INSTANTANEOUS UNDERVOLTAGE RELAY

Size: px
Start display at page:

Download "INSTANTANEOUS UNDERVOLTAGE RELAY"

Transcription

1 PHILADELPHIA, PA. GENERALS ELECTRIC POWER SYSTEMS MANAGEMENT DEPARTMENT PJV17A UNDERVOLTAGE RELAY INSTANTANEOUS GEI INSTRUCTIONS SUPR5EDES GEI-23986

2 2 MOVING CONTACT CONTACT STATIONARY COIL Fig. 2 ( ) Two Stick Cage Resistor Typical of the External Resistor Used with PJYI7A Relays -4 Fig. I ( ) PJVI7A Reley with Cover emd Hameplate Removed 0 0 C, a, AR MATURE ADJUSTABLE 1 OPERATIN Ci FRAME MAGNET GEI liistant.aneous Voltage Relay Type PJV TUBE CALI5RATION a > a C

3 INSTANTANEOUS UNDERVOLTAGE RELAY TYPE PJVII7A DESCRIPTI ON The PJV17A relay is an instantaneous d-c undervoltage relay with extra high dropout designed specifically to be used to monitor the d-c charging supply for a station battery and to sound an alarm if this supply falls. The relay is equipped with both an a-c and d-c coil with external resistors for each. Also the relay has one normally open and one normally closed contact but no target. It is packaged in a surface mounted, back connected molded case, and is normally used In conjunction with one time delay drop-out auxiliary relay. IARULAF ION OF EXTERNAL RESISTOR VAWES REQO FOR F J dll* UCCIRCItIT AC circjjit noel VOLTS - ANT MI WII l2pv PJVI PJy17A3 I2PJV17A4 12PJV1708 z --ï - -- o/5 or I APPLICATION Because the PJV17A drops out at 95, ot pickup voltage or more, it finds appitca tion wherever a high-speed, extra high dropout, d-c relay is required. It should be noted that although the PJV17A relay is applied to detect undervoltage, the relay requires an a-c supply in addition to the d-r voltage being measured. Usually the PJV17A relay s used to detect station battery undervoltage and to provide an alarm. Since some operating conditions may temporarily lower the d-c voltage, it is suggested that the PJV17A be used In conjunction with a time delay dropout auxiliary relay to prevent false alarms. 12 PJ Vi? Al? : /to / /60 50/60 I2PJV17A19 I2PJVI? / I2PJVI7A21 soio / PJ V 17* JV17p PJV17A SJV17A G PJV17A / PJV17A S S2PJV17A / iaju?suu 1200 Fig. 3 shows the PJVI7A used in con junction with a time delay dropout HGAB5D relay which provider a time delay of about two seconds and at the same time monttors the a-c supply to the battery charger. This arrangement wiil sound an alarm not only when a prolonged d-c undervoltage occurs but also when the a-c power is lost without waiting for the battery voltage to decay. When the PJV17A relay is used to monitor either a lead-acid or a nickelcadmium battery, it is suggested that the dropout be set about 98% of the fully charged open circuit voltage of the battery. For example, the fully charged open circuit voltage of a 80 cell lead-acid battery will be 123 volts and the suggested PJVIIA setting about 121 volts. Also the relay must pick up at the lowest acceptable battery charger output. RATINGS TAILE A Table A gives detailed Information on the PJV17A relay coil ratings and the ex ternal resistors which are used with these coils. The external resistors are supplied as a part of the relay and each relay is calibrated with Its resistors. Table B gives the relay contact inter rupting ratings. These contacts will make and carry five amperes continuously or 30 amperes for two seconds. INTERRUPTING RATINGS TABLE B A-C VOLTS AMPS INDUCTIVE NON-INDtJCTWE D-C VOLTS I Thea. kissructoni do not pwport to cover all detail, or variation, rn equipment nor to provid, fo, every possible I contingency to be met In connection with a#ation, operation or maintenance. Should further information be deair.d or should particular problems aria, which are not covered sufficiently for the purchaser s purpoa.., the maher should referred to hi General Electric Company. L6

4 4 in the side of the calibrating tube allow in unpacking the relay. H the relays are except they are mounted below the moving contact and the backstop arm Is omitted. from rough handing is evident, file a dam General Electric Apparatus Sales Office. Reasonable care should be exercised tive dropout point. upward as the armature is drawn upward when the relay is picked up. The action of a sizeable air gap In the magnetic circuit from limiting the armature travel to retain solenoid. The high dropout feature results rod which carries the moving contacts brating tube. This adjustable armature is erated direduy by the plunger (armature) CONSTRUCTION are given in Table A. BURDEN ture on its threaded haf I. The relay will changing the vertical position of the arma drop out at 95% or more of the pickup volt by an amrature drawn up vertically into a tion. The contacts are opened and closed the a c coil also helps to establigh a posi age at any setting. winding is approximately 4OVA. which operates by electromagnetic attrac The PJV17A Is a plunger-type relay The volt-ampere burden of the a-c mounted on the threaded portion of a plunger The stationary contacts, magnet frame The normally closed fixed contacts are company and promptly notify the nearest age claim at once with the transportation in transit. If Injury or damage resulting relay, examine it for any damage sustained damage. Immediately upon receipt of a relay by means of two thumb screws. See cartons designed to protect them against part of a control panel, will be shipped in These relays, when not included as AND STORAGE RECEIVING HANDLING access to the armature to permit adjust similar to the normally open fixed contacts A projecti in of the molded base paral brattng tube. rotation of the moving contacts. Openings pole piece and at the bottom by the fit of lel to the moving contact support prevents ment. rod are provided at the top by a hole in the the molded cntacl carrier inside the cali Fig. 5 for dimensions and panel drilling. the operating coils. Guides for the plunger CHARACTERISTICS GEI Instantaneous Voltage Relay Type PJV OPERATING PRINCWLES The PJV11A relay can be adjusted by The resistances of the d-c winciings The PJV17A relay contacts are op which moves vertically inside the cali into the solenoid by the flux established by and coil, are mounted on a compound base. The cover is attached to the front of the Immediately upon receipt of the relay mately 98% of rated DC voltage. The pickup dropout voltage. cheek by visual inspection that there are 1/64 inch. The normally open contact gap 1/32 inch. A backstop should be present between the backstop and contact brush at cage and in a level position. value should be no more than 106% of the electrical checks be made immediately tests should be made with the relay in Its creased until the contacts reset atapproxi test voltage should then be gradually de contacts with one continuous motion. The the tip should be approximately 1/16 inch mally supplied from the factory with the age applied to the DC coil (studs 1-2) In should pick up, closing its normally open series with the DC resistor. The relay resistor. Gradually increase DC test volt AC cotl (studs 5-6) in series with the AC MECHANICAL INSPECTION to a dropout of 98% of rated voltage. It on the calibration tube which corresponds 1. Pickup and Reset - The units are nor upon receipt of the relay. Note that all 1. Operate the plunger by hand and allow It is recommended that the following tion rang of the relay received agree with VISUAL INSPECTION calibrations have not been disturbed. screws are tight. Also check to see that made to insure that no damage has been Check the nameplate stamping to insure it to reset to Insure that all parts are free above the normally open contact. The gap an inspection and acceptance test should be ACCEPTANCE TESTS inside when the cover is removedand cause trouble in the operation of the relay. that the model number, rating and calibra signs of physical damage, and that all formed. mechanical adjustments be checked: closed contact should be approximately on the outside of the case may find its way no broken or cracked molded parts or other 2. The wipe on a normally open or normally metallic chips. Foreign matter collecten sustained in shipment and that the relay from friction or binds. this setting. Apply rated AC voltage to the a place that is free from moisture, duet and should be atored in their original cartons In the requlsition. Remove the relay from its case and the flexible moving contact leads extending back from the contacts have not been de ELECTRICAL TESTS It is recommended that the following bottom of the armature aligned with a mark should be sufficient to check the dropout at not to be installed Immediately, they with the armature fully reset should be with the armature reset. relays in the operation of a power system silver contacts should be cleaned with a surface. Burnishing tools designed per volt should be used for making the test. If it is necessary to makeadjustments cessive friction is present, check to see If there is any tendency to bind or If ex 1. Frtction charger output voltage with normal a-c terval between periodic checks will vary storing them. Manually operate the armature and allow it to reset to make sure that there is Check the contact gap and wipe and the backstop position; values should agree the battery charger at its lowest charging should be 106% or less of the dropout volt following points should be observed in re no excessive friction or tendency to bind. one to two years: MECHANICAL CHECKS PERIODIC CHECKS AND voltage on the outer operating coil. points be checked at an interval of from be followed. It is recognized that the in enough experience to select the test inter testing. Until the user has accumulated and- the user s experience with periodic to obtain the desired dropout. After the armature should be adjusted, If necessary, dropout value to be used and it should be location and preheated. The position of the dropout is set, check that the relay will ments it is suggested that the following Also the relay should be set at the checked. When making this check, the pick up at the lowest acceptable battery depending upon environment, type of relay, pickup and dropout. The pickup voltage rate and vary the test resistor to check the knives, files or abrasive paper or cloth of check the relay pickup and dropout. Set any kind to clean relay contacts. be obtained from the factory. Do not use especially for cleaning relay contacts can strip of metal, with an etched, roughened burnishing tool, which consists of a flexible of tarnishing or corrosion. These fine with those given in the section under AC is recommended that the visual and me chanical inspection described in the sec before Installation. it is important that a periodic testprogram val best suited to his individual require Examine the contact surfaces for signs storage before shipment to the job site, it relay should be installed in its permanent sections are found to be out of limits, the check points described in the previous SERVICING refer to the section on SERVICING. age. A voltmeter with at least 1000 ohms CEPTANCE TESTS, the relay is held in tion on ACCEPTANCE TESTS be repeated CEPTANCE TESTS. Using connections as indicated in Fig. 4 If after the performance of the AC In view of the vital roll of protective If any of the mechanical or electrical INSTALLATION PROCEDURE ROUTINE MAINTENANCE

5 5 b. There should be a 900 bend In the lead of the lead. damaged and probably the damage would be more than one turn over the complete length brating tube and that no foreign matter is reformed as follows: tact guide move freely inside the cali move it away from the base. Also check to ti.ibe would have to be straightened and/or deformation f the calibrating tube. This see that the armature and the molded con contact have been damaged, they ehodd be If the flexible leads from the moving tube. present between them and the ealibratine would indicate that the relay has been compound relay base. Inadequate clearance a shim placed behind the magnet frame to adequate (0.010 Inch) clearance from the that the moving contact molded support has a. The flexible leads should be twimed no at the terminal screw. which the relay was furnished. the General Electric requisition number on terminals to which they are connected.,hould touch no part of the relay except the p lete travel of the contacts; that is, they cj The leais should be free over the corn Instantaneous Voltage Relay Type PJV GEI complete nameplate data. If possible, give the relay calibration. gauge. horizontal. quired, name of the part wanted, and give Electric Company, specify quantity re c. Both normally open and normally closed the contact tip is attached should be nearly the nearest Sales Office of the General When ordering renewal parts, address section of the fixed contact brush to which that are worn, broken, or damaged. to enable the prompt replacement of any tities of renewal parts be carried in stock It is recomnended that sufficient quan RENEWAL PARTS e. After adjustments are complete the contacts should have a 1/64 Inch wipe. barely open. between the upper stationary and movable b. There should be about a t/32 gap 15 grams as measuredwitha standard gram adjusted to have an initial tension of about contacts when the lower contact is just a. Each stationary contact brush should be proceed as follows: - U it is necessary to replace a contact correctly formed, they may seriously affect Note that if the flexible leads are not assembly towards the base. d. ihe leads should not pull the contact

6 GEI Inatantaneoue Voltage Relay Type PJV BATTERY CHARGER I. STAT I ON SERVICE SUPPLY A.C. IN PUT TO BATTERY ( ) 27 EXT. RES. 27 AC INPUT OUTPUT ( ) D.C. (4.) RECTIFTER SUPPLIED WITH DEVICE ilj ±27x±27xJ27X ± X 21 I 6J 81 wt ALARM CONTACTS ARE REVERSIBLE IN FIELD FOR EITHER NORMALLY OPEN OR NORMALLY CLOSED OPERATION if TIME DELAY DROP OUT 27 LEGEND PJV17A HFA65D Fig. 3 (0148A ) External Connectioiis For The PJVI7A Relay U5ed Wth The KFA6SD Relay For Low Rattery Voltage Indication

7 7 Fig. 4 (0165A6010 O) Teat Connection tliagrm For The PJYI7A Relay 27 RtLAY UAGE FOR TEST. OAT1N CIRCWT TO VARY V(MLL TEST ESfSTOR INSERTED BATTERY TO Instantaneous Voltage Relay Type PJV GEI-83951

8 GEI-83g51 Inetantaneous Voltage Relay Type PJV ) T CODE 11 CONTACT CODE (FRONT VIEW) TOP OUTL I NE OF_RELAY 5 SPACE REQ D TO REMOVE COVER TYPE OF PANES.. A B C INSULATING 7 I 3 2 T fl. 11 STEEL (8 HOLES) INNER COIL DC) * 1 50-*--o OUTER COIL (AC) * NOrE 6 EXT. SERIES R REQ D. FOR EACH COl L..SEE 3HEET 2 DIA. ( HOLES) PANEL DRILLING (FRONT VIEW) INTERNAL CONNECTIONS (BACK VIEW) Fig. 5 ( ) Outline Pajiel Drilling Arid internal Connections For The P.JY17A Relay GENERAL ELECTRIC COMPANY, PHILADELPHIA, PA.

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC INSTRUCTIONS GEI-38974A Supersedes GEI 38974 INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC 2 DESCRIPTION APPLICATION MOUNTING SERVICING RENEWAL PARTS 10 PICKUP AND RESET ELECTRICAL TESTS ELECTRICAL

More information

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC INSTRUCTIONS GEI-98305C D-C UNDERVOLTAGE RELAY Type NGV18A GENERAL ELECTRIC 2 Fig (8035275) NOV18A Relay Removed From Case (Rear View) GEI-98305 D-C Undervoltage Relay Type NOV Fig. 1 (8035274) NGVI&L

More information

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC GENERALS ELECTRIC AUILIARV P A GENERAL ELECTRIC HGA11A, C, H, J, K, P, S, T, V, W, X TYPES INSTANTANEOUS AUXILIARY RELAY 0 INSTRUCT IONS GEH-1 793J 2 RENEWAL PARTS 8 CONTACT CLEANING 8 PERIODIC CHECKS

More information

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS g INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS Manual Part Number: GEI-83964H Copyright 2000 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905)

More information

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY TYPE HFA151 GE Protection and Control 25 Great Valley Parkway Malvern, PA 19355-1337 GEK 45484 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 RATINGS 3

More information

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 GEK-41931 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 TABLE I 3

More information

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

Type CRN-1 Reverse Power Relay 50 and 60 Hertz ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-251.2P Effective: June 1991 Supersedes I.L. 41-251.2N Dated April 1988 ( )Denotes Change

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F INSTRUCTIONS GEH-1768G IAV5 411 IAV5 511 IAV5 5J IAV54F IAV55F IAV54E IAV55C TYPES: UNDERVOL TAGE RELAYS 25 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control GEIL 1768 RESET B LiTTON

More information

B CW POWER RELAY

B CW POWER RELAY 41-241.31B CW POWER RELAY nected in such a way that current, (I A ), leads voltage, (V BA ), by 150 degrees when the motor is operating at unity power factor. Loss of excitation to the motor causes a large

More information

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION PHILAO[LPHA. PA GENERAL ELECTRIC POWER SYSTEMS MANAGEMENT DEPARTMENT latter should be referred to the General Electric Co.pany. probli erlie which are not covered sufficiently for the purchasers purpose.,

More information

P. Sub 4 184A404. Sub 3 876A220

P. Sub 4 184A404. Sub 3 876A220 Figure 1. Type CRN-1 Relay Without Case. 1 = Directional Unit (D). 2 = Timer Unit (T). 3 = Indicating Contactor Switch (ICS). Sub 4 184A404 Sub 3 876A220 Figure 2. Internal Schematic of the Single Trip

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION ABB Instruction Leaflet 41-163.2B Effective: January 1977 Supersedes I.L. 41-137.3A, Dated September 1974 ( ) Denotes Change Since Previous Issue Type CRQ Directional Negative Sequence Relay for Ground

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC GENERAL ELECTRIC AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C INSTRUCTION S GEK 7354J EK 73 54 FIG. 1 (838617) RELAY TYPE HA16fl TN CASE (FRONT VIEW) FIG. 2 (8938618) RELAY TYPE HAA16B REMOVCr) FPOM C?S

More information

UNION SERVICE SPECIFICATION NUMBER SU A

UNION SERVICE SPECIFICATION NUMBER SU A UNION SERVICE SPECIFICATION NUMBER SU-1862 -A UNION SWITCH & SIGNJU,.,... SWISSVALE, PAe DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY DN-10 TRAIN CONTROL SPECIAL SLOW DROP-AWAY RELAYS ********************

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay 41-106E Type CO-4 Step-Time Overcurrent Relay A core screw accessible from the top of the switch provides the adjustable pickup range. The IIT contacts are connected in the trip circuit to trip instantaneously.

More information

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View 41-503.21A TYPE KF Front View Rear View Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) 2 TYPE KF 41-503.21A lower pin bearing, which is mounted on the frame, with respect to the

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

INSTANTANEOUS CURRENT RELAYS

INSTANTANEOUS CURRENT RELAYS Handbook Reference 76 Supersedes GEH-179 B GENERAL ELECTRIC Type PJC INSTANTANEOUS CURRENT RELAYS GEH-179 C INSTRUCTIONS APPLICATION 3 INTRODUCTION. 3 PAGE out no -icc assurance is given with respect to

More information

THERMAL OVER CURRENT RELAY

THERMAL OVER CURRENT RELAY INSTRUCTIONS THERMAL OVER CURRENT RELAY Type TMCllA GEI-28826A GENERAL. ELECTRIC www. ElectricalPartManuals. com com GEI-28826A 2 Model Frequency 12TMC11A51A 50/60 12TMC11A52A 50/60 12TMC11A53A 50j60 12TMC11A54A

More information

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES INSTRUCTIONS GE I -288021 Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES PJV11J PJV11AL PJV11AZ PJV11L PJV1IAM PJV1IBF PJV11N PJV11AN PJV12B PJV11AF PJV11AR PJV12C PJV11AH PJV11AS PJV14B PJV11AJ

More information

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet Effective: October 1999 Supersedes I.L. 41-133R, Dated August 1998 ( ) Denotes Changed Since

More information

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits. HA Hinged Armature Auxiliary Hinged armature auxiliary relay to perform auxiliary functions in and circuits. eatures and Benefits Molded case with 4 mounting options Drawout case available Applications

More information

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A. INSTRUCTIONS and hjs52a Types IJS51A J CLO%NG - -* RELAY GENERALtEL1CTRjC SYNCHRONISM-CHECK RELAYS 205 Great Valley Parkway Malvern, PA 19355-07 15 GE Meter and Control GEl! 1791? INSTALLATION PROCEDURE

More information

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC. NSTRUCTONS MAGNETC TME RELAYS *C2820-054 *Also identified with prefix CR instead of C. GENERAL. ELECTRC GEH-85F NTRODUCTON The CR2820-054 relay is a d-e operated relay. t may be applied as an instantaneous

More information

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management 0 INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS Manual Part Number: GEI-83964H Copyright 2000 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC GENERAL ELECTRIC TYPE HGA17A TO F, H, M, R, S, T DC AUXILIARY RELAYS INSTRUCTIONS GEI-10190L RATINGS 3 CHARACTERISTICS a DESCRIPTION 3 CONTENTS PAGE BURDENS 4 CONSTRUCTION 4 LOCATION AND MOUNTING S MAINTENANCE

More information

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES BELL SYSTEM Plant Series PRACTICES SECTION 040-811-701 Issue 1, June, 1962 AT&TCo Standard RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION I I!

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

41-747G. Figure 1: Type DGF Relay without case (Photo)

41-747G. Figure 1: Type DGF Relay without case (Photo) Figure 1: Type DGF Relay without case (Photo) 2 183A113 EDSK 205342 Figure 2: Internal Schematic of the Type DGF Relay in the FT21 Case. When a ground appears in the generator field, the dc milliammeter

More information

4.0 OPERATION Type ITH-T Relay

4.0 OPERATION Type ITH-T Relay 41-771.2 Type ITH-T Relay 3.3 OPERATION INDICATOR This operation indicator is a small solenoid coil connected in the trip circuit. When the coil is energized a spring-restrained armature releases the white

More information

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection GEK 070B GE Power Management DIAC DIFC DSFC Digital Self Powered Overcurrent Protection *(RZHU0DQDJHPHQW $QGHUVRQ$YHQXH 0DUNKDPQWDULR &DQDGD/% ZZZJHFRPLQGV\VSP TABLE OF CONTENTS INTRODUCTION... PRODUCT

More information

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere . L. 41-793 NSTALLATON OPERATON MANTENANCE NSTRUCTONS TYPE CRN REVERSE POWER RELAY FOR MARNE SERVCE CAUTON Before putting relays into service remove all blocking which may have been inserted for the purpose

More information

SERVICE MANUAL

SERVICE MANUAL DN-18 SLOW PICK-UP. SLOW DROP-AWAY RELAYS SERVICE MANUAL 2 3 9 0 Supplemental Service Specifications: SU-2390-A SU-2390-B SU-2390-C DN-18 Slow Pick-Up, Ordinary Drop-Away Relay DN-19 Slow Drop-Away Relay

More information

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No. September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds

More information

Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225

Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225 Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225 P-205 819-0474 Installation Instructions Contents Installation Instructions

More information

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC IN ST RU CT ION S GE K 45487 D INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 J. GENERAL ELECTRIC DESCRIPTION 3 APPLICATION 3 PAGE CONTENTS 2 FIG. 1 (842734) COVER RENEWAL PARTS MECHANICAL ADJUSTMENTS S CONTACT

More information

www. ElectricalPartManuals. com INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR INSTALLATION OPERATION MAINTENANCE APPLICATION

www. ElectricalPartManuals. com INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR INSTALLATION OPERATION MAINTENANCE APPLICATION I. L. 41-610.2 INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR TYPE HKB SINGLE-POLE CAUTION Before putting relays into service, remove all blocking which may have been

More information

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING the voltage unit contacts, this effect is negligible. 3.2 Trip Circuit The main contacts will close 30 amperes at 250 volts dc and the seal-in contacts of the indicating contactor switch (ICS) will carry

More information

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT *****************

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT ***************** SERVICE MANUAL 4 5 7 8 PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT ***************** This service specification provides information required for repair and adjustment of PT-150 thermal

More information

Installation Sheet January, 2016 Supersedes June 2013

Installation Sheet January, 2016 Supersedes June 2013 s Installation Sheet January, 016 Supersedes June 01 E87010-A0105-T00-A6-CLM0 Lighting and Heating Contactor 60, 100, 00 Amp,, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES: 205 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control HFC21B, HFC22B, HFC23C TYPES: INSTANTANEOUS OVERCURRENT RELAYS INSTRUCTIONS GEK-49826D GEK-49826 CONTENTS PAGE DESCRIPTION APPLICATION

More information

~ SERVICE SPECIFICATION SU-4522-A ~

~ SERVICE SPECIFICATION SU-4522-A ~ WRBCC ~ ~ SERVICE SPECIFICATION SU-4522-A ~ ORP-66 PLUG-IN D. C. SWITCH OVERLOAD RELAY I. GENERAL The ORP-66 D. C. switch overload relay is furnished primarily for the overload protection of high voltage

More information

INFORMATION. covering use of Ammeter and Voltmeter ON and 1915 Model Six-54 Electrical System

INFORMATION. covering use of Ammeter and Voltmeter ON and 1915 Model Six-54 Electrical System INFORMATION covering use of Ammeter and Voltmeter ON- 1914 and 1915 Model Six-54 Electrical System Hudson Motor Car Company Detroit, Michigan, IX S. A USE OF AMMETER ON 1914 AND 1915 MODEL SIX-54 With

More information

Primary Brake Spline Drive Armature PB-825, PB-1000, PB-1225, PB-1525

Primary Brake Spline Drive Armature PB-825, PB-1000, PB-1225, PB-1525 Primary Brake Spline Drive Armature PB-825, PB-1000, PB-1225, PB-1525 P-209-WE 819-0517 Installation Instructions Contents Installation Instructions PB-825 PB-1000 PB-1225 PB-1525... 3 Coil Data... 5 Burnishing

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT 41-348.11C SA-1 Generator Differential Relay - Class 1E 2.0 CONSTRUCTION The type SA-1 relay consists of: Restraint Circuit Sensing Circuit Trip Circuit Surge Protection Circuit Operating Circuit Amplifier

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3. 41-348.1H Type SA-1 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are

More information

Installation Instructions

Installation Instructions Primary Brake Pin Drive Armature PB-825, PB-1000, PB-1225, PB-1525 Motor Brake and Spline Drive MB-825, MB-1000, MB-1225 Pin Drive P-208 819-036 Installation Instructions Contents Installation Instructions

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC 29006 Service Manual 3011 SL-6 & SL-6A Outlying Switch Lock Field and Shop Maintenance April, 1979 A-79-500-1496-3 1979, Union Switch & Signal

More information

CHEC"'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY

CHEC'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY CHEC"'- INSTRUCTION JUL S PA.MPH LET NUMBER U- 565 UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY j ELECTRO-PNEUMATIC CUT-OUT RELAY For Automatic Speed Control Car-Carried

More information

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control INSTRUCTIONS GEK-341 24G TYPES CFD22A AND CFD22B HIGH-SPEED DIFFERENTIAL RELAYS 205 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control GEK-341 24 CONTENTS PAGE APPLICATION 3 RATINGS

More information

PB-500 Pin Drive, PB-500 Spline Drive PB-650 Pin Drive

PB-500 Pin Drive, PB-500 Spline Drive PB-650 Pin Drive PB-500 Pin Drive, PB-500 Spline Drive PB-650 Pin Drive P-204 819-0485 Installation Instructions Contents Installation Instructions PB-500 Pin Drive.......................3 PB-500 Spline Drive....................6

More information

Installation Instructions

Installation Instructions Primary Clutch, Pin Drive Armature, Spline Drive Armature PC-825, PC-1000, PC-1225, PC-1525 Primary Clutch Coupling, Spline Drive Armature PCC-825, PCC-1000, PCC-1225, PCC-1525 P-206 819-0519 Installation

More information

GP/GPA GROUND FAULT PROTECTION

GP/GPA GROUND FAULT PROTECTION GP/GPA GROUND FAULT PROTECTION GROUND FAULT PROTECTION C-220EM Instruction Manual, June 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial and commercial customers with

More information

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F Instructions for De-Ion Air Circuit s Types DM2R, DM2F (Formerly Westinghouse Electric Corporation) 820 Washington Boulevard Pittsburgh, PA 15206 E-Mail: sales@homewoodsales.com Website: www.homewoodsales.com

More information

PC-500 Clutch, PCC-500 Clutch Coupling, PCBC-500 Clutch/Brake Coupling P-203-WE

PC-500 Clutch, PCC-500 Clutch Coupling, PCBC-500 Clutch/Brake Coupling P-203-WE PC-500 Clutch, PCC-500 Clutch Coupling, PCBC-500 Clutch/Brake Coupling P-203-WE 819-0484 Installation Instructions Contents Installation Instructions PC-500 Pin Drive.... 3 PCC-500 Spline Drive... 7 PCC-500

More information

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES Hubbell Industrial Controls, Inc. Instructions 5210 SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N 59364 SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N 59345 SERIES Publication

More information

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC Supersedes GEK45344 GEK.45344 A GENERAL ELECTRIC TYPE IAC66S TIME OVERCURRENT RELAY INSTRUCT ION S GEK4 5344 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 RATINGS 3 INDUCTION UNIT 3 TABLE I 3 TABLE II 4 STATIC

More information

DP140e. Installation & Operations Manual

DP140e. Installation & Operations Manual Installation & Operations Manual DP140e System Engineering International SEI Incorporated 5115 Pegasus Court, Suite Q Frederick, MD 21704 Phone 301-694-9601 / 800-765-4SEI Fax 301-694-9608 Web http//www.seipower.com

More information

INSTRUCTIONS GEH 2056F POWER RELAYS. Types ICW51A ICW52A ICW52B GENERALJ ELECTRIC

INSTRUCTIONS GEH 2056F POWER RELAYS. Types ICW51A ICW52A ICW52B GENERALJ ELECTRIC GENERALJ ELECTRIC ICW51A ICW52B ICW52A Types POWER RELAYS GEH 2056F INSTRUCTIONS CONTENTS DESCRIPTION 3 APPLICATION 3 RATINGS 4 CONTACTS 4 CHARACTERISTICS 5 OPERATING PRINCIPLES 5 PICK-UP 5 OPERATING AND

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

Vacuum Circuit Breakers (Vehicle)

Vacuum Circuit Breakers (Vehicle) Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

IGNITION COIL - 2.4L SPARK PLUG

IGNITION COIL - 2.4L SPARK PLUG TJ IGNITION CONTROL 8I - 13 IGNITION COIL - 2.4L DESCRIPTION - 2.4L The coil assembly consists of 2 different coils molded together. The assembly is mounted to the top of the engine (Fig. 21). REMOVAL

More information

Installation Instructions

Installation Instructions P-214 819-0518 PCB-1225/1000, PCB-1525/1225 Clutch-Brake, Pin Drive, Spline Drive PCBC-1225/1000, PCBC-1525/1225 Clutch-Brake/Coupling Installation Instructions Contents Installation Instructions PCB-1225/1000

More information

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION l.. L. 41-109 NSTALLATON OPERATON MANTENANCE NSTRUCTONS TYPE CO CONTACT MAKNG AMMETER CAUTON Before putting relays into service, remove all blocking inserted for the purpose of securing the parts during

More information

ELB ELB

ELB ELB ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical

More information

MODEL MAS BAR TO BAR TESTER INSTRUCTIONS

MODEL MAS BAR TO BAR TESTER INSTRUCTIONS INDEX: Mainframe Controls 1 Armature Head (Model H12) Operating Instructions 1 Diagnostics and Self Test Procedure 3 Interpretation of Bar to Bar Readings 4 Induction Rotor Testing (theory of operation)

More information

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

section-page Table 1. Transfer switching device ratings. Conditional short circuit current Operator s Manual 7000 Series ATS Automatic Transfer Switching Equipment D design 30 through 200 amperes TABLE OF CONTENTS section-page INSTALLATION... 1-1 Enclosures and Mounting... 1-1 Power Connections...

More information

Starting Systems. State a major safety precaution when removing or working around a starting motor

Starting Systems. State a major safety precaution when removing or working around a starting motor Starting Systems State a major safety precaution when removing or working around a starting motor Always unhook the battery ground before attempting to remove the starter motor. Starting Systems Identify

More information

RELAYS. Figure Relay construction.

RELAYS. Figure Relay construction. RELAYS The RELAY is a device that acts upon the same fundamental principle as the solenoid. The difference between a relay and a solenoid is that a relay does not have a movable core (plunger) while the

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 137NP 800 to 3500 Amperes ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1224-001B DISCLAIMER

More information

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G GLK 34117G INSTRUCTIONS POLYPHASE POWER DIRECTIONAL RELAY FOR ANTI I4OTORING PROTECTION TYPE GGP53C GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 PAGE CONTENTS 2 TOP UNIT 10

More information

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Vibrating Feeders Models: F-T01-A and DF-T01-A Contents Page

More information

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES Hubbell Industrial Controls, Inc. SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N 59495 SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N 59675 SERIES Instructions 5210 Publication

More information

PROCESS ELECTRONICS CORPORATION

PROCESS ELECTRONICS CORPORATION MINIVERTER MANUAL PROCESS ELECTRONICS CORPORATION 100 BRICKYARD ROAD MOUNT HOLLY, NORTH CAROLINA 28120 TELEPHONE (800) 421-9107 FAX (704) 827-9595 SALES@PECRECTIFIER.COM WWW.PECRECTIFIER.COM SOLID STATE

More information

February, Swissvale, Pa. INSTRUCTION PAMPHLET U-5623-A MASTER RELAY FOR AMPLIFIER FOR UNION CODED CAB SIGNAL EQUIPMENT

February, Swissvale, Pa. INSTRUCTION PAMPHLET U-5623-A MASTER RELAY FOR AMPLIFIER FOR UNION CODED CAB SIGNAL EQUIPMENT INSTRUCTION PAMPHLET U-5623-A MASTER RELAY FOR AMPLIFIER FOR UNION CODED CAB SIGNAL EQUIPMENT February, 1949 1 UNION SWITCH & SIGNAL COMPANY Swissvale, Pa. .. U. S. & S. Co. U-5623-A contact adjustments

More information

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION 505 z 509 FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION The movable contacts are carried in stainless steel cages which in turn are mounted in cavities in the molded portion of the cross bar. This

More information

Limit Switches. Reference Information. Proper Application of Limit Switches General Information. Definition of Limit Switch Terms.

Limit Switches. Reference Information. Proper Application of Limit Switches General Information. Definition of Limit Switch Terms. Reference Proper Application of General switches are used to convert a mechanical motion into an electrical control signal. The mechanical motion is usually in the form of a cam, a machine component or

More information

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS TJ STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS page DESCRIPTION AND OPERATION STARTER MOTOR... 2 STARTER RELAY... 3 STARTING SYSTEM... 1 DIAGNOSIS AND TESTING STARTER MOTOR... 8 STARTER MOTOR NOISE

More information

OPERATOR MANUAL Combo Belt Conveyor

OPERATOR MANUAL Combo Belt Conveyor 1 OPERATOR MANUAL Combo Belt Conveyor Document No. 11-01, Rev., 0816 2 WARNINGS THIS CONVEYOR IS DESIGNED FOR A SPECIFIC APPLICATION. CHECK FRAME AND METAL BELT FOR DAMAGE DURING SHIPMENT. READ THE MANUAL

More information

UNIT VIBRATOR MODELS 60U AND 70U

UNIT VIBRATOR MODELS 60U AND 70U VM-3560B Installation, Operation and Maintenance Instructions UNIT VIBRATOR MODELS 60U AND 70U ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506 1440 U.S.A. WORLD AUTHORITY IN ADVANCED TECHNOLOGY

More information

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS 1 Module 2 CONTROL SYSTEM COMPONENTS Lecture - 4 RELAYS Shameer A Koya Introduction Relays are generally used to accept information from some form of sensing device and convert it into proper power level,

More information

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label. Operator s Manual 7000 Series ACTS Automatic Closed Transition es 150 through 4000 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness...

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches, 600 1200 amps 600---1000 amp. sizes An experienced licensed electrician must install the ADTS. DANGER is used in this manual to

More information

OPERATOR MANUAL Magnetic Conveyor

OPERATOR MANUAL Magnetic Conveyor OPERATOR MANUAL Magnetic Conveyor Document No. 94-03, Rev. 0816-3 WARNINGS THIS CONVEYOR IS DESIGNED FOR A SPECIFIC APPLICATION. CHECK FRAME AND CHAIN FOR DAMAGE DURING SHIPMENT. READ THE MANUAL FOR PROPER

More information

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps Operator s Manual 7000 Series ATS Automatic Switches 600 through 1200 amps 600---1000 amp. size An experienced licensed electrician must install the ATS. DANGER is used in this manual to warn of high voltages

More information

Ch 4 Motor Control Devices

Ch 4 Motor Control Devices Ch 4 Motor Control Devices Part 1 Manually Operated Switches 1. List three examples of primary motor control devices. (P 66) Answer: Motor contactor, starter, and controller or anything that control the

More information