3.2. Confirmation of Current Status and Issues Relating to Operation and Maintenance Recent Status of Power Generation in Java-Bali Regions

Size: px
Start display at page:

Download "3.2. Confirmation of Current Status and Issues Relating to Operation and Maintenance Recent Status of Power Generation in Java-Bali Regions"

Transcription

1 3.2. Confirmation of Current Status and Issues Relating to Operation and Maintenance Thermal Power Stations Recent Status of Power Generation in Java-Bali Regions In Java-Bali regions as a whole, the power generating patterns from Monday through Friday are as shown in Figure and the light-up time zone is 17:00 to 18:00 hours and the peak time zone is 17:00 to 22:00 hours. However, the peak time zone in Jakarta-Banten area is 09:00 to 22:00 hours. Most of the thermal power stations of Indonesia Power and PJB perform operation without using governor-free function although the Grid Code (PLN s technical standard) provides that governor-free operation be performed. It is recommended that frequency fine-tuning operation utilizing the governor-free function be performed so that frequency can be stabilized. However, in case the above function is utilized, it is necessary to put the overload preventing security device into usable condition. * The Japanese electric power companies perform function confirmation tests of the security device to safely stop units as frequently as once a month. Source ; INDONESIA POWER data Figure Daily Load Curve in Java-Bali Regions (22 August, 2006) 3-57 Final Report

2 Operation Records Figure shows the annual operation records of Year 2004 seen from the viewpoint of operation hours of the thermal power stations under the study. Figure also covers 3 hydraulic power stations for reference. The following can be observed from this Figure ) Gilimanuk Power Station recorded the highest operating rate of 95.5% among the twelve thermal power stations. 2) In Java Island, PLTU Unit is basically in charge of the base load and PLTGU and PLTG Units are in charge of the peak load. In Bali Island, Gilimanuk P/S is in charge of the base load and Pesanggaran P/S and Pemaron P/S are in charge of the peak load. 3) Currently, the five highest ranking power stations in operating hours (ratios) are as stated below. Except Gilimanuk Power Station, PLTU power stations which are in charge of the base load are in the higher ranks followed by PLTGU power stations which are in charge of the peak load. This order is line with ELD (Economical Load Dispatcher) No. P/S Type Location Average SH 1 Gilimanuk PLTG Bali 92.4% 2 Suralaya PLTU (Coal) Jakarta-Banten 89.4% 3 Perak PLTU (MFO) Java-East 82.6% 4 Paiton PLTU (Coal) Java-East 82.5% 5 Gresik PLTGU+PLTG Java-East 72.9% 4) As for forced outage, the five highest ranking power stations with short outage times (ratios) are currently as shown below. The smallest forced outage ratio of 0.2% corresponds to 18 outage hours (=8,760 hrs 0.2%), while the highest outage was 3.7% recorded at Perak P/S. This corresponds to the annual outage hours of 324 hours. Thus, at this moment the forced outage hours vary from 18 hours to 324 hours. The forced outage hours tend to increase also in No. P/S Type Location Average FOH (D) 1 Pemaron PLTG Bali 0.2% 2 Gilimanuk PLTG Bali 0.3% 3 Tanjung Priok PLTGU + PLTG (+PLTU) Jakarta-Banten 0.7% 4 Gresik PLTGU + PLTG + PLTU Java-East 0.9% 5 Tambak Lorok PLTGU + PLTU Java-Central 0.9% 5) Both IP and PJB, which are power generating companies, have no obligation to make accident reports to PLN but have to submit a direct report to Board of PLN and press conference. They have to make finance status reports to PLN. Final Report 3-58

3 Gilimanuk P/S Gresik P/S Saguling P/S % 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH Suralaya P/S Tambak Lorok P/S Grati P/S % 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH Perak P/S Tanjung Priok P/S Sudirman P/S % 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH Paiton P/S Muara Tawar P/S Pesanggaran P/S % 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH SH POH MOH FOH (D) FOH(L) RSH Pemaron P/S (PLTG) Cirata P/S (PLTA) Muara Karang P/S (PLTGU + PLTU) Sutami P/S (PLTA) SH SH SH SH POH POH POH POH MOH MOH MOH MOH FOH (D) FOH (D) FOH (D) FOH (D) FOH(L) FOH(L) FOH(L) FOH(L) RSH RSH RSH RSH Total Total Total Total Note: PLTU : Conventional thermal power station (Oil-fired Power Station and Coal-fired Power Station or block) SH: Service Hours PLTG: Gas turbine thermal power station (or block) POH: Planned Outage Hours PLTGU: Combined Cycle power station (or block) MOH: Maintenance Outage Hours PLTD: Diesel Power Station (or block) FOH (D): Forced Outage Hours caused by power station PLTA: Hydro power station FOH(L): Forced Outage Hours caused by power grid system RSH: Reserve Shutdown Hours (=Stand by) Source: Developed by the JICA Study Team based on the provided data by each power station Pe maro n P/S Gilimanuk P/S (PLTG) Tanjung Priok P/S (PLTGU+PLTG+PLTU) SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total % 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH Cirata P/S Suralaya P/S (PLTU) Muara Tawar P/S (PLTGU + PLTG) SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total SH POH MOH FOH (D) FOH(L) RSH Perak P/S (PLTU) Saguling P/S (PLTA) SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total Muara Karang P/S Paiton P/S (PLTU) Grati P/S (PLTGU +PLTG) % SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total % 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH Sutami P/S Gresik P/S (PLTGU + PLTG + PLTU) Sudirman P/S (PLTA) SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total % 20% 40% 60% 80% 100% SH POH MOH FOH (D) FOH(L) RSH Tambak Lorok P/S (PLTGU + PLTU) Pesanggaran P/S (PLTG + PLTD) SH SH POH POH MOH MOH FOH (D) FOH (D) FOH(L) FOH(L) RSH RSH Total Total Figure Annual Operation Performance Relating Hours (%) for Objective Power Stations 3-59 Final Report

4 It is recommended that PLN and MEMR develop Regulation on power generation facility related accident reports aiming to more actively participate in the operation and maintenance of power stations. In order to reduce forced outage hours and increase power generation energy, it is essential to tackle the following and prevent repetition of similar accidents. For example, < Tasks for scheduled inspection work > 1 As for equipment which have repeatedly experienced similar accidents, it is important that the maintenance such as thorough inspection and adjustments are performed as intensive monitoring equipment during the scheduled inspection work period. 2 It is also important to make efforts to reduce the work period and ensure high operation ratio of the unit through rationalization of the scheduled inspection work. < Tasks for the prevention of routine accidents > It is crucial to promptly study measures against unexpected accidents such as Irregular Frequency and System Faults. For example, < Operational aspect > a. Education and training of troubleshooting of the unit utilizing simulators are considered to be the most effective. b. It is necessary to regularly conduct function checking tests of security devices to safely stop the plants in case of the unit trips. < Maintenance aspect > a. Since insufficient repairs frequently occur due to delay in procuring materials, it is necessary to establish a material management system to promptly cope with accidents by utilization of IT. b. It is very important to make efforts to prevent deterioration of facilities by means of predictive and preventive maintenance performed by IP and PJB power stations. c. It is essential to promote improvement of the skills of the thermal power staff and promote information sharing. Final Report 3-60

5 Numbers of Outage Times and Hours (from 2003 to 2005) The number and hours of forced outages are analyzed including the causes as mentioned later for 75 units (PLTU: 23, PLTG: 12, PLTGU: 40) among the objective thermal power stations. As for details, please refer to Table and Table (1) Number of outages and hours by unit type The numbers of outages and hours during the three years from 2003 to 2005 are as shown below 4. Table Forced Outage (Times) for Thermal Power Stations Type Total PLTU PLTG PLTGU ,042 Total , PLTU PLTG PLTGU Total Numbers of Forced Outages are too many and have been increasing in the past 3 years. Sources : INDONESIA POWER & PJB data Table Forced Outage (Hours) for Thermal Power Stations 20,000 18,000 18,443 Type Total 16,000 14,000 12,000 13,446 14,823 PLTU 2,600 5,158 9,318 17,076 PLTG 678 1,239 1,010 2,927 PLTGU 10,168 8,426 8,115 26,709 10,000 8,000 10,168 8,426 9,318 8,115 Total 13,446 14,823 18,443 46,712 6,000 4,000 2,000-5,158 2, ,239 1, PLTU PLTG PLTGU Total Forced Outage Hours are also too many and have been increasing in the past 3 years. Sources : INDONESIA POWER & PJB data 4 The electricity-related accidents for hydropower stations and thermal power stations for 2004 in Japan are 115 and 72 respectively for your reference (Source: nuclear and Industrial Safety Agency, METI) Final Report

6 (2) Number of outages by unit type The numbers of forced outages by unit type during the three years from 2003 to 2005 are as shown below. Table Causes of Forced Outage Code % Times A: Instrumentation and Control A 40.4% 157 B: Turbine/Generator B 20.3% 79 C: Boiler and Auxiliaries C 27.5% 107 D: Cable/Relay D 3.3% 13 E: Inerter E 0.5% 2 F: Transformer F 0.5% 2 G: System Fault or Irregular Frequency G 4.1% 16 H: Others H 3.3% 13 Total 100.0% % 40.0% 30.0% 20.0% 10.0% 0.0% 40.4% 20.3% 27.5% 3.3% Number of Forced Outages (Times) for PLTU 0.5% 0.5% 4.1% 3.3% A B C D E F G H Dominant causes are: - I & C : 40.4% (e.g.) MFT Trip Drum Level High/Low Furnace Draft Press. High/Low Flame Out Trip - Boiler & Auxiliaries: 27.5% (e.g.) Boiler/Tube Leak - Turbine & Generator: 20.3% (e.g.) Balancing Turbine/Generator Sources : INDONESIA POWER & PJB data Table Number of Forced Outages (Times) for PLTG Causes of Forced Outage Code % Times A: Instrumentation and Control A 50.0% 94 B: Turbine/Generator B 36.2% 68 C: Cable/Relay C 3.7% 7 D: Electrical Fault or Irregular Frequency D 2.7% 5 E: System Fault or Irregular Frequency E 3.7% 7 F: Derating F 3.2% 6 G: Others G 0.5% 1 Total 100.0% % 50.0% 40.0% 50.0% 36.2% Dominant causes are: - I & C : 50.3% (e.g.) Ignition Trouble Temperature Control Trouble Flame Out Trip - Turbine & Generator: 36.2% (e.g.) Balancing Turbine/Generator Exciter System Trouble 30.0% 20.0% 10.0% 0.0% 3.7% 2.7% 3.7% 3.2% 0.5% A B C D E F G Sources : INDONESIA POWER & PJB data Final Report 3-62

7 Table Number of Forced Outages (Times) for PLTGU Causes of Forced Outage Code % Times A: Instrumentation and Control A 36.8% 383 B: Turbine/Generator B 17.9% 186 C: HRSG and Auxiliaries C 10.4% 108 D: Relay D 1.2% 12 E: 6kV Bus E 0.8% 8 F: UPS System F 0.3% 3 G: Electrical G 1.1% 11 H: System Fault or Irregular Frequency H 7.4% 77 I: Derating I 14.6% 152 J: Others J 9.7% 101 Total 100.0% % 40.0% 30.0% 20.0% 10.0% 0.0% 36.8% 17.9% 10.4% 1.2% 0.8% 0.3% 1.1% 14.6% 9.7% 7.4% A B C D E F G H I J Dominant causes are: - I & C : 36.8% (e.g.) Exhaust Temperature High Flame Out Trip Ignition Trouble - Turbine & Generator: 17.9% Condenser Plugging Starting Motor Trouble - HRSG & Auxiliaries: 10.4% (e.g.) Exhaust Dumper Trouble Sources : INDONESIA POWER & PJB data The numbers of forced outages of PLTU, PLTG and PLTGU Units tend to increase year after year due mainly to accidents and troubles of Instrument & Control and Turbine & Generators. -The numbers of forced outages (times) due to failure of Instrument & Control is large because of repetitive occurrence of similar accidents due to unsatisfactory combustion adjustments and ABC adjustments (to specified temperature, pressure, etc.). In order to prevent recurrence of such accidents, it is essential to study alteration of the control circuits and be sure to perform combustion adjustments and ABC adjustments, etc. at scheduled inspection work. Since similar accidents also repetitively occurred on turbines/generators, it is necessary to thoroughly make the balance adjustments during scheduled inspection work. -In order to prevent repetitive occurrence of similar accidents and oversight of inspection during scheduled inspection, it is necessary to review and reinforce the current scheduled inspection system. -In order to promptly cope with accidents of the facilities, it is essential to review the education and training for trouble-shooting of the units utilizing simplified simulators (new installation) and current material procurement management system. -The following should be tackled in earnest as measures to prevent deterioration of the facilities. Facility maintenance and management aiming to expand not only the exclusive diagnosing technique but also the definition of CBM (Condition Based Monitoring) including routine inspection Implementation of inspection of thickness of pipelines for power generation Reinforcement of efforts to perform facility based maintenance -It is also very important to improve skills of thermal power operators -Efforts should be made to energetically promote sharing of useful information so that safe and stable operation of the power stations can be continued Final Report

8 Routine Management Condition (1) Confirmation of the current status 1) The power stations of Indonesia Power and PJB have acquired international certifications of ISO 14001(Environment Management System) of Integrated management system, ISO 9001 (Quality Management Systems) and OHSAS (Occupational Health and Safety Management Systems) and the general manager and staff of each power station have been enthusiastically making enormous efforts for the routine operation, maintenance and management. 2) Both Indonesia Power and PJB have been operating power stations since 1995 based on various indices defined by NERC (North America Electric Reliability Council). PJB Headquarters have introduced MOP (Maintenance Optimization Program) and are now implementing the program at Gresik, Paiton and M. Karang. 3) Trips/Shutdowns/Derating, etc. frequently occur at the power stations and the number of forced outages (times/hours) is overwhelmingly large when compared with that experienced by the power stations in Japan. Under such situation, operators of each power station are busy with troubleshooting of the facilities, while maintenance workers are busy with routinely occurring emergency works, scheduled inspection works and large-scale repair works. (2) Implementation status of routine inspection (inspection items, conditions, frequency, etc.) <Operation> Both Indonesia Power and PJB implement routine inspection under organizational systems similar to each other. Contents Shift system 3 shifts by 4 teams (All time monitoring system): 1st Shift: 07:00 ~ 15:00; 2nd Shift: 15:00 ~ 22:00, 3rd Shift: 22:00~07:00 Routine patrol inspection Operation monitoring of Control Room Others Based on Logsheet specifying operation managing values, patrol inspection of Ground Floor, Boiler area, Turbine area, etc. is conducted 2 times/shift and 6 times/day (08:00, 13:00, 16:00, 20:00, 23:00, 05:00). (Note: Almost of IP and PJB power stations takes every hour.) See Logsheet of Suralaya power station of Indonesia Power on APPENDIX TH-1 for inspection items. Output of generators, temperature and pressure of each equipment are recorded and monitored based on Logsheet every 30 minutes (or hour). As for Inspection items, see Logsheet Control Room of Suralaya power station of Indonesia Power on APPENDIX TH-2 for inspection items. At IP and PJB power stations, frequency of inspection is decided based on Log Sheet for all facilities, such as weekly, monthly, quarterly, and biannually. At the time of weekly inspection or monthly inspection, switchover of auxiliary machines such as compressors is conducted. * At some power stations, a unit trip was caused by governor-free test of turbines. Final Report 3-64

9 < Maintenance > Based on Logsheet, weekly inspection or monthly inspection is conducted and scheduled inspection work is also performed by establishing the work schedule. At IP/PJB power stations, Condition-Based Monitoring (of power source, voltage, temperature and pressure) is performed for machinery of less importance (pumps, motors, fans, compressors, etc.). Especially, at PJB, machinery analysis and monitoring by John S. Michell is adopted. Environmental monitoring data (NOX, SOX, P, etc.) are also collected. < Keeping and Management > Logsheet of patrol (results), design library, manuals maker s instructions and test records are kept and managed at each power station s Library. - Inspection through CBM (Condition Based Monitoring) is conducted basically with the exclusively diagnosing tool, but in order to prevent unforeseen facility troubles, it is very important to maintain and manage facilities aiming to expand the definition of CBM. - If there are any facilities, valves, etc. which do not have any description of such equipment, it is important to establish a procedural guideline and display names of equipment from the viewpoint of preventing erroneous operation at the time of operation and maneuvering and performing work. - It is also important to describe standard values and normal ranges for all instruments. - Trips, Shutdowns, Derating, etc. have occurred routinely at each power station. Under such situation, it is necessary to prevent oversight in patrol inspection and review ways to conduct reasonable patrol inspection instead of simply conducting patrol inspection based on Logsheet. (3) Preparation status of manuals and guidelines Based on the questionnaire survey, the Study Team has confirmed that the following manuals and guidelines have been prepared. 1) Guideline for thermal power handling jobs: 1 2 Standard guidelines which are common to operation and maintenance - Guideline for handling of accidents/troubles. - Guideline for handling of work sheet. - Guideline for disposal of industrial waste. Guidelines for operation (including environment and chemicals): - Guideline for Names of thermal power station facilities. - Guideline for management of lubricant oil, etc Final Report

10 - Guideline for procedure for operational power stoppage. - Guideline for water quality control. 2) Guidelines for quality control of scheduled inspections: - Guideline for prior assessment of work safety. - Guideline for preparation of specification. - Guideline for operation management of environment and chemical. 3) Manuals for management of power station operating jobs: - Manual for operator training. - Manual for operation jobs. - Manual for operation ad maneuvering. - Manual for patrol inspection management. - Manual for scheduled tests. - Manual for measurements to be taken in case an alarm is issued. - Manual for managements of valve locking. - Manual for safety and health activities. - Manual for environmental security management. - Manual for patrol inspection standards for maintenance workers. - Manual for security standards for power station facilities. - Manual for handling panel operation. - Manual for scheduled inspection work of measurement and control equipment. - Manual for budget plans and execution management. - The procedural guidelines have not been established for the scheduled inspection at both IP and PJB. (The inspections are conducted in accordance with scheduled inspection manuals proposed by the manufacturers.) - In order to improve quality of the scheduled inspection works and establish reliability of the equipment, it is necessary to prepare Procedural guideline for the implementation of scheduled inspections, Inspection guideline, Inspection procedure and Procedural guideline for welding inspections which are unique to IP and PJB. It is also crucial to attempt preparation and expansion of the manuals for quality and safety assurance. (4) Operation, maintenance, management of material procurement, etc. In order to conduct further operation and maintenance and management of material procurement, PJB employs ELLIPSE a consultant of Australian Mincom, while Indonesia Power employs MAXIMO, American MRO Software. They link the following modules by intra-office LAN to share information. * ELLIPSE is the latest Version of MIMS (Mincom Information management system) Final Report 3-66

11 ELLIPSE (PJB) and MAXIMO (IP) are almost the same modules with each other. 1 Operation and Maintenance Module Equipment Register Work Order (Predictive/Preventive/Corrective Maintenance) Production Statistic Fuel & Oil IP uses own its program for fuel & oil called PRONIA 2 Material Management Module Cataloger Inventory Control Management Warehouse Inventory Tracking Purchase Order In view of the current status that accidents and troubles of facilities occur repetitively because of insufficient repairs due to delay in procuring materials, it is necessary to improve the company-wide material procurement management. 3 Finance Module Journal Ledger COA : charge of Account Journal Holding Fixed Asset Financial Management 4 Labor Costing Module 5 Account Payable Module IP uses ORACLE for account payable 6 Human Resources Module Planning Establishment Training Payroll At the moment IP uses own program for Human Resources System IP is still developing Human Recourses system and use ORACLE 3-67 Final Report

12 (5) Education and training A. Indonesian Power and PJB provide the following education and training to the whole personnel. < Indonesian Power > 1 DIKLAT PENGADAAN 2DIKLAT PEMBINAAN - Recruitment Training Basic Course for Freshmen - Skill / Knowledge up Training Middle Course for some level and / or task staff 3DIKLAT PENGEMBANGAN - Developing Training Advanced Course for promotion or rotation staff 4DIKLAT PELEPASAN 5Certification / New Module (New standard program) - Retirement Training Mental spirit training Enterprise training for pre-retired person - Examination for operators and maintenance staff Module 0-General Module 1-for Auxiliary Equipment Module 2-for Boiler System Equipment Module 3-for Turbine/Generation Equipment Module 4-for Efficiency Operation < PJB > 1 Full Package Education and Training for PLTU, PLTGU, and PLTG -From Basic Course to Full standard for operators and maintenance staff. 2Refreshment Training -Middle Course of rotation staff 3 Certification / New Module (New standard program) -Examination for operators and maintenance staff Module 0-General Module 1-for Auxiliary Equipment Module 2-for Boiler System Equipment Module 3-for Turbine/Generation Equipment Module 4-for Efficiency Operation B. At PLN Suralaya Unit, the following education and training are provided to the operators and maintenance personnel of Indonesia Power and PJB. 1 On-Site Simulator Training for PLTU (Coal-Fired, 400 MW 600 MW) -CRT based PLTU Simulator -Panel based PLTU Simulator Final Report 3-68

13 -Panel based Ancillary PLTU Simulator -Generator operation Simulator etc. 2 Generator unit Operation Training -Boiler & Turbine Operation for PLTU -HRSG & Turbine Operation for PLTU -Logic & Sequence for Operator -Basic Training (Level 1, 2, 3) for PLTU Boiler Operation Turbine Operation -Basic Training (Level 1, 2, 3) for PLTG and PLTGU -Generator Operation Analysis etc. 3Generator unit Maintenance Training -General Maintenance for PLTU -Machine Maintenance for PLTU (Level 2, 3, 4) -Electric Maintenance for PLTU (Level 2, 3, 4) -Instrument and Control Maintenance for PLTU (Level 2, 3, 4) -Balancing & Alignment -Vibration Analysis -3 Phase Electric Motor -Water Treatment etc. C. Other education and training consist of lectures, discussions, etc. which are combined with simulated training and OJT on site. PLN Suralaya Unit has 5 Senior Instructors, out of whom 3 persons are scheduled to retire in They are faced with a great difficulty in selecting the successors. PLN needs to promptly select the successors and it is very important to bring up Instructors. The training simulator is the most effective to improve the skills of operators in the normal starts and stops of the unit and troubleshooting of the unit ; however, since there is no such simulator for PLTU (400 MW and 600 MW coal-fired thermal power), it is necessary to install a simulator for PLTGU. It is necessary to improve the current education of newcomers so that the reliability of the thermal power stations of Indonesia Power and PJB can be enhanced and maintained. It is also very important to prevent lessons gained from accidents, troubles, etc. from fading with time, prevent recurrence of similar accidents and pass on the skills to next generations and tackle these tasks as part of the routine education at Indonesia Power and PJB Division Final Report

14 Status of Maintenance Management (1) Implementation status of scheduled inspections The overall adjustment of specific schedules of the scheduled inspections at power stations in Java-Bali regions is made by P3B. The process and interval of the scheduled inspections are established by each power station based on the recommendations of the equipment manufacturers. The standard inspection periods and intervals and the actual results for the past 3 years from 2003 to 2005 are as shown in Table There are some scheduled inspection works whose periods were extended or in which repair works could not be done during designated work periods due to delay in the procurement of replacements, spare parts, parts, etc. Quality control during scheduled inspection work is conducted jointly by the power station and the maintenance teams (UBHAR/UHAR). However, since replacements of poor quality are used, machinery damage and troubles have frequently occurred once commercial operation is restored. Deterioration of facilities has occurred. There are some equipment which do not always exhibit sufficient function or whose capacities are deficient. As for such defective machineries, orders have already been placed for replacements; however, repairs have not been made due to delay in procuring such replacements. (2) Plans and actual results of the scheduled inspections by unit in 2006 Table shows Scheduled Maintenance and Inspection plans and results of Indonesia Power and PJB. - The insufficient repairs and deterioration of plants due to delay in procuring materials are common to both IP and PJB and urgent improvements are required for the whole company. - It is also important to take measures to reduce scheduled inspection period so that safer inspections and high operation rates can be ensured. - Since damage of equipment due to aging deterioration of power generation facilities is expected to increase, it is very important to review the inspection system at the time of scheduled inspections to prevent oversight of inspections. It is also necessary that improvements be made in the routine maintenance work. Final Report 3-70

15 P/S Suralaya (IP) Tanjung Priok (IP) Muara Karang (PJB) Muara Tawar (PJB) Tambak Lorok (IP) Perak (IP) Grati (IP) Table (1) Scheduled Maintenance / Inspection Standard Type / Interval / Period Records of Scheduled Maintenance/Inspection for 2003, 2004 and 2005 by Unit Type Unit No. Standard Plan Actual Standard Plan Actual Standard Plan Actual Type (days) (days) Type (days) (days) Type (days) (days) 8,000 8,000 8,000 8,000 TU-1 None SI ME ~10,000 (H) ~10,000 (H) ~10,000 (H) ~10,000 (H) TU-2 None SE SI TU-3 ME SI None TU-4 SE SI None 0 Simple Mean Simple Serious TU-5 ME None SI None (28 days) (30 days) (28 days) (60 days) TU-6 SI None TU-7 SI None SE (GT) GT-1.1 B B C ,000 (H) 6,000 (H) 6,000 (H) 6,000 (H) GT-1.1 C GT-1.2 B C B Type A Type B Type A Type C GT-1.3 B 10 8 B B (7 d) (14 d) (7 d) (45 d) GT-1.3 C (ST) ST-1.0 MI None None 8,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-2.1 C B C GT-2.2 B B B Simple Mean Simple Serious GT-2.3 None B C (28 d) (30 d) (28 d) (45 d) ST-2.0 None None None (GT) GT-1.1 MI 45 CI CI ,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-1.2 MI 45 MI CI GT-1.3 MI 45 MI CI CI HGPI CI MI ST-1.0 ME 30 SE 45 - SE (10 d) (30 d) (10 d) (45 d) TU-1 SI 18 None ME (ST) TU-2 ME 40 SE (SE) 8,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) TU-3 SE 45 SE (ME) ME TU-4 SE 45 SI - - ME Simple Mean Simple Serious TU-5 SI 21 ME SE (18 d) (30 d) (18 d) (45 d) - (GT) GT-1.1 Rep. HP 140 B C ,000 (H) 6,000 (H) 6,000 (H) 6,000 (H) GT-1.1 A 7 A 7 12 A 7 21 GT-1.2 B 21 B C Type A Type B Type A Type C GT-1.2 A 7 A 7 40 (MO) A 7 7 (7 d) (14 d) (7 d) (45 d) GT-1.3 A 7 B C 45 - MO: Major Overhaul GT-1.3 Gene. 46 None A 7 7 (ST) ST-1.4 ME 30 SI - - SI - - 8,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-2.1 C 100 C A 7 17 GT-2.1 B Simple Mean Simple Serious GT-2.2 Rep. HP 408 C A 7 19 (21 d) (30 d) (21 d) (45 d) GT-2.2 B 11 (GT) GT-1.1 CI 10 9 HGPI None 6,000 6,000 6,000 6,000 GT-1.2 CI HGPI None GT-1.3 MI CI HGPI CI HGPI CI MI ST-1.0 SI SI SE (7 d) (28 d) (7 d) (50 d) GT-2.1 HGPI CI MI (ST) GT-2.2 HGPI CI MI ,000 8,000 8,000 8,000 GT-2.3 MI HGPI None ~10,000 (H) ~10,000 (H) ~10,000 (H) ~10,000 (H) ST-2.0 SE SI TU-1 SI ME Simple Mean Simple Serious TU-2 ME SI (28 d) (30 d) (28 d) (45 d) TU-3 SI ME (GT) TU-3 SI None ME ,000*CDF (H) 8,000 (H) 8,000 (H) 8,000 (H) TU-4 SE None SI SI(21 d) ME30 d) SI(21 d) SE(45 d) - (GT) GT-1.1 TI None CI ,000*CDF (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-1.2 TI None CI 11 9 GT-1.3 CI TI CI CI(7 d) HGPI(28 d) CI(7 d) MI(45 d) ST-1.0 None TI: Turbine Inspection: HGPI GT-2.1 FYI None TI FYI: First year Inspection GT-2.2 FYI None None (ST) GT-2.3 FYI 14 8 None None 8,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) Simple Mean Simple Serious - (18 d) (30 d) (18 d) (45 d) Final Report

16 + P/S Gresik (PJB) Paiton (PJB) Pesanggaran (IP) Gilimanuk (IP) Pemaron (IP) Table (2) Records of Scheduled Maintenance/Inspection for 2003, 2004 and 2005 by Unit Type Scheduled Maintenance / Inspection Standard Type / Interval / Period Unit No. Standard Plan Actual Standard Plan Actual Standard Plan Actual Type (days) (days) Type (days) (days) Type (days) (days) (GT) GT-1.1 MI 45 CI TI ,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-1.2 TI 25 CI 10 9 MI GT-1.3 TI 25 CI MI CI(10 d) HPGI(30 d) CI(10 d) MI(45 d) ST-1.0 SE 45 SI SE 45 - GT-2.1 TI 25 TI MI TI: Turbine Inspection: HRSG GT-2.1 CI GT-2.2 MI 45 CI 10 9 TI (ST) GT CI ,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) GT-2.3 CI 10 CI MI GT-2.3 TI 25 MI MI None 0 Simple Mean Simple Serious ST-2.0 SE 45 SI 18 - SE 45 - (18 d) (30 d) (18 d) (45 d) GT-3.1 CI 10 TI CI GT-3.2 CI+Co. 30 MI CI 10 8 GT-3.3 CI+Co. 30 MI CI ST-3.0 ME 30 ME SI TU-1 SI 16 SE 45 - SE TU-2 ME 30 ME SI TU-3 SI 18 ME SE+Granti TU-4 ME 30 SI SE+Granti GT-1 CI HGPI GT HGPI (ST) TU-1 ME 42 ME SI ,000 (H) 8,000 (H) 8,000 (H) 8,000 (H) TU-1 None SE TU-2 SE 57 SI ME 42-0 Simple (26 d) Mean (42 d) Simple (26 d) Serious (57 d) - (GT: Alstom; GT-1, GE; GT-2) GT-1 MI HGPI CI 9 5 4,000 (H) 4,000 (H) 4,000 (H) 4,000 (H) GT-1 CI 9 9 GT-2 CI 9 4 CI 9 6 MI CI(7 d) HGPI(28 d) CI(7 d) MI(45 d) GT-2 HGPI (GT: WH; GT-3,4) GT-3 HGPI CI 9 6 None 6,000 (H) 6,000 (H) 6,000 (H) 6,000 (H) GT-3 GT-4 CI HGPI None 0 CI(7 d) HGPI(28 d) CI(7 d) MI(45 d) GT-4 CI 9 9 (GT) GT-1 A 15 9 A 9 10 B ,000 (H) 6,000 (H) 6,000 (H) 6,000 (H) GT-1 C None A 7 7 GT-1 C Type A (7 d) Type B (14 d) Type A (7 d) Type C(45 d) - (GT) GT-1 None None CI ,000 (H) 4,000 (H) 4,000 (H) 4,000 (H) GT-2 None None None - 0 CI (7 d) HGPI (28 d) CI (7 d) MI(45 d) - Final Report 3-72

17 Table Plans/Actual of Scheduled Maintenance/Inspection for 2006 by Unit Type (As of July 2006) < Indonesia Power > Power Station Suralaya Tanjung Priok Perak Grati unit unit Standard Plan Actual Power Station Standard Plan Actual No. No. Type (days) (days) Type (days) (days) Tu-1 None GT-1.1 MI Tu-2 None GT-1.2 HGPI Tu-3 ME GT-1.3 None Tu-4 ME ST-1.0 SI 21 Tu-5 SE GT-2.1 CI 8 5 Tu-6 ME 30 Tambak Lorok GT-2.2 MI Tu-7 SI+ 30 GT-2.3 MI 51 In progress GT-1.1 B ST-2.0 SE 51 GT-1.2 B Tu-1 SI 28 GT-1.2 C 45 Tu-2 SE 51 GT-1.3 B Tu-3 SI+ 76 ST-1.0 None Gilimanuk GT-1 A 9 9 GT-2.1 B 14 9 GT-1 B 14 GT-2.2 C 45 Pemaron GT-1 CI GT-2.3 B 14 GT-2 MI ST-2.0 MI 42 GT-2 CI 14 Tu-3 SI+Re 60 Pesanggaran GT-1 None Tu-4 ME+Reh 60 GT-2 CI 14 6 GT-1.1 None GT-3 MI GT-1.2 MI GT-4 MI GT-1.3 MI 41 ST-1.0 MI GT-2.1 None GT-2.2 TI GT-2.3 TI < PJB > Power Station Muara Karang Muara Tawar Paiton unit unit Standard Plan Actual Power Station Standard Plan Actual No. No. Type (days) (days) Type (days) (days) Tu-1 SE 60 Tu-1 SI Tu-2 ME 45 In progress Tu-2 SE 45 In progress Tu-3 SE Tu-3 SE+Grant Tu-4 SE 60 Tu-3 SI 18 Tu-5 ME Tu-4 SI 18 Tu-5 SE 60 GT-1 None GT-1.1 HGPI 30 GT-2 CI GT-1.2 CI 14 GT-1.1 CI 10 9 GT-1.3 CI 14 GT-1.1 MI+RI 45 ST-1.0 SI 18 GT-1.2 CI GT-1.1 B Gresik GT-1.2 TI 25 GT-1.1 A 8 GT-1.3 CI 10 GT-1.2 B ST-1.0 SE 45 GT-1.2 A 8 GT-2.1 CI GT-1.3 C GT-2.2 MI+RI 45 GT-1.3 A 8 8 GT-2.3 MI+RI GT-1.3 B 21 ST-2.0 SE ST-1.4 SE GT-3.1 MI GT-2.1 A 8 9 GT-3.2 TI GT-2.1 C 45 GT-3.3 TI GT-2.2 A 8 9 GT-3.0 SE 45 GT-2.2 C 45 Tu-1 None Tu-2 SE Sources : INDONESIA POWER & PJB data 3-73 Final Report

18 (3) Management of work plans Indonesia Power and PJB confirm the status of the Preventive/Predictive/Corrective Maintenance and the new work plans, taking into account the 5-year midterm work plans and load balance by the internal meetings as listed below. Items Internal Meetings at Power Station Main Agenda 1 - Yearly Meeting (Develop 5 year Plan by Unit) - Planned Outage Scheduling Rehabilitation, Major Modification, Re-powering, and Scheduled Inspection Plan etc. 2 - Quarterly Meeting (Develop Plan of the year) - Yearly Preventive Maintenance & Predictive Maintenance & Load Balancing - Yearly Maintenance Budget 3 - Monthly Meeting (Develop Plan of the Quarter) - Detail Planning & Scheduling of individual Outages - First Line Maintenance work orders Load Balancing - Monthly Schedule & Load Balancing - For coal 4 - Weekly Meeting (Develop Plan of the Week) - Work outside Outages - not urgent(required after 7 days) Preventive Maintenance Corrective Maintenance 5 - Daily Meeting (Develop Plan of the Day) - Work outside Outages - urgent (required in less than 7 days) Preventive Maintenance Corrective Maintenance It is essential to collect and put together actual data of accidents and have discussions at such Internal Meetings in an effort to solve pending items in terms of the facilities and operations of the power stations so that appropriate troubleshooting can also be carried out. (4) Information sharing among power stations As shown in Table below, efforts have been made by the power stations of Indonesia Power and PJB to share information on the operation and maintenance of such power stations. Final Report 3-74

19 Information Exchange Meetings among the power stations Items PJB Indonesia power 1 Coordination Meeting Attendance Frequency Main Agenda -Deputy Manager -Every 3 months -Performance Report -Condition of power station -GM or DGM - ditto - - ditto - 2 Operation & Maintenance Meeting Attendance Frequency Main Agenda None Internal Meeting =Daily meeting -GM or DGM -Every 2 months -Information Exchange 3 Technical Forum Attendance Frequency Main Agenda -DM & Supervisor -Every 6 months -Problem & Solution -Manager -Every year -ditto- 4 Working Group Meeting New Information Sharing Meeting Attendance Frequency Main Agenda -Start from Specialist -Every 6 months -Good Practice Information Sharing None Internal Meeting =Weekly meeting It is very important to have Information Exchange Meetings regularly on such information as is useful for safe and stable operation of the power stations, namely, information on tasks for all management and personnel such as 1) measures to prevent critical disasters and 2) measures to prevent accidents affecting power supply so that overall spiraling improvement of performance can be achieved Operation and Maintenance Management System (1) Organizations of Indonesia Power and PJB Power Stations A typical organizational chart of a power station of Indonesia Power and PJB is as shown below Final Report

20 Organization Chart of an Indonesia Power Station GENERAL MANAGER AUDITOR SPESIALIS OPERASI DAN NIAGA PEMELIHARAAN ENJINIRING MANAJER LOGISTIK SISTEM DAN SDM KEUANGAN HUMA Organization Chart of a PJB PowerStation Source : INDONESIA POWER data (T.PRIOK) MANAGER AUDITOR ENJINIRING OPERASI PEMELIHARAAN KIMIA DAN LK 3 KEUANGAN SUMBERDAYA MANUSIA UMUM Source : PJB data (M. KARANG) The organizations of Indonesia Power and PJB which are engaged in operation and maintenance management of the power stations are of the same structure with each other. (2) Routine Maintenance Management System of Power Stations As shown in Table 3.2-8, Indonesian Power has established Maintenance System based on Location of Facilities while PJB has established Maintenance System based on Category of Maintenance Method. Therefore, Indonesia Power and PJB conduct maintenance management under the systems which are different from each other. < Measures to cope with troubles due to deterioration of aging facilities > Since unpredictable troubles due to aged deterioration of power generation facilities are expected to increase in the future, it is essential for both Indonesia Power and PJB to consider reviewing the methods to tackle routine facility maintenance from the viewpoint of maintaining reliability of the facilities. For instance, measures to reinforce facility based maintenance are as follows: 1 Inspection activities focusing on investigation of deterioration status of the whole facilities 2 Visual inspection by maintenance personnel who are familiar with their own facilities 3 Study on the employment of new exclusive diagnosing tools as preventive measures against deterioration of facilities Final Report 3-76

21 Indonesia Power (IP) Table System for Maintenance Division at Power Station Duty Main Task (Deputy General Manager) Manager Machine Maintenance Turbine Maintenance Supervisor Senior Boiler Maintenance Control Maintenance Supervisor Electric Maintenance Pump & Compr. Maintenance Technician Senior Fan & Mill Maintenance etc. Technician Senior ( ):Only Suralaya Maintenance System Based on Location of Facilities PJB Deputy Manager Specialist Supervisor Technician Senior Technician Junior Corrective & Emergency Maintenance Predictive Maintenance Preventive Maintenance Maintenance System Based on Category of Maintenance Method IP adopts Maintenance System Based on Location of Facilities, while PJB adopts Maintenance System Based on Category of Maintenance Method. IP is recommended to strengthen their maintenance system and PJB is recommended to switch their maintenance system to the Maintenance System Based on Location of Facilities because it is envisaged the aged deterioration of power facilities is accelerating in the future. (3) Sharing of roles between Power Station and Maintenance Business Unit (UBHAR/UHAR) for Scheduled Maintenance As shown in Table and Table , there are differences between Indonesia Power and PJB in the details of assistance provided by the Maintenance Business Unit (UBHAR/UHAR) in Scheduled Inspection Work and Scheduled Special Order Maintenance Work. Indonesia Power s UBHAR/UHAR : Main facilities such as boilers, turbines, generators, etc. PJB s UBHAR/UHAR : All facilities such as main turbines, auxiliary machinery and commonly used facilities Final Report

22 < Review of Quality Control System for Scheduled Inspection Work > While the Quality Control of the Scheduled Inspection Work is performed jointly by Maintenance Division (UBHAR/UHAR), in view of the current status in which troubles due to inappropriate maintenance have frequently occurred and the increase of unexpected troubles due to aged deterioration of the power station facilities, it is recommended that Quality Control System be established with the user s power station taking a leadership role. Table Sharing of Role between Maintenance Department of the Power Station and Maintenance Business Unit (UBHAR/UHAR) Category of Maintenance 1. Corrective Maintenance & Emergency work for PLTU, PLTGU and PLTG e.g. 1 Unscheduled maintenance work (Fire accident or Trouble) 2 Maintenance work against malfunctions of facilities in operating division 2. Predictive Maintenance for PLTU, PLTGU and PLTG e.g. 1 Condition-based maintenance should be carried out on the low priority facilities Pump/Motor/Fan/Compressor, etc. 3. Preventive Maintenance for PLTU, PLTGU and PLTG e.g. 1 Daily maintenance work 2 Planning maintenance 3 Scheduled inspection work 4 Scheduled special order maintenance work :Responsible Task Indonesia Power PJB Power Station UBHAR Power Station UBHAR Major Accident or Trouble Major Accident or Trouble Auxiliary Ancillary Quality control Unit start-up Main Facility Quality control Quality control Unit start-up Main Facility Auxiliary Ancillary Quality control Remarks; UBHAR ; Maintenance Business Unit In Scheduled Inspection Work, UBHAR/UHAR of IP are in charge of the main facilities and UBHAR/UHAR of PJB are in charge of all the facilities including main turbines, auxiliary machinery and commonly used facilities. Final Report 3-78

23 Table Support System in UBHAR for Scheduled Maintenance/Inspection Work < Indonesia Power > - UBHAR Head-office in Jakarta city carries out two services as follows UBHAR Internal Service for Indonesian Power s Power station External Service for another IPP/companies -UBHAR Teams are dispatched to 5 units to support maintenance areas of each thermal power station in JAVA-BALI Region Suralaya Area,T. Priok Area,Perak-Grati Area and Bali Area, Semarang Area -Each UBHAR Area Team carries out coordinating Scheduled Inspection works and Special Order Maintenance works -UBHAR Head-office dispatches 1 or 2 persons (Expert persons) in order to support Quality Control for UBHAR Area Team during Scheduled Inspection work which are Serious (Major), Mean and Simple Inspection <PJB> - UBHAR Head-office at Gresik carries out the internal service only for PJB s power station - Every thermal power station in PJB has unit support maintenance as subordinate of UBHAR They works for Scheduled Inspection Work and Special Order Maintenance Work - UBHAR Head-office dispatches 2 persons (Specialist, Supervisor) in order to support Quality Control of UBHAR at power station during Scheduled Inspection works which are Serious (Major), Mean and Simple Inspection (4) Status of regular personnel interchanges between operators and maintenance personnel It appears that once the assignments of newcomers are fixed, their jobs are rarely changed. There have been few cases of regular personnel interchanges. It is very important to regularly effect personnel changes between operators and maintenance staff so that improvement of the overall skills can be achieved. From the viewpoint of improving skills of the maintenance personnel of the power stations, personnel changes with the Maintenance Business personnel should be effected at regular intervals Final Report

24 Table (1) Summary of Forced Outage for 2003, 2004 and 2005 at Each Unit Type PLTU Unit Suralaya P/S Paiton P/S Muara Karang P/S Gresik P/S Tambak Lorok P/S Perak P/S Base Load Unit Base Load Unit Base Load Unit Base Load Unit Base Load Unit Base Load Unit Coal Fired Coal Fired MFO/HSD/NG Fired MFO/NG Fired MFO Fired MFO Fired Total 4x400MW + 3x600MW 2 x 400 MW 3x100MW + 2x200MW 2x100MW + 2x200MW 2x50MW + 1x200MW 2 x 50MW Trouble Items Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours 1 Instrumentation and Control 42 (9.2) (38.7) (45.6) 1, (41.7) (37.0) (14.7) (40.4) 2, Turbine / Generator 14 (11.5) (25.8) (20.4) 1, (25.0) (17.4) (38.2) (20.3) 3, Boiler and Auxiliaries 34 (75.3) 1, (35.5) (19.8) 1, (30.4) (47.1) 6, (27.5) 11, Cable/Relay Trouble 3 (1.9) (33.3) (13.0) (3.3) Inverter Trouble 2 (1.2) (0.5) Transformer Trouble 2 (1.2) (0.5) System Fault or Irregular Frequency 10 (3.1) (3.1) (2.2) (4.1) Others 2 (0.9) (6.8) (3.3) Total 102 (100) 2, (100) (100) 5, (100) (100) 1, (100) 7, (100) 17, (Reference Attachment Sheets) - Summary of Forced Outage for 2003, 2004 and 2005 (~ Nov.) at Paiton and Suralaya P/S Remarks - Summary of Forced Outage for 2003, 2004 and 2005 (~ Dec.) at Muara Karang P/S - Summary of Forced Outage for 2003, 2004 and 2005 (~ Oct.) at Gresik P/S - Summary of Forced Outage for 2003, 2004 and 2005 (~ Oct.) at Tambak Lorok P/S - Summary of Forced Outage for 2003, 2004 and 2005 (~ May) at Perak P/S Source : Indonesia Power, PJB data Final Report 3-80

25 Table (2) Summary of Forced Outage for 2003, 2004 and 2005 at Each Unit Type PLTG Unit Muara Tawar P/S Grati P/S Pesanggaran P/S Gilimanuk P/S Pemaran P/S Peak Load Unit Peak Load Unit Peak Load Unit Base Load Unit Peak Load Unit HSD Fired HSD Fired HSD Fired HSD Fired HSD Fired 2 x 140 GT 3 x 100.8GT 1x x20 + 2x42 1 x 133.8GT 2 x 48.8GT Trouble Items Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours 1 Instrumentation and Control 21 (48.8) (70.9) (11.4) (20.0) (52.4) (50.0) 1, Total 2 Turbine / Generator 15 (34.9) (22.8) (68.6) (40.0) (33.3) (36.2) 1, Cable / Relay Trouble 2 (5.7) (20.0) (14.3) (3.7) Electrical Fault 5 (6.3) (2.7) System Fault or Irregular Frequency 1 (2.3) (11.4) (20.0) (3.7) Derating 6 (14.0) (3.2) Others 1 (2.9) (0.5) 8.02 Total 43 (100) 1, (100) 1, (100) (100) (100) (100) 2, (Reference Attachment Sheets) - Summary of Forced Outage for 2004 and 2005 (~ Oct.) at Muara Tawar P/S Remarks - Summary of Forced Outage for 2003, 2004 and 2005 (~ Dec.) at Grati P/S - Summary of Forced Outage for 2003, 2004 and 2005 (~ Oct.) at Pesanggaran P/S, Gilimanuk P/S and Pemaran P/S Source : Indonesia Power, PJB data 3-81 Final Report

26 Table (3) Summary of Forced Outage for 2003, 2004 and 2005 at Each Unit Type PLTGU Unit Tanjung Priok P/S Gresik P/S Muara Karang P/S Peak Load Unit Peak Load Unit Peak Load Unit HSD/NG Fired HSD/NG Fired NG Fired 3x130GT + 1x200ST 3x130GT + 1x200ST 3x112.5GT + 1x188.9ST 3x112.5GT + 1x188.9ST 3x112.5GT + 1x188.9ST 3x107.8GT + 1x185ST Trouble Items Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours Times (%) Hours 1 Instrumentation and Control 25 (45.5) (21.6) (30.6) (19.0) (37.5) (50.9) Turbine / Generator 15 (27.3) (52.9) (10.2) (12.7) (5.3) (22.3) 1, HRSG and Auxiliaries 19 (38.8) (47.6) (30.4) (2.7) Relay Trouble 12 (10.7) kV Bus Trouble 5 (10.2) (1.6) (3.6) UPS System Trouble 1 (2.0) (3.2) Electrical Trouble 8 System Fault or Irregular Frequency 13 (23.6) (25.5) (8.2) (14.3) (17.9) (8.9) Derating 10 Others 2 (3.6) (1.6) (5.3) (4.5) Total 55 (100) (100) (100) (100) (100) (100) 2, (Reference Attachment Sheets) - Summary of Forced Outage for 2004 and 2005 (~ Sep.) at Tanjung Priok P/S Remarks - Summary of Forced Outage for 2003, 2004 and 2005 (~ Dec.) at Gresik P/S - Summary of Forced Outage for 2003, 2004 and 2005 (~ Dec.) at Muara Karang P/S Source : Indonesia Power, PJB data Final Report 3-82

Low and medium voltage service. Power Care Customer Support Agreements

Low and medium voltage service. Power Care Customer Support Agreements Low and medium voltage service Power Care Customer Support Agreements Power Care Power Care is the best, most convenient and guaranteed way of ensuring electrification system availability and reliability.

More information

(1) Current State and Issues of the Electricity Sector in Indonesia

(1) Current State and Issues of the Electricity Sector in Indonesia Japanese ODA Loan Ex-ante Evaluation 1. Name of the Project Country: The Republic of Indonesia Project: Java-Sumatra Interconnection Transmission Line Project (I) Loan Agreement: April 30, 2010 Loan Amount:

More information

ELE-OS-E-2002 Start-up Shift Operation Engineer & Permit Coordinator PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS

ELE-OS-E-2002 Start-up Shift Operation Engineer & Permit Coordinator PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS 101934-ELE-OS-E-2002 Start-up Shift Operation Engineer & Permit Coordinator Holds a B. Sc. and a Diploma in Electrical Power & Machines Engineering. Has about 15 years hands-on experience working in operation,

More information

To Our Business Partners

To Our Business Partners CSR CSR > Social Performance > To Our Business Partners To Our Business Partners We build relationships of trust by engaging in open communication, with mutual prosperity as our goal. To Our Dealers Basic

More information

Chapter 5 Transmission Planning and System Analysis

Chapter 5 Transmission Planning and System Analysis Chapter 5 Transmission Planning and System Analysis In this chapter, various types of system analysis (power flow analysis, stability analysis, short circuit analysis, frequency analysis) are used and

More information

LIST OF MAJOR WORKS FOR POWER PLANT as of October 2009

LIST OF MAJOR WORKS FOR POWER PLANT as of October 2009 1 MUARA KARANG STEAM MUARA KARANG PT. PLN MARUBENI CORPORATION - MECHANICAL & PIPING WORKS 1975-1976 POWER PLANT UNIT 1, 2 & 3 (JAKARTA) (PERSERO) MITSUBISHI HEAVY INDUS. - ELECTRICAL WORKS 100 MW X 3

More information

Section 5 - Operations and Maintenance Program

Section 5 - Operations and Maintenance Program Section 5 - Operations and Maintenance Program A. Introduction The intent of this section of the SSMP is to describe the current operation of the City s wastewater collection system. There are five areas

More information

ABB Drive Services Your choice, your future

ABB Drive Services Your choice, your future ABB Drive Services Your choice, your future Your choice, your future The future of your drives depends on the service you choose. Whatever you choose, it should be a well-informed decision. No guesswork.

More information

Terry Blackwell Page 1 of 5. Education North Carolina State University BS, Electrical Engineering Power Systems emphasis

Terry Blackwell Page 1 of 5. Education North Carolina State University BS, Electrical Engineering Power Systems emphasis Terry Blackwell Page 1 of 5 Education 1977 North Carolina State University BS, Electrical Engineering Power Systems emphasis Professional Qualifications 1977 PE-Professional Engineer Business Experience

More information

Operational Opportunities to Minimize Renewables Curtailments

Operational Opportunities to Minimize Renewables Curtailments Operational Opportunities to Minimize Renewables Curtailments Clyde Loutan Principal, Renewable Energy Integration July 24, 2017 2017 CAISO - Public Page 1 Agenda Background Real-time control performance

More information

Coordinating Process Improvement in Multiple Geographically Dispersed Development Organizations Using CMMI. Aldo Dagnino and Andrew Cordes

Coordinating Process Improvement in Multiple Geographically Dispersed Development Organizations Using CMMI. Aldo Dagnino and Andrew Cordes Coordinating Process Improvement in Multiple Geographically Dispersed Development Organizations Using CMMI Aldo Dagnino and Andrew Cordes ABB Inc. US Corporate Research Center Raleigh, NC ABB Group - 1

More information

TEPCO NUCLEAR SAFETY REFORM PLAN PROGRESS REPORT 1 ST QUARTER FY 2014 EXECUTIVE SUMMARY

TEPCO NUCLEAR SAFETY REFORM PLAN PROGRESS REPORT 1 ST QUARTER FY 2014 EXECUTIVE SUMMARY Introduction TEPCO NUCLEAR SAFETY REFORM PLAN PROGRESS REPORT 1 ST QUARTER FY 2014 EXECUTIVE SUMMARY TEPCO established its Nuclear Safety Reform Plan (full text of the plan may be viewed at http://www.tepco.co.jp/en/press/corp

More information

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027)

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027) February 2013 Contents I. Introduction 1 II. Status of Electricity Supply and Demand 2 1. Electricity Demand 2 2. Electricity

More information

CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER

CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER CONTROLS UPGRADE CASE STUDY FOR A COAL-FIRED BOILER ABSTRACT This paper discusses the measures taken to upgrade controls for a coal-fired boiler which was experiencing problems with primary air flow, furnace

More information

Organization Structure

Organization Structure Organization Structure Overview KEPCO Group KEPCO KPS KEPCO Plant Service & Engineering Co., Ltd. KOMIPO Korea Midland Power Co., Ltd. KEPCO E&C KEPCO Engineering & Construction Company, Inc. KEPCO KDN

More information

Automotive Technology

Automotive Technology It is the mission of the Automotive Department of Victor Valley Community College to provide quality automotive instruction to a diverse community of students; the array of courses offered shall serve

More information

Technical Information

Technical Information Technical Information No. : 064-2016 1 August 2016 To Subject : Whom It May Concern : Summary Report of IMO Meetings of Sub-Committee on Implementation of IMO Instrument (III 3) 3 rd session Summary This

More information

Appendix L-2 Calculating Combined-Cycle and Cogeneration

Appendix L-2 Calculating Combined-Cycle and Cogeneration Appendix L-2 Calculating Combined-Cycle and Cogeneration Block Data Using the Fleet-type Rollup Method When Reporting Each Gas Turbine/Steam Turbine Unit Overview This document will explain the fleet-type

More information

CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event

CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event CCHMP Comments on ConocoPhillips Incident Report For 10/22/10 Flaring Event The following comments relate to reviewing ConocoPhillip s RCA report received on 12/21/10. 1. The report identified that operators

More information

ABB life cycle services Uninterruptible power supplies

ABB life cycle services Uninterruptible power supplies ABB life cycle services Uninterruptible power supplies 2 ABB Life cycle brochure UPS service portfolio Life cycle services for uninterruptible power supplies As your service partner, ABB guarantees you

More information

B. Sc., Mechanical power science Engineering, May 1987, Monofia University. - Construction Safety Health 30 hours Administration Training by (OSHA).

B. Sc., Mechanical power science Engineering, May 1987, Monofia University. - Construction Safety Health 30 hours Administration Training by (OSHA). PM-SOM-E-0137-1987 Mechanical Commissioning Manager He is an expert in fossil fuel power generating plants operation and commissioning. He has 23 years of experience in this field (in Egypt, KSA, Syria

More information

CITY OF OVERLAND PARK POSITION DESCRIPTION

CITY OF OVERLAND PARK POSITION DESCRIPTION CITY OF OVERLAND PARK POSITION DESCRIPTION TITLE: Equipment Mechanic, Senior BAND/LEVEL: Tech II DEPARTMENT: Public Works JOB NO: 7320 DIVISION: Fleet Maintenance Division DATE: 02/15/2016 REPORTS TO:

More information

Study on Economic Partnership Projects. in Developing Countries in FY kV Lines in West Java, in Indonesia SUMMARY.

Study on Economic Partnership Projects. in Developing Countries in FY kV Lines in West Java, in Indonesia SUMMARY. Study on Economic Partnership Projects in Developing Countries in FY2007 Study on Upgrading Transmission Capacity of Existing 500kV Lines in West Java, in Indonesia SUMMARY March 2008 Tokyo Electric Power

More information

PAGE 1 OF 5 HEALTH, SAFETY & ENVIRONMENTAL MANUAL PROCEDURE: S360 Overhead Cranes & Lifts Procedure REV 4.0 8/14/2012

PAGE 1 OF 5 HEALTH, SAFETY & ENVIRONMENTAL MANUAL PROCEDURE: S360 Overhead Cranes & Lifts Procedure REV 4.0 8/14/2012 PAGE 1 OF 5 PURPOSE: OVERHEAD CRANES AND LIFTS PROCEDURE The purpose of this procedure is to define the safety and training requirements for use of overhead cranes and lifts. Procedure: Definitions Designated

More information

Preventing Road Accidents and Injuries for the Safety of Employees Case Study: ALSA FACTFILE. Company: ALSA

Preventing Road Accidents and Injuries for the Safety of Employees Case Study: ALSA FACTFILE. Company: ALSA PRAISE Preventing Road Accidents and Injuries for the Safety of Employees Case Study: ALSA ETSC s PRAISE project addresses the safety aspects of driving at work and driving to work. Its aim is to promote

More information

Appendix L-1 Calculating Combined-Cycle and Cogeneration

Appendix L-1 Calculating Combined-Cycle and Cogeneration Appendix L-1 Calculating Combined-Cycle and Cogeneration Block Data Using the Synthesis Event and Performance Method When Reporting Each Gas Turbine/Steam Turbine Unit Overview This document will explain

More information

Your Engine. Our Ingenuity.

Your Engine. Our Ingenuity. MARKISCHES WERK Your Engine. Our Ingenuity. 3 Long live the engine... and the people who keep them running. Provide nothing but the best products and services, every time. Since 1859, MWH has earned the

More information

Experiences in a Motor Protection Retrofit

Experiences in a Motor Protection Retrofit Special Feature by Kyle Craig, Ontario Power Generation Amy Sinclair, Schweitzer Engineering Laboratories, Inc. Experiences in a Motor Protection Retrofit Introduction The initial stage of any project

More information

Success of the H-IIB Launch Vehicle (Test Flight No. 1)

Success of the H-IIB Launch Vehicle (Test Flight No. 1) 53 Success of the H-IIB Launch Vehicle (Test Flight No. 1) TAKASHI MAEMURA *1 KOKI NIMURA *2 TOMOHIKO GOTO *3 ATSUTOSHI TAMURA *4 TOMIHISA NAKAMURA *5 MAKOTO ARITA *6 The H-IIB launch vehicle carrying

More information

Rehabilitation of Diesel Railcars Project, Diesel Railcar Rehabilitation Project

Rehabilitation of Diesel Railcars Project, Diesel Railcar Rehabilitation Project Indonesia Rehabilitation of Diesel Railcars Project, Diesel Railcar Rehabilitation Project 1. Project Profile and Japan s ODA Loan Report Date: March 2001 Field Survey: September 2000 Project Site Project

More information

SUBJECT: Russell Hill Subway Train Accident Of August 11, 1995 Due Diligence Checklist Update

SUBJECT: Russell Hill Subway Train Accident Of August 11, 1995 Due Diligence Checklist Update MEETING DATE: August 31, 2005 SUBJECT: Russell Hill Subway Train Accident Of August 11, 1995 Due Diligence Checklist Update RECOMMENDATION It is recommended that the Commission: i) Receive for information

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

Grain LNG: A Collaborative Approach To LNG Terminal Business Performance Improvement

Grain LNG: A Collaborative Approach To LNG Terminal Business Performance Improvement Grain LNG: A Collaborative Approach To LNG Terminal Business Performance Improvement Nick Blair, Grain LNG, Commercial Operations Marco Fahl, Honeywell, Senior Consultant 2012 Business Optimization Conference

More information

Retrofitting of Mitsubishi Low NOx System

Retrofitting of Mitsubishi Low NOx System 111 Retrofitting of Mitsubishi Low NOx System Susumu Sato *1 Yoshinori Kobayashi *1 Takao Hashimoto *2 Masahiko Hokano *2 Toshimitsu Ichinose *3 (MHI) has long been engaged in low NOx combustion R & D

More information

Bus and coach engineering technician standard: Employer Occupational Brief

Bus and coach engineering technician standard: Employer Occupational Brief Bus and coach engineering technician standard: Employer Occupational Brief July 2016 Competence expectations at gateways There are three gateway competency points in the bus and coach engineering technician

More information

ELE-MOS-E-2006 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ELE-MOS-E-2006 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 101162-ELE-MOS-E-2006 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 7 years hands-on experience, mainly in operation, maintenance, commissioning and start-up.

More information

Service and Rehabilitation Electrical Power Systems

Service and Rehabilitation Electrical Power Systems Service and Rehabilitation Electrical Power Systems From water to wire 3 ANDRITZ HYDRO Electrical Power System Modernization and rehabilitation International technology group ANDRITZ is a globally leading

More information

European Responsible Care Award Celanese Contractor Safety Improvements. About Celanese

European Responsible Care Award Celanese Contractor Safety Improvements. About Celanese European Responsible Care Award 2011 Celanese Contractor Safety Improvements About Celanese Celanese Corporation is a leading, global integrated producer of chemicals and advanced materials used in consumer

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

Upcoming Public Training Courses in Sana a-yemen (July -Dec, 2013 )

Upcoming Public Training Courses in Sana a-yemen (July -Dec, 2013 ) 1 Upcoming Public Training Courses in Sana a-yemen (July -Dec, 2013 ) HS EC EE ME MS OE EM BS CM DE FS ND IT QM PM API ASME AT Health & Safety Electronics and Communication Electrical & Instrumentation

More information

Grid Operations & Planning R&D Area Overview

Grid Operations & Planning R&D Area Overview Grid Operations & Planning R&D Area Overview Daniel Brooks Speaker s Job Title Sept 2016 Advisory Committee 2016 Sept 19: Hollywood, FL Grid Operations & Planning R&D Area at a Glance Grid Operations Advanced

More information

Essential Elements of a Successful Preventive Maintenance Program

Essential Elements of a Successful Preventive Maintenance Program Essential Elements of a Successful Preventive Maintenance Program OCTOBER 19, 2015 PRESENTED BY: ROBBIE L. SARLES RLS & ASSOCIATES, INC. Why Be Concerned with Preventive Maintenance Required by FTA Required

More information

Owner s Information Manual

Owner s Information Manual 50ES---A and 50VL---C Comfort 13SEERThreePhase2½---5NominalTons (Sizes 30---60) Comfort 14 SEER Single and Three Phase 2---5 Nominal Tons (Sizes 24---60) Single Packaged Air Conditioner System With Puronr

More information

2018 OPERABILITY ASSESSMENT

2018 OPERABILITY ASSESSMENT 2018 OPERABILITY ASSESSMENT Mohab Elnashar, PhD, P.Eng. Senior Engineer Performance Validation and Modeling January 8, 2019 What is an Operability Assessment? An Operability Assessment is a study of the

More information

City of Palo Alto (ID # 6416) City Council Staff Report

City of Palo Alto (ID # 6416) City Council Staff Report City of Palo Alto (ID # 6416) City Council Staff Report Report Type: Informational Report Meeting Date: 1/25/2016 Summary Title: Update on Second Transmission Line Title: Update on Progress Towards Building

More information

UT Martin Environmental Health & Safety Safety Procedure

UT Martin Environmental Health & Safety Safety Procedure MOTOR VEHICLE SAFETY UT Martin Environmental Health & Safety Safety Procedure EFFECTIVE DATE: 03/15/86, REVISED: 09/14 1. GENERAL A. All drivers for the University are considered as representatives of

More information

BASIC PUMP TECHNOLOGY

BASIC PUMP TECHNOLOGY Training Title BASIC PUMP TECHNOLOGY Training Duration 5 days Training Venue and Dates REF Basic Pump Technology ME039 5 20 24 October, 2019 $4,250 Dubai, UAE In any of the 5 star hotel. The exact venue

More information

OEM PARTS & SERVICE GENUINE REPLACEMENT PARTS FACTORY-DIRECT SERVICE SUPPORT

OEM PARTS & SERVICE GENUINE REPLACEMENT PARTS FACTORY-DIRECT SERVICE SUPPORT F A I R B A N K S M O R S E E N G I N E OEM PARTS & SERVICE GENUINE REPLACEMENT PARTS FACTORY-DIRECT SERVICE SUPPORT E N G I N E S S U P P O R T E D Opposed Piston 38 8-1/8 Engines The O-P is a proven

More information

SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY

SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY THIS PRINT COVERS CALENDAR ITEM NO. : 10.3 DIVISION: Capital Programs and Construction BRIEF DESCRIPTION: SAN FRANCISCO MUNICIPAL TRANSPORTATION AGENCY Authorizing the Director of Transportation to execute

More information

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS

POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS POWER SYSTEM OPERATION AND CONTROL YAHIA BAGHZOUZ UNIVERSITY OF NEVADA, LAS VEGAS OVERVIEW Interconnected systems Generator scheduling/dispatching Load-generation balancing Area Control Error (ACE) Load

More information

USING LEAN TO ENGAGE AND ALIGN THE ENTIRE ORGANIZATION. Didier Rabino, VP Lean Sensei Julie Garrison, HR System Director November 9, 2015

USING LEAN TO ENGAGE AND ALIGN THE ENTIRE ORGANIZATION. Didier Rabino, VP Lean Sensei Julie Garrison, HR System Director November 9, 2015 USING LEAN TO ENGAGE AND ALIGN THE ENTIRE ORGANIZATION Didier Rabino, VP Lean Sensei Julie Garrison, HR System Director November 9, 2015 ABOUT THE PRESENTERS Julie GARRISON HR System Director 1999 2006:

More information

Training Program 2018 Where Education Meets Technology

Training Program 2018 Where Education Meets Technology Training Program 2018 Where Education Meets Technology January December 2018 Training Program 2018 At Ziehm Imaging, we are strongly committed to our customers and their patients. Which means a lot more

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

High Voltage Electrical Maintenance Training

High Voltage Electrical Maintenance Training High Voltage Electrical Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq High Voltage Electrical

More information

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION

PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH

More information

Caterpillar C3600 Diesel Engines Operation Maintenance & Troubleshooting

Caterpillar C3600 Diesel Engines Operation Maintenance & Troubleshooting Caterpillar C3600 Diesel Engines Operation Maintenance & Troubleshooting +9713 7630 634 +9713 7630 634 info@hotzoneme.com www.hotzoneme.com www.hotzoneme.com Caterpillar C3600 Diesel Engines About this

More information

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012 ERCOT Overview Paul Wattles Senior Analyst, Market Design & Development Solar Energy Industries Association History of Electric Reliability Council of Texas, Inc. 1941 Utilities band together to aid war

More information

An experienced diesel mechanic, well versed with all the latest equipment for repair and maintenance operations

An experienced diesel mechanic, well versed with all the latest equipment for repair and maintenance operations Andrew Hicks CONTACT 15 Keasor Ct Laconia NH 03246 E-mail: hicks90@aol.com Phone: 603-581-5510 SUMMARY An experienced diesel mechanic, well versed with all the latest equipment for repair and maintenance

More information

Final Report. LED Streetlights Market Assessment Study

Final Report. LED Streetlights Market Assessment Study Final Report LED Streetlights Market Assessment Study October 16, 2015 Final Report LED Streetlights Market Assessment Study October 16, 2015 Funded By: Prepared By: Research Into Action, Inc. www.researchintoaction.com

More information

http://www.bls.gov/oco/ocos184.htm Electrical and Electronics Installers and Repairers Nature of the Work Training, Other Qualifications, and Advancement Employment Job Outlook Projections Data Earnings

More information

CUCAMONGA VALLEY WATER DISTRICT FLEET AND EQUIPMENT MECHANIC I/II

CUCAMONGA VALLEY WATER DISTRICT FLEET AND EQUIPMENT MECHANIC I/II FLEET AND EQUIPMENT MECHANIC I/II Class specifications are intended to present a descriptive list of the range of duties performed by employees in the class. Specifications are not intended to reflect

More information

CITY OF MINNEAPOLIS GREEN FLEET POLICY

CITY OF MINNEAPOLIS GREEN FLEET POLICY CITY OF MINNEAPOLIS GREEN FLEET POLICY TABLE OF CONTENTS I. Introduction Purpose & Objectives Oversight: The Green Fleet Team II. Establishing a Baseline for Inventory III. Implementation Strategies Optimize

More information

Computer Aided Transient Stability Analysis

Computer Aided Transient Stability Analysis Journal of Computer Science 3 (3): 149-153, 2007 ISSN 1549-3636 2007 Science Publications Corresponding Author: Computer Aided Transient Stability Analysis Nihad M. Al-Rawi, Afaneen Anwar and Ahmed Muhsin

More information

Ancillary Services & Essential Reliability Services

Ancillary Services & Essential Reliability Services Ancillary Services & Essential Reliability Services EGR 325 April 19, 2018 1 Basic Products & Ancillary Services Energy consumed by load Capacity to ensure reliability Power quality Other services? o (To

More information

Douglas County Transportation & Land Services FLEET MAINTENANCE TECHNICIAN HEAVY EQUIPMENT MECHANIC

Douglas County Transportation & Land Services FLEET MAINTENANCE TECHNICIAN HEAVY EQUIPMENT MECHANIC Douglas County Transportation & Land Services FLEET MAINTENANCE TECHNICIAN HEAVY EQUIPMENT MECHANIC 1. GENERAL FUNCTIONS OF THE JOB Perform skilled trouble diagnosis, mechanical maintenance and repair

More information

Unitil Energy Demand Response Demonstration Project Proposal October 12, 2016

Unitil Energy Demand Response Demonstration Project Proposal October 12, 2016 Unitil Energy Demand Response Demonstration Project Proposal October 12, 2016 Fitchburg Gas and Electric Light Company d/b/a Unitil ( Unitil or the Company ) indicated in the 2016-2018 Energy Efficiency

More information

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks by Georges Barbarin Executive summary Aging electrical switchgear infrastructure is a threat to the reliability of power

More information

Life cycle services for protection and control relays Full support from start to finish

Life cycle services for protection and control relays Full support from start to finish Life cycle services for protection and control relays Full support from start to finish The main purpose of the protection and control relay is to protect both human lives and equipment as well as ensure

More information

Aim: Integration of Road Infrastructure of Georgia with European Standards and effective satisfaction of the Road User needs. Annual Report 2013

Aim: Integration of Road Infrastructure of Georgia with European Standards and effective satisfaction of the Road User needs. Annual Report 2013 www.georoad.ge Annual Report 2013 Aim: Integration of Road Infrastructure of Georgia with European Standards and effective satisfaction of the Road User needs Objectives: Improvement of road safety Reduction

More information

ADB Knowledge Partnership Week. Hirokazu Yamaguchi May, 2015

ADB Knowledge Partnership Week. Hirokazu Yamaguchi May, 2015 ADB Knowledge Partnership Week Hirokazu Yamaguchi May, 2015 TEPCO AT A GLANCE 1 THE 10 ELECTRIC POWER COMPANIES BY SERVICE AREA In Japan, 10 regional privately owned and managed General Electricity Utilities

More information

2011 Special Reliability Assessment: Power Interdependency in the United States

2011 Special Reliability Assessment: Power Interdependency in the United States 2011 Special Reliability Assessment: A Primer on the Natural Gas and Electric Power Interdependency in the United States John Moura Highlights Key differences exists between gas and electricity producers

More information

Alphabetical Listing of Unified Pay Scale Positions SY Effective: July 1, 2017

Alphabetical Listing of Unified Pay Scale Positions SY Effective: July 1, 2017 Alphabetical Listing of Unified Pay Scale Positions Work Calendar Annual Hours Daily Hours Grade Exemption Status Minimum Mid Point Maximum Minimum Mid Point Maximum ADM Division Superintendent EXC Exempt

More information

Georgia Transmission Corporation Georgia Systems Operations Corporation

Georgia Transmission Corporation Georgia Systems Operations Corporation Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia

More information

Stora Enso Helping Stora Enso achieve big energy savings

Stora Enso Helping Stora Enso achieve big energy savings Stora Enso Helping Stora Enso achieve big energy savings Stora Enso, the world s biggest papermaker, has slashed carbon dioxide emissions at one of its largest mills with the help of a range of technologies

More information

ELE-CMOS-E-1987 Electrical Construction & Maintenance Manager PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS

ELE-CMOS-E-1987 Electrical Construction & Maintenance Manager PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS 104788-ELE-CMOS-E-1987 Electrical Construction & Maintenance Manager Holds a B. Sc. in Electrical Engineering and has about 29 years hands-on experience working in installation, commissioning, start-up,

More information

Draft Results and Recommendations

Draft Results and Recommendations Waco Rapid Transit Corridor (RTC) Feasibility Study Draft Results and Recommendations Chris Evilia, Director of Waco Metropolitan Planning Organization Allen Hunter, General Manager Waco Transit System

More information

Role of Energy Storage Technologies in Providing Ancillary Services, Improving Power Quality and Reliability of the Indian Grid

Role of Energy Storage Technologies in Providing Ancillary Services, Improving Power Quality and Reliability of the Indian Grid Role of Energy Storage Technologies in Providing Ancillary Services, Improving Power Quality and Reliability of the Indian Grid India need regulations for energy storage to implement grid ancillary services

More information

LIST OF OPEN TRAINING TRAINING PLANNER 2016/2017 Course location: Lagos, Abuja, Port Harcourt.

LIST OF OPEN TRAINING TRAINING PLANNER 2016/2017 Course location: Lagos, Abuja, Port Harcourt. JANUARY 2016 Credit Management and Collection of 4-6 11-15 14-27 Abuja/Lagos/PH 150,000 220,000 320,000 Receivables Developing Executive Management 4-6 11-15 14-27 Abuja/Lagos/PH 150,000 220,000 320,000

More information

Motor and Generator Training

Motor and Generator Training Motors and Generator Training Course Directory External course offering Motor and Generator Training ABB offers product training courses for motors and generators. These courses are mainly targeted to

More information

PROGRESS ON BUDGET THEMES AND PERFORMANCE METRICS RECEIVE AND FILE PROGRESS REPORT ON BUDGET THEMES AND PERFORMANCE METRICS

PROGRESS ON BUDGET THEMES AND PERFORMANCE METRICS RECEIVE AND FILE PROGRESS REPORT ON BUDGET THEMES AND PERFORMANCE METRICS 20 One Gateway Plaza Los Angeles, CA 90012-2952 213-922.2000 Tel metro. net FINANCE, BUDGET AND AUDIT COMMITTEE MARCH 20,2013 SUBJECT: ACTION: PROGRESS ON BUDGET THEMES AND PERFORMANCE METRICS RECEIVE

More information

AIRCRAFT ENGINE MECHANIC, 8602

AIRCRAFT ENGINE MECHANIC, 8602 May 2000 Federal Wage System Job Grading Standards FEDERAL WAGE SYSTEM JOB GRADING STANDARD FOR AIRCRAFT ENGINE MECHANIC, 8602 Theodore Roosevelt Building 1900 E Street, NW Washington, DC 20415-8330 Classification

More information

Combustion Turbine Outages For 2008

Combustion Turbine Outages For 2008 OCKET E 09-091 EXHIBIT - MC-7 Combustion Turbine Outages For 2008 The following outages took place at PSNH's combustion turbine units during 2008: Lost Nation CT-l Major work that was completed at Lost

More information

Maintenance Safety. Jim Seay, ICAE Chairman, IAAPA Global Safety Committee President, Premier Rides Immediate Past Chair, ASTM F24

Maintenance Safety. Jim Seay, ICAE Chairman, IAAPA Global Safety Committee President, Premier Rides Immediate Past Chair, ASTM F24 Maintenance Safety Jim Seay, ICAE Chairman, IAAPA Global Safety Committee President, Premier Rides Immediate Past Chair, ASTM F24 August 30, 2016 Welcome Back! Overview Industry Growth in Asia Challenges

More information

Back ground Founded in 1887, and has expanded rapidly Altitude about 2500 meters above MSL Now among the ten largest cities in Sub Saharan Africa

Back ground Founded in 1887, and has expanded rapidly Altitude about 2500 meters above MSL Now among the ten largest cities in Sub Saharan Africa Back ground Founded in 1887, and has expanded rapidly Altitude about 2500 meters above MSL Now among the ten largest cities in Sub Saharan Africa Annual growth rate is 3.8% By 2020 population growth would

More information

2008 Capacity/Energy Planning

2008 Capacity/Energy Planning DOCKET DE 09-091 EXHIBIT - MDC-2 2008 Capacity/Energy Planning Background PSNH retains load serving responsibility for customers who have not selected a competitive supplier. PSNH's monthly peak load for

More information

Liebherr Troubleshoot Advisor

Liebherr Troubleshoot Advisor Liebherr Troubleshoot Advisor Worldclass support everywhere, every day 2 Liebherr Troubleshoot Advisor As a global mining solutions provider, Liebherr is more than a mining equipment manufacturer. Ensuring

More information

DIESEL ENGINES MAINTENANCE PONSIBILIT Training Duration 05 days

DIESEL ENGINES MAINTENANCE PONSIBILIT Training Duration 05 days Training Title DIESEL ENGINES MAINTENANCE PONSIBILIT Training Duration 05 days Training Venue and Dates Diesel Engine Maintenance 5 days 7-11 Sept. 2014 $3,750 Dubai, UAE In any of the 5 star hotel. The

More information

Industrial, Commercial and Institutional Boilers at Area Source Facilities (Boiler GACT) Final Reconsidered Rule Requirements Summary

Industrial, Commercial and Institutional Boilers at Area Source Facilities (Boiler GACT) Final Reconsidered Rule Requirements Summary Industrial, Commercial and Institutional Boilers at Area Facilities (Boiler GACT) Final Reconsidered Rule Requirements Summary Federal Regulation NESHAP, 40 CFR 63, Subpart JJJJJJ Proposed rule published

More information

Sample Geographic Information System (GIS) Staffing and Response Time Report Virtual County Fire Department GIS Analysis

Sample Geographic Information System (GIS) Staffing and Response Time Report Virtual County Fire Department GIS Analysis Sample Geographic Information System (GIS) Staffing and Response Time Report Fire Department GIS Analysis Executive Summary This study examines predicted response times and geographic coverage areas for

More information

: Nubaria Module III - Egypt (2x250MW GE gas turbines frame 9 FA)

: Nubaria Module III - Egypt (2x250MW GE gas turbines frame 9 FA) 103956-MEC-CMOS-E-2000 Gas Turbine Maintenance Engineer Holds a B. Sc. in Mechanical Power Engineering and has over 14 years hands-on experience working in construction, maintenance, operation, commissioning

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 MOTIVATION OF THE RESEARCH Electrical Machinery is more than 100 years old. While new types of machines have emerged recently (for example stepper motor, switched reluctance

More information

BIBB COUNTY SCHOOL DISTRICT FY2019 CLASSIFIED SALARY SCHEDULE

BIBB COUNTY SCHOOL DISTRICT FY2019 CLASSIFIED SALARY SCHEDULE GR009 03 180 CROSSING GUARD $8.75 $8.84 $8.94 $9.03 $9.12 $9.21 $9.31 $9.40 $9.49 $9.58 $9.68 $9.77 $9.86 GR016 03 180 Lunchroom Monitor $10.05 $10.15 $10.25 $10.36 $10.46 $10.56 $10.67 $10.77 $10.87 $10.99

More information

Development of Relief Valve Automatic assembly technology

Development of Relief Valve Automatic assembly technology Development of Relief Valve Automatic assembly technology Technology Explanation Development of Relief Valve Automatic assembly technology TAKIGUCHI Masaki Abstract Construction machinery is equipped with

More information

Western NY Public Policy Transmission Planning Report

Western NY Public Policy Transmission Planning Report Western NY Public Policy Transmission Planning Report Dawei Fan Supervisor, Public Policy and Interregional Planning Business Issues Committee September 12, 2017 Operating Committee September 15, 2017

More information

Voith Paper Coater Service. 40 th International Meeting of Slovenian Papermakers - Bled, November 21 st, 2013

Voith Paper Coater Service. 40 th International Meeting of Slovenian Papermakers - Bled, November 21 st, 2013 Voith Paper Coater Service 40 th International Meeting of Slovenian Papermakers - Bled, November 21 st, 2013 1 Coater Service Why? Here are some common issues Major problems Wrong blade type Extensive

More information

Analysis of Turbophase System Deployment on Natural Gas Generating Stations located in Florida Reliability Coordinating Council

Analysis of Turbophase System Deployment on Natural Gas Generating Stations located in Florida Reliability Coordinating Council Analysis of Turbophase System Deployment on Natural Gas Generating Stations located in Florida Reliability Coordinating Council - BY ENERGY EXEMPLAR 1 Page Table of Contents Table of Figures... 2 About

More information

B. HOLMQVIST Nuclear Fuel Division, ABB Atom AB, Vasteras, Sweden

B. HOLMQVIST Nuclear Fuel Division, ABB Atom AB, Vasteras, Sweden I Iflllll IPIBM1I IHtl!!!! Blini Vllll! «! all REDUCTION OF COST OF POOR QUALITY IN NUCLEAR FUEL MANUFACTURING XA0055764 B. HOLMQVIST Nuclear Fuel Division, ABB Atom AB, Vasteras, Sweden Abstract Within

More information

The Role of Electricity Storage on the Grid each location requires different requirements

The Role of Electricity Storage on the Grid each location requires different requirements Functional Requirements for Energy on the Utility Grid EPRI Renewable Council Meeting Bill Steeley Senior Project Manager Dan Rastler Program Manager April 5-6, 2011 The Role of Electricity on the Grid

More information

MTU Maintenance Berlin-Brandenburg An MTU Aero Engines Company. Excellent service for industrial gas turbines. GE LM2500, LM5000 and LM6000

MTU Maintenance Berlin-Brandenburg An MTU Aero Engines Company. Excellent service for industrial gas turbines. GE LM2500, LM5000 and LM6000 MTU Maintenance Berlin-Brandenburg An MTU Aero Engines Company Excellent service for industrial gas turbines GE LM2500, LM5000 and LM6000 Compelling capabilities Experience MTU Maintenance Berlin-Brandenburg

More information

E-Mobility Trainings. Handling electric drives safely. TÜV SÜD Akademie GmbH

E-Mobility Trainings. Handling electric drives safely. TÜV SÜD Akademie GmbH E-Mobility Trainings Handling electric drives safely TÜV SÜD Akademie GmbH 01 02 E-Mobility Trainings Handling electric drives safely Electric vehicle drives are gaining ground in both hybrid and pure

More information