Report Number BTC 12024F

Size: px
Start display at page:

Download "Report Number BTC 12024F"

Transcription

1 Report Number BTC F A FIRE RESISTANCE TEST ON A GYPROC GYPWALL PARTITION INCORPORATING A DOUBLE LAYER OF mm SOUNDBLOC EACH SIDE OF S STUDS, CONDUCTED IN ACCORDANCE WITH BS EN 4:999. Test Date: 9 th June Customer: Leicestershire LE 6HX Customer: BTC F: Page of

2 A FIRE RESISTANCE TEST ON A GYPROC GYPWALL PARTITION INCORPORATING A DOUBLE LAYER OF mm SOUNDBLOC EACH SIDE OF S STUDS, CONDUCTED IN ACCORDANCE WITH BS EN 4:999. TABLE OF CONTENTS FOREWORD REPORT AUTHORISATION TEST CONSTRUCTION 4 TEST MATERIALS 6 Gyproc SoundBloc 6 Metal Components 6 Fasteners 6 Jointing Material 6 TEST PROCEDURE 7 TEST RESULTS 7 LIMITATIONS 8 TEST DATA 9 Observations 9 Furnace Temperature Graph Unexposed Face Temperature Graph 4 Pressure Graph Unexposed Face Layout 6 Unexposed Face Standard Five Temperature Data 7 Additional Unexposed Face Temperature Data Additional Internal Temperature Data 6 Specimen Lateral Deflection PHOTOGRAPHS Customer: BTC F: Page of

3 FOREWORD This test report details a fire resistance test conducted on a sheet and stud partition system. The test sponsor was. The test specimen was installed by British Gypsum. The construction of the specimen took place between the st and nd May. designed and selected the materials comprising the test specimen. The test date was carried out on the 9 th June. This report details the method of construction, the test conditions and the results obtained when the specific element of construction described herein was tested following the procedures outlined in EN, and where appropriate EN. Any significant deviation with respect to size, constructional details, loads, stresses, edge or end conditions other than those allowed under the field of direct application in EN 4 is not covered by this report. Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result. REPORT AUTHORISATION Report Author Authorised by Brian Willson Test Report Writer Eur Ing. Paul Howard BSc. (Hons.), CEng., MIOA Head of Laboratory will not discuss the content of this report without written permission from the test sponsor. retains ownership of the test report content but authorises the test sponsor to reproduce the report as necessary in its entirety only. Customer: BTC F: Page of

4 TEST CONSTRUCTION The specimen was constructed in a refractory concrete lined steel restraint frame having an opening of mm high x mm wide. Gypframe C channels were fixed to the head and base of the test aperture at 6mm centres with 6mm Hilti Hus fixings. Gypframe S studs were positioned at 6mm centres between the channels. The right hand stud viewed from unexposed face was not fixed to the perimeter test frame, but the gap between the stud and the lining was filled with a mm Rockwool Firebatt gasket. The left hand stud was fixed to the test frame at 6mm centres with 6mm Hilti Hus fixings. The framework was lined on both sides with a double layer of mm Gyproc SoundBloc. The inner layer was fixed around the perimeter with mm Gyproc Drywall screws at mm centres. The outer layer was fixed around the perimeter and within the field of the board with 4mm Gyproc Drywall screws. All boards were staggered between layers. Horizontal joints were positioned mm from the base for the outer layers on both the exposed and unexposed faces of the construction. Horizontal joints were positioned mm from the base for the inner layers on both the exposed and unexposed faces of the construction. A Gypframe GFS fixing strap was used behind the horizontal board joints in the outer layers. All joints were taped and filled using Gyproc Paper Joint Tape and Gyproc Joint Filler. All screw heads were spotted using Gyproc Joint Filler. Customer: BTC F: Page 4 of

5 Figure. Crosssection through the partition. The descriptions of individual components making up the test specimen were provided by the customer and were checked for accuracy wherever possible. Customer: BTC F: Page of

6 TEST MATERIALS Gyproc SoundBloc Nominally, mm (long) x mm (wide) x mm (thick), Gyproc SoundBloc Wallboard manufactured and supplied by ex Works. Measured surface density:. kg/m. Measured thickness: 4.76 mm. Board identification numbers: 8: Measured moisture content:.% The surface density and board thickness were calculated using the actual weight and size of a selection of boards used in the test specimen. The moisture content of the board was determined using samples dried to a constant weight in an oven at 4 o C. Metal Components (i) (ii) (iii) Gypframe S metal studs. Manufactured from galvanised mild steel nominally.mm thick using the Ultrasteel process. Gypframe C metal channel. Manufactured from galvanised mild steel nominally.mm thick. Gypframe GFS fixing strap manufactured from galvanised mild steel nominally.mm thick. All metal components supplied by. Fasteners (i) (ii) (iii) mm Gyproc Drywall screws supplied by. 4mm Gyproc Drywall screws supplied by. 6mm Hilti Hus fixings supplied by Hilti Limited. Jointing Material (i) (ii) Gyproc Joint Filler supplied by. Gyproc Paper Tape supplied by. Customer: BTC F: Page 6 of

7 TEST PROCEDURE The test was conducted fully in accordance with BS EN 4:999. The specimen was subjected to fire from one side, as specified in BS EN 4:999. As the test specimen is considered to be symmetrical one test is adequate to cover the fire resistance performance in both directions. The test procedure used was EN 4 Issue. The ambient temperature at the commencement of the test was o C. The furnace pressure was maintained at 8 ± Pa positive with respect to atmosphere, at the top of the specimen, except during the first minutes of the test. The test conditions did not meet the full requirements of BS EN :999 as the furnace linings and test frame stiffness did not fully comply. The test centre is of the opinion that these deviations from the documented method will not unduly effect the result of the test. TEST RESULTS The requirements of the standard were satisfied for the following periods: Integrity: minutes (6mm x mm gap gauge) minutes (mm gap gauge) Insulation: 99 minutes (thermocouple N o exceeded 8 deg C.) The test was terminated at minutes. Customer: BTC F: Page 7 of

8 LIMITATIONS The results only relate to the behaviour of the specimen of the element of construction under the particular conditions of test; they are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they reflect the actual behaviour in fires. The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. Customer: BTC F: Page 8 of

9 TEST DATA Observations Observers: Unexposed face R Evans / L Cooper Exposed face K Hall hrs Observations mins All observations refer to the exposed face unless otherwise stated. Test Started 4 Jointing material started to fall away from the horizontal and vertical joints. Vertical crack on lower centre board 6mm in from joint, 6mm long open to approximately mm. Vertical crack on lower centre board (top left hand corner) approximately mm from left hand joint and approximately mm long. 6 Vertical cracking occurred on the lower centre board. 8 Vertical cracking near the top left of the lower right hand board. Horizontal cracking on the upper right hand board. Vertical cracking approximately mm in length on upper right hand board. Vertical joints where exposed open to 8mm. Horizontal joint where exposed open to 8mm. Vertical crack in lower centre board 6mm in from joint, 6mm long, now open to mm. Vertical cracking the full height of left hand lower board. More taper cracking open to approximately mm on lower centre board. Vertical cracking to upper left and upper centre boards. Horizontal cracking open to mm on all three lower boards. Vertical cracking open to mm on lower centre board. Customer: BTC F: Page 9 of

10 hrs Observations mins All observations refer to the exposed face unless otherwise stated. Horizontal and vertical joints open to approximately mm. Board fall from lower centre board adjacent to right hand joint approximately mm long x mm wide. 7 Cracking of inner layer where exposed. 9 Board fall from lower left hand board approximately mm x 6mm and from lower centre board, top left hand side approximately 6mm x 6mm. Inner vertical joint open to mm, studs exposed. Inner layer board bowing into cavity between studs to full depth of stud. 4 Inner layer board fall from top left of upper centre board. Vertical cracking of inner layer of unexposed side where exposed approximately mm x mm wide. 8 Voids in board core showing as popping of paper liner occurred when heated. Inner layer board fall on right hand side of upper centre board approximately 6mm wide x mm long. Inner layer board fall, left hand side of upper right hand board approximately 6mm x mm. Stud distortion at midheight to approximately mm x mm long on all exposed studs Unexposed face The bonding material came away bottom right hand corner of specimen. Customer: BTC F: Page of

11 Observations hrs mins All observations refer to the exposed face unless otherwise stated. Stud distortion at height to mm x mm on all exposed studs. Vertical cracking exposed the board core approximately mm either side of the studs where exposed, open to approximately mm. Unexposed face Screwhead discolouration on right hand vertical joint at / height. 8 Unexposed face Furnace glow was visible from midheight at the free end. 9 Horizontal cracking in inner layer unexposed open to approximately mm and 6mm long. Unexposed face Screwhead discolouration on left hand vertical joint above midheight. Horizontal and vertical cracking to approximately 8mm. Unexposed face Horizontal crack under paper liner, approximately mm long, 8mm high on centre board. Board fall unexposed face inner layer at approximately high, mm in from free end (approximately mm x mm). Unexposed face Horizontal crack under paper liner, approximately mm long, mm high on right hand board. Board fall, total area approximately 6mm wide x mm long. Voids in board core showing on outer layer unexposed face as popping of paper liner occurred. Unexposed face Discolouration on centreboard centre at midheight. Customer: BTC F: Page of

12 Observations hrs mins All observations refer to the exposed face unless otherwise stated. Unexposed face INSULATION FAILURE. The temperature rise on thermocouple No. exceeded 8 o C. 4 Unexposed face A cotton pad was applied to horizontal crack on centre board at 8mm height, midwidth of specimen. It did not glow or ignite. 4 Unexposed face The horizontal crack on centre board at 8mm height midwidth of specimen was now open approximately 4mm. A cotton pad was again applied but did not glow or ignite. Paper liner glowing. 4 Unexposed face INTEGRITY FAILURE. 6mm x mm gap gauge at horizontal crack on centre board at 8mm height midwidth of specimen through to furnace. INTEGRITY FAILURE. mm diameter gap visually observed at same position. TEST TERMINATED. Customer: BTC F: Page of

13 Furnace Temperature Graph 9 7 Temperature C Mean Furn Temp minutes Standard Furn Temp Figure. Furnace temperature graph Customer: BTC F: Page of

14 Unexposed Face Temperature Graph 4 Temperature C Mean St Temp minutes Max Unex Temp Figure. Unexposed face temperature graph. Customer: BTC F: Page 4 of

15 Pressure Graph Pressure Pa minutes Figure 4. Pressure graph. Customer: BTC F: Page of

16 Unexposed Face Layout mm down and mm in from vertical joint mm down at midwidth of specimen 6 mm down at centre of stud mm above horizontal joint at midwidth KEY: Standard Five mm down, mm from vertical joint and mm from horizontal joint Standard Five Standard positions Additional positions Outer Layer Board Joints Inner Layer Board Joints Stud positions mm from fixed edge and at midheight of the specimen mm from vertical joint at midheight of specimen Centre of stud at midheight mm from free edge at midheight of the specimen Standard Five Standard Five Standard Five Free end Exposed Face Internal s at mm height Left Stud Right Stud Unexposed Face Figure. Unexposed face thermocouple layout. Customer: BTC F: Page 6 of

17 Unexposed Face Standard Five Temperature Data Temperature Rise ( o C) (mins) No No No No No Customer: BTC F: Page 7 of

18 Temperature Rise ( o C) (mins) No No No No No Customer: BTC F: Page 8 of

19 Temperature Rise ( o C) (mins) No No No No No See figure for thermocouple layout Customer: BTC F: Page 9 of

20 Additional Unexposed Face Temperature Data Temperature Rise (ºC) (mins) No No No No No No Customer: BTC F: Page of

21 Temperature Rise (ºC) (mins) No No No No No No Customer: BTC F: Page of

22 Temperature Rise (ºC) (mins) No No No No No No See figure for thermocouple layout. Customer: BTC F: Page of

23 Additional Unexposed Face Temperature Data (continued) Temperature Rise (ºC) (mins) No No No Customer: BTC F: Page of

24 Temperature Rise (ºC) (mins) No No No Customer: BTC F: Page of

25 Temperature Rise (ºC) (mins) No No No See figure for thermocouple layout. Figures shown in red indicate insulation failure. Customer: BTC F: Page of

26 Additional Internal Temperature Data Actual Temperature (ºC) Stud Stud (mins) Hot Flange No Web No Cold Flange No Hot Flange No Web No Cold Flange No Customer: BTC F: Page 6 of

27 Actual Temperature (ºC) Stud Stud (mins) Hot Flange No Web No Cold Flange No Hot Flange No Web No Cold Flange No Customer: BTC F: Page of

28 Actual Temperature (ºC) Stud Stud (mins) Hot Flange No Web No Cold Flange No Hot Flange No Web No Cold Flange No Customer: BTC F: Page of

29 Actual Temperature (ºC) Stud Stud (mins) 4 Hot Flange No. Web No. Cold Flange No. Hot Flange No. Web No. Cold Flange No. See Figure for the location of the thermocouples. No. did not work after 89 minutes. No. did not work after 9 minutes. No. did not work after 9 minutes. No. did not work after 88 minutes. No. did not work after 86 minutes. No. did not work after 8 minutes. Customer: BTC F: Page of

30 Specimen Lateral Deflection Deflection (mm) (mins) Centrally On free end Customer: BTC F: Page of

31 Deflection (mm) (mins) Centrally On free end Customer: BTC F: Page of

32 Deflection (mm) (mins) Centrally On free end The deflection was recorded at the approximate centre of the specimen and at midheight on the free edge. Positive readings indicate deflection into the furnace. The deflection transducers were removed after 88 minutes. Customer: BTC F: Page of

33 PHOTOGRAPHS Photo. Exposed face prior to test. Customer: BTC F: Page of

34 Photo. Unexposed face prior to test. Customer: BTC F: Page of

35 Photo. Insulation failure on the centre board at hour minutes. The temperature rise on thermocouple No exceeded 8 o C. Customer: BTC F: Page of

36 Photo 4. View of the unexposed face after test termination showing area of insulation and integrity failure. Customer: BTC F: Page of

Report Number BTC 12261F

Report Number BTC 12261F Report Number BTC 6F A FIRE RESISTANCE TEST ON A 5m HIGH X m WIDE GYPROC SHAFTWALL SYSTEM INCORPORATING A 6mm METAL STUD FRAMEWORK CLAD WITH A DOUBLE LAYER OF 5mm GYPROC FIRELINE, EXPOSED TO THE FIRE FROM

More information

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date:

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date: Title: Fire Resistance Test In Accordance With BS EN 1364-1: 1999 On A Glazed Screen Assembly WF Report No: 164311, Prepared for: AGC Flat Glass Europe. Chaussee de la Hulpe 166 1170 Brussels. Date: 19

More information

Title: Fire resistance test in accordance with BS EN : 2008 on an uninsulated, face fixed rolling shutter doorset. Report No: Prepared for:

Title: Fire resistance test in accordance with BS EN : 2008 on an uninsulated, face fixed rolling shutter doorset. Report No: Prepared for: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Fire resistance test in accordance

More information

Title: WF Report No:

Title: WF Report No: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance

More information

WF Report No: Prepared for: Rohden UK Ltd Unit 2, Hayleys Manor Farm Upland Road, Epping Upland, Essex, CM16 6PQ. Date: Notified Body No:

WF Report No: Prepared for: Rohden UK Ltd Unit 2, Hayleys Manor Farm Upland Road, Epping Upland, Essex, CM16 6PQ. Date: Notified Body No: Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012

Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN : Report No: A

Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN : Report No: A Title: The fire resistance performance of a specimen of single-acting single-leaf doorset in accordance with BS EN 1634-1: 2000 Report No: 163712 A Prepared for: Novoferm GmbH Haldern Isselburger Str.

More information

InnoBYG small scale demonstration tests - Part 2

InnoBYG small scale demonstration tests - Part 2 Test report InnoBYG small scale demonstration tests - Part 2 File Serial No.: 2 Ref.: TDJ/AND Pages: 17 Enclosures: 31 2014-03-18 Date: 2014-07-09 Jernholmen 12, DK-2650 Hvidovre Phone: +45 36 34 90 00,

More information

Introduction. Our Ref: Chilt/IF12041 AR1. 24 th June Astra Door Controls Ltd Unit 10 Astra Business Centre Roman Way Preston PR2 5AP

Introduction. Our Ref: Chilt/IF12041 AR1. 24 th June Astra Door Controls Ltd Unit 10 Astra Business Centre Roman Way Preston PR2 5AP Chiltern House Stocking Lane Hughenden Valley High Wycombe Buckinghamshire HP14 4ND UK t +44 (0) 1494 569 800 f +44 (0) 1494 564895 e cif@chilternfire.co.uk w www.chilternfire.co.uk Our 24 th June 2012

More information

InnoBYG small scale demonstration tests - Part 1

InnoBYG small scale demonstration tests - Part 1 Test report InnoBYG small scale demonstration tests - Part 1 File FUN0001 Serial No.: 1 Ref.: TDJ/AND Pages: 18 2013-12-11 Date: 2014-01-20 Jernholmen 12, DK-2650 Hvidovre Phone: +45 36 34 90 00, Fax:

More information

No. Pr FIRE RESISTANCE TEST REPORT. Issued on: AUTHORIZED BODY AO 216. Project No: (Z )

No. Pr FIRE RESISTANCE TEST REPORT. Issued on: AUTHORIZED BODY AO 216. Project No: (Z ) Project No: 1 04 177 (Z210040305) AUTHORIZED BODY AO 216 TEST LABORATORY IN VESELÍ NAD LUŽNICÍ Accredited Test Laboratory - accreditation issued by the Czech Institute for Accreditation, o. p. s. Registered

More information

NFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia

NFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia NFPA 285 TEST REPORT Report No.: H1152.01-121-24 Test Date: June 1, 2017 Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia WALL SYSTEM: Exterior Non-loadbearing Wall Assembly COMBUSTIBLE COMPONENTS:

More information

Sound-absorbing spacer Sorp10

Sound-absorbing spacer Sorp10 Sponsor: Reference number: 7.3 / 27080 This document is only a translated version; not legally attested Max Frank GmbH & Co. KG Mitterweg 1 94339 Leiblfing Federal Institute for Materials Research and

More information

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c.

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c. 56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM Email: testing@inspec-international.com Website: www.inspec-international.com Tel: +44 (0) 16 17 37 06 99 Fax: +44 (0) 16 17 36 01 01

More information

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH

NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH Contego Latex Fire Barrier Intumescent (Also marketed in Canada by Pyrologistics,

More information

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference:

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference: Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN 14351-1:2006 Test

More information

Multideck 50-V2 Features and Applications

Multideck 50-V2 Features and Applications Features and Applications is a dovetail profile deck with a depth of 50mm providing spans up to 4m unpropped. Greater Design Efficiency The larger range of Multideck gauge thicknesses available allow much

More information

Urban Wildfire Interface: Exterior Wall Wildfire Testing

Urban Wildfire Interface: Exterior Wall Wildfire Testing Urban Wildfire Interface: Exterior Wall Wildfire Testing PN# 04018 Conducted for: WILDLAND FIRE TASK GROUP TESTING CONDUCTED ON APRIL 5 AND MAY 6, 2004 REPORT ISSUED ON: APRIL 25, 2004 Kelso, Washington

More information

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY GUIDANCE NOTE No. 60 SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY 1. Introduction The Solvents Industry Association has issued this Guidance Note because of the specific

More information

ARCONIC ARCHITECTURAL PRODUCTS FIRE TEST REPORT

ARCONIC ARCHITECTURAL PRODUCTS FIRE TEST REPORT ARCONIC ARCHITECTURAL PRODUCTS FIRE TEST REPORT SCOPE OF WORK CAN/ULC S134, STANDARD METHOD OF FIRE TESTS OF EXTERIOR WALL ASSEMBLIES CONTAINING ARCONIC REYNOBOND RB-160-FB REPORT NUMBER 103413434SAT-003

More information

Torus Coil. Construction and Geometry for Modeling. D. Kashy CLAS12 Collaboration Meeting March 6, 2018

Torus Coil. Construction and Geometry for Modeling. D. Kashy CLAS12 Collaboration Meeting March 6, 2018 Torus Coil Construction and Geometry for Modeling D. Kashy CLAS12 Collaboration Meeting March 6, 2018 Introduction We all know in general what the CLAS12 Torus is In this talk I will attempt to explain

More information

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006 FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. AUGUST 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Stainless Steel Side Seals. Constant Tension Stainless Steel

More information

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. FEBRUARY 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Optional Stainless Steel Side Seals. Constant Tension Stainless

More information

Godkjennelsesdokumenter for art. 4509, 4511

Godkjennelsesdokumenter for art. 4509, 4511 Godkjennelsesdokumenter for art. 4509, 4511 Innholdsliste: Samsvarserklæring side 2 SINTEF Produktdokumentasjon 050-0204 side 3 Efectis Nederland BV branntestunderlag side 8 Efectis Nederland BV testrapport

More information

The FRACOF Composite Slab Test

The FRACOF Composite Slab Test The FRACOF Composite Slab Test Experiment, Predictions & Results Anthony Abu & Ian Burgess Fire Resistance Assessment of partially protected COmposite Floors - FRACOF Introduction To increase the use of

More information

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist.

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist. DC1333 Testing of aier Plasterboard to AS/NZS 2588 (Electronic copy (PDF format) original signed by author) Author: Neil Lee Materials Scientist Reviewer: ryan Keen Senior Technician Contact: RANZ Limited

More information

Multideck 80-V2 Features and Applications

Multideck 80-V2 Features and Applications Features and Applications is designed to incorporate all the advantages of the Multideck 60-V2 but in a deeper profile to provide longer spans up to 5.4m unpropped. Concrete Volume Savings Due to its unique

More information

Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 08 / Hilti Firestop Collar CFS-C P

Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 08 / Hilti Firestop Collar CFS-C P Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P European Technical Approval ETA N o 10/0404 Issue 08 / 2015 Hilti Firestop Collar CFS-C P Issue 02/2015 page 1 General information

More information

Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515

Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515 Certifikat och provningsprotokoll för art. 4512, 4513, 4514 och 4515 Innehållsförteckning: Declaration of conformity... sid 2 SINTEF Produktdokumentation... sid 3 Efectis Nederland BV Brandtestunderlag...

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4212.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.118 thickness PC smooth/0.118 thickness

More information

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket Report No: Report Date: 10/31/12 130 Derry Court York, PA 17406-8405 phone:

More information

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 *

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * PRODUCT: Heavy Duty Stock Car Steel Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

13 th December Title: The Fire Resistance Performance Of Doorsets When Fitted With Perko Powermatic R100 Jamb Mounted Concealed Door Closers

13 th December Title: The Fire Resistance Performance Of Doorsets When Fitted With Perko Powermatic R100 Jamb Mounted Concealed Door Closers Warringtonfire Holmesfield Road Warrington WA1 2DS T: +44 (0)1925 655 116 F: +44 (0)1925 655 419 info.warrington@warringtonfire.com warringtonfire.com Title: The Fire Resistance Performance Of Doorsets

More information

CREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System

CREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System Architectural Testing CREEP PERFORMANCE TEST REPORT Rendered to: TREX COMPANY LLC Seclusions Composite Privacy Fence System TYPE: Composite Fence System Report No.: Report Date: Expiration Date: 130 Derry

More information

APPENDIX D. D.1 Macalloy Bars. Approximate safe working loads (kn) Appendix D - Proprietary Components (1/9) Stainless steel architectural ties

APPENDIX D. D.1 Macalloy Bars. Approximate safe working loads (kn) Appendix D - Proprietary Components (1/9) Stainless steel architectural ties Appendix D - Proprietary Components (1/9) APPENDIX D D.1 Macalloy Bars Bar dia. mm Stressing ties Stainless steel stressing ties Stainless steel architectural ties High strength Tie rods grades precision

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6458.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: Fiberglass In Swing Glazed Double Doors SERIES/MODEL:

More information

Multideck 60-V2. Contents

Multideck 60-V2. Contents The original and still the most popular deck in the market is a 60mm high, structurally efficient trapezoidal profile providing an excellent composite union between steel and concrete to maximise the load

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6839.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Double Doors with Speak Easy

More information

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT:

REPORT HOLDER: CLARKDIETRICH BUILDING SYSTEMS 9050 CENTRE POINTE DRIVE, SUITE 400 WEST CHESTER, OHIO EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1464 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 05 00

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6457.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Door with Side Lites SERIES/MODEL:

More information

DURAREEL TRAILING REELING CABLE

DURAREEL TRAILING REELING CABLE Supplementary Technical Information Reeling and trailing material characteristics: A. Power core conductor Flexible strands tinned annealed copper complies with AS/NZS 1802, AS/NZS 2802, AS/NZS 1125, and

More information

FUSELAGE ASSEMBLY SECOND SECTION (of three)

FUSELAGE ASSEMBLY SECOND SECTION (of three) FUSELAGE ASSEMBLY SECOND SECTION (of three) 1 FRONT FLOOR ASSEMBLY The front floor assembly is fabricated from three pieces of the two ply pre-pregnated panel material supplied. The basic floor panel and

More information

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Page 1 of 6 APPLICATION These dynamically rated fire/smoke and fire s are intended to restrict

More information

Bracket U Value at 1.5M Centres. 265mm 275mm 295mm 300mm 315mm 335mm 355mm mm.

Bracket U Value at 1.5M Centres. 265mm 275mm 295mm 300mm 315mm 335mm 355mm mm. Bracket Typically @ 1200 ELITE SYSTEMS 402 Top Sheet set out typically for straight sheets * Varies - See Table 39 75 Varies - See Table 32 Bracket Height 100mm 150mm 160mm 180mm 185mm 200mm 220mm Halter

More information

contents MALLEABLE PIPE FITTINGS BUsHEs NiPPlEs PlUgs caps BENds BackNUTs UNioNs TEEs 171 cross PN25 p socket PN25 p socket PN25 p.

contents MALLEABLE PIPE FITTINGS BUsHEs NiPPlEs PlUgs caps BENds BackNUTs UNioNs TEEs 171 cross PN25 p socket PN25 p socket PN25 p. contents BUsHEs 140 Hexagon Bush p.5 NiPPlEs 144 octagon Nipple p.6 145 Hexagon Nipple p.6 PlUgs 146 Beaded Plug - solid p.7 147 Plain Plug - Hollow p.7 148 Plain Plug - solid p.7 149 countersunk Plug

More information

Overview IMIARBBP13. Remove and Replace Motor Vehicle Body Panels Including Permanently Fixed Panels

Overview IMIARBBP13. Remove and Replace Motor Vehicle Body Panels Including Permanently Fixed Panels Overview This standard is about removing a variety of exterior and sub-structure body panels and panel sections, including permanently fixed panels, where these are damaged and replaced with new or repaired

More information

ARTECO. Ceiling products. Acoustic performance data

ARTECO. Ceiling products. Acoustic performance data August 7 CI/SfB ARTECO Ceiling products Acoustic performance data Contents Casoprano ALTO and FORTE 6 Casoprano BIANCA, ROC and STAR 6 Casoprano NOVA 7 Casoprano OLA 8 Casoprano VOICE 9 Gyprex SATINSPAR

More information

Design principles and Assumptions

Design principles and Assumptions Design principles and Assumptions The design and use of concrete slabs that utilise ARMOURDECK 300 in composite construction may be carried out using either: the relevant Australian and international Standards

More information

CV/LF and CV/CF. TICO Structural Bearings

CV/LF and CV/CF. TICO Structural Bearings CV/LF and CV/CF TICO Structural Bearings TICO CV/LF and TICO CV/CF Isolation of vibrations from one part of a building to another is as equally important as isolating the whole building itself. Indeed,

More information

TEST REPORT No. : SHCCM Date : May. 17, 2013 Page: 1 of 5

TEST REPORT No. : SHCCM Date : May. 17, 2013 Page: 1 of 5 Page: 1 of 5 IGEPA GROUP GMBH & CO. KG SACHSENFELD 4, 20097 HAMBURG, GERMANY The following sample(s) was/ were submitted and identified on behalf of the client as: Sample Name : MASTER JET S PREMIUM MESH

More information

FD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N

FD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N V1175 FD-C Series Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper ES classified fire dampers with reduced smoke leakage characteristics (BS E 1366-2) Aerodynamically

More information

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39 Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39 APPLICATION These dynamically rated fire/smoke and fire

More information

PV-ezRack SolarTerrace III-A Installation Guide V1.4

PV-ezRack SolarTerrace III-A Installation Guide V1.4 PV-ezRack SolarTerrace III-A Installation Guide V1.4 CONTENT 1. Introduction...2 2. Tools & Components...3 3. Installation Guide. 8 4. Service..15 Clenergy Australia 1/10 Duerdin St, Clayton VIC 3168 T:

More information

SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels

SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures

More information

CLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Explosion Relief Valves

CLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Explosion Relief Valves CLASSIFICATION NOTES Type Testing Procedure for Crankcase Explosion Relief Valves Contents 1. Scope, Application 2. Recognized Standards 3. Purpose 4. Test Facilities 5. Explosion Test Process 6. Testing

More information

Hazardous areas, as found around a service station, are classified into three zones as follow: Table 1: Zone Classification for Vapours

Hazardous areas, as found around a service station, are classified into three zones as follow: Table 1: Zone Classification for Vapours MIE TALK - July 2016 Compiled by Pieter H. Coetzee Introduction Far too many fires and burn injuries result from the careless or inappropriate use of petrol. Because petrol is so common in our environment,

More information

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for:

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for: assessment report Title: The Fire Resistance Performance of Modified Doorsets WF Assessment Report No: 187254 Prepared for: Phoenix Door Panels Ltd. Westnewlands Ind. Estate Somersham Huntingdon Cambs

More information

FIRE TEST REPORT FH 5154

FIRE TEST REPORT FH 5154 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5154 CONE CALORIMETER TEST AND NCC SPECIFICATION C1.10

More information

RECYCLABILITY EVALUATION PROTOCOL FOR PE FILMS

RECYCLABILITY EVALUATION PROTOCOL FOR PE FILMS Phone : +32 2 742 96 82 Fax : +32 2 732 12 18 e-mail : recyclass@plasticsrecyclers.eu website: www.recyclass.eu RECYCLABILITY EVALUATION PROTOCOL FOR PE FILMS Standard Laboratory Practice Version 1.0 Published

More information

TWIN FAN CONTROLLER. Models:- ITC and ITC-DS Maximum load : V 50Hz ~ 9A and V 50Hz 3 ~ 9A

TWIN FAN CONTROLLER. Models:- ITC and ITC-DS Maximum load : V 50Hz ~ 9A and V 50Hz 3 ~ 9A TWIN FAN Installation and Wiring Instructions Models:- ITC and ITC-DS Maximum load : 220-240V 50Hz ~ 9A and 380-415V 50Hz 3 ~ 9A IMPORTANT - READ THESE INSTRUCTIONS FULLY BEFORE COMMENCING INSTALLATION.

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR009.030.1 CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore

More information

Insulation type Firwin Hard Coat (HC): Outer layer Black color Composite fiber. Inner layer High alumina ceramic fiber (1260 ºC).

Insulation type Firwin Hard Coat (HC): Outer layer Black color Composite fiber. Inner layer High alumina ceramic fiber (1260 ºC). Performance Evaluation of Firwin Hard Coat Insulation Based on Independent Study conducted by Catalytic Exhaust Products Limited MDEC Presentation October 2009 Abstract In this study, Firwin Hard Coat

More information

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength Report No: 181947 Test of: Reversible aluminium/timber window Tested to: BS 6375-2:2009 Performance of windows & doors Part 2: Operation & strength For: A/S Peder Nielsen Beslagfabrik Norregade 25 Bronderslev

More information

FIRE TEST REPORT FH 5078

FIRE TEST REPORT FH 5078 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5078 CONE CALORIMETER TEST AND NZBC ACCEPTABLE SOLUTIONS

More information

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39 Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39 APPLICATION These dynamically rated fire/smoke and fire s are

More information

Investigation into UK socket-outlets incorporating USB charging points

Investigation into UK socket-outlets incorporating USB charging points Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft. T F

TNO report. Centre for Fire Research Van Mourik Broekmanweg 6 P.O. Box AA Delft.   T F ederlandse Organisatie voor toegepast-natuurwetenschappelijk onderzoek / etherlands Organisation for Applied Scientific Research TO report E 13823:22 "Single Burning Item" and E 11925-2:22 "Ignitability"

More information

RANGER FLANGE ADAPTORS

RANGER FLANGE ADAPTORS RANGER ADAPTORS RANGER products, in the form of wide range couplings and flange adaptors, are designed to join pipes of various outside diameters with the same or different nominal bore. Because of the

More information

Understanding BS 1363 Amendment No.4

Understanding BS 1363 Amendment No.4 Intertek Hilton House, Corporation Street, Rugby, Warwickshire, CV21 2DN UK info.uk@intertek.com 01788 578435 www.intertek.com Introduction A new Amendment applying to several parts of the BS 1363 standard

More information

FR11S Fender, Welded-On

FR11S Fender, Welded-On Uniform Procedures For Collision Repair UPCR FR11S Fender, Welded-On 1. Description This procedure describes the repair and complete replacement of a welded-on steel fender. Inspection and evaluation requirements

More information

FIRE TEST REPORT FH 5728

FIRE TEST REPORT FH 5728 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5728 CONE CALORIMETER TEST AND NZBC VERIFICATION METHOD

More information

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telefon 0 74 63-980 - 0 Telefax 0 74 63-980 - 200

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR427.203.2 CERTIFICATE OF FIRE APPROVAL This is to certify that The product(s) detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations for use on offshore

More information

RTS536 Toyota Prado 150 Track Mount

RTS536 Toyota Prado 150 Track Mount Important: Please read these instructions carefully prior to installation. Please refer to your fi tting instruction to ensure that the track mount system is installed in the correct location. Check the

More information

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems.

TEST REPORT. Ceram Reference: (QT21489/2/SL)/Ref: 1.0A. Tensile and Frictional Tests on the Fast Fit BeamClamp Systems. TEST REPORT Ceram Reference: 121557 (QT21489/2/SL)/Ref: 1.0A Project Title: Tensile and Frictional Tests on the Fast Fit BeamClamp Systems Client: Kee Safety Limited For The Attention of: Mr Phil Higgs

More information

Test Report No.: SDHGR FM Date: Jun.08, 2012 Page 1 of 3

Test Report No.: SDHGR FM Date: Jun.08, 2012 Page 1 of 3 Test Report No.: SDHGR120501002FM Date: Jun.08, 2012 Page 1 of 3 HONGGE (GUANGZHOU) PAPER CO., LTD BUILDING 1, HE TAI INDUSTRY ZONE, HE TAI ROAD NO.2, HE BIAN, JIA HE TOWN, BAI YUN DISTRICT, GUANGZHOU.

More information

KT AIR SUSPENSION (Engineering Lit. No. KL006)

KT AIR SUSPENSION (Engineering Lit. No. KL006) KT AIR SUSPENSION (Engineering Lit. No. KL006) KT250 T KT300T KT250U KT300U Contents 1. Preassembly Considerations 2. KT Welding Instruction Axle Connection o Engineering LIT No: KL004 3. KT Welding Instruction

More information

CONTROL CABLES CABLES FZE.

CONTROL CABLES CABLES FZE. CONTROL CABLES CABLES FZE www.markcables.com Index Introduction 03 Particulars & Guarantees 05 Copper Conductor, PVC Insulated, PVC Sheathed Cables 08 Copper Conductor, XLPE Insulated, PVC Sheathed Cables

More information

Test Report No. AJHL FB Date: APR.06, 2016 Page 1 of 5

Test Report No. AJHL FB Date: APR.06, 2016 Page 1 of 5 Test Report AJHL1603002392FB Date: APR.06, 2016 Page 1 of 5 SOYANG TECHNICAL TEXTILE (ZHEJIANG) CO., LTD NO.36 JINNIU ROAD, JIANSHAN DISTRICT, HAINING CITY, ZHEJIANG PR., CHINA The following sample(s)

More information

Mineral Insulated Resistance Thermometers (RTD)

Mineral Insulated Resistance Thermometers (RTD) Mineral Insulated Resistance Thermometers (RTD) Electronic Temperature Measurement Data sheet : MIRTD/2012 Contents Page RTD Element Type 2 Conductors & Number of Wires 2 Probe Diameter 3 Length Types

More information

A vehicle constructed so that it can be unloaded by part of the vehicle being tipped side-ways or rearwards.

A vehicle constructed so that it can be unloaded by part of the vehicle being tipped side-ways or rearwards. Form Number: DVT 847 Issue: 5 Origin: DVT Review: 1 Jan 2015 SIDEGUARD, REAR UNDER-RUN DEVICE AND BUMPER BARS APPLICATION SIDEGUARDS Goods Vehicles first used from 1 April 1984 with a maximum gross weight

More information

50 HERTZ METRIC BLOWER

50 HERTZ METRIC BLOWER CAPACITIES 50 HERTZ METRIC BLOWER Pressure Range 500mm 20 wc 12 osi 700mm 27 wc 16 osi 900mm 35 wc 20 osi 1100mm 43 wc 24 osi Model Number TBA 500-1.5 TBA 500-2.2 TBA 500-3 TBA 500-4 TBA 500-5.5 TBA 500-

More information

TEST REPORT No. : SHCCM Date : Mar. 12, 2013 Page: 1 of 5

TEST REPORT No. : SHCCM Date : Mar. 12, 2013 Page: 1 of 5 Page: 1 of 5 IGEPA GROUP GMBH & CO.KG SACHSENFELD 4, 20097 HAMBURG, GERMANY The following sample(s) was/ were submitted and identified on behalf of the client as: Sample Name : MASTER JET S FRONTLIT 510

More information

Appendix C - Roll Over Bars Appendix D - Roll Cages

Appendix C - Roll Over Bars Appendix D - Roll Cages NATIONAL SOLOSPORT REGULATIONS AUTOSLALOM Appendix C - Roll Over Bars Appendix D - Roll Cages Effective January 1, 2018 ASN Canada FIA 481 North Service Road West, Suite A21, Oakville, Ontario, L6M 2V6

More information

Compression Testing of Single Column Studs with Sheathing Configurations

Compression Testing of Single Column Studs with Sheathing Configurations Compression Testing of Single Column Studs with Sheathing Configurations Yared Shifferaw, Luiz Vieira and Ben Schafer Department of Civil Engineering Johns Hopkins University August 29 Introduction The

More information

2012 IECEE CTL PTP Workshop. Ingrid Flemming IFM Quality Services Pty Ltd

2012 IECEE CTL PTP Workshop. Ingrid Flemming IFM Quality Services Pty Ltd 2012 IECEE CTL PTP Workshop Ingrid Flemming IFM Quality Services Pty Ltd Today QM discussion Re-cap on corrective actions (group exercise) Record keeping Creepageand Clearance discussion and exercises

More information

European Fire Pump Listing

European Fire Pump Listing European Fire Pump Listing EN12259-12 Current Status of European Listings Germany - National Listings France - National Listings UK - National Listings Poland - National Listings Hungary - National Listings

More information

Plaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser

Plaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser 1/1.5/B/1 Plaster In Grilles AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Telephone +44 (0) 1842

More information

With Compliments PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : : 1006

With Compliments PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : : 1006 For the Attention of: Mr Ian Davies Mideas Limited 12 Openshaw Drive Blackburn Lancashire BB1 8RH With Compliments DATE REPORT ISSUED: 10/11/2006 PLEASE FIND ENCLOSED OUR REPORT REFERENCE ALC E : 99316

More information

SERVICE LETTER No.: 0007/2012/R1

SERVICE LETTER No.: 0007/2012/R1 SERVICE LETTER No.: 0007/2012/R1 Concerning: Reason: Measure: Operators of in-line engines M 132, M 137, M 332, and M 337 of all versions and organisations approved for the maintenance of the engines according

More information

PENTAGON PROTECTION USA

PENTAGON PROTECTION USA PENTAGON PROTECTION USA Shock Tube Testing for Window Systems March 2009 San Antonio, Texas ABS Consulting Project Number 2127174 ABSG Consulting, Inc. 14607 San Pedro, Suite 215 San Antonio, TX 78232

More information

FR11A Fender, Welded-On

FR11A Fender, Welded-On Uniform Procedures For Collision Repair FR11A Fender, Welded-On 1. Description This procedure describes the repair and complete replacement of a welded-on aluminum fender. Inspection and evaluation requirements

More information

Standard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2

Standard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2 Reprinted Feb 2013 APPLICATION These dynamically rated fire/smoke and smoke dampers are intended to restrict the passage of smoke. The dynamically rated fire/smoke dampers are also intended to restrict

More information

2008 Crown Victoria/Grand Marquis Workshop Manual. REMOVAL AND INSTALLATION Procedure revision date: 01/25/2010

2008 Crown Victoria/Grand Marquis Workshop Manual. REMOVAL AND INSTALLATION Procedure revision date: 01/25/2010 SECTION 501-35: Body Repairs 2008 Crown Victoria/Grand Marquis Workshop Manual REMOVAL AND INSTALLATION Procedure revision date: 01/25/2010 Ballistic Door Panel Special Tool(s) Heavy Duty Riveter 501-D011

More information

R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests

R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests Materials Testing Canada Inc. R-Solutions Spike Hole Plugging Compound Static and Dynamic Load Tests Presented to: 100 South Santa Fe Dr. Denver, Colorado 80223 Attn: Walter Vizcaino, Date Issued 03 March

More information

DeltaStud - Lightweight Steel Framing

DeltaStud - Lightweight Steel Framing DeltaStud - Lightweight Steel Framing B C H A t P Load Tables for Wind Bearing and Combined Wind & Axial Load Bearing Condition January 2014 Table of Contents Commentary Introduction...3 Product Identification...3

More information

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 9 Transformer bushings, type GOB Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Installation STUD JOIST A237R SPECIFICATIONS. Width Height Depth Weight Max. Spacing between Mounts Max. Load

Installation STUD JOIST A237R SPECIFICATIONS. Width Height Depth Weight Max. Spacing between Mounts Max. Load WILREP LTD. 08 13 48 13 SPECIAL CONSTRUCTION 14 manufactured sound & vibration control components Installation A237R SPECIFICATIONS Width Height Depth Weight Max. Spacing between Mounts Max. Load FURRING

More information

About TekMarine. Disclaimer. Copyright

About TekMarine. Disclaimer. Copyright Marine Fenders About TekMarine From its base in the United States, TekMarine Systems LLC designs and supplies advanced marine fendering and mooring systems to ports, harbors and waterways across the world.

More information