Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide

Size: px
Start display at page:

Download "Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide"

Transcription

1 Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide

2 Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide, Part Number Copyright 2010, Telect, Inc., ll Rights Reserved Telect and Connecting the Future are registered trademarks of Telect, Inc N Madson St., Liberty Lake, Washington Telect assumes no liability from the application or use of these products. Neither does Telect convey any license under its patent rights nor the patent rights of others. This document and the products described herein are subject to change without notice. bout Telect Telect offers complete solutions for physical layer connectivity, power, equipment housing and other network infrastructure equipment. From outside plant and central office to inside the home, Telect draws on more than 25 years of experience to deliver leading edge product and service solutions. Telect is committed to providing superior customer service and is capable of meeting the dynamic demands of customer and industry requirements. This commitment to customer and industry excellence has positioned Telect as a leading connectivity and power solution provider for the global communications industry. Technical Support getinfo@telect.com Phone: or Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page ii

3 Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide Table of Contents 1.1 Overview Specifications Inspection Installation larm Wiring Standard larms uxiliary larms GMT Fuses Schematics List of Figures Figure 1 - Model Figure 2 - Front View... 1 Figure 3 - Model (Rear View)... 2 Figure 4 - Model (Rear View)... 2 Figure 5 - Panel With Mounting rackets in Stowed Position for Shipping... 5 Figure 6 - racket Installation (Examples)... 6 Figure 7 - Mounting the Panel... 6 Figure 8 - Connecting the Lug to the Rear Panel... 7 Figure 9 - Inserting Conductors... 7 Figure 10 - Fail Relay larm Pins... 8 Figure 11 - Designation Card... 9 Figure 12 - Inserting the Designation Card Figure 13 - Standard larm Wiring Figure 14 - uxiliary larm Wiring...11 Figure 15 - lock Diagram Figure 16 - Rear, Top, and Front Views Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page iii

4 Low-Current 20/20 GMT Series Fuse Panels Models & Installation Guide 1.1 Overview Telect s 1RU Traditional Low-Current GMT Series Fuse Panels provide protected secondary -24 Vdc to -48 Vdc Front power distribution to telecommunications equipment at the bay level. Fuse panels are available for GMT outputs up Rear to 10 per position in dual-circuit panel configurations having 20 GMT fuse positions per circuit. Model is the standard panel containing separate Side and Side GMT fuse failure alarms and corresponding LEDs. Standard features for Model include Dual-circuit, separately fused input buses for Sides and Minimal rack space: one, 1.75-in. EI or 2-in. WECO rack unit (1RU) for rear access connections 20 GMT outputs per side with each side protected by a Type C 20 ceramic input fuse Dummy GMT fuses provided for all fuse holders Figure 1 - Model Two sets of Form C relay contacts per side for reliable fail alarm connections Side and alarms can be wired for separate or common alarming. (ll basic and auxiliary alarms can be wired for separate or common alarming.) 19-in. or 23- in. rack mounting, with mounting brackets provided Model adds separate power failure auxiliary alarms for Sides and along with a load-sharing fail-safe circuit. (ll basic and auxiliary alarms can be wired for separate or common alarming.) If power fails on one bus, the other picks up the loads on the failed bus. oth Models are UL Recognized for US and Canada, E199668, and NES3 Compliant. 20 Input Fuses for Circuits & Designation Card Holder "FIL SFE" pplies only to Model POWER POWER FIL SFE LRM Circuit Output GMT Fuse Holders Circuit Output GMT Fuse Holders Figure 2 - Front View Fuse larm LEDs for Circuits & Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 1

5 GMT output fuses are available in capacities ranging from 0.18 to 10. GMT splash covers are optional for maximum safety when fuses blow. (Visit our website at or see Section 1.6 GMT Fuses on page 12 for ordering GMT fuses.) The panel is delivered with dummy fuses in all positions. The standard front panel includes a tri-color fuse alarm LED for each circuit (LRM and LRM ): The LRM LEDs are green when all installed input and output fuses are operational. The LRM LED is red when any output fuse blows. The LRM LED is orange when either of the input fuses blows. The back contains input and output terminal connections (NEG connections at top; POS RTN connections below), chassis ground connections, and wire-wrap pins for external alarm hookups. Plastic Caps* CUTION: DO NOT REVERSE POLRITY larm Pins for Circuits & Screw-Tight, W ire-clamping Output Terminals -24V TO -48V FIL RELY RTN Screw-Tight, W ire-clamping Input Terminals * Plastic caps cover screw-tight terminals used by the manufacturer for installing interior wiring. DO NOT REMOVE CPS or LOOSEN CLMPING SCREWS. Figure 3 - Model (Rear View) Plastic Caps* CUTION: DO NOT REVERSE POLRITY larm Pins for Circuits & Screw-Tight, W ire-clamping Output Terminals F UX RLY F UX RLY F -24/48V IN F +GND IN -24V TO -48V FIL RELY RTN Screw-Tight, W ire-clamping Input Terminals * Plastic caps cover screw-tight terminals used by the manufacturer for installing interior wiring. DO NOT REMOVE CPS or LOOSEN CLMPING SCREWS. Figure 4 - Model (Rear View) Model includes a fail-safe circuit. Schottky diodes are cross-connected at the input to the power distribution circuits. When both power supplies are energized, power is balanced between the two supplies by the diodes. If one of the power supplies loses its power or is shut down, the other supply shares its power with both outputs ( and ) through the Schottky diodes. The positive battery return circuits for and are common since both circuits must operate from either the or power source. The fail-safe feature limits the and inputs to 15 maximum for each bus (total 30 per panel). NOTE: For the Fail Safe load sharing to function properly, the capacity of each of the usersupplied external feeder fuses or breakers must be greater than the total load of the panels and Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 2

6 outputs combined. For example, if the panel s total Load = 10 and Load = 10, then the feeder fuse for Side and Side must each be at least Specifications Physical: Specifications: Dimensions (nominal without bracket)* Width: Height: Depth: 17 in. (432 mm) 1.75 in. (44.4 mm) 9.25 in. (235.0 mm) Weight 8.5 lb (~3.8 kg) Ground terminals Screws: #10-32 Phillips** panhead Torque: 20 in.-lb (~2.26 N m), max. Wire: Same size as input terminals Ring Lug urndy T1010, 12 WG, no insulation; MP 35771, WG, no insulation Material Cold-rolled steel, powder-coat telcom grey * See 1.7 Schematics on page 12. for complete dimensions. ** Screws with cross-recessed heads Custom color/finish available. Mechanical: Specifications: Input terminals Type: Screw-tight, wire-clamping Wire: 14 to 6 WG, copper wire Torque: 16 in.-lb (1.80 N m), max. Output terminals Type: Screw-tight, wire-clamping Wire: 22 to 14, copper wire Torque: 4.5 in.-lb (0.51 N m), max. larm terminals Wire Wrap.045 in. square wire-wrap pins on.200 in. centers. Use 18 to 22 WG copper Environment: Temperature range, ambient Humidity Specifications: -17 C to 49 C (0 F to 120 F) 0% to 90% and noncondensing Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 3

7 Electrical Interface: Operating voltages, nominal Current capacity Fuse capacity Maximum output interruption device rating Maximum continuous output load rating larm contact relay Panel heat dissipation per 20 bus Percentage of full load heat dissipation at nominal voltage Specifications: -24 Vdc to -48 Vdc 20 per bus (40 total for both buses), max. with 20 ceramic input fuse (Type C) 15 per bus (30 total for both buses), max, with 20 ceramic input fuse (Type C) 20 (ea side) 10 GMT fuse 7 for a 10 fuse 30 Vdc 3.9W (13.3 0% load less than 1% of total load wattage Reliability: MTF 200,000 hr 1.3 Inspection Please read these instructions carefully before beginning installation. If you need assistance, call Technical Support at (domestic calls), or (Option 2), or us at getinfo@telect.com. Inspect equipment after unpacking and compare it to the packing list. Immediately report any shipping damage, defects, or missing parts to Telect at Keep all documentation that comes with your shipment. Telect is not liable for shipping damage. If the product is damaged, notify the carrier and call Telect s Customer Service Department at (domestic only) or for further recourse. NOTE: For service or warranty information, please visit the telect.com website, or inquiries to getinfo@telect.com and click on the Support tab, or phone us at (domestic only) or Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 4

8 1.4 Installation LERT LERT Install this product within a restricted access location where access is through the use of a tool, lock and key, or other means of security, and is controlled by the authority responsible for the location. Only qualified personnel may install and maintain this product. LERT LERT Verify all connections meet requirements specified in local electric codes or operating company guidelines before supplying power. Protect this equipment with a fuse or breaker sufficient to interrupt power levels specified under Electrical Specifications. LERT LERT Each panel is tested at the factory. Telect recommends that you perform the testing outlined in the following procedure to ensure that no damage has occurred during shipping and handling. oth Sides and input circuits, as applicable, need to be tested. rackets are provided for either flush or extended (increments of 0.5 in. [12.7 mm]) mounting in a 19-in. or 23-in. rack with either EI or WECO spacing. For shipping, both pairs of brackets are affixed to the sides of the panel. 1. Remove the brackets, shown in the following illustration, from the sides of the panel. Left racket for 19-in. Rack Remove Screws (4) on Each Side of Panel to Remove rackets from Stowed Position Right racket for 23-in. Rack Right racket for 19-in. Rack Left racket for 23-in. Rack Figure 5 - Panel With Mounting rackets in Stowed Position for Shipping Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 5

9 2. Select the proper pair of brackets and discard the other two. 3. Mount the brackets to sides of the panel, as shown in the following examples. Tighten screws to about 29 in.-lb (~3.3 N m). The panel can be mounted so that the panel s face is flush or extended in 0.5-in. (12.7 mm) increments from the rack. (The clover-leaf pattern on the face of the bracket points downward on the right side of the panel and upward on the left.) racket for a 19-in. Rack (Extended 2 in.) racket for a 23-in. Rack (Flush Mount) racket for a 19-in. Rack (Flush Mount) Clover-Leaf Pattern Points Downward on Right Side of Panel. Figure 6 - racket Installation (Examples) 4. Locate an unused rack position and mount the panel using the four, thread-cutting screws and lockwashers provided, as shown on the right. 5. Tighten the screws to 35 in.-lb (4.29 N m). 6. efore connecting any conductor, use a multimeter to measure the resistance between the input terminal of each side (+ and - for Side ; + and - for Side ) at the rear corner of the panel. Expect 500Ω or more for both Side and Side. Figure 7 - Mounting the Panel WRNING WRNING Failure to properly ground this equipment can create hazardous conditions to installation personnel and to the equipment. LERT LERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories (UL), TUV, etc. 7. For ground wiring, use a listed (approved) crimping tool to attach a listed (approved), singlehole compression lug suitable for a #10 (~5 mm) screw onto a suitable ground wire. Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 6

10 Ground wire should be same gauge as the input wiring. Input wire size depends solely on input interruption device at the primary power distribution unit. 8. If necessary, use a coarse, non-metallic cleaning pad to clean the lug and stud. 9. Telect recommends that you lightly coat anti-oxidant on the lug, grounding screw, and surrounding contacting surface. 10. Connect the lug to the rear panel using the ground screw provided. See Figure 1. FIL RELY Figure 8 - Connecting the Lug to the Rear Panel 11. Tighten the screws to 20 in.-lb (~2.26 N m). WRNING WRNING efore connecting input power cables, make sure input power to panel is turned off. 12. For input wiring wiring used as inputs to this distribution panel strip approximately 3 /8 in. (~10 mm) of insulation from the end of suitable input conductors. Input conductor (14 to 6 WG) must match or exceed the rating of the fuse or breaker at the PDU. (Stranded wires should be tinned.) 13. Lightly coat anti-oxidant on the bare conductors. 14. Insert the conductors at the bottom of the screw-tight terminals, as shown on the right. 15. Tighten screws to 16 in.-lb (1.80 N m). Figure 9 - Inserting Conductors LERT LERT -24 Vdc to -48 Vdc always goes to - and -. RTN always goes to + and +. RTN always goes to the other terminal. For Model with fail-safe circuitry, make sure that RTN is common to both Side and. 16. Make sure power is off (open breaker, dummy fuse, or vacant fuse holder at the power distribution unit [PDU]) before connecting this panel s cables to the PDU. 17. Make sure that only dummy GMT fuses are installed in this panel or that the GMT fuse holders are vacant. 18. Enable the fuse or breaker at the PDU (25 max. for Model ; 35 max. for Model which contains a fail-safe circuit) to turn on Feed to Side of the panel. Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 7

11 19. Check voltage and polarity at the input connectors of the panel. lso, check that The LED on front of the panel turns on (green). The LED must remain red. If the LED doesn t turn green, recheck polarity at input connectors. (Reversing input connections will not harm the panel.) However, if the input power leads were reversed, the fuse fail relay will fail to energize, causing the normally open contacts to remain closed and normally closed contacts to remain open. If necessary, check across the FIL RELY alarm pins located on the rear of the panel and shown in Figure On the rear of the panel, with LED lit (normal operation), but with LED off (failure operation), test the Side- FIL RELY pins. Expect continuity (0Ω) between Terminals C and NC. Expect an open circuit ( Ω) between Terminals C and NO. 21. Conversely, when testing the Side- pins, Expect an open circuit ( Ω) between Terminals C and NC. Expect continuity (0Ω) between Terminals C and NO. 22. Repeat Steps 18 to 21 for Feed and observe that the LED turns green. cross all FIL RELY alarm pins Expect continuity (0Ω) between Terminals C and NC. Expect an open circuit ( Ω) between Terminals C and NO. 23. For output wiring, strip off ¼ in. (~7 mm) of insulation. Like the input terminals, the output terminals are screw-tight, wire-clamping. The output terminals will accommodate 14-WG to 6-WG conductors. Like the output terminals, stranded wires for outputs should be tinned. Remember: output conductors must be rated at or above the amperage rating of the GMT fuse. For example, use no smaller than #16-WG output wiring for 10 output fuses. Do not exceed 8 continuous load for a 10 fuse. LERT LERT GMT fuses have a small inherent electrical resistance resulting in a small inherent power loss. For this reason, the GMT fuse manufacturer recommends that the load for GMT fuses up to and including 7.5 not exceed 80% of the fuse rating and that the load for 10 GMT fuses not exceed 70% of the fuse rating. (For example, 10 fuse x.70 = 7 max. load). Total load for all GMT outputs on each side must not exceed 20 for a panel without a fail-safe circuit, or 15 for a panel with a fail-safe circuit. FIL RELY Figure 10 - Fail Relay larm Pins Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 8

12 24. Telect recommends that you lightly coat anti-oxidant on bare wires before connecting to output terminals. (NEC specifies only one conductor and load for each output terminal.) 25. Tighten the screws to 4.5 in.-lb (0.51 N m). 26. Connect the other end of output wires to load. 27. Record the circuits on the designation card provided, as specified by the operating company procedures.(the front side of the card is shown in Figure 10.) The designation card has entries for Outputs 1-10 on the front and on the rear. Use the left half of each side for Side outputs and the right half for Side outputs. 28. Make sure the inputs at the loads are disabled by removing all power cards or all input fuses at the load equipment. (lways follow recommended operating company guidelines when disabling load equipment.) INPUT FUSE FUSE MP CIRCUIT INPUT FUSE FUSE MP CIRCUIT INPUT FUSE FUSE MP CIRCUIT INPUT FUSE FUSE MP CIRCUIT Figure 11 - Designation Card WRNING WRNING Use only UL-listed or UL-recognized component secondary protection devices. 29. Insert the proper sizes of GMT fuses in designated fuse holders using the designation card to identify circuits. Check voltage and polarity at input of loads. 30. fter all designated GMT fuses have been installed, check that the and LEDs are still green. If an output fuse blows, the corresponding or LED will turn red; if an input fuse blows, the corresponding or LED will be orange or amber. gain, test FIL RELY alarm pins on rear of the panel. s before Expect continuity (0Ω) between Terminals C and NC. Expect an open circuit ( Ω) between Terminals C and NO. 31. If available, replace one of the output fuses with a blown fuse and check that the or LED changes to red. Check the FIL LRM pins again: Expect an open circuit ( Ω) between Terminals C and NC. Expect continuity (0Ω) between Terminals C and NO. 32. When finished, re-install the operable fuse. 33. Do the same with one of the input fuses. Notice that the or LED changes to amber. The FIL RELY alarm pins will indicate a failure condition. Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 9

13 34. If desired, wire-wrap the remote external audio/visual alarm indicator wires (solid copper wires, #22 to #18 WG) to the alarm terminals. See larm Wiring, following this section One by one, re-enable the load equipment and verify proper operation. 36. Fold the designation card on the score line and slip into the holder on the front of the panel, as shown in Figure larm Wiring Model has a standard alarm relay (FIL RELY) for each feed one for Side and one for Side. Model contains the standard alarm relay plus an auxiliary relay (UX RELY) that can be triggered externally. ll relays have two sets of Form C dry contacts for wiring to audible and visual alarm indicators. udible and/or visual failure indicators can be wired to the alarm pins in several ways Standard larms Designation Card Holder Figure 12 - Inserting the Designation Card When an input or output fuse blows the relay is de-energized and the normally open contacts close and the normally closed contacts open to indicate the failure. larm Device larm Device FIL RELY larm Device larm Device larm Device larm Device FIL RELY NEG (or -GND) +GND (or POS) NEG (or -GND) NEG (or -GND) +GND (or POS) a. Separate larms for Side & Side b. Combined larms for Side & Side Figure 13 - Standard larm Wiring uxiliary larms uxiliary alarms are triggered from either an external CO or site source or by the standard alarm relay. Like the standard relay, when triggered, the auxiliary relay is de-energized, causing the normally open contacts to close and the normally closed contacts to open. Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 10

14 larm Device larm Device larm Device larm Device +GND (or POS) NEG (or -GND) NEG (or -GND) +GND (or POS) uxiliary Relay Contacts uxiliary Relay Trigger F UX RLY F UX RLY F -24/48V IN* F +GND IN** FIL RELY Internal Wiring F -24/48V IN* F +GND IN** Nomenclature is for contacts * NEG (or -GND) trigger. ** POS (or +GND) trigger. a. Separate larms for Side & Side larm Device larm Device +GND (or POS) NEG (or -GND) uxiliary Relay Contacts uxiliary Relay Trigger F UX RLY F UX RLY F -24/48V IN* F +GND IN** FIL RELY Internal Wiring b. Combined larms for Side & Side F -24/48V IN* F +GND IN** Nomenclature is for contacts * NEG (or -GND) trigger. ** POS (or +GND) trigger. larm Device larm Device larm Device larm Device +GND (or POS) NEG (or -GND) NEG (or -GND) +GND (or POS) uxiliary Relay Contacts uxiliary Relay Trigger F UX RLY F UX RLY F -24/48V IN F +GND IN FIL RELY F -24/48V IN* F +GND IN** Nomenclature is for contacts +GND (or POS) c. Using the Standard larm to Trigger uxiliary larms When a Fuse lows Figure 14 - uxiliary larm Wiring Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 11

15 1.6 GMT Fuses GMT Fuse Part Numbers GMT Fuse GMT Fuse Part Numbers GMT Fuse.18 Yellow (YEL) White/Orange (WHT/ORN) ¼ Violet (VIO) lue (LU) ½ Red (RED) White/lue (WHT/LU) ¾ rown (RN) White/rown (WHT/RN) Gray (GRY) Green (GRN) /3 White (WHT) ½ lack/white (LK/WHT) ½ White/Yellow (WHT/YEL) Red/White (RED/WHT) Orange (ORN) Order E RC for each ¼ X 1¼, V input fuse. For dummy fuses order For GMT safety (splash/splatter) covers order Schematics POWER OUTPUT FIL SFE LOD SHRING POWER OUTPUT T T R T N GROUND OUTPUT GROUND OUTPUT Figure 15 - lock Diagram T T R T N Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 12

16 -24V TO -48V FIL RELY RTN Model F UX RLY F UX RLY F -24/48V IN F +GND IN -24V TO -48V FIL RELY RTN #10-32 Panhead Screw R0.21 [R5.4] Model Min. length of lug tongue is 0.43 in. (10.8 mm) RER VIEWS (ROTTED) 0.77 [19.7] 8.17 [207.5] Face of panel can be extended beyond rack flange by as much as 2.50 in. (63.5 mm) in 0.5 in. (12.7 mm) [63.5] 0.19 [4.9] TOP VIEW "FIL SFE" pplies only to Model [44.5] 1.25 [31.7] POWER POWER FIL SFE LRM 1.00 [25.4] [432.2] [465.1] 0.39 [9.9] [482.6] [566.7] [584.6] FRONT VIEW Figure 16 - Rear, Top, and Front Views Telect assumes no liability for the application or use of these products. Neither does Telect convey any license under its patent rights or the patent rights of others. This document and the products described herein are subject to change without notice. Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 13

17 U.S. Conformity ssessment ody Certificate of Conformity No Upon assessment of Technical Construction File TCF it has been determined that the Hendry Telephone Products Power Distribution and Fan Panels conform to the protection requirements set out in article 4 of EMC Directive 89/336/EEC as per EN :94 with 1 :95 & 2 :97 (class ), EN :95, EN :95, EN V1.2.1 :00-03, and ETS ; and in accordance with the greement on Mutual Recognition between the United States of merica and the European Community, Sectoral nnex for EMC, this U.S. Conformity ssessment ody hereby certifies attestations of compliance to the EMC requirements so demonstrated. National Technical Systems 1536 E. Valencia Drive; Fullerton, C, US ; Tel (714) ; Fax (714) Telect, Inc. US Mexico Telect, Inc., ll Rights Reserved, Page 14

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel. Model Installation Guide

Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel. Model Installation Guide Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide Dual-Feed 200A 4/5 TPA/GMT Fuse Alarm Panel Model 009-8005-0404 Installation Guide, Part number 123518-6 Copyright 2010,

More information

Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel. Model N Installation Guide

Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel. Model N Installation Guide Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel Model 009-8004-0100N Installation Guide Dual 100A 4/4-KLM & 4/4-GMT Fuse Panel Model 009-8004-0100N Installation Guide, Part Number 123759-3 Copyright 2011, Telect,

More information

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel

50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel 50A Dual-Feed 5/5 GMT Total Front Access Fuse Panel Power :: GMT05FA User Manual Applys to : GMT05FA Table of Contents 1.1 Overview...3 1.2 Rack-mounting Considerations...4 1.3 Specifications...4 1.4 Installation...6

More information

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide

Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08. Installation Guide Demarcation Fuse/Circuit Breaker Alarm Panel 125DM08 Installation Guide Table of Contents 1.1 Overview... 2 1.2 Specifications... 3 1.3 Inspection... 3 1.4 Installation... 4 1.4.1 Important Installation

More information

Dual-Feed 600A 8-Circuit Breaker/TPC/TFD Load Center With 5 GMTs

Dual-Feed 600A 8-Circuit Breaker/TPC/TFD Load Center With 5 GMTs Installation Guide pplys to : 600C08 Table of Contents 1.1 Overview...3 1.2 Specifications...4 1.3 Preparation...6 1.3.1 larm Card...7 1.4 Installation...8 1.5 Parts & ccessories...17 1.5.1 Compression

More information

100A Universal Voltage Dual-Feed GMT Fuse Panels Power :: HPGMT10xx and HPGMT15 Installation Guide

100A Universal Voltage Dual-Feed GMT Fuse Panels Power :: HPGMT10xx and HPGMT15 Installation Guide Installation Guide HPGMT10 / HPGMT10RC HPGMT15 / HPGMT15RC HPGMT10FA HPGMT10FA-1RU Applies to : HPGMT10 :: HPGMT10RC :: HPGMT10FA :: HPGMT10FA-1RU :: HPGMT15 :: HPGMT15RC Table of Contents 1.1 Overview...1

More information

Demarcation Fuse Alarm Panel

Demarcation Fuse Alarm Panel Installation Guide Applies to: 009-7001-0104 & 009-7001-0104-TFD Table of Contents 1.1 Overview...3 1.2 Inspection...3 1.3 Specifications...4 1.4 Installation...5 1.4.1 Important Installation Guidelines...5

More information

HMW Filtered Fuse Panel for GMT Fuses

HMW Filtered Fuse Panel for GMT Fuses FUSE MP CIRCUIT FUSE MP 1 3 2 5 3 1 2 5 CIRCUIT L P R O D U C T S P E C I F I C T I O N November 8, 1999 HMW 06020 Filtered Fuse Panel for GMT Fuses -2 to DC 7-000015-H POWER POWER F F 1 5 10 15 20 1 5

More information

Dual-Feed 600A Load Center Frame Power :: 600CB10 and 600CB12 User Manual

Dual-Feed 600A Load Center Frame Power :: 600CB10 and 600CB12 User Manual Power :: 600CB10 and 600CB12 User Manual 600CB10 - Front View 600CB10-C - Rear View Applies to : 600CB10 :: 600CB10-C :: 600CB10-VL :: 600CB10-CL :: 600CB12 :: 600CB12-C :: 600CB12-VL :: 600CB12-CL Table

More information

100A/60A Universal Voltage GMT Fuse Panels With Enhanced Power/Fuse & Bay Alarms Power :: HPGMTXX & GMTXX Installation Guide

100A/60A Universal Voltage GMT Fuse Panels With Enhanced Power/Fuse & Bay Alarms Power :: HPGMTXX & GMTXX Installation Guide 100/60 Universal Voltage GMT Fuse Panels With Enhanced Power/Fuse & Bay larms Installation Guide pplies to : GMT10 :: GMT10F :: GMT20 :: GMT20S :: HPGMT10 :: HPGMT10F :: HPGMT15 :: HPGMT20 :: HPGMT20S

More information

Dual-Feed 600A Load Center Frame

Dual-Feed 600A Load Center Frame Dual-Feed 600A Load Center Frame 600CB10 Front View 600CB10-C Rear View Installation Guide Part Number, 136429-2 Applies to: 600CB10 :: 600CB10-C :: 600CB10-VL :: 600CB10-CL :: 600CB12 :: 600CB12-C ::

More information

PowerWorx GMT Series Power Distribution Panel Uninterrupted (C-Source) Power User Manual

PowerWorx GMT Series Power Distribution Panel Uninterrupted (C-Source) Power User Manual Content PowerWorx GMT Series Power Distribution Panel Uninterrupted (C-Source) Power User Manual Page INTRODUCTION...2 Revision History...5 Trademark Information...5 Admonishments...5 General Safety Precautions...6

More information

TPM/GMT Panel Installation Guide

TPM/GMT Panel Installation Guide TPM/GMT Panel Installation Guide Document INS-837xxxxxxx This manual covers the following part numbers- Trimm 837xxxxxxx Family Table of Contents Table of Contents... 2 Section 1- General Information...

More information

FUSE PANEL. Technical Practice N N-L33 10/10 GMT Front Access NEBS Level 3 Certified

FUSE PANEL. Technical Practice N N-L33 10/10 GMT Front Access NEBS Level 3 Certified 530-063 Rev K 0220-03K November 3, 202 Westell FUSE PANEL Technical Practice N25020-N-L33 0/0 GMT Front Access NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 0 GMT fuses in each (5Amps/GMT

More information

GMT Fuse Panel Installation Guide

GMT Fuse Panel Installation Guide GMT Fuse Panel Installation Guide Document INS-707XXXXXXX This manual covers the following part numbers- Trimm 707XXXXXXX Family Table of Contents Section 1- General Information... 3 1.1 - Product Description...

More information

FUSE PANEL Technical Practice N N-L34 20/20 GMT (23 panel) NEBS Level 3 Certified

FUSE PANEL Technical Practice N N-L34 20/20 GMT (23 panel) NEBS Level 3 Certified 530-101732 Rev L 0223-03K September 30, 2010 Westell FUSE PANEL Technical Practice N250140-N-L34 20/20 GMT (23 panel) NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 20 GMT fuses each (15Amps/GMT

More information

Noran Tel. FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified

Noran Tel. FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified 0322-03D Sept 02, 2010 Noran Tel FUSE PANEL Technical Practice N21C110-NCY 5/5 GMT (20Amp GMT) NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 5 GMT fuses each (20Amps/GMT position). Polarity

More information

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual ADCP-80-580 Issue 3 11/2010 17943-A Circuit Breaker for ±24 or ±48 Vdc 1474485 Rev C Preface COPYRIGHT

More information

Installation Manual. AC Edge. Split Phase 60 A (6/6) AC Power Distribution Unit. AC Edge. Model AC60DF 6/6 Part#

Installation Manual. AC Edge. Split Phase 60 A (6/6) AC Power Distribution Unit. AC Edge. Model AC60DF 6/6 Part# Installation Manual AC Edge Split Phase 60 A (6/6) AC Power Distribution Unit AC Edge Model AC60DF 6/6 Part# 1101-1071 1402-036 RevE Installation Manual AC Edge Table of Contents AC Edge Introduction 3

More information

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family TPM Fuse Panel Installation Guide Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family Table of Contents Section 1- General Information... 3 1.1 - Product Description...

More information

PowerWorx DSX Series GMT Fuse Panel User Manual

PowerWorx DSX Series GMT Fuse Panel User Manual PowerWorx DSX Series GMT Fuse Panel User Manual ADCP-80-538 Issue 4 2/2012 1206873 Rev E Preface COPYRIGHT 2011, Tyco Electronics Corporation All Rights Reserved REVISION HISTORY ISSUE DATE REASON FOR

More information

FUSE PANEL. NTI-N NC(Y)/M3 NEBS Level 3 Certified NTI NCD(Y)/M3 Standard Panel with Diodes

FUSE PANEL. NTI-N NC(Y)/M3 NEBS Level 3 Certified NTI NCD(Y)/M3 Standard Panel with Diodes 0113-03K September 2, 2010 FUSE PANEL Technical Practice NTI-N250140-NC(Y)/M3 NEBS Level 3 Certified NTI-230140-NCD(Y)/M3 Standard Panel with Diodes FEATURES ƒ Negative (-) VDC input voltage, -24 or 48Vdc

More information

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified 0406-03E August 11, 2005 Fuse Panel Technical Practice N215120-NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified FEATURES Compatible with +24V, +48V, -24V or -48V dc input voltages (battery voltages). 2 busses

More information

Secondary DC Distribution E R P R P I 2. Technical Reference Guide

Secondary DC Distribution E R P R P I 2. Technical Reference Guide Secondary DC Distribution Technical Reference Guide EI IR 2 2 E R P P E I E R P R E I 2 E P R P I 2 E P I IR PR Secondary DC Distribution Technical Reference Guide, Part Number 118101 Copyright 2010, Telect,

More information

Noran Tel. a subsidiary of Westell Inc. Fuse Panel Technical Practice NPGMT /10 GMT NEBS Level 3 Verified

Noran Tel. a subsidiary of Westell Inc. Fuse Panel Technical Practice NPGMT /10 GMT NEBS Level 3 Verified 1107-03B Aug 16, 2011 a subsidiary of Westell Inc Fuse Panel Technical Practice NPGMT1107 10/10 GMT NEBS Level 3 Verified FEATURES 2 isolated groups (busses) of 10 GMT style fuses in each (20Amps/GMT position

More information

FUSE PANEL Technical Practice FDP /10 GMT NEBS Level 3 Certified

FUSE PANEL Technical Practice FDP /10 GMT NEBS Level 3 Certified 0521-03A May 2006 FUSE PANEL Technical Practice FDP 1010 10/10 GMT NEBS Level 3 Certified FEATURES 2 isolated groups (busses) of 10 GMT fuses in each (15Amps/GMT position) Polarity insensitive (+/-24 or

More information

Westell FUSE PANEL. Technical Practice N Position Type VDC Floating

Westell FUSE PANEL. Technical Practice N Position Type VDC Floating 530-101760 REV C 0808-03C December 7, 2012 Westell FUSE PANEL Technical Practice 180108-N-0808 8 Position Type 70 130 VDC Floating FEATURES Single floating input distributing power via Type-70 fuses each

More information

Application Note. Best Solutions for Managing High-Current Power Distribution

Application Note. Best Solutions for Managing High-Current Power Distribution Best Solutions for Managing High-Current Power Distribution High-Current Demarcation Panels Provide a Platform for Distribution & Protection M any of today s network applications include equipment that

More information

FUSE PANEL Technical Practice FDP /20 GMT NEBS Level 3 Certified

FUSE PANEL Technical Practice FDP /20 GMT NEBS Level 3 Certified 0522-03A May 2006 FUSE PANEL Technical Practice FDP 2020 20/20 GMT NEBS Level 3 Certified FEATURES Polarity insensitive (+/-24 or +/-48 Vdc) battery voltage This panel can operate at 200 Amps of output

More information

:: :: TFD4 :: TFD6

:: :: TFD4 :: TFD6 User Manual Applies to: 007-0001-2600 :: 007-0001-2602 :: 007-0001-2602-TFD4 :: 007-0001-2602-TFD6 :: 007-0001-2602-4 :: 007-0001-2602-6 1 Table of Contents Chapter 1: Dual 600A BDFB/BDCBB Description...

More information

Installing Power Components

Installing Power Components This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco

More information

Fuse / Circuit Breaker Panels

Fuse / Circuit Breaker Panels Critical Power from GE Micro-BDCBB DC Battery Distribution Circuit Breaker Bay Overview The GE Micro-BDCBB serves as a secondary power distribution center for +24Vdc or -48Vdc DC power delivered from a

More information

Total Front Access Wall Mount Fuse Panel Installation Guide. Document INS This manual covers the following part numbers

Total Front Access Wall Mount Fuse Panel Installation Guide. Document INS This manual covers the following part numbers Total Front Access Wall Mount Fuse Panel Installation Guide Document INS-7473121031 This manual covers the following part numbers- 7473121031 Table of Contents Section 1- General Information... 3 1.1 -

More information

IOE-XXX-XXXX Training Guide

IOE-XXX-XXXX Training Guide IOE-XXX-XXXX Training Guide 1 IOE-XXX-XXXX Training Guide. nrgsmart 2-compartment 32RU Enclosures: IOE-XXX-XXXX 2011, Telect, Inc., All Rights Reserved Telect, nrgsmart, and Connecting the Future are registered

More information

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions

DS1 Plug-In Digital Signal Cross-Connect (PIX-DSX-1) 19-Inch Shelf Kit Installation Instructions DS Plug-In Digital Signal Cross-Connect (PIX-DSX-) 9-Inch Shelf Kit Installation Instructions Contents Page INTRODUCTION... Revision History... List of Changes... Trademark Information... Related Publications...2

More information

CPS2000 Cabinet Power System

CPS2000 Cabinet Power System Input (Nominal): 90 Vac to 264 Vac (Autoranging) Output (Nominal): -48 Vdc (up to 28.8 A) and Optional 50 VA Ringing Generator The low-maintenance, outside-plant CPS2000 (Cabinet Power System) integrates

More information

OPERATING MANUAL BDP600 UNIVERSAL BATTERY DISTRIBUTION PANEL

OPERATING MANUAL BDP600 UNIVERSAL BATTERY DISTRIBUTION PANEL BDP600 UNIVERSAL BATTERY DISTRIBUTION PANEL www.unipowerco.com Manual No. BDP600-2 bdp600-man-rev2-0416.indd 2016 UNIPOWER LLC All Rights Reserved NORTH AMERICA 3900 Coral Ridge Drive, Coral Springs, Florida

More information

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company Manufacturer of Dimensions Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com OWNERS MANUAL April

More information

DC to AC Power Inverters

DC to AC Power Inverters Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com ISO 9001:2000 Certified

More information

DC to AC Power Inverters

DC to AC Power Inverters Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121114C OWNERS

More information

BLADE TERMINAL AND SPECIAL PURPOSE FUSES

BLADE TERMINAL AND SPECIAL PURPOSE FUSES BLADE TERMINAL AND SPECIAL PURPOSE FUSES LOW VOLTAGE ATO Fuse Fast-Acting Type U L Designed and originated by Littelfuse for the automotive industry, the ATO fuse has become the original equipment circuit

More information

MIL-24/2600Q MIL-24/3200DQ

MIL-24/2600Q MIL-24/3200DQ Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121473B OWNER'S

More information

miconverter 18-Module Rack-Mount Power Chassis User Manual 38 Tesla, Irvine, CA USA Phone: (949) ; Fax: (949) Page 12

miconverter 18-Module Rack-Mount Power Chassis User Manual 38 Tesla, Irvine, CA USA Phone: (949) ; Fax: (949) Page 12 miconverter 18-Module Rack-Mount Power Chassis User Manual Page 12 38 Tesla, Irvine, CA 92618 USA Phone: (949) 250-6510; Fax: (949) 250-6514 General and Copyright Notice This publication is protected by

More information

nrgsmart Power Distribution Remote Monitoring

nrgsmart Power Distribution Remote Monitoring nrgsmart Power Distribution Remote Monitoring nrgsmart is remote monitoring at the individual circuit level. Software and hardware, joined. Actionable network analytics. For the first time. Ever. nrg600bt10

More information

Installing the Switch Chassis

Installing the Switch Chassis Safety, page 1 Installation Options with Racks and Cabinets, page 2 Airflow Considerations, page 2 Installation Guidelines, page 2 Unpacking and Inspecting the Switch, page 3 Installing the Switch, page

More information

Unity Low Voltage Disconnect & Monitor

Unity Low Voltage Disconnect & Monitor Unity Low Voltage Disconnect & Monitor Installation/Operation Manual Model: ULM-100 Table of Contents Page Table of Contents Page 1.0 Overview 2 5.14 LVD Level Mapping 4 2.0 Materials Provided 2 5.2 Meter

More information

Lighting Control Unit Installation Instructions

Lighting Control Unit Installation Instructions Lighting Control Unit Installation Instructions DOC. #560066000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements

More information

NTK599BAE5 and NTK599BGE5 Breaker Interface Panel (BIP) Installation Manual

NTK599BAE5 and NTK599BGE5 Breaker Interface Panel (BIP) Installation Manual IMK599BAE5 Issue 5 December 2011 NTK599BAE5 and NTK599BGE5 Breaker Interface Panel (BIP) Installation Manual 19981-B 1294798 Rev E Preface COPYRIGHT All Rights Reserved Printed in the U.S.A. REVISION HISTORY

More information

Secondary DC Distribution

Secondary DC Distribution GE Critical Power Secondary DC Distribution -48V Battery Distribution Bay 24 Inches Deep, BDFB / BDCBB Overview The GE Battery Distribution Fuse Bay (BDFB) or Battery Distribution Circuit Breaker Bay (BDCBB)

More information

Switching DC Power Supply

Switching DC Power Supply 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Model 1693, 1694 Switching DC Power Supply INSTRUCTION MANUAL 1 Safety Summary

More information

WAVETRAX USER MANUAL

WAVETRAX USER MANUAL WAVETRAX USER MANUAL 107719-2A0 WAVETRAX User Manual Document Number 107719-1A0 Copyright 2001, Telect, Inc., All Rights Reserved. Telect and Connecting the Future are registered trademarks of Telect,

More information

DC Distribution Panel User Guide # S

DC Distribution Panel User Guide # S DC Distribution Panel User Guide # S2-61256-100 68-11926-100 Standard Limited Hardware Warranty LIMITED WARRANTY. Equipment manufactured by CTI Products, Inc. is warranted to be free from defects in material

More information

24/3000H-3PH 24/4500H-3PH 24/6000H-3PH

24/3000H-3PH 24/4500H-3PH 24/6000H-3PH Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 120015D OWNERS

More information

5067 Mini BDFB / BDCBB

5067 Mini BDFB / BDCBB PRODUCT OVERVIEW 5067 Mini BDFB / BDCBB Up to 4 Loads, 600 Amps per Load Compact unit can be placed at the point of load High density models available with 48 circuits in 16RU Digital metering, extended

More information

Shelf 19 version) (Expansion Shelf 19 version) (Main Shelf 23 version) (Expansion Shelf 23 version)

Shelf 19 version) (Expansion Shelf 19 version) (Main Shelf 23 version) (Expansion Shelf 23 version) SYSTEM OVERVIEW Description: +24VDC to -48VDC @ up to 375A converter system. The NetSure DCS48375 Converter System is comprised of a main shelf and up to two (2) expansion shelves. Each shelf provides

More information

IMPORTANT SAFEGUARDS

IMPORTANT SAFEGUARDS INSTRUCTION MANUAL NON-INTERRUPTIBLE AC INVERTER SYSTEM MODEL EAC FTM 350 FOR EMERGENCY LIGHTING POWER IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed,

More information

RU SERIES UPGRADE TempAssure Compatible

RU SERIES UPGRADE TempAssure Compatible RU SERIES UPGRADE TempAssure Compatible This converter section has been designed as a converter section replacement in the following MagneTek or Parallax Power Supply series products and models with DC

More information

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-10 ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS Features: Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit Protection Standby Battery

More information

OWNERS MANUAL JANUARY 2007 ISO

OWNERS MANUAL JANUARY 2007 ISO Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com OWNERS MANUAL JANUARY

More information

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

M9206-GGx-2S Series Proportional Electric Spring Return Actuators Installation Instructions M9206-GGx-2S Issue Date November 17, 2004 M9206-GGx-2S Series Proportional Electric Spring Return ctuators pplications The M9206-GGx-2S Series Proportional ctuators are direct-mount,

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

VA9203-AGx / VA9203-Bxx / VA9203-GGx

VA9203-AGx / VA9203-Bxx / VA9203-GGx V9203-Gx / V9203-xx / V9203-GGx Spring Return ctuators Product ulletin The V9203 Series Electric Spring Return ctuators are direct-mount actuators. These bidirectional actuators are used to provide accurate

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

Product Manual Select Code Comcode Issue 9 September Secondary DC Power Distribution Bay H

Product Manual Select Code Comcode Issue 9 September Secondary DC Power Distribution Bay H Product Manual Select Code -00- Comcode 0 Issue September 00 Secondary DC Power Distribution Bay H- Product Manual Select Code -00- Comcode 0 Issue September 00 Secondary DC Power Distribution Bay H-

More information

Patient Care Facility

Patient Care Facility ISIMET Patient Care Facility DLA Controller Individual Room Configuration Style 1 W/ Ver 4.41 pcb & Pulse Relay pcb Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for

More information

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions ISIMET Drug Testing Labs DLA Controller Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions Meets all Standards for Canadian Industrial Control

More information

1370 DC Loop Contactors and Lug Kits

1370 DC Loop Contactors and Lug Kits Installation Instructions 1370 DC Loop Contactors and Lug Kits 1370 DC Contactors are electromagnetically held contactors specially designed to switch the armature current from a DC drive module to a shunt

More information

MANSI CLS Series LPG/CNG Closed Loop System with Harness and Actuator Motor

MANSI CLS Series LPG/CNG Closed Loop System with Harness and Actuator Motor MANSI CLS Series LPG/CNG Closed Loop System with Harness and Actuator Motor ratio(afr) is efficiently controlled to minimize emissions, maximize efficiency and improve mileage. This product features extremely

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally 38.18.The red wire on the OCR plug carries battery voltage. Behavior: D.C. battery voltage should show-up on a volt meter when the red probe is touched to this terminal and the black probe is grounded,

More information

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A) TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29499-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the user

More information

Fuse and Distribution Module

Fuse and Distribution Module Charles Industries, Ltd. Section 428 500 204 Equipment Issue 4 Fourth Printing, July 1999 4285 00 Fuse and Distribution Module CLEI Code: PWPQW021AA CONTENTS PAGE Part 1. GENERAL.............................................................................

More information

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE MODEL A96 SERIES 130Vdc Switchmode Utility Rectifier / Battery Charger Used with LaMarche Power Cage CPN112138 ECN/DATE ISSUE DATE: ECN 17010-12/05 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847)

More information

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation Instructions M9206-Bxx-2S Issue Date May 14, 2003 M9206-Bxx-2S Series On/Off Electric Spring Return Actuators Installation IMPORTANT: Use this M9206-Bxx-2S Series actuator to control equipment

More information

Raritan PX. Power Cord Installation Guide. Safety Guidelines. Safety Instructions

Raritan PX. Power Cord Installation Guide. Safety Guidelines. Safety Instructions QS Rule Raritan PX Power Cord Installation Guide This installation guide explains how to install power cords on Raritan PX products that do not come with a factory installed power cord. This type of product,

More information

A25 Series Warm Air Control with Manual Reset

A25 Series Warm Air Control with Manual Reset FANs 125, 121 Product/Technical Bulletin A25 Issue Date 0316 A25 Series Warm Air Control with Manual Reset The A25 Series Warm Air Control with Manual Reset is designed to shut down fans, burners, dampers,

More information

Power and Cooling. Chassis Power System

Power and Cooling. Chassis Power System This chapter describes the Cisco NCS 6000 Series Routers power and cooling systems. It also provides the power, grounding, and cooling requirements for the installation site to help you plan the site facilities

More information

BREAK-SAFE Load Break & Pick-up Tool

BREAK-SAFE Load Break & Pick-up Tool BREAK-SAFE Load Break & Pick-up Tool USBS-15-1-PS USBS-27-1-PS USBS-46-1-PS USBS-15-2-PS USBS-27-2-PS USBS-46-2-PS Available Options: H - Hard Case S - Soft Case Second Generation Models Only. For tools

More information

ADI-125/750 ADI-125/1500 ADI-125/2500

ADI-125/750 ADI-125/1500 ADI-125/2500 Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121094B OWNERS

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Installation and Operation Manual. LD LED Dimmer

Installation and Operation Manual. LD LED Dimmer Installation and Operation Manual LD12-002 LED Dimmer SM85 ISSUE 1.00 Northern Airborne Technology Ltd. 1925 Kirschner Road Kelowna, BC, Canada. V1Y 4N7 Telephone (250) 763-2232 Facsimile (250) 762-3374

More information

Outdoor Enclosure Power System ENC X100MP48F20-AC6

Outdoor Enclosure Power System ENC X100MP48F20-AC6 Outdoor Enclosure Power System ENC673034-1X100MP48F20-AC6 Manual MA015151A4 Issue 1 Nov 2010 Copyright 2010 Myers Power Products, Inc. Part# A015151A4 MA015151A4 Iss1 Page 1 of 24 Dimensions Outdoor Enclosure

More information

Circuit Breakers/Protection, Fuses/Fuse Products

Circuit Breakers/Protection, Fuses/Fuse Products Circuit Breakers/Protection, Fuses/Fuse Products CRCUT BREAKERS/PROTECTON, PAGES 169-172 FUSES/FUSE PRODUCTS, PAGES 174-182 i Understanding Type 1, Type 2 & Type 3 Circuit Breakers Type 1 Automatic Reset

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 1 27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2 STX2401-C STX2401-T FEATURES 0843-CPR-0213 14 Elmdene International Ltd Tel: +44(0)23 9269 6638 3 Keel Close, Interchange Park, Fax:

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

E.S.P. Embedded Sensing Probes for Motor Brushes

E.S.P. Embedded Sensing Probes for Motor Brushes E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com

More information

BREAK-SAFE Load Break & Pick-up Tool

BREAK-SAFE Load Break & Pick-up Tool BREAK-SAFE Load Break & Pick-up Tool USBS-15-1-PS USBS-15-2-PS USBS-27-1-PS USBS-27-2-PS USBS-38-1-PS USBS-38-2-PS USBS-46-1-PS USBS-46-2-PS Available Options: H - Hard Case S - Soft Case Second Generation

More information

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual Combiner Box Installation & Operations Manual SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual TABLE OF CONTENTS Notices and Safety Precautions Pages 1-2 Combiner

More information

5067 Mini-BDFB Battery Distribution Fuse Bay

5067 Mini-BDFB Battery Distribution Fuse Bay Installation Guide! 5067 Mini-BDFB Battery Distribution Fuse Bay -48 VDC @ 600 Amps per Load TPS Fuse / Circuit Breaker Distribution, 23 With VIM2 meter 1 Fuse / Breaker Positions Total Per Battery Bus

More information

Installation Instructions

Installation Instructions AQU244 & AQU128 Series Installation Instructions Installation Instructions AQU244 24vdc 5A Supervised Power Supply/Charger module AQU128 12vdc 10A Supervised Power Supply/Charger module Both Mounted in

More information

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Defender 1 8.0KW to 14.0KW Online Lighting Inverter Technical Manual #018-0102-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail:

More information

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B Users Manual Cobra Plus Stand-By Lighting Inverter Technical Manual #018-0110-01 Revision B Phone: 1.877.DSPM.POWER 1.877.377.6769 Fax: 909.930.3335 Website: www.dspmanufacturing.com E-Mail: techsupport@dspmanufacturing.com

More information

Instruction Book for. ContouR ElECtRol

Instruction Book for. ContouR ElECtRol Instruction Book for ContouR ElECtRol IMPORTANT SAFETY INSTRUCTIONS When using your video equipment, basic safety precautions should always be followed, including the following: 1. Read and understand

More information

AccuPower AQU128B Installation Instructions

AccuPower AQU128B Installation Instructions Tel 1.800.MAGLOCK info@securitron.com 1.800.624.5625 www.securitron.com AccuPower AQU128B Installation Instructions Recommended Tools & Additional Materials #2 Phillips Screw Driver Wire connectors Lead

More information

OWNERS MANUAL JANUARY 2007 ISO

OWNERS MANUAL JANUARY 2007 ISO Manufacturer of Dimensions TM Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000 Fax: 651-653-7600 E-mail: inverterinfo@sensata.com Web: www.dimensions.sensata.com 121231B OWNERS

More information

RSDCOM. Installation and Operation Guide. Commercial Rapid Shutdown Combiner. DOCR Published March 2017 Revision C English

RSDCOM. Installation and Operation Guide. Commercial Rapid Shutdown Combiner. DOCR Published March 2017 Revision C English f Commercial Rapid Shutdown Combiner RSDCOM Installation and Operation Guide Models: RSDCOM M-PC-1Z-4F RSDCOM M-PC-1Z-4F-24V RSDCOM M-PC-1Z-5F RSDCOM M-PC-1Z-5F-24V RSDCOM M-FG-2Z-4F RSDCOM M-FG-2Z-4F-24V

More information

Installation and Operations Manual

Installation and Operations Manual Installation and Operations Manual SEI 150/48-SEL-XXX DC-UPS SEI Incorporated 5115 Pegasus Court, Suite Q Frederick, Md 21704 Phone 301-694-9601 Fax 301-694-9608 Email Info@seipower.com Web http://www.seipower.com

More information

LB LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS

LB LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS LB-60-30 LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS 4031 W Kiehnau Ave Milwaukee, WI 53209 CAUTION THIS LOAD BANK IS DESIGNED FOR THE TESTING AND SERVICING

More information

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator. Technical Information and Diagnostic Guide for SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator. This guide will assist you in becoming more

More information