MV100 Series Compact Vector Control Drive Quick Start and Installation Manual

Size: px
Start display at page:

Download "MV100 Series Compact Vector Control Drive Quick Start and Installation Manual"

Transcription

1 MV1 Series Compact Vector Control Drive Quick Start and Installation Manual Document Version: V1. Archive Date: 214/5/9 BOM Code: R33115 Shenzhen Megmeet Drive Technology Co., Ltd. provides full technical support for our customers,customers can contact local Megmeet offices or customer service centers, or directly contact Megmeet headquarters. Shenzhen Megmeet Drive Technology Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Shenzhen Megmeet Drive Technology Co., Ltd. Address: 5th Floor, Block B, Unisplendor Information Harbor, Langshan Rd., Science & Technology Park, Nanshan District, Shenzhen, 51857, China Website: Tel: Fax: Service 1

2 Foreword Thank you for choosing the MV1 series compact vector control variable speed drive of Shenzhen Megmeet Drive Technology Co., Ltd. MV1 drive with a new hardware design platform that integrates V / F and no PG vector control mode, provide excellent motor driving performance, this series of drive with excellent performance, perfect functions, compact structure, convenient installation, simple debugging, easy maintenance, is the cost-effective products for drive generic and OEM markets. The relevant precautions during the installation, wiring, parameter setting and troubleshooting will be detailed in this manual. To ensure the correct installation and operation of the MV1 series drive as well as its high performance, please read carefully this user manual before installing the equipment. This manual shall be kept properly and delivered to the actual users of the drive. Safety Precautions Operation without following instructions can cause death or severe personal injury. Operation without following instructions can cause medium or slight personal injury or damage to the product and other equipment. Please install the product on the incombustible materials (e.g., metal), do not place any combustible material near the product, otherwise, fire may be caused. Do not install the product in the environment with explosive gas, otherwise, explosion may be caused. Only qualified personal can wire the drive, Never wire the drive unless the input AC supply is completely disconnected The grounding terminal of the drive must be reliably grounded, do not operate the drive with wet hands, maintaince operation can not be conducted until 1 minutes has passed after disconnecting the power supply, the bare parts of the terminal lugs in the main circuit must be wrapped with insulation tape, otherwise, electric shock may be caused. When powering up the drive that has been stored for over 2 years, the input voltage must be gradually increased with the voltage regulator, otherwise, electric shock and explosion may be caused. Only qualified personal can replace the components. Do not leave any wire or metal parts inside the drive, otherwise, fire may be caused. After changing the control board, the parameters must be properly set before operating the drive, otherwise, property damage may be caused. 2

3 Do not install the drive in the environment with water splash (e.g., near the water pipe), otherwise, you may suffer the property loss. Do not install and operate the drive if it is damaged or its components are not complete, otherwise, fire and human injury may be caused. Do not install the product in the place exposed to direct sunlight, otherwise, property damage may be caused. Do not short circuit terminal PB and terminal DC or +DC, otherwise, fire and property damage may be caused. Cable lugs must be firmly connected to the terminals of main circuit, otherwise, property damage may be caused. Do not connect AC 22V input to the control terminals other than terminal TA, TB, TC otherwise, property damage may be caused. 3

4 Contents MV1 Series Compact Vector Control Drive... 1 Chapter 1 Introduction of MV1 Drive Product model and nameplate Technical specifications of product Outline, mounting dimensions and gross weight of drive Outline and mounting dimensions of operation panel... 1 Chapter 2 Wiring of Drive Wiring and configuration of main circuit terminals Wiring and configuration of control circuit Chapter 3 Operation Panel Chapter 4 Parameter List Chapter 5 Troubleshooting

5 Chapter 1 Introduction of MV1 Drive 1.1 Product model and nameplate Product model ~ ZZ ~ ZZ.4kW ~3.7kW Product nameplate 5

6 1.2 Technical specifications of product Various series power specifications Drive model Table 1-1 Three-phase 38V series power specifications Three-phase 38V series MV1G-4T.75 MV1G-4T1.5 MV1G-4T2.2 MV1A-4T.4 MV1A-4T.75 MV1A-4T1.5 MV1A-4T2.2 MV1G-4T3.7 Applicable motor power Applicable motor power Input current Rated voltage.4kw.75kw 1.5kW 2.2kW 3.7kW.5HP 1HP 2HP 3HP 5HP 1.9A 3.2A 4.3A 7.1A 11.2A Three-phase 38~48V Input Power Output Voltage fluctuation range Rated Frequency fluctuation range Rated capacity Rated current Output voltage Output Carrier Overload capacity ±1%(342~528V) 5Hz/6Hz ±5%(47~63Hz) 1.2KVA 2KVA 3.3KVA 4.4KVA 6.8KVA 1.5A 2.5A 4.2A 5.5A 8.5A ~ the corresponding three-phase input voltage, the error is less than ± 3% V/F:.~2.Hz (unit:.1hz); vector control: ~65.Hz.7~15KHz 1 min for 15% rated current,.5 s for 2% rated current Cooling mode Forced air cooling 6

7 Table 1-2 Single-phase 22V series power specifications Single-phase 22V series Drive model MV1G-2S.4 1 MV1G-2S.75 1 MV1G-2S1.5 MV1G-2S2.2 Applicable motor power.4kw.75kw 1.5kW 2.2kW Applicable motor power.5hp 1HP 2HP 3HP Input current 6.5A 9.7A 15.4A 24A Input Power Rated voltage Voltage fluctuation range Rated Frequency fluctuation range Single-phase 2~24V ±1%(18~264V) 5Hz/6Hz ±5%(47~63Hz) Rated capacity 1KVA 1.6KVA 2.9KVA 4.2KVA Rated current 2.5A 4.2A 7.5A 11A Output voltage ~ the corresponding three-phase input voltage, the error is less than ± 3% Output Output Carrier Overload capacity V/F:.~2.Hz (unit:.1hz); vector control: ~65.Hz.7~15KHz 1 min for 15% rated current,.5 s for 2% rated current Cooling mode Forced air cooling Note: 1 means being developed 7

8 Table 1-3 Three-phase 22V series power specifications Three-phase 38V series Drive model MV1G-2T.4 1 MV1G-2T.75 1 MV1G-2T1.5 MV1G-2T2.2 Applicable motor power.4kw.75kw 1.5kW 2.2kW Applicable motor power.5hp 1HP 2HP 3HP Input current 2.7A 5.1A 9A 15A Input Power Rated voltage Voltage fluctuation range Rated Frequency fluctuation range Three-phase 2~24V ±1%(18~264V) 5Hz/6Hz ±5%(47~63Hz) Rated capacity 1KVA 1.6KVA 2.9KVA 4.2KVA Rated current 2.5A 4.2A 7.5A 11A Output Output voltage ~ the corresponding three-phase input voltage, the error is less than ± 3% Output V/F:.~2.Hz (unit:.1hz); vector control: ~65.Hz Carrier Overload capacity Cooling mode Note: 1 means being developed Control Specifications Control mode.7~15khz 1 min for 15% rated current,.5 s for 2% rated current Forced air cooling Table 1-4 Control Specifications Vector control without PG, V/F control without PG Operation control features Product functions Maximum output Speed adjusting range Speed control precision Speed fluctuation Torque response Torque control Startup torque Key functions Basic Startup Frequency setting mode Acceleration/deceleration time 2.Hz for V/F control, 65.Hz for vector control 1: 2 (vector control without PG) ±.2% (vector control without PG) ±.3% (vector control without PG) <1ms (vector control without PG) The torque control precision is 7.5% when vector control without PG Hz (vector control without PG) Fast tracking, torque limit, multi-stage speed operation, auto-tuning, skip operation, PID adjustment, non-stop upon instantaneous power interruption, switching of multi-command, MODBUS communication, torque control, torque and speed control mode switching, automatic restart, DC braking, dynamic braking, dwell function.1hz~2.hz.hz~6.hz Digital panel setting, terminal UP/DN setting, host device communication setting, analog setting (AI1/AI2/), terminal pulse setting.1~36. (unit can be selected among.1s, s and min) 8

9 Dynamic braking capacity Built-in braking unit, braking rate.~1.% DC braking capacity Initial :.Hz~6.Hz Braking time:.1s~3.s Braking current: %~1% Protection function Overcurrent, overvoltage, undervoltage, overheat, overload protection, etc. Others Efficiency 93% Environment Installation method Protection degree Cooling mode Operating site Altitude Ambient temperature Humidity Vibration Storage temperature Wall-mounted IP2 Air cooling Indoor, away from direct sunlight, free from corrosive gas, combustible gas, oil mist, water vapor, water dripping or salt Used at the place lower than 1m, (derated at the place above 1m, derated 1% for every increase of 1m) -1 ~+4 (derated when used in the ambient temperature of 4 ~5 ) 5%~95%RH, non-condensing less than 5.9m/s2(.6g) -4 ~ Outline, mounting dimensions and gross weight of drive Fig. 1-1 Outline, mounting dimensions for products 9

10 Table 1-5 Outline, mounting dimensions and gross weight Enclosure Diameter of Gross weight model A(mm) B(mm) H(mm) W(mm) D(mm) mounting aperture (mm) ±.5 (kg) G1R G1R Table 1-6 Model list Series.4kW.75kW 1.5kW 2.2kW 3.7kW Three-phase 38V Single-phase 22V Three-phase 22V MV1G-4T.75 MV1G-4T1.5 MV1G-4T2.2 MV1G-4T3.7 MV1A-4T.4 MV1A-4T.75 MV1A-4T1.5 MV1A-4T2.2 MV1G-2S.4 1 MV1G-2S.75 1 MV1G-2S 1.5 MV1G-2S2.2 MV1G-2T.4 1 MV1G-2T.75 1 MV1G-2T1.5 MV1G-2T2.2 Note: In the table 1-6 without shading part of the product corresponding enclosure model G1R1, with shading part of the product corresponding enclosure model G1R2. Note: 1 means being developed 1.4 Outline and mounting dimensions of operation panel Fig. 1-2 Outline and mounting dimensions of operation panel 1

11 Chapter 2 Wiring of Drive 2.1 Wiring and configuration of main circuit terminals Terminal type 1 Applicable models: Three-phase 38V or 22V Series Terminal type 2 Applicable models: Single-phase 22V Series Terminal R/L1,S/L2,T/L3 L N +DC +DC PB -DC U/T1,V/T2,W/T3 Three-phase AC 38Vor 22V input terminals Single-phase AC 22V input terminals DC positive bus output terminal Reserved terminals for an external braking resistor (configuration information of built-in braking unit refer to Table 1-6) DC negative bus output terminals Three-phase AC output terminals Safety grounding terminal 11

12 Recommended fuse capacity and cross section area of the copper-cored insulation wire Table 2-1 Recommended fuse capacity and cross section area of the copper-cored insulation wire MCCB circuit Main circuit (mm 2 ) Control Series Drive model breaker (A) Input wire Brake wire Output wire Ground wire circuit (mm 2 ) MV1A-4T Three-phase 38V Single-phase 22V Three-phase 22V Note: 1 means being developed MV1G-4T.75,MV1A-4T MV1G-4T1.5,MV1A-4T MV1G-4T2.2,MV1A-4T MV1G-4T MV1G-2S MV1G-2S MV1G-2S MV1G-2S MV1G-2T MV1G-2T MV1G-2T MV1G-2T Recommended braking resistor specifications Braking resistor connected between PB and + DC, the selection is as shown in the following table. Table 2-2 Recommended braking resistor specifications and configuration Utilization Braking torque Maximum continuous Series Drive model Specification (%) (%) use time(s) MV1A-4T.4 4Ω/3W Three-phase 38V Single-phase 22V Three-phase 22V MV1G-4T.75,MV1A-4T.75 4Ω/3W MV1G-4T1.5,MV1A-4T1.5 3Ω/5W MV1G-4T2.2,MV1A-4T2.2 2Ω/65W MV1G-4T Ω/1W MV1G-2S Ω/18W MV1G-2S Ω/25W MV1G-2S1.5 7Ω/4W MV1G-2S2.2 5Ω/6W MV1G-2T Ω/18W MV1G-2T Ω/25W MV1G-2T1.5 7Ω/4W MV1G-2T2.2 5Ω/6W Note: 1 means being developed 12

13 Wiring for basic operation Fig. 2-1 Basic wiring diagram 1 Fig. 2-1 applicable models: Three-phase 38V or 22V series 13

14 Fig. 2-2 Basic wiring diagram 2 Fig. 2-2 applicable models: single-phase 22V series Note: in the figure is main circuit terminal and in the figure is control circuit terminal. 2.2 Wiring and configuration of control circuit The arrangement sequence diagram of the control circuit terminals Wiring of control circuit terminals 14

15 It is suggested to use the wire with cross section area over 1mm 2 as the connecting wire of the control circuit terminals. Control terminal function Table 2-3 Control terminal function Terminal Specifications and others GND +1 AI1 AI2 AO1 AO2 +RS485- COM P24 X1 X2 X3 X4 X5 PLC The ground for +1 V power, analog Internal isolated with COM signals and communication signals To provide +1V power for external Allowable maximum output current: 1mA load( grounding: GND) Analog input, voltage/current is selected via the Input voltage range:~1v (input resistance: 2kΩ) jumper( grounding: GND) Input current range: ~2mA (input resistance: 246Ω) Analog output, voltage/current is selected via the Voltage output range: /2~1V jumper( grounding: GND) Current output range: /4~2mA RS485 communication interface, differential signal "+" Indicates the positive end, "-" indicates the negative ( grounding: GND) end, use twisted pair wire or shielded wire. The ground for 24V power, Internal isolated with GND, CME multi-function input To provide +24V power for external Maximum output current: 2mA load( grounding: GND) Input resistance: R=2kΩ High-speed pulse multi-function inputs, Maximum input frequendy: 1kHz opto-isolated inputs (common terminal: PLC). Input voltage range: 2V~3V Input resistance: R=3.1kΩ Common signal multi-function input, opto-isolated Maximum input frequendy: 2kHz inputs (common terminal: PLC or COM). Input voltage range: 1V~3V Short with P24 upon delivery Multi-function input terminal common terminal Common terminal for X1~X5, internal isolated with P24 CME Multi-function output common terminal Internal isolated with COM PLC GND Opto-isolated output Y1 Y2 TA TB TC Open collector output terminal 1 / DO pulse output terminal(common terminal: COM) Open collector output terminal 2(common terminal: CME) Relay output Maximum operating voltage: 3V Maximum output current: 5mA The DO pulse output range depends on P9.23 and the maximum is 5kHz Opto-isolated output Maximum operating voltage: 3V Maximum output current: 5mA TA-TB: normally closed; TA-TC: normally open Contact capacity: AC 25V/2A(COSФ=1) AC 25V/1A(COSФ=.4) DC 3V/1A 15

16 Panel appearance Chapter 3 Operation Panel Fig. 3-1 Panel appearance Panel function description Table 3-1 Panel function description Panel structure Panel function name and description of each part MENU/ESC: Program/exit key : Increase key ENTER/DATA: /data key Keys M:Multi-functional key : Decrease key : Shift key STOP/RESET: Stop/reset key RUN: Run key Digital tube Potentiometer Display the function number and content or other parameters Run setting Status lights FWD: forward indicator REV: Reverse Indicator Unit lights Hz: Frequency Indicator A: Current indicators V:Voltage Indicator Panel operation example MENU ESC > 5. P. P. P2. P2. MENU ESC ENTER DATA > ENTER DATA > 25. P P2.4 Fig. 3-2 Operation example for setting the set 16

17 Chapter 4 Parameter List Explanation to the terms in the function parameter table Table field Explanation Representing the number of the function, e.g. P. number of the function, explaining it name Leave-factory The of the function after restoring the leave-factory settings P.2 P.3 Parameter initialization Parameter copy : Parameter changing status 1: Clear fault memory information 2: Restore to leave-factory : Disabled 1: Uploading parameter 2: Downloading parameters 3: Downloading parameters (except the motor parameters) Note: The drive parameters will not be Set range The minimum and maximum s of the function allowed to set uploaded/downloaded V: voltage; A: current; : temperature; Ω: resistance; mh: inductance; Unit place: Manufacturer commissioning Unit rpm: rotate speed; %: percentage; bps: baud rate; Hz/ khz: ; ms/s/min/h/kh: time; kw: power : Means the function can be changed during running; : Means the Property function can be changed in the stop state; *: Means the function can be read only, can not be changed Basic menu function parameter table Group P: System management User : No password P. password Other: Password protection P.4 Selection of key functions Tens place: selection of the STOP/RESET key : The STOP key is valid only in the panel control mode 1: The STOP key is valid in all control modes Note: The RESET key is valid in any control mode Hundreds place: selection of M key : No function 1: JOG 2: FWD/REV 1H : All the data can be changed; 3: Command channel switching 1 (valid 1: Only the main set (digital only in stop status) P.1 Parameter protection setting P2.4) and this function can be changed 1 4: Command channel switching 2 (valid both in stop & running status) 2: Only this function can be 5: Panel locking function changed Thousands place: Panel locking function 17

18 : Lock all the keys BIT1: Analog closed loop (%, 1: Lock all the keys except the STOP key flashing) 2: Lock all the keys except the >> key BIT2: Terminal status (without unit) 3: Lock all the keys except the RUN & BIT3: DC bus voltage STOP key Binary setting: Binary setting: : No display; 1: Display : No display; 1: Display Unit place of LED: Unit place of LED: BIT: Preset (Hz) BIT: Output (Hz) BIT1: Running speed (r/min) BIT1: Preset (Hz,flashing) BIT2: Preset speed (r/min) P.5 LED display parameter selection 1 when running BIT2: Output current (A) Tens place of LED: BIT: Running rotating speed (r/min) BIT1: Set rotating speed (r/min, flashing) BIT2: Running line speed(m/s) BIT3: Preset line speed (m/s, flashing) 7H P.7 LED display parameter selection when stop BIT3: DC bus voltage (V) Tens place of LED: BIT: Running line speed (m/s) BIT1: Preset line speed (m/s) BIT2: Analog closed loop feedback (%) BIT3: Analog closed (%) 9H Hundreds place of LED: Hundreds place of LED: BIT: Output power BIT: AI1 (V) BIT1: Output toque (%) BIT1: AI2 (V) Note: the default display shall be output BIT2: Reserved when all the parameters are BIT3: Terminal status (without unit) Binary setting: Note: The default display shall be set : No display; 1: Display when all the parameters are P.6 LED display parameter selection 2 when running Unit place of LED: BIT: Output voltage (V) BIT1: AI1(V) BIT2: AI2(V) BIT3: Reserved Tens place of LED: BIT: Analog closed loop feedback (%) H P1. Main channel Group P1: Status display parameters : Disabled 1: Digital 1: Keyboard 2: Digital 2: Terminal UP/DN 3: Digital 3:Serial port 18

19 communication 4: AI analog 5: Terminal PULSE 6: Panel potentiometer 7: Process closed loop PID P1.1 Main set -2.~2.Hz. P1.2 Auxiliary set -2.~2.Hz. P1.3 Set -2.~2.Hz. P1.4 Output -2.~2.Hz. P1.5 Output ~48V voltage P1.6 Output current.~3ie. P1.7 Output torque -3.~+3.%. P1.8 Motor power.%~2.% (relative to the rated. power of the motor) P1.9 Bus voltage ~8V P1.1 Operation state of the drive ~7FFFH: Bit : RUN/STOP Bit 1: REV/FWD Bit 2: Running at zero speed Bit 3: Accelerating Bit 4: Decelerating Bit 5: Running at constant speed Bit 6: Reserved State of digital P1.11 input terminal State of digital P1.12 output terminal AI1 input P1.13 voltage AI2 input P1.14 voltage P1.15 AO1 output P1.16 AO2 output Torque P1.17 X1 terminal pulse P1.18 Radiator 1 P1.19 temperature Bit 7: Tuning Bit 8: Over-current limiting Bit 9: DC over-voltage limiting Bit 1: Torque limiting Bit 11: Speed limiting Bit 12: Drive in fault Bit 13: Speed control Bit 14: Torque control ~FFH, : off; 1: on The high-speed pulse will not be refreshed synchronously ~FH, : open; 1: close The high-speed pulse output will not be refreshed synchronously.~.v..~1.v..~1.%. (percentage relative to the full range).~1.%. (percentage relative to the full range) -3.%~3.% (relative to the rated. torque of the motor).~1.khz. -4.~1.. 19

20 Accumulated P1.2 P1.21 power-on hours Accumulated running hours ~ maximum hours ~ maximum hours Unit place of LED: Main digital saving control : Save when power down 1: Do not save when power down Group P2: Basic parameters Tens place of LED: Main digital P2. P2.1 P2.2 P2.3 P2.4 Control mode selection Running command channel selection Running direction setting Main source selection Digital setting of main Induction motor control mode selection : Vector control without PG 1: V/F control without PG : Keyboard control 1: Terminal control 2: Communication control : Forward running; 1: Reverse running : Digital 1: Keyboard 1: Digital 2: Terminal UP/DN 2 : Digital 3:Serial port communication 3: AI analog 4: Terminal PULSE 5: Panel potentiometer 6: Process closed loop PID P2.14~P P2.5 P2.6 Main & auxiliary digital control Auxiliary source selection control when stop : Maintained when stop 1: Reset P2.4 when stop Hundreds place of LED: Auxiliary digital saving control : Save when power down 1: Do not save when power down Thousands place of LED: Auxiliary digital control when stop : Maintained when stop 1: Reset when stop Note: The unit and tens places are only applicable for P2.3=, 1, 2 hundreds and thousands place are only applicable for P2.6=1, 2, 3 : No auxiliary 1: Digital 1: Keyboard 2: Digital 2: Terminal UP/DN 3: Digital 3: Serial port communication 4: AI analog 5: Terminal PULSE H 2

21 6: Panel potentiometer /deceleration 7: Process closed loop PID time P2.7 P2.8 P2.9 P2.1 P2.11 P2.12 P2.13 P2.14 P2.15 P2.16 P2.17 Digital setting of auxiliary Main/auxiliary calculation Acceleration time Deceleration time Unit of acceleration/d eceleration time Maximum output Upper limit Lower limit Upper limit of skip Lower limit of skip Jog acceleration.~2.hz. : + 1: -.~ ~ :.1s 1: s 1 2: min MAX{5., upper limit 5. P2.13}~ 2.Hz P2.14~P ~P2.13. P2.16~2...~P ~6.s 6. P2.18 Jog interval.~1.s. P2.19 Frequency of jog running.1~5.hz 5. Group P3: Motor parameters P3. Rated power of motor.1~999.9kw Depending on model P3.1 Rated voltage of motor ~ rated voltage of drive(p98.5) Depending on model P3.2 Rated current of motor.1~999.9a Depending on model P3.3 Rated of 1.~2.Hz Depending on model motor P3.4 Rated rotating speed of ~6rpm Depending on model motor P3.5 Power factor of motor.1~1. It shall be used when calculating the Depending on model motor parameters with the nameplates P3.6 Stator resistance of.%~5.% Depending on model motor %R1 P3.7 Leakage inductance of.%~5.% Depending on model motor %X P3.8 Rotator resistance.%~5.% Depending on model 21

22 of motor %R2 Mutual P3.9 inductance of.%~2.% Depending on model motor %Xm P3.1 No-load current (I ) of.1~999.9a Depending on model motor P3.11 Overload protection 2.%~11.% Set action level (%) = motor rated current/ drive rated current 1 Low speed compensation actual action level = set action level (output 1. factor of motor / 3HZ ) Actual converted current of overload protection = sampling current/overload protection action level P3.12 Parameter auto-tuning : Disabled 1: Enabled (motor in static status) 2: Enabled (motor in rotate status) 3: Reserved (according to the nameplate setting) Group P5: Vector and torque control parameters P5. ASR1-P.1~2. 2. P5.1 ASR1-I.~1.s.2 P5.2 ASR switching 1.%~5.% 1. P5.3 ASR2-P.1~2. 2. P5.4 ASR2-I.~1.s.6 P5.5 ASR switching 2.%~1.% 2. P5.6 Speed/torque : Speed control mode control mode 1: Torque control mode : AI P5.7 Torque 1: Terminal PULSE 2: Communication selection 3: Closed loop output 4: Digital P5.8 Digital of -3.%~3.%. torque P5.9 Electric torque.%~+3.% 18. limit P5.1 Braking torque limit.%~+3.% 18. P5.11 FWD speed limit.%~+1.% 1. P5.12 REV speed limit.%~+1.% 1. Group P7: VF control parameters P7. : User-customized V/F curve 3: 1.2 times power curve Motor V/F 1: 2 times power curve curve setting 2: 1.7 times power curve Motor V/F P7.1 2 P7.3~P2.12. P7.2 Motor V/F P7.4~1.%. 22

23 voltage 2 P7.3 Motor V/F 1.~P7.1. P7.4 Motor V/F voltage 1.~P7.2. P7.5 Motor torque increase.%~3.%. P7.6 Motor torque increase.%~5.%(corresponds to P3.3) 1. cut-off point P7.7 Motor stable factor ~255 1 P7.8 AVR function : Disabled 1: Always enabled 2: Disabled only in deceleration situation 2 Group P8: Start and stop control parameters : Start from the startup 1: Start from the startup after P8. Startup mode braking 2: Start after speed tracking (including the judgment of direction) P8.1 Startup.~MIN(P2.13,6.). P8.2 Startup.~1.s. retention time P8.3 Startup DC braking current.% ~ 1.% of the rated current of the drive. Startup DC P8.4 braking time P8.5 Stop mode Stop P8.6 detection Stop P8.7 detection retention time Stop speed P8.8 detection mode Initial for P8.9 stop DC braking Waiting time P8.1 for stop DC braking Stop DC P8.11 braking current Stop DC P8.12 braking time Selecting P8.13 restart function upon. (Disabled)..1~3.s : Decelerate to stop 1: Coast to stop 2: Decelerate to stop + DC braking.~15.hz.5.~1.s. : Speed set (the only one detection mode under the V/F mode) 1 1: Speed detection.~min(p2.13,6.)..~1.s..% ~ 1.% of the rated current of the. drive. (Disabled)..1~3.s : Disabled 1: Enabled 23

24 power fault P8.14 Waiting time for restart upon power fault.~36.s. : Reverse operation is allowed P8.15 command) Anti-reverse 1: Reverse operation is prohibited (run at selection zero upon reverse running Use ratio of P8.16 dynamic.~1.%. braking Braking 38V Model: 7~78V 75 P8.17 startup voltage 22V Model: 33~37V 35 Group P9: Digital input/output parameters : No function P9. selection of 1: Forward running (FWD) input 2: Reverse running (REV) 1 terminals X1 3: External jog forward running control input P9.1 selection of 4: External jog reverse running control input input 2 terminals X2 5: Three-wire operation control 6: Multi- terminals 1 P9.2 selection of 7: Multi- terminals 2 input 8: Multi- terminals 3 P9.3 terminals X3 9: Multi- terminals 4 1~11: Reserved P9.4 selection of input terminals X4 selection of input terminals X5 12: Main pulse input (valid only for X1) 13: Auxiliary pulse input (valid only for X1) 14: Frequency increase command (UP) 15: Frequency decrease command (DN) 16: External fault normally open input 17: External fault normally closed input 18: External interrupt normally open contact input 19: External interrupt normally closed contact input 2~21: Reserved 22: External reset (RESET) input 23: Coast to stop input (FRS) 24: Acceleration/deceleration disable command 25: Stop DC braking input command 26~28: Reserved 29:Closed-loop disabled 3~33: Reserved 34: Main source selection 1 35: Main source selection 2 36: Main source selection 3 37: Switching main to AI 38: Command source selection 1 24

25 39: Command source selection 2 eceleration 4: Switching command to terminal rate 41: FWD disabled 42: REV disabled P9.7 Terminal filtering time ~5ms 1 43: Drive running disabled Maximum 44: External stop command (it is valid for all the control modes, the device will be P9.8 input pulse.1~1.khz 1. P9.5 P9.6 FWD/REV running mode setting Terminal UP/DN acceleration/d stopped in accordance with the current stop mode) 45: Auxiliary reset 46: Reserved 47: Speed control and torque control switching terminal 48~52: Reserved 53: Torque pulse input terminal (valid only for X1) 54~59: Reserved 6: Emergency stop 61~73: Reserved 74: PID pulse input (valid only for X1) 75: PID feedback pulse input (valid only for X1) : Two-wire control mode 1 1: Two-wire control mode 2 2: Three-wire running control 1 3: Three-wire running control 2.1~99.99Hz/s 1. P9.9 P9.1 P9.11 P9.12 Pulse central point selection Pulse filtering time Input terminal enabled status setting Virtual input terminal : Without central point 1: With central point, it is (P9.8)/2. It is positive when the is less than the central point 2: With central point, it is (P9.8)/2. It is positive when the is larger than the central point.~1.s.5 Binary setting: : Normal logical, enabled upon connection 1: Inverted logical, enabled upon disconnection H Unit place of LED: BIT~BIT3: X1~X4 Tens place of LED: BIT~BIT3: X5 Binary setting: H : Disabled 25

26 setting 1: Enabled terminal : Enabled upon connection Unit place of LED: enabled 1: Enabled upon disconnection BIT~BIT3: X1~X4 status setting Unit place of LED: Tens place of LED: BIT~BIT3:Y1 Y2 R1 Output BIT~BIT3: X5 P9.18 Relay R output delay.1~1.s.1 P9.13 selection of Multi-function al output : Open collector output terminal Y1 1: DO terminal output P9.19 Frequency arrival (FAR) detection.~p terminal Y1 width P9.14 Open collector output : Drive in running state signal (RUN) 1: Frequency arrival signal (FAR) P9.2 FDT level upper limit P9.21~P P9.15 P9.16 terminal Y1 Open collector output terminal Y2 Relay R1 output function selection 2: Reserved 3: Frequency level detection signal (FDT) 4: Reserved 5: Overload detection signal (OL) 6: Lockout for under-voltage (LU) 7: External fault stop (EXT) 8: Frequency upper limit (FHL) 9: Frequency lower limit (FLL) 1: Drive running at zero-speed 11~14: Reserved 115: Drive ready for running (RDY) 16: Drive fault 17: Host device switch signal 18~19: Reserved 2: Drive FWD/REV indication terminal 21~24: Reserved 1 15 P9.21 P9.22 FDT level lower limit DO terminal output.~p : No function 1: Output 2: Set (~Maximum output ) 3: Output current Iei (~2 * Iei) 4: Output current Iem (~2 * Iem) 5: Output torque (~3 * Tem) 6: Reserved 7: Motor rotating speed (~Maximum output ) 8: Output voltage (~1.5 * Ve) 9: Adjusted AI1(~1V/4~2mA) 1: Adjusted AI2(~1V/4~2mA) 11: Reserved 12: Output power (~2*Pe) P9.17 Output Binary setting: 13~15: Reserved 26

27 P9.23 P9.24 P9.25 P1. P1.1 16: Torque (~3Tem) 17: Percentage of host device (~65535) 18~19: Reserved Maximum output pulse.1~5. 1. : Without central point 1: With central point It is (P9.23)/2. It is positive when the Pulse output is less than the central point central point selection 2: With central point It is (P9.23)/2. It is positive when the is larger than the central point Pulse output.~1.s.5 filtering time Group P1: Analog input/output terminal parameters Unit place: AI1 : Voltage input Analog input 1: Current input H properties Tens place: AI2 : Voltage input 1: Current input Unit place of LED: AI1 function selection Analog AI : No function function 1: Main setting H selection 2: Auxiliary setting 3~7: Reserved 8: Torque command () Tens place of LED: AI2 function selection is the same as AI1 P1.2 AI1 zero offset -1.%~1.%. P1.3 AI1 gain.~1. 1. P1.4 AI1 filtering.~1.s.1 P1.5 AI1 zero offset correction : Bias as a center 1:Lower than the bias is equal to the bias 2: Higher than the bias is equal to the mode bias 3: Bias as a center and get the absolute P1.6 AI2 zero offset -1.%~1.%. P1.7 AI2 gain.~1. 1. P1.8 AI2 filtering.~1.s.1 P1.9 AI2 zero offset correction The same as P1.5 mode P1.1 Curve Unit place of LED: AI1 curve selection : Curve 1 1: Curve 2 Tens place of LED: AI2 curve selection : Curve 1 H selection 1: Curve 2 Hundreds place of LED: Pulse input curve selection : Curve 1 1: Curve 2 27

28 Maximum curve 2 P1.11 P1.12 P1.13 P1.14 P1.15 P1.16 of curve 1 Actual corresponds to the maximum of curve 1 Minimum of curve 1 Actual corresponds to the minimum of curve 1 Maximum of curve 2 Actual corresponds to the maximum of curve 2 P1.13~1.% 1. Frequency :.~1.% of Fmax Torque:.~3.% of Te Process closed loop : 1. synchronous speed of.~1.% maximum (ie., the corresponding analog input of ~1V).%~P1.11. The same as P1.12. P1.17~1.% 1. The same as P P1.18 P1.19 P1.2 Actual corresponds to the minimum of curve 2 Types of analog output Analog output terminal AO1 functions The same as P1.12. Unit place of LED: AO1 selection : ~1V(~2mA) 1: 2~1V(4~2mA) H Tens place of LED: AO2 selection : ~1V(~2mA) 1: 2~1V(4~2mA) : Output (~ maximum ) 1: Set (~ maximum ) 2: Set (after acceleration/deceleration) (~ maximum ) 3: Motor rotating speed (~ maximum rotating speed) 4: Output current (~2*Ie) 5: Output current (~2*Iem) 6: Output torque (~3 * Tem) 7: Reserved 8: Output voltage (~1.2*Ve) 9: Bus voltage (~8V) P1.17 Minimum of.%~p : AI1 after adjustment 11: AI2 after adjustment 28

29 12: Reserved 13: Output power (~2*Pe) P12.1 Carrier wave.7~15.khz 8. 14: Percentage of host device (~495) Unit place: enable the over-modulation 15~17: Reserved : Disabled 18: Torque command (+1V/+3%) 1: Enabled 19~2: Reserved Tens place: automatic adjustment 21: Output torque (-3.~+3.%) selection for carrier wave 22~23: Reserved : No automatic adjustment 24: Motor rotating speed (bipolar, output during V/F slip P12.2 PWM mode optimization 1: Automatic adjustment Hundreds place: modulation mode 11H compensation) : Two-phase/ three-phase switching 25~26: Reserved 1: Three-phase modulation P1.21 AO1 filtering.~2.s.1 Thousands place: low carrier P1.22 AO1 gain.%~2.% 1. P1.23 AO1 zero offset -1.%~1.%. correction P1.24 Analog output terminal AO2 The same as P1.2 functions P1.25 AO2 filtering.~2.s.1 P1.26 AO2 gain.%~2.% 1.% P1.27 AO2 zero offset correction -1.%~1.%. P12.3 P12.4 P12.5 Current loop proportional gain ACR-P Current loop integral time ACR-I Anti-trip function enabling Frequency limit : Disable 1: Enable 1~5 6.5~1.ms 8. ~1 P12. Group P12: Advanced function parameters Energy-saving : Disabled running 1: Enabled P12.6 reduction rate upon voltage compensation.~99.99hz/s 1. 29

30 P12.7 Pre-magnetizi ng time.~1.s.1 P13.6 Multi-stage 7 5. P12.8 Minimum flux 1%~15% 1 P13.7 Multi-stage 8 5. Flux-weakeni P13.8 Multi-stage 9 1. P12.9 ng adjustment coefficient 1 ~1 1 P13.9 Multi-stage 1 2. P12.1 Flux-weakeni ng adjustment ~1 1 P13.1 Multi-stage coefficient 2 Flux-weakeni P13.11 Multi-stage P12.11 ng control mode ~1 1 P13.12 Multi-stage P12.12 ~P12.14 Reserved P13.13 Multi-stage P13. Group P13: Multi-stage speed parameters Multi-stage 1 5. P13.14 Multi-stage 15 Group P14: Process PID parameters 5. P13.1 Multi-stage 2 1. Reference : Digital 1: AI1 analog P13.2 P13.3 Multi-stage 3 Multi-stage 4 P2.14~P P14. channel selection 2: AI2 analog 3: Terminal PULSE 4: Serial port communication : AI1 analog P13.4 Multi-stage 5 4. P14.1 Feedback channel 1: AI2 analog 2: AI1+AI2 P13.5 Multi-stage selection 3: AI1-AI2 4: MIN(AI1,AI2) 3

31 5: MAX(AI1,AI2) 6: Terminal PULSE P14.13 PID pre-set ~2.Hz. Reference Pre-set P14.2 channel.1~5.s.5 P14.14.~36.s. filtering retention time Feedback : PID output is negative, P14.3 channel.1~5.s.5 PID output operation filtering P14.15 reverse 1: PID output is negative, reverse P14.4 PID digital -1.%~1.%. selection Note: When PID output as auxiliary always 1 Proportional P14.5 gain KP Integral gain P14.6 Ki P14.7 Reserved Sampling P14.8 cycle Output P14.9 filtering time P14.1 Deviation limit PID P14.11 adjustment feature Integral P14.12 adjustment selection.~1. 2..~1..1.1~5.s.5.1~1.s.5.~2.%(Corresponds to PID 2. ) : Positive interaction 1: Reverse interaction Note: Adjust the relationship between the and the speed : Frequency reaches the upper and lower limit, stop integral adjustment 1: Frequency reaches the upper and lower limit,continue the integral regulator P14.16 P14.17 P14.18 P15. P15.1 : PID lost no action 1: When the action continues to run at PID feedback the current set, no fault signal loss action output, display alarm selection 2: When the action coast to stop, a fault signal output PID feedback.~1.% lost detection. The maximum output is 1%. PID feedback lost detection.~25.s 1. time Group P15: Communication parameters Protocol : MODBUS selection 1: Reserved Unit place of LED: Baud rate selection Communicatio : 48bps n 1H 1: 96 bps configuration 2: 192 bps 31

32 3: 384 bps : Activate protection and coast to stop Tens place of LED: Data format 1: Alarm and keep running : N format, RTU Hundreds place of LED: Action upon 1: E format, RTU EEPROM abnormality 2: O format, RTU : Activate protection and coast to stop 3: N format, ASCII 1: Alarm and keep running 4: E format, ASCII Thousands place of LED: Action upon 5: O format, ASCII 24V/1V short circuit Hundreds place of LED: Wiring mode : Activate protection and coast to stop : Direct cabling (232/485) 1: Alarm and keep running 1: MODEM (232) Unit place of LED: Action upon phase P15.2 Local address ~247, is the broadcast address 5 loss P15.3 P15.4 P97. Communicatio n timeout detection time.~1.s. Response delay of the ~1ms 5 drive Group P97: Protection and fault parameters Unit place of LED: Action upon communication fault : Activate protection and coast to stop 1: Alarm and keep running Protection 2: Alarm and stop in the stop mode (only action H in serial port control mode) selection 1 3: Alarm and stop in the stop mode (in all control modes) Tens place of LED: Action upon contactor abnormality P97.1 P97.2 Protection action selection 2 Fault indication selection 1 : Activate protection upon input and output phase loss 1: No protection upon input phase loss 2: No protection upon output phase loss 3: No protection upon input and output phase loss Tens place of LED: Action upon analog input (AI1, AI2) fault : Activate protection and decelerate 1 : Activate protection and coast to stop 2 : Alarm and keep running Unit place of LED: Action upon under-voltage fault indication : No action 1 : Action (under-voltage is regarded as a kind of fault) Tens place of LED: Action upon auto-reset interval fault indication H H 32

33 P97.3 Overload protection setting for motor : No action 1 : Action Hundreds place of LED: Fault lockup function selection : Prohibited 1 : Open (without fault output) 2 : Open (with fault output) Unit place of LED: Overload compensation mode : No action 1: Common motor (with low-speed compensation) 2: Variable- motor (without low-speed compensation) Tens place of LED: Overload pre-alarm detection selection : Always detect 1: Detect only at constant speed Hundreds place of LED: Overload pre-alarm action selection : Alarm and keep running 1H detection level Overload P97.5 pre-alarm detection time Over-voltage P97.6 stall selection Over-voltage P97.7 point at stall Auto current P97.8 limiting action selection Auto current P97.9 limiting level Frequency reduction rate P97.1 upon current limiting P97.11 Reserved.~6.s 5. : Disabled (when the braking resistor is installed) 1 1: Enabled 12.%~15.%Udce 14.% : Disabled at constant speed 1: Enabled at constant speed 1 Note: Always enabled for acceleration/deceleration 2.%~2.%Ie 15..~99.99Hz/s 1. P97.4 Overload pre-alarm 1: Activate protection and coast to stop Thousands place of LED: Overload detection level selection : Relative to rated current of the motor (Er.OL2) 1: Relative to rated current of the drive (Er.oL1) 2.%~2.% 13. P97.12 Reserved The first fault P97.13 type : No abnormal record 1: Over-current during the drive acceleration (Er.oC1) 2: Over-current during the drive deceleration (Er.oC2) 3: Over-current when the drive is running with constant speed (Er.oC3) 4: Over-voltage during the drive 33

34 acceleration (Er.oU1) (Er.24v) 5: Over-voltage during the drive 3~4: Reserved deceleration (Er.oU2) 41: Abnormal AI analog input fault 6: Over-voltage when the drive is running (Er.AIF) with constant speed (Er.oU3) 42: Inverter module temperature 7: Reserved sampling disconnection protection 8: Input side phase loss (Er.IrF) (Er.THI) 9: Output side phase loss (Er.odF) 43: Reserved 1: Power module protection (Er.drv) 44: Short circuit of 1V power (Er.1v) 11: Inverter bridge over-temperature Others: Reserved (Er.oH1) Note: 12: Reserved 1. Er.drv fault can not be reset until 1s 13: Drive overload (Er.oL1) later; 14: Motor overload (Er.oL2) 2. For continuous over-current less than 15: External fault(er.eft) 3 times (including 3 times), it can not be 16: EEPROM read-write error (Er.EEP) reset until 6s later; if it is more than 3 17: Abnormal serial port communication times, it can not be reset until 2s later; (Er.SC1) 3. The keyboard displays AL.xxx in case 18: Abnormal contactor (Er.rLy1) of any fault (e.g. in case of the contactor 19: Abnormal current detection circuit fault, keyboard displays Er.xxx if there is (Er.CUr) protection action, and displays AL.xxx if 2: Reserved continuing running with alarm) 21: PID feedback lost (Er.FbL) 22: Reserved P97.14 The second fault type The same as P : Keyboard parameter copy error (Er.CoP) 24: Poor auto-tuning (Er.TUn) 25~27: Reserved 28: Parameter setting error (Er.PST) 29: Control board 24V power short circuit The third fault P97.15 The same as P97.13 type P97.16 DC bus voltage at the ~999V V 3rd fault P97.17 Actual current.~999.9a. 34

35 at the 3rd fault P97.18 Running at.~2.hz. the 3rd fault P97.19 Drive running status at the ~FFFFH 3rd fault Group P98: Drive parameters P98. Serial No. ~FFFFH Manufactur er setting P98.1 MCU software.~99.99 Manufactur version No. er setting P98.2 User-customiz ~9999 Manufactur ed version No. er setting P98.3 DSP software.~99.99 Manufactur version No. er setting P98.4 Rated Output power,~999.9kva(depending Manufactur capacity on model) er setting P98.5 Rated voltage ~999V(Depending on model) Manufactur er setting P98.6 Rated current ~999.9A(Depending on model) Manufactur er setting P98.7 Drive series :22V Manufactur selection 1:38V er setting 35

36 Chapter 5 Troubleshooting Displaying exception and solutions All possible fault types for MV1 are summarized as shown in table 5-1. Before consulting the service department, the user can perform self-check according to the hints of the table and record the fault symptoms in detail. To seek for service support, please contact the sales person. Table 5-1 Fault record table Fault Fault type Possible fault cause Solutions The acceleration time is too short. Lengthen the acceleration time The motor parameters are incorrect. Perform the parameter auto-tuning of the motor Er.oC1 Acceleration over-current of the drive When instantaneous stop happens, restart the rotating motor The drive power is too low. Set the start mode P8. as the speed tracking restart function Adopt the drive with high power class V/F curve is improper. Adjust the V/F curve setting and the manual torque increase Er.oC2 Deceleration over-current of the drive The deceleration time is too short. There is potential energy load or the load inertial torque is large. The drive power is low. Lengthen the deceleration time Use additionally appropriate dynamic braking components Adopt the drive with high power class The acceleration/deceleration time is Lengthen the acceleration/deceleration time Er.oC3 Constant speed over-current of the drive too short. Sudden load change or abnormal load Low grid voltage appropriately Check the load Check the input power supply The drive power is low Adopt the drive with high power class Abnormal input voltage Check the input power supply Er.oU1 Acceleration over-voltage of the drive Acceleration time is too short. When instantaneous stop happens, Lengthen the acceleration time appropriately Set the start mode P8. as the speed tracking restart the rotating motor restart function The deceleration time is too short Er.oU2 Deceleration over-voltage of the (compared with regeneration energy). Lengthen the deceleration time drive There is potential energy load or the load inertial torque is large. Select appropriate dynamic braking components Constant speed When the vector control functions, Er.oU3 over-voltage of the the ASR parameter setting is See the ASR parameter setting of Group P5 drive improper. 36

37 Fault Fault type Possible fault cause Solutions The acceleration/deceleration time is too short. Abnormal input voltage Lengthen the acceleration/deceleration time appropriately Check the input power supply The input voltage fluctuates abnormally Large load inertia Install the input reactor Adopt dynamic braking components Er.IrF Input side phase loss There is phase loss in input R.S.T. Check the installation wiring Check the input voltage Er.odF Output side phase loss There is phase loss in output U.V.W. Check the output wiring Check the motor and the cables There is interphase short circuit or grounding short circuit in output Rewiring and check if the motor insulation is good. three phases. Instantaneous over-current of the drive See the over-current solutions The duct is blocked or the fan is damaged. Unblock the duct or replace the fan The ambient temperature is too high. Lower the ambient temperature Er.drv Power module protection The wirings or the plug-in units of the control board loosens. Check them and rewiring Abnormal current waveform caused by output phase loss and so on Check the wiring The auxiliary power supply is damaged; the drive voltage is Seek for service support insufficient. Inverter module bridging conduction Seek for service support Abnormal control board Seek for service support Braking pipe damaged Seek for service support Er.oH1 Inverter module heatsink over-temperature The ambient temperature is too high. Lower the ambient temperature The duct is blocked. Clean the duct 37

38 Fault Fault type Possible fault cause Solutions The fan is damaged. Replace the fan The inverter module is abnormal. Seek for service support The motor parameters are incorrect. Perform the parameter auto-tuning of the motor The load is too large. Adopt the drive with higher power The DC braking amount is too large. Reduce the DC braking current and lengthen the braking time Er.oL1 Drive overload When instantaneous stop happens, Set the start mode P8. as the speed tracking restart the rotating motor restart function The acceleration time is too short. Lengthen the acceleration time The grid voltage is too low. Check the grid voltage V/F curve is improper. Adjust V/F curve and torque increase The motor overload protection factor setting is incorrect. Set the overload protection factor of motor correctly. The motor is blocked or the sudden change of load is too large. Check the load Er.oL2 Motor overload The universal motor runs at low speed for a long time, with heavy load. If long-term low-speed running is required, special motor should be used. The grid voltage is too low. Check the grid voltage V/F curve is improper. Set V/F curve and torque increase correctly Stop suddenly by pressing the STOP See the function definition of the STOP key in Er.EFT Emergency stop or external device fault key External fault emergency-stop P.4 After the external fault is revoked, release the terminal is enabled. external fault terminal Er.EEP EEPROM read/write fault The read/write error of the control parameters occurs. Reset by pressing the STOP/RESET key, seek for service support The baud rate is set improperly. Set the baud rate properly. Er.SC1 Abnormal remote serial port communication Serial port communication error Reset by pressing the STOP/RESET key, seek for service support The fault alarm parameters are set Modify the P15.3 and P97. settings 38

39 Fault Fault type Possible fault cause Solutions improperly. The host device does not work. Check if the host device is working and if the wiring is correct. The grid voltage is too low. Check the grid voltage The contactor is damaged. Replace the contactor of the main circuit, seek for service support Er.rLy Abnormal contactor The power-up buffer resistance is Replace the buffer resistance, seek for service damaged. support The control circuit is damaged. Seek for service support Input phase loss Check the input R.S.T. wiring Er.CUr Current detection circuit abnormal Current detection device damage The amplifying circuit is abnormal. Seek for service support Seek for service support The parameters for feedback loss are set improperly. Modify the P14.17 setting Er.FbL Closed loop feedback loss Feedback wire-break Rewiring The of closed loop See the P14.1 setting and increase the feedback feedback is too low. Er.CoP Operation panel parameter copying error The operation panel parameters are incomplete or the operation panel version is inconsistent with main control panel version. The operation panel EEPROM is damaged. Refresh the operation panel data and version, use P.3=1 for uploading the parameters first and then use P.3=2 or 3 for downloading. Seek for service support The nameplate parameters of the Set the parameters properly according to the motor motor are incorrect. nameplate When reverse running is prohibited, Er.TUn Poor auto-tuning reverse rotating auto-tuning is performed. Cancel the reverse running prohibition Check motor wiring Auto-tuning overtime Check the P2.13 (upper limit ) and see whether the P3.3 set is lower than rated. 39

40 Fault Fault type Possible fault cause Solutions Er.PST Parameter setting error Wrong analog AI function selection setting The same function shall not be selected for different analogs simultaneously. Er.24v Control board 24V power short circuit Short circuit of P24 and terminal COM Confirm whether the wiring of P24 and COM is correct Abnormal control circuit Seek for service support Er.AIF Abnormal AI analog input The input analog is out of the range and the absolute is greater Check the analog input than 11V Er.THI Inverter module temperature sampling disconnection Abnormal temperature sampling circuit The inverter module temperature Seek for service support Check the inverter module temperature sampling sampling wire is poorly connected. wire connection Er.1v Control board ±1V power short circuit ±1V grounding Confirm whether the ±1V wiring is correct The interface board circuit is Replace the interface board, seek for service damaged. support Note: 1. Er.drv fault can not be reset until 1s later; 2. For continuous over-current less than 3 times (including 3 times), it can not be reset until 6s later; if it is more than 3 times, it can not be reset until 2s later; 3. The keyboard displays AL.xxx in case of any fault (e.g. in case of the contactor fault, keyboard displays Er.xxx if there is protection action, and displays AL.xxx if continuing running with alarm). 4

41

Quick Start Guide of CV50- ControlVIT Series

Quick Start Guide of CV50- ControlVIT Series ❶ Safety precautions Do not refit the inverter unauthorizedly; otherwise fire, electric shock or other injury may occur. Please install the inverter on fire-retardant material and keep the inverter away

More information

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL Dual Rating NRTL/C CERTIFIED Technologies Inc. mgitech.com Sensor/Sensorless Vector Control Dual current rated for constant and variable torque Auto

More information

Tension Control Inverter

Tension Control Inverter Tension Control Inverter MD330 User Manual V0.0 Contents Chapter 1 Overview...1 Chapter 2 Tension Control Principles...2 2.1 Schematic diagram for typical curling tension control...2 2.2 Tension control

More information

GS2 Series - Introduction

GS2 Series - Introduction GS2 Series - Introduction GS2 Series Drives Rating Hp.25.5 1 2 3 5 7.5 10 kw 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Single-Phase 115 Volt Class Single/Three-Phase 230 Volt Class Three-Phase 230 Volt Class Three-Phase

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

Shenzhen Sine Electric Co., Ltd.

Shenzhen Sine Electric Co., Ltd. Page 1 of 5 Favorite Contact 中文 Please enter key words 提交查 Home Products Solutions Service About us Products EM500 Open loop Inverter Your current location:home > Products Standard Inverters EM500 Open

More information

RM B. Features. Drive Model Number Scheme. A RM6 Product Series

RM B. Features. Drive Model Number Scheme. A RM6 Product Series Features RM6 series are suitable for constant and variable torque loads (mixer, conveyor, fan, pump, etc.) Overload capacity with 150% drive s rated output current for 1 min can sustain heavy load conditions

More information

User Manual. V6/V5 T T8 Tension Control Inverter

User Manual. V6/V5 T T8 Tension Control Inverter User Manual V6/V5 T T8 Tension Control Inverter V&T Foreword The V6/V5 T series inverter is a kind of high performance vector control/torque control inverter for tension control produced by V&T Technologies

More information

Technical Information

Technical Information Yaskawa Electric Europe GmbH Hauptstraße 185 65760 Eschborn Germany Tel. +49 (0)61 96/569 300 Technical Information Topic Replacement Varispeed C+ with Reference: UEW0101D Source: Based on YEC document

More information

Technical Explanation for Inverters

Technical Explanation for Inverters CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor

More information

L300P Inverter Specifications

L300P Inverter Specifications L300P Inverter Specifications Tables for 200V class inverters Note that General Specifications on page 1 9 covers all L300P inverters, followed by footnotes for all specifications tables. Seven 200V models

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA Honeywell CORE Drive SPECIFICATION DATA FEATURES APPLICATION The new Honeywell VFD CORE Drive addresses the need to save time for installation, and provides the lower total installed costs with years of

More information

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP. Catalog. Edition 03/ / EN

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP. Catalog. Edition 03/ / EN Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP Edition 03/2009 Catalog 16798015 / EN SEW-EURODRIVE Driving the world 1 Important Notes... 4 1.1 Structure of the safety

More information

Quick Reference Guide. For NFX9000 Adjustable Frequency Drives. February 2006 NQ00. MN E February 2006

Quick Reference Guide. For NFX9000 Adjustable Frequency Drives. February 2006 NQ00. MN E February 2006 Quick Reference Guide For NFX9000 Adjustable Frequency Drives February 2006 5011640900 NQ00 MN04001003E February 2006 Hazardous High Voltage WARNING Motor control equipment and electronic controllers are

More information

TRIPS AND FAULT FINDING

TRIPS AND FAULT FINDING WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing

More information

J1000 D E F I 1000 J1000 J1000 J1000 J1000

J1000 D E F I 1000 J1000 J1000 J1000 J1000 Compact Inverter SERIES J1000 GB D E F I 1000 J1000 J1000 J1000 J1000 The J-Type YASKAWA Inverter Drive Technology Contents Page 2 Experience & Innovation A leader in Inverter Drives technology Page 3

More information

VFD E Series. Features

VFD E Series. Features VFD E Series Output Frequency : 0.1 ~ 600 Hz. Built in PLC Function 500 Step program in Ladder Language. Side by side installation. Easy maintenance. Modular & Compact Design. Built-in MODBUS communication.

More information

HIGH PERFORMANCE VECTOR CONTROL DRIVE

HIGH PERFORMANCE VECTOR CONTROL DRIVE JI350 SERIES IP 54 Drive for PMSM and IM Accuracy speed and torque control for motor VF control and vector control 180% rated starting torque Plug n play control box with emergency stop HIGH PERFORMANCE

More information

SYSDrive Frequency Inverter

SYSDrive Frequency Inverter SYSDrive Frequency Inverter T V/f control T PID control T Standard LED, optional LCD operator T Fieldbus options: DeviceNet T 7 configurable digital inputs T 3 configurable digital outputs T Low audible

More information

SJ300 Inverter Specifications

SJ300 Inverter Specifications SJ300 Inverter Specifications Tables for 200V class inverters Note that General Specifications on page 1 9 covers all SJ300 inverters, followed by footnotes for all specifications tables. The 200V models

More information

J1000. Compact Inverter Series.

J1000. Compact Inverter Series. J1000 Compact Inverter Series www.yaskawa.eu.com Focus on Application Customer orientation and application focus two attributes of machine equipment YASKAWA offers with its J1000 compact inverter drive

More information

MaxPak Plus Analog DC V S Drive

MaxPak Plus Analog DC V S Drive Three-Phase 3-600 HP non-regenerative and 5-150 HP regenerative drives Designed to accommodate a wide range of industrial requirements, the DC V S Drive has been widely applied worldwide. Selected ratings

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

RS232 Communications cable with PC ER M. RJ-45 / USB Adapter Remote Operator Extansion Cable. Communication Unit. Mounting Accesories

RS232 Communications cable with PC ER M. RJ-45 / USB Adapter Remote Operator Extansion Cable. Communication Unit. Mounting Accesories JZ J1000 The basic inverter V/f controlled inverter Good torque performance (150% / 3 Hz) Double rating ND 120%/1min and HD 150%/1 min Overload detection function (150% during 60s) Motor thermal function

More information

MULTI LANGUAGE KEYPAD

MULTI LANGUAGE KEYPAD FREQUENCY INVERTER MULTI LANGUAGE KEYPAD E 800 E 2000 EP 66 EM 30 Universal remote keypad- display unit, compatible with all EURA Drives products Robust, for any critical environments, IP66 waterproof

More information

S100 series high performance VC control Frequency Inverter

S100 series high performance VC control Frequency Inverter S100 series high performance VC control Frequency Inverter SG600 series MPPT Solar Pump Inverter Company introduction: www.zundrive.com SHENZHEN ZUNDRIVE AUTOMATIO CO., LIMITED ( hereinafter called ZUNDRIVE

More information

5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults

5.1 Errors (Alarms) Error (alarm) definitions PROTECTIVE FUNCTIONS. (1) Major faults .1 Errors (Alarms) If any fault has occurred in the inverter, the corresponding protective function is activated and the error (alarm) indication appears automatically on the PU display. When the protective

More information

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C

Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C , SIEP C , and SIEP C Yaskawa AC Drive L1000A Supplement to the L1000A Technical Manual No. SIEP C710616 32, SIEP C710616 33, and SIEP C710616 38 Introduction This supplement to the L1000A Technical Manual describes features

More information

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES INVERTER SERIES Varispeed E VARISPEED E YASKAWA INVERTER DRIVE TECHNOLOGY Contents Content Page 2 Experience & Innovation A leader in Drives technology Page 3 Specifications Experience & Innovation For

More information

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen. Kelly HSR Opto-Isolated Series Motor Controller with Regen User s Manual HSR72601 HSR72801 HSR12401 HSR12601 HSR12901 HSR14301 HSR14501 HSR14701 Rev.3.3 Dec. 2011 Contents Chapter 1 Introduction... 2 1.1

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

Fincor Series 2230 MKII/2240

Fincor Series 2230 MKII/2240 Fincor Series 2230 MKII/ Fincor Series 2200 regenerative drives are ideal for your more demanding applications. They feature flexibility with ratings up to 5 horsepower. The Series 2230 MKII offers new

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

IP 20/NEMA 1 & IP 66/NEMA 4X Compact Vector Control Drive

IP 20/NEMA 1 & IP 66/NEMA 4X Compact Vector Control Drive IP 0/NMA & IP 66/NMA 4X Compact Vector Control rive APPLICATIONS General multi-function model IP 0/NMA Textiles oodworking Small andling Machine Simple Metal Processing Machine Tools Packaging & Labeling

More information

HSV-180S Series AC Spindle Drive Unit. User's Manual V Wuhan Huazhong Numerical Control Co., Ltd. Wuhan China

HSV-180S Series AC Spindle Drive Unit. User's Manual V Wuhan Huazhong Numerical Control Co., Ltd. Wuhan China Series HSV-180S AC Spindle Drive User's Manual V2.0 2010.11 Wuhan Huazhong Numerical Control Co., LTD Wuhan China Contents 1. Safety Precautions... 6 1.1 Symbols of Safety Precautions...6 1.2 Meaning of

More information

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA SmartVFD HVAC APPLICATION The SmartVFD HVAC is a variable frequency drive designed for use in HVAC application to control the speed of HVAC pumps and fans in order to maximize energy efficiency. Smart

More information

Names and Functions of Driver Parts

Names and Functions of Driver Parts List of Motor Connection and Extended Accessories Installation Product Line Dimensions and Operation Functions Connection and Operation Names and Functions of Parts 5 Power Supply Input/ Regeneration Unit

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / /

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / / Non-Regen Drives Non-regenerative drives are typically used on applications which primarily motor in one direction and stopping is achieved through friction or infrequent use of a dynamic braking resistor.

More information

HVAC Products. Introducing the SED2 Variable Frequency Drives

HVAC Products. Introducing the SED2 Variable Frequency Drives HVAC Products Introducing the SED2 Variable Frequency Drives Designed Specifically for HVAC Applications From a global leader in drives technology and innovation, now comes a drive specifically configured

More information

Troubleshooting. YASKAWA ELECTRIC SIEP C D YASKAWA AC Drive A1000 Technical Manual 301

Troubleshooting. YASKAWA ELECTRIC SIEP C D YASKAWA AC Drive A1000 Technical Manual 301 6 This chapter provides descriptions of the drive faults, alarms, errors, related displays, and guidance for troubleshooting. This chapter can also serve as a reference guide for tuning the drive during

More information

USER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT

USER INSTRUCTION FOR PROGRAMMING INVERTER FUJI FRENIC LIFT Quadri di Manovra per Ascensori Lifts Control Panels PELAZZA PEPPINO S.r.l. 20063 CERNUSCO SUL NAVIGLIO (MI) ITALY Via Ponchielli, 6/8 Tel. 02/92.31.694 Fax 02/92.42.706 Tel. 02/92.42.706 Web Site: www.pelazza.com

More information

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide

Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide Parker AC10 Frequency Inverter (to 22kW) Easy Start Guide CAUTION: 1)Do not re-set while the motor is rotating 2)Perform parts replacement after discharge is finished 3)Do not connect output terminals

More information

SHENZHEN KEWO ELECTRIC TECHNOLOGY CO., LTD

SHENZHEN KEWO ELECTRIC TECHNOLOGY CO., LTD SHENZHEN KEWO ELECTRIC TECHNOLOGY CO., LTD KEWO AC DRIVES, VARIABLE FREQUENCY DRIVE, FREQUENCY INVERTER ADD: 3 Floor,Block 8,St George Industrial Park,Xinyu Road,Sha Jing,Bao'an, Shenzhen, Guangdong, China,518104.

More information

SINUS PENTA 2T/4T SINUS PENTA 2T/4T

SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T Technical Highlights One product, 5 integrated functions - IFD (Inverter Frequency Drive): vector modulation function for general-purpose applications (V/F pattern).

More information

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V LIFT INVERTER SERIES EN DE ES FR IT 1000V YASKAWA INVERTER DRIVE TECHNOLOGY Contents Page 2 Introduction Experience & Innovation YASKAWA speaks Lift Page 3 YASKAWA Main Features Page 4 Specifications Page

More information

Overvoltage Suppression F7 Drive Software Technical Manual

Overvoltage Suppression F7 Drive Software Technical Manual Overvoltage Suppression F7 Drive Software Technical Manual Software Number: VSF11015X, Drive Models: CIMR-F7UXXXXXX-062, CIMR-F7U40750F-145. Document Number: TM.F7SW.062, Date: 09/17/2010, Rev: 10-09 This

More information

VSD Series II Variable Speed Micro Drives

VSD Series II Variable Speed Micro Drives VSD Series II Variable Speed Micro Drives Product Bulletin Code No. LIT-12011813 Issued March 26, 2013 Refer to the QuickLIT website for the most up-to-date version of this document. Johnson Controls VSD

More information

Chapter 1: Getting Started User Manual Overview...1 2

Chapter 1: Getting Started User Manual Overview...1 2 Getting Started Chapter 1 Table of Contents Chapter 1: Getting Started User Manual Overview.........................................1 2 Overview of this Publication.........................................

More information

MCW Application Notes 24 th August 2017

MCW Application Notes 24 th August 2017 MCW Application Notes 24 th August 2017 www.motorcontrolwarehouse.co.uk Document number MCW-E3-051 Revision 0.0 Author Gareth Lloyd Product Optidrive E3 Title Summary Optidrive E3 Fault Finding This document

More information

SD1 Series General Purpose AC Variable Speed Drives

SD1 Series General Purpose AC Variable Speed Drives 1 200/240V 50/60Hz 0.4~2.2kW (0.5~3HP) 3 200/240V 50/60Hz 0.4~7.5kW (0.5~10HP) 3 380/440V 50/60Hz 0.75~110kW (1~150HP) IP20 Torque Vector Control STO (safe torque off) Up to 150% Starting Torque Front

More information

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

1333 (SERIES B & C) TROUBLESHOOTING GUIDE 1333 (SERIES B & C) TROUBLESHOOTING GUIDE Preventive Maintenance: Problems with Your Drive? Bulletin 1333 is convection or fan cooled by air flowing through the heat sink slots. The slots must never be

More information

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible DC Drives Flexible & Powerful single-phase DC drives provide a complete family solution from the compact Series 2120 chassis drive to the powerful Series 2230 and it s feature rich application specific

More information

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3 Type number key VFD 007 CP 43 Option cards A B C S -XY Y=0: UL open 1: NEMA1 X=0: IP00 2: IP20 Version number: A=Wall mount B=Higher rated current C=Cabinet S=Frame D0 Input voltage 23=230VAC 3φ 43=400VAC

More information

FE100/FE200. AC Speed Control Motors. Features

FE100/FE200. AC Speed Control Motors. Features AC Speed Control Motors FE1/FE2 Additional Information Technical reference Page G-1 Safety standards Page H-2 The FE1/FE2 is a speed controller using inverter technology that enables speed control to be

More information

User Manual Solar Charge Controller 3KW

User Manual Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...

More information

VF-S11 RS485 built-in board option RS4003Z Instruction Manual

VF-S11 RS485 built-in board option RS4003Z Instruction Manual VF-S11 RS485 built-in board option RS4003Z Instruction Manual NOTICE 1. Make sure that this instruction manual is delivered to the end user of RS485 built-in option board. 2. Read this manual before installing

More information

V1000. Inverter Series.

V1000. Inverter Series. V1000 Inverter Series www.yaskawa.eu.com One for all The V1000 is a general purpose inverter drive covering the demands of a wide field of applications. Simple duties as well as requirements of complex

More information

V1000 Inverter Series

V1000 Inverter Series V1000 Inverter Series www.yaskawa.eu.com One for all The V1000 is a general purpose inverter drive covering the demands of a wide field of applications. Simple duties as well as requirements of complex

More information

ATOTH-G Series BLDC Motor Controller. User s Manual

ATOTH-G Series BLDC Motor Controller. User s Manual ATOTH-G Series BLDC Motor Controller User s Manual Contents Chapter One Summary...1 Chapter Two Main Features and Specifications.2 2.1 Basic Functions...2 2.2 Features... 5 2.3 Specifications...6 Chapter

More information

LIFT INVERTER SERIES L1000A

LIFT INVERTER SERIES L1000A LIFT INVERTER SERIES L1000A EN DE For Modernization and New Installation YASKAWA L1000A FOR HIGH PERFORMANCE LIFT APPLICATION Contents Page 2 Experience & Innovation Page 3 Main Features Page 4 Energy

More information

Addendum to Instruction Manual GP10 and VG10

Addendum to Instruction Manual GP10 and VG10 to Instruction Manual GP10 and VG10 Several functions have been added and a few functions are changed to increase the versatility of the GP10 and VG10 drives. Please refer to both the instruction manual

More information

Varispeed J7 CIMR-J7AZ. System configuration

Varispeed J7 CIMR-J7AZ. System configuration CIMR-J7AZ Varispeed J7 Small, simple and smart V/f controlled inverter Compact size Good torque performance: 100% torque at 1.5 Hz, 150% at 3 Hz 150% overload / 60sec Overload detection function. Motor

More information

TOSVERT VF-S11. V/F control functions

TOSVERT VF-S11. V/F control functions TOSVERT VF-S11 V/F control functions The technical information in this manual is provided to explain the principal functions and applications of the product, but not to grant you a license to use the intellectual

More information

MAKING MODERN LIVING POSSIBLE. Instruction Manual VLT AutomationDrive FC 300

MAKING MODERN LIVING POSSIBLE. Instruction Manual VLT AutomationDrive FC 300 MAKING MODERN LIVING POSSIBLE Instruction VLT AutomationDrive FC 300 Safety Safety WARNING HIGH VOLTAGE! Adjustable frequency drives contain high voltage when connected to AC line power. Installation,

More information

CRANE FUNCTION MANUAL. FR-A (0.4K) to 04750(90K)-CRN FR-A (0.4K) to 06830(280K)-CRN FR-A (315K) to 12120(500K)-CRN

CRANE FUNCTION MANUAL. FR-A (0.4K) to 04750(90K)-CRN FR-A (0.4K) to 06830(280K)-CRN FR-A (315K) to 12120(500K)-CRN INVERTER CRANE FUNCTI MANUAL FR-A820-00046(0.4K) to 04750(90K)-CRN FR-A840-00023(0.4K) to 06830(280K)-CRN FR-A842-07700(315K) to 12120(500K)-CRN Crane Function The FR-A800-CRN has dedicated functions for

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

YASKAWA AC Drive A1000

YASKAWA AC Drive A1000 YASKAWA AC Drive A000 High Performance Vector Control Drive Quick Start Guide Type: CIMR-AC Models: 200 V Class: 0.4 to 55 kw 400 V Class: 0.4 to 90 kw To properly use the product, read this manual thoroughly

More information

Kelly KDHA High Voltage Series/PM Motor Controller User s Manual

Kelly KDHA High Voltage Series/PM Motor Controller User s Manual Kelly KDHA High Voltage Series/PM Motor Controller User s Manual KDH07500A KDH07501A KDH07700A KDH07701A KDH09400A KDH09401A KDH09500A KDH09501A KDH12400A KDH12401A KDH12500A KDH12501A KDH14300A KDH14301A

More information

LIFT INVERTER SERIES L1000A

LIFT INVERTER SERIES L1000A LIFT INVERTER SERIES L1000A EN DE ES FR IT For Modernisation and New Installation YASKAWA L1000A FOR HIGH PERFORMANCE LIFT APPLICATION Contents Page 2 Experience & Innovation Page 3 Main Features Page

More information

Symbol Input rating Symbol 2 Three-phase, 200 ~ 230V N 4 Three-phase, 380 ~ 480V. None. Loader. Graphic. Loader

Symbol Input rating Symbol 2 Three-phase, 200 ~ 230V N 4 Three-phase, 380 ~ 480V. None. Loader. Graphic. Loader is7 Variable Frequency Drive / Inverter High Torque Performance and Precise VFD 3 phase 0.75~22kW(1~30HP), 200~230V 3 phase 0.75~160kW(1~250HP), 380~480V Constant torque / Variable torque dual rating Selectable

More information

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications

2.3. Adjustable Frequency Drives. Contents. Standards and Certifications Contents Selection................ Product Selection....................... Accessories........................... Technical Data and Specifications.......... Dimensions........................... Page

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS INSTALLATION 13. ACCESSORIES 13.1. Braking resistors 13.1.1. APPLICATION TABLES From size S05 to size S30, inverters are supplied with a built-in braking unit. The braking resistor is to be incorporated

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

DE ES A A. For Modernisation and New Installation L1000A L1000A L1000A

DE ES A A. For Modernisation and New Installation L1000A L1000A L1000A lift Inverter Series L1000A EN DE ES FR IT A1000 1000A L1000A L1000A L1000A For Modernisation and New Installation Yaskawa L1000A for High Performance Lift Application Contents Page 2 Experience & Invation

More information

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4 Braking Resistor Units 3G3IV-PCDBR2 B/4 B Braking Units Thank you for choosing an OMRON Braking Resistor Unit and Braking Unit. Proper use and handling

More information

Start-up guide of LSLV-M100

Start-up guide of LSLV-M100 2mm 2mm Start-up guide of LSLV-M100 Download manual For detailed information on installation and commissioning, full version of the M100 manual can be downloaded at www.lsis.com Verify & Identify the delivery

More information

Description 1/8-7.5HP

Description 1/8-7.5HP Description 1/8-7.5HP J1000 In our pursuit to create drives optimized for variable speed needs in compact applications, the J1000 is the solution. This micro-drive is simple and reliable with Yaskawa quality.

More information

Kelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual

Kelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual Kelly HPM High Power Full Bridge Permanent Magnet DC Motor Controller User s Manual HPM72601 HPM72801 HPM12401 HPM12601 HPM12801 HPM14301 HPM14501 HPM14701 Rev.3.4 Dec. 2016 Contents Chapter1 Introduction...

More information

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING AUGUST, 2004 REV.A CURTIS TOLEDO OPERATOR S MANUAL SUPPLEMENT AF Series Compressors VS models with VFD WARNING Personal injury and/or equipment damage will result by failing to pay attention to the vital

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Electrohydraulic Servo Drive

Electrohydraulic Servo Drive Electrohydraulic Servo Drive Shenzhen Veichi Electric Co., Ltd. is a high-tech enterprise that is professionally engaged in the development, manufacturing and marketing of industrial automation control

More information

General Specifications

General Specifications General Specifications C2 FECA-TE-2015 1. Standard Specifications 1) Three-phase 200V series(0.1 to 15kW / 1/8 to 20HP) ( = A, U only) Items Type (FRN C2S-2 = A,U) Nominal applied motor *1) [kw] ( =A)

More information

JC-VSD FP Series II Drives Product Bulletin 1

JC-VSD FP Series II Drives Product Bulletin 1 JC-VSD FP Series II Drives Product Bulletin Code No. LIT-12012081 Issued May 2017 The Johnson Controls VSD FP Series II provides the advanced technology and features of the Johnson Controls VSD Series

More information

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module.

Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. Welcome to ABB machinery drives training. This training module will introduce you to the ACS850-04, the ABB machinery drive module. 1 Upon the completion of this module, you will be able to describe the

More information

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the

More information

Kelly KDC Series/PM Motor Controller User s Manual

Kelly KDC Series/PM Motor Controller User s Manual Kelly KDC Series/PM Motor Controller User s Manual KDC48600 KDC48601 KDC48602 KDC48603 KDC72600 KDC72601 KDC72602 KDC72603 KDC72800 KDC72801 KDC72802 KDC72803 KDC12602 KDC12603 Rev.3.3 May 2011 Contents

More information

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs 0.25 kw - 110 kw (0.33 hp - 150 hp) 100 V 200 V 400 V 575 V 690 V Unidrive M400 features Optional AI-485

More information

AC drive has detected too high a Check loading

AC drive has detected too high a Check loading Fault code Fault Name Fault type Default Possible Cause Remedy 1 Over Current Fault AC drive has detected too high a Check loading current (>4*IH) in the motor cable: Check motor Sudden heavy load increase

More information

HIB Enclosed Inverter User Guide

HIB Enclosed Inverter User Guide HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit

More information

Brushless Motors. BMU Series. Connector Type NEW. Easy speed control, easier to use. New connector type with smart wiring.

Brushless Motors. BMU Series. Connector Type NEW. Easy speed control, easier to use. New connector type with smart wiring. Brushless Motors BMU Series NEW Connector Type Easy speed control, easier to use. New connector type with smart wiring. The new connector type in the compact, high-efficiency BMU series, directly connects

More information

BR Second Position Voltages. AA Fourth Position

BR Second Position Voltages. AA Fourth Position 1336S First Position Bulletin Number BR Second Position Voltage Letter AQ BR CW A B BP BX C Q R RX W Voltages 200-240V AC or 3V DC 380-480VAC or 513-620V DC 500-600V AC or 775V DC or 200-240V AC 380-480V

More information

Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB

Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB Kelly KEB Brushless Motor Controller User s Manual Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 KEB EB72 72331 KEB72450 KEB EB72 72451 KEB72600 KEB

More information

SECTION VARIABLE FREQUENCY DRIVE UNITS

SECTION VARIABLE FREQUENCY DRIVE UNITS SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

UE-MINI HYDRO BOOSTER SYSTEM

UE-MINI HYDRO BOOSTER SYSTEM Preface We appreciate you very much for purchasing the Ebara Hydro Booster System. Please read the user's manual carefully for appropriate use of the product that is developed in order to provide the most

More information

8 Troubleshooting and Maintenance

8 Troubleshooting and Maintenance 8 Troubleshooting and Maintenance 8.1 Troubleshooting 8.1.1 Troubleshooting of LED Indicators See Tab. 7-4 State Descriptions of LED Indicators for the definition. Fault Type LED indicators and LCD screen

More information

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951

More information