Condenser Fan Pak Installation and Wiring Guide
|
|
- Avis Dickerson
- 6 years ago
- Views:
Transcription
1 Condenser Fan Pak Installation and Wiring Guide 2200IB1501 Make the most of your energy SM
2 Condenser Fan Pak: Installation and Wiring Guide p The purpose of this document is to illustrate the recommended field wiring and segregation of the different circuits within the Condenser Fan Pack (CFP). p The CFP shown in this document has 8 condenser fans/circuit (CFP Size 2). This is representative for all CFP panel installations. Your CFP may have fewer condenser fans/circuit than shown. p For illustration purposes, in this document only, different conductor colors are used to illustrate the different field-wired circuits within the CFP and the segregation needed between these different circuits: Blue Circuit #1 (VFD #1) motor load circuits Red Circuit #2 (VFD #2) motor load circuits Orange Bypass Circuit #1 (from OEM chiller panel) Black Bypass Circuit #2 (from OEM chiller panel) Yellow cables Supplied refrigerant sensor cables Gray cable Supplied outdoor air temperature sensor cable 2
3 Step 1: Carefully plan and layout the conduit entries into the bottom of the CFP panel and stagger the conduit entry hole penetrations (see Figure 1, Figure 2, and Figure 3) to enable: a. the most direct wiring to the respective field wired components within the CFP b. segregation of the different circuits c. installation of the electrical conduits The CFP Size 2 (free-standing) enclosure has a removable conduit entry plate. Refer to the CFP User Manual for complete installation instructions. For electrical wiring, refer to the CFP electrical schematic provided with the CFP for instructions and details. 3
4 Figure 1 Figure 3 Figure 2 (Return to Step 1) 4
5 Step 2: Wire the condenser fan motors for Circuit #2 (VFD #2 circuit). These circuits are at the rear of the CFP Size 2 panel. a. Remove terminal cover of motor overload relay by inserting a screwdriver into one of the openings of the overload terminal cover and pushing the terminal cover away from the overload relay (see Figure 4 and Figure 5). b. Cut the field wiring to the required length and insert conductors underneath the respective terminal clamp (see Figure 6). c. Support the back side of motor overload with your fingers while tightening terminal screw (see Figure 7). d. Reinstall motor overload terminal cover. 5
6 Figure 4 Figure 5 Figure 6 Figure 7 (Return to Step 2) 6
7 Step 3: Complete the field wiring for the remaining motor overloads of Circuit #2 (VFD #2). For illustration purposes, Red conductor wiring is used for the Circuit #2 motor loads. p Terminate the motor load ground conductors to the isolated ground bar designated VFD2 MTR GND. p Bundle the wiring of each motor circuit with tie-wraps and segregate the circuits (see Figure 8). Figure 8 7
8 Step 4: Route CFP power input supply wiring up along the right side wall of the CFP. p Cut the power wiring to the required length and terminate to the respective circuit breaker input terminals. p Terminate the supply ground wire to the main ground bar GND1. p Route, bundle, and secure wiring in place with tie-wraps (see Figure 9, Figure 10, Figure 11, and Figure 11a). Use the studs on the side wall to secure the power wire bundle in place as needed. Figure 9 Figure 10 Figure 11 Figure 11a 8
9 Step 5: Wire the condenser fan motors for Circuit #1 (VFD #1 circuit). These circuits are at the front of the CFP panel (see Figure 12). For illustration purposes, Blue conductor wiring is used for the Circuit #2 motor loads. Follow the same procedure as in Step 2 and Step 3. For Circuit #1 (VFD #1), terminate the motor load ground conductors to the isolated ground bar designated VFD1 MTR GND. Figure 12 9
10 Step 6: If the CFP has the Bypass option, wire the Bypass Circuit #2 conductors to the respective Bypass Circuit #2 terminal strip (see Figure 13). For illustration purposes, Orange conductor wiring is used for the Bypass Circuit #2 circuits. Figure 13 10
11 Step 7: If the CFP has the Bypass option, wire the Bypass Circuit #1 conductors to the respective Bypass Circuit #1 terminal strip (see Figure 14). For illustration purposes, Black conductor wiring is used for the Bypass Circuit #1 circuits. Route and bundle the Bypass conductors with tie-wraps to provide segregation from all other circuits. Figure 14 11
12 Step 8: The CFP may be provided with either two or four refrigerant sensors and cables, depending on chiller application. p Route the provided sensor cables through the provided cable glands. p Wire the Outdoor Air (Gray cable) and Refrigerant (Yellow cables) sensors to the respective terminals of the sensor terminal strip TSCNT (see Figure 15). p Route and bundle the sensor cables with tie-wraps to provide segregation from all other circuits (see Figure 16). p Tighten the cable gland fittings. 12
13 Figure 15 Figure 16 (Return to Step 8) 13
14 Step 9: Clean all debris from the bottom of the CFP. Bundle and secure circuit conductors with tie-wraps as needed to position and segregate circuits from all other circuits within the CFP (see Figure 17, Figure 18, and Figure 19). Figure 17 14
15 Figure 18 Figure 19 (Return to Step 9) 15
16 Schneider Electric USA, Inc Knightdale Blvd. Knightdale, NC USA Customer Care Center Tel: Schneider Electric Canada 5985 McLaughlin Rd. Missassauga, Ontario, Canada L5R 1B8 Canada Customer Care Center Tel: Schneider Electric. All rights reserved. Schneider Electric, and Make the most of your energy are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are property of their respective owners. Design: Schneider Electric Photos: Schneider Electric 2200IB1501, 02/2015
The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller
The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the
More informationAltivar 212 Drive. A variable speed AC drive for 1 to 100 HP, three-phase asynchronous motors. Make the most of your energy SM
Altivar 212 Drive A variable speed AC drive for 1 to 100 HP, three-phase asynchronous motors Discover an economical solution for centrifugal pumps and fans and achieve up to 50 percent savings on your
More informationSED2-BT300-XX-C09 Migration Kits. Product Numbers
Document No. 129-710 SED2-BT300-XX-C09 Migration Kits Product Numbers SED2-BT300-AB-C09 Migration Kit, SED2 FSAB 09 to BT300 FS4 * 208 Vac: Up to 3 hp 480 Vac: Up to 5 hp SED2-BT300-C4-C09 Migration Kit,
More informationAldi V4 & V V1.1 5/23/2014
Aldi V4 & V5 2012 2013 V1.1 5/23/2014 Aldi Control Techniques SK Series VFD & Hussmann MX Series MicroChannel Condenser Equipment Operation Component Orientation Control Wiring Programming and Start Up
More informationInstallation Instructions
CRLOWAMB039A00 CRLOWAMB040A00 CRTRXKIT002A00 ACCESSORY MOTORMASTER I HEAD PRESSURE CONTROL KIT 12.5 TON HEAT PUMP Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PRODUCT USAGE... 2 SAFETY
More informationANZI Transfer Switch and Generator Wiring Installation Addendum
ANZI Transfer Switch and Generator Wiring Installation Addendum Reference all appropriate documentation. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT CAN BE INSTALLED BY THE
More informationLow Oil Controller Installation and Operations Manual. CS SS07-A2 P/N Enclosure
Low Oil Controller Installation and Operations Manual CS-105-552-SS07-A2 P/N 174383 552 Enclosure 2/8 Table of Contents 1 System Layout 3 2 3 4 5 Installation Recommendations Connection Instructions Connection
More informationInstallation Instructions for Key Switch SNOWRATOR
2017 Installation Instructions for Key Switch SNOWRATOR We appreciate your purchase of L.T. Rich s Product. Please read carefully before Operating or detaching. AES L.T.RICH 6/15/2017 SHIPPING CONTENTS...
More informationTECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS
TECHNICAL BROCHURE BSPDDRIVE C U L US Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS Aquavar SPD variable speed, constant pressure pump controller
More informationCombo HPU Kidney Loop Motor
Serial #: See below Product Bulletin # DC-002 Combo HPU Kidney Loop Motor Serial numbers DC1041-DC1050, DC1052, DC1053, DC1055-DC1057, DC1062, DC1064, DC1068, DC1070, DC1072 Background The Combo HPU Part
More informationInstallation. InfraStruXure PDU 80kW PD80F6FK1-M-14 PD80F6FK1-M PD80G6FK1-M PD80G6FK1-M-14
Installation InfraStruXure PDU 80kW PD80F6FK1-M-14 PD80F6FK1-M PD806FK1-M PD806FK1-M-14 Contents Certified Electrician s Instructions... 1 How to Connect Utility Conductors and an Emergency Power Off
More informationControl Box Wiring For PRSstandard Tool
888-680-4466 ShopBotTools.com Control Box Wiring For PRSstandard Tool Copyright 2017 ShopBot Tools, Inc. page 1 Copyright 2017 ShopBot Tools, Inc. page 2 Table of Contents Introduction...5 Installation...5
More informationALTIVAR FLEX58 Chassis Drive Controller Product Selection
ALTIVAR FLEX58 Chassis Drive Controller Product Selection Class 8806 CONTENTS Description Page General Information and Selection....................................... 2 Specifications and Ratings...........................................
More informationSED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options
SED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options Product Description The SED2 Electronic Bypass (E-Bypass) Options are companion packages for the family of SED2 Variable Frequency Drives
More informationAir-Cooled Scroll Compressor Chillers Models AGZ 010A to AGZ 034A Models AGZ 026B to AGZ 130B. Revised Electrical Data Tables.
Supplement #1 -A, -B Air-Cooled Scroll Compressor Chillers Models 010A to 034A Models 026B to 130B Revised Electrical Data Tables Replaces Electrical Tables in PM -6, IOMM 1, and IOMM -5 Engineered for
More informationSingle and Parallel Installation
Single and Parallel Installation Smart-UPS VT 10 40 kva 380/400/415 V with Batteries American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American
More informationFM800R SERVICE PARTS
This parts list contains the service parts and wiring diagrams for this model. Check the model number in question to be sure that it is applicable to this parts list. Caution: This model ice maker has
More informationPRODUCT: Install Instructions, MV-1 C/O Std, With Aux Fan RELEASE DATE: 2/28/14 REVISION DATE: 9/30/2014 PART NUMBER: Rev C
Parts List (1) 01 000 027 Switch, 4 Position Blower (1) 04 000 007 Hose, 1/2 ID Drain, 6 (1) 01 000 087 Harn, Resistor (1) 04 000 078 Tube, Convo 1/2 x 24 (2) 01 000 136 Relay, 40 Amp (1) 04 000 015 Hose,
More informationTherm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual
Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 01/2015 Index Index 1 Electrical Requirements for Therm-L-Tec
More informationFlorham Park, NJ USA Call (ASCO) for sales or service
Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious
More informationAltivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit
Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit Instruction Bulletin 30072-453-27 Retain for future use. For Frame Sizes 2 5: ATV61H075M3, -HU15M3, -HU22M3, -HU30M3, -HU40M3,
More informationBD Dual Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE) Ford (5R110) & Chevy (Allison 1000) Transmissions
7 March 2018 1030606-DS Dual Transmission Cooler Instruction Manual (I-00214) 1 DOWNLOAD COLOR INSTALL MANUALS AT dieselperformance.com BD Dual Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE)
More informationACE AUDIO KIT P/N
ACE AUDIO KIT P/N 2879703 Application SPORTSMAN ACE MODELS Before you begin, read these instructions twice and check to be sure all parts and tools are accounted for. Please retain these installation instructions
More informationSingle and Parallel Installation. MGE Galaxy kva 208/220 V
Single and Parallel Installation MGE Galaxy 3500 10-30 kva 08/0 V American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corporation
More informationSPECTRACOOL Slim Fit Air Conditioners (Surface-Mount Units Only) Quick Start Operation Guide
SPECTRACOOL Slim Fit Air Conditioners (Surface-Mount Units Only) Quick Start Operation Guide Rev. D 2018 nvent PH 763 422 2211 nvent.com NOTE: Refer to the instruction manual for all other installation
More informationTrane Liqui-Flo Addendum. Instruction Manual D2-3415
Trane Liqui-Flo Addendum Instruction Manual D2-3415 The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations:!
More informationTeSys Enclosed Starters. Let TeSys ensure safety in your simple motor applications
TeSys Enclosed Starters Let TeSys ensure safety in your simple motor applications TeSys Innovative and intuitive solutions to protect, monitor and control The TeSys range is suitable for motor and power
More informationFROG-D 3P. FREQUENCY READOUT OF GENERATOR THREE PHASE GENERATOR DISPLAY MODELS: FDA700 for Delta Winding FDA710 for Star Winding
Document Number: XE-FDA7PM-R0A FDA700 Rev160509 FROG-D 3P FREQUENCY READOUT OF GENERATOR THREE PHASE GENERATOR DISPLAY MODELS: FDA700 for Delta Winding FDA710 for Star Winding FIRE RESEARCH CORPORATION
More informationCENTRIFUGAL CHILLER TECHNICAL DATA SHEET Job Name: Mt Healthy Junior Senior HS Date: 6/25/2009 Version: 06.12 Submitted By: Mary Wilking Unit Description: McQuay Model Number: WSC100MBJ72R/E4212-CE-3**/C3612-BLYY-2*****/R134-BAABM
More informationSymmetra PX kw 208 V. Installation 01/
Symmetra PX 10 40 kw 208 V Installation 01/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationProduct Manual MNX10015 / REV B MODEL SB142, SB242. Dual Output Series Switch Boxes
Product Manual MNX10015 / REV B MODEL SB142, SB242 Dual Output Series Switch Boxes Contents Section I Overview Introduction.... 2 Description... 2 Section II Installation Mounting... 3 Electrical Connections...
More informationCP (Vdc) CP (Milliamp) CP (Slidewire)
CP-91-456 (Vdc) CP-91-716 (Milliamp) CP-91-717 (Slidewire) Electronic General Instructions Application Electronic actuator drive is used to provide proportional control of an electric gear train actuator
More informationPBA Series Prelube Controls
VARNA Products Engineered Innovation PBA Series Prelube Controls Simple, Compact, Industrial Full featured control for running prelube from the control or from a remote station Easy internal wiring connections
More informationControl Box Wiring For PRSstandard Tool
888-680-4466 ShopBotTools.com Control Box Wiring For PRSstandard Tool Copyright 2018 ShopBot Tools, Inc. page 1 Table of Contents Introduction...5 Installation...5 Powering the PRSstandard Control Box...5
More informationAltivar 660 Drive Systems
Altivar 660 Drive Systems The Schneider Electric Altivar 660 Drive Systems provides a robust, packaged, adjustable-speed solution for commercial, industrial, and municipal applications. All ratings are
More informationCustomized drive solutions
Customized drive solutions Altivar 680 low-harmonic drive system 150 900 hp ND/125 700 hp HD altivardrives.com 2 altivardrives.com altivardrives.com 3 What will you get with drive systems? Whatever you
More informationINSTALLATION INSTRUCTIONS
TABLE OF CONTENTS GENERAL...2 SPECIFICATIONS...2 PACKAGE CONTENTS...2 PACKAGE CONTENTS: ACCESSORIES...3 REQUIRED TOOLS...3 ADD-ON COMPONENTS...3 CLOSURE MOUNTING...3 LOCK AND UNLOCK EXTERIOR DOOR...3 CABLE
More informationInstallation Tips for your Remote Start system (for RS4LX>GMBP for GM vehicles)
Installation Tips for your Remote Start system (for RS4LX>GMBP for GM vehicles) Thank you for purchasing your remote start from MyPushcart.com - an industry leader in providing remote starts to doit-yourself
More informationAir Conditioning Disconnects Molded Case Switch
Air Conditioning Disconnects Molded Case Switch Catalog 3150CT0401R08/09 2009 Class 3150 QO200TR QO200TRNM CONTENTS Description............................................. Page..........................................
More informationInstallation Guide. Kennedy Technology Group, Inc.
Installation Guide Harley-Davidson Amp Module - Base Kit Kennedy Technology Group, Inc. 614 Ridgeway, Rose Hill, Kansas 67133 - USA voice 316.776.1111 fax 316.776.9035 email:kennedy@cellset.com www.cellset.com
More informationGalaxy Installation 08/
Galaxy 5000 40 130 kva 480 V Installation 08/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to
More informationE.S.P. Embedded Sensing Probes for Motor Brushes
E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com
More informationSPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E
SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit C24YE MC24Y3E MR24Y3E1 SPECIFICATIONS TYPE COOL & HEAT INDOOR UNIT MC24Y3E OUTDOOR UNIT MR24Y3E1 COOLING CAPACITY 23,500-22,500
More informationCutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter
Operation, and Maintenance of the Instruction Bulletin Read and understand these instructions before attempting any installation, operation, or maintenance of the. This equipment shall be installed and
More informationBD Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE) Ford (All) & Chevy (Allison) Transmissions
20 September 2012 1030606 Transmission Cooler Instruction Manual 1 BD Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE) Ford (All) & Chevy (Allison) Transmissions P/N# 1030606-5/16 P/N# 1030606-3/8
More informationWMVE Series Rugged Wall Mounts
I N S T A L L A T I O N WMVE Series Rugged Wall Mounts C2253M-B (1/14) Important Notices IMPORTANT SAFETY INSTRUCTIONS 1. Read these instructions. 2. Keep these instructions. 3. Heed all warnings. 4. Follow
More informationSED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options
SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options Product Description The SED2 Conventional Bypass (C-Bypass) Options are companion packages for the family of SED2 Variable Frequency
More informationChevrolet Chevelle with Factory Air Control Panel Conversion Kit (473065)
an ISO 9001:2008 Registered Company 1966-67 Chevrolet Chevelle with Factory Air Control Panel Conversion Kit (473065) FAN HI INSIDE A/C OUTLETS COLD TEMPERATURE AIR OUTSIDE DEFROSTER DE-ICE HEATER HOT
More informationFord Mustang, Mercury Cougar with Factory Air OEM Control Panel Replacement Kit (474266)
an ISO 9001:2008 Registered Company 1967-68 Ford Mustang, Mercury Cougar with Factory Air OEM Control Panel Replacement Kit (474266) COOL HI 18865 Goll St. San Antonio, TX 78266 Phone: 210-654-7171 Fax:
More information1996 Aerostar/Ranger/Explorer
Page 1 of 11 Section 03-01B: Engine, 3.0L V-6 IN-VEHICLE SERVICE 1996 Aerostar and Ranger Vehicles Workshop Manual Water Pump SPECIAL SERVICE TOOL(S) REQUIRED Description Tool Number Fan Clutch Holding
More information2015 Current F150/Raptor Venom Side Steps Installation Instructions
2015 Current F150/Raptor Venom Side Steps Installation Instructions PREPARATION STEPS 1. Disconnect the negative terminal on the battery. Park the vehicle on level ground and set the emergency brake. 2.
More informationDesigned for the Street Proven on the Track
TDR Fuel and Timing Card Wiring Thank you for using our TDR Fuel and or Timing Cards (F/T). There are two options on how to wire the F/T cards. Our preferred method is to use our TDR Patch Harness as shown
More information1956 Ford Passenger Car Control Panel Conversion Kit (473150)
an ISO 900:2008 Registered Company 956 Ford Passenger Car Control Panel Conversion Kit (47350) 8865 Goll St. San Antonio, TX 78266 Phone: 20-654-77 Fax: 20-654-33 www.vintageair.com 900505 REV B 04/4/5,
More informationFlorham Park, NJ USA Call (ASCO) for sales or service
Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual
More informationCHEV PICK-UP
an ISO 9001: 2008 Registered Company 1964-66 CHEV PICK-UP WITHOUT AC w/ DELUXE CONTROL PANEL CONVERSION KIT 47264 DEF AIR FAN HEAT 90264 REV C 4/1/15, 1964-66 CHEV P-UP wo AC w/ DELUXE CONTROL PANEL KIT
More informationPontiac GTO with Factory Air Control Panel Conversion Kit (473167)
an ISO 900:008 Registered Company 964-67 Pontiac GTO with Factory Air Control Panel Conversion Kit (4767) DE-ICE HEAT OFF VENT OUT INSIDE 8865 Goll St. San Antonio, TX 7866 Phone: 0-654-77 Fax: 0-654-
More informationCertified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers
Certified for best-in-class performance, reliability, and safety Trihal sets a new standard for dry-type cast resin transformers Setting a new standard for dry-type cast resin transformers hospitals wind
More informationCHEV PICK-UP
an ISO 9001: 2008 Registered Company 1967-72 CHEV PICK-UP WITHOUT AC CONTROL PANEL CONVERSION KIT 47266 ACC-OFF-ON-START DEF AIR FAN HEAT 90271 REV D 4/1/15, 1967-72 CHEV P-UP wo AC CONTROL PANEL KIT PG
More informationInstallation Instructions
Installation Instructions Jeep JK Unlimited (2007 Present) Mounting Bracket and Air Line System Kit for ARB On-Board Twin Air Compressor (CKMTA12) Made in the USA Kit Contents: 1 Bracket for ARB Compressor
More information1963 Chevrolet Impala Control Panel Conversion Kit (471063)
an ISO 9001:2008 Registered Company 196 Chevrolet Impala Control Panel Conversion Kit (47106) 18865 Goll St. San Antonio, TX 78266 Phone: 210-654-7171 Fax: 210-654-11 www.vintageair.com 901065 REV E 01/12/16,
More information1969 Chevrolet Camaro with Factory Air Control Panel Conversion Kit (474269)
an ISO 900:2008 Registered Company 969 Chevrolet Camaro with Factory Air Control Panel Conversion Kit (474269) 8865 Goll St. San Antonio, TX 78266 Phone: 20-654-77 Fax: 20-654-33 www.vintageair.com 904269
More informationInnovative servo-based die transfer system helps manufacturers save costs and improve productivity for the high-demand automotive market
Schneider Electric Case Study DieBotics Grand Rapids, Michigan Innovative servo-based die transfer system helps manufacturers save costs and improve productivity for the high-demand automotive market The
More informationChevrolet Impala Control Panel Conversion Kit (471062)
an ISO 9001:2008 Registered Company 1961-62 Chevrolet Impala Control Panel Conversion Kit (471062) 20 30 40 50 60 70 80 90 100 110 120 C T E M P EF F U E L FAN DEF AIR HEAT 18865 Goll St. San Antonio,
More informationRS4 / RS7 + (4) + SPDT
TIP SHEET Installation Tips for RS4 / RS7 + Honda-SL3 (4) + SPDT + Diode x2 T0776, T0731 Honda: ( 08-12 Accord), ( 12-13 Civic), 12-13 CRV), ( 11-13 Odyssey), ( 09-13 Pilot) Acura: ( 09-13 TSX) Thank you
More informationPower Operated Retrofit Kit for Manual Door 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual
Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit for Manual Door 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 10/2014 Index Index 1 Electrical Requirements
More informationBD Dual Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE) Ford (5R110) & Chevy (Allison 1000) Transmissions
8 January 2013 1030606-DS Dual Transmission Cooler Instruction Manual 1 BD Dual Transmission Cooler Dodge (68RFE, 518, 47RH, 47RE & 48RE) Ford (5R110) & Chevy (Allison 1000) Transmissions P/N# P/N# 1030606-DS-1/2
More informationwiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
wiring diagrams SINGLE PACKAGE ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS 580F 036-150 3 to 12 1 / 2 Tons Cancels: New WD 580F.36.1 10/15/00 *Low NOx/California compliant units. DIAGRAM INDEX UNIT LABEL
More informationVertical Vinyl Curtain Door
Vertical Vinyl Curtain Door Face Mount Installation Instructions System Overview: Your Aleco Vinyl Vertical Curtain Door is a high quality, high performance flexible door system based on proven components
More informationChevrolet Chevelle with Factory Air Control Panel Conversion Kit (473063)
an ISO 9001:2008 Registered Company 1964-65 Chevrolet Chevelle with Factory Air Control Panel Conversion Kit (4706) COND TEMP DEF 18865 Goll St. San Antonio, TX 78266 Phone: 210-654-7171 Fax: 210-654-11
More informationNM650 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor...
This parts list contains the service parts and wiring diagrams for this model. Check the model number in question to be sure that it is applicable to this parts list. Caution: This model ice maker has
More informationSECTION MOTORS AND VARIABLE FREQUENCY DRIVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal
More informationEclipse 2000 Service Parts
This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior
More informationInstallation Instructions for Lingenfelter GM 2500 Suburban & Yukon XL Auxiliary Fan System (with AC clutch controlled fan output)
Installation Instructions for Lingenfelter 2007-2013 GM 2500 Suburban & Yukon XL Auxiliary Fan System (with AC clutch controlled fan output) PN L300080607 Revision - 1.1 Lingenfelter Performance Engineering
More informationW-VACiMB FIXED SECONDARY TERMINAL BLOCK OEM CONVERSION TYPE #2 RING-TYPE TERMINAL BLOCK
W-VACiMB FIXED SECONDARY TERMINAL BLOCK OEM CONVERSION TYPE #2 RING-TYPE TERMINAL BLOCK 1 of 41 PLEASE READ These instructions are provided so that an OEM can officially convert a W-VACiMB Mining Breaker
More informationTeSys Enclosed Starters. Let TeSys watch over your machinery
TeSys Enclosed Starters Let TeSys watch over your machinery Standard offer applications: Fans, blowers, ventilators Pumps: water pumps, heat pumps, etc. Compressors Elevators Automatic gates, roof window
More informationAcme Conduit Entry. String Combiner/Pass-Through. FOR PHOTOVOLTAIC INSTALLATION Installation Manual
Acme Conduit Entry String Combiner/Pass-Through FOR PHOTOVOLTAIC INSTALLATION Installation Manual Table of Contents Important Safety Instructions -----------------------------------------------------------------------------------------------------------
More informationIM K IM K. Instructions for Cutler-Hammer Jockey Pump Controllers
IM05805004K IM05805004K Instructions for Cutler-Hammer Jockey Pump Controllers IM05805004K Page i TABLE OF CONTENTS 1. INSTALLATION AND MOUNTING OF THE CONTROLLER... 1 2. SYSTEM PRESSURE CONNECTIONS...
More informationInstalling the Throttle Commander Ford F250 F550 Super Duty T L Diesel T L Diesel
Installing the Commander Ford F250 F550 Super Duty T500106 2005-2007 6.0L Diesel T500116 2008-2010 6.4L Diesel 1.0 Preparing for Installation...5 2.0 Installing the Control...5 2.1 2005-2007 T500106 Connecting
More informationCompany Switch Installation Instructions and User Manual
Lex Products Corporation 15 Progress Drive Shelton, CT 06484 203.363.3738 203.363.3742 Fax Lex West 11847 Sheldon Street Sun Valley, CA 91352 818.768.4474 818.768.4040 Fax www.lexproducts.com info@lexproducts.com
More informationHybrid XT Retrofit GE 1.5 SLE Turbines
NRG Retrofit Kits #5388 & #5389 Authors: Technical Services TABLE OF CONTENTS SUMMARY... 3 WARNING AND NOTICES... 3 GROUNDING AND MOUNTING CONSIDERATIONS... 3 TOOLS AND MATERIALS REQUIRED... 4 Materials...
More informationInstallation Instructions: ACCENT HIGH OUTPUT SYSTEM
Installation Instructions: ACCENT HIGH OUTPUT SYSTEM READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS WILL VOID YOUR WARRANTY! INSTALLATION TIPS
More informationSELECTRIC, INC. Selectric (PX) Full Voltage Type Motor Control Panel Installation And Operation Manual
SELECTRIC, INC. Selectric (PX) Full Voltage Type Motor Control Panel Installation And Operation Manual Table of Contents I. Description of Equipment Page 3 II. Description of Operation 3 III. Installation
More informationMcQuay. Evaporative Condenser Cooled Chiller. EGR Vintage A. Last Manufactured: Replacement Parts List No Revision B 07/2010
Replacement Parts List No. 700015100 Revision B 07/2010 McQuay Evaporative Condenser Cooled Chiller EGR 060-240 Vintage A Last Manufactured: 2004 To find your Daikin Applied parts distributor, call 1-800-377-2787
More informationSCM-Power Distribution PLUS system Installation and User Instructions:
SCM-PD-PLUS shown with optional SCM-WC-SN wireless controller installed SCM-Power Distribution PLUS system Installation and User Instructions: Page 1 SCM-PD-PLUS includes: 1 NEMA Box with Power distribution
More informationLighting Control Unit Installation Instructions
Lighting Control Unit Installation Instructions DOC. #560066000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements
More informationACE Variable Frequency Drive System
ACE Variable Frequency Drive System Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IF 1690 BLOWER COOLING INTAKE SHROUDS BLOWER FUSE BLOCK TEMPERATURE CONTROLLER TRANSFORMER
More informationChevrolet Chevelle without Factory Air Control Panel Conversion Kit (473066)
an ISO 9001:2008 Registered Company 1966-67 Chevrolet Chevelle without Factory Air Control Panel Conversion Kit (473066) COLD TEMPERATURE FAN ON HOT DEFROSTER DE-ICE 18865 Goll St. San Antonio, TX 78266
More informationInstalling the Throttle Commander
Installing the Throttle Commander Ford 6.0L Diesel Powerstroke 2005-2007 F250-550 Super Duty 2005-2010 E250-550 Econoline (8500+ GVW) Ford 6.4L Diesel Powerstroke 2008-2010 F250-550 Super Duty T500107
More informationInstalling Power Components
This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco
More informationProduct Manual MNX10043 REV 0 MODEL DSB. Dual Sensor Modular Switch box
Product Manual MNX10043 REV 0 MODEL DSB Dual Sensor Modular Switch box Contents Section I Overview Introduction..... 2 Description 2 DSB Model Selection.. 2 Section II Installation Mounting Instructions....
More informationChevrolet Full-Size 3-Lever Control Panel Conversion Kit (473059)
an ISO 900:2008 Registered Company 955-56 Chevrolet Full-Size -Lever Control Panel Conversion Kit (47059) 8865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support:
More informationILISP610-A Shift Interlock Chevy/GMC Full Size Van Chevy/GMC Full Size Van L Contact InterMotive for specific applications
An ISO 9001:2008 Registered Company ILISP610-A Shift Interlock Chevy/GMC Full Size Van 2008-2018 Chevy/GMC Full Size Van 2008-2015 4.6L Contact InterMotive for specific applications Introduction The ILISP610-A
More informationInstallation Manual. E-design A Transfer Switches A
ASCO 3ATS & 3NTS 3ATS & 3NTS E-design 260-400 A Transfer Switches DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury. is used in this
More informationHardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN
Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN February 2004 CNT-SVN02B-EN Tracer AH541
More informationATTENTION. Custom Dynamics UTV Turn Signal Kit Installation Instructions
Custom Dynamics UTV Kit Installation Instructions We thank you for purchasing the Custom Dynamics UTV LED Kit. Our products utilize the latest technology and high quality components to ensure you the most
More informationInstallation Instructions: ACCENT SYSTEM
Installation Instructions: ACCENT SYSTEM READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS WILL VOID YOUR WARRANTY! INSTALLATION TIPS Read this entire
More informationSunwize Power Ready Express Quick Start
Document # 310002 Sunwize Power Ready Express Quick Start The purpose of this guide is to assist you in setting up your system quickly and efficiently. Important! Prior to field installation Determine
More informationIntelliTouch Expansion Center Kit
pool/spa control system IntelliTouch Expansion Center Kit Installation Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS 2005 Pentair Water Pool and Spa, Inc.
More informationREPLACEMENT PARTS MANUAL
REPLACEMENT PARTS MANUAL WAA-C Wall-Mount Air Conditioner with 0- VFD-High Resistance Ground Kit NOTE: For installation guidance for the 0- kit, contact Bard Technical Services at () -0. Contents Description
More information