INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

Size: px
Start display at page:

Download "INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC"

Transcription

1 INSTRUCTIONS GEI-98305C D-C UNDERVOLTAGE RELAY Type NGV18A GENERAL ELECTRIC

2 2 Fig ( ) NOV18A Relay Removed From Case (Rear View) GEI D-C Undervoltage Relay Type NOV Fig. 1 ( ) NGVI&L e1ey Removed From Case (Front Viev) RI

3 specifically to be used to monitor the d-c charging undervoltage relay with extra high dropout designed The NGV18A relay is an instantaneous d-c DESCRIPTION The resistors are supplied as a and each relay is calibrated with TABLE A listed on Fig. 3. its resistors. part of the relay 3 but no such assurance is given with respect to local codes and ordinances because they vary greatly. RATINGS NGV18A relay coil ratings and the resistors are delay dropout HFA65D relay which provides a time Figure 5 shows the NGV18A used with a time This arrangement will sound an alarm not only when a prolonged d-c undervoltage occurs but also when delay of about two seconds and at the same time voltage to decay. fully charged open circuit voltage of the battery. Table A gives detailed information on the either a lead-acid or a nickel-cadmium battery, it is suggested that the dropout be set about 98% of the For example, the fully charged open circuit voltage battery charger output. the relay must pickup at the lowest acceptable the a-c power is lost without waiting for the battery the suggested NGV18A setting about 121 volts. Also of a 60 cell lead-acid battery will be 123 volts and When the NGV18A relay is used to monitor monitors the a-c supply to the battery charger. * The inductive rating is based on the indictive of an To the extent required the products described herein meet applicable ANSI, IEEE and NEMA standards; the purchasers purposes, the matter should be referred to the General Slectric Company. further information be desired or should particular problems arise which are not covered sufficiently for every possible contingency to be met in connection with installation, operation or maintenance. Should These instructions do not purport to cover all details or variations in equipment nor to provide for BURDEN in Table A. OPERATING PRINCIPLES The NGV18A is a hinged armature type relay which operates by electromagnetic attraction. The The NGV1SA relay pick up can be adjusted by The resistances of the d-c windings are given means of the variable resistor Ri. The relay will droput feature results from the characteristic of pick up at 105% or less of dropout voltage. the zener diode regulator. average tripping coil. contacts are opened and closed by the movement spring and operated by the D.C. solenoid. The high of an armature which is restrained by an opening CHARACTERISTICS delay auxiliary relay to prevent false alarms. alarm. Since some operating conditions may temporarily lower the d-c voltage, It is suggested station battery undervoltage and to provide an Usually the NGV18A relay is used to detect Because the NGV18A picks up at 105% of drop high-speed, extra high dropout, d-c relay Is re quired. that the NGV18A be used in conjunction with a time A-C VOLTS D-C VOLTS AMPS INDUCTWE* NON-INDUCTIVE APPLICATION out voltage or less, It finds application wherever a TABLE B INTERRUPTING RATINGS target. It is packaged in a S-i drawout case, for mally open and one normally closed contact but no In series with the operating coil and the fixed and telephone-type voltage unit with a zener regulator The relay undervoltage element consists of a this supply falls. either flush or surface mounting. It is normally auxiliary relay. adjustable resistors. Also the relay has one nor used in conjunction with one time delay dropout seconds. ratings. These contacts will make and carry three amperes continuously or 30 amperes for two Table B gives the relay contact interrupting NGV18A NGVL8A I 125 NGV18A OHMS RELAY MODEL RESISTANCE VOLTAGE D.C. COIL D.C. supply for a station battery to sound an alarm if TYPE NGV18A D.C UNDERVOLTAGE RELAY

4 4 by a test plug. The cover, which is attached to the Relay Type NGV18A (Front View) * 0 connected by removing the connection plug which when desired. To do this, the relay Is first die assembly which is latched into a drawout case whes completes the electrical connections between the case block and the cradle block. To test the relay front bf the relay case, contains an interlock arm 0 lock circuits. CONSTRUCTION in its case this connection block can be replaced GEI D-C Undervoltage Type NGV18A The relay components are mounted in a cradle the relay is in operation but It can be easily removed ment. These relays, when not included as part of a from rough handling is evident, file a damage claim control panel, will be shipped in cartons designed promptly notify the nearest General Electric Apparatus Sales Office. at once with the transportation company and tained in transit. If injury or damage resulting receipt of a relay, examine it for any damage sus to protect them against damage. Immediately upon RECEIVING, HANDLING AND STORAGE 5+ I2NGV1HA1 OOO 12GVThA2 OOO v -!O6T EICEP Fig. 3 (D165A7720-3) Internal Connections, (C pressure to prevent the opening of important inter makes contact as Indicated in FIg. 4 with adequate it is especially Important that the auxiliary brush with shorting bars (see Fig. 3). On these circuits, adequate overlap when the connecting plug is with drawn or inserted. Some circuits are equipped auxiliary brush, as shown in Fig. 4, to provide Fig. 6. Every circuit In the drawout case has an included. For outilne and drilling dimensions, see relay order to insure that proper hardware will be However, panel thickness must be indicated on the The relay case Is suitable for either semiflush or surface mounting on all panels up to 2 inches thick and appropriate hardware is available. which prevents the cover from being replaced until the connection plugs have been inserted. indicates revision TESTS, the relay is held In storage before shipment to the job site, it is recommended that the visual If alter the performance of the ACCEPTANCE INSTALLATION PROCEDURE before the residual screw strikes the shim. With closed contacts should be.ol0 to.020. The wipe on each normally open contact should and the pole piece and operating the armature by the armature picked up, the gap on jhe normally hand. The normally open contacts should make inserting a shtm between the residual screw be approxiniit*iv.005. This can be checked by mately.005. contact by deflecting the station contact member towards the frame. Wipe should be approxi Observe the wipe on each normally closed contact should have a gap of.015 or more. 2. WIth the relay de-energized each nqrmally open parts are free from friction or binds. hand and allow it to reset to insure that all 1. Operate the armature of the voltage unit by adjustments be checked; It is recommended that thefollowingmechanical * MECHANICAL INSPECTION damage, and that all screws are tight. visual inspection that there are no broken or cracked molded parts or other signs of physical Remove the relay from its case and check by the relay received agree with the requisition. Check the nameplate stamping to insure that the model number, rating and calibration range of VISUAL INSPECTION Insure that no damage has been sustained in ship Immediately upon receipt of the relay an in spection and acceptance test should be made to ACCEPTANCE TESTS of the relay. cover is removed and cause trouble in the operation outside of the case may find its way Inside when the cartons in a place that is free from moisture, dust ing the relay. If the relays are not to be Installed and metallic chips. Foreign matter collected on the Reasonable care should be exercised in unpack immediately, they should be stored in their original

5 Also the relay should be set at the dropout the lowest acceptable battery charger outputvoltage. The ratio of pickup to dropout can be changed by value to be used and it should be checked. When droput is set, check that the relay will pick up at in its permanent location and preheated. After the making this check, the relay should be installed stallation. setting of the variable resistor Ri, (see Fig. 3.) on ACCEPTANCE TESTS be repeated before in and mechanical inspection described in the section D-C Undervoltage Relay Type NGV GEI The pickup voltage is adjusted by changing the observed in restoring them. to be out of limits, the following points should be points described in the previous sections are found If any of the mechanical or electrical check SERVICING. sary to make adjustments, refer to the section on age. A voltmeter with at least 1000 ohms per volt should be used for making the test. If it Is neces voltage should be 106% or less of the dropout volt rate and check the pickup and dropout. The pickup Set the battery charger at Its lowest charging tarnishing or corrosion. Examine the contact surfaces for signs of Check that the contact gap andwtpe values agree with those given in the ectien under ACCEPTANCE TESTS. or tendency to bind. reset to make sure thatthere is no excessive friction Manually operate the armature and allow it to MECHANICAL CIECKS Showing P sition of Auxiliary Brush and Shorting Bar Fig. 4 ( ) Cross Section of Drawout Case THE TERMINAL BLOCK TRAVELS /4 INCH BEFORE ENGAGING THE MAIN BRUSH ON NOTE. AFTER ENRAGING AUXILIARY BRUSH CONNECTING PLUG SHORTING BAR AUXILIARY BRUSHJ TERMILL BLOCK select the test interval best suited to his individual requirements, it is suggested that the following will vary depending upon environment, type of relay recognized that the interval between periodic checks that a periodic test program be followed, It Is points be checked at an Interval of from one to two years. the operation of a power system it is important and the user s experience with periodic testing. Until the user has accumulated enough experience to In view of the vital role of protective relays In MAINTENANCE PERIODIC CHECKS AND ROUTINE 5 for Type NGV18A Relay with Type HFA65D for Low Battery Indicator Fig. 5 (01781o9003 (2])Exrernal Connection Diagrwn Th eoooo 111 NO 27 NG11 wr,.e. -c : F 10 Cl 0-4) OFC0700N. IOU)FC FOR R Olf fir N4F+A.LLY N0 A1._Y 01OL7i d IN 1 C oo roost: 104 f 1L1 t1l 1Z 11L j Ill 147V number on which the relay was furnished. possible, give the General Electric requisition wanted, and give complete nameplate data. If pany, specify quantity required, name of the part nearest Sales Office of the General Electric Com When ordering renewal parts, address the damaged. prompt replacement of any that are worn, broken or renewal parts be carried in stock to enable the It is recommended that sufficient quantities of RENEWAL PARTS tool as described above can be obtained from the paper or cloth to clean relay contacts. A burnishing superfine file which removes corroded material bility of the tool insures the cleaning of the actual roughened strip of flexible metal, resembling a quickly without scratching the surface. The flexi ing tool should be used. This consists of an etched For cleaning relay contacts, a flexible burnish points of contact. Never use knives, files, abrasive factory. voltage unit. The minimum gap must be inch between armature and pole face. turning the residual screw of the telephone-type SERVICING

6 tnches 5/16 18 STUD CASE L 168MM PANEL DRILLING (TYPICAL).500 CU ThU T PANEL LOCATION SEMI FLUSH SURFACE PANEL DRILLING MM ;--- SURFACE MTG. CUTOUT MAY REPLACE 1 09MM.1,156 (2) 5/16 18 STUDS 6. * Indicates revision LYICAL DIM. 232MM 4 HOLES 6MM GLASS 29MM BACK VIEW 144MM FUR SEMI-FLUSH MOUNTING FRONT VIEW 12MM FOR SURFACE MOUNTING FRONT VIEW * Fig. 6 ( [8]) Outline and Panel Drilling Dimensions for Type NGV18A Relay 10 HOLES P3/4 DRILL DRiLLED HOLES 1/4 DRILL STUD NUMBER ING 29MM 37MM MM 5MM PANEL 19MM MM VIEW FOR GEI DC Undervoltage Re ay Type NGV

7

8 GE Power Management 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) Fax: (905) wwwgeindustrial.com/pm

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS g INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS Manual Part Number: GEI-83964H Copyright 2000 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905)

More information

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 GEK-41931 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 TABLE I 3

More information

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC INSTRUCTIONS GEI-38974A Supersedes GEI 38974 INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC 2 DESCRIPTION APPLICATION MOUNTING SERVICING RENEWAL PARTS 10 PICKUP AND RESET ELECTRICAL TESTS ELECTRICAL

More information

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY TYPE HFA151 GE Protection and Control 25 Great Valley Parkway Malvern, PA 19355-1337 GEK 45484 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 RATINGS 3

More information

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC GENERALS ELECTRIC AUILIARV P A GENERAL ELECTRIC HGA11A, C, H, J, K, P, S, T, V, W, X TYPES INSTANTANEOUS AUXILIARY RELAY 0 INSTRUCT IONS GEH-1 793J 2 RENEWAL PARTS 8 CONTACT CLEANING 8 PERIODIC CHECKS

More information

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management 0 INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS Manual Part Number: GEI-83964H Copyright 2000 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:

More information

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC GENERAL ELECTRIC AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C INSTRUCTION S GEK 7354J EK 73 54 FIG. 1 (838617) RELAY TYPE HA16fl TN CASE (FRONT VIEW) FIG. 2 (8938618) RELAY TYPE HAA16B REMOVCr) FPOM C?S

More information

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F INSTRUCTIONS GEH-1768G IAV5 411 IAV5 511 IAV5 5J IAV54F IAV55F IAV54E IAV55C TYPES: UNDERVOL TAGE RELAYS 25 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control GEIL 1768 RESET B LiTTON

More information

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A. INSTRUCTIONS and hjs52a Types IJS51A J CLO%NG - -* RELAY GENERALtEL1CTRjC SYNCHRONISM-CHECK RELAYS 205 Great Valley Parkway Malvern, PA 19355-07 15 GE Meter and Control GEl! 1791? INSTALLATION PROCEDURE

More information

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION PHILAO[LPHA. PA GENERAL ELECTRIC POWER SYSTEMS MANAGEMENT DEPARTMENT latter should be referred to the General Electric Co.pany. probli erlie which are not covered sufficiently for the purchasers purpose.,

More information

INSTANTANEOUS UNDERVOLTAGE RELAY

INSTANTANEOUS UNDERVOLTAGE RELAY PHILADELPHIA, PA. GENERALS ELECTRIC POWER SYSTEMS MANAGEMENT DEPARTMENT PJV17A UNDERVOLTAGE RELAY INSTANTANEOUS GEI-83951 INSTRUCTIONS SUPR5EDES GEI-23986 2 MOVING CONTACT CONTACT STATIONARY COIL Fig.

More information

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

Type CRN-1 Reverse Power Relay 50 and 60 Hertz ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-251.2P Effective: June 1991 Supersedes I.L. 41-251.2N Dated April 1988 ( )Denotes Change

More information

THERMAL OVER CURRENT RELAY

THERMAL OVER CURRENT RELAY INSTRUCTIONS THERMAL OVER CURRENT RELAY Type TMCllA GEI-28826A GENERAL. ELECTRIC www. ElectricalPartManuals. com com GEI-28826A 2 Model Frequency 12TMC11A51A 50/60 12TMC11A52A 50/60 12TMC11A53A 50j60 12TMC11A54A

More information

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction

More information

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View 41-503.21A TYPE KF Front View Rear View Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) 2 TYPE KF 41-503.21A lower pin bearing, which is mounted on the frame, with respect to the

More information

P. Sub 4 184A404. Sub 3 876A220

P. Sub 4 184A404. Sub 3 876A220 Figure 1. Type CRN-1 Relay Without Case. 1 = Directional Unit (D). 2 = Timer Unit (T). 3 = Indicating Contactor Switch (ICS). Sub 4 184A404 Sub 3 876A220 Figure 2. Internal Schematic of the Single Trip

More information

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing

More information

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES INSTRUCTIONS GE I -288021 Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES PJV11J PJV11AL PJV11AZ PJV11L PJV1IAM PJV1IBF PJV11N PJV11AN PJV12B PJV11AF PJV11AR PJV12C PJV11AH PJV11AS PJV14B PJV11AJ

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay 41-106E Type CO-4 Step-Time Overcurrent Relay A core screw accessible from the top of the switch provides the adjustable pickup range. The IIT contacts are connected in the trip circuit to trip instantaneously.

More information

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits. HA Hinged Armature Auxiliary Hinged armature auxiliary relay to perform auxiliary functions in and circuits. eatures and Benefits Molded case with 4 mounting options Drawout case available Applications

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC GENERAL ELECTRIC TYPE HGA17A TO F, H, M, R, S, T DC AUXILIARY RELAYS INSTRUCTIONS GEI-10190L RATINGS 3 CHARACTERISTICS a DESCRIPTION 3 CONTENTS PAGE BURDENS 4 CONSTRUCTION 4 LOCATION AND MOUNTING S MAINTENANCE

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES: 205 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control HFC21B, HFC22B, HFC23C TYPES: INSTANTANEOUS OVERCURRENT RELAYS INSTRUCTIONS GEK-49826D GEK-49826 CONTENTS PAGE DESCRIPTION APPLICATION

More information

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control INSTRUCTIONS GEK-341 24G TYPES CFD22A AND CFD22B HIGH-SPEED DIFFERENTIAL RELAYS 205 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control GEK-341 24 CONTENTS PAGE APPLICATION 3 RATINGS

More information

4.0 OPERATION Type ITH-T Relay

4.0 OPERATION Type ITH-T Relay 41-771.2 Type ITH-T Relay 3.3 OPERATION INDICATOR This operation indicator is a small solenoid coil connected in the trip circuit. When the coil is energized a spring-restrained armature releases the white

More information

B CW POWER RELAY

B CW POWER RELAY 41-241.31B CW POWER RELAY nected in such a way that current, (I A ), leads voltage, (V BA ), by 150 degrees when the motor is operating at unity power factor. Loss of excitation to the motor causes a large

More information

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION ABB Instruction Leaflet 41-163.2B Effective: January 1977 Supersedes I.L. 41-137.3A, Dated September 1974 ( ) Denotes Change Since Previous Issue Type CRQ Directional Negative Sequence Relay for Ground

More information

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection GEK 070B GE Power Management DIAC DIFC DSFC Digital Self Powered Overcurrent Protection *(RZHU0DQDJHPHQW $QGHUVRQ$YHQXH 0DUNKDPQWDULR &DQDGD/% ZZZJHFRPLQGV\VSP TABLE OF CONTENTS INTRODUCTION... PRODUCT

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC IN ST RU CT ION S GE K 45487 D INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 J. GENERAL ELECTRIC DESCRIPTION 3 APPLICATION 3 PAGE CONTENTS 2 FIG. 1 (842734) COVER RENEWAL PARTS MECHANICAL ADJUSTMENTS S CONTACT

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

GEK 65513D INSTRUCTIONS AUXILIARY LOCKOUT RELAY HAND RESET WITH TARGET. GE Meter and Control 205 Great Valley Parkway Malvern, PA

GEK 65513D INSTRUCTIONS AUXILIARY LOCKOUT RELAY HAND RESET WITH TARGET. GE Meter and Control 205 Great Valley Parkway Malvern, PA GEK 65513D INSTRUCTIONS AUXILIARY LOCKOUT RELAY HAND RESET WITH TARGET TYPE FISA11 GE Meter and Control 205 Great Valley Parkway Malvern, PA 19355-07 15 GEK-65513 CONTENTS PAGE DESCRIPTION 3 TABLE I -

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G GLK 34117G INSTRUCTIONS POLYPHASE POWER DIRECTIONAL RELAY FOR ANTI I4OTORING PROTECTION TYPE GGP53C GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 PAGE CONTENTS 2 TOP UNIT 10

More information

Installation Sheet January, 2016 Supersedes June 2013

Installation Sheet January, 2016 Supersedes June 2013 s Installation Sheet January, 016 Supersedes June 01 E87010-A0105-T00-A6-CLM0 Lighting and Heating Contactor 60, 100, 00 Amp,, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator GE Consumer & Industrial Electrical Distribution Operation & Maintenance Manual GEK-99986 Catalog # WPEGRRLV 115 VAC, 60/50 Hz Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking

More information

[ These instruction: do not purport to cover all details or variations eqiipment GENERAL ELECTR INSTRUCTIONS. Insert Book t Ci[ V.

[ These instruction: do not purport to cover all details or variations eqiipment GENERAL ELECTR INSTRUCTIONS. Insert Book t Ci[ V. mounted. surface for this relay. TYPE NGA Insert Book t Ci[ V.-12 : PHILADELPHIA, PA. GENERAL ELECTR POWER SYSTEMS MANAGEMENT DEPARTMENT probls arias which ru not covered sufficiently for he pu h.sers

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Type SOQ Negative Sequence Time Overcurrent Relay

Type SOQ Negative Sequence Time Overcurrent Relay ABB Power T&D Company Inc. Power Automation & Protection Division Coral Springs, FL Allentown, PA April 1998 Supersedes DB dated August 1991 Mailed to: E,D, C/41-100B For Protection of Rotating Machinery

More information

INSTANTANEOUS CURRENT RELAYS

INSTANTANEOUS CURRENT RELAYS Handbook Reference 76 Supersedes GEH-179 B GENERAL ELECTRIC Type PJC INSTANTANEOUS CURRENT RELAYS GEH-179 C INSTRUCTIONS APPLICATION 3 INTRODUCTION. 3 PAGE out no -icc assurance is given with respect to

More information

41-747G. Figure 1: Type DGF Relay without case (Photo)

41-747G. Figure 1: Type DGF Relay without case (Photo) Figure 1: Type DGF Relay without case (Photo) 2 183A113 EDSK 205342 Figure 2: Internal Schematic of the Type DGF Relay in the FT21 Case. When a ground appears in the generator field, the dc milliammeter

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

Operation and Maintenance Manual

Operation and Maintenance Manual DEH-41482 GE Energy Industrial Solutions Low Voltage Switchgear Remote Racking Operator For AKR Circuit Breakers Cat. # AKREGRR 115 VAC, 60/50 Hertz Operation and Maintenance Manual TABLE OF CONTENTS Section

More information

GENERALS ELECTRIC INSTRUCTIONS. GEK Insert Booklet- GEI SYNCHRONISM CHECK RELAY IJS52F INTRODUCTION

GENERALS ELECTRIC INSTRUCTIONS. GEK Insert Booklet- GEI SYNCHRONISM CHECK RELAY IJS52F INTRODUCTION INSTRUCTIONS GEK- 26469 Insert Booklet- GEI-982 SYNCHRONISM CHECK RELAY IJS52F INTRODUCTION These instructions are a supplement to instruction book GEI-982 which is included in this book. The com bination

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3. 41-348.1H Type SA-1 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are

More information

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC Supersedes GEK45344 GEK.45344 A GENERAL ELECTRIC TYPE IAC66S TIME OVERCURRENT RELAY INSTRUCT ION S GEK4 5344 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 RATINGS 3 INDUCTION UNIT 3 TABLE I 3 TABLE II 4 STATIC

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet Effective: October 1999 Supersedes I.L. 41-133R, Dated August 1998 ( ) Denotes Changed Since

More information

INSTRUCTIONS GEH 2056F POWER RELAYS. Types ICW51A ICW52A ICW52B GENERALJ ELECTRIC

INSTRUCTIONS GEH 2056F POWER RELAYS. Types ICW51A ICW52A ICW52B GENERALJ ELECTRIC GENERALJ ELECTRIC ICW51A ICW52B ICW52A Types POWER RELAYS GEH 2056F INSTRUCTIONS CONTENTS DESCRIPTION 3 APPLICATION 3 RATINGS 4 CONTACTS 4 CHARACTERISTICS 5 OPERATING PRINCIPLES 5 PICK-UP 5 OPERATING AND

More information

UNION SERVICE SPECIFICATION NUMBER SU A

UNION SERVICE SPECIFICATION NUMBER SU A UNION SERVICE SPECIFICATION NUMBER SU-1862 -A UNION SWITCH & SIGNJU,.,... SWISSVALE, PAe DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY DN-10 TRAIN CONTROL SPECIAL SLOW DROP-AWAY RELAYS ********************

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC 12IAC77S(-)A INTRODUCTION

INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC 12IAC77S(-)A INTRODUCTION GEK- 27936A INSERT BOOKLET GEH-2059 INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC MODEL 12IAC77S(-)A INTRODUCTION This supplements in conjunction with GEH-2059, forms the instructions for relay model 121AC77S(-)A.

More information

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT 41-348.11C SA-1 Generator Differential Relay - Class 1E 2.0 CONSTRUCTION The type SA-1 relay consists of: Restraint Circuit Sensing Circuit Trip Circuit Surge Protection Circuit Operating Circuit Amplifier

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

PROCESS ELECTRONICS CORPORATION

PROCESS ELECTRONICS CORPORATION MINIVERTER MANUAL PROCESS ELECTRONICS CORPORATION 100 BRICKYARD ROAD MOUNT HOLLY, NORTH CAROLINA 28120 TELEPHONE (800) 421-9107 FAX (704) 827-9595 SALES@PECRECTIFIER.COM WWW.PECRECTIFIER.COM SOLID STATE

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

BBC. Renewal Parts. I-T-E Low-Voltage Power Circuit Breakers

BBC. Renewal Parts. I-T-E Low-Voltage Power Circuit Breakers BBC BROWN BOVERI RP 6..2.8-2C Renewal Parts I-T-E Low-Voltage Power Circuit Breakers Type K-000, 4000, 0008, and 40008 Stationary and Drawout Mounted 000 and 4000 Amperes 600 Volts RP 6..2.8-2 Page 2 Table

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

www. ElectricalPartManuals. com Operator s Manual

www. ElectricalPartManuals. com Operator s Manual Operator s Manual TABLE OF CONTENTS section-page... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness... 1-2 Engine Starting Contacts... 1-2 Functional Test... 1-3, 1-4, 1-5, 1-6

More information

GEK 65602B INSTRUCTIONS RECLOSING RELAYS TYPES HGA18M, HGA18N. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA

GEK 65602B INSTRUCTIONS RECLOSING RELAYS TYPES HGA18M, HGA18N. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA INSTRUCTIONS GEK 65602B TYPES HGA18M, HGA18N RECLOSING RELAYS Malvern, PA 19355-1337 205 Great Valley Parkway GE Protection and Control GEK-65 602 CON TENTS PAGE DESCRIPTION 3 APPLICATION 4 GENERAL CONSIDERATIONS

More information

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual Series 386 Electrically Operated Non Automatic Switches J design 600 amps DANGER is used in this manual to warn of high voltages capable of causing shock, burns, or death. WARNINGisusedinthismanualtowarn

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series ATS Automatic Transfer Switches H design 600 through 1200 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and

More information

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC. NSTRUCTONS MAGNETC TME RELAYS *C2820-054 *Also identified with prefix CR instead of C. GENERAL. ELECTRC GEH-85F NTRODUCTON The CR2820-054 relay is a d-e operated relay. t may be applied as an instantaneous

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

N1233 Series Troubleshooting Guide for N Alternator

N1233 Series Troubleshooting Guide for N Alternator N1233 Series Troubleshooting Guide for N1233-2 Alternator Hazard Definitions These terms are used to bring attention to presence of hazards of various risk levels or to important information concerning

More information

INSTRUCTIONS GEH-1789B GEH-1789A SUPERSEDES BALANCED-CURRENT RELAYS. Types. IJCSlB IJCSlC IJC53A. www. ElectricalPartManuals. com. GENERAL f) ELECTRIC

INSTRUCTIONS GEH-1789B GEH-1789A SUPERSEDES BALANCED-CURRENT RELAYS. Types. IJCSlB IJCSlC IJC53A. www. ElectricalPartManuals. com. GENERAL f) ELECTRIC NSTRUCTONS GEH-1789B SUPERSEDES BALANCED-CURRENT RELAYS Types JCSlB JCSlC JC53A GENERAL f) ELECTRC GEH-1789A Balanced-Current Relays Type JC 3 5? - 6 J 1\JUMBE!NG OF STUDS (FRONT VEW) 7 5-\t--z:r-i rz%._,

More information

GEI-90802E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEI-90802E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D. GE Protection and Control 205 Great Valley Parkway Malvern, PA E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 CONTENTS INTRODUCTION 3 APPLICATION 3 RATINGS 4 CHARACTERISTICS 4 Operating

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches, 600 1200 amps 600---1000 amp. sizes An experienced licensed electrician must install the ADTS. DANGER is used in this manual to

More information

GP/GPA GROUND FAULT PROTECTION

GP/GPA GROUND FAULT PROTECTION GP/GPA GROUND FAULT PROTECTION GROUND FAULT PROTECTION C-220EM Instruction Manual, June 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial and commercial customers with

More information

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No. September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds

More information

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label. Operator s Manual 7000 Series ACTS Automatic Closed Transition es 150 through 4000 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness...

More information

Electropneumatic Timing Relays Series 7000 Industrial

Electropneumatic Timing Relays Series 7000 Industrial DESIGN FEATURES Available in On-Delay, True Off-Delay, and On/Off-Delay. Timing from 0.1 seconds to 60 minutes, fully calibrated in linear increments. Oversize time-calibrated adjustment knobs, serrated

More information

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps Operator s Manual 7000 Series ATS Automatic Switches 600 through 1200 amps 600---1000 amp. size An experienced licensed electrician must install the ATS. DANGER is used in this manual to warn of high voltages

More information

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

section-page Table 1. Transfer switching device ratings. Conditional short circuit current Operator s Manual 7000 Series ATS Automatic Transfer Switching Equipment D design 30 through 200 amperes TABLE OF CONTENTS section-page INSTALLATION... 1-1 Enclosures and Mounting... 1-1 Power Connections...

More information

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING the voltage unit contacts, this effect is negligible. 3.2 Trip Circuit The main contacts will close 30 amperes at 250 volts dc and the seal-in contacts of the indicating contactor switch (ICS) will carry

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label. Operator s Manual 7000 Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes TABLE OF CONTENTS Note: Refer to the outline and wiring drawings provided with your 7000 Series

More information

Model HEA Multicontact Auxiliary

Model HEA Multicontact Auxiliary GE Grid Solutions Model HEA Multicontact Auxiliary Features and Benefits Electrically separate outputs available Various shaft lengths available Locks equipment out of service Applications Contact multiplication

More information

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches 150 through 4000 amp. Note: Refer to the outline and wiring drawings provided with your 7000 Series ADTS for all installation and

More information

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide Hazard Definitions These terms are used to bring attention to presence of hazards of various risk levels or to important information

More information

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS TJ STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS page DESCRIPTION AND OPERATION STARTER MOTOR... 2 STARTER RELAY... 3 STARTING SYSTEM... 1 DIAGNOSIS AND TESTING STARTER MOTOR... 8 STARTER MOTOR NOISE

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series ACTS Automatic Closed Transition Transfer Switches E design 150 400A, F design 600 800A, G design 1000 4000A, F design 3000 4000A, DANGER is used in this manual to warn of

More information

GEK 41880D INSTRUCTIONS MACHINE FIELD GROUND DETECTOR RELAY TYPE PJG12B. GE Protection and Control. 205 Great Valley Parkway Malvern, PA

GEK 41880D INSTRUCTIONS MACHINE FIELD GROUND DETECTOR RELAY TYPE PJG12B. GE Protection and Control. 205 Great Valley Parkway Malvern, PA 25 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control TYPE PJG12B MACHINE FIELD GROUND DETECTOR RELAY INSTRUCTIONS GEK 4188D GEK-41 88 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 RATINGS

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Vibrating Feeders Models: F-T01-A and DF-T01-A Contents Page

More information

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES BELL SYSTEM Plant Series PRACTICES SECTION 040-811-701 Issue 1, June, 1962 AT&TCo Standard RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION I I!

More information