TEN YEAR FORECAST OF FAULT LEVELS SEPTEMBER 2016

Size: px
Start display at page:

Download "TEN YEAR FORECAST OF FAULT LEVELS SEPTEMBER 2016"

Transcription

1 TEN YEAR FORECAST OF FAULT LEVELS SEPTEMBER 2016

2 Introduction This publication presents an update to the ten year forecast fault levels report. The Connection Code contained in Schedule 8 to the Benchmark Agreement requires Transpower to publish a ten year forecast of the expected fault levels at each customer point of service annually. 1 Transpower last published the Ten Year Forecast of Fault Levels in September Connection Code clause 4.2(g): to publish annually a 10 year forecast of the expected minimum and maximum fault level at each customer point of service.

3 Index INTRODUCTION... 2 INDEX... 3 FORECAST FAULT LEVELS CALCULATION ASSUMPTIONS... 4 TEN YEAR FORECAST OF MAXIMUM THREE-PHASE FAULT LEVELS... 6 NORTHLAND... 6 AUCKLAND... 6 WAIKATO... 7 BAY OF PLENTY... 8 CENTRAL NORTH ISLAND... 9 TARANAKI HAWKE S BAY WELLINGTON NELSON-MARLBOROUGH WEST COAST CANTERBURY SOUTH CANTERBURY OTAGO-SOUTHLAND TEN YEAR FORECAST OF MAXIMUM SINGLE-PHASE TO GROUND FAULT LEVELS.. 16 NORTHLAND AUCKLAND WAIKATO BAY OF PLENTY CENTRAL NORTH ISLAND TARANAKI HAWKE S BAY WELLINGTON NELSON-MARLBOROUGH WEST COAST CANTERBURY SOUTH CANTERBURY OTAGO-SOUTHLAND... 24

4 Forecast fault levels calculation assumptions Calculated fault levels are very dependent on the assumptions used in, and method of, the calculation. Minimum fault level calculations depend on generation and grid asset dispatch assumptions, and are generally used for ensuring the coordination of protection relays between asset owners. Protection coordination has very important consequences for power system security and safety of people and assets. Accordingly, we are not going to publish minimum fault levels which may be misunderstood and used in a way that threatens security and safety. We encourage connected parties to talk with us directly on matters concerning protection coordination. Table 3 and Table 4 list the maximum three-phase fault current and maximum single-phase to ground fault current respectively for all Transpower s transmission buses. Both tables list the 10 year forecast of fault current for existing grid configuration. The listed value is the initial RMS symmetrical short-circuit current (I k ) as defined by IEC The 10 year forecast of maximum fault levels is based on information currently known to Transpower. The values in the tables should be regarded as indicative only. We have modelled committed future transmission upgrades and generation projects using the best information we have at this time. We know that towards the end of the 10 year period, there may be additional transmission upgrades and additional generation required to meet the power and energy requirements of New Zealand. We do not know exactly the nature or location of these future transmission upgrades and new generation. The maximum fault level at a transmission bus 2 may also change where the number of supply transformers increase or get replaced as part of a Service Change to meet load growth or provide supply security. Therefore the maximum short-circuit currents listed should not be relied upon for specifying shortcircuit requirements for new substation equipment. The forecast fault levels provide an early warning of when plant capability may be exceeded. Accordingly, while Transpower endeavours to forecast fault levels accurately, the levels may change for a number of reasons and Transpower does not accept liability for other parties reliance on the fault values contained in the forecast. We encourage asset owners to consult with us for detailed information on maximum fault levels at specific sites relating to new equipment connection. The Connection Code (5.1(h)) puts an obligation on Transpower and the customer to ensure equipment connected to the grid does not cause the maximum short-circuit power and current limits in Appendix B Table B2 of the Connection Code to be exceeded on or nearby to the grid. Table 1 shows the short-circuit power and limits in Table B2 of Appendix B of the Connection Code. Note that the fault levels at some buses are already near or exceed these values. Table 1: Maximum short-circuit power and current limits Nominal voltage (kv) Maximum short-circuit power and current limits (MVA) (ka) , , , , , This report includes the maximum fault level for all Transpower s transmission buses, which encompasses customer point of service. 4 Transpower New Zealand Limited 2016.All rights reserved.

5 We have calculated maximum fault levels in Table 3 and Table 4 using the 2001 IEC method. The values are the initial RMS symmetrical short-circuit levels. The fault levels have been calculated on the following basis: All generating units and all transmission assets are assumed to be in service. A full representation of the existing transmission grid, directly connected generation and embedded generation above 1 MW known to us is assumed. The existing wind farms are assumed to provide only full load current into a fault. Motor loads are not modelled. The breaker time is 0.1 seconds and the fault clearing time is 1 second. The fault impedance is zero ohms. Future committed changes to the power system including transmission upgrades and new generation detailed in the 2015 Transmission Planning Report. We represented new transmission lines in the model with electrical parameters estimated from the best matches with existing lines of the same conductor type. We have represented committed generation in our power system model with their electrical parameters scaled from the latest example which their type is known to us. We based the timing of these connections on open discussion with the asset owner, and from the generator s website. The actual commissioning date may vary. See Table 2 the assumption of fault current contributions from future generation Table 2: Fault current contributions from future generation Category Technology / application Fault current contribution (per unit of capacity) Thermal Coal, diesel, combined cycle gas turbine, open cycle gas turbine, gas-fired peaker, cogeneration 2.87 Thermal Geothermal 3.60 Hydro Peak hydro, stored hydro, run of river 3.67 Wind Wind 0.0 Solar Photovoltaic 0.0 Load Interruptible load, demand side response 0.0 Transpower New Zealand Limited 2016.All rights reserved. 5

6 Ten year forecast of maximum three-phase fault levels Table 3: Ten year forecast of maximum three-phase fault levels (ka) Grid exit point Transmission bus NORTHLAND Bream Bay 33 kv Bream Bay 220 kv Marsden 110 kv Marsden 220 kv Maungatapere 110 kv Maungaturoto 33 kv Maungaturoto 110 kv (T1) Maungaturoto 110 kv (T2) Wellsford 33 kv Wellsford 110 kv (T1) Wellsford 110 kv (T2) AUCKLAND Albany 33 kv Albany 110 kv Albany 220 kv Bombay 33 kv Bombay 110 kv Drury 220 kv Glenbrook 33 kv (T4/T5) Glenbrook 33 kv (T6) Glenbrook 220 kv Henderson 33 kv Henderson 110 kv Henderson 220 kv Hepburn Road 33 kv Hepburn Road 110 kv Hobson Street 110 kv Hobson Street 220 kv Huapai 220 kv Mangere 33 kv Mangere 110 kv Mount Roskill 22 kv Mount Roskill 110 kv Otahuhu 22 kv Otahuhu 110 kv (T2/T4) Otahuhu 110 kv (T3/T5) Transpower New Zealand Limited 2016.All rights reserved.

7 Otahuhu 220 kv Pakuranga 33 kv Pakuranga 220 kv Penrose 22 kv Penrose 33 kv Penrose 110 kv Penrose 220 kv Silverdale 33 kv Silverdale 220 kv (T1) Silverdale 220 kv (T2) Southdown 220 kv Takanini 33 kv Takanini 220 kv (T5) Takanini 220 kv (T8) Wairau Road 33 kv Wairau Road 220 kv Wiri 33 kv Wiri 110 kv (T1) Wiri 110 kv (T2) WAIKATO Arapuni 110 kv (North Bus) Arapuni 110 kv (South Bus) Atiamuri 220 kv Cambridge 11 kv Cambridge 110 kv (T3) Cambridge 110 kv (T4) Hamilton 11 kv Hamilton 33 kv Hamilton 110 kv Hamilton 220 kv Hangatiki 33 kv Hangatiki 110 kv Hinuera 33 kv Hinuera 110 kv Huntly 11 kv Huntly 33 kv Huntly 220 kv Karapiro 110 kv Kinleith 11 kv (T1A) Kinleith 11 kv (T2) Kinleith 11 kv (T3A and T3B) Kinleith 11 kv (T5) Kinleith 33 kv Kinleith 110 kv Transpower New Zealand Limited 2016.All rights reserved. 7

8 Kopu 66 kv Kopu 110 kv (T3) Kopu 110 kv (T4) Lichfield 110 kv (T1) Lichfield 110 kv (T2) Maraetai 220 kv Ohakuri 220 kv Ohinewai 220 kv Piako 110 kv Te Awamutu 11 kv Te Awamutu 110 kv Te Kowhai 33 kv Te Kowhai 220 kv Waihou 33 kv Waihou 110 kv Waikino 33 kv Waikino 110 kv Waipapa 220 kv Whakamaru 220 kv BAY OF PLENTY Aniwhenua 110 kv Edgecumbe 33 kv Edgecumbe 110 kv Edgecumbe 220 kv Kaitimako 33 kv Kaitimako 110 kv Kaitimako 220 kv Kawerau 11 kv (T1/T2) Kawerau 11 kv (T6) Kawerau 11 kv (T7) Kawerau 11 kv (T8) Kawerau 11 kv (T9) Kawerau 11 kv (T11/T14) Kawerau 110 kv Kawerau 220 kv Matahina 110 kv Mt Maunganui 33 kv Mt Maunganui 110 kv Okere 110 kv Owhata 11 kv Owhata 110 kv Rotorua 11 kv Rotorua 33 kv Rotorua 110 kv (Tarukenga 1) Transpower New Zealand Limited 2016.All rights reserved.

9 Rotorua 110 kv (Tarukenga 2) Tarukenga 11 kv Tarukenga 110 kv Tarukenga 220 kv Tauranga 11 kv Tauranga 33 kv Tauranga 110 kv Te Kaha 11 kv Te Kaha 50 kv Te Matai 33 kv Te Matai 110 kv Waiotahi 11 kv Waiotahi 50 kv Waiotahi 110 kv CENTRAL NORTH ISLAND Aratiatia 220 kv Bunnythorpe 33 kv Bunnythorpe 110 kv Bunnythorpe 220 kv Dannevirke 11 kv Dannevirke 110 kv (T1) Dannevirke 110 kv (T2) Linton 33 kv Linton 220 kv (T2) Linton 220 kv (T3) Mangahao 33 kv Mangahao 110 kv (T3) Mangahao 110 kv (T4) Mangamaire 33 kv Mangamaire 110 kv Marton 33 kv Marton 110 kv (T1) Marton 110 kv (T2) Mataroa 33 kv Mataroa 110 kv National Park 33 kv National Park 110 kv Nga Awa Purua 220 kv Ngatamariki 220 kv Ohaaki 220 kv Ohakune 11 kv Ohakune 110 kv Ongarue 33 kv Ongarue 110 kv Transpower New Zealand Limited 2016.All rights reserved. 9

10 Poihipi 220 kv Rangipo 220 kv Tangiwai 11 kv Tangiwai 220 kv Tararua Central 220 kv Te Mihi 220 kv Tokaanu 33 kv Tokaanu 220 kv Waipawa 11 kv Waipawa 33 kv Waipawa 110 kv (T1) Waipawa 110 kv (T2) Wairakei 33 kv Wairakei 220 kv Woodville 11 kv Woodville 110 kv TARANAKI Brunswick 33 kv Brunswick 220 kv Carrington St 33 kv Carrington St 110 kv Hawera 33 kv (T1/T2) Hawera 33 kv (T3) Hawera 110 kv Huirangi 33 kv Huirangi 110 kv Junction Road Tee 110 kv Kapuni Tee 110 kv McKee Tee 110 kv Motunui 11 kv (T3) Motunui 11 kv (T4) Motunui 110 kv New Plymouth 33 kv New Plymouth 110 kv New Plymouth 220 kv Opunake 33 kv Opunake 110 kv (T4) Opunake 110 kv (T5) Stratford 33 kv Stratford 110 kv Stratford 220 kv Taumarunui 220 kv Wanganui 33 kv Wanganui 110 kv Transpower New Zealand Limited 2016.All rights reserved.

11 Waverley 11 kv Waverley 110 kv HAWKE S BAY Fernhill 33 kv Fernhill 110 kv Redclyffe 33 kv Redclyffe 110 kv Redclyffe 220 kv Tuai 110 kv Whakatu 33 kv Whakatu 220 kv (T3) Whakatu 220 kv (T4) Whirinaki 11 kv (T1) Whirinaki 11 kv (T2) Whirinaki 11 kv (T3) Whirinaki 220 kv WELLINGTON Central Park 11 kv (T11) Central Park 11 kv (T12) Central Park 33 kv Central Park 110 kv (T3) Central Park 110 kv (T4) Central Park 110 kv (T5) Gracefield 33 kv Gracefield 110 kv (T5) Gracefield 110 kv (T6) Greytown 33 kv Greytown 110 kv (T2) Greytown 110 kv (T3) Haywards 11 kv Haywards 33 kv Haywards 110 kv Haywards 220 kv Kaiwharawhara 11 kv (T1) Kaiwharawhara 11 kv (T3) Kaiwharawhara 110 kv (T1) Kaiwharawhara 110 kv (T3) Masterton 33 kv Masterton 110 kv Melling 11 kv Melling 33 kv Transpower New Zealand Limited 2016.All rights reserved. 11

12 Melling 110 kv (T1/T3) Melling 110 kv (T2/T4) Paraparaumu 33 kv Paraparaumu 220 kv (T1) Paraparaumu 220 kv (T2) Pauatahanui 33 kv Pauatahanui 110 kv (T1) Pauatahanui 110 kv (T2) Takapu Road 33 kv Takapu Road 110 kv Upper Hutt 33 kv Upper Hutt 110 kv West Wind 110 kv (Circuit 2) West Wind 110 kv (Circuit 3) Wilton 33 kv Wilton 110 kv Wilton 220 kv NELSON-MARLBOROUGH Argyle 110 kv Blenheim 33 kv Blenheim 110 kv Stoke 33 kv Stoke 66 kv Stoke 110 kv Stoke 220 kv WEST COAST Arthurs Pass 11 kv Arthurs Pass 66 kv Atarau 110 kv Castle Hill 11 kv Castle Hill 66 kv Dobson 33 kv Dobson 66 kv Dobson T11 (110 kv) Dobson T12 (110 kv) Greymouth 66 kv Hokitika 66 kv Inangahua 110 kv Kikiwa 11 kv Kikiwa 110 kv Kikiwa 220 kv Transpower New Zealand Limited 2016.All rights reserved.

13 Kumara 66 kv Murchison 11 kv Murchison 110 kv Orowaiti 110 kv (Circuit 1) Orowaiti 110 kv (Circuit 2) Otira 11 kv Otira 66 kv Reefton 110 kv (Circuit 1) Reefton 110 kv (Circuit 2) Waimangaroa 110 kv (Circuit 1) Waimangaroa 110 kv (Circuit 2) Westport 11 kv Westport 110 kv (T1) Westport 110 kv (T2) CANTERBURY Ashburton 33 kv Ashburton 66 kv Ashburton 220 kv Ashley 11 kv (T5) Ashley 11 kv (T3) Ashley 66 kv Bromley 66 kv Bromley 220 kv Coleridge 11 kv Coleridge 66 kv Culverden 33 kv Culverden 66 kv Culverden 220 kv (T22) Culverden 220 kv (T23) Hororata 33 kv Hororata 66 kv Islington 33 kv Islington 66 kv Islington 220 kv Kaiapoi 11 kv Kaiapoi 66 kv Kimberley 66 kv (T1) Kimberley 66 kv (T2) Southbrook 33 kv Southbrook 66 kv Waipara 33 kv Waipara 66 kv Waipara 220 kv (T12) Waipara 220 kv (T13) Transpower New Zealand Limited 2016.All rights reserved. 13

14 SOUTH CANTERBURY Albury 11 kv Albury 110 kv Aviemore 220 kv Bells Pond 110 kv Benmore 220 kv Black Point 110 kv Livingstone 220 kv Oamaru 33 kv Oamaru 110 kv (T1) Oamaru 110 kv (T2) Ohau A 220 kv Ohau B 220 kv Ohau C 220 kv Studholme 11 kv Studholme 110 kv Tekapo A 11 kv Tekapo A 33 kv Tekapo A 110 kv Tekapo B 220 kv Temuka 33 kv Temuka 110 kv (T1) Temuka 110 kv (T2) Timaru 11 kv Timaru 110 kv Timaru 220 kv (T5) Timaru 220 kv (T8) Twizel 33 kv (T18) Twizel 33 kv (T19) Twizel 220 kv Waitaki 11 kv (T28) Waitaki 33 kv (T28) Waitaki 220 kv OTAGO-SOUTHLAND Balclutha 33 kv Balclutha 110 kv Berwick 110 kv Brydone 11 kv Brydone 110 kv Clyde 33 kv Clyde 220 kv Cromwell 33 kv Transpower New Zealand Limited 2016.All rights reserved.

15 Cromwell 110 kv (T5A/B) Cromwell 110 kv (T8) Cromwell 220 kv (T5A/B) Cromwell 220 kv (T8) Edendale 33 kv Edendale 110 kv Frankton 33 kv Frankton 110 kv (T2) Frankton 110 kv (T4) Gore 33 kv Gore 110 kv (T2/T3) Gore 110 kv Gore 220 kv (T11) Gore 220 kv (T12) Halfway Bush 33 kv (T1/T2) Halfway Bush 33 kv (T5) Halfway Bush 110 kv Halfway Bush 220 kv Invercargill 33 kv Invercargill 110 kv Invercargill 220 kv Manapouri 220 kv North Makarewa 33 kv North Makarewa 220 kv Naseby 33 kv Naseby 220 kv Roxburgh 110 kv Roxburgh 220 kv South Dunedin 33 kv South Dunedin 220 kv Three Mile Hill 220 kv Tiwai 220 kv Transpower New Zealand Limited 2016.All rights reserved. 15

16 Ten year forecast of maximum single-phase to ground fault levels Table 4: Ten year forecast of maximum single-phase to ground fault levels (ka) Grid exit point Transmission bus NORTHLAND Bream Bay 33 kv Bream Bay 220 kv Marsden 110 kv Marsden 220 kv Maungatapere 110 kv Maungaturoto 33 kv Maungaturoto 110 kv (T1) Maungaturoto 110 kv (T2) Wellsford 33 kv Wellsford 110 kv (T1) Wellsford 110 kv (T2) AUCKLAND Albany 33 kv Albany 110 kv Albany 220 kv Bombay 33 kv Bombay 110 kv Drury 220 kv Glenbrook 33 kv (T4/T5) Glenbrook 33 kv (T6) Glenbrook 220 kv Henderson 33 kv Henderson 110 kv Henderson 220 kv Hepburn Road 33 kv Hepburn Road 110 kv Hobson Street 110 kv Hobson Street 220 kv Huapai 220 kv Mangere 33 kv Mangere 110 kv Mount Roskill 22 kv Mount Roskill 110 kv Otahuhu 22 kv Otahuhu 110 kv (T2/T4) Transpower New Zealand Limited 2016.All rights reserved.

17 Otahuhu 110 kv (T3/T5) Otahuhu 220 kv Pakuranga 33 kv Pakuranga 220 kv Penrose 22 kv Penrose 33 kv Penrose 110 kv Penrose 220 kv Silverdale 33 kv Silverdale 220 kv (T1) Silverdale 220 kv (T2) Southdown 220 kv Takanini 33 kv Takanini 220 kv (T5) Takanini 220 kv (T8) Wairau Road 33 kv Wairau Road 220 kv Wiri 33 kv Wiri 110 kv (T1) Wiri 110 kv (T2) WAIKATO Arapuni 110 kv (North Bus) Arapuni 110 kv (South Bus) Atiamuri 220 kv Cambridge 11 kv Cambridge 110 kv (T3) Cambridge 110 kv (T4) Hamilton 11 kv Hamilton 33 kv Hamilton 110 kv Hamilton 220 kv Hangatiki 33 kv Hangatiki 110 kv Hinuera 33 kv Hinuera 110 kv Huntly 11 kv Huntly 33 kv Huntly 220 kv Karapiro 110 kv Kinleith 11 kv (T1A) Kinleith 11 kv (T2) Kinleith 11 kv (T3A and T3B) Kinleith 11 kv (T5) Transpower New Zealand Limited 2016.All rights reserved. 17

18 Kinleith 33 kv Kinleith 110 kv Kopu 66 kv Kopu 110 kv (T3) Kopu 110 kv (T4) Lichfield 110 kv (T1) Lichfield 110 kv (T2) Maraetai 220 kv Ohakuri 220 kv Ohinewai 220 kv Piako 110 kv Te Awamutu 11 kv Te Awamutu 110 kv Te Kowhai 33 kv Te Kowhai 220 kv Waihou 33 kv Waihou 110 kv Waikino 33 kv Waikino 110 kv Waipapa 220 kv Whakamaru 220 kv BAY OF PLENTY Aniwhenua 110 kv Edgecumbe 33 kv Edgecumbe 110 kv Edgecumbe 220 kv Kaitimako 33 kv Kaitimako 110 kv Kaitimako 220 kv Kawerau 11 kv (T1/T2) Kawerau 11 kv (T6) Kawerau 11 kv (T7) Kawerau 11 kv (T8) Kawerau 11 kv (T9) Kawerau 11 kv (T11/T14) Kawerau 110 kv Kawerau 220 kv Matahina 110 kv Mt Maunganui 33 kv Mt Maunganui 110 kv Okere 110 kv Owhata 11 kv Owhata 110 kv Rotorua 11 kv Transpower New Zealand Limited 2016.All rights reserved.

19 Rotorua 33 kv Rotorua Rotorua 110 kv (Tarukenga 1) 110 kv (Tarukenga 2) Tarukenga 11 kv Tarukenga 110 kv Tarukenga 220 kv Tauranga 11 kv Tauranga 33 kv Tauranga 110 kv Te Kaha 11 kv Te Kaha 50 kv Te Matai 33 kv Te Matai 110 kv Waiotahi 11 kv Waiotahi 50 kv Waiotahi 110 kv CENTRAL NORTH ISLAND Aratiatia 220 kv Bunnythorpe 33 kv Bunnythorpe 110 kv Bunnythorpe 220 kv Dannevirke 11 kv Dannevirke 110 kv (T1) Dannevirke 110 kv (T2) Linton 33 kv Linton 220 kv (T2) Linton 220 kv (T3) Mangahao 33 kv Mangahao 110 kv (T3) Mangahao 110 kv (T4) Mangamaire 33 kv Mangamaire 110 kv Marton 33 kv Marton 110 kv (T1) Marton 110 kv (T2) Mataroa 33 kv Mataroa 110 kv National Park 33 kv National Park 110 kv Nga Awa Purua 220 kv Ngatamariki 220 kv Ohaaki 220 kv Ohakune 11 kv Transpower New Zealand Limited 2016.All rights reserved. 19

20 Ohakune 110 kv Ongarue 33 kv Ongarue 110 kv Poihipi 220 kv Rangipo 220 kv Tangiwai 11 kv Tangiwai 220 kv Tararua Central 220 kv Te Mihi 220 kv Tokaanu 33 kv Tokaanu 220 kv Waipawa 11 kv Waipawa 33 kv Waipawa 110 kv (T1) Waipawa 110 kv (T2) Wairakei 33 kv Wairakei 220 kv Woodville 11 kv Woodville 110 kv TARANAKI Brunswick 33 kv Brunswick 220 kv Carrington St 33 kv Carrington St 110 kv Hawera 33 kv (T1/T2) Hawera 33 kv (T3) Hawera 110 kv Huirangi 33 kv Huirangi 110 kv Junction Road Tee 110 kv Kapuni Tee 110 kv McKee Tee 110 kv Motunui 11 kv (T3) Motunui 11 kv (T4) Motunui 110 kv New Plymouth 33 kv New Plymouth 110 kv New Plymouth 220 kv Opunake 33 kv Opunake 110 kv (T4) Opunake 110 kv (T5) Stratford 33 kv Stratford 110 kv Transpower New Zealand Limited 2016.All rights reserved.

21 Stratford 220 kv Taumarunui 220 kv Wanganui 33 kv Wanganui 110 kv Waverley 11 kv Waverley 110 kv HAWKE S BAY Fernhill 33 kv Fernhill 110 kv Redclyffe 33 kv Redclyffe 110 kv Redclyffe 220 kv Tuai 110 kv Whakatu 33 kv Whakatu 220 kv (T3) Whakatu 220 kv (T4) Whirinaki 11 kv (T1) Whirinaki 11 kv (T2) Whirinaki 11 kv (T3) Whirinaki 220 kv WELLINGTON Central Park 11 kv (T11) Central Park 11 kv (T12) Central Park 33 kv Central Park 110 kv (T3) Central Park 110 kv (T4) Central Park 110 kv (T5) Gracefield 33 kv Gracefield 110 kv (T5) Gracefield 110 kv (T6) Greytown 33 kv Greytown 110 kv (T2) Greytown 110 kv (T3) Haywards 11 kv Haywards 33 kv Haywards 110 kv Haywards 220 kv Kaiwharawhara 11 kv (T1) Kaiwharawhara 11 kv (T3) Kaiwharawhara 110 kv (T1) Kaiwharawhara 110 kv (T3) Transpower New Zealand Limited 2016.All rights reserved. 21

/14 QUALITY PERFORMANCE REPORT. QUALITY PERFORMANCE REPORT 2013/14

/14 QUALITY PERFORMANCE REPORT.  QUALITY PERFORMANCE REPORT 2013/14 QUALITY PERFORMANCE REPORT 213/14 www.transpower.co.nz QUALITY PERFORMANCE REPORT 213 /14 Contents Contents... 1 Highlights... 2 From the Chief Executive... 3 1 Management and Operation of Transpower s

More information

Submission for Tactical Transmission Upgrade Approval

Submission for Tactical Transmission Upgrade Approval Submission for Tactical Transmission Upgrade Approval April 2005 Electricity Commission Submission Tactical Transmission Projects April 05 1 Executive Summary Transpower seeks approval from the Electricity

More information

UNI Generation Decommissioning Report

UNI Generation Decommissioning Report UNI Generation Decommissioning Report APPENDIX 1: Upper North Island Dynamic Reactive Support - Need Analysis March 2016 Report No: Prepared By: Group Manager: NP622 Si Kuok Ting NIKKI NEWHAM File: Contents

More information

3 Existing National Grid

3 Existing National Grid 3 Existing National Grid 3.1 Introduction 3.2 Load and generation 3.1 Introduction This chapter provides an overview of New Zealand s existing National Grid as at 28 February 2012 with respect to load

More information

System Operator Reports December Contents System Operator Monthly Operational Performance Report System Performance Report

System Operator Reports December Contents System Operator Monthly Operational Performance Report System Performance Report System Operator Reports December 2010 Contents Section 1 Section 2 System Operator Monthly Operational Performance Report System Performance Report Operational Performance Report to the Electricity Authority

More information

2016 INTEGRATED TRANSMISSION PLAN SCHEDULES SEPTEMBER 2016

2016 INTEGRATED TRANSMISSION PLAN SCHEDULES SEPTEMBER 2016 2016 INTEGRATED TRANSMISSION PLAN SCHEDULES SEPTEMBER 2016 Contents 1 Expenditure overview Summary of all capital and operating expenditure 2 Base capital expenditure Capital expenditure by asset class

More information

Horowhenua District Council Local Authority. Transpower New Zealand Limited Submitter

Horowhenua District Council Local Authority. Transpower New Zealand Limited Submitter Before a Hearing Panel at Levin under: the Resource Management Act 1991 in the matter of: between: and: The Proposed Horowhenua District Plan - Rural Environment Horowhenua District Council Local Authority

More information

SSF Section Location of Change SSF Issue Change(s) Comments Chapter Part B All Multiple Formatting, spelling and minor Changes applied -

SSF Section Location of Change SSF Issue Change(s) Comments Chapter Part B All Multiple Formatting, spelling and minor Changes applied - SSF Update December 2017 Summary of Changes This table only mentions SSF chapters that were updated. All other SSF chapters were checked and confirmed as still being uptodate. SSF Section Location of Change

More information

EFFECT OF SOLAR PV ON TRANSIENT STABILITY OF THE NEW ZEALAND POWER SYSTEM

EFFECT OF SOLAR PV ON TRANSIENT STABILITY OF THE NEW ZEALAND POWER SYSTEM EFFECT OF SOLAR PV ON TRANSIENT STABILITY OF THE NEW ZEALAND POWER SYSTEM DECEMBER 2017 TECHNICAL REPORT Table of Contents Table of Contents EXECUTIVE SUMMARY... VIII 1 INTRODUCTION...1 1.1 Programme

More information

PlaceMakers WARDROBES YOUR GUIDE TO A COMPLETE WARDROBE SOLUTION

PlaceMakers WARDROBES YOUR GUIDE TO A COMPLETE WARDROBE SOLUTION PlaceMakers WARDROBES YOUR GUIDE TO A COMPLETE WARDROBE SOLUTION ELEGANTLY ORGANISED Made to order wardrobes with a range of standard size configurations or created custom to your requirements. You choose

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Property Market Report

Property Market Report Property ket Report Dwellings Median Price Comparison Over Last 10 Years 07 April, 17:00:54 District 2008 2009 2010 2011 2012 Northland $325,000 $311,000 $319,000 $331,000 $315,000 $300,000 $309,000 $320,500

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Electric vehicles demand forecast. Erwan Hemery and Bruce Smith

Electric vehicles demand forecast. Erwan Hemery and Bruce Smith Electric vehicles demand forecast Erwan Hemery and Bruce Smith Friday 9 th February Introduction Growing interest in Electric Vehicles (EVs) International developments EVs included in the SoO scenarios

More information

Suburb Stockist Address Phone Post Code. ASHBURTON BNT Ashburton 107 Moore Street

Suburb Stockist Address Phone Post Code. ASHBURTON BNT Ashburton 107 Moore Street ASHBURTON BNT Ashburton 107 Moore Street 03 307 6192 7700 ASHBURTON Repco Ashburton Cnr Grey & East Streets 03 307 8092 7700 AUCKLAND Appco Central 111 Station Road, Otahuhu 09 570 2226 1062 AUCKLAND Appco

More information

Powerco Limited. Electricity Pricing Schedule

Powerco Limited. Electricity Pricing Schedule Powerco Limited Electricity Pricing Schedule Effective 1 April 2012 TABLE OF CONTENTS PART A: GENERAL TERMS AND CONDITIONS... 3 1.0 INTRODUCTION... 3 2.0 INTERPRETATION... 3 3.0 ICP STATUS... 3 4.0 SELECTION

More information

Powerco Limited. Electricity Price Schedule. Effective 1 April 2011

Powerco Limited. Electricity Price Schedule. Effective 1 April 2011 Powerco Limited Electricity Price Schedule Effective 1 April 2011 TABLE OF CONTENTS PART A: GENERAL TERMS AND CONDITIONS...3 1.0 INTRODUCTION... 3 2.0 INTERPRETATION... 3 3.0 ICP STATUS... 3 4.0 SELECTION

More information

Knife Gate we PIPE ( ) Resilient Seat Highly Ground Gate. W4.18 Hydrotite Knife Gate Valves Stainless Steel December 2012

Knife Gate we PIPE ( )  Resilient Seat Highly Ground Gate. W4.18 Hydrotite Knife Gate Valves Stainless Steel December 2012 Knife Gate Valves Stainless Steel Resilient Seat Highly Ground Gate W4.18 Hydrotite Knife Gate Valves Stainless Steel December 2012 0800 we PIPE (93 7473) www.hynds.co.nz The XDV-150 range features investment

More information

ROAD USER BEHAVIOUR SURVEYS

ROAD USER BEHAVIOUR SURVEYS ROAD USER BEHAVIOUR SURVEYS Photo courtesy of NZTA 154 MOTOR VEHICLE CRASHES IN NEW ZEALAND 2012 ROAD USER BEHAVIOUR SURVEYS 155 CONTENTS TABLES Table 1 Safety belt wearing rates for front seat adults

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

ELECTRICITY PRICING METHODOLOGY 2017

ELECTRICITY PRICING METHODOLOGY 2017 ELECTRICITY PRICING METHODOLOGY 2017 EFFECTIVE 1 APRIL 2017 DISCLOSED IN ACCORDANCE WITH SECTION 2.4.1 OF THE ELECTRICITY DISTRIBUTION INFORMATION DISCLOSURE DETERMINATION 2012 CONTENTS PAGE 1. Definitions...

More information

TRANSPOWER PLANS, BUILDS, MAINTAINS AND OPERATES NEW ZEALAND S HIGH VOLTAGE ELECTRICITY TRANSMISSION NETWORK THE NATIONAL GRID.

TRANSPOWER PLANS, BUILDS, MAINTAINS AND OPERATES NEW ZEALAND S HIGH VOLTAGE ELECTRICITY TRANSMISSION NETWORK THE NATIONAL GRID. A GUIDE TO TRANSPOWER 2009 TRANSPOWER PLANS, BUILDS, MAINTAINS AND OPERATES NEW ZEALAND S HIGH VOLTAGE ELECTRICITY TRANSMISSION NETWORK THE NATIONAL GRID. Contents 01 Introduction 02 System Operator 24/7

More information

The New Zealand Power System in Balance

The New Zealand Power System in Balance The New Zealand Power System in Balance OTAGO Physics Department Seminar 10 August 2009 Kieran Devine System Operations Transpower New Zealand Limited Overview New Zealand and its Power System Balancing

More information

starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard

starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard FAR_01994 Contents Welcome... 5 How to use your Farmlands Fuel Starcard... 6 Using your PIN number...

More information

2018 LIFESTYLE RANGE

2018 LIFESTYLE RANGE 2018 LIFESTYLE RANGE 20B/25B BIG PERFORMANCE IN A SMALL PACKAGE With its proven three cylinder, high torque diesel engine and easy to operate two-range hydrostatic transmission, these purpose built compact

More information

PLUG VALVE we PIPE ( ) Twice the tensile strength of cast iron Greater yield strength than steel

PLUG VALVE we PIPE ( )   Twice the tensile strength of cast iron Greater yield strength than steel PLUG VALVE ECO-Centric Twice the tensile strength of cast iron Greater yield strength than steel W4.10 Hydrotite Eco-Centric Plug Valve December 2012 0800 we PIPE (93 7473) www.hynds.co.nz Features Ductile

More information

Relative Power Factor Correction costs

Relative Power Factor Correction costs SSG REF: S026 Friday 19 th October 2007 TO: John Gleadow Senior Adviser Transmission Electricity Commission FROM: David Hume Ranil de Silva System Studies Group NZ Ltd Relative Power Factor Correction

More information

ELECTRICITY PRICING POLICY

ELECTRICITY PRICING POLICY ELECTRICITY PRICING POLICY Effective 1 April 2016 Powerco Limited Schedule Ten: Schedule Eleven: Schedule Twelve: Electricity Pricing Schedule Loss Factors Billing and Settlement Process Effective 1 April

More information

Powerco Limited Pricing Guide 2015 ANNUAL REPORT 2015

Powerco Limited Pricing Guide 2015 ANNUAL REPORT 2015 ANNUAL REPORT 2015 PRICING GUIDE 2015 1 CONTENTS Introduction Page 03 Who we are Page 04 The Electricity Industry Page 05 Our Pricing Policy Page 08 How Powerco Performs Page 10 Pricing Methodology Page

More information

EFFECT OF SOLAR PV ON VOLTAGE MANAGEMENT IN NEW ZEALAND

EFFECT OF SOLAR PV ON VOLTAGE MANAGEMENT IN NEW ZEALAND EFFECT OF SOLAR PV ON VOLTAGE MANAGEMENT IN NEW ZEALAND DECEMBER 2017 TECHNICAL REPORT Table of Contents Table of Contents EXECUTIVE SUMMARY... VIII 1 INTRODUCTION...1 1.1 Programme Overview...1 1.2 The

More information

Electricity Pricing Policy

Electricity Pricing Policy Electricity Pricing Policy 2019 Powerco Limited Electricity Pricing Policy Schedule Ten: Schedule Eleven: Schedule Twelve: Electricity Pricing Schedule Loss Factors Billing and Settlement Process Effective:

More information

Areas marked grey are days floral studio is closed Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Mem City Florist

Areas marked grey are days floral studio is closed Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Mem City Florist Areas marked grey are days floral studio is closed Opening hours indicated Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Wed Thur Fri Sat Sun Mon Tues Mem City Florist 19th 20th 21st 22nd 23rd 24th

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

HOW SAFE ARE OUR ROADS? Tracking the safety performance of New Zealand s state highway network

HOW SAFE ARE OUR ROADS? Tracking the safety performance of New Zealand s state highway network taranaki, manawatuwhanganui and wellington Regional results 0 What is KiwiRAP? KiwiRAP analyses the road safety ratings of New Zealand s (80+km/h) ral state highway network. KiwiRAP is part of an international

More information

Air Temperature. Absolute Max and Min. Differ ence From Normal. Max Date Min Date

Air Temperature. Absolute Max and Min. Differ ence From Normal. Max Date Min Date s bsolute and Cape Reinga WS 214 19.9 15.4 17.7 +0.5 23.1 2 7.2 12 41 12-68 22 27.. Kaitaia ero EWS 80 21.4 13.7 17.6 +0.7 24.6 1 7.1 12 77 13-42 16 27.. Kaitaia EWS 85 21.5 14.0 17.8 +0.9 24.6 2 7.2 12

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

New 115 kv Disconnect Switches at Bloomsburg MTS

New 115 kv Disconnect Switches at Bloomsburg MTS 115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115

More information

Wind Generators Evolving Technology

Wind Generators Evolving Technology Wind Generators Evolving Technology Transmission Advisory Group Ray Brown Transmission Manager - Meridian Energy April 2008 Overview of Presentation 3 Different Wind Farms 3 Different Technologies Te Apiti

More information

Electricity Pricing Policy

Electricity Pricing Policy Electricity Pricing Policy 2018 Powerco Limited Schedule Ten: Schedule Eleven: Schedule Twelve: Electricity Pricing Schedule Loss Factors Billing and Settlement Process Effective: 1 April 2018 Version:

More information

Connecting your business diesel generation

Connecting your business diesel generation Connecting your business diesel generation March 2018 For connections more than 10kW 2 Contents Introduction to large distributed generation systems 3 Congestion management and safety 6 Application form

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

EC Forum on Model Approaches to Distribution Pricing. June 2009

EC Forum on Model Approaches to Distribution Pricing. June 2009 EC Forum on Model Approaches to Distribution Pricing June 2009 Session Explain Aurora UoS Pricing and fit with the Retail Model Approach Discuss how we transitioned a Demand tariff structure to Aurora

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard FAR_04982

starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard FAR_04982 starcard Farmlands Fuel Starcard Handbook A guide to where you can use your Farmlands Fuel Starcard FAR_04982 Contents Welcome... 3 How to use your Farmlands Fuel Starcard... 4 Using your PIN number...

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission

More information

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION El Paso Electric Company System Operations Department System Planning Section August 2006 I. INTRODUCTION The

More information

Powerco CPP Portfolio Overview Document

Powerco CPP Portfolio Overview Document Putaruru-Tirau Cable Powerco CPP Portfolio Overview Document Portfolio Name Expenditure Class Expenditure Category Putaruru-Tirau Cable Capex Growth & Security As at Date 12 June 2017 Expenditure Forecast

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

Supplement 8 Energy Lifelines Assets

Supplement 8 Energy Lifelines Assets West Coast Lifelines 徔 ulnerability and Interdependency Assessment Energy Lifelines Assets West Coast Civil Defence Emergency Management Group August 2017 IMPORTANT NOTES Disclaimer The information collected

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Rail safety statistics Six monthly statistics for the period ended 30 June August 2015

Rail safety statistics Six monthly statistics for the period ended 30 June August 2015 Rail safety statistics Six monthly statistics for the period ended 30 June 2015 August 2015 Disclaimer All reasonable endeavours are made to ensure the accuracy of the information in this report. However,

More information

DETOUR GOLD CORPORATION SYSTEM IMPACT ASSESSMENT FOR DETOUR LAKE PROJECT

DETOUR GOLD CORPORATION SYSTEM IMPACT ASSESSMENT FOR DETOUR LAKE PROJECT DETOUR GOLD CORPORATION SYSTEM IMPACT ASSESSMENT FOR DETOUR LAKE PROJECT Report No.: RP-160388-02-141-0001 CAA ID No. 2010-380 Rev. 01 Prepared by: AMEC Americas Limited Energy and Mining Division Power

More information

Seal on disc we PIPE ( ) Double Flanged Seal On Disc AS 4795:2006 Compliant

Seal on disc we PIPE ( )  Double Flanged Seal On Disc AS 4795:2006 Compliant Seal on disc BUTtEFLY VALVE 2000 SEIES Double Flanged Seal n Disc AS 4795:2006 Compliant W4.9 Hydrotite Seal n Disc Butterfly Valve December 2012 0800 we IE (93 7473) www.hynds.co.nz The 2000 series has

More information

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer (a) Purpose - This report

More information

WHAKAMARU POWER STATION REHABILITATION PROJECT. Author: Glen Twining, PMP, RMU Program Manager - Whakamaru, Mercury NZ Ltd, New Zealand.

WHAKAMARU POWER STATION REHABILITATION PROJECT. Author: Glen Twining, PMP, RMU Program Manager - Whakamaru, Mercury NZ Ltd, New Zealand. WHAKAMARU POWER STATION REHABILITATION PROJECT Author: Glen Twining, PMP, RMU Program Manager - Whakamaru, Mercury NZ Ltd, New Zealand. ABSTRACT Whakamaru Power Station in the North Island of New Zealand

More information

Project Manager: Neil Beckett. Prepared by: Bernadette Bañez. Reviewed by: Neil Beckett. Approved for issue by: David Darwin

Project Manager: Neil Beckett. Prepared by: Bernadette Bañez. Reviewed by: Neil Beckett. Approved for issue by: David Darwin Annual Weigh-In-Motion (WiM) Report 2010 This report has been prepared for the benefit of the NZ Transport Agency (NZTA). No liability is accepted by this company or any employee or sub-consultant of this

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY Short Circuit Analysis System Operations Department System Planning Section March 2001 I. Introduction XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

More information

Rail safety statistics

Rail safety statistics Rail safety statistics QUARTERLY STATISTICS FOR THE PERIOD ENDED 31 MARCH 2013 Prepared by Financial, Economic and Statistical Analysis, Ministry of Transport Rail safety statistics April 2013 This report

More information

Rail safety statistics

Rail safety statistics Rail safety statistics STATISTICS FOR THE SIX MONTHS PERIOD ENDED 31 DECEMBER 2013 Prepared by Financial, Economic and Statistical Analysis, Ministry of Transport Rail safety statistics January 2014 This

More information

OTAHUHU-MANGERE-ROSKILL- HEPBURN ROAD 110 KV CIRCUITS

OTAHUHU-MANGERE-ROSKILL- HEPBURN ROAD 110 KV CIRCUITS NORTH AUCKLAND AND NORTHLAND GRID UPGRADE PROJECT ATTACHMENT J OTAHUHU-MANGERE-ROSKILL- HEPBURN ROAD 110 KV CIRCUITS UPGRADE WITH HIGH TEMPERATURE LOW SAG CONDUCTOR September 2007 Contents 1 INTRODUCTION

More information

Interconnection Feasibility Study Report GIP-084-FEAS-R2

Interconnection Feasibility Study Report GIP-084-FEAS-R2 Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power

More information

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Breaker Technology Operational Advantages Development Schedule Dave Richardson, Ph.D.,P.E. Powell Power Electronic

More information

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655) - (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility

More information

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation

Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction

More information

Feasibility Study Report

Feasibility Study Report Report For: Orion Renewable Resources LLC ( Customer ) Queue #: Service Location: Rockingham County, NC Total Output Requested By Customer: 100 MW Commercial Operation Date Requested By Customer: 11/1/2019

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Electricity Network pricing schedule. Module 15 Effective April 1, 2011 for Electricity line charges. Version

Electricity Network pricing schedule. Module 15 Effective April 1, 2011 for Electricity line charges. Version Electricity Network pricing schedule Module 15 Effective April 1, 2011 for Electricity line charges Version 2011.1 Contents Section 1: Pricing Schedules...3 1.1 Wellington electricity Network line charges...3

More information

Feasibility Study Report

Feasibility Study Report Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility

More information

TRUCKS YOU CAN RELY ON GIGA SERIES HEAVY TRUCKS TAKING YOU ALL THE WAY

TRUCKS YOU CAN RELY ON GIGA SERIES HEAVY TRUCKS TAKING YOU ALL THE WAY TRUCKS YOU CAN RELY ON GIGA SERIES HEAVY TRUCKS TAKING YOU ALL THE WAY THE KEY TO YOUR BUSINESS As New Zealand s favourite truck our customers expect Isuzu to offer industry leading products that meet

More information

Feasibility Study Report

Feasibility Study Report Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014

More information

1 Ethnic group (detailed total responses), 2001, 2006, 2013 Censuses 2 Ethnic group (detailed total responses) by age group, 2013 Census 3 Ethnic

1 Ethnic group (detailed total responses), 2001, 2006, 2013 Censuses 2 Ethnic group (detailed total responses) by age group, 2013 Census 3 Ethnic QuickStats about culture and identity definitions and forms has more about subject populations List of tables 1 Ethnic group (detailed total responses), 2001, 2006, es 2 Ethnic group (detailed total responses)

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

Black Diamond Solar PV Panels

Black Diamond Solar PV Panels Black Diamond Solar PV Panels Premium Monocrystalline Photovoltaic Panels 43 MITSUBISHI ELECTRIC 1974 2017 YEARS SOLAR INNOVATION World Leaders in Photovoltaic Technology, backed by ongoing local support.

More information

ABB New Zealand Capability Guide

ABB New Zealand Capability Guide ABB New Zealand Capability Guide Contents 02 ABB nationwide 03 ABB s vision 04 Message from Managing Director 06 Power Products division 07 High Voltage Products 09 Medium Voltage Products 11 Transformers

More information

MILLIGAN SOLAR PROJECT

MILLIGAN SOLAR PROJECT February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission

More information

Interconnection Feasibility Study Report GIP-157-FEAS-R2

Interconnection Feasibility Study Report GIP-157-FEAS-R2 Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia

More information

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012 POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORT WEST TASMANIA ON 6 APRIL 2012 PREPARED BY: Systems Capability DATE: 28 September 2012 FINAL IN NORT WEST TASMANIA ON 6 APRIL 2012

More information

HOME SHOW ALL PRICES INCLUDE GST & ARE VALID UNTIL 28TH SEPTEMBER TSM / HOME SHOW ACCOUNT

HOME SHOW ALL PRICES INCLUDE GST & ARE VALID UNTIL 28TH SEPTEMBER TSM / HOME SHOW ACCOUNT 2018 HOME SHOW ALL PRICES INCLUDE GST & ARE VALID UNTIL 28TH SEPTEMBER TSM / HOME SHOW ACCOUNT 457381 WE VE GOT YOU COVERED FROM WHANGAREI TO INVERCARGILL The Ideal Electrical team understand what you

More information

Functional Specification Revision History

Functional Specification Revision History Functional Specification Revision History Revision Description of Revision Author Date B0 For comments Yale Zhou January 26, 2016 B1 Updated as per comments Yale Zhou February 1, 2016 Final issuance Yale

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

TRUCKS YOU CAN RELY ON N SERIES LIGHT TRUCKS THE STRAIGHT FORWARD CHOICE

TRUCKS YOU CAN RELY ON N SERIES LIGHT TRUCKS THE STRAIGHT FORWARD CHOICE TRUCKS YOU CAN RELY ON N SERIES LIGHT TRUCKS THE STRAIGHT FORWARD CHOICE THE KEY TO YOUR BUSINESS As New Zealand s favourite truck our customers expect Isuzu to offer industry leading products that meet

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

System Impact Study Report

System Impact Study Report Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS

More information

Approved profiles. Version May Approved profiles v2.29: _25 1 of 15

Approved profiles. Version May Approved profiles v2.29: _25 1 of 15 Approved profiles Version 2.29 30 May 2018 Approved profiles v2.29: 646892_25 1 of 15 Version control Version Date amended Comments 1.0 23 February 2005 Initial guide sheet. 1.1 8 February 2006 New profiles

More information

Genesis Energy s customer focused strategy increases customer acquisitions across New Zealand

Genesis Energy s customer focused strategy increases customer acquisitions across New Zealand Genesis Energy s customer focused strategy increases customer acquisitions across New Zealand INTRODUCTION This disclosure includes market and operational information for Genesis Power Limited, trading

More information

Interconnection Feasibility Study Report GIP-046-FEAS-R2

Interconnection Feasibility Study Report GIP-046-FEAS-R2 Interconnection Feasibility Study Report GIP-046-FEAS-R2 Generator Interconnection Request #46 32 MW Wind Generating Facility Colchester (L-6513), NS August 17, 2007 Control Centre Operations Nova Scotia

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 Short Circuit

More information

Climate change drivers for a single and smart EU grid

Climate change drivers for a single and smart EU grid Climate change drivers for a single and smart EU grid Smart and Secure Transmission Grids to Realise US and EU Renewable Energy Potentials Keith Bell University of Strathclyde, Scotland Expected growth

More information

Impact of Distributed Energy Resources on Transmission System Reliability

Impact of Distributed Energy Resources on Transmission System Reliability S E P T E M B E R 1 3, 2 0 1 8 W E B I N A R Impact of Distributed Energy Resources on Transmission System Reliability National Council on Electricity Policy (NCEP) Alan McBride D I R E C T O R, T R A

More information

The Energy Queensland Group Notice of no non-network options

The Energy Queensland Group Notice of no non-network options The Energy Queensland Group Notice of no non-network options 24 September 2018 MCE Mount Crosby East Establish new substation to replace Mount Crosby Substation (SSMTC) Page 1 of 1 DISCLAIMER While care

More information

Category 3 and 4 overdimension vehicles and loads

Category 3 and 4 overdimension vehicles and loads Category 3 and 4 overdimension vehicles and loads Version 1.0 Land Transport Safety Authority PO Box 2840 Wellington New Zealand Introduction The Land Transport Rule: Vehicle Dimensions and Mass 2002,

More information

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect

More information

briefing notes crash analysis

briefing notes crash analysis August 11 briefing notes crash analysis Bay of Plenty Region to briefing notes crash analysis a safe system approach Bay of Plenty Region This report details aspects of the Bay of Plenty road safety Region

More information

Mikael Dahlgren, ABB Corporate Research, 02 December 2011 ABB Technology providers perspective Energidagen Chalmers Energyinitiative

Mikael Dahlgren, ABB Corporate Research, 02 December 2011 ABB Technology providers perspective Energidagen Chalmers Energyinitiative Mikael Dahlgren, ABB Corporate Research, 02 December 2011 ABB Technology providers perspective Energidagen Chalmers Energyinitiative ABB HVDC Slide 1 ABB Five global divisions Power Products Power Systems

More information

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements

More information

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Study Performed by El Paso Electric Company System Planning Section - 1 I.

More information