1 CR circuit breaker - hydraulic magnetic, Datasheet railway, compact Features Precise, temperature independent operation Panel mount Integrated auxiliary contacts (optional) Up to 6 poles configuration High interrupting capacities due to unique arc chute method Mid-trip handle for electrical trip indication (optional) Immediate resetting possible Wide current range: A Wide choice of time delays Maximum voltage 37.5 VDC / 484 VAC High contact pressure & longer contact life due to wiping self-cleaning contacts Flexibility by many options Benefits Description Compact hydraulic magnetic circuit breaker for railway applications to protect electronic equipment and components against unintended high currents. ptional with integrated auxiliary contacts to monitor the circuit. The trip point is always at maximum allowable current, independent of ambient temperature. Mid-trip handle to indicate clearly a breaker operation caused by electrical fault. With unique arc chute design which results in high interrupting capacities. Up to 6 poles which all break its electronic circuits when breaker trips, for optimal protection of the system. Wide range of currents and options available. Application To be used in every application where electrical systems, circuits or components must be protected against too high currents. This situation can occur, when under strained or heavy use a motor or other load-generating component within the equipment will draw additional current from the power source. High currents cause the wires or components to overheat and ultimately burn up. A circuit protection device should be employed at any point where a conductor size changes. Many electronic circuits and components like transformers have a lower overload withstand threshold level than conductors such as wires and cables. These components require circuit protection devices featuring very fast overload sensing and opening capabilities. The CR-Series circuit breaker can be used in all Railway applications where protection against overload and short circuit is necessary, for example HVAC systems, (door) control systems, braking systems, passenger information systems, etc. DS-CR circuit breaker V4.7 February 207 Proven reliable Long term availability Low lifecycle cost No maintenance Railway compliancy All our circuit breakers are designed according: IEC /2/3/4 NF F /2/3 NF F6-0/02 EN EN 5055 EN 6373 EN IEC IEC NF F6-00 MIL Method 07D, condition A MIL-STD-202G, Method 204C

2 Technical specifications Electrical characteristics Application voltage Rated voltage Min. operating voltage Max. operating voltage Current ratings Voltage coils Dielectric strength Creepage and clearance Insulation resistance perating frequency DC for -6 poles 2-0 VDC 8.4 VDC 37.5 VDC Remark: VDC: max 00 A VDC: max 70 A AC for pole VAC 0.8 VAC 253 VAC A. ther ratings on request. 6 VDC - 65 VDC / 6 VAC VAC. ther ratings on request. AC for 2-6 poles VAC 0.8 VAC 484 VAC 5000 VAC, 50/60 Hz for minute between all electrically isolated terminals. EN mm spacing requirements from hazardous voltage to operator accessible surfaces, between adjacent poles and from main circuits to auxiliary circuits. Minimum of VDC 50/60 Hz, DC Max. interrupting capacity UL 489 IEC IEC IEC IEC IEC IEC IEC IEC IEC IEC Auxiliary switch VDC, - 00 A VDC, - 70 A VDC, A VDC, - 60 A VAC, - 70 A VAC, 7-00 A VAC, A VAC, - 30 A VAC, 3-70 A VAC, - 60 A VAC, 6-00 A Integrated, load side. SPST. Auxiliary switch senses the on-off position of circuit breaker handle, as well as the open-closed position of breaker contact. AC min. switching capacity Silver auxiliary contacts 5-20 VAC: 00 ma > 20 VAC: 0 ma Gold auxiliary contacts 5 ma / 5 VAC AC max. switching capacity 5 A / 25 VAC 00 ma / 25 VAC DC min switching capacity DC max. switching capacity All loads mentioned are resistive loads. < 20 VDC: 00 ma > 20 VDC: 0 ma 3 A / 32 VDC 00 ma / 25 VDC (max cycles) 5 ma / 5 VDC 00 ma / 32 VDC 2 ma / 0 VDC (max cycles) 2 DS-CR circuit breaker V4.7 February 207

3 Technical specifications General characteristics Number of poles, 2, 3, 4, 5 or 6 poles For DC and AC applications: -2 poles 00 A 3-6 poles 70 A Terminals Auxiliary contacts Mounting Body Actuator handle Int. circuit configuration Weight (average, depending on configuration) Stud / screw / double faston, see circuit & terminal diagrams Faston or solder type, see circuit & terminal diagrams The hydraulic-magnetic circuit breakers of Mors Smitt can be mounted in any position. A hydraulic-magnetic breaker is designed to must hold at 00% of the breaker s current rating and is calibrated to must trip at 25% of the breaker s current rating. If the mounting position is +90 degrees from a vertical panel mount (handle facing down, ceiling mount position) the trip and must hold rating is reduced by 0%. Blue colour Several colours with I and n-off legends Series trip, shunt trip, relay trip & switch only -pole without aux. contact 2-pole without aux. contact 3-pole without aux. contact 4-pole without aux. contact 5-pole without aux. contact 6-pole without aux. contact 0 g 202 g 303 g 404 g 505 g 606 g Width per pole -pole with aux. contact 2-pole with aux. contact 3-pole with aux. contact 4-pole with aux. contact 5-pole with aux. contact 6-pole with aux. contact 9.2 mm Material Half shell - BMC 605 Handle - Valox 420SE UL94V0 Terminals - Brass with acid tin plate 04 g 205 g 306 g 407 g 508 g 609 g DS-CR circuit breaker V4.7 February 207 3

4 Technical specifications Mechanical characteristics Endurance Trip free mechanism Trip indication: Standard (no mid-trip) Mid-trip Mid-trip with alarm switch N- 6 per minute without current & voltage and N- operations with rated current & voltage. Trips on short-circuit or on overload, even when the actuator is forcibly held in the N position. When manually moving the operating handle from to N position, an auxiliary switch is actuated. When an overload or a short circuit causes the circuit breaker to trip, the operating handle moves positively to the position and the auxiliary switch is actuated. When manually moving the operating handle from to N position, an auxiliary switch is actuated. When an overload or a short circuit causes the circuit breaker to trip, the operating handle moves positively to the mid position and the auxiliary switch is actuated. When manually moving the operating handle from to N position, an auxiliary switch is not actuated. When an overload or a short circuit causes the circuit breaker to trip, the operating handle moves positively to the mid position and the auxiliary switch is actuated. In this case the auxiliary switch is only actuated by an electrical trip, not by manually operating the handle. Remark: It is possible to manually switch the circuit breaker to the mid-trip position when the handle is switched from to N position quickly and with strong upwards force. Normally this won t occur in standard use. This is a normal phenomenon related to the design of the product. Environmental characteristics Environmental Complies to EN and IEC perating temperature -50 C C Vibration Shock Thermal shock IEC 6373, Category, class B body mounted IEC 6373, Category, class A & B body mounted Complies to MIL-07 D method, condition A Salt mist Complies to IEC severity level 3 Damp heat Complies to IEC test method Db variant Fire & smoke Complies to NFF 60, NFF 602, EN Protection Moisture resistance / humidity IEC 60529, IP40 when a panel is mounted over the circuit breaker; when no panel is mounted IP20 Complies to MIL-STD 202G method 4 DS-CR circuit breaker V4.7 February 207

5 Technical specifications Resistance, impedance Resistance, impedance values from Line to Load terminals (Values based on series trip circuit breaker) Current (amps) Tolerance (%) % + 25 % + 35 % hms Ampere rating Inrush pulse tolerance (00 (00 DS-CR circuit breaker V4.7 February 207 5

6 Technical specifications Table of time delay values Notes: Delay curves, 2, 4, 6, 2, 22, 24, 26, 42, 44, 46, 52, 54, 56: Breakers to hold 00% and must trip at 25% of rated current and greater within the time limit shown in this curve. Delay curves 0, 20: Breakers to hold 00% and must trip at 50% of rated current and greater within the time limit shown in this curve. All curves: Curve data shown represents breaker response at ambient temperature of 25 C (77 F) with no preloading. Breakers are mounted in standard wall-mount position. Delay times may vary at different temperature, the trip current rating remains unchanged. n 50 amp and less current ratings, the minimum inrush pulse tolerance handling capability is 2 times the rated current on standard delays and 25 times the rated current on high inrush delays. These values are based on a 60 Hz /2 cycle, 8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration such as switching power supplies, highly capacitive loads and transformer loads. 6 DS-CR circuit breaker V4.7 February 207

7 Time delay values AC Instantaneous Medium /60 Hz INSTANTANEUS CURVE N /60 Hz MEDIUM DELAY CURVE N. 24 TRIP TIME IN SECNDS TRIP TIME IN SECNDS PERCENT F RATED CURRENT PERCENT F RATED CURRENT 50 Ultrashort Long /60 Hz ULTRASHRT DELAY CURVE N /60 Hz LNG DELAY CURVE N. 26 TRIP TIME IN SECNDS TRIP TIME IN SECNDS PERCENT F RATED CURRENT PERCENT F RATED CURRENT 50 Short /60 Hz SHRT DELAY CURVE N. 22 TRIP TIME IN SECNDS PERCENT F RATED CURRENT 50 DS-CR circuit breaker V4.7 February 207 7

8 Time delay values High inrush AC Short /60 Hz - HI-INRUSH SHRT DELAY CURVE N. 42 TRIP TIME IN SECNDS PERCENT F RATED CURRENT Medium /60 Hz - HI-INRUSH MEDIUM DELAY CURVE N TRIP TIME IN SECNDS PERCENT F RATED CURRENT Long /60 Hz - HI-INRUSH LNG DELAY CURVE N TRIP TIME IN SECNDS PERCENT F RATED CURRENT 8 DS-CR circuit breaker V4.7 February 207

9 Time delay values DC Instantaneous Medium D.C. INSTANTANEUS CURVE N D.C. MEDIUM DELAY CURVE N. 4 TRIP TIME IN SECNDS TRIP TIME IN SECNDS PERCENT F RATED CURRENT 50 PERCENT F RATED CURRENT Ultrashort Long D.C. ULTRASHRT DELAY CURVE N D.C. LNG DELAY CURVE N. 6 TRIP TIME IN SECNDS TRIP TIME IN SECNDS PERCENT F RATED CURRENT PERCENT F RATED CURRENT Short D.C. SHRT DELAY CURVE N TRIP TIME IN SECNDS PERCENT F RATED CURRENT 50 DS-CR circuit breaker V4.7 February 207 9

10 Time delay values High Inrush DC Short D.C. - HI - INRUSH SHRT DELAY CURVE N TRIP TIME IN SECNDS PERCENT F RATED CURRENT Medium D.C. - HI - INRUSH MEDIUM DELAY CURVE N. 54 TRIP TIME IN SECNDS PERCENT F RATED CURRENT Long D.C. - HI - INRUSH LNG DELAY CURVE N. 56 TRIP TIME IN SECNDS PERCENT F RATED CURRENT 0 DS-CR circuit breaker V4.7 February 207

11 Circuit & terminal diagrams ±.05 ± [3.80] Notes. All dimensions are in inches [millimeters] 2. Tolerance on stud lengths is ±.03 [±.79] unless otherwise specified DS-CR circuit breaker V4.7 February 207

12 Circuit & terminal diagrams Terminal hardware Description Code Ampere rating Hardware supplied #0-32 stud Flat washer - Lockwasher - Nut M5 stud Flat washer - Lockwasher - Nut #/4-20 stud 3 M6 stud Flat washer - Lockwasher - Nut 8-00 Lockwasher - Nut - (2) Flat washer - Lockwasher - Nut Flat washer - Lockwasher - Nut 8-00 Lockwasher - Nut - (2) Flat washer - Lockwasher - Nut #0-32 / M5 2 & Flat washer - Lockwasher - Screw M5 stud R M6 stud S SS flat washer per NFR Trepp or CS NFE 25 5 springwasher - self-locking nut per NFE 25 4 SS flat washer per NFR Trepp or CS NFE 25 5 springwasher - self-locking nut per NFE Notes. All dimensions are in inches [millimeters] 2. Tolerance ±.020 [.5] unless otherwise specified. 3. Available on Series Trip and Switch nly Circuits when called for on multi-pole units. nly one aux. switch is normally supplied as viewed in multi-pole identification scheme. (ordering scheme box 0 codes, A, 2, F, 6, 7) Smaller terminal barriers available upon request 2 DS-CR circuit breaker V4.7 February 207

13 Form & fit drawings 9 A B 9 A B max..0 Nm max. 2.3 Nm Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.5 [0.38] unless otherwise specified 3 Schematic shown represents current trip circuits max. 2.3 Nm max. 4.0 Nm DS-CR circuit breaker V4.7 February 207 3

14 Form & fit drawings pole configuration ±.060 ± [65.35] TYP # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE TYPICAL-PTINAL "N-F, I-" LEGEND N I.25 [28.58].406 [0.3].850 [47.00] TYP.438 [36.53] [63.50] 30 ±.020 ± [49.28] LAD.755 [9.8] MAX..540 [3.72].50 [3.8] ±.020 ±.5.28 [7.4] TYP.35 [3.42] (SHRT HANDLE) #0-32 THREADED STUD TERMINALS INSERIES TRIP CIRCUIT CNFIGURATIN SHWN. FR THER CNFIGURATINS, SEE CIRCUIT AND TERMINAL DIAGRAMS. ±.060 ± [65.35] TYP # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE TYPICAL-PTINAL N-, "N-F, I-" I- LEGEND N I.406 [0.3].760[9.03].760[9.03] [9.30].25 [28.58] [47.00] DIA. TYP [Ø3.96].56 DIA. [Ø3.96] 2PLC'S. 2PLC'S. PER PLE PER PLE -PLE.438 [36.53] [36.78].448 [36.78] [63.50] ±.020 ± [49.28] LAD.755 [9.8] MAX..432 [0.97].432 [0.97].50 [3.8].540 [3.72].35 [3.42] (SHRT HANDLE) PANEL CUTUT DETAIL TLERANCES ±.005 [.2] ±.020 ±.5.28 [7.4] TYP #0-32 THREADED STUD TERMINALS INSERIES CNFIGURATIN SHWN. FR THER CNFIG SEE CIRCUIT AND TERMINAL DIAGRAMS. Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified 4 DS-CR circuit breaker V4.7 February 207

15 Form & fit drawings 2 pole configuration 2-PLE (ACTUATR CDE A) 2-PLE (ACTUATR CDE A) MULTI-PLE UNITS ARE ASSEMBLED AT FACTRY WITH MULTI-PLE CMMN HANDLE UNITS TIE. ARE ASSEMBLED AT FACTRY WITH CMMN HANDLE TIE. N I N I [3.72].406 [0.3].25 [28.58].406 [0.3].25 [28.58] 30 ±.060 ± [65.35] TYP.850 ±.060 [47.00] ±.52 TYP [65.35] TYP.850 [47.00] TYP.50 [3.8] LAD LAD TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) ±.020 ± [63.50] ±.020 ± [49.28] TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) LAD LAD PLE C N C N NC NC PLE 2.55 [38.48] MAX..55 [38.48] MAX..750 [9.05].750 [9.05].35 [3.42] (SHRT.540 [3.72] HANDLE).35 [3.42] (SHRT HANDLE).50 [3.8] ±.020 ±.5.28 [7.4] TYP PLE PLE 2 #0-32 THREADED STUD TERMINALS IN SERIES TRIP CIRCUIT CNFIGURATIN SHWN. FR THER CNFIGURATINS, SEE CIRCUIT AND TERMINAL DIAGRAMS [78.23] [78.23].980 [24.89] TYP 2-PLE (ACTUATR CDE B) 2-PLE (ACTUATR CDE B).940 [49.28] [99.06].55 [38.48] MAX. LAD.55 [38.48] MAX..850 [47.00].520[38.6] BARRIER FR MULTI-PLE BREAKERS Barrier with other dimensions on request..520[38.6].56 DIA. [Ø3.96] 2PLC'S. PER PLE.56 DIA. [Ø3.96] 2PLC'S. PER PLE.448 [36.78].448 [36.78] Notes.432 [0.97].432 [0.97].750 [9.05] PANEL CUTUT DETAIL.750 [9.05] TLERANCES ±.005 [.2] PANEL CUTUT DETAIL TLERANCES ±.005 [.2] All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified DS-CR circuit breaker V4.7 February 207 5

16 Form & fit drawings 3 pole configuration # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE # 6-32 [M3] THREADED x.95 TYPICAL-PTINAL [4.95] DEEP (2 PLC'S.) /PLE "N-F, I-" LEGEND TYPICAL-PTINAL "N-F, I-" LEGEND.438 [36.53] 3-PLE (ACTUATR CDE A).438 [36.53] 3-PLE (ACTUATR CDE A) N I [28.58] 30 N I [3.72] ±.060 ± [65.35] TYP.406 [0.3].850 [47.00] TYP ±.060 ± [65.35] TYP.25 [28.58].406 [0.3].850 [47.00] TYP LAD.50 [3.8] ±.020 LAD ± [49.28] TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) ±.020 ± [63.50].940 [49.28] ±.020 ±.5.28 [7.4] TYP LAD TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) [63.50] LAD C N NC PLE C N NC PLE [9.05].755 [9.8] MAX..540 [3.72].35 [3.42].50 [3.8] (SHRT HANDLE) ±.020 ±.5.28 [7.4] TYP PLE PLE 2 PLE [57.53] MAX..750 [9.05].755 [9.8] MAX [57.53] MAX..35 [3.42] (SHRT HANDLE) #0-32 THREADED STUD TERMINALS IN SERIES TRIP CIRCUIT CNFIGURATIN SHWN. FR THER CNFIGURATINS, SEE CIRCUIT AND TERMINAL DIAGRAMS [78.23].980 [24.89] TYP [78.23].980 [24.89] TYP 3-PLE (ACTUATR CDE B) 3-PLE (ACTUATR CDE B).940 [49.28] [99.06] [57.53] MAX [57.53] MAX. LAD.850 [47.00] 2.280[57.9] 2.280[57.9].56 DIA. [Ø3.96] 2PLC'S. PER PLE BARRIER FR MULTI-PLE BREAKERS Barrier with other dimensions on request..56 DIA. [Ø3.96] 2PLC'S. PER PLE.448 [36.78].448 [36.78].432 [0.97].432 [0.97] PANEL CUTUT DETAIL TLERANCES ±.005 [.2] PANEL CUTUT DETAIL.750 [9.05] TLERANCES ±.005 [.2].750 [9.05] Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified 6 DS-CR circuit breaker V4.7 February 207

17 Form & fit drawings 4 pole configuration 4-PLE (ACTUATR CDE A) 4-PLE (ACTUATR CDE A) # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE TYPICAL-PTINAL "N-F, I-" LEGEND # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE.438 [36.53] TYPICAL-PTINAL "N-F, I-" LEGEND.438 [36.53] N I [28.58] 30 N I.406 [0.3] [28.58] [3.72].406 [0.3] ±.060 ± [65.35] TYP.850 [47.00] TYP ±.060 ± [65.35] TYP.850 [47.00] TYP.50 [3.8] ±.020 ± [49.28] TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) [63.50] ±.020 ± [49.28] LAD [63.50] ±.020 ±.5.28 [7.4] TYP TYPICAL TERMINAL BARRIER (PTINAL SEE FIELD 0) LAD PLE C N NC PLE 3 P.750 [9.05].755 [9.8] MAX..35 [3.42] (SHRT HANDLE) LAD LAD 3.05 [76.58] MAX..540 [3.72].50 [3.8] ±.020 ±.5.28 [7.4] TYP PLE PLE 2 PLE 3 PLE [9.05] 3.05 [76.58] MAX..755 [9.8] MAX..35 [3.42] (SHRT HANDLE) #0-32 THREADED STUD TERMINALS IN SERIES TRIP CIRCUIT CNFIGURATIN SHWN. FR THER CNFIGURATINS, SEE CIRCUIT AND TERMINAL DIAGRAMS [78.23].980 [24.89] TYP [78.23].980 [24.89] TYP 4-PLE (ACTUATR CDE B) 4-PLE (ACTUATR CDE B) 3.05 [76.58] MAX..940 [49.28] [99.06] 3.05 [76.58] MAX. LAD [77.22].56 DIA. [Ø3.96] 2PLC'S. PER PLE.850 [47.00] BARRIER FR MULTI-PLE BREAKERS Barrier with other dimensions on request [77.22].448 [36.78].56 DIA. [Ø3.96] 2PLC'S. PER PLE.448 [36.78].432 [0.97].432 [0.97] PANEL CUTUT DETAIL TLERANCES ±.005 [.2] PANEL CUTUT DETAIL TLERANCES ±.005 [.2].750 [9.05].750 [9.05] Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified DS-CR circuit breaker V4.7 February 207 7

18 Form & fit drawings Short handle option N I.25 [28.58].406 [0.3].850 [47.00] TYP F F.438 [36.53] [9.8] MAX. # 6-32 [M3] THREADED x.95 [4.95] DEEP (2 PLC'S.) /PLE.35 [3.42].50 [3.8] Rocker style actuator on request Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified 8 DS-CR circuit breaker V4.7 February 207

19 Form & fit drawings Auxiliary switch cover and shrouds on terminals option 0 N I C N NC LAD N NC Notes All dimensions are in inches [millimeters] 2 Tolerance ±0.0 [0.25] unless otherwise specified DS-CR circuit breaker V4.7 February 207 9

20 Form & fit drawings Busbar connection To connect terminals of different CR-circuit breakers, busbars are available in different configurations. Contact Mors Smitt for more information. Example: 3-phase busbar with 9 poles: Note All dimensions are in millimeters 20 DS-CR circuit breaker V4.7 February 207

21 rdering scheme CR B - A B - 2. Series 2. Poles 3. Current rating 4. Frequency 5. Circuit 6. Actuator 7. Actuator 8. Auxiliary 9. Terminal 0. Mounting. Max. 2. Agency & delay colour & switch & barriers application approval legend rating Series CR 2 Poles ne 4 Four 2 Two 5 Five 3 Three 6 Six 3 Current rating (amperes) or voltage coil (nominal rated voltage) 3 A06 6 DC A32 32 DC J2 2 AC J65 65 AC A2 2 DC A48 48 DC J8 8 AC K20 20 AC A8 8 DC A65 65 DC J24 24 AC L AC A24 24 DC J06 6 AC J48 48 AC ther values on request 7 Actuator colour & legend Actuator colour I- N- Dual Legend colour White A B Black Black C D 2 White Red F G 3 White Green H J 4 White Blue K L 5 White Yellow M N 6 Black Grey P Q 7 Black range R S 8 Black 4 Frequency & delay 03 4 DC, 50/60 Hz, switch only 0 DC instantaneous DC ultra short 2 DC short 4 DC medium 6 DC long 20 50/60 Hz instantaneous 22 50/60 Hz short 24 50/60 Hz medium 26 50/60 Hz long /60 Hz short, hi inrush /60 Hz medium, hi inrush /60 Hz long, hi inrush 52 5 DC, short, hi-inrush 54 5 DC, medium, hi-inrush 56 5 DC, long, hi-inrush 5 Circuit A 4 Switch only (no coil) 6 Actuator 7 A Handle, one per pole White (short handle) 6 V W 0 Black See notes on page 23 B C D 6 E 6,8 F 6,8 G 6,8 B S T Series trip (current) Series trip (voltage) Shunt trip (current) Shunt trip (voltage) Relay trip (current) Relay trip (voltage) Handle, one per multipole unit Mid-trip handle, one per pole Mid-trip handle, one per pole & alarm switch DS-CR circuit breaker V4.7 February 207 2

22 rdering scheme 8 Auxiliary switch 8 0 Without auxiliary switch 2 SPDT, 0.0 QC term. 3 SPDT, 0.39 solder lug 4 SPDT, 0.0 QC term. (gold contacts) 9 SPDT, 0.87 QC term. A 9 Terminal 9 Stud 0-32, threaded 2 0 Screw 0-32 w/saddle & washer clamps 3 Stud /4-20, threaded 4 0 Stud M5 x 0.8, threaded R 0 T 0 U 0 Stud M5 x 0.8, threaded with NFF washers and lockable nut Stud M5 x 0.8, threaded with shrouds on terminals all poles Stud M5 x 0.8, threaded with NFF washers and lockable nut, with shrouds on terminals all poles 5 0 Screw M5 x 0.8 w/saddle & washer clamp 6 Stud M6 threaded S V W SPDT, 0.0 QC term. with mounted cover including shrouds* B SPDT, 0.0 QC term. (gold contacts) with mounted cover including shrouds* * only on terminals pole with auxiliary contact Stud M6 threaded with NFF washers and lockable nut Stud M6 threaded with shrouds on terminals all poles Stud M6 threaded with NFF washers and lockable nut, with shrouds on terminals all poles 7 2 Double quick terminal connection 0 Mounting & barriers Mounting style Threaded insert Barriers x 0.95 inch Yes, between poles only (multi pole) A x 0.95 inch Yes, between poles and at right side viewed from back (multi pole) x 0.95 inch Yes, barrier at right side viewed from back (single pole) x 0.95 inch No 2 9 IS M3 x 5 mm Yes, between poles only (multi pole) F 9 IS M3 x 5 mm Yes, between poles and at right side viewed from back (multi pole) 7 9 IS M3 x 5 mm Yes, barrier at right side viewed from back (single pole) 4 IS M3 x 5 mm No Maximum application rating B 25 VDC C 3 20/240 VAC D 4 J VAC 45 VAC 2 Agency approval 2 TUV certified, UL recognized 7 A No agency approvals (configuration not tested by external agency) 22 DS-CR circuit breaker V4.7 February 207

23 rdering scheme Notes:. Standard multipole units have all poles identical except when specifying auxilary switch, mixed poles on request 2. Current rating 60 A - 00 A are available with circuit codes A & B only. Current ratings 80 A - 00 A are available up to 2 poles maximum 3. Voltage coils not rated for continuous duty. Available only with delay codes 0 and For 0.02 to 30 A, select current code 630 For A, select current code 650 For A, select current code 670 For A, select current code 80 Maximum number of poles on request 5. Available with circuit codes B & D only, and up to 50 A maximum 6. Circuit codes D, E, F & G available with terminal codes,2,4 & 5 only. Circuit codes D available up to 50 A maximum current rating 7. Actuator code: B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker, available with all circuit codes except switch only T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker, available with circuit codes B & C 8. Auxiliary switch available with series trip and switch only circuits. n multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole (rear view) 9. Available to 60 A maximum 0. Available to 50 A maximum. Available to 00 A maximum 2. Available to 25 A maximum 3. 2 & 3 pole circuit breakers required for 20/240 VAC applications, terminal barrier is required. Third pole is for 20/240 VAC applications requiring neutral disconnect. The 3rd pole has the same construction as poles & 2 4. Code only applicable for single pole. For multiple poles select code C 5. Multiple pole only 6. Single pole only 7. TUV certified: not for switch only circuit and not for actuator legend N- UL recognized: for most applications, not for all UL listed: possible on request Special applications without approvals: agency approval code A 8. Not TUV certified, agency approval code A 9. Barriers not in combination with terminal shrouds DS-CR circuit breaker V4.7 February

24 DS-CR circuit breakers -V4.7 February 207 Mors Smitt France SAS Tour Rosny 2, Avenue du Général de Gaulle, F Rosny-sous-Bois Cedex, FRANCE T +33 (0) , F +33 (0) E sales.msf@wabtec.com Mors Smitt Asia Ltd. 29/F., Fun Towers, 35 Hung To Road Kwun Tong, Kowloon, HNG KNG SAR T , F E sales.msa@wabtec.com Mors Smitt B.V. Vrieslantlaan 6, 3526 AA Utrecht, NETHERLANDS T +3 (0) E sales.msbv@wabtec.com Mors Smitt Technologies Inc. 00 Johnson Drive, Buffalo Grove, IL , USA T , F E salesmst@wabtec.com Mors Smitt UK Ltd. Graycar Business Park, Barton under Needwood, Burton on Trent, Staffordshire, DE3 8EN, UK T +44 (0) F +44 (0) E sales.msuk@wabtec.com RMS Mors Smitt 6 Anzed Court, Mulgrave, VIC 370, AUSTRALIA T +6 (0) F +6 (0) E sales.rms@wabtec.com (c) Copyright 207 All rights reserved. Nothing from this edition may be multiplied, or made public in any form or manner, either electronically, mechanically, by photocopying, recording, or in any manner, without prior written consent from Mors Smitt. This also applies to accompanying drawings and diagrams. Due to a policy of continuous development Mors Smitt reserves the right to alter the equipment specification and description outlined in this datasheet without prior notice and no part of this publication shall be deemed to be part of any contract for the equipment unless specifically referred to as an inclusion within such contract. Mors Smitt does not warrant that any of the information contained herein is complete, accurate, free from potential errors, or fit for any particular purpose. Mors Smitt does not accept any responsibility arising from any party s use of the information in this document.

FR circuit breaker - hydraulic magnetic, railway, very high current. Datasheet

FR circuit breaker - hydraulic magnetic, railway, very high current. Datasheet FR circuit breaker - hydraulic magnetic, railway, Datasheet very high current Features Ideal for very high current applications Precise, temperature independent operation Panel mount Integrated auxiliary

More information

AR circuit breaker - Hydraulic magnetic,

AR circuit breaker - Hydraulic magnetic, AR circuit breaker - Hydraulic magnetic, Datasheet railway, small Features Description Small hydraulic magnetic circuit breaker for railway applications to protect electronic equipment and components against

More information

ER circuit breaker - Hydraulic magnetic,

ER circuit breaker - Hydraulic magnetic, ER circuit breaker - Hydraulic magnetic, Datasheet railway, high current and voltage Features Ideal for high current and high voltage applications Precise, temperature independent operation Panel mount

More information

FR circuit breaker - hydraulic magnetic,

FR circuit breaker - hydraulic magnetic, FR circuit breaker - hydraulic magnetic, Datasheet railway, very high current Features Ideal for very high current applications Precise, temperature independent operation Panel mount Integrated auxiliary

More information

RBR circuit breaker - Remote operated

RBR circuit breaker - Remote operated - Remote operated Datasheet Features ON-OFF and trip indication Load shedding Energy management Compact size Automatic reset capable Choice of interface styles Panel or 35 mm rail mounting Manual operation

More information

PDR circuit breaker - Ground fault Datasheet

PDR circuit breaker - Ground fault Datasheet - Ground fault Datasheet protection device Features Blue housing 1-3 poles plus neutral 7-100mA Preciese, temperature independent operation Choise of time delays, terminals and actuator colours Application

More information

G-Series. Circuit Breaker.

G-Series. Circuit Breaker. -Series Circuit Breaker Carling Technologies -Series hydraulic/magnetic circuit breakers offer the highest quality solution to your circuit protection requirements. The -Series is designed to sense over-current

More information

N.S1-P relay - Signalling, post

N.S1-P relay - Signalling, post - Signalling, post Datasheet Features Instantaneous electro-mechanical vital relay Weld resistant contacts Weld no transfer contacts Gravity drop out Solid gold and bifurcated contacts -25 C...+70 C operating

More information

F-Series. Circuit Breaker

F-Series. Circuit Breaker F-Series Circuit Breaker The F-Series hydraulic/magnetic high amperage circuit breakers are designed to handle high current applications in extremely hot and/or cold locations. Due to its timeproven hydraulic/magnetic

More information

F-Series. Circuit Breaker

F-Series. Circuit Breaker F-Series Circuit Breaker The F-Series hydraulic/magnetic high amperage circuit breakers are designed to handle high current applications in extremely hot and/or cold locations. Due to its timeproven hydraulic/magnetic

More information

AG 400 relay - Gold plated, 4 contacts

AG 400 relay - Gold plated, 4 contacts - Gold plated, 4 contacts Datasheet Features Instantaneous relay Plug-in design with secure locking feature for maximum ease of maintenance 4 double make / double break C/O contacts (form Z), gold plated

More information

PB-Series. GFCI/ELCI & Panel Seal

PB-Series. GFCI/ELCI & Panel Seal PB-Series GFCI/ELCI & Panel Seal The PB-Series utilizes the hydraulic magnetic principle which provides precise operation and performance even when exposed to extremely hot and/or cold application environments.

More information

PD-Series Ground Fault Circuit Protection

PD-Series Ground Fault Circuit Protection PD-Series Ground Fault Circuit Protection SmartGuard is an equipment ground fault protection device that functions as a standard high-quality Carling hydraulic/ magnetic circuit breaker, offering customized

More information

Description The EA 112 socket has crimp contacts to allow rear connection on the socket.

Description The EA 112 socket has crimp contacts to allow rear connection on the socket. E 112 - Socket Datasheet Features Rear connection, with crimp contacts No internal soldering / connections For panel/flush mount Wire locking spring E 112 suitable for all relays and modules ( 400, K,

More information

Single Pole Circuit Protectors 67 Multi-Pole Circuit Protectors 68 Printed Circuit Board Mounting 70 Configurations 72 Operating Characteristics 73

Single Pole Circuit Protectors 67 Multi-Pole Circuit Protectors 68 Printed Circuit Board Mounting 70 Configurations 72 Operating Characteristics 73 Single Pole Circuit Protectors 67 Multi-Pole Circuit Protectors 68 Printed Circuit Board Mounting 70 Configurations 72 perating Characteristics 73 Delay Curves 74 Specifications 76 Decision Tables 78 SIGLE

More information

G-Series DIN-RAIL CIRCUIT BREAKER

G-Series DIN-RAIL CIRCUIT BREAKER G-Series DIN-RAIL CIRCUIT BREAKER The G-Series hydraulic-magnetic circuit breaker insures maximum protection by integrating wiping contacts for longevity; a common trip linkage between poles; a unique

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 845-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-freemechanism and toggle actuation. A choice of switching characteristics

More information

Renewable Energy. Circuit Breakers and Disconnects

Renewable Energy. Circuit Breakers and Disconnects Renewable Energy Circuit Breakers and Disconnects HARNESS THE POWER About Carling Technologies Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches and

More information

J-Series CIRCUIT BREAKER

J-Series CIRCUIT BREAKER J-Series CIRCUIT BREAKER Designed to provide high levels of circuit protection, the J-Series is a compact, low profile hydraulic magnetic circuit breaker ideally suited for high power density applications.

More information

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59. Single Pole Circuit Protectors 55 Multi-Pole Circuit Protectors 56 Configurations 58 Operating Characteristics 59 Delay Curves 60 Specifications 61 Decision Tables 62 SINGLE POLE CIRCUIT PROTECTORS The

More information

CX-Series. Circuit Breaker

CX-Series. Circuit Breaker CX-Series Circuit Breaker The CX-Series circuit breaker features a unique and innovative arc-quenching configuration that allows the breaker to safely handle high amperage and high DC voltage applications

More information

L-Series. Circuit Breaker

L-Series. Circuit Breaker L-Series Circuit Breaker Carling Technologies is pleased to introduce the new L-Series Circuit Breaker, a compact, high performance breaker ideally suited for the rigors and confined spaces found in today

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 835-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics

More information

AP/UP, AP/MIL Series Magnetic Circuit Protectors

AP/UP, AP/MIL Series Magnetic Circuit Protectors AP/UP, AP/MIL AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction 68 Single Pole 69 Multi-Pole 70 Configurations 72 Operating Characteristics 73 Delay Curves 74 Specifications 75 Decision Tables

More information

JAE Series. Magnetic Circuit Protectors. Introduction Poles Configurations Operating Characteristics Delay Curves Decision Tables

JAE Series. Magnetic Circuit Protectors. Introduction Poles Configurations Operating Characteristics Delay Curves Decision Tables JAE Series Magnetic Circuit Protectors Introduction Poles Configurations Operating Characteristics Delay Curves Decision Tables 205 207 211 213 216 217 JAE/JRE/JLE Series Hydraulic Magnetic Circuit Protectors

More information

Magnetic Overcurrent Circuit Breaker

Magnetic Overcurrent Circuit Breaker Magnetic Overcurrent Circuit Breaker 808-... Description ngle pole miniaturised magnetic circuit breakers with unique highspeed operating mechanism and push/pull on/off manual actuation. Fitted with electrically

More information

DD Frame - Series Circuit Breakers

DD Frame - Series Circuit Breakers The DD Frame is a compact yet very powerful circuit breaker. Using the hydraulic-magnetic technology which ensures that the breaker performance is unaffected by ambient temperature, the CI DD Frame series

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 835-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-free - mechanism and toggle actuation. A choice of switching characteristics

More information

MS-Series. Circuit Breaker

MS-Series. Circuit Breaker MS-Series Circuit Breaker Carling Technologies MS-Series Sealed Toggle Circuit Breaker was designed and tested to operate flawlessly in the harshest of environments. Ideally suited for COTS (commercial

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of single pole, double pole with single pole protection,

More information

H-Series. Circuit Breaker.

H-Series. Circuit Breaker. -Series Circuit Breaker The -Series hydraulic/magnetic circuit breaker provides dependable circuit protection in a low cost, compact package. By meeting the IEC spacing requirements, the -Series is the

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 0-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker -F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 694 with trip free mechanism) offering the choice of single

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series KTU7 UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s KTU7 series of UL Molded Case Circuit Breakers are UL489 and CE listed

More information

Catalog Issued 3-03 (PDF Rev )

Catalog Issued 3-03 (PDF Rev ) W6/W9 series Magnetic Hydraulic P& Circuit reakers Features Designed for the international market. UL Recognized (UL77 and UL5), CS ccepted and VDE approved. Ratings to 5 amps. Heavy duty #-32 stud connections.

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 0-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (S-type TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (Stype TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G V

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G V Description Single and two pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast magnetic only or hydraulically delayed switching characteristics

More information

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Thermal-magnetic Miniature Circuit Breaker 4230-T... Thermal-magnetic Miniature Circuit Breaker 420-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-2, UL 077 and UL 489 for DIN rail

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (Stype TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Thermal Overcurrent Circuit Breaker 3120-F...

Thermal Overcurrent Circuit Breaker 3120-F... Thermal Overcurrent Circuit Breaker 20-F... Description An extremely versatile range of rocker switch/thermal circuit breakers (Stype TO CBE to EN 6094 with trip free mechanism) offering the choice of

More information

Thermal Circuit Breaker 3120-F...

Thermal Circuit Breaker 3120-F... Description The 320 circuit breaker/switch combination is an ON/OFF switch with integral overcurrent protection (S-type TO CBE to EN/IEC 60934). The trip element is a bimetal. Type 320 is ideally suited

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s series of UL are UL489 and CE listed for global applications. The current

More information

Thermal-Magnetic Circuit Breaker 201/-WA

Thermal-Magnetic Circuit Breaker 201/-WA Thermal-Magnetic Circuit Breaker 0/-WA Description Single pole thermal-magnetic circuit breaker with tease-free, trip-free, snap action mechanism and two button operation (M-type TM CBE to EN 60934). Featuring

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650515200 Ed.1 of 21/02/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and

More information

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A Thermal-Magnetic Circuit Breaker 0-S9-P9M-40033-...A Description Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

209 Series. Magnetic Circuit Protectors

209 Series. Magnetic Circuit Protectors 29 Series Magnetic Circuit Protectors Introduction 249 Power Selector System Multi-Pole Configurations Operating Characteristics Delay Curves Specifications Decision Tables 73 75 77 79 8 82 85 87 29/29/229/249/279

More information

QF(13) - Series Miniature Circuit Breakers

QF(13) - Series Miniature Circuit Breakers DIN Mount 1 pole DIN Mount 2 pole Dual Mount 3 pole Dual Mount 3 + N Features AC circuit breaker Hydraulic-magnetic technology % rating capability, independent of ambient temperature One, two, three, four

More information

NRBM Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute

NRBM Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute NRBM circuit breakers are the largest in rated current (A to 50A) among the IDEC circuit breakers series. These small sized, high-effi ciency breakers offer a variety of protection characteristics that

More information

AP/UP, AP/MIL Series Magnetic Circuit Protectors

AP/UP, AP/MIL Series Magnetic Circuit Protectors AP/UP, AP/MIL AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction 77 Single Pole 78 Multi-Pole 79 Configurations 8 Operating Characteristics 82 Delay Curves 83 Specifications 84 Decision Tables

More information

PCB Relay. Contact form Terminals Coil terminals Rated voltage Model SPST-NO #250 tab terminals PCB terminals 5, 12, 24 VDC G4A-1A

PCB Relay. Contact form Terminals Coil terminals Rated voltage Model SPST-NO #250 tab terminals PCB terminals 5, 12, 24 VDC G4A-1A PCB Relay Miniature Single-pole Relay with 80-A Surge Current and 20-A Switching Current Ideal for motor switching. Miniature, relay with high switching capacity built-in applications. Creepage distance

More information

IAL/IUL/IEL/LEL Series Magnetic Circuit Protectors

IAL/IUL/IEL/LEL Series Magnetic Circuit Protectors IAL/IUL/IEL/LEL IAL/IUL/IEL/LEL Series Magnetic Circuit Protectors Introduction 29 Single & Multi-Pole 3 Rocker, Sealed Toggle 32 Configurations 36 perating Characteristics 4 Delay Curves 4 Specifications

More information

209/219/229/249/279 Series Magnetic Circuit Protectors

209/219/229/249/279 Series Magnetic Circuit Protectors 29/29/229/249/279 29/29/229/249/279 Series Magnetic Circuit Protectors Introduction 65 249 Power Selector System 67 Multi-Pole 69 Configurations 7 Operating Characteristics 73 Delay Curves 74 Specifications

More information

F-Series General Specifications

F-Series General Specifications arling F-Series General Specifications F-Series breakers are available up to 700, and are also available with a 25 millivolt metering shunt construction. This optional construction provides a safe method

More information

Thermal-Magnetic Circuit Breaker M1-...

Thermal-Magnetic Circuit Breaker M1-... Thermal-Magnetic Circuit Breaker 320-...-M-... Description Two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 6034). The addition of a magnetic tripping

More information

Carling Circuit Breakers

Carling Circuit Breakers Carling Circuit Breakers Standard Inventory Products Guide July 2016 Edition Introduction Amelec Australia Pty Ltd is pleased to introduce our new Carling Technologies' Standard Inventory Products Guide

More information

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Series High Performance Circuit Breakers Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific

More information

QF(19) - Series Miniature Circuit Breakers

QF(19) - Series Miniature Circuit Breakers Dual mount 1 pole Dual mount 2 pole Dual mount 3 pole Dual mount 3+N Features AC circuit breaker Hydraulic-magnetic technology % rating capability, independent of ambient temperature One, two, three pole,

More information

These devices meet the requirements of OSHA 29 CFR (b)(1)(ii) and OSHA 29 CFR (a) (2)(ii)(G). Airpax LEL series

These devices meet the requirements of OSHA 29 CFR (b)(1)(ii) and OSHA 29 CFR (a) (2)(ii)(G). Airpax LEL series PGFM Series GFCI Ground Fault Protection Sensing Module INTRODUCTION The LineGard PGFM GFCI Sensing Module is a ground fault or equipment leakage sensing device designed and manufactured by North Shore

More information

QF(26) - Series Miniature Circuit Breakers - Low Rating (5-63 A)

QF(26) - Series Miniature Circuit Breakers - Low Rating (5-63 A) QF(26) - Series Miniature Circuit Breakers - Low Rating (5-63 A) Dual Mount 1 pole Dual Mount 2 pole Dual Mount 3 + N Features AC circuit breaker Hydraulic-magnetic technology % rating capability, independent

More information

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489 MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

Thermal-Magnetic Circuit Breaker M1-..

Thermal-Magnetic Circuit Breaker M1-.. Thermal-Magnetic Circuit Breaker 30-...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic

More information

Electronic Circuit Breaker ESS20-0..

Electronic Circuit Breaker ESS20-0.. Electronic Circuit Breaker ES-0.. Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

PVGard 600 and 1000 Vdc solar photovoltaic circuit breakers

PVGard 600 and 1000 Vdc solar photovoltaic circuit breakers Supersedes October 2013 photovoltaic circuit breakers Contents Description Page Product description........................ 1 PVGard 600 Vdc........................... 2 Technical data...........................

More information

Products :: Circuit Protection :: Thermal Circuit Breakers

Products :: Circuit Protection :: Thermal Circuit Breakers Products :: Circuit Protection :: Thermal Circuit Breakers Thermal Circuit Breaker CLB-Series CLB-Series PDF elibrary The CLB-Series is a compact, single pole, push-to-reset family of thermal circuit breakers

More information

Circuit Breakers Series AM/S

Circuit Breakers Series AM/S Heinemann fi Circuit Breakers Series AM/S UL489 LISTED / MEETS INTERNATIONAL STANDARDS Heinemann fi wrote the book on the HYDRAULIC MAGNETIC CIRCUIT BREAKERS by patenting the original technology back in

More information

Ordering Information. Text PCB Power Relay G5RL. Low-profile Relay with Various Models. Power Relays

Ordering Information. Text PCB Power Relay G5RL. Low-profile Relay with Various Models. Power Relays Low-profile Relay with Various Models Low profile:.7 mm in height Clearance and creepage distance Between coil and contacts: 8 mm/8 mm Between contacts of the same polarity: 3 mm/4 mm Models with AC coil

More information

UMBW-UL489 and UL1077 Listed

UMBW-UL489 and UL1077 Listed -UL489 and UL77 Listed Introducing the New WEG Series Thermal-Magnetic Miniature Breakers. This new offering includes both UL489 and UL77 approvals to provide a solution for circuit & equipment protection

More information

Electronic Circuit Breaker ESS20

Electronic Circuit Breaker ESS20 Electronic Circuit Breaker ESS20 Description Electronic circuit breaker type ESS20 is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 24 V switch-mode

More information

Energy and traction control solutions

Energy and traction control solutions Mors Smitt Railway Technology Energy and traction control solutions Accurate technology for all high voltage and high current measurement applications Mors Smitt Railway Technology Energy and traction

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

High Performance Thermal-Magnetic Circuit Breakers 410/520/

High Performance Thermal-Magnetic Circuit Breakers 410/520/ High Performance Thermal-Magnetic Circuit Breakers 0/0/30-... Description Single, double and three pole high performance thermal-magnetic circuit breakers with tease-free, trip-free, snap action mechanism

More information

NRA Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute

NRA Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute RA Series RA Series Key features of the RA series include: Available in 5 different styles Excellent overload and short circuit protection Small size and high-efficiency Life expectancy of over 0,000 operations

More information

Single Pole Circuit Protectors 129. Multi-Pole Circuit Protectors 130. BX Style Circuit Protectors 131. High-Current Magnetic Circuit Protectors 132

Single Pole Circuit Protectors 129. Multi-Pole Circuit Protectors 130. BX Style Circuit Protectors 131. High-Current Magnetic Circuit Protectors 132 Single Pole Circuit Protectors 29 MultiPole Circuit Protectors 3 BX Style Circuit Protectors 3 HighCurrent Magnetic Circuit Protectors 32 Panel Seal Circuit Protectors 33 Rocker Handles 34 Configurations

More information

Ordering Information. Text PCB Power Relay G5LE

Ordering Information. Text PCB Power Relay G5LE A Cubic, Single-pole 10-A Power Relay Single-pole 10A 35VDC, 0.8mm contact gap: G5LE-G Single-pole 16A 250VAC: G5LE-E ROHS compliant. Sub-miniature sugar cube relay with universal terminal footprint. Conforms

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

SAR & SAS Circuit Protectors

SAR & SAS Circuit Protectors SAR & SAS Circuit Protectors 280 QAS, QAL, QFS, QFL Quick-Action Fuses 282 HVS & SARPV Compact Switches for 28 Solar Power Applications SAR & SAS Circuit Protectors Applications: Typical applications include

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Thermal-magnetic Miniature Circuit Breaker 4230-T... Thermal-magnetic Miniature Circuit Breaker 40-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-, UL 1077 and UL 489 for DIN rail

More information

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h) Mechatronic Analog Timer H3AM Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and

More information

Thermal Overcurrent Circuit Breaker 3130

Thermal Overcurrent Circuit Breaker 3130 Thermal Overcurrent Circuit Breaker 330 Description Single, two and three pole rocker switch/thermal trip free circuit breakers (S-type TO CBE to EN 60934) of compact design for snap-in panel mounting.

More information

Manual Motor Starters. Meta-MEC

Manual Motor Starters. Meta-MEC Manual Motor Starters Meta-MEC Manual Motor Starters LS Meta-MEC Manual Motor Starters provide completed ranges up to 100A 45 mm 55 mm 32AF 2 2 45 mm 70 mm 63AF 100AF 3 3 Manual LS Meta-MEC Motor Starters

More information

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A Transfer switches The solution for > Genset < 90 kva > Heating systems > Climate control > Ventilation systems > Telecommunications atys-s_018_a Strong points Function products are 4 pole remotely operated

More information

Single Pole Circuit Breakers 107 Multi-Pole Circuit Breakers 108 IAGX/IUGX/IEGX/CEGX/ IAGZX/IUGZX/IEGZX/CEGZX Breakers 110 IAGBX/IUGBX/IEGBX/CEGBX

Single Pole Circuit Breakers 107 Multi-Pole Circuit Breakers 108 IAGX/IUGX/IEGX/CEGX/ IAGZX/IUGZX/IEGZX/CEGZX Breakers 110 IAGBX/IUGBX/IEGBX/CEGBX Single Pole Circuit Breakers 07 MultiPole Circuit Breakers 08 IAGX/IUGX/IEGX/CEGX/ IAGZX/IUGZX/IEGZX/CEGZX Breakers 0 IAGBX/IUGBX/IEGBX/CEGBX Breakers IAG/IUG Breakers 2 IEGS/CEGS/IEGHS/CEGHS SnapIn Circuit

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Electronic overload relays EF205 and EF370

Electronic overload relays EF205 and EF370 Data sheet Electronic overload relays EF205 and EF370 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

S840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en

S840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en Snap-action switches S80, S85, S86 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D0.en Snap-action switches, S80, S85, S86 Series Single-break

More information

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet SBC042D020 06/04/ -22-00-.. / Z-22-00-.. 4-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 440 V DC.

More information

N W. Thermal Circuit Breaker / Switch Series Description. Typical applications Circuit breaker. Technical data

N W. Thermal Circuit Breaker / Switch Series Description. Typical applications Circuit breaker. Technical data Thermal Circuit Breaker / Switch Series 33 Description Combination of single pole circuit breaker and N/FF switch with soft-touch rocker actuation. Contoured rockers are available with a choice of colours

More information

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions Accessories

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions Accessories Switching & ontrols Selection Guide... 922 1V Series... 923 Dimensions... 929 Accessories... 932 ircuit Breakers Switches & Pilot Lights Signaling Lights Relays & Sockets Timers ontactors Terminal Blocks

More information