Configuration Software, set the VorTek Direct input parameters as show below for the given size valve. Function Name: AV3100-L8 AV AV AV AV AV AV AV AV Input, Vortek Direct CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH CFM CMH Sensor Sel: 1x1 1x1 1x1 1x1 1x1 1x1 1x1 1x1 1x1 Threshold: (Hz) Cal Bias: (Hz) Cal Span: (Hz) Duct (sq ft) After these parameters are saved to the SmartLab Controller, the VorTek Direct input will provide the properly scaled CFM value for the AV3000 transmitter to which it is connected. If it is necessary to adjust the airflow calibration in the field, the Cal Span parameter can be modified. Contents of this Manual are Subject to Change Without Notification Page 14

18 SECTION 9 MAINTENANCE 9.1 Maintenance Due to the simplistic design of the AccuValve and high reliability of the vortex shedding airflow sensor and transmitter, scheduled maintenance is not required. However, each AccuValve does include an access cover which can be removed to inspect the airflow sensors if desired Round Valve Access Cover Equipment Required: 5/16 deep socket with ratchet drive or power driver, safety glasses and safety gloves suitable for sheet metal working. Access Cover 1. Loosen the 5/16 lock-nut, but do not remove it from the bolt. The nut only needs to be loose enough to allow the access door to slide forward. Loosen Nut CAUTION: If the lock-nut is removed from the bolt, the access cover can spring open possibly causing injury due to the sharp edges. Be sure to take precautions against this. 2. Using two hands; squeeze the access cover and slide it forward on the valve enough to uncover the access hole. Slide Cover Forward 3. Once the cover is slid forward, the airflow sensors can be visually inspected. 4. When inspection is complete, slide the access cover over the access hole, being careful not to damage gasket around the hole. Inspect Sensors 5. Verify the access cover is in position to completely cover the hole. Secure in place by tightening the 5/16 lock-nut using care not to over tighten. Contents of this Manual are Subject to Change Without Notification Page 15

19 9.1.1 Rectangular Valve Access Cover Equipment Required: 5/16 socket with ratchet drive or power driver, safety glasses and safety gloves suitable for sheet metal working. Access Cover 1. The access cover is secured to the valve using (12) Tek-Screws. Remove the (12) Tek-Screws using a 5/16 socket and put the screws aside for reinstalling the cover later. Remove (12) Screws 2. Remove the access cover from the valve. Inspect Sensors 3. Once the cover is removed the sensors are accessible for inspection. 4. When inspection is complete, place the access cover in position and secure using the (12) screws previously removed. Contents of this Manual are Subject to Change Without Notification Page 16

20 APPENDIX ACTUATOR TECHNICAL DATA SHEETS NOTE: Reference Model Code Description in Section 3. Actuator Code 1 : Fail Open/Closed (2-10v) Neptronic BM060F(TE3) Actuator Code 2 : Fail Last Position (0-10v) Belimo NMQB24-MFT-A FLP Actuator Code 3 : Fail Last Position (2-10v) Belimo NMQB24-MFT-B FLP Actuator Code 4 : Fail Open/Closed (0-10v) Belimo NKQ24-MFT-A FSP Actuator Code 5 : Fail Open/Closed (2-10v) Belimo NKQ24-MFT-B FSP Contents of this Manual are Subject to Change Without Notification Page 17

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVC6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVT6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

ACCUSTATION SUBMITTAL MATERIALS

ACCUSTATION SUBMITTAL MATERIALS ACCUSTATION SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE SIZE 06 = 06" DIAMETER 08 = 08" DIAMETER

More information

Accutrol, LLC Product Sheet AVT6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVT6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVT6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVT6000! AHR Expo AWARDS WINNER Intuitive Graphical User Interface

More information

Acid Resistant AVT6000

Acid Resistant AVT6000 Accutrol, LLC Product Sheet Acid Resistant AVT6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVT6000! AHR Expo AWARDS WINNER Manufactured in the

More information

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare AHR Expo AWARDS WINNER epi Innovative features for the AVC6000! Intuitive Graphical User Interface

More information

Operating and Installation Instructions

Operating and Installation Instructions Model Number 20902 Fabricator's Power Module Kit - Aluminum Operating and Installation Instructions CAUTION! This product is to be installed only by persons knowledgeable in the repair and modification

More information

Accutrol, LLC Product Sheet. VTS Series. US Patents 6,991,177 & 7,543,759. Digital Airflow Measurement Station

Accutrol, LLC Product Sheet. VTS Series. US Patents 6,991,177 & 7,543,759. Digital Airflow Measurement Station Accutrol, LLC Product Sheet VTS Series US Patents 6,991,177 & 7,543,759 Digital Airflow Measurement Station Innovative features of the AccuStation VTS Series! Digital Airflow Sensing Modular Design Intuitive

More information

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC5000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare epi Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5 Pa) Electronic

More information

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4) MOEL COE UCT SHAPE = Round = Rectangular = Flat Oval PROBE MATERIAL = Aluminum/ABS = CPVC & ABS = 0SS = High Temp SS (50 F / C Max) PROBE QUANTITY = = s = s = s SENSORS PER PROBE = Sensor per = Sensors

More information

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System Product Bulletin Code No. LIT-12011620 Issued July 2, 2014 RA-1250 Thermal Dispersion Fan Inlet Sensor Airflow Measuring System averages

More information

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks Accutrol, LLC Product Sheet Cage Rack Valve H-AVC5000 US Patents 6,991,177 & 7,543,759 Specially Made for Vivarium Cage Racks Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5

More information

Acid Resistant AVC6000

Acid Resistant AVC6000 Accutrol, LLC Product Sheet Acid Resistant AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVC6000! AHR Expo AWARDS WINNER Intuitive Graphical

More information

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology NMQB-MFT, NMQX-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, V, Multi-Function Technology Application For proportional modulation of dampers in HVAC systems. Actuator sizing should

More information

Operating and Installation Instructions This Product is Protected by U.S. Patent

Operating and Installation Instructions This Product is Protected by U.S. Patent Model Number 30303 Velocity Series 200 Fuel System Operating and Installation Instructions This Product is Protected by U.S. Patent 8388322 CAUTION! This product is to be installed only by persons knowledgeable

More information

Superchips Model 2704 MAX MicroTuner GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions

Superchips Model 2704 MAX MicroTuner GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions Page 1 of 12 Form 0137D 11/30/2004 Superchips Inc. Superchips Model 2704 MAX MicroTuner 2004-2005 GM Trucks with 6.6L Duramax Diesel Engines Vehicle Programming Instructions PLEASE READ THIS ENTIRE INSTRUCTION

More information

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY GC-1 Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY GENERAL INFORMATION The GC-1 heating cable controller has been designed and manufactured for

More information

- Wiring Brochure Zone Manager 336

- Wiring Brochure Zone Manager 336 - Wiring Brochure W 336 12/08 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in 4 Wiring Brochure Wiring

More information

MA40-704X Series MA41-707X Series MA41-715X Series

MA40-704X Series MA41-707X Series MA41-715X Series MA4-74X Series MA4-77X Series MA4-75X Series SmartX Actuators Spring Return Two-Position General Instructions Application SmartX Direct Coupled Actuators are designed to be used in both damper and valve

More information

6. Electrical. 7. Settings. 8. Quick

6. Electrical. 7. Settings. 8. Quick Grundfos Variable Speed Circulator Pump Pumps Incorporating the VS, Variable Speed Control 1. Shipment Inspection Page 2 2. General Page 2 3. Operational Limits Page 3 4. Pump Installation Page 4 5. Installation

More information

- Wiring Brochure Zone Manager 335

- Wiring Brochure Zone Manager 335 - Wiring Brochure W 335 12/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications Rough-in Wiring Rough-in wiring instructions 3 4 Wiring

More information

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology NMB (X) -MFT Proportional Control, Non-Spring Return, Direct Coupled, V, Multi-Function Technology Torque min. 90 in-lb for control of damper surfaces up to sq ft. Technical Data NMB(X)-MFT Power Supply

More information

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma LMX0-SR Proportional Control, Non-Spring Return, Direct Coupled,00 to 0 VAC, for to 0 VDC and to 0 ma Torque min. 5 in-lb for control of damper surfaces up to sq ft. Application For proportional modulation

More information

Installation & Operation Manual

Installation & Operation Manual tn4 Wiring Center 316 Installation & Operation Manual D 316 05/11 Zoning Replaces: 04/09 Introduction The tekmarnet 4 Wiring Center 316 is designed to operate up to four zone pumps in a hydronic heating

More information

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-126 REV A 12/09

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-126 REV A 12/09 HAND CRANK & MOTORIZED POWER CORD REELS: SERIES 1125PC SERIES: 1125PC HAND CRANK SERIES: 1125PC MOTORIZED COXREELS The technical data and images which appear in this manual are for informational purposes

More information

Powerware Vdc Extended Battery Cabinet User s Guide.

Powerware Vdc Extended Battery Cabinet User s Guide. Powerware 9125 48 Vdc Extended Battery Cabinet User s Guide www.powerware.com FCC Part 15 Class A EMC Statements NOTE This equipment has been tested and found to comply with the limits for a Class A digital

More information

Superchips Model 1725 MAX MicroTuner 4.6L Ford Automobiles Vehicle Programming Instructions

Superchips Model 1725 MAX MicroTuner 4.6L Ford Automobiles Vehicle Programming Instructions Page 1 of 16 Form 0130K 06/06/2004 Superchips Model 1725 MAX MicroTuner 4.6L Ford Automobiles Vehicle Programming Instructions PLEASE READ THIS ENTIRE INSTRUCTION SHEET BEFORE YOU PROCEED This product

More information

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation GRUNDFOS INSTRUCTIONS Grundfos Variable Speed Installation and Operation Pumps Incorporating the (VS) Variable Speed Control with Date Code 0838 or higher 1. 2. 3. 4. Shipment Inspection General Features

More information

Installation & Operation Manual

Installation & Operation Manual tn2 Wiring Center 314 Installation & Operation Manual D 314 05/11 Zoning Replaces: 11/10 Introduction The tekmarnet 2 Wiring Center 314 is designed to operate up to four zone pumps in a hydronic heating

More information

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1. LMCB4-SR (-T) Proportional Control, Non-Spring Return, Direct Coupled, 4V, for to 0 VDC and 4 to 0 ma Torque min. 45 in-lb for control of damper surfaces up to sq ft. LMCB4-SR LMCB4-SR-T HALOMO Brushless

More information

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 00 to 40 VAC Torque min. 60 in-lb for control of damper surfaces up to 90 sq ft. Application For on/off and floating point control of dampers

More information

Operating and Installation Instructions

Operating and Installation Instructions Operating and Installation Instructions This Product is Protected by U.S. Patent 8388322 This product is to be installed only by persons knowledgeable in the repair and modification of vehicle fuel systems

More information

- Wiring Brochure Mixing Expansion Module 440

- Wiring Brochure Mixing Expansion Module 440 - Wiring Brochure Mixing Expansion Module 440 W 440 12/08 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

453X Series. Application. Features. Two-Position Damper Actuator General Instructions 453X Series Two-Position Damper Actuator General Instructions Application The 453L, light duty damper actuators are designed for a variety of two-position, spring return, damper applications. The 453L

More information

MaxLite StaxMax LED Flood Lights

MaxLite StaxMax LED Flood Lights Operating Instructions MaxLite StaxMax LED Flood Lights Input Rating 120V-277V 50/60Hz (347/480v optional) Wet Location Rated IP65 Operating temperature -22⁰F to 105⁰F General Safety Information 1. READ

More information

Exhaust Fan Flow Meter. Operation Manual. The ENERGY CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE

Exhaust Fan Flow Meter. Operation Manual. The ENERGY CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE Exhaust Fan Flow Meter Operation Manual The ENERGY Exhaust Fan Flow Meter Operation Manual The Energy Conservatory 2801 21st Ave. S., Suite 160 Minneapolis, MN 55407 612-827-1117 Fax 612-827-1051 www.energyconservatory.com

More information

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma Proportional Control, Non-Spring Return, Direct Coupled, 4V, for to 0 VDC and 4 to 0 ma Torque min. 360 in-lb for control of damper surfaces up to 90 sq ft. Application For proportional modulation of dampers

More information

BroadBand PowerShield. 20 AHr Battery. User Manual

BroadBand PowerShield. 20 AHr Battery. User Manual BroadBand PowerShield 20 AHr Battery User Manual 990-1316A 10/2004 Chapter 1 General Information The PowerShield provides a power source for broadband telephony applications. Important Safety Instructions

More information

Versatile and Powerful

Versatile and Powerful AM Series Direct Coupled Actuator Versatile and Powerful Minimum 180 in-lb torque in a compact package. For damper areas up to 45 sq-ft* All Actuators have BDCM AM Series - At A Glance AMB(X)24-3 (p. 148)

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

MS41-634X Series. Features. SmartX Actuators Non-Spring Return Proportional General Instructions

MS41-634X Series. Features. SmartX Actuators Non-Spring Return Proportional General Instructions MS4-634X Series SmartX Actuators Non-Spring Return Proportional General Instructions Application Direct Coupled SmartX Actuators are designed to be used in both damper and valve control applications. The

More information

REDI-LINE. Rugged, Reliable, DC to AC Power Conversion ELECTRIC GENERATORS USER'S GUIDE. KARAM A.L.

REDI-LINE. Rugged, Reliable, DC to AC Power Conversion ELECTRIC GENERATORS USER'S GUIDE. KARAM A.L. REDI-LINE ELECTRIC GENERATORS USER'S GUIDE Rugged, Reliable, DC to AC Power Conversion KARAM A.L. www.alternatorstarter.com 1-888-515-2726 REDI-LINE ELECTRIC GENERATOR MODEL INPUT ACTUAL OUTPUT ACTUAL

More information

II DISTRIBUTION & SUBSTATION TYPE C

II DISTRIBUTION & SUBSTATION TYPE C CapCheckIII DISTRIBUTION & SUBSTATION TYPE Ca p a c i t o r C h e c ke r Operating & Instruction Manual 1475 Lakeside Drive Waukegan, Illinois 60085 U.S.A. 847.473.4980 f a x 8 4 7. 4 7 3. 4 9 8 1 w e

More information

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V LMB- (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, V Torque min. 5 in-lb for control of damper surfaces up to sq ft. Technical Data LMB- on/off-floating Power Supply VAC ±

More information

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203) TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2600 SASH SENSING VAV FUME HOOD SYSTEM MODEL 2600: Variable volume control based on sash position utilizes microprocessor based electronics and linear air control

More information

Minimum 27 in-lb torque

Minimum 27 in-lb torque LU Series Actuator Minimum 27 in-lb torque For damper areas up to 6.8 sq-ft* All Actuators have BDCM LU Series - At A Glance LUB(X)24-3 (p. 258) LUB(X)24-SR (p. 260) LUX24-MFT (p. 262) Basic Product Flexible

More information

QSB (Q-Star) Electronics for QSE Electromagnetic Meter. Owner s Manual TABLE OF CONTENTS

QSB (Q-Star) Electronics for QSE Electromagnetic Meter. Owner s Manual TABLE OF CONTENTS Owner s Manual QSB (Q-Star) Electronics for QSE Electromagnetic Meter Plain Cover Plate and Pulse-Out Transmitter (QSB) Display Mount Cover Plate (to mount a Q09 Display) and Pulse-Out Transmitter (QSB)

More information

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21) EFB and EFX Series Spring Return Direct Coupled Actuator Minimum 70 in-lb Torque For damper areas up to 66 sq-ft* (For lower torque, see AFB, AF, NFB, LF, or TF series) Applications New standard clamp

More information

TC26-B Vehicle Sensor

TC26-B Vehicle Sensor Section 1 General Description The Model TC26-B is a microprocessor controlled vehicle sensor with a variable range. It is designed to trigger the operation of a traffic controller. The TC26-B will only

More information

SPC Series. Digital Scale. Operation Manual

SPC Series. Digital Scale. Operation Manual SPC Series Digital Scale Operation Manual Revision 1.0 August 17, 2000 ! WARNING Use only the AC adapter which comes with the scale. Other adapters may cause damage. Internal service to this product should

More information

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V AMB4-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 4 V Torque min. 80 in-lb for control of damper surfaces up to 45 sq ft. Application For on/off and floating point control of

More information

IAQ-CALC TM Indoor Air Quality Meter

IAQ-CALC TM Indoor Air Quality Meter ENERGY AND COMFORT Indoor Air Quality IAQ-CALC TM Indoor Air Quality Meter Model 7515 Operation and Service Manual Copyright TSI Incorporated / May 2007 / All rights reserved. LIMITATION OF WARRANTY AND

More information

SUNTURA SOLAR TRACKER

SUNTURA SOLAR TRACKER WindyNation SUNTURA SOLAR TRACKER SOT-TRKS-NF User s Manual Page 1 of 10 WindyNation 08/09/2012 Table of Contents 1 Introduction... 3 1.1 Limited Warranty... 3 1.2 Restrictions... 3 1.3 Warranty Claims

More information

Operating and Installation Instructions

Operating and Installation Instructions Model Number 41402-c Electronic Fuel Pump Operating and Installation Instructions CAUTION! This product is to be installed only by persons knowledgeable in the repair and modification of vehicle fuel systems

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

ipd Catback Oval Tube Exhaust System S60R ( ), V70R ( ) ipd #120056

ipd Catback Oval Tube Exhaust System S60R ( ), V70R ( ) ipd #120056 PI-408 02/12 Dedicated to improving vehicle fun, safety & performance Installation Instructions *PI408* ipd Catback Oval Tube Exhaust System S60R (2004-2007), V70R (2004-2007) ipd #120056 SUGGESTED TOOLS

More information

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V AMB-(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, V Torque min. 80 in-lb for control of damper surfaces up to 5 sq ft. Application For on/off and floating point control of dampers

More information

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V NFB4, NFB4-S, NFX4, NFX4-S On/Off, Spring Return, 4 V Torque min. 90 in-lb, for control of air dampers Technical Data Power supply Power consumption Transformer sizing Electrical connection NFB4... NFX4...

More information

DRAGO. Corn Header Manual f HEADSIGHT.COM

DRAGO. Corn Header Manual f HEADSIGHT.COM DRAGO Corn Header Manual 09020801f HEADSIGHT.COM 574.546.5022 About Headsight Headsight Contact Info Headsight, Inc. 4845 3B Road Bremen, IN 46506 Phone: 574-546-5022 Fax: 574-546-5760 Email: info@headsight.com

More information

Versatile and Powerful

Versatile and Powerful LM Series Direct Coupled Actuator Versatile and Powerful Minimum 45 in-lb torque in a compact package. For damper areas up to 11 sq-ft* Actuators in bold have BDCM LM Series - At A Glance LMB(X)24-3(-S)(-T)

More information

AD-1251 Probe with Differential Pressure Transducer

AD-1251 Probe with Differential Pressure Transducer AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)

More information

Rotating Vane Anemometer

Rotating Vane Anemometer Ventilation Testing Rotating Vane Anemometer Alnor Model RVA801 AIRFLOW Model LCA301 Operation and Service Manual Copyright TSI Incorporated / 2007-2008 / All rights reserved. Address TSI Incorporated

More information

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-122 REV A 12/09

INSTALLATION AND MAINTENANCE MANUAL FORM #PM-122 REV A 12/09 HAND CRANK WELDING CABLE REEL: SERIES 100WC COXREELS The technical data and images which appear in this manual are for informational purposes only. NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES

More information

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1 STEEL NIPPLES S40 & S80 Steel Nipple Product Specifications Manufacturing Facility is ISO9001:2000 Welded Steel Pipe Conform to ASTM A53 Threads Conform to ASME B1.20.1 800-678-2544 800-678-0857 www.msi-products.com

More information

Minimum 27 in-lb Torque

Minimum 27 in-lb Torque LU Series Actuator Minimum 27 in-lb Torque For damper areas up to 6.8 sq-ft* Actuators in bold have BDCM LU Series - At A Glance LUB(X)24-3 (p. 351) LUX120-3 (p. 353) LUB(X)24-SR (p. 355) LUX120-SR (p.

More information

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY Issue 5 24/48 VOLT DC SWITCHING POWER SUPPLY INTRODUCTION These instructions provide the specifications, installation and maintenance information for the VP-4124 and VP-4124-E, 24/48 Volt Power Supplies.

More information

Level Alert Model Multi-Switch Liquid Level Sensor. Assembly and Installation Instructions

Level Alert Model Multi-Switch Liquid Level Sensor. Assembly and Installation Instructions Level Alert Model 2000 Multi-Switch Liquid Level Sensor Assembly and Installation Instructions Kit Form Each unit is provided in kit form with step-by-step instructions, making it extremely easy to custom

More information

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions MS40-77X Series DuraDrive Series Spring Return Proportional Actuators General Instructions Application DuraDrive Direct Coupled Actuators are designed to be used in both damper and valve control applications.

More information

FADE SERIES. Typical Specifications for Model FADE Sidewall Propeller Fans Sidewall propeller fans shall be of the direct driven type.

FADE SERIES. Typical Specifications for Model FADE Sidewall Propeller Fans Sidewall propeller fans shall be of the direct driven type. January 2008 FADE0108 Fantech, Inc. certifies that the FADE Series shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA

More information

UHC-202 Hardware Guide

UHC-202 Hardware Guide R Description The UHC202 is a fullyintegrated VAV terminal unit controller, complete with differential pressure sensor and integral Belimo LM24M zone damper motor. The UHC202 is designed for singlebox

More information

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control

More information

Rotating Vane Anemometer

Rotating Vane Anemometer Ventilation Testing Rotating Vane Anemometer Alnor Model RVA801 AIRFLOW Model LCA301 Operation and Service Manual Copyright TSI Incorporated / 2007-2012 / All rights reserved. Address TSI Incorporated

More information

INSTRUCTIONS SMOKE BLOWER WITH HONDA ENGINE PART NUMBER

INSTRUCTIONS SMOKE BLOWER WITH HONDA ENGINE PART NUMBER 1 INSTRUCTIONS SMOKE BLOWER WITH HONDA ENGINE PART NUMBER 303-568 CHERNE INDUSTRIES INCORPORATED 1-800-THE PLUG 5700 LINCOLN DRIVE (1-800-843-7584) MINNEAPOLIS, MN 55436-1695 FAX: 1-800-843-7585 www.cherneind.com

More information

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0330 Rev 0 0416 TABLE OF CONTENTS SAFETY SUMMARY... 3 SPECIFICATIONS... 4 1.0 INTRODUCTION/DESCRIPTION.... 5 2.0 LOCATION AND MOUNTING... 5 3.0 CONNECTIONS

More information

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator NFB and NFX Series Spring Return Direct Coupled Actuator Minimum 90 in-lb Torque For damper areas up to sq-ft* Applications 1 3/4 1/ New standard clamp fits standard 1/ shafts to 1.05 jackshafts. Mount

More information

BlinkerBeam Solar Controller

BlinkerBeam Solar Controller Blinker Division Solar LED Solutions The Route To Safety, One Solution At A Time BlinkerBeam Solar Controller BlinkerSign, BlinkerBeacon or RRFB 2.0 with 55 W Solar Panel User Guide TAPCO Traffic & Parking

More information

F261 Series Fluid Flow Switches

F261 Series Fluid Flow Switches F261 Series Fluid Switches Product Bulletin Code No. LIT-12011987 Issued March 9, 2015 The F261 Series Switches respond to fluid flow in lines carrying water, ethylene glycol, or other nonhazardous fluids.

More information

HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS

HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS HYGRODYNAMICS DIGITAL DEW POINT MONITOR PC BOARD MODEL 6392N & 6392N2 TABLE OF CONTENTS INTRODUCTION... 2 SPECIFICATIONS... 2 INSTALLATION... 3 PC Board Mounting...3 Sensor Installation...3 Manifold Assembly...4

More information

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Product Overview. Product Identification. Amps One CT Two CTs Three CTs AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

Flange Spreader Parts and Operating Manual

Flange Spreader Parts and Operating Manual Mathey Dearman Inc. 4344 South Maybelle Ave. Tulsa, OK 74107 Phone: 800-725-7311 918-447-1288 Fax: 918-447-0188 Flange Spreader Parts and Operating Manual General Information The Flange Spreader is used

More information

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II Document No.: LMSII_V100_OM Page 1 of 8 LMS II Document No.: LMSII_V100_OM Page 2 of 8 1. Operation: When the wet well level rises above the on level set point, the lead pump will start after an adjustable

More information

AGCO. Corn Header Manual d HEADSIGHT.COM

AGCO. Corn Header Manual d HEADSIGHT.COM AGCO Corn Header Manual 09020401d HEADSIGHT.COM 574.546.5022 About Headsight Headsight Contact Info Headsight, Inc. 4845 3B Road Bremen, IN 46506 Phone: 574-546-5022 Fax: 574-546-5760 Email: info@headsight.com

More information

Tissue Master. User Manual

Tissue Master. User Manual Tissue Master User Manual This page left blank intentionally This manual is a guide for the use of the Omni International Tissue Master and accessories. Data herein has been verified and validated. It

More information

SUNTURA HD SOLAR TRACKER

SUNTURA HD SOLAR TRACKER WindyNation SUNTURA HD SOLAR TRACKER SOT-TRKS-NFHD User s Manual Page 1 of 11 WindyNation 08/09/2012 Table of Contents 1! Introduction... 3! 1.1! Limited Warranty... 3! 1.2! Restrictions... 3! 1.3! Warranty

More information

Adjustable Angled Incline Conveyor Owners Manual with Operating Instructions

Adjustable Angled Incline Conveyor Owners Manual with Operating Instructions Adjustable Angled Incline Conveyor Owners Manual with Operating Instructions Revision 012211 Table of Contents Basic Conveyor Features 3 Getting Started 4 Setting Up the Incline Conveyor 5 Belt Removal

More information

8" - 12" Hydraulic Steel Squeeze Off Tool

8 - 12 Hydraulic Steel Squeeze Off Tool 8" - 12" Hydraulic Steel Squeeze Off Tool ECN 19130 C812S Hydraulic Steel Squeeze Off Tool for Steel Pipe Page 1 of 8 This Footage Tools C812S Steel Squeeze Off Tool is sold with one pump configuration

More information

Installation and Operating Manual

Installation and Operating Manual Model u002 & u003 Installation and Operating Manual Ultrasonic Level Switch 60 Great Hill Road Naugatuck, CT 06770 ph: 203-729-6434 fax: 203-729-6696 www.innovativesensing.com Read this Manual Before Installing

More information

PORTABLE PLATFORM SCALES Digital Type Series 850F Owner s Manual

PORTABLE PLATFORM SCALES Digital Type Series 850F Owner s Manual PORTABLE PLATFORM SCALES Digital Type Series 850F Owner s Manual Model 850F CARDINAL SCALE MFG. CO. 0066-M176-O1 Rev J 203 E. Daugherty, Webb City, MO 64870 USA 11/14 Ph: 417-673-4631 Fax: 417-673-5001

More information

BMRX Series ROTARY LEVEL CONTROL

BMRX Series ROTARY LEVEL CONTROL BMRX Series ROTARY LEVEL CONTROL OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0292 Rev C TABLE OF CONTENTS GENERAL SPECIFICATIONS... 3 SAFETY SUMMARY... 4 1.0 INTRODUCTION... 5 2.0 INSTALLATION...

More information

YCCS Zone/Bypass Damper Assembly

YCCS Zone/Bypass Damper Assembly YCCS Zone/Bypass Damper Assembly UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x The York Commercial Comfort System (YCCS) Zone/Bypass Damper are zone control and pressure control devices that include

More information

Operating and Installation Instructions

Operating and Installation Instructions Model Number 10301 Electronic Fuel Pump Operating and Installation Instructions This Product is Protected by U.S. Patent 8388322 CAUTION! This product is to be installed only by persons knowledgeable in

More information

Operation Key D4BS - K Head Mounting Direction F: Four mounting directions possible (front-side mounting at shipping)

Operation Key D4BS - K Head Mounting Direction F: Four mounting directions possible (front-side mounting at shipping) Safety-door Switch D4BS The Special Activates a Direct Opening Mechanism to Open the Contacts and Shut Off Control Circuits when Protective Doors Are Opened on Machine Tools or Other Equipment CSM_D4BS_DS_E_6_1

More information

CRD610 Automatic Fitting Inserter

CRD610 Automatic Fitting Inserter CRD610 Automatic Fitting Inserter OPERATIONS MANUAL VERSION 1.2 LAST EDITED 12.12.2018 cleanroomdevices.com 1 Table of Contents Title Page. 1 Table of Contents...2 1.0 General Product & Safety Information....3

More information

Quick Connection Cabinet (QCC)

Quick Connection Cabinet (QCC) Quick Connection Cabinet (QCC) Installation / Operation / Maintenance Manual 400A thru 1200A Ratings, 480Vac Max Quick Connection Cabinet Installation/Operation/Maintenance Manual Page 1 of 6 WARNING!

More information

YCCS Zone/Bypass Damper Assembly

YCCS Zone/Bypass Damper Assembly YCCS Zone/Bypass Damper Assembly UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x The York Commercial Comfort System (YCCS) Zone/Bypass Damper Assemblies are zone control and pressure control devices that

More information

Air Curtain. Installation, Operating and Maintenance Instructions

Air Curtain. Installation, Operating and Maintenance Instructions Installation, Operating and Maintenance Instructions Save this manual for future reference. Air Curtain Model Numbers: ES026, ES036, ES042, ES048, ES060, ES072 READ THIS OWNER S MANUAL CAREFULLY BEFORE

More information

A Member of the. Integrated Metering Technologies

A Member of the. Integrated Metering Technologies I n s t a l l a t i o n M a n u a l A Member of the Integrated Metering Technologies 1.0 General and Safety Do not install, operate or maintain this flow meter without reading, understanding and followingthe

More information

LIGHTSTICK / LIGHTSTICK PLUS Germicidal Ultraviolet Light

LIGHTSTICK / LIGHTSTICK PLUS Germicidal Ultraviolet Light LIGHTSTICK / LIGHTSTICK PLUS Germicidal Ultraviolet Light Installation & Operation Manual This manual covers the following models: LightStick #19300 LightStick Plus #19301 GENERAL This product emits germicidal

More information

Model C230 Pump Controller

Model C230 Pump Controller MANUAL Model C230 Earthsafe Systems, Inc. 7553 S. Madison Willowbrook, IL 60527 T: (630) 794-5100 F: (630) 794-5106 info@earthsafe.com www.earthsafe.com March 1, 2010 The information contained herein is

More information