SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)

Size: px
Start display at page:

Download "SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)"

Transcription

1 Doc No: SP-ELE-006 Rev: A Page 1 of 11 SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)

2 Doc No: SP-ELE-006 Rev: A Page 2 of 11 List of Contents Pages 1.0 Scope Technical Specification Mode of Operation: Design Criteria Battery Charger SMF (VRLA) Battery D.C. Distribution Board Component Specification 9

3 Doc No: SP-ELE-006 Rev: A Page 3 of Scope 1.1 This specification intended to cover Design, Engineering, Manufacture, Assembly, Painting, Inspection, Testing at manufacturer s works, Delivery to site inclusive of packing & transportation, Testing and Commissioning assistance of Battery, Battery Charger & DCDB complete with all accessories. 1 set of 110V D.C. system (Battery, Battery Charger & DCDB) in accordance with this specification, standards stated herein and Appendices enclosed herewith, shall comprise of the following: a) SMF (VRLA) Battery complete with racks & accessories. b) One No. Float charger. c) One No. Float cum Boost charger. d) DCDB 1.2 This specification shall be read in conjunction with Tender for Major Electrical Equipment. 1.3 All equipment supplied shall be new and best of their respective kinds and shall be of the class most suitable for the purpose for which they are intended. 1.4 Modification / changes in components, if any suggested during scrutiny / approval of drawings and execution of work shall be carried out by successful vendor at no extra cost. 2.0 Technical Specification 2.1. Mode of Operation: Under the normal conditions, i.e. when A.C. supply is available at Battery Charger input terminals, the float charger shall supply the continuous D.C. load plus the float/trickle charging current of the Battery. In addition some of the impulse loads of duration less than a minute shall also be fed by charger. Therefore, charger shall be designed to meet such momentary overload conditions In the event of failure of A.C. supply, the emergency D.C. load shall be supplied by the Battery for the duration of 2 Hrs On restoration of A.C. supply, the Float charger shall supply the load current and Float cum boost charger shall charge the battery. During such conditions battery remains connected to load through intermediately tapped cell. Each diode shall be rated to carry the maximum discharge current of the battery An interlock shall be provided such that when boost charger is charging the battery, the float charger gets disconnected automatically from battery, through D.C. contactor. D. C. contactor shall be rated to carry safely the various currents of the Batteries. Power supply for D.C. contactor coil shall be derived from Battery terminals Design Criteria The battery shall be used to supply protection & control circuits of electrical Breakers, annunciators, D.C. critical lighting etc. independently of outside power sources. The Battery Backup power shall be available for 120 minutes in the event of complete power failure The battery sizing shall account for suitable temperature correction factors, ageing factors of 1.25, depth of discharge of 80% Load details for determining load cycle

4 Doc No: SP-ELE-006 Rev: A Page 4 of 11 Load cycle shall be decided based on the following load details: A) First minute : i) 33kV breaker trip coil - 3 nos ii) LV incomer breaker trip coil - 3 nos B) Last minute : i) 33kV breaker closing coil - 3 nos ii) LV incomer breaker closing coil - 3 nos C) Continuous load : i) Emergency lighting load 1500watts ii) All indicating lamp, annunciator window, multifunction meter shall be continuous and vendor to workout in detail to size the battery. Vendor shall calculate the AH capacity of battery based on the above load details and furnish sizing calculations and backup documents/graphs, along with the offer The Float Charger shall be used to supply normal D.C. loads and float charging current of charged Battery. The Float cum Boost charger shall be designed to supply boost charging current requirement of the associated battery as well as to supply normal D.C.Load. After full discharge of battery bank, the Float Cum boost charger shall be capable of charging the battery to its full capacity in 8 hours duration while supplying normal D.C.Load. Output voltage shall not vary more than ±10%; Vendor shall specify output voltage regulator or dropping diode etc. used to achieve the above requirement. The end cell voltage after discharge shall be limited to 1.75 volts/cell. The rating of battery charger shall be suitable for the battery size selected. Vendor shall size the Charger, suitable to chosen Battery AH capacity and furnish charger sizing calculations along with the offer Complete Battery charger system including rectifier, battery, static switches etc. shall have 15% spare capacity for future load growth DC distribution board shall be provided to feed various loads. The provision of incoming and outgoing feeders on DC distribution boards shall be as specified in the enclosed SLD in Attachment The maximum temperature rise in any part of the equipment as well as that of any component and their terminals while delivering rated current shall not exceed the permissible limits stipulated in relevant standards The Battery, Battery Charger & DCDB shall be located in substation having clean but hot, humid and tropical atmosphere. All equipment shall be designed to operate satisfactorily under the ambient and environmental conditions specified. Batteries shall not be located in separate room Maximum noise level of charger shall be less than 80 db Battery Charger Constructional features: a) The charging equipment shall be housed in a free standing, floor mounted compartmentalized panels having separate compartments for float and float cum boost charging equipment, battery connection to DC bus, DC distribution equipment, including incoming feeders and outgoing feeders in different compartments. Panels shall have provision for bottom entry of cables with removable cable gland plate. (i.e. separate compartmentalised panels for each float charger, float cum boost charger and DC distribution).

5 Doc No: SP-ELE-006 Rev: A Page 5 of 11 b) The panel shall be of CRCA sheet steel construction and provided with concealed hinges. Adequate ventilating grills or louvers with fine brass wire mesh shall be provided. Thickness of sheet steel shall be at least 2.0 mm. Degree of protection provided by the enclosure to the internals of charger shall be IP-42. c) The instruments, switches and indicating lamps shall be flush mounted on the front panel. d) Suitable neoprene rubber gaskets shall be provided all around doors and cover plates, between two shipping sections, two charger sections, two panel sections, for making charger construction dust and vermin proof. e) All PCBs used in the charger shall be made of glass epoxy material. Electronic cards shall be plug in type and shall be mounted on standard racks. Rack shall have PCB guides which shall allow the insertion of PCBs smoothly without requiring force. Racks shall be mounted on hinged pivot to enable the rack to be turned for access to back side terminals. PCBs shall include status indicating LED lights and test connections in the front to facilitate fault diagnosis. PCBs shall be identified with proper permanent labels as per approved drawings Operation a) The Battery charger shall be with static Silicon Controlled Rectifiers (SCRs), It shall be complete with filter circuits to limit the ripple within ±1% (RMS) in the DC output. The rectifier transformers shall be of dry type, AN cooled, vacuum impregnated double wound with adequate number of primary taps. Transformer shall be Class B insulation having a continuous rating at least 125 % of the rating of the charger. Reactance of transformer shall be suitable to take care of regulation and surges. b) Battery charger shall be designed for a maximum voltage ripple of ±1 % (rms) when connected to a battery with an ampere-hour capacity equal to or greater than four times the ampere capacity of the charger. c) The rectifier-charger shall be of the current-limiting type set not higher than 125 % for the solid state design. d) Charger shall be current limited to both the float and equalize positions in order to protect the equipment from a short circuit on the load side. e) The rectifier-charger shall have a minimum power factor (PF) of 0.8 under the following operating conditions: -15 % of the rated input voltage -5 % of the rated frequency Full rectifier output f) A walk-in circuit shall be provided to limit in-rush current to 110 % of rectifier/charger full-load current. g) The RMS sum of all harmonics in the input waveform shall not exceed 10 % of the RMS value of the fundamental harmonic with the system operating at rated voltage and current. h) The charger output shall be filtered to eliminate any harmonics superimposed on the rectifier output voltage Voltage Regulation a) The float charger shall have both auto and manual voltage regulation arrangements with provision of selector switch. Output DC voltage shall not vary beyond ±1% of the set value when controlled through AVR with load varying from no load to full load simultaneously with specified fluctuations in input voltage and frequency.

6 Doc No: SP-ELE-006 Rev: A Page 6 of 11 b) Charger output voltage shall vary no more than ±10 as a result of a transient 4,000-volt peak lasting 100 microseconds with 40-ohm source impedance, the batteries, and the full load connected Controls a) The Float cum boost charger shall be complete with manually controlled motorized, variac and three phase rectifier bank. The voltage regulation shall be uniform and step less throughout the voltage variation range. For achieving this, voltage Raise/Lower push buttons shall be provided on front of float cum boost charger section. An interlock shall be provided in the float cum boost charger so that float cum boost charger can be made ON only when the autotransformer is in minimum position. b) The float charger controller shall have built in load limiting feature, which will limit the load on charger in the event of overload and reduce the output voltage in order to transfer the load to the battery. The current setting of load limiting device shall be uniformly adjustable between 100% and 150% of full load. c) Charger shall be provided with all required float and equalizer controls. Chargers shall be provided with an automatic charging control circuit to switch the rectifier output automatically from float charging to equalize charging if the charger is in current limit for more than 30 seconds. Equalize charging time shall be controlled by a timer that has an adjustable setting from 8 to 12 hours Protection, Indicators & Alarms a) The rectifier equipment shall be complete with heat sink and have its own protective devices. In addition, surge protection devices and fast acting HRC fuses suitable for rectifier protection shall be provided in each arm of rectifier connections. b) Battery charger shall be furnished with the manufacturer's standard indicating and Audio & Visual alarm devices, which shall include, but not be limited to, the following: AC circuit breaker and AC power-on light AC power-failure relay for remote alarm AC under voltage DC disconnect switch, without over current protection DC ground-detection lights with relay for remote alarm contacts DC under voltage & over voltage. DC positive to earth and D.C. negative to earth faults. Low DC-voltage relay for remote alarm DC voltmeter and ammeter with 2-percent accuracy Charger failure alarm (loss of DC current) Float & Float cum Boost charger rectifier fuse failure. Float/ Float cum Boost charger D.C. side output fuse failure. Float charger overload. Float cum Boost charger overload. Battery Fuse Failure Float and equalize potentiometer and selector switch to override automatic charge control

7 Doc No: SP-ELE-006 Rev: A Page 7 of 11 Equalize pilot light Battery-disconnected relay for remote alarm Chargers-out-of-balance relay for remote alarm (for load sharing chargers) Unit of common alarm contact for remote indication c) Alarms shall have local indication on the battery charger. d) Indicator lamps on the charger panel shall be operated at no more than 75 of the rated voltage of the lamp for extended life. e) If cooling fans are approved, an alarm shall be provided to signal a loss of ventilation. A sail switch upstream of the cooling fans shall activate the alarm. The sail switch shall be mounted inside the charger enclosure. f) Alarm contacts shall be rated for 5 amps at 110 volts DC for connection to a remote annunciator. Isolated alarm contacts shall be provided. The contacts shall open to actuate the alarms SMF (VRLA) Battery General Features a) The chargeable batteries shall be Lead acid maintenance free (SMF-VRLA). type of nominal voltage specified in SLD in Attachment-3. The end cell voltage after discharge shall be limited to 1.75 volts/cell. Batteries shall not require any water topping up and shall emit no corrosive fumes or gases under normal operating conditions. b) The batteries shall be supplied along with the necessary mounting racks or sheet steel enclosure complete with the provision for clamping the cables. Battery racks shall be of steel frame with epoxy painted/ PVC lined. c) Vendor shall indicate the ventilation requirements if any, for the battery Constructional features a) Electrolyte b) Plates The Electrolyte shall be of battery grade sulphuric acid. The Positive & Negative plates shall be constructed of heavy duty lead alloy grids type.the plates shall be corrosion resistant & shall have low self discharge properties. The plates shall be designed for maximum durability during all service, conditions including high rate of discharge and rapid fluctuation of load. c) Containers & Covers Each cell shall be assembled in high grade, flame retardant polymer or moulded hard rubber container. The container shall be leak proof, non-absorbent, shock absorbing not liable to deformation within the range of working temperature and not affected by the acid. Electrolyte high-level and low-level lines shall be marked on at least two of the four sides of a cell and visible from the front of the completed assembly. A permanent airtight seal shall be provided between the cover & container to stop electrolyte & air leakage. The container shall be designed to withstand the pressure caused by charging & discharging characteristics of the battery.

8 d) Cell lids VISAKH MARKETING INSTALLATION RESITEMENT Doc No: SP-ELE-006 Rev: A Page 8 of 11 Cells lids shall be of glass, plastic or ebonite complete with either suitable rubber gasket for closed type or bituminous sealing compound for sealed type of containers. e) Safety Vents Flame arresting vent plug housing the safety valve shall be provided. The vent plugs shall be explosion proof, self resealing, resisting acid overflow and pressure regulating types. The valve shall be automatically sealed to prevent diffusion of air. f) Separators Separator between plates shall permit free flow of electrolyte and shall maintain the electrical insulation between the plates. Separators shall be of wood or high density absorbent Glass MAT non woven with excellent porosity. g) Connectors Lead coated copper connectors shall be furnished to use as inter cell, interior, inter tier and inter row connectors. The lead plating shall be adequate to ensure proper protection against corrosion during the entire life of the battery. Nuts, bolts and washers shall be of lead coated copper. h) Terminal Posts The cell terminal posts shall be provided with connector bolts and nuts, effectively coated with lead to prevent corrosion. Positive and negative terminal posts shall be clearly and indelibly marked for easy identification. Lead plated plate, tubular tinned copper lugs, bolts, nuts, washers etc. shall be furnished for connection of outgoing purchaser s aluminium conductor cables. Intermediate posts for easy termination of purchaser s cable shall be provided. i) Cell Insulators The cells shall be supported on hard rubber/pvc pads, fixed on the rack with adequate clearance between the adjacent cells. j) All hardware necessary for complete assembly of system shall be provided. k) A disconnect switch shall be provided near battery bank for isolation of batteries D.C. Distribution Board Constructional Features a) D.C. Distribution Board shall be a separate panel, but shall form an integral part of a panel board, when placed by the side of the charger panels. b) Cubicle door shall have rolled edges with suitable neoprene gasket to make it dust proof. The door shall be provided with lock and key arrangement to prevent unauthorised opening of the door. c) Outgoing MCB/Fuse mounting plates shall be adequately braced to avoid wobbling during pulling or insertion of fuses. d) DCDB shall comprise of double pole MCBs as specified in SLD attached in Attachment Bus bars a) Busbars in the battery charger and DCDB shall be Aluminium liberally sized for the specified current rating (both short circuit and continuous currents.) b) The main horizontal busbars of distribution boards shall be located in a separate chamber extending over entire length. Bus bar chamber shall have separately screwed covers. All bus bars, links, etc. shall be provided with heat-shrinkable insulating sleeves to prevent accidental contacts.

9 Doc No: SP-ELE-006 Rev: A Page 9 of 11 c) Power shall be distributed to each circuit in each section by flexible copper conductor cables. d) Buses shall be spaced with adequate clearances between positive and negative and between positive/negative and ground. Minimum clearance shall not be less than 25 mm. e) Bus supports shall be of arc resistant, non tracking low moisture absorption type moulded insulators of high impact strength and high Creepage surface. Material of bus supports shall be cast epoxy resin/dmc/smc. Supports for each bus shall be independent from support for other phase/pole busbar. f) All bus works shall be braced to withstand stresses due to short circuit current without damage. g) Colour code shall be used to identify the busbars as per relevant standards. Suitable sleeving shall be provided over busbars for insulating the same as secondary insulation Low Voltage Disconnect DC Power System shall be supplied with a low voltage disconnect which will automatically disconnect the load from the battery upon low voltage to prevent the battery from becoming completely discharged on charger malfunction or failure. The low voltage disconnect shall have an adjustable trip point and shall be capable of breaking full DC load current Component Specification Switches/ MCCBs/MCBs Fuses a) Switches or 4 pole MCCBs as per SLD shall be provided for incomer. MCCBs/A.C. Switches shall be four pole, air break and heavy duty type, capable of safely breaking the full load current of associated feeder. A.C. incoming MCCB/Switch shall have a quick-make, quick-break mechanism operated by a suitable external handle complete with position indicator. b) MCBs for outgoing feeders shall be double pole type, and shall be suitably rated to make and break and carry the rated D.C. current. a) Fuse shall be HRC, link type, with a maximum rupturing capacity suited for rated voltage. Rewirable fuses shall not be acceptable. Fuses provided for protection of rectifier shall be of the type suitable for the intended duty. b) Fuses shall be furnished complete with fuse bases and carriers of such design as to permit easy replacement of fuse elements. Visible indication shall be provided on blowing of the fuse. c) The incomer fuse rating shall be so chosen as to provide discrimination with feeder fuses Contactors CTs and PTs Relays Contactors shall be air break type with 2 NO + 2NC auxiliary contacts. Utilisation category shall be AC-1 or DC-1. Continuous current rating of contactors shall be at least 15% higher than full load current of connected equipment. CTs and PTs shall be of epoxy resin cast type. Accuracy class of the metering CTs and PTs shall be 1.0. Relays shall be microprocessor/static type. Further, relays shall be draw out plug in type and shall be provided with hand reset type flag indicator. Thermal overload relays shall be ambient temperature compensated and shall be hand reset type.

10 2.6.6 Meters VISAKH MARKETING INSTALLATION RESITEMENT Doc No: SP-ELE-006 Rev: A Page 10 of 11 a) Meters shall be square type, flush mounting. b) Each meter shall be provided with zero adjuster on the front. c) Accuracy of the meters shall be ± 3%. d) Minimum size of the meters shall be 96 mm x 96 mm and meters shall be of taut band type. e) Meters shall be operated from outputs of CTs/PTs/DC shunts as required Following control switches/ pushbuttons to be provided as a minimum. a) ON /OFF control switch for AC supply to charger. b) Auto / Manual selector switch to select mode of operation. c) Potential meters for voltage & current adjustment in float mode. d) Potential meters for voltage & current adjustment in Float cum Boost mode Push Buttons and Indicating Lamps a) Push Buttons and Indicating Lamps shall be panel mounting type. b) Lamps shall be clustered LED type with low watt consumption. c) Push Button actuator shall be shrouded with dust tight rubber grommet cover. Associated springs and contacts shall be of robust construction. Push Button shall be provided with integral escutcheon plates with 2NO + 2NC contacts rated to make, break and carry 5A DC at 110V, 30V or 220V DC Space Heaters & Panel a) Each vertical section of panel shall be provided with thermostat controlled space heaters rated 240 volts, single phase, 50 Hz. The heaters shall have individual ON-OFF MCB. b) Wiring of space heaters in each board shall be grouped and brought out to easily accessible terminals. c) Cubicle illumination lamp along with MCB operating on 240V, 1 phase supply shall be provided. Lamp operation shall be controlled through door limit switch. d) 240V supply shall be suitably tapped by vendor from incoming supply Wiring a) The wiring shall be complete in all respects so as to ensure proper functioning of control, protection, interlocking and measurement schemes. b) Control wiring shall be done with flexible, heat resistant, switchboard wires; 650/1100V grade, multi-stranded copper conductor. Each wire shall be identified at both ends using engraved ferrules designation in accordance with the approved wiring diagram. Interlocking type plastic ferrules shall be used for identification. Minimum size of the wires used for plug cord for electronic cards shall be 0.5mm 2 copper. Wires shall not be spliced or tapped between terminal points. Wherever wires cross sheet steel barriers rubber grommets shall be provided around holes in sheet steel barrier. All internal wires shall be terminated with tinned copper crimping type lugs Cable Termination a) Distribution boards shall be designed to facilitate cable entry from bottom. Removable undrilled plates shall be furnished for this purpose. Sufficient space shall be provided to avoid sharp bending and for ease of connection, a minimum space of 300mm from the gland plate to the nearest terminal shall be provided.

11 Doc No: SP-ELE-006 Rev: A Page 11 of 11 b) Multiway, clip on type terminal blocks complete with screws, nuts, washers, and marking strips shall be furnished for terminating the internal wiring and outgoing control cables. Stud type terminals shall be provided for power cables. c) Each control terminal shall be capable of connecting 2 nos. 2.5 sq. mm copper wire at one end without any damage to the conductor or any looseness of connection Ground Bus a) Copper ground bus of size 25mm x 6mm shall be furnished along the entire length of each section of Battery Charger and DCDB. b) Each equipment of board shall be connected directly to the ground bus by two separate and distinct connections. Doors of charger shall be effectively earthed through flexible copper wires of adequate size. c) Grounding terminals on the ground bus shall be provided at two points of the Battery Charger. Connectors shall be provided at either ends for connection to Purchaser s ground conductor. d) DC Power shall be Ungrounded.

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

West Bengal State Electricity Distribution Co. Ltd.

West Bengal State Electricity Distribution Co. Ltd. West Bengal State Electricity Distribution Co. Ltd. TECHNICAL SPECIFICATIONS FOR D. C. DISTRIBUTION BOARD (FOR 33 KV SUB STATIONS) Page 1 of 14 1.0 SCOPE: This specification covers the design, manufacturing,

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (100A) & BOOST CHARGER (60A) FOR WITH REQUIREMENT FOR SCADA

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR GETCO/E/TS-50V BCHR(SCADA)

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011 Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

GENERAL SPECIFICATION ELECTRICAL

GENERAL SPECIFICATION ELECTRICAL GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID

TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID TENDER FOR FOR 2 X 1010 KVA, 1500 RPM, 415 V DG SETS FOR CONSTRUCTION OF NEW CDRI CAMPUS AT SITAPUR ROAD, LUCKNOW (U.P.) SUMMARY OF PRICE BID S.NO. HEAD DESCRIPTION AMOUNT (Rs.) 1 A DG SETS & ACCESSORIES

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT. (SPECIFICATION NO. MSEB/Dist/IV/2004.

TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT. (SPECIFICATION NO. MSEB/Dist/IV/2004. TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT (SPECIFICATION NO. MSEB/Dist/IV/2004.) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 18

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

Central Battery Systems Loadstar AC/DC Systems

Central Battery Systems Loadstar AC/DC Systems The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources of emergency power for escape

More information

INVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station

INVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station INVITATION TO TENDER MR 84/2016 SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station Fiji Electricity Authority seeks reputable Manufacturer/Supplier

More information

: Material Description Quantity UOM

: Material Description Quantity UOM Page : 1 / 2 OIL INDIA LIMITED (A Govt. Of India Enterprise) Tel :033 2230 1657, 1658 4, India Exchange Place, Fax :91 33 2230 2596 Kolkata-700001 E-mail :oilcalmn@cal2.vsnl.net.in ANNEXURE-I Item No./

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB Annexure-V (Under Two Part Bid System) Tender No: NFV/ PUR/ BEC 160546 K for VCB Technical specification for NIT SL NO 1 S.No. Description NFL requirement as per NIT Vendors Comment [Agreed / If not agreed,

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GETCO / E / TS- BCHR 3202 / R2 Oct 15 Seal & Sign

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

AME. Rectifier - Battery charger. Industrial applications: Key features:

AME. Rectifier - Battery charger. Industrial applications: Key features: Rectifier - Battery charger AME VRLA batteries, flooded battery or Ni/Cd with output voltage from 24, 48, 110, 220 Vdc up to 150A Industrial applications: Oil&Gas (Petrochemicals Offshore, Onshore, Pipelines);

More information

D.C. DISTRIBUTION BOARD

D.C. DISTRIBUTION BOARD PRAMBL: The TC is maintaining 50-volt battery backup system for the PLCC communication. The 50-volt D.C. supply from the Float cum Boost charger is brought to D.C. Distribution Board from where supply

More information

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller Number: 5344-1.1.311 Rev. 8 Portable Mine Power Centres Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller SCOPE This specification covers general material and design

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

24V 3A EN54 Ancillary Power Supply

24V 3A EN54 Ancillary Power Supply 24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

with Vacuum Circuit Breaker HAF

with Vacuum Circuit Breaker HAF M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO

KENYA POWER-MOMBASA BRANCH REPLACEMENT OF AIR-CONDITIONING AND ASSOCIATED WORKS BILLS OF QUANTITIES FOR ELECTRICAL INSTALLATIONS BILL NO BILL 1 MAINS POWER DISTRIBUTION 2-1 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test, commission and set to work the following:- 1.01 Free-standing purpose made front access sub main switchboard

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations 1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

SBC / 2140 / Stage Battery Charger User Manual

SBC / 2140 / Stage Battery Charger User Manual SBC - 2130 / 2140 / 2150 3 Stage Battery Charger User Manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions for correct

More information

0.3 This standard is generally based on the following standards:

0.3 This standard is generally based on the following standards: IPSS GENERAL TECHNICAL SPECIFICATION FOR INDOOR HIGH VOLTAGE SWITCHGEAR (FIRST REVISION) BASED ON IS 12729:2004, IEC60694:2002, IEC62271-1:2007, -100:2008, -200:2003 IPSS:1-04-030-15 Formerly: IPSS:1-04-030-97

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date: 10111. 4711M1 An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY Corrigendum 1

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Motor-drive mechanism, type BUL. Technical guide

Motor-drive mechanism, type BUL. Technical guide Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

Technical Specification of GECOL. Packaged Transformers

Technical Specification of GECOL. Packaged Transformers GES 26211 Technical Specification of GECOL Packaged Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company of Libya Contents 1 SCOPE AND SERVICE CONDITIONS... 6 1.1 SCOPE...

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance M E T A L - C L A D S W I T C H G E A R Safe and Reliable Flexible, Compact Design Easy Installation and Maintenance We build a better future! Hyundai HMS medium-voltage metal-clad switchgears and control-gears,

More information

INTERPLANT STANDARD - STEEL INDUSTRY GENERAL TECHNICAL SPECIFICATION FOR LV SWITCHGEAR. Based on IS 60947(Part 1) : 2004 & IS 8623 (Part 1): 1993

INTERPLANT STANDARD - STEEL INDUSTRY GENERAL TECHNICAL SPECIFICATION FOR LV SWITCHGEAR. Based on IS 60947(Part 1) : 2004 & IS 8623 (Part 1): 1993 INTERPLANT STANDARD - STEEL INDUSTRY GENERAL TECHNICAL SPECIFICATION FOR LV SWITCHGEAR IPSS:1-04-029-15 IPSS Based on IS 60947(Part 1) : 2004 & IS 8623 (Part 1): 1993 0. FOREWORD 0.1 This Inter Plant Standard

More information

31-SDMS-10 REV. 00 SPECIFICATIONS FOR

31-SDMS-10 REV. 00 SPECIFICATIONS FOR 31-SDMS-10 REV. 00 SPECIFICATIONS FOR AUXILIARY AC/DC PANELS FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without any notice TABLE OF

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A Technical Specification Of 12KV, 400A, 18.4 KA Floor Mounted totally enclosed Ring Main Unit consisting of 2 nos. Vacuum Interrupting Incoming Unit and one no. Series Trip Metering Switchgear with Vacuum

More information

FUM-24xxCBP Series 3 Stage Battery Charger User Manual

FUM-24xxCBP Series 3 Stage Battery Charger User Manual FUM-24xxCBP Series 3 Stage Battery Charger User Manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions for correct use

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY PURCHASE ENQUIRY Inquiry No : MDG/PUR/PKS/ENQ/Panels, Dated: Nov 3, 2014 Description Qty Specifications : Purchase Inquiry for Supply, installation and commissioning of Panels for PFP Expansion project.

More information

Switchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C)

Switchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C) 12-373 UL Recognized Component RETURN LEAD RECYCLE LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY FOR STANDBY APPLICATIONS Capacities from 100 to 600 Ampere-hours (8 hours to 1.75 VPC) 343 to

More information

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants World Class Power Solutions Rectifiers For Stationary Battery Systems in Nuclear Power Plants General 2 1.1 Application Electronically controlled rectifier assemblies are used in conjunction with suitable

More information

SCHEDULE OF QUANTITIES ITEM DESCRIPTION

SCHEDULE OF QUANTITIES ITEM DESCRIPTION SCHEDULE OF QUANTITIES ITEM DESCRIPTION A. SUBSTATION EQUIPMENT Suplly, installation, Testing and Commissiong of kv, 350 MVA ( 8.4 ka ), 630A, HT Panel Vacuum circuit breaker Switchboard, cubicle type,

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

RU BMS Power Supply and Battery Management System Owners Guide

RU BMS Power Supply and Battery Management System Owners Guide RU2-4012- BMS Power Supply and Battery Management System Owners Guide (These instructions are intended for use by a technician familiar with electronic products) RU2-4012- BMS is a continuous duty power

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

S H A D E S ELECTRICAL DB MANUFATURING

S H A D E S ELECTRICAL DB MANUFATURING CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service

More information

SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB. TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ Date:

SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB. TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ Date: SECTION-IV TECHNICAL SPECIFICATION OF MATERIALS FOR 33KV & 11KV VCB TENDER N O T I C E NO:- NESCO Utility / VCB/ 20/ 17-18/ 13099 Date: 14.12.16 Tech. Specification NIT No. NESCO Utility/ VCB/20/ 11.10.17

More information

Miniature Circuit Breaker

Miniature Circuit Breaker Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the

More information

AT30 SERIES BATTERY CHARGER

AT30 SERIES BATTERY CHARGER STANDARD FEATURES 5 YEAR WARRANTY 5 Year Product Warranty Universal main control board operates in any AT Series charger Alarm assembly with local LEDs and summary relay contact for AC Failure, DC Failure,

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

ype UP T Busplugs Low Voltage Switchboard Equipment

ype UP T Busplugs Low Voltage Switchboard Equipment Busplugs Type UP Low Voltage Switchboard Equipment Publication UP 2013 Since product improvement is a continuing policy, we reserve the right to change specifications without notice. Contents Descriptive

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

MEDIUM-VOLTAGE SWITCHGEAR

MEDIUM-VOLTAGE SWITCHGEAR REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.

More information

BASIC TROUBLESHOOTING START / STOP PUSHBUTTONS, PILOT LIGHTS, RELAYS, TIMER LIMIT SWITCHES, FLOW SWITCHES, THERMAL SWITCHES, AND OVERLOAD RELAYS.

BASIC TROUBLESHOOTING START / STOP PUSHBUTTONS, PILOT LIGHTS, RELAYS, TIMER LIMIT SWITCHES, FLOW SWITCHES, THERMAL SWITCHES, AND OVERLOAD RELAYS. BASIC TROUBLESHOOTING FOUR BASIC BUILDING BLOCKS OF A PLATING RECTIFIER: 1. ELECTRICAL CONTROLS 2. AC POWER CIRCUITS 3. DC POWER CIRCUITS 4. ELECTRONIC CONTROL 1. ELECTRICAL CONTROLS START / STOP PUSHBUTTONS,

More information