1 SHREE RAMCHANDRA EDUCATION SOCIETY S SHREE RAMCHANDRA COLLEGE OF ENGINEERING, LONIKAND, PUNE DEPARTMENT OF ELECTRICAL ENGINEERING LAB MANUAL SWITCHGEAR AND PROTECTION (403147) BE (EE) Semester-VIII S.R.C.O.E, PUNE Page 1

2 INDEX Sr. No. Name of Experiment Page No. 1. Study of switchgear testing kit Study of Fuse, MCB & their testing Study and testing of contactors Study and testing of thermal overload relay for Induction Motor protection 5. Study and plotting Characteristics of IDMT type Induction over current relay Percentage differential protection of transformer Protection of alternator Study of various LT switchgears like RCCB, timers S.R.C.O.E, PUNE Page 2

3 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY OF SWITCHGEAR TESTING KIT LABORATORY MANUAL EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/01 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:03-07 STUDY OF SWITCHGEAR TESTING KIT AIM: To study the switchgear testing kit. APPRATUS (Specifications): Sr. No. Variable AC current: Name of Equipment Range 0-50 Amp. with 500 VA/1000VA Variable AC voltage: V AC, 2 Amps. Variable DC voltage: V DC, 2 Amps. Mains Input:(three terminal instrument Normal 230V AC, 50 Hz, mains plugs provided.) Outputs: Variable AC current source: 0-20A. VA burden maximum: 200VA. Timer OFF connection from relay contacts. Monitors: Other components: Time counter: Range: milli seconds with auto range. Accuracy: +/- 0.05%. Mains ON/OFF switch, Indication Lamps, Sturdy Current variable knob. DESCRIPTION: This unit is specially designed to suit relay testing requirements of power station testingengineers. Purpose of modern instrumentation engineering is to reduce the total instrumentweight and still give single equipment which can be used for testing of different type ofpower system relays. The unit is a portable. Stability and accuracy of digitalindication is in-built. Numbers of functional units are included in single cabinet. They can beused S.R.C.O.E, PUNE Page 3

4 individual or in association with other unit. The connection terminals are front loadedand plug in or wire connections can be used. The set operates on single phase 230 Volts, AC, 50 Hz power supply and provides acontrollable test voltage and completely adjustable output current. The unit is housed in apowder coated sheet metal panel with table mounting facility, detachable lid, latches andcarrying handles. All the switches, terminals, meters and knobs are mounted on frontof the panel, with properlabels. Terminals for the test voltage, current source and relay contact terminals are provided on the front Ammeter and digital time interval meter is also provided on thefront of the panel for metering purpose. The ammeter will indicate in the percentage of therange selected and the voltmeter will indicate the voltage. Mains ON indication is provided. The voltage circuit and current circuit can be used simultaneously. FEATURES: Micro controlled based time measuring unit with 1 ms resolution. Special provision for relay s ON delay/off delay time measurement. Specially designed for testing of all types of IDMT over current relay/under-over voltage relay/auxiliary relay. Designed for checking the operating characteristic of protective relay on site. With timer control circuit, timer automatically starts output is initiated and stops when the. Auto cut-off facility. Provided with Single pole IDMT Over Current/ Earth fault relay. Numerical/ Electromechanical type of Relay with Secondary CT ratio 1A/ 5A. PROCEDURE TO USE CURRENT SOURCE: 1. Connect the relay coil to current range selector. 2. Switch on Mains. 3. Select current range from current selector switch 4. To adjust current range for the injection, keep the timer open, marked as +V & C2. 5. Push the stat button, after staring, the timer gets started & current to be injected should be as per indication on the ammeter as % of the selected range. 6. After setting the current range, short the time terminals, to automatically stop the current source. 7. Now connect the NO contactor the relay to the timer terminals are marked as +V & C2. 8. Reset the timer & reset the current circuit by pushing the start button& current will be injected & relay will be operated. The NO contacts turn NC & the timer circuit gets automatically cut off. 9. After testing of the relay for 2 to 3 times at various ranges, zero the current control knob. 10. Switch OFF the main supply. S.R.C.O.E, PUNE Page 4

5 PROCEDURE TO USE VOLTAGE SOURCE: 1. Switch ON main switch. 2. Select AC/DC voltage source as per requirement by switching selector switch to 1 or 2 Position for AC /DC source respectively. 3. The voltage can be adjusted from the voltage control knob as per requirements. 4. After using for various operations turn OFF the voltage selector switch. 5. Turn OFF main switch & before zero voltage control knob is zero. 6. Voltage is shown on the voltmeter on the respective meters for Ac & DC. Procedure for Time Vs Current (IDMT)Characteristics test 1) Connect the relay coil (termination ) to the current source (Terminated as ). as shown in the figure 1. 2) Connect the Aux. contact of the relay ( ) to the Timer contact of the kit ( ). 3) Connect the 230V AC supply to the kit 4) Keep the TMS setting at maximum position (1 sec). 5) Keep the Phase setting plug at 2.5A (50%) Setting 6) Switch ON the unit and push the Start Push button. 7) Now slowly increase the current value upto 3A by adjusting the current variable knob. 8) Switch OFF the output by pushing the stop PB and reset the Timer without changing the setting 9) Switch ON the output, which will also start timer. Timer will stop counting when the relay trips Note the delay. 10) Repeat the procedure for various current values as per table no ) Switch OFF the mains supply. Procedure for Testing TMS Setting 1) Connect the relay coil (termination ) to the current source (Terminated as ). as shown in the figure 1. 2) Connect the Aux. contact of the relay ( ) to the Timer contact of the kit ( ). 3) Connect the 230V AC supply to the kit. 4) Keep the TMS setting at minimum position (0.1s). 5) Keep the Phase setting plug at 2.5A (50%) Setting. 6) Switch ON the unit and push the Start Push button. 7) Now slowly increase the current value up to 3.5A by adjusting the current variable knob. 8) Switch OFF the output by pushing the stop PB and reset the Timer without changing the setting. 9) Switch ON the output, which will also start timer. Timer will stop counting when the relay trips Note the delay. 9) Repeat the procedure for various TMS setting values as per table no ) Switch OFF the mains supply. S.R.C.O.E, PUNE Page 5

6 OBSERVATION TABLE Table No. 1.1 Pick up Test TMS(Time Multiplier setting) Setting- 1 Sec. Sr.No. % Set (I >) Current (Amps) A (50%) A (75%) 3. 5A (100%) A (125%) A (150%) A (175%) 7. 10A (200%) Table no. 1.2: Time Vs. Current (IDMT) Characteristics for O/C or EF TMS Setting: 1 Sec. Phase trip setting as 2.5A (50%) Set current at 3A 5A 7.5A 10A 3A Time in Sec. Phase trip setting as 3.75A (50%) Set current at 5A 7.5A 10A 15A Time in Sec. Phase trip setting as 5A (100%) Set current at 7.5A 10A 15A 20A Time in Sec. Table no. 1.3: TMS Setting Test: S.R.C.O.E, PUNE Page 6

7 Current to be injected : 3.5 A SWITCHGEAR AND PROTECTION (SGP) (403147) TMS Switch Position Phase Switch At 2.5 A X 0.1 X 0.2 X 0.5 X 0.75 X 0.1 CONCLUSION: In this way we studied the switchgears testing kit. S.R.C.O.E, PUNE Page 7

8 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY OF FUSE & MCB & TESTING OF MCB EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/02(A) SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING PAGE:08- SEMESTER : II (BE) 10 STUDY OF FUSE & MCB & TESTING OF MCB AIM: Study of Fuses THEORY: The fuse is a protecting device of simplest form. It consists of a small piece of metal when excessive current flows through it. The metal elements melts & the current is interrupted & the circuit gets disconnected from the supply.thus it protects the circuit from dangerous excessive current. So fuse is used to interrupts a fault current.it is simple protective device which works on the principal of current interruption, if current through it becomes excessive. Types of fuse 1. Expulsion fuses 2. Cartridge fuse 3. Drop out fuse 4. Liquid fuse 5. Open fuse 6. Striker fuse 7. Switch Fuse 8. HRC Fuse 1. Expulsion Fuse - The Expulsion fuse consists of modern cutout. In such fuse the arc occurring during the current interruption is extinguished by the expansion produced by the arc. 2. Rewirable Fuse or Semi closed Fuse- In such a fuse the fuse element is placed in a semi closed carrier. Fuse carriers can be pulled out & the fuse element can be replaced, after the fuse operation. The carrier can be then placed in the fuse base.such fuses are very commonly used in our houses. 3. Cartridge Fuse This fuse is totally enclosed fuse. The fuse element is placed in a totally enclosed carrier with two Metal contacts provided on the two sides of a carrier. The entire cartridge is required to be replaced once fuse operates. 4. Drop-out Fuse S.R.C.O.E, PUNE Page 8

9 In such fuse, the fuse carrier drops out once, the fuse operates, the dropping out of fuse carrier provides the necessary isolation between the terminals. 5. Liquid Fuse When fuse operates, in case of high current there exists an arc. The arc must be extinguished properly. The fuse in which the arc is extinguished using a liquid medium is called liquid fuse. The liquid medium used is generally oil. The various types of liquid fuses are:- a) Oil break b) Oil expulsion fuse c) Oil blast fuse 6. Open Fuse This fuse consists of a plain fuse wire and the fuse operates any provision for extinguishing the arc. 7. Striker Fuse In this fuse, there exists a combination of a fuse and a mechanical device. When the fuse operates,strikes get released under pressure which gives the tripping indication. 8. Switch Fuse This fuse is a combination of a switch & fuse. The combined unit is called switch fuse. 9. HRC Fuse It is high rupturing capacity fuse. It is also called breaking capacity cartridge fuse. In such a fuse the arc is extinguished with the help of quartz, sand powder such a powder provides very high resistance which helps to extinguish the arc. It is basically a low voltage fuse which is used for various distribution purposes. DEFINITIONS: 1] Fuse The fuse is device which consists of a small piece of metal which is connected in series circuit when current through it increases beyond some predetermined value, the metal melts to interrupt the circuit current which protects the circuit from excessive high current. 2] Fuse element The part of the fuse which melts excessive current flows through it is called fuse element or fuse wire. 3] Current rating of wire It is that maximum current which fusing element can normally Withstand without any undue overheating or melting. It depends on: i) Temperature rise of fuse contacts of fuse holder ii) Fusing elements material S.R.C.O.E, PUNE Page 9

10 iii) Determination of fuse due to oxidation. 4] Fusing factor The ratio of the minimum fusing current & the current rating of fuse is called the fusing factor. As minimum fusing current is more than the current rating. The fusing factor is always greater than 1. 5] Prospective current The figure shows how the ac current is cut off using a fuse. This is called cut-off characteristic of fuse. The rms value of the 1 st loop of the fault current calculated if fuse is assumed to be replaced by a link of a negligible resistance is called the prospective current. 6] Cut-off current The current value at which the fuse melts before fault current achieve its peak value is called cut- off current. 7] Pre-arcing time The time between the commencement of the fault current and the instant when the fuse melts & the arc starts is called pre-arcing time. 8] Arcing time The time between the end of pre-arcing time and the instant when the arc gets completely extinguished is called arcing time. 9] Braking capacity The braking capacity is the fuse rating corresponding to the rms value of the ac component of maximum prospective current at its rated service voltage. 10] Pre-arcing (I 2 t) It is the time integral of the square of current passing through the fusing during pre-arcing time. 11] Arcing (I 2 t) It is the time integral of the square of the current through the fuse during the arcing time. 12] Clearing (I 2 t) It is the sum of the pre-arcing I 2 t and the arcing I 2 t is called clearing I 2 t or total I 2 t. 13] Voltage rating of fuse The voltage rating of fuse is specified by the manufacture. The rated voltage of the fuse must be equal or greater than i) Voltage of a single phase circuit ii) Line voltage in case of three phase circuit iii) Voltage between two outer wires in 3 wire dc circuit. CONCLUSION: In this way we have studied the different types of fuses. S.R.C.O.E, PUNE Page 10

11 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY OF FUSE & MCB & TESTING OF MCB EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/02(B) SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:-11 AIM : To study Miniature Circuit Breaker (MCB). CONSTRUCTION : As the name indicates, miniature circuit breaker is housed in moldings of insulating materials, which also has fire resistance property normally ceramic. The MCB consists of a bimetallic strip for thermal overload protection as well as instantaneous magnetic release type short circuit protection. These releases are fixed on each pole and in case of three phase circuit they are connected to common connecting base. FUNCTION : MCB automatically isolates the electrical circuit under sustained overload or short circuit. A bimetallic element provided on inverse time current characteristic which prevents interruption on normal inrush currents or temporary overload. An instantaneous magnetic trips release protects the equipments against very high currents. MCB s are available in 3 tripping circuit via B, C, D. Considering the fusing factor and aging effect of rewirablefuse, the smaller transformer of 25to 200 KVA will be better protected with MCB. OBSERVATION TABLE : Sr. No. Current Time in Sec CONCLUSION : Hence we have studied the working of miniature circuit breaker (MCB) and testing of miniature circuit breaker MCB is also performed successfully. S.R.C.O.E, PUNE Page 11

12 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY & TESTING OF CONTACTORS. LABORATORY MANUAL EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/03 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:12-17 STUDY & TESTING OF CONTACTORS. AIM: To study & test the contactors. APPARATUS: Switchgear testing kit, contactors & connecting wires etc. THEORY: Contactor is mechanical switching device capable of making, carrying & breakingelectric current under normal circuit conditions including operating overload conditions.acontactor is electromagnetically operated switches which can be operating remotely.contactor may be capable of making & braking short circuit currents, if they are designed for short circuit of emerging the control circuit namely. SOME TERMS & DEFINITIONS Electromagnetic contactor A contactor in which the opening & closing of main Contacts is achieved by means of an electromagnet. Electropneumatic contactor A contactor in which the force for closing & opening The main contacts is provided by an electrically opening pneumatic device. Main Circuit The conducting parts of the contactor designed to close & open. The current flows from the supply to load through the main circuit of the contactor. Main Contacts The contacts in the main circuit to carry the load current when the contactor is closed position. Control Unit The circuit which is energized or de-energized electrically for opening S.R.C.O.E, PUNE Page 12

13 /closing operation the contactor. Auxillry circuit The circuit other than main & control circuit is called auxillary circuit. PRINCIPAL: When a definite voltage is applied the coil energizes an electromagnet system comprising of fixed & moving parts, the moving parts get attracted to fixed part. Thus the electrical circuit is completed through this contact system. When magnet is de-energized, it gets pushed back by return spring & contacts open & thus electric circuit is broken. CONSTRUCTION OF TYPICAL CONTACTOR: Parts of contactor & their function: Rubber Padding:-It is provided for absorbing shocks during closing and opening the contactor. Magnets :- AC magnets are made up of laminations stacked together to reduce effect of eddy currents. Since in DC frequency is zero, problems of eddy currents losses & hysteresis losses do not exist & hence no laminations are required.there is designed gap between the central limb of fixed magnet & the moving magnet.when this gap reduces over millions of operations or magnet starts bulging it indicate thatmechanical life of contactor is over & needs replacement.if during maintenance or cleaning, emery or sand paper is used for the magnets the designedgap between the central limb increases as surface material reduces, increasing the air gap.hence while opening this remains some residual magnetic flux which does not allowthe moving magnet to separate immediately, causing severe pitting of contacts. This resultin frequent changing of contacts. Thus wage of emery or sand, paper should be avoided at magnets; it can be cleaned with CRC-2-26 / CTC & rough cloth. Contact System :- The contacts are made up of cadmium alloy. These have well anti welding properties. The gap between the contacts is less than that between magnets which ensures that contacts are S.R.C.O.E, PUNE Page 13

14 closed before magnet pole faces touch each other. LEAF Spring : - The moving contacts have to be held under certain contact pressure which is ensured by providing leaf springs over the contact carrier bridge. It also helps in bounce free closing Return Spring :- The moving assembly is held against the stored energy of two main springs called as return springs which helps the bridge assembly in opening the contact. Shading ring :- In A.C. magnets alternating flux (main flux) goes through natural zero point so force of attraction created becomes zero.this results in repeated de -energization of the magnets & leads to chattering.some additional force is require to hold the magnet when main flux passes through zero. It does this by generating an auxiliary flux which is out of phase with main flux, the shading ring is embedded in the pole face of the magnet for this. Terminals:- Terminals are made up of silver plated copper and are provided for both power circuit & control circuit terminators. Auxiliary contacts :- Set of normally open (NO) & normally close (NC) contacts are available for indication & alarm purpose. Arc Chute Set :- While breaking high currents between the contacts needs to be effectively quenched. Arc is quenched by following 3 methods: 1) Arc is split by providing number of Deion-plates. 2) The arc or current when drawn to Deion plates induces a voltage across the plates which 3) opposes the cause producing it. (arc) as per Lenz s Law 4) The resistance of the arc = specific resistivity x length of arc Area of arc S.R.C.O.E, PUNE Page 14

15 Due to splitting of arc its length increases as resistance of arc is directly proportional to length. The resistance of arc increases & thus arc is quenched. Housing :- Material having good thermal withstand and mechanical strength are used for housing. Mostly ceramic,smc ( sheet moulded compound ) & DMC (dough moulded compound ) are used for front housing while Die- cast. Aluminum is used for rare housing. SPECIFICATION OF CONTACTOR: 1) Rated Voltage 415 V 2) Rated coil voltage coils are available in various voltage rating eg.24,48,380,240,415 etc (AC/DC) 3) Contactor has following main current ratings & is selected as per the type of load ie. (application) Rated current for AC 1 Resistive load AC 2 Slightly Inductive load ( e.g. slip ring induction motor ) AC 3 Highly inductive load (e.g. Squirrel cage I.M. normal operation) AC 4 Inching & highly inductive load like squirrel cage induction motor. Contacts can be fitted with following accessories 1. Auxiliary contact blocks (add on block ) 2. Mechanical interlock etc. 3. Surge suppressor. Advantages of contactors: 1. High number of make- break operations 2. High making & braking capacity 3. Remote ON/OFF 4. High mechanical & electrical life Disadvantages of contactors: S.R.C.O.E, PUNE Page 15

16 1. It cannot sense fault itself. 2. It should be installed with relay unit. 3. Therefore it becomes costly. Applications of contactors: Remote controlling:- Mobile applications, Telecommunication, security, water pumps, green houses, remote power generator, solar systems, traffic control, field control, In agricultural industries where voltage is less & voltage fluctuations are more. Programming controllers. Voltage Monitors - They provide protection against phase loss, phase reversal.over, under & unbalanced voltage. It will also protect motor against voltagefaults. It will operate when voltage is exceeding the set value. Illumination control. 1. Timers 2. Starters Contactor starter from motor 1. D.O.L. contactor starter 2. Reversing contactor starter 3. / contactor starter 3. Air break contactors are used in L.V. switchgear. (suitable for large no. of switching operations on load/ over load ) 4. Key or push button. 5. Auxiliary switches. 6. Medium voltage vacuum contactors ( 3.6 to 12 KV)(suitable for controlling A.C. loads with high switching rate & unlimited on time) 7. Switching off - 3 Ø motor in A.C. 3 duty - Transformers - Capacitors - Resistive load (electric furnace ) S.R.C.O.E, PUNE Page 16

17 8. There is also an upcoming Biological contactor technology for Mine efficient treatment. PROCEDURE : 1) Check the rated voltage of contactor coil 2) Keep the contactor in vertical position. 3) Connect the coil terminals of the contactor to voltage output terminals of the test panel 4) For pick up voltage test, increases the voltage gradually till contacts close without humming. OBSERVATION TABLE: Rated Pick-up Drop-off Voltage (V) Voltage ( V) Voltage (V) V V V Current rating = A Pick up voltage = V (85 to 110 % of rated coil voltage) Drop off. Voltage = V (10 to 70 % of rated coil voltage) CONCLUSION: Thus we have observed the testing of contactor. It is rated for V& it s pick up & drop off voltage is V and V respectively. S.R.C.O.E, PUNE Page 17

18 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY & CHARACTISTICS OF THERMAL OVERLOAD RELAY EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/04 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:18-23 STUDY & CHARACTISTICS OF THERMAL OVERLOAD RELAY AIM : To study and test thermal overload relay. APPARATUS : Thermal overload relay ( 500 V, 50 Hz, 2 A AC ) Contactors Switch gear testing panel THEORY : Thermal overload relay prevent an electric motor from drawing excess current and overheating. Thermal overload conditions are the most likely faults to be encountered in industrial motor application, which produces an increase in the motors, Thermal dissipation and temperature. Overload protection prevents on electric motor from drawing excess current, overheating and finally bumping out. Thermal overload relays can be bimetallic relays, eutectic alloy relays, temperature control or probe relays and solid state relays. A bimetallic device is made up of two strips of different metals. The dissimilar metals are permanently joined. Heating the bimetallic strips causes it to bend because, the dissimilar metals expand & contracts at different rates. The bimetallic strips applies tension to a spring on a contact. It heat begins to rise the strip bends and spring pulls the contact apart breaking the circuit. A melting alloy ( or electric ) overload relay and a mechanical mechanism to activate a tripping device when an overload occurs. The relay measures the temperature of the motor by monitoring the amount of current being drawn. S.R.C.O.E, PUNE Page 18

19 This is done indirectly through a heater coil. Temperature control relays are used to protect the motor by directly sensing the temperature of the windings using thermister of RTD probes. The motor must have on or more positive temperature co-efficient thermister probes embedded in its windings. When nominal operating temperature of the probe is reached, its resistance increases rapidly. This increase is detected by a threshold circuit which controls a set of relay contacts solid state relays have no moving or mechanical parts. The relay calculates the average temperatures within the motor by monitoring its starting and running current. A solid state relay is also another type of over current relay. PRINCIPLE OF OPERATION : A bimetal is formed by two metals with unequal coefficient of linear expansion brazed together in the form of strip. When heated strip bends one end is fixed and other bends when heated under overload/ single phasing. CONSTRUCTIONS : The over current relay operates on thermal effect of electric current. Basically, it consist of a bimetallic strips. The bimetallic strip is nothing but two metal strips having different co-efficient of thermal expansion joined together. Here one end is supported and fixed and uneven expansion caused bending of strips. This operates the relay contacts. The fig. shows the construction of overload thermal relay. It consists of following parts Upper Slider bar :- One end of slider bar is connected to spring for pull action and other end is connected to spring for pull action and other end is connected to contact tripping level and top pivot points when bimetallic strip bends due to overload / unbalance current, this upper slider bar moves and pushes the contact tripping level, i.e. The upper slider bar is movable. Lower Slide bar :- S.R.C.O.E, PUNE Page 19

20 One end is connected to spring which has push action and other end is connected to bottom pivot point and contact tripping level. This bar has slots for carrying bimetallic strip. The spring apposes movement of contact tripping lever towards contact carrier i.e. lever slide bar is fixed one. Bimetallic strips :- It is made up of metal strips having different co-efficient of thermal expansion. They are three in number and housed in slots of lower slider. It gets supply from CT s for high currents. WORKING : Under normal conditions :- Strips are strained; contacts tripping lever is in vertical position and relay contacts are in normal position. Under overload condition :- Currents are greats than normal but balanced and hence all three bimetal and bend equally. The lower slider moves towards contact right and pushes control carrier. Hence NC contacts open which givessignal to the contactor and supply is cut off.suppose the R phase opens therefore any bimetals of Y and B phases operates due to bending of other two bimetals. Thus for the same power, the other two phase bimetals operates and trip the circuitproviding the single phasingproduction. Effect of over loading / over heating : The effect of overloading is an incipient fault which generally cause the damage of the insulation is supported to withstand certain temperature without damage. If the temperature increases beyond this for long periods, then the insulation deteriorates. The final stage is breakdown of insulation, thus this reduces the life of motor and so it becomes necessary to prevent this overheating due to overloading. Causes of overheating : Overload high current S.R.C.O.E, PUNE Page 20

21 Supply variation low voltage result in high current Heavy starting high starting current. High starting frequency motor is required to start often. High duty factor motor remains on for long periods and off for short periods. Single phasing complete load comes on two windings hence high current. Faulty bearings and other mechanical reasons. Defect in cooling systems for very large machines. Advantages of Thermal overload Relays : As the motor gets damaged due to higher temperature and causes of higher temperature are basically higher currents, the most commonly used protection is of current sensing devices, bimetallic thermal relay is used extensively. The main advantages are : Thermal overload relay gives protection for both balance and unbalance faults. They give protection against overloading & single phasing. The relay is compensated per ambient temp. variation from 5 c to 55 c so that it can protect the motor for both cold start & hot start condition These relays come as attachment with contactors They are quite economical. Application of Thermal Overload Relay : Overload Protection :- The relay protects motor against damage resulting from overloading as per international standard established for the protection of motor. Adjustment of relay to match the full load current of motor is a lever which moves against a calibrated scale marked in full load current. The range of current setting on any relay is between 100 % & 160 % of its minimum rating. Single Phasing Protection :- S.R.C.O.E, PUNE Page 21

22 The relay offers protection against single phasing, though, its sensitive differential mechanism in excess of the requirements of IEC specifications & trips even when it carries in healthy phases 0.9 times the minimum currents setting, regardless of the value to which the current adjustment lever is set. Full protection is provide on single phasing under varying operational load conditions up to 50 % of the full load rating of motor. No protection is required below the value. Direct coupling or free standing :- Incoming connectors are in the form of copper prongs that fir directly under the screw terminals. They can also be bent to a limited degree to suit the terminal position according to the type & contactor being used. When the relay is required free standing for separate mounting on additional inexpensive add-on terminal block is available. PROCEDURE : 1. For load connection, we connect the overload relay with contactor ( instead, we can use lamp.) 2. The three terminals of the overload relay are connected in series so that we can test the relay with Singlephase 3. The two terminals of the overload relay are connected to the switch-gear testing panel (0-50 A) 4. The connections from the relay to the testing panel are made as tight as possible. 5. The contactor coil is energized through the NC contact of the overload relay. Under normal operation condition the NC contacts (95 and 96) of overload relay remains NC which energises the coil of the contactor. Under overload condition, the relay trips ie. NC contacts of overload relay become NO which de-energises the contact coil & trips the contacts.then set the current more than rated value and for different current setting note down the trip time. S.R.C.O.E, PUNE Page 22

23 OBSERVATION TABLE : Current Setting Current (Amp.) Time (sec.) CONCLUSION : From the graph it can be concluded that as current increases the trip time decreases since it has inverse time characteristics. S.R.C.O.E, PUNE Page 23

24 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY CHARACTERISTIC OF IDMT RELAY /INDUCTION TO DIGITAL OVER CURRENT RELAY EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/05 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:24-27 STUDY OF CHARACTERISTIC OF OVER CURRENT RELAY AIM: To study the characteristic of over current relay. APPARATUS: Switchgear testing kit Over current relay Connecting cords. Screw driver. SPECIFICITIONS: Sr. No. Name of Equipment Variable AC current: Range 0-50 Amp. with 500 VA/1000VA Variable AC voltage: V AC, 2 Amps. Variable DC voltage: V DC, 2 Amps. Mains Input:(three terminal Normal 230V AC, 50 Hz, mains instrument plugs provided.) Outputs: Variable AC current source: 0-20A. Monitors: Other components: VA burden maximum: 200VA. Timer OFF connection from relay contacts. Time counter: Range: milli seconds with auto range. Accuracy: +/- 0.05%. Mains ON/OFF switch, Indication Lamps, Sturdy Current variable knob. S.R.C.O.E, PUNE Page 24

25 COMPLETE FUNCTION TESTING OF THE RELAY: Consist of the following instruments/ components, Current variable knob, relay IDMT EF 1 Pole, / Over Current relay, push button, timer, output terminals, etc. Procedure for Pick Up test :- 1) Connect the relay coil ( termination as ) to the current source (Terminated as ). as showm in the figure 1. 2) Connect the Aux. contact of the relay ( ) to the Timer contact of the kit ( ). 3) Connect the 230V AC supply to the kit. 4) Keep the Pick up setting at minimum position (50% i.e. 2.5A). 5) Switch ON the unit and push the Start Push button. 6) Now slowly increase the current value still relay operates i.e. Disc starts rotation or Pick Up LED Glow ON. 7) Note down the current value it must be equal to within +/- 10% of pick up setting. 8) Switch off the current source by pushing the stop Push button. 9) Reset the relay. 10) Repeat the procedure for the different pick-up setting i.e. 50 to 200%. 11) Switch OFF the mains supply. Procedure for Time Vs Current (IDMT)Characteristics test :- 1) Connect the relay coil ( termination ) to the current source (Terminated as ). as showm in the figure 1. 2) Connect the Aux. contact of the relay ( ) to the Timer contact of the kit ( ). 3) Connect the 230V AC supply to the kit. 4) Keep the TMS setting at maximum position (1 sec). S.R.C.O.E, PUNE Page 25

26 5) Keep the Phase setting plug at 2.5A (50%) Setting. 6) Switch ON the unit and push the Start Push button. 7) Now slowly increase the current value upto 3A by adjusting the current varaible knob. 8) Switch OFF the output by pushing the stop PB and reset the Timer without changing the setting. 9) Switch ON the output, which will also start timer. Timer will stop counting when the relay trips Note the delay. 10) Repeat the procedure for various current values as per table no ) Switch OFF the mains supply. Procedure for Testing TMS Setting:- 1) Connect the relay coil ( termination ) to the current source (Terminated as ). as showm in the figure 1. 2) Connect the Aux. contact of the relay ( ) to the Timer contact of the kit ( ). 3) Connect the 230V AC supply to the kit. 4) Keep the TMS setting at minimum position (0.1s). 5) Keep the Phase setting plug at 2.5A (50%) Setting. 6) Switch ON the unit and push the Start Push button. 7) Now slowly increase the current value upto 3.5A by adjusting the current varaible knob. 8) Switch OFF the output by pushing the stop PB and reset the Timer without changing the setting. 9) Switch ON the output, which will also start timer. Timer will stop counting when the relay trips Note the delay. 9) Repeat the procedure for various TMS setting values as per table no ) Switch OFF the mains supply. S.R.C.O.E, PUNE Page 26

27 Sample Table: Table no. 1.1: Pick-up test: TMS Setting: 1 Sec % Set (I >) Current in Amp. 2.5A (50%) 3.75A (75%) 5A (100%) 6.25A (125%) 7.5A (150%) 8.75A (175%) 10A (200%) Table no. 1.2: Time Vs. Current (IDMT) Characteristics for O/C or EF: TMS Setting: 1 Sec. Phase trip setting at 2.5A (50%) Phase trip setting at 3.75A (75%). Set current At Time in Sec. Set current At 3A 5A 5A 7.5A 7.5A 10A 10A 15A Time in Sec. Phase trip setting at 5A (100%). Set current At 7.5A 10A 15A 20A Time in Sec. CONCLUSION: S.R.C.O.E, PUNE Page 27

28 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY OF PERCENTAGE DIFFERENTIAL PROTECTION OF TRANSFORMER EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/06 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:28-29 STUDY OF PERCENTAGE DIFFERENTIAL PROTECTION OF TRANSFORMER AIM: To study the percentage differential protection of transformer. SPECIFICATIONS: Sr.No. Name of Equipment Range 1 AC Digital Voltmeter 500V,Aux. Supply of 230 V AC for Input Side 2 AC Digital Ammeter 5A,Aux. Supply of 230 V AC for Input Side 3 AC Digital Voltmeter 500V,Aux. Supply of 230 V AC for load Side 4 AC DigitalAmmeter 500V,Aux. Supply of 230 V AC for load Side TESTING OF DIFFERENTIAL PROTECTION TO TRANSFORMER: Connect: R3 TO R7&R5 TO R8 Y3 TO Y7& Y5 TO Y8 B3 TO B7&B5 TO B8 N3 TO N7&N5 TO N8 PROCEDURE: 1) Ensure all fault simulating switches in OFF position. 2) Switch ON the Mains MCB. 3) Push the Start Push button of Secondary side to give supply to input to transformer. S.R.C.O.E, PUNE Page 28

29 4) Primary Mains ON indication will glow and Voltmeter will show reading. 5) Push the start push button of secondary side and the load gets connected. 6) Secondary Mains on indication will glow and voltmeter will show the readings. 7) Now switch ON the fault simulating switch L-L fault. 8) Within a few micro seconds the fault will be created and the differential relay will protect the transformer by cutting OFF the mains supply to transformer. 9) As the relay get activated the mains supply will get cut OFF due to operation of contactor C2. 10) Now switch OFF the fault simulating switch and reset the relay. 11) Now repeat the above procedure from 3 to 10 for other faults like L-N fault and inter turnfault. CONCLUSION: S.R.C.O.E, PUNE Page 29

30 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND LABORATORY MANUAL PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY OF MERZ PRICE PROTECTION OF ALTERNATOR EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/07 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:30-36 STUDY OF MERZ PRICE PROTECTION OF ALTERNATOR AIM: To study the Merz Price Protection of Alternator. SPECIFICATIONS: Sr.No. Name of Equipment Range 1 AC Digital Voltmeter 750V, AC,Aux. Supply of 230 V AC 2 AC Digital Ammeter 5A,Aux. Supply of 230 V AC 3 DC Digital Voltmeter 750V, DC,Aux. Supply of 230 V AC 4 DC Digital Ammeter 20A, DC,Aux. Supply of 230 V AC 5 AC Frequency Meter Hz., Aux. Supply 230V AC Connect: Load Terminals R1 TO R2 Y1 TO Y2 B1 TO B2 N1 TO N2 S.R.C.O.E, PUNE Page 30

31 OPERATION INSTRUCTION: 1) Connect the Mains input of 1 Phase, 3 wire, 230V, AC to the demo panel, 15Amp. 1) Connect the Mains input of 1 Phase, 3 wire, 230V, AC to the demo panel, 15Amp. 2) Keep all the load switches & fault simulating switch in OFF position. 3) Connect the lamps for load bank. 4) Connect 1 Sq.mm. wire Red, Yellow, blue & Black to R, Y, B & N terminalsof alternator. 5) Connect blue tape red and black bunched to F & FF of field terminals of Alternator.. 6) Connect 1.5 sq.mm. Yellow & Blue to A & AA terminal of DC Motor. 7) Connect 1.5 sq.mm. bunched wire with blue tape to DC Motor Controller Terminalblock with similar colour. TESTING OF UNDER/ OVER VOLTAGE RELAY: For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 6) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 7) Now stable condition is achieved. 8) Now push the reset push button Green and Red both to reset the relays. 9) Now the load will get connected. 10) Now for Under Voltage protection reduce the Field Excitation of Alternator so that the Alternator voltage reduce to a value and the under voltage relay will trip and Under Voltage fault lamp will glow and the load gets disconnected. 11) Now again set the alternator field excitation upto normal voltage of 415V AC. 12) The Under/ Over Voltage relay get reset automatically. 13) Similarly for Over Voltage increase the field excitation to alternator and the Alternator output voltage increase at a over voltage vaule and relay will trip and the lamp will glow. 14) As the relay glow the load gets disconnected. 15) The relay get reset automaticaly. S.R.C.O.E, PUNE Page 31

32 TESTING OF UNDER/ OVER FREQUENCY RELAY: For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 6) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 7) Now stable condition is achieved. 8) Now push the reset push button Green and Red both to reset the relays. 9) Now the load will get connected. 10) Now for Under Frequency protection reduce the Armature Voltage to DC Motor and increase filed excitation of Alternator to maintain voltage, due to which speed of DC Motor reduces and hence Frequency reduces and the under frequency relay will trip. and Under Frequency fault lamp will glow and the load gets disconnected. 11) Now again set the alternator field excitation upto normal voltage of 415V AC and Armature voltage of DC Motor upto 208 V Frequency upto 50 Hz. 12) The Under/ Over Frequency relay get reset automatically. 13) Similarly for Over Frequency increase the Armature DC Voltage and decrease field excitation to alternator simultaneously and the Alternator output Frequency increase at a over frequency value the relay will trip and the lamp will glow. 14) As the relay glow the load gets disconnected. 15) The relay get reset automatically. Testing of Under/ Over Frequency Relay: For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. S.R.C.O.E, PUNE Page 32

33 6) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 7) Now stable condition is achieved. 8) Now push the reset push button Green and Red both to reset the relays. 9) Now the load will get connected. 10) Now for Under Frequency protection reduce the Armature Voltage to DC Motor and increase filed excitation of Alternator to maintain voltage, due to which speed of DC Motor reduces and hence Frequency reduces and the under frequency relay will trip and Under Frequency fault lamp will glow and the load gets disconnected 11) Now again set the alternator field excitation upto normal voltage of 415V AC and Armature voltage of DC Motor upto 208 V Frequency upto 50 Hz 12) The Under/ Over Frequency relay get reset automatically 13) Similarly for Over Frequency increase the Armature DC Voltage and decrease field excitation to alternator simultaneously and the Alternator output Frequency increase at a over frequency value the relay will trip and the lamp will glow. 14) As the relay glow the load gets disconnected. 15) The relay get reset automatically. Testing of Negative Phase Sequence Fault: Correct Connection: R1 TO R5 Y1 TO Y5 B1 TO B5 Fault Connection: R1 TO Y5 Y1 TOY5 B1 TO B5 For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Connect initially for correct connection and do below procedure. 5) Increase alternator filed supply upto 20% of scale. 6) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 7) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 8) Now stable condition is achieved. S.R.C.O.E, PUNE Page 33

34 9) Now push the reset push button Green and Red both to reset the relays. 10) Now the load will get connected. 11) For correct connection the relay will not trip. 12) For incorrect connection repeat the above procedure from 4) to 8). 13) As the Negative phase sequence is achieved hence the relay trip and the load does notget connected and the fault lamp glows. Testing of Over Current Relay: Connect: R1 TO R6 R7 TO R2 Y1 TO Y2 B1 TO B2 For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 6) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 7) Now stable condition is achieved. 8) Now push the reset push button Green and Red both to reset the relays. 9) Now the load will get connected. 10) Now switch ON the load switch. And increase the DC Voltage upto 208V DC and Alternator voltage to 415V AC. 11) Now switch ON the second load switch. 12) Moment the second load switch is switched ON the relay trips and the complete set gets cut OFF as the alternator is over loaded. 13) And the over current lamp will glow. S.R.C.O.E, PUNE Page 34

35 14) Now Set all the excitation and Armature Voltage to zero position and load switches to OFF position and reset the relay by pushing the reset push button. Testing of EARTH FAULT Relay: Connect: R1 to R10 N1 to N3 Y1 to Y2 B1 to B2 For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 6) Now against increase filed excitation of alternator upto 415V AC output on AC 7) Voltmeter. 8) Now stable condition is achieved 9) Now push the reset push button Green and Red both to reset the relays. 10) Now the load will get connected. 11) Now switch ON the load switch. And increase the DC Voltage upto 208V DC and Alternator voltage to 415V AC 12) Now switch ON the Earth Fault simulating switch. The moment the switch Turns ON the earth fault relay trips and the load gets disconneted. Switch OFF the fault switch immediately. 13) Switch OFF the load and reset the relay. Testing of Reverse Power Relay: Faulty Connections: R1 TO R8 R9 TO R2 Correct Connections: R1 TOR9 R8 TO R2 S.R.C.O.E, PUNE Page 35

36 Y1 TO Y2 & B1 TO B2 Y1 TO Y2&B1 TO B2 For Testing of Above Protection: 1) Ensure Zero at Armature Voltage and Field voltage Control knob at Zero Position. 2) Switch ON the Mains MCB. 3) Mains ON indication will glow ON. 4) Increase alternator filed supply upto 20% of scale. 5) Give DC supply upto 208V DC to DC Shunt Motor by Armature control knob. 6) Now against increase filed excitation of alternator upto 415V AC output on AC Voltmeter. 7) Now stable condition is achieved. 8) Now push the reset push button Green and Red both to reset the relays. 9) Now the load will get connected. 10) Now switch ON the load switch. And increase the DC Voltage upto 208V DC and Alternator voltage to 415V AC. 11) For correct connection the relay will not trip. 12) For incorrect connection repeat the above procedure from 4) to 10). 13) As the Reverse flow of current is achieved hence the relay trip and the load get disconnected and the fault lamp glows. CONCLUSION: S.R.C.O.E, PUNE Page 36

37 SHREE RAMCHANDRA COLLEGE OF ENGG. LONIKAND PRACTICAL EXPERIMENT INSTRUCTION SHEET EXPERIMENT TITLE: STUDY & TESTING OF MCCB LABORATORY MANUAL EXPERIMENT NO. : SRCOE/ELECT/BE/SGP/08 SWITCHGEAR AND PROTECTION (403147) DEPT. : ELECTRICAL ENGINEERING SEMESTER : II (BE) PAGE:37-38 STUDY & TESTING OF MCCB AIM: To study MCCB & testing of MCCB APPARATUS :3 pole,600v AC,50 A 5KA(Breaking current rating) Switchgear testing kit. THEORY :MCCB is used extensively in low voltage domestic, commercial, industrial applications. Tripping mechanism & the terminal contacts are assembled in a moulded case. When this circuit breaker goes out of service, it has to be placed with a new one. PROCEDURE: 1.Connect MCCB to be tested as shown. 2.Connect the 4 core cable provided at the back of switchgear testing kit to supply. 3.Switch ON the supply. 4.Reset the timer. 5.Push the ON push button provided on the front panel of the switchgear testing kit. 6.Using variac adjust the current greater than the rated current of MCCB. 7.Push OFF button. 8.Put MCCB in ON position & reset timer. 9.Again push ON push button. 10.See the timer & note down the reading of timer when MCCB trips. 11.Push the OFF push button. 12.Repeat the steps from4 to 11, for tracking more reading to plot the characteristics. S.R.C.O.E, PUNE Page 37

38 OBSERVATION TABLE : Sr.No Operating Current (A) Time of Operation(Sec) CONCLUSION: From the graph it is clear that current verses time of operation characteristics of MCCB are inverse nature. i.e. if the current through the MCCB is more,time of operation required is less& vice versa. S.R.C.O.E, PUNE Page 38

39 S.R.C.O.E, PUNE Page 39

40 S.R.C.O.E, PUNE Page 40

41 S.R.C.O.E, PUNE Page 41

42 S.R.C.O.E, PUNE Page 42

43 S.R.C.O.E, PUNE Page 43

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

ELECTRICAL MAINTENANCE

ELECTRICAL MAINTENANCE ELECTRICAL MAINTENANCE II PRACTICAL JOURNAL DATA 1 EXPERIMENT NO. 1 AIM: TO FIND VOLTAGE RATIO OF A GIVEN TRANSFORMER. CIRCUIT DIAGRAM: OBSERVATION TABLE: Sr.No. 1 2 3 4 Primary Voltage (V 1 ) Secondary

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter Direct On Line (DOL) Motor Starter Direct Online Motor Starter Different starting methods are employed for starting induction motors because Induction Motor draws more starting current during starting.

More information

Electrical Control System Components Basics of Magnetic Control :

Electrical Control System Components Basics of Magnetic Control : Electrical Control System Components Basics of Magnetic Control : Dr.M.S.Narkhede, LEE, GP Mumbai 1 Contact Types : Contacts are classified into different ways as follows. According to applications contacts

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES PROK DEVICES PRIVATE LIMITED B-80, 2 nd & 3 rd Floor, KSSIDC Industrial estate, 4 th Main Road, 6 th Block, Rajaji Nagar, Bengaluru -560010 Ph no: 080-41480777, 080-41157700, Email:,, www.prokdvs.in DIP

More information

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS 1 Module 2 CONTROL SYSTEM COMPONENTS Lecture - 4 RELAYS Shameer A Koya Introduction Relays are generally used to accept information from some form of sensing device and convert it into proper power level,

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector. Starters Overview Siemens caters with following types of starters to agricultural and industrial sector. 55 Application The main purpose of motor starters is to start the electrical motor by switching

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1 University f Jordan School of Engineering Department of Mechatronics Engineering Electrical Machines Lab Eng. Osama Fuad Eng. Nazmi Ashour EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1 OBJECTIVES To

More information

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) 1. Which drawing type shows physical details as seen by the eye? 2. Which drawing is similar to a pictorial drawing but has

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

Ch 4 Motor Control Devices

Ch 4 Motor Control Devices Ch 4 Motor Control Devices Part 1 Manually Operated Switches 1. List three examples of primary motor control devices. (P 66) Answer: Motor contactor, starter, and controller or anything that control the

More information

Electric Motor Controls BOMA Pre-Quiz

Electric Motor Controls BOMA Pre-Quiz Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,

More information

MINIATURE CIRCUIT BREAKER

MINIATURE CIRCUIT BREAKER Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.

More information

The galvanic separation of the primary or actuating circuit and the load circuits

The galvanic separation of the primary or actuating circuit and the load circuits RELAY BASICS Relays are electro magnetically operated switches. An actuating current on a coil operates one or more galvanically separated contacts or load circuits. The electro mechanical relay is a remote

More information

(Miniature Circuit Breaker)

(Miniature Circuit Breaker) (Miniature Circuit Breaker) Features : l Uniform 10KA breaking capacity for B and C Curve l Low power consumption, thus cost effective & energy saving l Suitable for DC and for a wide frequency range of

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

Exercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers

Exercise 1-5. Current Protection Devices EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Circuit breakers Exercise 1-5 Current Protection Devices EXERCISE OBJECTIVE Describe and test the operation of circuit breakers, fuses, and overload relays. DISCUSSION OUTLINE The Discussion of this exercise covers the

More information

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay 41-106E Type CO-4 Step-Time Overcurrent Relay A core screw accessible from the top of the switch provides the adjustable pickup range. The IIT contacts are connected in the trip circuit to trip instantaneously.

More information

B CW POWER RELAY

B CW POWER RELAY 41-241.31B CW POWER RELAY nected in such a way that current, (I A ), leads voltage, (V BA ), by 150 degrees when the motor is operating at unity power factor. Loss of excitation to the motor causes a large

More information

Electrical Protection

Electrical Protection Electrical Protection Excessive current in any electrical circuit is hazardous and not desired, and these maybe caused by the following; 1. Overloads, and 2. Short-circuits. Overload Currents: These are

More information

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

320 to 327 M Series Low and Medium Voltage Motor Protection Relays 1. Protection Features 320 to 327 M Series Low and Medium Voltage Motor Protection Relays INSTALLATION AND SETTING UP PROCEDURE Overloading (for both cyclic and sustained overload conditions) Start stall

More information

2014 ELECTRICAL TECHNOLOGY

2014 ELECTRICAL TECHNOLOGY SET - 1 II B. Tech I Semester Regular Examinations, March 2014 ELECTRICAL TECHNOLOGY (Com. to ECE, EIE, BME) Time: 3 hours Max. Marks: 75 Answer any FIVE Questions All Questions carry Equal Marks ~~~~~~~~~~~~~~~~~~~~~~~~~~

More information

Miniature Circuit Breaker

Miniature Circuit Breaker Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.

More information

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION ABB Instruction Leaflet 41-163.2B Effective: January 1977 Supersedes I.L. 41-137.3A, Dated September 1974 ( ) Denotes Change Since Previous Issue Type CRQ Directional Negative Sequence Relay for Ground

More information

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram:

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram: Question Set(2017) Switch Gear & protection(5 th SEm) 1. What is fault in power system? Classify the fault. What are the bad effects of fault? 2. Define with example: Symmetrical fault and unsymmetrical

More information

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

Type CRN-1 Reverse Power Relay 50 and 60 Hertz ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-251.2P Effective: June 1991 Supersedes I.L. 41-251.2N Dated April 1988 ( )Denotes Change

More information

MX431 Generator Automatic Voltage Regulator Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator 1 1. SPECIFICATION Sensing Input Voltage Frequency 190 ~ 264 VAC Max, 1 phase, 2 wire 50 / 60 Hz, selectable

More information

Electrical Motor Controls (Fourth Edition)

Electrical Motor Controls (Fourth Edition) Electrical Motor Controls (Fourth Edition) 1. Which drawing type shows physical details as seen by the eye? Pictorial Drawing 2. Which drawing is similar to a pictorial drawing but has circles or rectangles

More information

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER EXPERIMENT CALIBRATION OF PHASE ENERGY METER THEORY:- Energy Meters are integrating instruments used to measure the quantity of electrical energy supplied to a circuit in a given time. Single phase energy

More information

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Introduction A contactor is an electrical device which is used for switching an electrical circuit on or off. It is considered to be a special type of relay. However, the basic difference between the relay

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Dev Bhoomi Institute Of Technology LABORATORY Department of Electrical And Electronics Engg. Electro-mechanical Energy Conversion II

Dev Bhoomi Institute Of Technology LABORATORY Department of Electrical And Electronics Engg. Electro-mechanical Energy Conversion II REV. NO. : REV. DATE : PAGE: 1 Electro-mechanical Energy Conversion II 1. To perform no load and blocked rotor tests on a three phase squirrel cage induction motor and determine equivalent circuit. 2.

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION 505 z 509 FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION The movable contacts are carried in stainless steel cages which in turn are mounted in cavities in the molded portion of the cross bar. This

More information

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Chapter 8 Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits. Article 430 of the NEC covers application and installation of

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave

AC Rectifiers for use with Armature Actuated Brakes. Product Overview. Full Wave. Half Wave. Combination Full and Half Wave. TOR-AC Full and Half Wave Rectifiers for use with Armature Actuated Brakes Product Overview NOTE: For brake response times with and without rectifiers see page 94. Full Wave A rectifier in which both positive and negative half-cycles

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 22 CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 3.1 INTRODUCTION A large number of asynchronous motors are used in industrial processes even in sensitive applications. Consequently, a defect can induce

More information

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4 CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power

More information

Functions provided by measuring relays in railway equipment

Functions provided by measuring relays in railway equipment Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch

More information

DISSECTIBLE TRANSFORMER - large

DISSECTIBLE TRANSFORMER - large DESCRIPTION: DISSECTIBLE TRANSFORMER - large Cat: EM1660-001 220/240V.AC. 50/60Hz. The IEC Dissectible Transformer is a very useful instrument for the teaching of transformer theory and many other AC phenomena.

More information

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines Department of Electrical Engineering Lecture Introduction to Electrical Machines 1 In this Lecture Induction motors and synchronous machines are introduced Production of rotating magnetic field Three-phase

More information

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2 Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand ( July 14-18, 2007) Lecture on L33-2 By S.N.Singh Senior Scientific officer ALTERNATE HYDRO

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012 SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet Effective: October 1999 Supersedes I.L. 41-133R, Dated August 1998 ( ) Denotes Changed Since

More information

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No. September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

DHANALAKSHMI COLLEGE OF ENGINEERING MANIMANGALAM. TAMBARAM, CHENNAI B.E. ELECTRICAL AND ELECTRONICS ENGINEERING

DHANALAKSHMI COLLEGE OF ENGINEERING MANIMANGALAM. TAMBARAM, CHENNAI B.E. ELECTRICAL AND ELECTRONICS ENGINEERING DHANALAKSHMI COLLEGE OF ENGINEERING MANIMANGALAM. TAMBARAM, CHENNAI B.E. ELECTRICAL AND ELECTRONICS ENGINEERING V SEMESTER EE2305 ELECTRICAL MACHINES II LABORATORY LABORATORY MANUAL 1 CONTENT S. No. Name

More information

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date: CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in

More information

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.

More information

Range of Starters... for Every Need CITATION STARTERS

Range of Starters... for Every Need CITATION STARTERS Range of Starters... for Every Need CITATION STARTERS A Range of Starters BCH manufactures a wide range of motor starters to suit every application in the field. The capacity starts from fractional horse

More information

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG TM is truly the next generation in medium voltage vacuum circuit breaker

More information

RECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS

RECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS RECOMMENDATIONS FOR USING FREQUENCY INVERTERS WITH POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS Contents Page 1 Scope and purpose... 1 2 General... 1 3 Operation... 2 4 Application ranges... 5 5 Design

More information

Ktec Contactors and thermal overloads

Ktec Contactors and thermal overloads Contactors and thermal overloads Techna KTEC series contactors provide a complete solution for your ac contactor requirements.the range carries TUV, UL & CSA certification, for use in Europe, North America

More information

SURE TRIP RETRO KITS

SURE TRIP RETRO KITS RMS CURRENT MEASUREMENT with SURE TRIP RETRO KITS Circuit Breaker Solid State Controls with SURE TRIP LOGIC The Sure Trip Solid State Tripping Systems Have Been Designed, Tested And Produced To all Applicable

More information

Motor Protection Fundamentals. Motor Protection - Agenda

Motor Protection Fundamentals. Motor Protection - Agenda Motor Protection Fundamentals IEEE SF Power and Energy Society May 29, 2015 Ali Kazemi, PE Regional Technical Manager Schweitzer Engineering Laboratories Irvine, CA Copyright SEL 2015 Motor Protection

More information

Power System Solutions (PSS)

Power System Solutions (PSS) About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and

More information

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products Station Automation & Protection Inverse-Time Overcurrent & /F Relays Type ICM, ICM B ABB Substation Automation Products Features the driving solenoid has tappings, corresponding to the seven stages of

More information

Electrical Machines-I (EE-241) For S.E (EE)

Electrical Machines-I (EE-241) For S.E (EE) PRACTICAL WORK BOOK For Academic Session 2013 Electrical Machines-I (EE-241) For S.E (EE) Name: Roll Number: Class: Batch: Department : Semester/Term: NED University of Engineer ing & Technology Electrical

More information

Euclid Full Voltage Magnet Controller

Euclid Full Voltage Magnet Controller Hubbell Industrial Controls, Inc. Euclid Full Voltage Magnet Controller Instruction & Renewal Parts Manual Instructions/Parts Manual Publication No. 180 Replaces Sept. 1991 4291 & 4295/ 96 Type 4291 Type

More information

CI-TI Contactors and Motor Starters Type CI 6-50

CI-TI Contactors and Motor Starters Type CI 6-50 Data sheet CI-TI Contactors and Motor Starters CI 6-50 CI-TI contactors and motor starters provide trouble-free switching and maximum protection for costly motors and other electrical equipment. The components

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information