PENTAGON PROTECTION USA
|
|
- Aubrey Small
- 5 years ago
- Views:
Transcription
1 PENTAGON PROTECTION USA Shock Tube Testing for Window Systems March 2009 San Antonio, Texas ABS Consulting Project Number ABSG Consulting, Inc San Pedro, Suite 215 San Antonio, TX USA Tel: Fax:
2 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Table of Contents Introduction...3 Test Approach...3 Test Specimens...4 Test Fixtures...6 Test Procedure...7 Results...8 Appendix A Appendix B Appendix C Window Data Sheets Testing Photographs Summary Tables 2
3 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Introduction ABSG Consulting, Inc. (ABS Consulting) has conducted testing of window systems upgrades for Pentagon Protection USA (Pentagon Protection). The tests were conducted in accordance with testing protocol in ASTM F and US General Services Administration (GSA) 2. The windows consisted of single pane commercial windows retrofitted with four sided anchored film. The film anchorage system consisted of Pentagon Protection s Elite Glass Security Seal attachment with 3M ST1200 tape. The objective of the testing was to certify the performance of windows upgraded with Pentagon Protection s Glass Security Seal, when subjected to blast loads resulting from attack scenarios defined by the Unified Facilities Criteria (UFC) 3 and GSA. Testing was conducted at the ABS Consulting facilities in San Antonio, Texas, USA March 17-18, Test Approach Blast loads were applied using a shock tube as shown in Figure 1. This device uses a sudden burst of compressed air to create a blast pulse, which travels down the tube and is applied to the test specimen which is secured to the end of the tube. An enclosure (test cubicle) is attached to the end of the tube. The blast load creates a specified positive blast pressure and impulse on the test specimens. Negative phase blast loads may occur but the system is not designed to produce a negative pulse typical of a high explosive load. Testing commenced with blast loads designed to meet the various threat standoff combinations as described in the UFC. The same blast pressure was applied to each specimen. 1 ASTM Standard, F , Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings, ASTM Book of ASTM Standards, Vol , March US General Services Administration (GSA), GSA-TS , Standard Test Method for Glazing and Glazing Systems Subject to Dynamic Overpressure Loadings, GSA, January, Department of Defense (DoD), Unified Facilities Criteria (UFC) UFC , DoD Minimum Antiterrorism Standards for Buildings, DoD, October
4 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Figure 1. ABS Consulting Shock Tube Apparatus Test Specimens Pentagon Protection provided the window systems fully assembled with a four sided anchored film system pre-installed. ABS Consulting personnel measured framing, glazing and film dimensions and confirmed glass type for each window assembly. The window glazing for each of the tests consisted of annealed monolithic glass in a single ¼-inch pane. 3M Ultra 6-mil fragment retaining film was bonded to the interior face of the windows. The film was anchored to the frame using a proprietary product developed by Pentagon Protection USA called Elite Glass Security Seal (GSS). This anchoring system consists of three attachment legs as detailed in Figure 2. One was inserted in place of the interior dry glazing gasket. The remaining two were bonded to the frame and film using 3M ST1200 tape. Window frame assemblies were rigidly supported along the head and sill of the window frame. Steel angles and plates were used to support the framing to prevent lateral displacement. This configuration simulates a fully anchored window system installed in the field. Figure 3 shows a typical Pentagon Protection test window mounted in the ABS shock tube. A close-up view of the shock tube mounting restraint is shown in Figure 4. 4
5 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Figure 2. GSS Film Anchoring Detail Figure 3. Window Mounted in Test Fixture 5
6 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Figure 4. Close-up View of Mounting Restraint Test Fixtures The test enclosure, nominally 10 feet deep, 10 feet wide and 10 feet tall, was placed flush with the end of the tube. A bulkhead plate on the end of the tube prevented blast pressures from wrapping around the structure and reaching the back side of the window. This represents a typical window installation on an exterior wall. A witness panel was provided on the back wall to detect the impact of glass shards. Composition of the witness panel was in accordance with ASTM Five dynamic pressure sensors (gauges 1-5) measuring applied pressure were mounted on the shock tube bulkhead facing the oncoming blast wave, immediately adjacent to the test specimen (see Figure 5). A single pressure sensor (gauge 6) was also mounted inside the test cubicle to measure pressure changes. Dynamic pressure sensors were selected based on rise time and frequency response and calibrated for a 0-10 psi peak pressure range. Pressure waveforms were recorded by a Yokagawa digital data acquisition system sampling at a minimum of 1000 khz. 6
7 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Figure 5. Pressure Gauge Locations Test Procedure Testing was conducted in accordance with ASTM F and the GSA Standard Test Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings dated January 1, The objective of the testing is to determine the performance of the windows as defined in Table 2.1 and 2.2 in the UFC. Blast loads varied by test and were selected to encompass specified charge weights and standoffs as defined by the UFC and GSA. Actual applied loads are included in the appendices. Window performance conditions were assigned in accordance with the performance criteria in ASTM 1642 and the GSA test protocol. Ambient and glass temperatures were recorded at 30 minutes and 5 minutes prior to each test. Photographs were taken of test specimens and the test setup prior to and following each test to document window performance. Appendix B contains photographs taken of the test specimen throughout the testing. Normal speed (30 pps) and high speed video (1000 pps) were also recorded for each test. The normal speed video is submitted with this report. Following each test, glass fragments were collected and the unified dimensions of fragments projected into the test cubicle were determined for classification per the ASTM 1642 protocol. Fragments striking and embedding in the witness panel were collected and documented. Frame deformations were recorded and performance of framing was documented. Hazard Ratings and Performance Conditions for each test item were assigned and recorded in accordance with ASTM and the GSA criteria as shown in Figure 6 and Figure 7, respectively. 7
8 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Figure 6. ASTM F Performance Criteria Figure 7. GSA Performance Conditions Results Appendix A contains a data sheet for each test specimen. The data sheet includes the following information: Detailed description of the unit including the frame, glazing, and attachment into the shock tube. Description of the test conditions. Detailed description of the performance condition for both ASTM and GSA criteria. A pretest and post test photograph. A graph of the applied blast history. Appendix B contains a photographic log for each test. Appendix C summarizes the loads and window responses. 8
9 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number All tests were conducted with the Elite GSS attachment system installed on all 4-sides. Each window was filmed with 3M Ultra 6-mil film. The applied load was the pressure and impulse generated by the UFC Charge Weight II at 82-ft of standoff. The anchoring system retained the glass fragments and resulted in an ASTM certification of Minimal Hazard. ASTM certification resulting from shock tube tests performed for this project is listed below. Three samples of the window retrofit system were tested in accordance with the ASTM test method to permit certification. Minimal Hazard Elite GSS with 3M Ultra 6-mil film (3M ST1200 Tape) Approved: Jerry Collinsworth Lead Engineer Extreme Loads and Structural Risk San Antonio, Texas 9
10 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Appendix A Window Data Sheets
11 Pretest Information Test Information Client: Model Number: SPECIMEN Number: Description: Test Date: Test Number: Project Number Report Date Test Location: Test Director: ABS Shock Tube Testing Report Pentagon Protection GSS w/ 3M ST mil 4-Sided Anchored Film 3/17/ Mar-09 ABS Test Range Jerry Collinsworth Test Method: Notes: GSA "Standard Testing Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings" ASTM F "Standard Test Method for Glazing and Glazing Systems Subjected to Airblast Loadings" Elite Glass Security Seal (GSS) w/ 3M ST1200 adhesive tape (4-sides) 3M Ultra 6 mil Film No Silicone Attachment Frame Information Glazing Information Width (in): Multiple Lites? No Height (in): Lite 1 Lite 2 Lite 3 Frame Width (in): 4.50 Width (in): Material: Aluminum Height (in): Frame Support: Captured along head & sill IGU? No Air Gap: in steel sub-frame. Temperature 30 min 5min Thickness (in): 1/4" Ambient (F): Glass Type: Monolithic Annealed Glass Surface (F): Notes: Elite GSS replaces interior dry gasket. 3M ST1200 tape 13mm wide. UFC Charge Weight II at 82-ft Blast Pressure Information Gauge Number Average Cubicle Peak Reflected Pressure (psi) Positive Phase Impulse (psi-ms) Positive Phase Duration (ms) Glazing Damage Summary Notes: United Dimension (in): 0-40 in in Dusting None 0 0 Interior Perimeter Sum Tears and Pullout (%): Witness Panel Perforations/Indents: Witness Panel Penetrations: Low Hazard/Zone 4 None None High Hazard/Zone 5 None None Notes: Glass Security Seal pealed off frame in several localized areas. Small tears in corners of film. Dusting in cubicle. GSA Performance Condition: 2 ASTM F-1642 Hazard Level: Minimal Hazard Test Certification GSA Performance Condition: 3B Certified for Test Pressure per ASTM F1642: No Test Number: 3 ASTM F-1642 Hazard Level: Minimal Other Test No.: 4, 5 A - 2
12 Photographs and Blast Trace Pre-Test Photograph Post-Test Photograph Blast Trace A - 3
13 Pretest Information Test Information Client: Model Number: SPECIMEN Number: Description: Test Date: Test Number: Project Number Report Date Test Location: Test Director: ABS Shock Tube Testing Report Pentagon Protection GSS w/ 3M ST mil 4-Sided Anchored Film 3/17/ Mar-09 ABS Test Range Jerry Collinsworth Test Method: Notes: GSA "Standard Testing Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings" ASTM F "Standard Test Method for Glazing and Glazing Systems Subjected to Airblast Loadings" Elite Glass Security Seal (GSS) w/ 3M ST1200 adhesive tape (4-sides) 3M Ultra 6 mil Film No Silicone Attachment Frame Information Glazing Information Width (in): Multiple Lites? No Height (in): Lite 1 Lite 2 Lite 3 Frame Width (in): 4.50 Width (in): Material: Aluminum Height (in): Frame Support: Captured along head & sill IGU? No Air Gap: in steel sub-frame. Temperature 30 min 5min Thickness (in): 1/4" Ambient (F): Glass Type: Monolithic Annealed Glass Surface (F): Notes: Elite GSS replaces interior dry gasket. 3M ST1200 tape 13mm wide. UFC Charge Weight II at 82-ft Blast Pressure Information Gauge Number Average Cubicle Peak Reflected Pressure (psi) Positive Phase Impulse (psi-ms) Positive Phase Duration (ms) Glazing Damage Summary Notes: United Dimension (in): 0-40 in in Small Fragments None 3.5 <10" Interior Perimeter Sum Tears and Pullout (%): Witness Panel Perforations/Indents: Witness Panel Penetrations: Low Hazard/Zone 4 None None High Hazard/Zone 5 None None Notes: Glass Security Seal did not release from frame. Tearing occurred in corners of film. Majority of fragments thrown less than 40" into cubicle. Farthest fragment at 74-inch. GSA Performance Condition: 3B ASTM F-1642 Hazard Level: Minimal Hazard Test Certification GSA Performance Condition: 3B Certified for Test Pressure per ASTM F1642: No Test Number: 4 ASTM F-1642 Hazard Level: Minimal Other Test No.: 3, 5 A - 4
14 Photographs and Blast Trace Pre-Test Photograph Post-Test Photograph Blast Trace A - 5
15 Pretest Information Test Information Client: Model Number: SPECIMEN Number: Description: Test Date: Test Number: Project Number Report Date Test Location: Test Director: ABS Shock Tube Testing Report Pentagon Protection GSS w/ 3M ST mil 4-Sided Anchored Film 3/17/ Mar-09 ABS Test Range Jerry Collinsworth Test Method: Notes: GSA "Standard Testing Method for Windows and Glazing Systems Subject to Dynamic Overpressure Loadings" ASTM F "Standard Test Method for Glazing and Glazing Systems Subjected to Airblast Loadings" Elite Glass Security Seal (GSS) w/ 3M ST1200 adhesive tape (4-sides) 3M Ultra 6 mil Film No Silicone Attachment Frame Information Glazing Information Width (in): Multiple Lites? No Height (in): Lite 1 Lite 2 Lite 3 Frame Width (in): 4.50 Width (in): Material: Aluminum Height (in): Frame Support: Captured along head & sill IGU? No Air Gap: in steel sub-frame. Temperature 30 min 5min Thickness (in): 1/4" Ambient (F): Glass Type: Monolithic Annealed Glass Surface (F): Notes: Elite GSS replaces interior dry gasket. 3M ST1200 tape 13mm wide. UFC Charge Weight II at 82-ft Blast Pressure Information Gauge Number Average Cubicle Peak Reflected Pressure (psi) Positive Phase Impulse (psi-ms) Positive Phase Duration (ms) Glazing Damage Summary Notes: United Dimension (in): 0-40 in in Small Fragments None <10" 0 Interior Perimeter Sum Tears and Pullout (%): Witness Panel Perforations/Indents: Witness Panel Penetrations: Low Hazard/Zone 4 None None High Hazard/Zone 5 None None Notes: Glass Security Seal did not release from frame. Tearing occurred in corners of film. No fragments thrown over 40" into cubicle. Farthest fragment at 24-inch. GSA Performance Condition: 3A ASTM F-1642 Hazard Level: Minimal Hazard Test Certification GSA Performance Condition: 3B Certified for Test Pressure per ASTM F1642: No Test Number: 5 ASTM F-1642 Hazard Level: N/A Other Test No.: 3, 4 A - 6
16 Photographs and Blast Trace Pre-Test Photograph Post-Test Photograph Blast Trace A - 7
17 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Appendix B Testing Photographs
18 Pre Test 03 B - 2
19 Post Test 03 B - 3
20 Pre Test 04 B - 4
21 Post Test 04 B - 5
22 Pre Test 05 B - 6
23 Post Test 05 B - 7
24 Pentagon Protection USA - Shock Tube Testing for Window Systems March 2009 ABS Project Number Appendix C Summary Tables
25 Table 1. Response Summary Test Number Date 3 3/18/ /18/ /18/2009 Window Description Single Pane Fixed Lite Single Pane Fixed Lite Single Pane Fixed Lite * Tested for UFC Applicable Explosive Charge Weight II. Anchoring System (4-sided) Elite GSS 3M ST1200 Tape Elite GSS 3M ST1200 Tape Elite GSS 3M ST1200 Tape Film Type 3M Ultra 6-mil 3M Ultra 6-mil 3M Ultra 6-mil Glazing Description 1/4-inch Annealed Glass 1/4-inch Annealed Glass 1/4-inch Annealed Glass Frame Width inch Frame Height inch Glazing Response ASTM GSA F Minimal * B Minimal * A Minimal * C - 2
26 Pressure (psi) Impulse (psi-msec) Average Test Date Time Gauge 1 Gauge 2 Gauge 3 Gauge 4 Gauge 5 Gauge 1 Gauge 2 Gauge 3 Gauge 4 Gauge 5 P (psi) I (psi*msec) 3 3/18/ :30 AM /18/2009 3:30 PM /18/2009 4:10 PM C - 3
FULL SCALE ARENA ASTM F 1642 TEST REPORT. Rendered to: Solar Gard
Architectural Testing FULL SCALE ARENA ASTM F 1642 TEST REPORT Rendered to: Solar Gard MODEL DESIGNATION: Solar Gard Armorcoat Safety & Security Films PRODUCT TYPE: Safety and Security Films This report
More informationBLAST CAPACITY ASSESSMENT AND TESTING A-60 OFFSHORE FIRE DOOR
BLAST CAPACITY ASSESSMENT AND TESTING Final Report December 11, 2008 A-60 OFFSHORE FIRE DOOR Prepared for: JRJ Alum Fab, Inc. Prepared by: Travis J. Holland Michael J. Lowak John R. Montoya BakerRisk Project
More informationHigh Strength Glass Testing and Model Validation for Static and Dynamic Loading
High Strength Glass Testing and Model Validation for Static and Dynamic Loading Ryan M. Alberson 1, Carrie E. Davis 2, and Kirk A. Marchand 3 1 Associate Engineer, Protection Engineering Consultants, Austin,
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 2000 Double Hung Window PRODUCT TYPE: PVC Double Hung Window Summary of Results Title Test Specimen
More informationBlast Protection Damper
Protection Damper plate shown as transparent height width 250mm wide 6.35mm thick blast plate bolted to damper frame 178mm 250mm standard depth 76mm standard flange Application The damper is designed for
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6458.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: Fiberglass In Swing Glazed Double Doors SERIES/MODEL:
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6457.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Door with Side Lites SERIES/MODEL:
More informationCONSTRUCTION CONSULTING LABORATORY, INTERNATIONAL
TEST REPORT: SERIES 8220 ALUMINUM SINGLE HUNG WINDOW Prepared for: 5625 E. Firestone Boulevard South Gate, CA 90280 1601 Luna Road S-UNITED, INC. Office: (972) 242-0556 Carrollton, Texas 75006 A Quality
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A6839.01 801 18 Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas PRODUCT TYPE: In Swing Fiberglass Double Doors with Speak Easy
More information600 Amp Surge Arrester
R&D Center 497 Schooley s Mountain Road Hackettstown, NJ 07840-3906 Tele: 908-852-1122 Fax: 908-813-2091 TEST REPORT NUMBER: 379-17-12164 DATE: 4-3-2012 REPORT OF TEST ON 600 Amp Surge Arrester Statements
More informationSINGLE SLIDING WINDOW 1000 SERIES 4-1/2" FRAME SINGLE SLIDER LIFT OUT
PERFORMANCE EVALUATION OF SINGLE SLIDING WINDOW 1000 SERIES 4-1/2" FRAME SINGLE SLIDER LIFT OUT For Dominion Doors & Windows Ltd. IN ACCORDANCE WITH: AAMA/WDMA/CSA 101/I.S.2/A440-11 AND A440S1-17 Report
More informationNFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia
NFPA 285 TEST REPORT Report No.: H1152.01-121-24 Test Date: June 1, 2017 Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia WALL SYSTEM: Exterior Non-loadbearing Wall Assembly COMBUSTIBLE COMPONENTS:
More informationSFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 *
SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards
More informationSFI SPECIFICATION 14.3 EFFECTIVE: AUGUST 25, 2017 *
SFI SPECIFICATION 14.3 EFFECTIVE: AUGUST 25, 2017 * PRODUCT: Nitro-Methane Fuel Supercharger Restraint Devices 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and
More informationGENERATOR SHELTER IMPACT TEST REPORT (.08 Material)
GENERATOR SHELTER IMPACT TEST REPORT (.08 Material) Florida Division of Emergency Management 2555 Shumard Oak Boulevard Tallahassee, FL 32399 Office: 850-413-9969 Department of Management Services 4050
More informationBlast Protection Damper
height width 250mm standard 76mm standard flange Application The damper is designed for protection against sudden blasts and instantaneous pressure changes. Vertical and horizontal mounting applications
More informationARCONIC ARCHITECTURAL PRODUCTS FIRE TEST REPORT
ARCONIC ARCHITECTURAL PRODUCTS FIRE TEST REPORT SCOPE OF WORK CAN/ULC S134, STANDARD METHOD OF FIRE TESTS OF EXTERIOR WALL ASSEMBLIES CONTAINING ARCONIC REYNOBOND RB-160-FB REPORT NUMBER 103413434SAT-003
More informationNFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH
NFPA 286 STANDARD METHODS OF FIRE TESTS FOR EVALUATING CONTRIBUTION OF WALL AND CEILING INTERIOR FINISH TO ROOM FIRE GROWTH Contego Latex Fire Barrier Intumescent (Also marketed in Canada by Pyrologistics,
More informationCALIBRATION REPORT. Rendered to: United States Aluminum Corp. LOCATION: Waxahachie, Texas
CALIBRATION REPORT Rendered to: United States Aluminum Corp. LOCATION: Waxahachie, Texas Report No.: 79241.01-801-47 Calibration Date: 12/14/07 Report Date: 03/20/08 2865 Market Loop Southlake, Texas 76092
More informationmga research corporation
mga research corporation UNDERGROUND TECHNOLOGIES MAN-HOLE CONSTRUCTION VERTICAL STATIC LOAD TEST SERIES (PO# 11521) 446 executive drive troy, mi 48083 248 / 577-5001 fax 248 / 577-5025 www.mgaresearch.com
More informationTEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket
TEST REPORT Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket Report No: Report Date: 10/31/12 130 Derry Court York, PA 17406-8405 phone:
More informationAAMA/WDMA/CSA 101/I.S.2/A440-08
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Product Manufacturer: Report No.: AI-04016-U1 Rev.1 ACRYLON PLASTICS 122 PAQUIN ROAD WINNIPEG, MANITOBA R2J 3V4 204-669-2345 Report
More informationIEA SHC Task 27: Accelerated Aging of IG units: North American Test Methods
IEA SHC Task 27: Accelerated Aging of IG units: North American Test Methods Hakim Elmahdy, Ph. D., MBA, P. Eng. Institute for Research in Construction National Research Council of Canada Introduction There
More informationFOR COMPLETE INFORMATION AND DETAILS ON ALL BULLET/BLAST PROTECTION PRODUCTS WE OFFER PLEASE VISIT OR
13 40 00.11/ARM BuyLine 4484 800-880-8306 FAX 210-661-8308 WWW.ARMORTEX.COM BLLET RESISTANT DOORS AND WINDOWS BLLET / BLAST RESISTANT FIBERGLASS COMPOSITE PANELS BLAST RESISTANT DOORS AND WINDOWS ARMORTEX
More informationNFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.
Architectural Testing NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: 143.095 DH 143.195 DH 145.095 DH 145.195 DH Baseline
More informationBlast tested to 100kg and now 500kg charges and also IED devices
Technical Data Sheet TDSBB 1005 Blast tested to 100kg and now 500kg charges and also IED devices Ballistic and Blast Steel and Aluminium Glazed Window, Door and Screen Systems Blast rated ballistic window
More informationAbstract. 1 Description of the Problem
Pressure loading on a luggage container due to an internal explosion J.A. Gatto, S. Krznaric Office of Aviation Security Research and Development, FAA Technical Center, Atlantic City International Airport,
More informationCollecting In-theatre Vehicle Blast Data using Stand-alone On-board Data Acquisition Technology
Collecting In-theatre Vehicle Blast Data using Stand-alone On-board Data Acquisition Technology Allen Vanguard s Blackbird: A Vehicle Mounted Blast Data Acquisition System ALLENVANGUARD 2010 Authored by:
More informationAmerican National Standard
STANDARD METHOD FOR TESTING SECTIONAL DOORS, ROLLING DOORS, AND FLEXIBLE DOORS: DETERMINATION OF STRUCTURAL PERFORMANCE UNDER MISSILE IMPACT AND CYCLIC WIND PRESSURE Door & Access Systems Manufacturers
More informationINSTALLATION INSTRUCTIONS
Aero Twin, Inc. Single Place Folding Seat P/N DFS1-01W TSO-C127a INSTALLATION INSTRUCTIONS Document No. DFS1W-IM1-T Note: This installation and weight and balance data is identical to that contained within
More informationAn Evaluation of the Effectiveness of Common Door Blast Shields
An Evaluation of the Effectiveness of Common Door Blast Shields Adrian Pierorazio, J. Kelly Thomas, & Jihui Geng Baker Engineering and Risk Consultants, Inc. 55 th Canadian Chemical Engineering Conference
More information*Friedman Research Corporation, 1508-B Ferguson Lane, Austin, TX ** Center for Injury Research, Santa Barbara, CA, 93109
Analysis of factors affecting ambulance compartment integrity test results and their relationship to real-world impact conditions. G Mattos*, K. Friedman*, J Paver**, J Hutchinson*, K Bui* & A Jafri* *Friedman
More informationCREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System
Architectural Testing CREEP PERFORMANCE TEST REPORT Rendered to: TREX COMPANY LLC Seclusions Composite Privacy Fence System TYPE: Composite Fence System Report No.: Report Date: Expiration Date: 130 Derry
More informationAFG501 ALUMINUM FEMA 361 LOUVER LOUVER TYPE RECOMMENDED SPECIFICATION
LOUVER TYPE AFG501 ALUMINUM FEMA 361 LOUVER Visible Mullion Louver Type... AFG501 Blade Material... Extruded Aluminum, Alloy 6061-T6 Blade... 0.25 in. (6.35 mm) Frame Material... Formed Aluminum, Alloy
More informationSTATUS OF NHTSA S EJECTION MITIGATION RESEARCH. Aloke Prasad Allison Louden National Highway Traffic Safety Administration
STATUS OF NHTSA S EJECTION MITIGATION RESEARCH Aloke Prasad Allison Louden National Highway Traffic Safety Administration United States of America Stephen Duffy Transportation Research Center United States
More informationNFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.
Architectural Testing NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: 143.095 SH 145.095 SH 143.095 SH Common Head Baseline
More informationNFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.
Architectural Testing NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: 143.191 Casement / Awning / Fixed Baseline Product
More informationAAMA/WDMA/CSA 101/I.S.2/A440-08
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Product Manufacturer: Report No.: AI-04016-T1 Rev.1 ACRYLON PLASTICS 122 PAQUIN ROAD WINNIPEG, MANITOBA R2J 3V4 204-669-2345 Report
More informationSFI SPECIFICATION 6.1 EFFECTIVE: FEBRUARY 26, 2014 *
SFI SPECIFICATION 6.1 EFFECTIVE: FEBRUARY 26, 2014 * PRODUCT: Containment Bellhousing for SFI 1.1 & 1.2 Clutch Assemblies for limited normally aspirated applications, and forced induction applications
More informationHURRICANESHIELD IMPACT-RESISTANT GLASS SECTION DIRECTORY. Size and performance summary. Glazing performance. Grille profiles and patterns.
SECTIN DIRECTRY Size and performance summary Glazing performance Grille profiles and patterns Size tables Design Data Detailed Product Description Cross sections The information published in this document
More informationFebruary 8, In Reply Refer To: HSSD/CC-104
February 8, 2008 200 New Jersey Avenue, SE. Washington, DC 20590 In Reply Refer To: HSSD/CC-04 Barry D. Stephens, P.E. Sr. Vice President Engineering Energy Absorption Systems, Inc. 367 Cincinnati Avenue
More informationSFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994*
SFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994* PRODUCT: Tractor Blankets 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for evaluating
More informationSFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 *
SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 * PRODUCT: Sportsman Lower Engine Containment Device 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum
More informationLightweight Shock and Type I Vibration Test Report on UPS Model No. PS3200RM for Powerstar Inc. Gaithersburg, MD
Test Report No. 12069.1 No. of Pages 21 Lightweight Shock and Type I Vibration Test Report on UPS Model No. PS3200RM for Powerstar Inc. Gaithersburg, MD NU LABORATORIES 312 Old Allerton Road, Annandale,
More informationMILITARY SPECIFICATION MICROCIRCUITS, LINEAR, CMOS, ANALOG SWITCH WITH DRIVER, MONOLITHIC SILICON
INCH-POUND 4 February 2004 SUPERSEDING MIL-M-38510/116 16 April 1980 MILITARY SPECIFICATION MICROCIRCUITS, LINEAR, CMOS, ANALOG SWITCH WITH DRIVER, MONOLITHIC SILICON This specification is approved for
More informationBlast Pendulum Testing of Milliken Tegris Panels
Blast Pendulum Testing of Milliken Tegris Panels by Donald J. Grosch, Erick J. Sagebiel, and Hal Eleazer ARL-CR-0600 January 2008 prepared by Southwest Research Institute San Antonio, Texas and Milliken
More informationTest report. Type VRLTC load tap changer VRLTC 1500A Type test summary report
Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum
More informationTEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina
TEST REPORT Report No.: G4212.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.118 thickness PC smooth/0.118 thickness
More informationCLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Explosion Relief Valves
CLASSIFICATION NOTES Type Testing Procedure for Crankcase Explosion Relief Valves Contents 1. Scope, Application 2. Recognized Standards 3. Purpose 4. Test Facilities 5. Explosion Test Process 6. Testing
More informationPERFORMANCE TEST REPORT. Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent
Architectural Testing PERFORMANCE TEST REPORT Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent This report contains in its entirety: Cover Page: 1 page Report Body: 6 pages
More informationSummary of HALT, IPx7 & IP69K testing for AT Series connectors
S1-15227 Rev. A1 Corp. SINE Systems Corporation 44724 Morley Drive Clinton Twp, MI 48036 Summary of HALT, IPx7 & IP69K testing for AT Series connectors IPx7 (Submersion) PASS Requirements: Acceptance conditions
More informationTABLE OF CONTENTS Page
TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: SPECIALTY WHOLESALE SUPPLY
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: SPECIALTY WHOLESALE SUPPLY SERIES/MODEL: 4000 / 4500 DuraGard XT Double Hung Report Number: Original
More informationNFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: SS 145.
Architectural Testing NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: 143.095 SS 145.095 SS Baseline Product for Validation
More informationLEGACY REPORT. (800) (562) A Subsidiary of the International Code Council
ICC-ES Legacy Report ER- Reissued May 0 www.icc-es.org (00) - () -0 A Subsidiary of the International Code Council Legacy report on the Uniform Building Code DIVISION: 0 DOORS AND WINDOWS Section: 0 Unit
More informationDYNAMIC LOAD IN OPERATION OF HIGH-SPEED TRACKED VEHICLES
Journal of KONES Powertrain and Transport, Vol. 16, No. 4 29 DYNAMIC LOAD IN OPERATION OF HIGH-SPEED TRACKED VEHICLES Wac aw Borkowski, Piotr Rybak Military University of Technology S. Kaliskiego Street
More informationGENERAL SPECIFICATION
ALPHA 2001 MD TMA (Truck Mounted Attenuator GENERAL SPECIFICATION I. GENERAL A. All ALPHA 2001 MD Truck Mounted Attenuators (ALPHA 2001 MD TMA) shall be designed and manufactured by Energy Absorption systems,
More informationCRASH TEST REPORT FOR PERIMETER BARRIERS AND GATES TESTED TO SD-STD-02.01, REVISION A, MARCH Anti-Ram Bollards
CRASH TEST REPORT FOR PERIMETER BARRIERS AND GATES TESTED TO SD-STD-02.01, REVISION A, MARCH 2003 Anti-Ram Bollards Prepared for: RSA Protective Technologies, LLC 1573 Mimosa Court Upland, CA 91784 Test
More informationLorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA
Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary
More informationALPHA 70K TMA (Truck Mounted Attenuator) GENERAL SPECIFICATIONS
ALPHA 70K TMA (Truck Mounted Attenuator) GENERAL SPECIFICATIONS I. GENERAL A. All ALPHA 70K Truck Mounted Attenuators (ALPHA 70K TMA) shall be designed and manufactured by Energy Absorption Systems, Incorporated,
More informationGeneral Information SECTION DIRECTORY
SECTION DIRECTORY General Information Product Summary... V-AW-2 Product Selection Guide... V-AW-3 Size and Performance Data... V-AW-3 Features and Options... V-AW-3 Sound Transmission Class and Outdoor-Indoor
More informationNATIONAL TECHNICAL SYSTEMS
Test Report Number 41418-09.PPC Testing of Pancake Alternator & PMU PREPARED FOR: The Perfect Parts Company Sullivan Products 1 North Haven Street Baltimore, MD 21224 PREPARED BY: National Technical Systems
More informationVoluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems
Task Group Approval Council Approval Product Group Approval Successful Re-ballot 16-1052 Successful Ballot (#17-1011) Out for Ballot #18-1016 AAMA 1304-XX DRAFT #7 DATED 2/21/2018 Voluntary Specification
More informationCRASH TEST REPORT FOR PERIMETER BARRIERS AND GATES TESTED TO SD-STD-02.01, REVISION A, MARCH Anti-Ram Bollards
CRASH TEST REPORT FOR PERIMETER BARRIERS AND GATES TESTED TO SD-STD-02.01, REVISION A, MARCH 2003 Anti-Ram Bollards Prepared for: RSA Protective Technologies, LLC 1573 Mimosa Court Upland, CA 91784 Test
More informationSECTION SWING CHECK VALVES
PART 1 GENERAL 1.1 DESCRIPTION This section includes materials, testing, and installation of swing check valves as shown in the Drawings and specified herein, in accordance with the requirements of the
More informationSPCT Method. The SPCT Method - Testing of Dog Crates. Utskrivet dokument är ostyrt, dvs inte säkert gällande.
Kvalitetsdokument Författare, enhet Mikael Videby Bygg och Mekanik Hållfasthet och konstruktion Utgåva 1 (7) Godkännare 2 The Testing of Dog Crates Application Area... 2 References... 2 1 Test Sample Selection...
More informationCRASH TEST OF MILE POST MARKER. T. J. Hirsch Research Engineer. and. Eugene Buth Assistant Research Engineer. Research Report Number 146-8
CRASH TEST OF MILE POST MARKER by T. J. Hirsch Research Engineer and Eugene Buth Assistant Research Engineer Research Report Number 146-8 Studies of Field Adaption of Impact Attenuation Systems Research
More informationAn Urgent Bulletin from CSA Group
Ref No: I15-014 Elevator Equipment No. 20 (Supersedes Elevator Equipment Certification Notice No. 1A, and Informs Elevator Equipment No 1B) Date: January 21, 2015 An Urgent Bulletin from CSA Group Existing
More information3M Brand Composite Conductor Connector Current Cycle Qualification Test for 795 kcmil Compression Connectors
3M Brand Composite Conductor Connector Current Cycle Qualification Test for 7 kcmil Compression Connectors 3M Company Purchase Orders 0000797063 and 0000866974 NEETRAC Project Number: 03-071 September,
More informationUTEC CORPORATION, / R&D LABORATORY 8500 SE JAYHAWK DR, RIVERTON, KANSAS (620) FAX (620)
UTEC CORPORATION, / R&D LABORATORY 85 SE JAYHAWK DR, RIVERTON, KANSAS 6677 (62) 783-1361 FAX (62) 783-136 EMAIL: john@utec-corp.com Project: Test N2 2 x14 Steel Bodied Generators for Heat Transfer and
More informationTEST REPORT UL Fire test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces
UL 2043 TEST REPORT Fire test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces Pipe Fixings TSMI TSMI Non-metallic Tubing Channel Clip for
More informationComparison of IG Testing Standard. IGMA Summer Meeting August 8, 2004
Comparison of IG Testing Standard IGMA Summer Meeting August 8, 2004 1 The Task Compare the new Harmonized standards to: Old ASTM stds. Canadian stds. CEN stds. (Europe) ISO std. (proposed) 2 The Standards
More informationTest Report Current (Gen 2) Pendant Armor and Gen 3 Pendant Armor Polymer A Hanger and Polymer B Hanger March 16, 2016 (Q022516U1R2) Testing Location
Client Roboworld Molded Products, LLC 8216 Pricinceton-Glendale Road, Suite 246 West Chester, OH 45069 Test Report Current (Gen 2) Pendant Armor and Gen 3 Pendant Armor Polymer A Hanger and Polymer B Hanger
More informationVIBRATION AND MECHANICAL SHOCK TEST REPORT
Report No. :DH1701190024A-1 Version:A VIBRATION AND MECHANICAL SHOCK TEST REPORT Company :OTO Photonics Inc. Address :9F-5,No. 27, Guanxin Rd., East Dist., Hsinchu City 30072, Taiwan(R.O.C.) Sample Name
More informationGuideline No.: E-03(201806) E-03 MOTORS. Issued date: June 7, China Classification Society
Guideline No.: E-03(201806) E-03 MOTORS Issued date: June 7, 2018 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements, inspection and testing
More informationLEGACY REPORT ER ICC Evaluation Service, Inc. Reissued May 1, Legacy report on the 1997 Uniform Building Code
LEGACY REPORT ER- Reissued May, 0 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 0 Workman Mill Road, Whittier, California 00 # () -0 Regional Office # 00 Montclair Road, Suite
More informationSection Traffic Doors
Section 08380 Traffic Doors SR 9000 Series Part 1: General 1.1 Summary 1. ABS outer skin, foamed in place insulated High Impact Traffic Doors. 2. Lower hinge guards 3. Spring Bumpers, Impact Plates 4.
More informationAAMA THERMAL PERFORMANCE REPORT. Rendered to: TORO ALUMINUM. SERIES/MODEL: Commdoor 225 Awning (Project Out) TYPE: Projecting, Awning
Architectural Testing AAMA 507-12 THERMAL PERFORMANCE REPORT Rendered to: TORO ALUMINUM SERIES/MODEL: Commdoor 225 Awning (Project Out) TYPE: Projecting, Awning Report No: Report Date: 130 Derry Court
More informationVoluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems
Task Group Approval Council Approval Product Group Approval Successful Re-ballot 16-1052 Successful Ballot (#17-1011) Out for Ballot #17-1062 AAMA 1304-XX DRAFT #6 DATED 10/4/2017 Voluntary Specification
More informationAAMA THERMAL PERFORMANCE REPORT (Revised) Rendered to: UNITED STATES ALUMINUM
AAMA 507-07 THERMAL PERFORMANCE REPORT (Revised) Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 7600 Projected Vent TYPE: Projecting (Awning - Single) Report No: Original Report Date: Revised Report
More informationOFS Brands Test Facility Report No: OFSB Date: April 2, 2015 Page: 1 of 29. Test Report For: ANSI/BIFMA X Storage Units.
Date: April 2, 2015 Page: 1 of 29 Test Report For: ANSI/BIFMA X5.9-2012 Storage Units FastenLink This report shall not be reproduced, except in full, without written permission from OFS Brands Quality
More informationCrashworthiness Evaluation. Roof Strength Test Protocol (Version III)
Crashworthiness Evaluation Roof Strength Test Protocol (Version III) July 2016 CRASHWORTHINESS EVALUATION ROOF STRENGTH TEST PROTOCOL (VERSION III) Supporting documents for the Insurance Institute for
More informationPlanet Range of TERRA BOLLARDS
Planet Range of TERRA BOLLARDS Frontier Pitts manufacture a portfolio of IWA 14 & PAS 68 bollards, each proven to stop the different energy ratings of the HVM (Hostile Vehicle Mitigation) specification.
More informationBS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference:
Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN 14351-1:2006 Test
More informationReport No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength
Report No: 181947 Test of: Reversible aluminium/timber window Tested to: BS 6375-2:2009 Performance of windows & doors Part 2: Operation & strength For: A/S Peder Nielsen Beslagfabrik Norregade 25 Bronderslev
More informationReport No 2370/ This Report consists of 40 pages. Authority & date Request by Client dated 25 November 2010
Test Report Report No 2370/7612199 This Report consists of 40 pages Client Smarts Systems Limited Arnolds Way Yatton BS49 4QN Authority & date Request by Client dated 25 November 2010 Items tested 3 off
More information1 st Quarter Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations. Prepared for:
1 st Quarter 2018 Summary of Meteorological and Ambient Air Quality Data Kennecott Utah Copper Monitoring Stations Prepared for: Prepared by: Mr. Bryce C. Bird Director Division of Air Quality 195 North
More informationMESA Cornerstone Segmental Retaining Wall Unit and Tensar Geogrid Connection Strength Testing
MESA Cornerstone Segmental Retaining Wall Unit and Tensar Geogrid Connection Strength Testing Prepared for Tensar Earth Technologies, Inc. 5883 Glenridge Drive, Suite 2 Atlanta, GA 3328 Prepared by National
More informationOptical Techniques in Gasoline Engine Performance and Emissions Development Injector Spray Visualisation
Injector Spray Visualisation Denis Gill, Wolfgang Krankenedl, DEC Ernst Winklhofer 20.03.15 Emissions Development Injector Spray Visualisation Contents Introduction Spray Box Direct Injection (GDI) Spray
More informationGeorgia Pacific Crossett Operations Hydrogen Sulfide and Meteorological Monitoring Program
Results you can rely on Georgia Pacific Crossett Operations Hydrogen Sulfide and Meteorological Monitoring Program 6-Month Report for October 1, 2014 through March 31, 2015 TRC Project Number: 222437.0000.0000
More informationSFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 *
SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * PRODUCT: Heavy Duty Stock Car Steel Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards
More informationFAAC International, Inc.
TEST REPORT FOR: FAAC International, Inc. J 355 HA M30 (K4) Bollard TESTED TO: ASTM F 2656-07 Standard Test Method for Vehicle Crash Testing of Perimeter Barriers Test M30 PREPARED FOR: FAAC International,
More informationGuideline No.: E-03(201610) E-03 MOTORS. Issued date: October 28,2016. China Classification Society
Guideline No.: E-03(201610) E-03 MOTORS Issued date: October 28,2016 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements, inspection and
More information24" DLO 24" DLO 1 1/2" 1 1/2" 1 1/2" 1 1/2" 1 1/2" " FRAME DIMENSION 34" DAYLITE OPENING 1/8" 85 1/2" FRAME DIMENSION 3 OPP 3.
SERIES 87-AR SINGLE AND DOUBLE BUTT HINGE HUNG DOORS W/ & W/O SIDELITE(S), W/ & W/O TRANSOM SHOWN WITH OPTIONAL CRL WOOD FLUSH DOOR SYSTEM DESIGNED TO WRAP -7/8" ( MM) WALLS DESIGNED FOR TOP LOAD GASKETS
More informationRevision 1 January 10, 2018
Kalsi Seals Handbook Chapter C7 BDRP rotary shaft seals Revision 1 January 10, 2018 Individual chapters of the Kalsi Seals Handbook are periodically updated. To determine if a newer revision of this chapter
More informationILED Dorado. User Manual
10NM U-code Medium Intensity Obstruction Light Helideck Status Light 15NM U-code Contents 1. Safety... 3 2. Warranty... 3 2.1 General... 3 2.2 Life span... 3 3. Type plate... 4 4. Product Description...
More information95/115D 65/ HSX20. Shock Test Systems
Mechanical shock tests accurately measure the fragility of products and evaluate how they respond to particular shock inputs. Shock test data is key information to ensure any product is capable of withstanding
More informationSAFETY COMPLIANCE TESTING FOR FMVSS 202a Head Restraints
FINAL REPORT NUMBER 202a-MGA-10-003 SAFETY COMPLIANCE TESTING FOR FMVSS 202a FORD MOTOR COMPANY 2010 Lincoln MKT MPV NHTSA No. CA0213 MGA RESEARCH CORPORATION 446 Executive Drive Troy, Michigan 48083 Test
More informationAFCEC-CX-TY-TR
AFCEC-CX-TY-TR-2013-0013 DEFORMED SHAPE ANALYSIS OF COUPLED GLAZING SYSTEMS Ryan Alberson and Carrie Davis Protection Engineering Consultants 14144 Trautwein Road Austin, TX 78737 Kirk Marchand Protection
More informationStandards & Regulations Guide. For manual attacks/ballistic/blast resistance
Standards & Regulations Guide For manual attacks/ballistic/blast resistance Standards & regulations Guide Which level of security is suitable for your needs? Vandalism, manual attacks, ballistic attacks,
More information