OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)

Size: px
Start display at page:

Download "OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)"

Transcription

1 MOEL COE UCT SHAPE = Round = Rectangular = Flat Oval PROBE MATERIAL = Aluminum/ABS = CPVC & ABS = 0SS = High Temp SS (50 F / C Max) PROBE QUANTITY = = s = s = s SENSORS PER PROBE = Sensor per = Sensors per = Sensors per = Sensors per Model Shown Below: VT with Remote isplay Remote isplay Model VTM-05 (sold separately) VT The following information shall be provided with order:. One cable is provided with each probe. Contact factory if cables longer than 00' are required. Cable type is based on the Enclosure Selection per table below.. Maximum length for CPVC and High Temp SS Material is 60".. When Option (Internal Transmitter isplay) is selected, the Remote isplay can not be used. Transmitter evice Tag Number Analog Output Full Scale Range Analog Output Signal Type uct Size Internal uct Lining/Insulation Thickness Enclosure Selection Type of Cable Provided Cable Terminations 0 Plenum Rated Standard RJ5 / Standard RJ5 Outdoor Rated Waterproof RJ5 / Standard RJ5 Outdoor Rated Waterproof RJ5 / Standard RJ5 Outdoor Rated Waterproof RJ5 / Waterproof RJ5 Cables OPTIONS BLANK = No Options B = BACnet MS/TP = Internal Transmitter isplay (Ref Note ) ENCLOSURES 0 = Standard Transmitter, Standard = NEMA X Transmitter, Standard = Standard Transmitter, NEMA X = NEMA X Transmitter, NEMA X = Standard Transmitter, NEMA X w/purge 5 = NEMA X Transmitter, NEMA X w/purge CABLE LENGTH (Ref Note ) 0 = 0' (.0m) = 5' (.6m) = 50' (5.m) = 5' (.9m) = 00' (0.5m) PROBE LENGTH (Ref Note ) xx = Inches (0-) Sensor Sensor Sensor Sensor SPECIFICATIONS PERFORMANCE Accuracy Individual Sensors System Accuracy EMC AN SAFETY Emissions Immunity Safety +/-% of reading (factory verified to NIST traceable standard) +/-% of reading (installed accuracy expected when installation meets or exceeds minimum placement guidelines) +/- 0.% of reading Factory efault is,000 FPM (5. m/s) (software configurable) Repeatability Sensor FS Range ENVIRONMENTAL Operating Temperature Aluminum -0 to 0 F (-9 to 60 C) CPVC -0 to 0 F (-9 to 60 C) 0SS -0 to 00 F (-9 to 9 C) 0SS High Temp -0 to 0 F (-9 to 60 C) Transmitter -0 to 50 F (-9 to 66 C) isplay (optional) - to 58 F (-0 to 0 C) Storage Temperature s and Transmitter -0 to 50 F (-0 to 66 C) isplay (optional) - to 6 F (-0 to 80 C) Humidity Sensors Non-condensing Transmitter 0 to % non-condensing ELECTRICAL Input Power VAC +/- 0% 50-60Hz,. VA with no options,.8 VA with display & BACnet options VC +/-0%, W with no options, W with display & BACnet options Inputs to s with up to Sensors per (6 Sensors Max) Output 0-0mA, -0mA, 0-0v, -0v, 0-5v or -5v (software configurable) -bit Resolution, Capable of driving K ohm load Configuration Port USB.0, Isolated, Mini B Connector USB Power Switch Selects alternate power source for configuration when main power is not available raws 5v power from USB configuration port Status Indicators LE Status Indicators for; Power, Output, Configuration Port, Power Source Switch, Sensor Input Channel and, isplay and BACnet Communications I/O Terminal Block position vertical pluggable screw terminal block, screw access on top, -0 AWG Cables Plenum rated cables provided with standard enclosures Outdoor rated cables with waterproof plug provided with NEMA X enclosures Network Com Port EIA 85 -wire BACnet MS/TP (Optional) Galvanically Isolated ata Rates 9600, 900, 800, 5600, 6800 and 500 /8 Unit Load Receiver Input Impedance Network bias and EOL Termination not provided within the Transmitter isplay Remote mount or transmitter mount (Optional) Liquid Crystal isplay, lines x 8 characters with white LE backlight Includes USB Configuration Port MATERIALS CONSTRUCTION Insertion s Standard Aluminum bar, galvanized steel mounting plate, polycarbonate/abs plastic sensor CPVC CPVC plastic bar, 0SS mounting plate, polycarbonate/abs plastic sensor 0SS 0SS bar, 0SS mounting plate, 0SS sensor Enclosures Standard Optional Transmitter: Aluminum Alloy 505-H, 6 Gauge Electronics: Galvanized Steel, 8 Gauge Transmitter: NEMA X (IP66) Polycarbonate Plastic, V-0 Electronics: NEMA X (IPX6) Polycarbonate Plastic, V-0 EN 550:009+A:00, FCC Part 5:0, ICES-00 Issue 6, EN6000--:0, EN6000--:0 EN66-:0, EN6000--:009, EN6000--:006+A:008+A:00 EN6000--:0, EN :006, EN :009, EN :00 EN6000--:00 EN600-:00 Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL

2 PROBE INSTALLATION To optimize performance, it is always best to locate duct insertion probes with as much distance from upstream obstructions, transitions, elbows etc as possible. The examples shown below are provided as a minimum guideline only. If the application provides a greater distance of straight duct run than shown below, the probe should be installed to maximize the distance from upstream obstructions.. Match the device TAG I to the HVAC design documents as required to ensure the probe is installed per the design requirements.. Select optimum location in the duct for probe installation. Be sure the location selected has enough clearance to insert and extract probe from duct after equipment from all trades has been installed.. Install the probes into the duct by following the appropriate set of instructions provided on the following pages. Recommended Minimum Placement Guidelines for VorTek uct Insertion s uct Elbows uct Transitions ampers ucted Fans Elbows with Turning Vanes Reducing Transition Expanding Transition Upstream of Single Blade amper ownstream of Single Blade amper Centrifugal ischarge Elbows with No Turning Vanes <0 Reducing Offset Transition <0 Expanding Offset Transition Upstream of Opposed Blade amper Not Recommended ownstream of Opposed Blade amper 6 Centrifugal Inlet.5 <0 <5 5 Vane Axial ischarge uct Junctions Angle Fittings Radius Elbows Supply Junction Return Junction <5 5 Key.5.5 Round uct: = iameter >5 Rectangular & Oval uct: = (W + H) / Airflow : Airflow irection: Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL

3 PROBE INSTALLATION - Round uct Applications WARNING: Use eye protection, cut-resistant gloves and clothing suitable for working with sheet metal. Failure to do so may result in personal injury. Each probe will require either one or two holes to be drilled into the duct for installation. s " and less require only one hole which is referred to as the Insertion. s " and greater include a threaded stud at the probe end which requires an additional hole referred to as the. Reference Table to determine the hole drilling requirements for your application. Reference Table for the recommended probe/sensor density based on the duct size. For ducts with internal lining or insulation, the probes provided have been manufactured to accommodate the insulation thickness. X X X X Insertion 60. Mark the duct where probe is to be inserted.. rill the Insertion per Table.. Insert into.. Position per Airflow irection Arrow. 5. Secure to uct by installing #0 Tek- Screws into the mounting plate holes. Slot in Stud to be Aligned With Airflow " 60 Length inches to > uct iameter inches millimeters 8 to to 8 0 to 5 5 to mm 6 to 5 8 to 0 > 56 Insertion iameter.5 Table 6 to 5 0 to to 6 to to 89 Table 6 iameter. Configuration (probe qty X sensors/probe) X X X X X 8. Mark the duct where the center of the Insertion is to be located.. Measure the circumference of the duct and mark a straight line extending from the center of the Insertion around the circumference of the duct.. Locate and mark the center of the by measuring ½ the Circumference of the duct from the center of the Insertion.. For applications with two probes, shall be located degrees from with a " offset. Mark the duct where the center of the Insertion is to be located and repeat steps and. 5. For applications with three probes, each probe shall be located 60 degrees from the next with a " offset. Mark the duct where the center of the Insertion is to be located and repeat steps and. Mark the duct where the center of the Insertion is to be located and repeat steps and. 6. rill the required holes (Reference Table ) and install each probe with the threaded stud extending through the.. Position each probe so the Airflow irection Arrow is aligned with the airflow direction in the duct. 8. Secure the mounting plate of each using #0 Tek-Screws. For probes " and longer, secure the threaded stud using the locknuts provided. " ". Be sure the location selected has enough clearance to insert and extract probe from duct after equipment from all trades has been installed.. Tek-Screws provided by others. Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL

4 PROBE INSTALLATION - Rectangular uct Applications WARNING: Use eye protection, cut-resistant gloves and clothing suitable for working with sheet metal. Failure to do so may result in personal injury. Each probe will require either one or two holes to be drilled into the duct for installation. s " and less require only one hole which is referred to as the Insertion. s " and greater include a threaded stud at the opposite end which requires an additional hole referred to as the. Reference Table to determine the hole size requirements for your application. Before proceeding, confirm the probes provided are correct for the application (Reference Figure & Table ). The of the duct H is where the probes are to be installed and the other side of the duct W should be the same as the probe length for probes >". For ducts with internal lining or insulation, the probes provided have been manufactured to accommodate the insulation thickness. of uct (H) W uct Width (W) (Bar Length) Inches 6 8 9,0, x x x x Insertion Slot in Stud to be Aligned With Airflow 6 x x x x x x x x x x x x 8 x x x x x x x x x x x x x x x 9,0 x x x x x x x x x x x x x x x H, x x x x x x x x x x.x x.x x -8 x x x x x x x x x x x x x x 9- x x x x x x x x x x x x x x 5-0 x x x x x x x x x x x x x x -6 x x x x x x x x x x x x x x - x x x x x x x x x x x x x x -8 x x x x x x x x x x x x x x 9-5 x x x x x x x x x x x x x x x x x x x x x x x x x x x x Figure 6-66 x x x x x x x x x x x x x x 6- x x x x x x x x x x x x x x Table Figure Figure A A A A The duct hole locations A-A are based on the quantity of probes and the size of the duct H on the insertion side. To determine A-A for the application, reference the device schedule and probe tag. Single probe applications require A only, -probe applications require A & A, -probe applications require A, A & A and -probe applications require A, A, A and A.. Identify the of the duct and draw a straight line perpendicular to the edges of the duct extending edge-to-edge per Figure.. Mark the center of each Insertion location A-A per Figure.. Repeat the above steps on the opposite side of the duct to mark the corresponding s.. rill the required holes in the positions marked. Reference Table for the hole sizes. 5. Install each probe through the insertion hole until the threaded stud extends through the. 6. Position each probe so the Airflow irection Arrow is aligned with the airflow direction in the duct.. Secure the mounting plate of each to the duct using #0 Tek-Screws. For probes " and longer, secure the threaded stud on the using the locknuts provided. Length inches to > mm 6 to 5 8 to 0 > 56. Tek-Screws provided by others. Insertion iameter.5 Table 6 iameter.. Be sure the location selected has enough clearance to insert and extract probe from duct after equipment from all trades has been installed.. For - applications with duct H between and 6", the probes are factory-mounted onto a single plate. 8 Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL

5 PROBE INSTALLATION Flat Oval uct Applications WARNING: Use eye protection, cut-resistant gloves and clothing suitable for working with sheet metal. Failure to do so may result in personal injury. Each probe will require either one or two holes to be drilled into the duct for installation. s " and less require only one hole which is referred to as the Insertion. s " and greater include a threaded stud at the opposite end which requires an additional hole referred to as the. Reference Table to determine the hole size requirements for your application. Reference Figure : Before proceeding, confirm the probes provided are correct for the application. The is where the probes are to be installed over the flat F area. The dimension should be the same as the probe length for probes >". For ducts with internal lining or insulation, the probes provided have been manufactured to accommodate the insulation thickness. M F A A A A M = Major imension = Minor imension F = Flat = M- Figure Figure Slot in Stud to be Aligned With Airflow The duct hole locations A-A are based on the quantity of probes and the Major uct imension M on the insertion side. To determine A-A for the application, reference the device schedule and probe tag. Single probe applications require A only, -probe applications require A & A, -probe applications require A, A & A and -probe applications require A, A, A and A.. Identify the of the duct and draw a straight line perpendicular to the edges of the duct extending edge-to-edge per Figure.. Mark the center of each Insertion location A-A per Figure.. Repeat the above steps on the opposite side of the duct to mark the corresponding s.. rill the required holes in the positions marked. Reference Table for the hole sizes. 5. Install each probe through the insertion hole until the threaded stud extends through the. 6. Position each probe so the Airflow irection Arrow is aligned with the airflow direction of the duct.. Secure the mounting plate of each to the duct using #0 Tek-Screws. For probes " and longer, secure the threaded stud using the locknuts provided.. Be sure the location selected has enough clearance to insert and extract probe from duct after equipment from all trades has been installed.. Tek-Screws provided by others. Length inches to > mm 6 to 5 8 to 0 > 56 Figure Insertion iameter.5 Table 6 iameter. 8 Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL 5 :

6 TRANSMITTER INSTALLATION. Select an easily accessible location to install the transmitter within the range of the Cables that have been provided. Provide clearance to remove the cover and easily access the connectors and field connections.. Using the four 0.0" diameter holes located on the transmitter enclosure, secure the transmitter to mounting surface using () #8 or #0 Pan Head Screws. For sheet metal mounting surface, use sheet metal or tek screws, for plywood surface use coarse thread wood screws, for drywall surface, use drywall anchors with the appropriate screws.. Connect each probe to the corresponding probe input channel on the transmitter using the cables provided (Reference Figure ) Removable Terminal Plug (Power, Com, Output) NOTE Captive cable ties provided on the Transmitter and Electronics Enclosures are to be used for probe cable strain relief. uct of of vac Input of ANALOG INPUT - + BAS Controller Power Source Switch USB Config. Port Remote isplay Port (For Optional isplay) BACnet MS/TP Port (Optional) Input Input Input Ch., Input Board Ref Note CAUTION: o not use transmitter enclosure as a junction box. Only wires terminating on the transmitter board should enter the enclosure. Cables.6" (8mm) Figure Ø 0." (5mm) ( places) of Cable Connectors CAUTION: Polarity must be maintained if v power source is used to power more than one device otherwise equipment may be damaged. The power source must include a circuit breaker and be current limited to 8 amps maximum and grounded on the (-) side. TRANSMITTER WIRING Figure Strain Relief for Cables Strain Relief Fitting.85" dia. knock-out provided for Remote isplay Cable.85" dia. knock-out provided for BACnet. Loosen the thumb screw located on the transmitter enclosure cover and remove cover.. Run -conductor cable from the field controller to the transmitter through the strain relief fitting.. Remove the terminal block from the power/signal header, loosen the three screws and terminate the power, common and output signal wires in the terminal block per markings.. Tighten the terminal block screws, verify wires are secure and reconnect to the header. 5. If BACnet is required; run BACnet MS/TP cable into enclosure, remove terminal block from BACnet header and terminate the BACnet wires in the appropriate terminals. Tighten the terminal block screws, verify wires are secure and reconnect to header. 6. If Remote isplay is required; remove knock-out located directly in line with the isplay Port, install strain relief fitting into.85" dia. hole, run the factory cable provided with the Remote isplay into the enclosure and plug cable into the isplay Input Port.. The Channel - input board is required for applications that have and probes. Applications with or probes do not require this board. Cover Thumb Screw 5.9" (5mm) 5.6" (mm) Figure 6." (6mm)." (5mm) Strain Relief for Cables Commerce r anbury, CT 0680 SUBMITTAL RAWING VorTek G uct Insertion Model VT THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: REV. ATE: VT SUBMITTAL 6

7 INTERNAL ISPLAY TRANSMITTER WITH OPTIONAL ISPLAY 5.6 in mm.65 in 8 mm NEMA X (IP66) TRANSMITTER WITH OPTIONAL ISPLAY.5 in 88 mm 9. in mm NEMA X PROBE PROBE CABLE CONNECTORS 6. in 6mm 5.9 in 5 mm INTERNAL ISPLAY 8.58 in 8mm.50 in mm INTERNAL ISPLAY (OPTIONAL) ` POWER/SIGNAL CABLE ENTRY BACNET POWER/SIGNAL CABLE ENTRY.0 in 9 mm EXTERNAL ISPLAY CONNECTOR (NOT PROVIE WITH OPTIONAL INTERNAL ISPLAY) 5.60 in mm 5.9 in 50 mm NEMA X PROBE CABLE CONNECTORS SENSOR NEMA X FACTORY CABLE Commerce r anbury, CT 0680 SUBMITTAL RAWING THIS OCUMENT IS SUBJECT THIS OCUMENT OR THE CONTENTS THERE SHALL NOT BE MOIFIE WG. NO: VorTek G uct Insertion Model VT /06/8 REV. ATE: VT SUBMITTAL F ECN: SHEET:

ACCUSTATION SUBMITTAL MATERIALS

ACCUSTATION SUBMITTAL MATERIALS ACCUSTATION SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE SIZE 06 = 06" DIAMETER 08 = 08" DIAMETER

More information

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVC6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVT6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

Accutrol, LLC Product Sheet. VTS Series. US Patents 6,991,177 & 7,543,759. Digital Airflow Measurement Station

Accutrol, LLC Product Sheet. VTS Series. US Patents 6,991,177 & 7,543,759. Digital Airflow Measurement Station Accutrol, LLC Product Sheet VTS Series US Patents 6,991,177 & 7,543,759 Digital Airflow Measurement Station Innovative features of the AccuStation VTS Series! Digital Airflow Sensing Modular Design Intuitive

More information

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC5000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare epi Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5 Pa) Electronic

More information

Accutrol, LLC Product Sheet AVT6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVT6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVT6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVT6000! AHR Expo AWARDS WINNER Intuitive Graphical User Interface

More information

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks Accutrol, LLC Product Sheet Cage Rack Valve H-AVC5000 US Patents 6,991,177 & 7,543,759 Specially Made for Vivarium Cage Racks Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5

More information

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare AHR Expo AWARDS WINNER epi Innovative features for the AVC6000! Intuitive Graphical User Interface

More information

Acid Resistant AVC6000

Acid Resistant AVC6000 Accutrol, LLC Product Sheet Acid Resistant AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVC6000! AHR Expo AWARDS WINNER Intuitive Graphical

More information

Acid Resistant AVT6000

Acid Resistant AVT6000 Accutrol, LLC Product Sheet Acid Resistant AVT6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVT6000! AHR Expo AWARDS WINNER Manufactured in the

More information

Installation & Operation Manual - Model AV3000

Installation & Operation Manual - Model AV3000 Airflow Control Valve U.S. Patent # 6,991,177 Distributed by: Manufactured by: Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT 06810 USA 600 Pepper Street, Monroe, CT 06468 USA WWW.ACCUVALVE.COM For Service,

More information

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options Application and Design Thermal Dispersion Air Measuring Station with VCD-42 Control Damper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage

More information

SECTION FLOW INSTRUMENTS

SECTION FLOW INSTRUMENTS SECTION 230923.14 FLOW INSTRUMENTS Data contained in this guide specification may be placed in either of the following sections, depending on the specifics of the system design, or incorporated within

More information

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options Application Thermal Dispersion Air Measuring Station with VCD-23 Control Damper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage control

More information

Gold Series Thermal Dispersion Airflow Measurement Technology. Advantage. Installation, Operation and Maintenance Technical Manual GF1

Gold Series Thermal Dispersion Airflow Measurement Technology. Advantage. Installation, Operation and Maintenance Technical Manual GF1 Thermal Dispersion Airflow Measurement Model GF1 Technical Manual Gold Series Thermal Dispersion Airflow Measurement Technology Advantage Gold Series by Ebtron Installation, Operation and Maintenance Technical

More information

INSTALLATION MANUAL. Melink Corporation (513) Revision

INSTALLATION MANUAL. Melink Corporation (513) Revision INSTALLATION MANUAL Revision 130711 Table of Contents Step Installation Contractor Page 1 Install System Controller Electrical 4 2 Install Variable Frequency Drive Electrical 6 3 Install Touchpad Mechanical

More information

TURNING AIR INTO SOLUTIONS. COMPACT PLENUM FANS ECLFN ECLQN

TURNING AIR INTO SOLUTIONS. COMPACT PLENUM FANS ECLFN ECLQN TURNING AIR INTO SOLUTIONS. COMPACT PLENUM S ECLFN ECLQN CATALOG 456 July 2017 PLENUM S Overview ECLFN I ECLQN Plenum fans are unhoused fans designed to operate inside of field-fabricated or factory-built

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

YCCS Zone/Bypass Damper Assembly

YCCS Zone/Bypass Damper Assembly YCCS Zone/Bypass Damper Assembly UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x The York Commercial Comfort System (YCCS) Zone/Bypass Damper are zone control and pressure control devices that include

More information

YCCS Zone/Bypass Damper Assembly

YCCS Zone/Bypass Damper Assembly YCCS Zone/Bypass Damper Assembly UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x The York Commercial Comfort System (YCCS) Zone/Bypass Damper Assemblies are zone control and pressure control devices that

More information

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42V Air Measuring Station with VCD-42V Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) 14 ga. (2mm) Frame Type 5 in. x 1 in. hat channel - Blade

More information

AMD-42 Air Measuring Station with VCD-42 Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper Application and Design W x H Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness External Minimum Size 16 ga. (1.5mm) Internal Single Section Maximum Size Multiple

More information

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Document number 480938 AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Use this manual when AMS and AMD series dampers were purchased prior

More information

Model FDD Dynamic Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

Model FDD Dynamic Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed Tag: Project: Engineer: Contractor: Location: ate: pplication: rchitect: Submitted by: The NC model F fire damper utilizes a curtain style blade to prevent the spread of fire through a penetration in a

More information

Air Quality Solutions

Air Quality Solutions Air Quality Solutions Installation & Maintenance Manual Primary Remote Ancillary Model: TDP05K Advanced Thermal Dispersion Airflow & Temperature Measuring Probe II-TDP05K-917/Replaces II-TDP05K-617 ALL

More information

SRX Series Stainless Steel Body Air Cylinders with Continuous Position Feedback

SRX Series Stainless Steel Body Air Cylinders with Continuous Position Feedback with Continuous Position Feedback P P1L SRX SR/SRM, SR/SRM Contents Features... 42 Cylinder Ordering Information... 43 Specifications... 44 Engineering Specifications... 45 imensions...46-50 Mechanical

More information

Silver Series Thermal Dispersion Airflow Measurement Technology

Silver Series Thermal Dispersion Airflow Measurement Technology Thermal Dispersion Airflow Measurement Model STx104-U Unit Ventilator Airflow Measurement System Technical Data Silver Series Thermal Dispersion Airflow Measurement Technology APPLICATIONS Direct outdoor

More information

MODULAR CORE CEILING DIFFUSERS

MODULAR CORE CEILING DIFFUSERS MOEL SQUARE 12345-10 MOULAR CORE SQUARE IFFUSERS ROUN NECK SQUARE 1, 2, 3 OR ROUN 4-WAY AJUSTABLE NECK SQUARE ISCHARGE ROUN PATTERN NECK Steel Model: 7500 Suffix '-O' adds a steel opposed blade damper

More information

F-1500 SERIES INSERTION TURBINE FLOW METER FEATURES Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727)

F-1500 SERIES INSERTION TURBINE FLOW METER FEATURES Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727) F-1500 SERIES INSERTION TURBINE FLOW METER Insertion turbine flow meters are ideal for use in larger steam lines where downsizing the line size to improve flow measurement is not desirable. In these applications,

More information

Appendix. Clearance. Skewed profiles. Application Schematics

Appendix. Clearance. Skewed profiles. Application Schematics Appendix Application Schematics The purpose of the application schematics is to show different applications and the best sensor location for a particular application. Clearance Because the sensor will

More information

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure 592 Theory of Operation The 592 sensor is a two terminal integrated-circuit temperature sensor. The 592 provides an output current directly proportional to absolute temperature. When the temperature of

More information

F-1500 SERIES INSERTION TURBINE FLOW METER

F-1500 SERIES INSERTION TURBINE FLOW METER F-1500 SERIES INSERTION TURBINE FLOW METER APPLICATIONS Saturated steam Hot water to 450 F (232 C) standard 850 F (454 C) optional Applications with optional pressure sensor Superheated steam to 450 F

More information

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A Automation, Inc. Model EAC1100 /A QUICK INSTALL GUIDE Advanced Outdoor Airflow Control, DCV Control and Alarm Solution Enhancer QUICK INSTALL GUIDE for ENHANCER Advanced Outdoor Airflow Control, DCV Control

More information

NJK Precision Product NJK-02 Sensor Installation Guide

NJK Precision Product NJK-02 Sensor Installation Guide Precision -02 Sensor 2017 Product Line Precision Product Table of Contents Precision Company Overview - Page 2-02 Installation Guidelines - Page 3-02 Recommended Installations - Page 5-02 Non-Recommended

More information

MF4E MF4E

MF4E MF4E MF4E-60830-100 TAC DuraDrive Non-Spring Return Floating Actuator General Instructions Application The 35 lb-in. (4 N-m) and MF4E-60830-100 70 lb-in. (8 N-m) non-spring return, direct-coupled actuators

More information

FOR USE IN SOLUTION AIR HANDLING UNITS

FOR USE IN SOLUTION AIR HANDLING UNITS AMS-60 AIRFLOW MONITORING DEVICE APPLICATION GUIDE Supersedes: NOTHING Form 102.20-AG1 (303) FOR USE IN SOLUTION AIR HANDLING UNITS GENERAL The YORK AMS-60 is an airflow monitoring device which combines

More information

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control

More information

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations Overview The BA/T#-A is a flexible averaging duct mounted 4-20mA or Voltage transmitter probe. It comes in a variety of probe lengths and optional mounting enclosures shown below. The 4-20mA transmitter

More information

Model FD Static Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed

Model FD Static Curtain Fire Damper 1-½ or 3 Hour, UL555 Listed Tag: Project: Engineer: Contractor: Location: ate: pplication: rchitect: Submitted by: The NC model F fire damper utilizes a curtain style blade to prevent the spread of fire through a penetration in a

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

Differential pressure sensor

Differential pressure sensor s 1 916 QBM3x20-.. QBM3x20-..D Differential pressure sensor for air and non-aggressive gases QBM3020-.. QBM3120-.. High degree of measuring accuracy Adjustable characteristic curve (pressure-linear or

More information

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators MAx-305 & MAx-38 Series MAx-405 Through MAx-49 Series Two-Position Actuators General Instructions Application For two-position operation of dampers, valves, and other equipment which require the return

More information

F-2600 SERIES INLINE VORTEX FLOW METER

F-2600 SERIES INLINE VORTEX FLOW METER F-2600 SERIES INLINE VORTEX FLOW METER APPLICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260

More information

Seismic Sensor Accessories SA, SV & ST 6000 Series

Seismic Sensor Accessories SA, SV & ST 6000 Series Seismic Sensor Accessories SA, SV & ST 6000 Series Part Number Name Used With Description Housing Material 7295-002 Accelerometer EP Housing SA6200A-X0X; SV6300A-001 Physical protection and access to 1/4-28

More information

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation 592 Theory of Operation The 592 sensor is a two terminal integrated-circuit temperature sensor. The 592 provides an output current directly proportional to absolute temperature. When the temperature of

More information

Hour Meter Series HM36

Hour Meter Series HM36 Robust design with high degree of Accuracy and Compact size Frequency independent for AC applications Indicates operating time in hours and tenths with running indicators Totally sealed from Dust and Moisture

More information

Differential Pressure Sensors

Differential Pressure Sensors 1 910 1910P01 Differential Pressure Sensors for air or nonaggressive gases QBM66... Pressure-linear characteristic with selectable pressure measuring range Operating voltage AC 24 V or DC 13.5...33 V Output

More information

OE326-23I-OR VAV/Zone Controller

OE326-23I-OR VAV/Zone Controller + 4 8 - Description The OE36-3I-OR is a that is designed for pressure independent VAV Box and Zone Damper applications. It is supplied with an integral Airflow Sensor and is mounted in a plastic enclosure.

More information

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD

INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K-SERIES UNDER CABINET HOOD Read All Instructions Thoroughly Before Beginning Installation

More information

F-2700 SERIES INSERTION VORTEX FLOW METER

F-2700 SERIES INSERTION VORTEX FLOW METER F-2700 SERIES INSERTION VORTEX FLOW METER CALIBRATION Every ONICON flow meter is wet calibrated in a flow laboratory against standards that are directly traceable to N.I.S.T. A certificate of calibration

More information

JC-VSD FP Series II Drives Product Bulletin 1

JC-VSD FP Series II Drives Product Bulletin 1 JC-VSD FP Series II Drives Product Bulletin Code No. LIT-12012081 Issued May 2017 The Johnson Controls VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series

More information

CCS Zone/Bypass Damper Assembly

CCS Zone/Bypass Damper Assembly Code No. LIT-1900539 Issued July 15, 2011 UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x CCS Zone/Bypass Damper Assembly Description The Commercial Comfort System (CCS) Zone/Bypass Damper are zone control

More information

F-2700 SERIES INSERTION VORTEX FLOW METER

F-2700 SERIES INSERTION VORTEX FLOW METER F-2700 SERIES INSERTION VORTEX FLOW METER APPLICATIONS Saturated steam Hot water to 500 F (260 C) standard 750 F (400 C) optional Applications with optional pressure sensor Superheated steam to 500 F (260

More information

GE Measurement & Control

GE Measurement & Control GE Measurement & Control Telaire Ventostat 8000 Series CO 2 Sensor User Instructions Installing the Sensor!WARNING! Before performing service or maintenance operations on the systems, turn OFF main power

More information

INSTALLATION MANUAL. Melink Corporation (513) Revision

INSTALLATION MANUAL. Melink Corporation (513) Revision INSTALLATION MANUAL Revision 130815 Table of Contents Step Installation Contractor Page 1 Install System Controller Electrical 4 2 Install Variable Frequency Drive Electrical 6 3 Install Touchpad Mechanical

More information

Technical specification

Technical specification 15. Nov. 2010 Page 1 (5) Metso Rotating Sensor part - Rotating shear force based transmitter for pulp consistency measurement in pulp and paper industry. - Sensing element selection based on pulp type

More information

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options Application and Design The combines the functionality of an accurate airflow measuring station and a low leakage control damper into one compact assembly that both measures and regulates airflow volumes

More information

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT

INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS K SERIES LINER INSERT Read All Instructions Thoroughly Before Beginning Installation WARNING

More information

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Technical Specification Sheet Document No. 149-855 November 04, 2015 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules NOTE: The 570-8xxPA BACnet laboratory controllers have new 67xx

More information

VOC Duct and Rough Service Sensor

VOC Duct and Rough Service Sensor Overview and Identification Humans respirate Volatile Organic Compounds (VOCs) as well as CO 2. The BAPI sensor measures these VOCs and indicates space occupancy just as well as a CO 2 sensor. The advantage

More information

PERFORATED CEILING DIFFUSERS

PERFORATED CEILING DIFFUSERS PERFORAE MOEL PERFORAE 12345-10 CEILING SQUARE IFFUSERS ROUN NECK SQUARE ROUN NECK SUPPLY SQUARE 1, 2, 3 OR ROUN 4-WAY AJUSABLE NECK ISCHARGE PAERN Steel Models: 4320 Flush Face 4325 rop Face Aluminum

More information

Air Flow Measurement Technologies

Air Flow Measurement Technologies Page 1/7 Typical Air Flow Measurement Applications Air Flow Control True Flow Feedback Theory of Vortex Shedding Air Flow Measurement Pitot Air Flow Measurement Thermal Air Flow Measurement Advantages

More information

SOUND GUARD SST-E INSTALLATION INSTRUCTIONS & PARTS LIST

SOUND GUARD SST-E INSTALLATION INSTRUCTIONS & PARTS LIST SOUND GUARD SST-E INSTALLATION INSTRUCTIONS & PARTS LIST FOR DIESEL GENERATOR MODELS 12.5-15.0 ETD SOUND GUARD SST-E INSTALLATION INSTRUCTIONS & PARTS LIST FOR DIESEL GENERATOR MODELS 12.5-15.0 ETD INTRODUCTION

More information

V-SENSOR LOW AIR VELOCITY SENSOR

V-SENSOR LOW AIR VELOCITY SENSOR home VSENSOR LOW AIR VELOCITY SENSOR Ultra low velocity pressure measurement Traceable Calibration Certificate Excellent repeatability Self compensating zero Climate chamber compensated Long term span

More information

AMD-33 Air Measuring Station with VCD-33 Control Damper

AMD-33 Air Measuring Station with VCD-33 Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS

PERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINTS 50FN-1SB 50FNX,FNY078,088,104 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE AIR VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE WITH INTEGRAL ECONOMIZER AND HIGH-CAPACITY MODULATING

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit Instruction Sheet 10-2004 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch.

More information

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2100/2200 FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER MODEL 2100: Constant face velocity, variable volume MODEL 2200: Constant face velocity, variable volume

More information

Centrifugal, Tubular Inline Fan, Model CIR

Centrifugal, Tubular Inline Fan, Model CIR Centrifugal, Tubular Inline Fan, Model CIR TABLE OF CONTENTS 3 Introduction, Certifications & Listings 4 Features & Benefits 5 Options & Accessories 6 irect rive imensional & Performance ata 7 Belt rive

More information

ELECTRICAL PANELS. Chap.

ELECTRICAL PANELS. Chap. ELECTRICAL PANELS 360 Panel System Electrical Panels 360 Panel System Modular Panels DC Electric Panels AC Electric Panels AC/DC Electric Panels Aber Marine Panels IP 67 Watertight Panels Rotary Switch

More information

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions Product Identification Fig 1. BAPI-Com Communication Output Module Fig 2. BAPI-Com Room Sensor, BA/BS4SCOM Operations Overview The BAPI-Com sensor is designed to be used in retrofit applications on just

More information

HUMIDITY / TEMPERATURE TRANSMITTER

HUMIDITY / TEMPERATURE TRANSMITTER HUMIDITY / TEMPERATURE TRANSMITTER SEM161, SEM16 CONFIGURATION USING USB PORT POWERED CONFIGURATOR HUMIDITY, TEMPERATURE, DEW POINT MEASUREMENT INTERCHANGEABLE DIGITAL SENSOR HIGH ACCURACY AND STABILITY

More information

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations Overview The BA/#-SA is for duct mounting 4 to 20mA or Voltage temperature transmitter for measurement of moisture saturated, stratified air across a duct with a humidifier or outside air intake to give

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options Application and Design The series is a general purpose, low leakage control damper intended for application in low pressure and velocity systems. atings Pressure: 2 in. wg (.5 kpa) - pressure differential.

More information

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES FLS F6.60 MAGMETER FLOW SENSOR The new F6.60 and F6.63 are flow meters without moving mechanical parts which can be applied for the measurement of dirty liquids so long as they are conductive and homogeneous.

More information

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction. Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

BAPI-Stat 3 Room Sensor

BAPI-Stat 3 Room Sensor Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read

More information

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology NMQB-MFT, NMQX-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, V, Multi-Function Technology Application For proportional modulation of dampers in HVAC systems. Actuator sizing should

More information

CURRENT TRANSFORMER MODEL N. SS BAND SECURES BRACKET (view of screw clamp band omitted for clarity) 0.25 x 0.50 SLOT (2 PLACES)

CURRENT TRANSFORMER MODEL N. SS BAND SECURES BRACKET (view of screw clamp band omitted for clarity) 0.25 x 0.50 SLOT (2 PLACES) MODEL N 4." I.D. PAGE No 1-30 TERMINAL OPTION LEAD WIRE OPTION 6.75 SS BAND SECURES BRACKET (view of screw clamp band omitted for clarity) 0.75 1.36 1.16 5.75 7.00 0. x 0.50 SLOT (2 PLACES) UL 1015 #16

More information

Series TFXL ULTRASONIC CLAMP-ON FLOW METER DIMENSIONAL SPECIFICATIONS PRODUCT INSTALLATION

Series TFXL ULTRASONIC CLAMP-ON FLOW METER DIMENSIONAL SPECIFICATIONS PRODUCT INSTALLATION Series PROUT INSTLLTION Series IMENSIONL SPEIFITIONS MEHNIL IMENSIONS: INHES (MM) Installation onsiderations 1. Select the optimum mounting location on the piping system a full pipe with at least 10 straight

More information

RETROFIT TERMINAL UNITS

RETROFIT TERMINAL UNITS GENERAL PROUCT OVERVIEW Retrofit Terminal s Convert Constant Air Volume Systems to Variable Air Volume. Convert Constant Volume ual uct Systems to Variable Air Volume. Convert Multizone Systems to Variable

More information

Model DFX Doppler ultrasonic flow meter

Model DFX Doppler ultrasonic flow meter Badger Meter Europa GmbH Nürtinger Str. 76 72639 Neuffen (Germany) Tel. +49-7025-9208-0 Fax +49-7025-9208-15 www.badgermeter.de badger@badgermeter.de Model DFX Doppler ultrasonic flow meter Features Badger

More information

Softstarter Intelligent Controllers

Softstarter Intelligent Controllers Softstarter Intelligent Controllers Series Modes of Operation (Standard) Soft Start 100% Percent Voltage Initial Torque Start Run This method has the most general application. The motor is raised from

More information

MA-5200 Series MA-5300 Series

MA-5200 Series MA-5300 Series MA-5200 Series MA-5300 Series Two-Position Actuators General Instructions Application The MA-5200 series and MA-5300 series actuators are used for two-position control of valves and dampers which require

More information

Sentinel Field Satellite Controller

Sentinel Field Satellite Controller WARNING HIGH VOLTAGE 115V M AP Sentinel Field Satellite Controller Installation Instructions Important: For your protection and the safety of the product user, please comply with all Caution and Warning

More information

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System Product Bulletin Code No. LIT-12011620 Issued July 2, 2014 RA-1250 Thermal Dispersion Fan Inlet Sensor Airflow Measuring System averages

More information

TM-9100 Series Room Command Module

TM-9100 Series Room Command Module FANs 216, 1628.3 Product/Technical Bulletin TM-9100 Issue Date 0400 TM-9100 Series Room Command Module The TM-9100 Series Room Command Modules are designed for use with the TC-9100 series of DDC (Direct

More information

DST600 Series Digi-Stem Thermometers

DST600 Series Digi-Stem Thermometers DST600 Series Digi-Stem Thermometers User Manual 04/12/12 WD1032 Rev L (05/24/16) For use with models: DST600 DST610, DST611, DST620 & DST621 DST640 DST650, DST651, DST660, DST661 Including I, R and P

More information

SECTION WELDING FUME EXHAUST SYSTEM

SECTION WELDING FUME EXHAUST SYSTEM SECTION 233500 WELDING FUME EXHAUST SYSTEM PART 1 - GENERAL 1.1 WORK INCLUDES Welding fume exhaust system and controls Accessories Additional System Equipment Engineering Support Commissioning 1.2 RELATED

More information

1100 Series Piston Type Differential Pressure Gauges

1100 Series Piston Type Differential Pressure Gauges 1100 Series Piston Type Differential Pressure Gauges 1. Safety Before installing, check the Series Number and verify compatibility to the process media and temperature in contact with the wetted parts.

More information

The readings you need, right where you need them. AX Series Vortex Meters

The readings you need, right where you need them. AX Series Vortex Meters The readings you need, right where you need them. AX Series Vortex Meters Multivariable function from a single meter Vortex multivariable meters from Azbil North America employ three sensing elements in

More information

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation Instructions M9206-Bxx-2S Issue Date May 14, 2003 M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation IMPORTANT: Use this M9206-Bxx-2S Series actuator to control equipment

More information

MF /MS Series

MF /MS Series MF41-6153/MS41-6153 Series 24 Vac, Three-position/Modulating Non-spring Return Rotary Electronic Damper SmartX Actuators General Instructions Description The direct-coupled, 24 Vac, non-spring return electronic

More information

GE Monogram. Installation. Instructions. Professional Vent Hoods. 48" Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS. 36" Models ZV671WSS, ZV681YSS

GE Monogram. Installation. Instructions. Professional Vent Hoods. 48 Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS. 36 Models ZV671WSS, ZV681YSS GE Monogram Installation Instructions Professional Vent Hoods 48" Models ZV881WSS, ZV891YSS ZV880WSS, ZV890YSS 36" Models ZV671WSS, ZV681YSS ZV670WSS, ZV680YSS 30" Models ZV370YSS, ZV371YSS CAUTION WARNING

More information

VT-SENSOR AIR VELOCITY AND TEMP

VT-SENSOR AIR VELOCITY AND TEMP home VTSENSOR AIR VELOCITY AND TEMP Ultra low velocity pressure measurement Traceable Calibration Certificate Excellent repeatability Self compensating zero Climate chamber compensated Long term span stability

More information

MS Application. Features. Proportional Valve Actuator General Instructions

MS Application. Features. Proportional Valve Actuator General Instructions Proportional Valve Actuator Application The Proportional Valve Actuator is a non-spring return actuator used with proportional to 10 Vdc or 4 to 0 ma controllers and standard 1/" to 1-1/4" two-way and

More information

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER

INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD WITH M600 OR M1200 BLOWER WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK C U L R Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS WALL MOUNT RANGE HOOD

More information