ALPF Factory Sealed Lighting - APPF Power Distribution Panelboards Explosionproof, Dust-Ignitionproof, Watertight

Size: px
Start display at page:

Download "ALPF Factory Sealed Lighting - APPF Power Distribution Panelboards Explosionproof, Dust-Ignitionproof, Watertight"

Transcription

1 ALPF Factory Sealed Lighting - APPF Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG Applications Distribution panelboards are used to furnish protection and control of electrical equipment in hazardous locations. These compact units provide a centrally controlled switching system for large quantities of branch circuits for: Lighting Heating Small motors Similar electrical equipment Features operators included as standard. O-ring gasket insures watertight integrity. Factory sealed, no external seals are required for most branch circuits. All conduits must be sealed adjacent to enclosure for Class I, Division 1, Groups B and C. s are housed in the panel section and prewired to maximum circuit capacity, then wired to numbered terminals in the wiring compartment. Terminal compartment is interconnected to panel section with sealing hubs, unions and poured with sealing compound. Permits selection of 1-, 2- or 3-pole breakers. Precision machined flame path between body and cover. Bolt on stainless steel slotted mounting feet. operators can be padlocked in the or position. All panelboards are supplied with Cutler-Hammer interiors. Chassis assembles with mains at top (bottom optional). Provisions for 12, 18, 24, 30, 36 and 42 circuit 1-pole chassis. 100 Amp or 225 Amp main lug. Up to 100 Amp backfed main breaker available with main lug chassis. Up to 225 Amp main breaker available with main breaker chassis. Factory installed ground and neutral bar as standard. Standard aterials Bodies and covers: copperfree (4/10 of 1% max.) aluminum Cover bolts: Quad-Lead, captive, stainless steel operators: copperfree (4/10 of 1% max.) aluminum Hinges: stainless steel Bus bars: copper O-ring: neoprene Standard Finish Corrosion resistant gray epoxy powder coat to provide NA 4X rating Options ust be listed in alphanumeric sequence at the end of the catalog number. Options Breather, NA 4X add suffix BR. Drain, NA 4X add suffix DN. xternal ground stud add suffix GS. Grounding neutral lug add suffix GNL. Terminal breaker located at bottom, add suffix INV. ain breaker located at bottom, add suffix LB. Phenolic nameplate (specify legend) add suffix NP. For 50 C (122 F) breaker rating, add suffix V. For stainless steel terminal enclosure for Division 2 applications only, contact your local sales representative. ain Options Auxiliary switch (1A or 1B) add suffix AS1. Auxiliary switch (2A or 2B) add suffix AS2. Shunt trip (specify voltage) add suffix ST. Under voltage release (specify voltage) add suffix UV. Branch Option ALPF quipment Protection Devices (1- or 2-Pole -30 ma sensitivity) add suffix PD. Ground Fault Interrupter (1- or 2-Pole -5 ma sensitivity) add suffix GFI. GFI Indicating Light add suffix L5. Branch Options APPF GHB quipment Protection Devices (1- or 2-Pole -30 ma sensitivity) add suffix PD. Branch Options APPF F-Frame Auxiliary switch (1A or 1B) add suffix AS1. Auxiliary switch (2A or 2B) add suffix AS2. Shunt trip (specify voltage) add suffix ST. Under voltage release (specify voltage) add suffix UV. 400 Amp panel available, contact your local sales representative. NC Certifications and Compliances UL Standard: UL 1203 UL Classified: DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS Cutler-Hammer is a trademark of the aton Corporation. GFI Push-to-Test Buttons are standard with GFI or PD options. 339

2 ALPF Lighting Factory Sealed Distribution boards xplosionproof, Dust-Ignitionproof, Watertight DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG Select branch breakers as desired in panel. First and second digits are the quantity of breakers, third and fourth digits are ampere rating, the fifth digit is number of poles. xample: An 18 circuit 120/240 V 1-phase 3-wire 225 Amp ain panel with 12 1-pole 20 Amp and 3 2-pole 30 Amp branch breakers should read ALP18B GFI. Catalog Numbering Guide ALPF 2 1 A 18 B GFI Duty: Appleton Factory Sealed Lighting Voltage: 1-120/ / Vdc 7-24 Vdc 8-125/250 Vdc ain Type: B - ain L - ain Lug Rating : 10-10AT 15-15AT 20-20AT 25-25AT 30-30AT 35-35AT 40-40AT 45-45AT 50-50AT 55-55AT 60-60AT 70-70AT 80-80AT (not for 1-Pole) 90-90AT (not for 1-Pole) Additional Branch s: Repeat Step Size: J - 12 Circuit, 100 Amp ain Lug K - 18 Circuit, 100 Amp ain Lug - 30 Circuit, 100 or 225 Amp ain Lug or 18 Circuit with ain N - 42 Circuit, 225 Amp ain Lug or 36 Circuit with ain Q - 42 Circuit with ain Wire System: A - 1P, 3W B - 3P, 3W for 240 Vdc C - 3P, 4W D - 2P, 2W for 24 Vdc Rating: AT AT AT AT AT AT AT AT AT AT AT AT AT AT AT No. of Poles : (include only if different from wiring system) Suffix for Other Options/ Features: ust be listed in alphanumeric sequence (See Options) Current Rating: Amp Amp Number of Circuits: Quantity of Branch s : 1 thru 42 Type : Normal Duty (Leave Blank) PD GFI HID Suffix for Other Options/Features: ust be listed in alphanumeric sequence. See Options. 340

3 ALPF Lighting Factory Sealed Distribution boards xplosionproof, Dust-Ignitionproof, Watertight NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG 100 Amp ain Lug 225 Amp ain Lug ain 100AF ain 225AF Number of Circuits 120/240 Volt 1-Phase 3-Wire BAB Type 120/208 Volt 3-Phase 4-Wire BAB Type 240V 3-Phase 3-Wire Delta BAB Type Size Approx. Weight (lbs) 12 ALPFJ112L ALPFJ122L ALPFJ152L J / ALPFK118L ALPFK128L ALPFK158L K / ALP14L ALP24L ALP54L / ALP1A30L ALP2C30L ALP5C30L / ALP18L ALP28L ALP58L / ALP14L ALP24L ALP54L / ALP1A30L ALP2C30L ALP5C30L / ALPFN21A36L ALPFN22C36L ALPFN25C36L N / ALPFN21A42L ALPFN22C42L ALPFN25C42L N / ALP12B100 ALP22B100 ALP52B / ALP18B100 ALP28B100 ALP58B / ALPFN114B100 ALPFN124B100 ALPFN154B100 N / ALPFN11A30B100 ALPFN12C30B100 ALPFN15C30B100 N / ALP18B225 ALP28B225 ALP58B / ALPFN214B225 ALPFN224B225 ALPFN254B2225 N / ALPFN21A30B225 ALPFN22C30B225 ALPFN25C30B225 N / ALPFN21A36B225 ALPFN22C36B225 ALPFN25C36B225 N / ALPFQ21A42B225 ALPFQ22C42B225 ALPFQ25C42B2225 Q /447 Note: For Back Fed main, replace L, B100, or B225 in part number with BF. For 400 Amp ain Lug, contact your local representative. Standard interrupting capacity is 14,000 AIC. For higher interrupt ratings, contact your local representative. DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS Typical board Wiring Diagram 1-Phase, 3-Wire Systems 3-Phase, 4-Wire Systems Sealed Together J /08 K / /08 N /08 Q /08 Suffix for Other Options/Features: ust be listed in alphanumeric sequence. See Options. 341

4 APPF Series Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight GHB Cutler-Hammer Circuit s DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG Select GHB branch breakers as desired in panel. First and second digits are the quantity of breakers, third and fourth digits are ampere rating, the fifth digit is number of poles. xample: An 18-circuit 277/480 V 3-phase 4-wire 100 A LO panel with 12 1-pole 20 Amp and 3 2-pole 30 Amp branch breakers should read APPFK148L PD Catalog Numbering Guide APPF K 1 4 C 18 L PD Duty: Appleton Factory Sealed Power Voltage: 4-277/480 (3P 4W ) 7-24 Vdc 8-125/250 Vdc ain Type: B - ain L - ain Lug Rating : 15-15AT 20-20AT 25-25AT 30-30AT 35-35AT 40-40AT 45-45AT 50-50AT 55-55AT 60-60AT 70-70AT 80-80AT 90-90AT Additional Branch s: Repeat Step Size: J - 12 Circuit, 100 Amp ain Lug K - 18 Circuit, 100 Amp ain Lug - 30 Circuit, 100 or 225 Amp ain Lug or 18 Circuit with ain N - 42 Circuit, 225 Amp ain Lug or 36 Circuit with ain Q - 42 Circuit with ain Wire System: C - 3P, 4W D - 2P, 2W for 24 Vdc Rating: AT AT AT AT AT AT AT AT AT AT AT AT AT AT AT No. of Poles : (include only if different from wiring system) Suffix for Other Options/ Features: ust be listed in alphanumeric sequence (See Options) Current Rating: Amp Amp Number of Circuits: Quantity of Branch s : 1 thru 42 Type : Normal Duty (Leave Blank) PD PD Single Phase (requires 2-Poles) 277 Vac, 30 ma. Suffix for Other Options/Features: ust be listed in alphanumeric sequence. See Options. GHB and Cutler-Hammer are trademarks of the aton Corporation. 342

5 APPF Series Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight GHB Cutler-Hammer Circuit s NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG 100 Amp ain Lug 225 Amp ain Lug ain 100 Amp F ain 225 Amp F Number of Circuits 277/480 Volt 3-Phase 4-Wire GHB Type Size Approximate Weight kgs (lbs) 12 APPFJ142L J (135) 18 APPFK148L K (165) 24 APP44L (210) 30 APP4C30L (215) 18 APP48L (180) 24 APP44L (230) 30 APP4C30L (235) 36 APPFN24C36L N (290) 42 APPFN24C42L N (295) 12 APP42B (165) 18 APP48B (180) 24 APPFN144B100 N (210) 30 APPFN14C30B100 N (315) 18 APP48B (185) 24 APPFN244B225 N (295) 30 APPFN24C30B225 N (300) 36 APPFN24C36B225 N (305) 42 APPFQ24C42B225 Q (345) Note: For Back Fed main, replace L, B100, or B225 in part number with BF. For 400 Amp ain Lug, contact your local representative. Standard interrupting capacity is 14,000 AIC. For higher interrupt ratings, contact your local representative. DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS Typical board Wiring Diagram 3-Phase, 4-Wire Systems Suffix for Other Options/Features: ust be listed in alphanumeric sequence. See Options. GHB and Cutler-Hammer are trademarks of the aton Corporation. 343

6 APPF 480, 600 Volt Factory Sealed Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight F-Frame Cutler Hammer Circuit s DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG Select branch breakers as desired in panel. First and second digits are the quantity of breakers, third and fourth digits are ampere rating, the fifth digit is number of poles. xample: An 18-circuit 277/480 V 3-phase 100 A LO panel with 12 1-pole 20 Amp and 3 2-pole 30 Amp branch breakers should read APPFP148L Catalog Numbering Guide APPF P 1 4 C 18 L Duty: Appleton Factory Sealed Power Size: P - 12 Circuit with ain or 24 Circuit without ain R - 24 Circuit with ain or 36 Circuit without ain or S - 42 Circuit with or without ain Current Rating: Amp Amp Voltage: / Vdc 8-125/250 Vdc Wire System: B - 3P, 3W C - 3P, 4W D - 2P, 2W for 24 Vdc Number of Circuits: ain Type: B - ain L - ain Lug Rating: AT AT AT AT AT AT AT AT AT AT AT AT AT AT AT PD Single Phase (requires 2-Poles) 277 Vac, 30 ma. Cutler-Hammer is a trademark of the aton Corporation. Quantity of Branch s : 1 thru 42 Rating : 10-10AT 15-15AT 20-20AT 25-25AT 30-30AT 35-35AT 40-40AT 45-45AT 50-50AT 60-60AT 70-70AT 80-80AT 90-90AT AT (2-, 3-Pole ) AT (2-, 3-Pole ) AT (2-, 3-Pole ) AT (2-, 3-Pole ) AT (2-, 3-Pole ) No. of Poles : (include only if different from wiring system) Additional Branch s: Repeat Step Suffix for Other Options/ Features: ust be listed in alphanumeric sequence (See Options) 344

7 APPF 480, 600 Volt Factory Sealed Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight F-Frame Cutler Hammer Circuit s NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG 100 Amp ain Lug 225 Amp ain Lug ain 100 Amp F Number of Circuits 480 V 3-Phase 3-Wire HD Type 277/480 V 3-Phase 4-Wire HD Type 600 V 3-Phase 4-Wire FDB Type 12 APPFP13B12L APPFP142L APPFP162L 18 APPFP13B18L APPFP148L APPFP168L 24 APPFP13B24L APPFP144L APPFP164L 30 APPFR13B30L APPFR14C30L APPFR16C30L 18 APPFP23B18L APPFP248L APPFP268L 24 APPFR23B24L APPFR244L APPFR264L 30 APPFR23B30L APPFR24C30L APPFR26C30L 36 APPFR23B36L APPFR24C36L APPFR26C36L 42 APPFS23B42L APPFS24C42L APPFS26C42L 12 APPFP13B12B100 APPFP142B100 APPFP162B APPFR13B18B100 APPFR148B100 APPFR168B APPFR13B24B100 APPFR144B100 APPFR164B APPFR13B30B100 APPFR14C30B100 APPFR16C30B100 DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS 18 APPFR23B18B225 APPFR248B225 APPFR268B225 ain 225 Amp F 24 APPFR23B24B225 APPFR244B225 APPFR264B APPFS23B30B225 APPFS24C30B225 APPFS26C30B APPFS23B36B225 APPFS24C36B225 APPFS26C36B APPFS23B42B225 APPFS24C42B225 APPFS26C42B225 Note: For Back Fed main, replace L, B100, or B225 in part number with BF. For 400 Amp ain Lug, contact your local representative. Standard interrupting capacity is 14,000 AIC. For higher interrupt ratings, contact your local representative. Typical board Wiring Diagram 3-Phase, 3-Wire Systems 3-Phase, 4-Wire Systems Suffix for Other Options/Features: ust be listed in alphanumeric sequence. See Options. 345

8 ALPF Factory Sealed Lighting - APPF Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight F-Frame Cutler Hammer Circuit s DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG ALPF and APPF (GHB Type) Factory Sealed Distribution board Size Sealed Together Top Outlets Side Outlets ounting Hdw. Set N /08 (1) 3 and (8) 1 NPT (4) 1 NPT AH8 Q /08 (1) 3 and (8) 1 NPT (4) 1 NPT AH8 Dimensions in illimeters (Inches) SIDS K N SIDS K SIDS K SIDS Q K K Size B1 B2 D1 D2 G H K N Q (19.75) (21.75) (19.63) (23.00) (13.00) (32.00) (38.38) (21.00) (23.75) (42.94) (47.75) (67.13) (74.13) 69.9 (2.75) 96.8 (3.81) (6.19) (2.63) 88.9 (3.50) (3.94) (5.00) (13.00) (12.81) 346

9 FB766 FB766 APS APS APS APS APS APS FB766 FB766 APS APS APS APS APS APS FB766 FB766 CIRCUIT NO. APS CIRCUIT NO. APS CIRCUIT NO. APS CIRCUIT NO. APS CIRCUIT NO. APS CIRCUIT NO. APS ALPF Factory Sealed Lighting - APPF Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG ALPF and APPF (GHB Type) Factory Sealed Distribution board Size Sealed Together Top Outlets Side Outlets ounting Hdw. Set J /08 (1) 2 and (8) 1 NPT AH8 K /08 (1) 2 and (8) 1 NPT AH /08 (1) 3 and (8) 1 NPT AH8 Dimensions in illimeters (Inches) J K G HG H G H H G GH H K K K HG H G GH H K K HG G H G GH H K K SIDS SIDS DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS 1/2" NP 1/ FO Size B1 B2 D1 D2 G H K J K (19.75) (19.75) (19.75) (19.75) (19.38) (18.75) (15.50) (21.00) (21.40) (20.80) (27.31) (32.80) (46.88) (52.88) (58.50) 69.9 (2.75) 69.9 (2.75) 69.9 (2.75) 82.6 (3.25) 82.6 (3.25) (3.25) 82.6 (3.25) 66.8 (2.63) (3.94) (3.94) (3.94) 347

10 ALPF Factory Sealed Lighting - APPF Power Distribution boards xplosionproof, Dust-Ignitionproof, Watertight F-Frame Cutler Hammer Circuit s DISTRIBUTI QUIPNT: NC/CC HAZARDOUS LOCATI PANLBOARDS NC: Class II, Division 1 and 2, Groups, F, G NA 4, 4X, 7BCD, 9FG APPF 480, 600 Volt Factory Sealed Power Distribution board Size Sealed Together Top Standard Outlets Sides ounting Hdw. Set P /08 (1) 3 and (8) 1 NPT CH8 (2) R /08 (1) 3 and (8) 1 NPT (4) 1 NPT CH8 (2) S /08 (1) 3 and (8) 1 NPT (4) 1 NPT CH8 (2) Dimensions in illimeters (Inches) P R S K SID H G G H K B1D1 SID K B1D1 B2D2 B2D2 Size B1 B2 D1 D2 G H K P R S (21.75) (21.75) (21.75) 21.75/ 522.5) (21.38) (23.50) (13.00) (13.00) (13.00) (29.00) (36.00) (50.00) (23.50) (23.00) (25.00) (41.75) (53.00) (65.00) (67.63) (78.88) (91.00) 74.7 (2.94) 74.7 (2.94) 74.7 (2.94) (7.50) (7.50) (3.50) 88.9 (3.50) 88.9 (3.50) (4.13) (4.13) (4.13) (13.06) (10.50) (13.06) 348

P-9. ALPN, APPN and AGPN Series: Explosionproof, Dust-Ignitionproof, Watertight Non-Factory Sealed.

P-9. ALPN, APPN and AGPN Series: Explosionproof, Dust-Ignitionproof, Watertight Non-Factory Sealed. ALN, AN and AGN Series: Non-Factory Sealed. -9 Applications Distribution panelboards are used to furnish protection and control of electrical equipment in hazardous locations. These compact units provide

More information

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

D2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant Applications Protection and control of electrical equipment and circuits such as lighting and heat tracing in hazardous locations or in damp, wet or corrosive conditions. D2P Series designed for use in

More information

P-2 D2P and EWP Factory Sealed Circuit Breaker Panelboards: Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant

P-2 D2P and EWP Factory Sealed Circuit Breaker Panelboards: Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant P-2 D2P and EWP Factory Sealed Circuit Breaker Panelboards: Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant Applications Protection and control of electrical equipment and circuits

More information

XP Series Pre-Wired Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof System

XP Series Pre-Wired Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof System NEC/ Applications Protection and control of electrical apparatus and circuits in hazardous environments, either indoor or outdoor. Designed for Class I, Division 2 areas where flammable gases or vapors

More information

DISTRIBUTION EQUIPMENT: NEC/CEC HAZARDOUS LOCATION SWITCHES. Application

DISTRIBUTION EQUIPMENT: NEC/CEC HAZARDOUS LOCATION SWITCHES. Application - and 3-Pole, Non-Interchangeable Trip. Bolted Enclosure Type. Class I, Division 1 and, Groups B, C, D Class II, Division 1 and, Groups E, F, G Application Explosionproof circuit breaker enclosures are

More information

NEC/CEC CLASS/ZONE RATED HAZARDOUS LOCATION CIRCUIT BREAKERS. Application

NEC/CEC CLASS/ZONE RATED HAZARDOUS LOCATION CIRCUIT BREAKERS. Application - and 3-Pole, Non-Interchangeable Trip. Bolted Enclosure Type. Class I, Division 1 and, Groups B, C, D Class II, Division 1 and, Groups E, F, G Distribution Equipment NEC/CEC CLASS/ZONE RATED HAZARDOUS

More information

Lighting and Power Distribution Panelboards

Lighting and Power Distribution Panelboards EXPLOSIONPROOf Lighting and Power Distribution Panelboards The design offers sufficient gutter space on sides to allow through wiring and easy lug connection. All enclosures are furnished with hinges,

More information

DBR Receptacle Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 9FG

DBR Receptacle Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 9FG EBR/DBR 30, 60, 100 and 150 Amp Series Receptacles With Disconnect Switch or Circuit Breaker. Weatherproof Spring Cover. Explosionproof, Dust-Ignitionproof 600 Vac Max. 250 Vdc Max. EBR Receptacle Class

More information

Division 1 Explosionproof Panelboards

Division 1 Explosionproof Panelboards Division 1 Explosionproof Panelboards Designed for use in Class 1, Division 1 Zone 1 areas such as petroleum refineries, chemical or petrochemical facilities, the X1Pb panelboards are used to control lighting

More information

PLUGS AND RECEPTACLES: NEC/CEC HAZARDOUS LOCATION

PLUGS AND RECEPTACLES: NEC/CEC HAZARDOUS LOCATION Explosionproof, Dust-Ignitionproof With Disconnect Switch or Circuit Breaker. Weatherproof Spring Cover. 600 Vac Max. 250 Vdc Max. Applications Locations where receptacles are used with stationary or portable

More information

NEC DBR Receptacle: Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 9FG

NEC DBR Receptacle: Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 9FG EBR/DBR 30, 60, 100 and 150 Amp Series Receptacles With Disconnect Switch or Circuit Breaker. Weatherproof Spring Cover. Explosionproof, Dust-Ignitionproof 600 Vac Max. 250 Vdc Max. NEC EBR Receptacle:

More information

X1PB: Explosionproof Panelboards

X1PB: Explosionproof Panelboards X1PB: Explosionproof FEATURES Spring-loaded through the door circuit breaker handles for 1P, 2P, and 3P breakers Padlock provision for breaker handles Copper bus bars Aluminum hinge with stainless steel

More information

PlexPower Factory Sealed Panelboard 15 to 150 Amps. Stainless Steel Enclosures

PlexPower Factory Sealed Panelboard 15 to 150 Amps. Stainless Steel Enclosures Applications The PlexPower panelboard provides indoor and outdoor protection and control of electrical circuits in hazardous environments such as: Petroleum plants Chemical plants Refineries Wastewater

More information

Standard Materials Bodies and covers: copper-free aluminum.

Standard Materials Bodies and covers: copper-free aluminum. -26 AEB Series: Bolted Combination and Non-Combination Full Voltage Motor Starters: Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection. Application Combination and

More information

CIRCUIT BREAKER PANELBOARDS

CIRCUIT BREAKER PANELBOARDS CIRCUIT BREAKER PANELBOARDS Class l, ones 1 & 2, Groups llb+h 2 Certified File LR 11713 for B7L FEATURES-SPECIFICATIONS Applications Hazardous locations due to the presence of flammable gases or vapors,

More information

PlexPower Fused Factory Sealed Panelboard with Bus Bar Up to 30 Amps. Stainless Steel Enclosures

PlexPower Fused Factory Sealed Panelboard with Bus Bar Up to 30 Amps. Stainless Steel Enclosures Applications The PlexPower panelboard provides indoor and outdoor protection and control of electrical circuits in hazardous environments such as: Petroleum plants Chemical plants Refineries Wastewater

More information

Product Description. Junction Boxes...V1-V23 Meter and Instrument Enclosures...V24-V33

Product Description. Junction Boxes...V1-V23 Meter and Instrument Enclosures...V24-V33 SECTION V INDEX Product Description Page Number Junction Boxes......................................V-V2 Meter and Instrument Enclosures.......................V24-V Control Centers.....................................V4-V9

More information

Applications. Housings: copperfree (4/10 of 1%) aluminum Shaft, bushings and exposed hardware: stainless steel Standard Finishes

Applications. Housings: copperfree (4/10 of 1%) aluminum Shaft, bushings and exposed hardware: stainless steel Standard Finishes AE Threaded Combination and Non-Combination Full Motor Starters Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection. Class I, Division and, Groups C, D Class II, Division

More information

Panelboard Protection on a Global Scale

Panelboard Protection on a Global Scale Panelboard Protection on a Global Scale Appleton Panelboards Brochure Selection guide. No matter what environment, location or power requirement, our panelboards have your facility covered. From a petrochemical

More information

FACTORY SEALED CIRCUIT BREAKER PANELBOARDS

FACTORY SEALED CIRCUIT BREAKER PANELBOARDS FACTORY SEALED CIRCUIT BREAKER BOARDS Applications Hazardous areas due to the potential of explosive gas atmospheres, combustible dusts or easily ignited fibers or flyings and areas subjected to corrosive

More information

D2LC Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments

D2LC Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments D2LC Series Circuit Breaker Panelboards for Harsh and Hazardous Environments IBUTI TR HA ON DIS KILLARK Z LO C Type 4X Gasket Stainless Steel Tri-Lead Cover Bolts Spare Sealed Wires Termination at Terminal

More information

U-Line Contender Factory Sealed 20 Amp Plugs and Receptacles Explosionproof, Dust-Ignitionproof

U-Line Contender Factory Sealed 20 Amp Plugs and Receptacles Explosionproof, Dust-Ignitionproof U-Line Contender Factory Sealed 20 Amp Plugs and Receptacles Explosionproof, Dust-Ignitionproof Class I, Groups C, D Class I, Division 2, Group B Class I, Zone 1, Group IIB Class I, Zone 2, Group IIB +

More information

ATX DPD Series Distribution Panelboards Flameproof

ATX DPD Series Distribution Panelboards Flameproof ATX DPD Series Distribution Panelboards Applications Protection and control of electrical equipment in hazardous areas where ignitable vapors, gases or highly combustible dusts are present. For installation

More information

PLUGS AND RECEPTACLES: NEC/CEC HAZARDOUS LOCATION

PLUGS AND RECEPTACLES: NEC/CEC HAZARDOUS LOCATION DBR 30, 60, 100 and 150 Amp Series Receptacles Explosionproof, Dust-Ignitionproof With Disconnect Switch or Circuit Breaker. Weatherproof Spring Cover. 600 Vac Max. 250 Vdc Max. Applications Locations

More information

EXBLI & EXBSPI Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments

EXBLI & EXBSPI Series. Circuit Breaker Panelboards for Harsh and Hazardous Environments EXBLI & EXBSPI Series Circuit Breaker Panelboards for Harsh and Hazardous Environments KILLARK Z A H LO C NEMA 4X O Ring Gasket Stainless Steel Tri-Lead Cover New Slide MCB Assembly Handles Padlockable

More information

Plugs and Receptacles: Hazardous Location

Plugs and Receptacles: Hazardous Location U-Line Factory Sealed 15 and 20 Amp Plugs and Receptacles V Plugs and Receptacles Plugs and Receptacles: Hazardous Location Applications Locations where receptacles are used with stationary or portable

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Standard Finishes Receptacles: epoxy powder coat Cord connector housings and caps: epoxy powder coat

Standard Finishes Receptacles: epoxy powder coat Cord connector housings and caps: epoxy powder coat U-Line Factory Sealed 15 and 20 Amp Plugs and Receptacles V Applications Locations where receptacles are used with stationary or portable electrically operated devices such as: Lighting systems Conveyors

More information

Spring-loaded cover seats against neoprene gasket.

Spring-loaded cover seats against neoprene gasket. U-Line Factory Sealed 20 Amp Plugs and Receptacles Dead-Front Safety Construction. Choice of Aluminum or Thermoplastic Polyester Plug. Class I, Division 1 and 2 Groups B, C, D NEMA 3, 3R, 7BCD, 9FG Plugs

More information

CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES. Applications. Illustrated Features

CONTROLS: NEC/CEC EXPLOSIONPROOF CONTROL STATIONS AND SWITCHES. Applications. Illustrated Features Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground. Applications Designed to prevent arcing of enclosed switches in ignitable atmospheres during connect and

More information

Receptacle housing and cover optional malleable iron on EFS-M Series. Spring-loaded cover seats against neoprene gasket.

Receptacle housing and cover optional malleable iron on EFS-M Series. Spring-loaded cover seats against neoprene gasket. U-Line Factory Sealed 20 Amp Plugs and Receptacles Dead-Front Safety Construction. Choice of Aluminum or Thermoplastic Polyester Plug. Class I, Division 1 and 2 Groups B, C, D NEMA 3, 3R, 7BCD, 9FG Applications

More information

Receptacle housing and cover optional malleable iron on EFS-M Series. Spring-loaded cover seats against neoprene gasket.

Receptacle housing and cover optional malleable iron on EFS-M Series. Spring-loaded cover seats against neoprene gasket. U-Line Factory Sealed 20 Amp Plugs and Receptacles Dead-Front Safety Construction. Choice of Aluminum or Thermoplastic Polyester Plug. Class I, Division 1 and 2 Groups B, C, D NEMA 3, 3R, 7BCD, 9FG Applications

More information

PLEXPOWER LIGHTING AND POWER PANELBOARDS PRODUCT GUIDE

PLEXPOWER LIGHTING AND POWER PANELBOARDS PRODUCT GUIDE PLEXPOWER LIGHTING AND POWER PANELBOARDS PRODUCT GUIDE EASY TO INSTALL, OPERATE AND MAINTAIN. PlexPower Panelboards use circuit breaker modules that provide explosionproof protection for standard off-the-shelf

More information

CIRCUIT BREAKERS. Explosionproof Circuit Breaker Enclosures EXPLOSIONPROOF MOTOR CONTROL EXPLOSIONPRROOF MOTOR CONTROL BREAKERS ENCLOSURES

CIRCUIT BREAKERS. Explosionproof Circuit Breaker Enclosures EXPLOSIONPROOF MOTOR CONTROL EXPLOSIONPRROOF MOTOR CONTROL BREAKERS ENCLOSURES CIRCUIT BREAKERS Explosionproof Circuit Breaker Enclosures BREAKERS Circuit breakers are thermal magnetic type and are available in frame sizes ranging from 15 to 800 amperes Also available as non-automatic

More information

EBMC Combination Line Starters and Enclosures

EBMC Combination Line Starters and Enclosures EBMC Combination Line 3, 3R, 4, 4X, 7BCD, 9EFG, 12 Applications: Spectrum EBM hinged cover motor control enclosures are used: For general motor control and circuit protection indoors and outdoors in damp,

More information

Circuit Breakers Hazardous

Circuit Breakers Hazardous s Hazardous 3C Description Page No. Application/Selection 364 Auxiliary s & s EFD, EFDC Series 382 Thermal Magnetic s & s General Information and Dimensions EPC Series 370, 371 FLB Series 375 EBMB Series

More information

EFS Non-Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw.

EFS Non-Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw. Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw. Applications Designed to prevent arcing of enclosed switches in ignitable atmospheres during connect

More information

P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE

P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE P SERIES POWERPLEX DISTRIBUTION PANELBOARDS SAFETY MADE SIMPLE A BREAKER PROTECTION BREAKTHROUGH Simplify flameproof protection for lighting, heat trace and power circuit distribution with the new generation

More information

Applications. Separate sealing chamber and switch construction. Used on 20 Amp 4-way and all 30 Amp models.

Applications. Separate sealing chamber and switch construction. Used on 20 Amp 4-way and all 30 Amp models. Contender Series Factory Sealed Front Operated Tumbler Switches Malleable Iron Body and Cover. Furnished with Internal Ground. NEMA 3, 7CD, 9EFG Applications Designed to prevent arcing of enclosed switches

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

POWERPLEX PANELBOARD 1

POWERPLEX PANELBOARD 1 1 POWERPLEX PANELBOARD 2 ADVANCING PANELBOARD TECHNOLOGY WITH COMPONENT LEVEL PROTECTION. Introducing the PowerPlex Panelboard. Appleton's PowerPlex Panelboard changes the face of hazardous location panelboards

More information

FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC.

FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC. FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC. : Conduit Bodies Applications Serve as pulling fittings. Make bends in conduit system. Provide

More information

Eylander Electric Inc

Eylander Electric Inc Eylander Electric Inc. 1-800-932-8986 To Order Call: 1-800-932-8986 ADVANTAGES OF THE MTS MANUAL TRANSFER 1. THE MOST VERSATILE Assembled from CUTLER-HAMMER CH and BR (old Challenger/Westinghouse), GENERAL

More information

EFS Non-Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw.

EFS Non-Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw. EFS Non-Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof Malleable Iron Body and Cover. Furnished with Internal Ground Screw. Controls CONTROLS: HAZARDOUS LOCATION CONTROL STATIONS AND SWITCHES

More information

FM9 Aluminum Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC.

FM9 Aluminum Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC. Applications Serve as pulling fittings. Make bends in conduit system. Provide openings for splicing. Connect and change direction of conduit runs. Allow connections for branch runs. Permit access to conductors

More information

Form 85 Unilets Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum, IMC, and EMT Conduit.

Form 85 Unilets Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum, IMC, and EMT Conduit. For use with Rigid Steel, Rigid Aluminum, IMC, and EMT Conduit. NEC/CEC Suitable for use in the following Applications Serve as pulling fittings. Make bends in conduit system. Provide openings for splicing.

More information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service No One Does It Like Mipco Mipco Interlocked Reefer Power Outlets are used extensively in port terminals and shipboard applications to provide a safe, watertight electrical connection for refrigerated containers.

More information

O-3. Compliances UL Classified UL 508, 698, 1203 NEMA 4, 4X, 7CD, 9EFG For CSA approvals, please consult factory.

O-3. Compliances UL Classified UL 508, 698, 1203 NEMA 4, 4X, 7CD, 9EFG For CSA approvals, please consult factory. Combination and Non-Combination Full Voltage Motor Starters: Units Provide Disconnecting Means and Undervoltage, Circuit and Motor Running Protection. -3 Applications AE series threaded type combination

More information

Hazardous Factory Sealed Control Devices

Hazardous Factory Sealed Control Devices Hazardous Factory Sealed Control Devices Description Page No. Application/Selection 428, 429 Dimensions 40 Manual Motor Starting Switches & Enclosures EDS Series 440, 44 Pilot Lights EFS Series 45 Pilot

More information

P-2 ccsaus, curus Class I Div. 2 Group B,C, D Class I Zone 1 AEx de IIB+H 2 T6 Ex d IIB+H 2 T6 U Type 4X, IP66

P-2 ccsaus, curus Class I Div. 2 Group B,C, D Class I Zone 1 AEx de IIB+H 2 T6 Ex d IIB+H 2 T6 U Type 4X, IP66 -2 ccsaus, curus Class I Div. 2 Group B,C, D Class I Zone 1 AEx de IIB+H 2 T6 Ex d IIB+H 2 T6 U Type 4X, I66 owerlex anelboards: Steel Enclosures Applications The owerlex anelboard provides indoor and

More information

Lighting Panelboards EPLU and D2LU Series IF Installation & Maintenance Information APPLICATION

Lighting Panelboards EPLU and D2LU Series IF Installation & Maintenance Information APPLICATION Lighting Panelboards EPLU and D2LU Series Installation & Maintenance Information APPLICATION EPLU and D2LU Series panelboards provide a centrally controlled switching system and short circuit protection

More information

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Applications Designed to supply power to portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors,

More information

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures

Enclosures for hazardous areas EBMX clamped enclosures. Clamped EBMX. NEMA 7 classifi ed enclosures Enclosures for hazardous areas clamped enclosures Clamped NEMA 7 classifi ed enclosures Clamped : NEMA 7 classified enclosures Safer. Faster. Easy access, lower risk and less downtime. Creative thinking

More information

6.2. Power Pedestals. Contents

6.2. Power Pedestals. Contents Power Pedestals.2 Power Outlet Panels Contents Description Page Product Overview................................. 287 Application Description.......................... 288 Features and Benefits...........................

More information

PANELBOARDS C1/C2 SECTION 6

PANELBOARDS C1/C2 SECTION 6 SECTION 6 C1/C2 PANELBOARDS Page General Specifications 6-2 Box Sizing 6-2 Gauge Steel Boxes 6-2 Fronts 6-2 Main Breaker Connectors 6-2 Main Lug Connectors 6-2 Selection 6-3 6-5 Main Lugs Only C1 and C2

More information

1E EJB Junction Boxes Cl. I, Div. 1 and 2, Groups B, C, D

1E EJB Junction Boxes Cl. I, Div. 1 and 2, Groups B, C, D Cl. I, Div. and 2, Groups B, C, D Cl. II, Div., Groups E, F, G Cl. II, Div. 2, Groups F, G Cl. III NEMA 3, 4, 4*,, Ex d IIB + H2 T, IP Explosionproof Dust-Ignitionproof Raintight Wet Locations Applications:

More information

EDS Factory Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof UNILETS for Use with Threaded Metal Conduit.

EDS Factory Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof UNILETS for Use with Threaded Metal Conduit. EDS Factory Sealed Tumbler Switches UNILETS for Use with Threaded Metal Conduit. Class I, Division 1 and 2, Groups B, C, D NEMA 7 B CD, 9EFG Applications Designed to prevent arcing of enclosed switches

More information

Power distribution SynergEX panelboards. SynergEX. Class I, Division 2 panelboards

Power distribution SynergEX panelboards. SynergEX. Class I, Division 2 panelboards Power distribution SynergEX panelboards SynergEX Class I, Division 2 panelboards SynergEX panelboards for hazardous rated areas Maximum safety. Easy access, lower risk and less downtime. One of the biggest

More information

T38 1" T Form 7 Malleable Iron Conduit Body. Material, Color, and Finish Color Gray 0 Zinc Electroplate/Chromate/Epoxy Powder Coat

T38 1 T Form 7 Malleable Iron Conduit Body. Material, Color, and Finish Color Gray 0 Zinc Electroplate/Chromate/Epoxy Powder Coat 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 T38 1" T Form 7 Malleable Iron Conduit Body Appleton/Oz Gedney Catalog Number Manufacturer Description Weight per unit

More information

5.2. Power Pedestals. Contents Description

5.2. Power Pedestals. Contents Description .2 Power Outlet Panels Contents Description Product Overview......................... Application Description.................. Features and Benefits................... Standards and Certifications..............

More information

EDS Factory Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof UNILETS for Use with Threaded Metal Conduit.

EDS Factory Sealed Tumbler Switches Explosionproof, Dust-Ignitionproof UNILETS for Use with Threaded Metal Conduit. UNILETS for Use with Threaded Metal Conduit. Class I, Division 1 and 2, Groups B, C, D Applications Designed to prevent arcing of enclosed switches in ignitable atmospheres during connect and disconnect

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

FM8 Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC Conduit.

FM8 Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC Conduit. NEC/CEC Suitable for use in the following Applications Serve as pulling fittings. Make bends in conduit system. Provide openings for splicing. Connect and change direction of conduit runs. Allow connections

More information

Dry-Type Transformers Mini-Power Centers

Dry-Type Transformers Mini-Power Centers Dry-Type Transformers Mini-Power Centers Product Focus Three individual components combined into a single unit to save space and costs, 3 to 30 kva Dry-Type Transformers Mini-Power Centers Significant

More information

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY EDSC210 -Way Switch Cooper Crouse-Hinds Catalog Number Manufacturer Description Weight per unit Product Category Features Box Type Contact Configuration Current Rating Voltage Rating Material, Color, and

More information

EOEM panelboard and switchboard (OPS) Program

EOEM panelboard and switchboard (OPS) Program Instructional Leaflet IL02009EN EOEM panelboard and switchboard (OPS) Program OPS Program overview The OPS Program enables EOEMs to purchase panelboard/switchboard chassis, boxes, trims, molded-case circuit

More information

Product Information. Receptacles and Plugs: Explosionproof For use with Threaded Metal Conduit. MD2SR Interlocked Switched Receptacle

Product Information. Receptacles and Plugs: Explosionproof For use with Threaded Metal Conduit. MD2SR Interlocked Switched Receptacle L02-L12 01 Receptacles and Plugs: Explosionproof For use with Threaded Metal Conduit. Applications Locations where receptacle is used with stationary or portable electrically operated devices such as lighting

More information

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Applications Designed to supply power to portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors, cellular relay stations, and similar apparatus. Ideal for use

More information

Hazardous Duty Applications

Hazardous Duty Applications Hazardous Location Hazardous Duty Plugs, Receptacles and Interlocks Hazardous Duty Plugs, Receptacles and Interlocks Hazardous Duty Applications Russellstoll Hazardous Duty Plugs, Receptacles and Interlocks

More information

Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box

Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box 1 TECHNICAL DATA SHEET Explosionproof enclosures XPCJ series Cast aluminum steel control/junction box XPCJ series series of explosionproof aluminum enclosures are typically used in the packaging of electrical/electronic

More information

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Applications Designed to supply power to portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors, cellular relay stations, and similar apparatus. Ideal for use

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

Laser Service Factory-assembled Panelboards

Laser Service Factory-assembled Panelboards Factory-assembled Panelboards Price List 1600PL0701 2009 Class 1600 CONTENTS Description............................................. Page Product Overview........................................ Page

More information

CH215AFIT 2P 15A Arc Fault Shared Neutral/Indpndt Trip BRKR. Features. Dimensions and Weight. Descriptions. Manufacturer Information

CH215AFIT 2P 15A Arc Fault Shared Neutral/Indpndt Trip BRKR. Features. Dimensions and Weight. Descriptions. Manufacturer Information Manufacturer Description Weight per unit Product Category CH2AFIT 2P A Arc Fault Shared /Indpndt Trip BRKR Eaton Corp Features Current Rating AMPERE Interrupting Rating 10 KILOAMPERE Poles 2 Terminal Type

More information

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC

Explosion Proof Receptacle - Integral Circuit Breaker - Class 2 Division 1-30 Amp 480VAC 9419 E US HWY 175, Kemp, TX 75143 Phone: 1 8003696671 Fax: 903.498.3364 Email: sales@larsonelectronics.com Explosion Proof Receptacle Integral Circuit Breaker Class 2 Division 1 30 Amp 480VAC Part #: EPO3W4P30AICB

More information

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Applications Designed to supply power to portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors, cellular relay stations, and similar apparatus. Ideal for use

More information

Industrial Control & Circuit Breakers

Industrial Control & Circuit Breakers Industrial Control & Circuit Breakers Section C Innovative, intelligent NEC and IEC solutions safely and efficiently control power and protect circuits in explosive, wet, and corrosive environments worldwide.

More information

LB125A 1-1/4" LB Form 5 Aluminum Conduit Body. Dimensions and Weight STUD SIZE #10; 0.97 INCH LENGTH; INSULATION SUPPORT

LB125A 1-1/4 LB Form 5 Aluminum Conduit Body. Dimensions and Weight STUD SIZE #10; 0.97 INCH LENGTH; INSULATION SUPPORT 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 LB125A 1-1/4" LB Form 5 Aluminum Conduit Body Appleton/Oz Gedney Catalog Number Manufacturer Description Weight per unit

More information

Contents. Volume 1 Residential and Light Commercial CA E December

Contents. Volume 1 Residential and Light Commercial CA E December Power Pedestals.2 Power Outlet Panels Contents Description Page Product Overview................................. 287 Application Description.......................... 288 Features and Benefits...........................

More information

Contender Series Factory Sealed Control Stations and Pilot Lights Explosionproof, Dust-Ignitionproof Furnished with Internal Ground Screw.

Contender Series Factory Sealed Control Stations and Pilot Lights Explosionproof, Dust-Ignitionproof Furnished with Internal Ground Screw. Contender Series Factory Sealed Control Stations and Pilot Lights Furnished with Internal Ground Screw. Applications Push buttons and selector switches are used in conjunction with contactors or magnetic

More information

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION MPH66125 with Horn Bypass Square D brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications: UL Listed

More information

AE Series Pin and Sleeve Plugs, Connectors and Receptacles Weatherproof 600 Vac, 250 Vdc. Pressure Wire Terminals.

AE Series Pin and Sleeve Plugs, Connectors and Receptacles Weatherproof 600 Vac, 250 Vdc. Pressure Wire Terminals. AE Series Pin and Sleeve Plugs, Connectors and Receptacles 600 Vac, 250 Vdc. Pressure Wire Terminals. Applications Designed to supply power to portable or fixed electrical equipment such as: Welders Generators

More information

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles

Powertite Series Pin and Sleeve Plugs, Connectors and Receptacles Applications Designed to supply power to portable or fixed electrical equipment such as motor generator units, welders, pumps, compressors, cellular relay stations, and similar apparatus. Ideal for use

More information

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com J QMB Panel boards Switchboards 200,000A. short circuit rating QMB Fusible Switches Throughout our complete line of 30-SOOA. ULiisted QMB fusible switches, we've combined timeproven Square D safety switches

More information

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers

MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION. MP Meter-Pak Meter Centers Product Description PRODUCT DESCRIPTION MPH66125 with Horn Bypass Square D brand MP Meter-Pak meter centers from Schneider Electric offer a wide range of solutions for multi-metering applications: UL Listed

More information

RCS1000 Data Sheet. RCS1000 Series Controllable Circuit Breaker Panel

RCS1000 Data Sheet. RCS1000 Series Controllable Circuit Breaker Panel RCS000 Series Controllable Circuit Breaker Panel RCS000 Data Sheet Overview The RCS000 Series Controllable Circuit Breaker Panels combines the benefi ts of traditional relay based load control and the

More information

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English. -174 Series C Molded Case Circuit s July 7 Molded Case Switches Refer to Eaton for UL listed, series tested Molded Case Switch application data. Table -278. Molded Case Switches Cont. Amp Rating at 40

More information

Engine Generator Circuit Breakers

Engine Generator Circuit Breakers Engine Generator Circuit Breakers Product Description............................................. 2 Application Description........................................... 2 Standards and Certifications......................................

More information

Aluminum Conduit Bodies, Covers and Gaskets For Rigid Conduit & IMC.

Aluminum Conduit Bodies, Covers and Gaskets For Rigid Conduit & IMC. NEC/CEC Suitable for use in the following Applications To provide access to conductors for pulling, splicing, maintenance and future changes/upgrades. Allows connection of straight conduit runs, branch

More information

1E EJB Junction Boxes Cl. I, Div. 1 and 2, Groups B, C, D

1E EJB Junction Boxes Cl. I, Div. 1 and 2, Groups B, C, D EJB Junction Boxes Cl. I, Div. and 2, Groups B, C, D Cl. II, Div., Groups E, F, G Cl. II, Div. 2, Groups F, G Cl. III NEMA 3, 4, 4X*,, Ex d IIB + H2 T6, IP66 Explosionproof Dust-Ignitionproof Raintight

More information

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY EDS2274 Pos D.E. Selector Switch Cooper Crouse-Hinds Catalog Number Manufacturer Description Weight per unit Product Category Features Box Type SINGLE GANG Contact Configuration 4NO-4NC Number of Circuits

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description

Panelboards and Lighting Control. Types PRL1a, 2a, 3a, 3E, 4 and Column Modifications. Contents Description .5 Types PRL1a, 2a, a, E, 4 and Column Modifications s Types PRL1a, 2a, a, E, 4, Column Modifications Selection Guide Modifications Alphabetical Index Modification Item Contents Types PRL1a, 2a, a, E,

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not

More information

Benefits. Safety. Durability. Performance. Russellstoll. Heavy Industrial/ Marine

Benefits. Safety. Durability. Performance. Russellstoll. Heavy Industrial/ Marine eavy Industrial/ Marine Benefits builds a variety of benefits into one plug, receptacle and interlock system for your application. Safety Waterproof construction: standard neoprene O ringed interior components

More information

Panelboards Circuit Breaker / Lighting and Distribution

Panelboards Circuit Breaker / Lighting and Distribution Circuit Breaker / Lighting and Distribution 480Y/277 Vac Maximum 600Y/ 347 Vac (CSA only) Maximum 400 Ampere Mains 400 Ampere Maximum Branch UL Short Circuit Rating 200,000 A. @ 240 Vac / 100,000 A. @

More information

PowerPact B. Molded case circuit breakers and switches from A

PowerPact B. Molded case circuit breakers and switches from A PowerPact B Molded case circuit breakers and switches from 15-125 A 2 schneider-electric.us Efficiency that clicks. PowerPact B molded case circuit breakers Schneider Electric introduces a new family member

More information

EPOXY POWDER COATED COPPER FREE ALUMINUM

EPOXY POWDER COATED COPPER FREE ALUMINUM 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 AJA510 Alum MTG Unilet Appleton/Oz Gedney Catalog Number Manufacturer Description Weight per unit Product Category Features

More information