RDSO/PE/SPEC/AC/ (Rev. 0 ) SPECIFICATION FOR VANE TYPE AIR FLOW RELAY FOR ROOF MOUNTED AC PACKAGE UNIT

Size: px
Start display at page:

Download "RDSO/PE/SPEC/AC/ (Rev. 0 ) SPECIFICATION FOR VANE TYPE AIR FLOW RELAY FOR ROOF MOUNTED AC PACKAGE UNIT"

Transcription

1 Page 1 of 12 RESEARCH DESIGN & STANDARDS ORGANISATION MINISTRY OF RAILWAY POWER SUPPLY & EMU DIRECTORATE TITLE SPECIFICATION FOR VANE TYPE AIR FLOW RELAY FOR ROOF MOUNTED AC PACKAGE UNIT S.No. Date of amendment Revision APPROVED EDPS

2 Page 2 of 12 Government of India Ministry of Railways Research Designs & Standards Organisation Manak Nagar, Lucknow SPECIFICATION FOR VANE TYPE AIR FLOW RELAY FOR ROOF MOUNTED AC PACKAGE UNIT 0.0 FOREWARD 0.1 At present vane type air flow relay are being used in RMPU to supervise the correct operation of blower provided in RMPU to ensure the air flow through evaporator coil and heaters. Zonal Railways have complained that present design for vane relays is not having sufficient mechanical strength resulting the breakage of flapper lever provided for operating the microswitch. RDSO has prepared this specification to overcome the existing defects as well as to standardise their design to be used by all the suppliers. This specification will supersedes the earlier design of vane relay as per RDSO drawing No. SKEL-4428 and its mounting arrangement will remain as per RDSO drawing No. SKEL SCOPE 1.1 This specification covers the design parameters and testing requirements of vane type air flow relays for use in RMPU s. 1.1 The vane type airflow relay is to be provided in Roof Mounted AC Package Unit. The contacts of the relay will open or close the appropriate/respective circuit as shown in RDSO drawing No. SKEL The vane type airflow relay shall be mounted at both the return air entry/ path of RMPU. 1.3 The coil of the auxiliary contractors in heating and cooling circuit shall be energised through this vane relay.

3 Page 3 of TERMINOLOGY 2.1 The following definitions shall be applied in this specification Pickup speed : The air velocity in meters per second required to make the electrical contact close Dropout speed : The air velocity in meters per second required to make the electrical contact open A single pole micro switch will have three terminals (contacts) with one NO, one NC and third used as common. 3.0 SERVICE CONDITION 3.1 Environmental conditions : Maximum ambient air temp : 57 deg.c. Average ambient air temp. : 35 Deg. C. Maximum relative humidity : 100% Atmosphere : Coastal area : Extremely dusty and desert weather and desert terrain in certain areas. The dust content in air may reach as high values as 1.6 mg/m³. The equipment shall be designed to work in coastal areas in humid, salt laden and corrosive atmosphere. The maximum value of the

4 Page 4 of 12 condition will be as under ; Max. PH Value 8.5 Sulphate 7 mg/litre Max Concentration 6 mg/litre of chlorine Max. conductivity 130 micro- Semen/CM Annual rainfall : Altitudes : Ranging Between 1750 to 6250 mm Not exceeding 1200 m 4.0 RATING Microswitch Rating Rated Voltage Normal operating voltage range Current rating 250 V AC V AC 15 Amp. 4.1 Vibration and shocks : The vane type air flow relay shall withstand satisfactory vibrations and shock normally encountered in service as indicated blow:- (a) Maximum vertical acceleration g (b) Maximum lateral acceleration g. (c ) Maximum longitudinal acceleration g. ( g being the value of acceleration due to gravity)

5 Page 5 of 12 The vibrations are of sine wave from and frequency of vibrations is between 1 Hz and 50 Hz. The amplitude a expressed in mm is given as a function of f by a=25/f for value of f from 1 to 10 Hz. And a=250/f²for the value of F exceeding 10 Hz. And upto 50 Hz. 5.0 GENERAL DESIGN ASPECT 5.1 Electrical requirement The contact of the relay shall close or open to energise or de-energise the coil of auxiliary contactor provided to connect or disconnect the supply of the cooling and heating circuit through it s auxiliary contact as shown in RDSO drawing NoSKEL-4391 of RDSO Specification for AC Control Panel for RM PU no. ELPS/ SPEC/ AC/ 04 ( Rev. 2) Of Aug The circuit shall be active at an air velocity of 5 meter per second and should be inactive when the velocity falls below 2 meter per second The design of the vane type air relay shall be in such a way that under normal condition, the contact of the micro-switch remain open and shall be closed under air pressure The opening and closing of contact of the micro-switch shall not be accompanied by any rebound The relay shall be designed so as to avoid the contact chattering, bounce and hesitation The terminal of the micro-switch shall be accessible for external connection. The connection shall be made from the rear by means of crimped lug over PTFE wire The clearance and creepage distance shall be as per IS: 4237 of latest version.

6 Page 6 of Mechanical Requirements The relay shall be so designed and constructed that it will withstand, vibrations and shock encountered during service as specified in clause 4.1 of this specification The housing assembly and the attachment of flap shall generally confirmed to the RDSO drawing No. RDSO/PE/SK/AC/0039 (Rev. 0 ) enclosed with this specification Sharp edges and sharp corners shall be made blunt The flap design will be as per RDSO drg. No.RDSO/PE/SK/AC/0040 (Rev. 0 ) enclosed with this specification The housing assembly and the flap shall be made of corrosion resistance grade 304 of Stainless Steel having thickness not less than 18 SWG and 32 SWG respectively The general arrangement for mounting the vane type air flow relay is shown in RDSO drawing No. SKEL 4429 of Specification for RMPU, no. ELPS/ SPEC/ AC/ 03 ( Rev. 1) Of Aug. 99 with suitable provision for fixing the relay assembly Minor modification in the mounting bracket for vane relay as shown in RDSO Drg. No. SKEL4429 may be done with prior approval of RDSO to suit the housing assembly Screws, nut & bolts used in manufacturing the same shall confirm to IS:1364 (Pt. 1 to 5) The freely movement of the flap shall be ensured The general workmanship & welding quality shall be of high quality. 6. MARKING 6.1 Each vane type air flow relay shall be marked the following information : 1) Manufacturer s name or trade mark, if any

7 Page 7 of 12 2) Make and rating of Micro-switch 6.2 The information mentioned in clause 6.1 shall be screen printed in white color on black ground for easy identification on aluminum plate and shall be riveted on the side wall of the housing. 6.3 The manufacturer shall supply the design drawings, technical detail of the microswitch, maintenance instruction (schedule + trouble shooting) and internal test report to the purchaser with the first batch of the supply. 7. TESTS 7.1 Type test : After the approval of drawings from RDSO, the manufacturer shall develop a prototype of the Vane type airflow relay and shall offer the same alongewith their internal test report to RDSO for type test. The following test shall be conducted on prototype at firms premises as type test: 1. Physical inspection and dimensional checks 2. Performance t est 3. Mechanical endurance test 4. Electrical endurance test 5. Insulation resistance test 6. Vibration and shunting shocks test 7. Contact resistance test 8. Di-electric test 7.2 Routine test : The following tests shall be conducted on series production on each vane type airflow relay by the manufacturer at their premises: 1. Physical inspection and dimensional checks

8 Page 8 of Performance Test 3. Insulat ion resistance test 4. Di-electric test 7.3 Acceptance test: For accepting a lot of vane type airflow, the following test on sample basis shall be conducted at firm s premises: 1. Physical inspection and dimensional checks 2. Performance Test 3. Insulation resistance test For accepting the lot of vane type airflow relay, the samples for acceptance tests shall be chosen at random 5% (Minimum 2 pieces) of the lot offered. 8. TEST DETAILS AND PROCEDURE 8.1 Physical inspection and dimensional checks The vane type airflow relay housing, flaps and other part of the assembly shall be examined for its dimensions and workmanship. The tightening of bolts and fixation of various components to be also checked. The general workmanship should be good with all the component properly secured and sharp edges rounded off. 8.2 Performance Test (Pickup and dropout speed) Relay assembly including flap shall be fitted in an air duct specially made for testing. Anemometer to measure the air velocity shall be

9 Page 9 of 12 installed in the circuit. The pick up and dropout speed will be measured by gradually increasing and decreasing the air velocity. Maximum pick up speed should be 5meter per second and minimum drop out speed should be 2 meter per second. 4.3 Di-electric Test The dielectric test shall be conducted as per IEC for supply voltage range between 72 V and 125 V with rms value of test voltage as 1500 V. 4.4 Insulation Resistance Test The insulation resistance of the unit between earth and current carrying parts shorted together shall be more than 10 mega ohm at a ambient temperature of 55 degree C measured with 500 V megger. 4.5 Electrical endurance test The Electrical & Mechanical endurance after successful completion of vibration and shock test. The complete relay assembly shall be subjected to 50,000-make and break operation with 3A inductive load at 110 V AC. The frequency of operation shall be 6 per minute with 5 sec. on and off periods each. At the completion of the test, the relay contacts shall be visually examined for any damages, making it unsuitable for use. 4.6 Mechanical endurance test The complete relay assembly shall be subjected to 1,00,000 operations (closing and opening) at the rate of one operation in two seconds. The operational values such as pick up and drop out speed and contact resistance shall be recorded before commencement of the test and

10 Page 10 of 12 subsequently after every 50,000 operations at the end of the test. The variation in operating values shall not exceed +/- 10 percent of the specified values after 1,00,000 operations. There should not be any physical deterioration making it unsuitable for use. Mechanical & Electrical endurance tests will be conducted on separate relays. 4.7 Test for withstanding vibration and shock Vibration and shock test to be conducted as per clause and 5.10 of IEC at 3g. After the test the performance and visual test to be repeated. 4.8 Contact resistance measurements : Contact resistance values of the contacts in closed position shall be recorded as per IEC 512 (Pt.2) before and after the electrical and mechanical endurance test. Before the test the contact resistance should not be more than 10 milli ohm and after the test it should not deteriote by more than 10% PROTOTYPE APPROVAL 9.1 Manufacturers shall obtain prior approval of Research Designs and Standards Organisation for each production model. He should submit the sample alongwith assembly and part drawings, copies of the reports of prototype carried by the manufacturer for inspection and approval. 9.2 The manufacturer shall submit clause by clause compliance of the specification TECHNICAL DOCUMENTS & MANUALS The manufacturer shall furnish with each order a prototype test data obtained on the batch under supply and a test certificate for each relay confirming that the relay has passed the routine tests at the manufacturer s works. Manufacturer shall also supply sufficient copies of maintenance instructions and spare parts lists.

11 Page 11 of TESTING FACILITIES The venue of testing shall be indicated by the purchaser. If the purchaser chooses the manufacturer s works as the place of testing, the latter shall provide personnel, equipment and premises for conducting the tests, free of charge. **********

12 Page 12 of 12 DISTRIBUTION: 1 CEE / Eastern Railway, Fairlie Place, Kolkata 2 CEE / Northern Railway, Baroda House, New Delhi 3 CEE / Central Railway, Mumbai CST 4 CEE / Northeast Frontier Railway, Maligaon, Guwahati 5 CEE / North Eastern Railway, Gorakhpur 6 CEE / South Central Railway, Secunderabad 7 CEE / Southern Railway, Park Town, Chennai 8 CEE / South Eastern Railway, Kolkata 9 CEE / Western Railway, Churchgate, Mumabi 10 CEE / North Central Railway, Hasting Road, Allahabad 11 CEE / Western Central Railway, Jabalpur 12 CEE / Integral Coach Factory, Chennai. 13 CEE / East Coast Railway, Bhuvneshwar 14 CEE / East Central Railway, Hajipur 15 CEE/ Rail Coach Factory, Kapurthala 16 CEE./ North Western Railway, Jaipur 17 Director / IRIEEN, Nasik Road 18 Director / CAMTECH, Gwalior 19 Secy.(Elec.) Railway Board, New Delhi 20 DDSE/DOC. 21 ADE-9 22 Unit Supervisor

13

14

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. DRAFT SPECIFICATION NO : RDSO/PE/SPEC/D/PS/0010-99 (REV. 0 ) SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. 0. FOREWORD 0.1 This specification covers manufacturing and

More information

RESEARCH DESIGNS & STANDARDS ORGANISATION MINISTRY OF RAILWAY POWER SUPPLY & EMU DIRECTORATE TITLE

RESEARCH DESIGNS & STANDARDS ORGANISATION MINISTRY OF RAILWAY POWER SUPPLY & EMU DIRECTORATE TITLE Page 1 of 21 File No. EL/7.1.108 Effective from 7.10.2003 K2-B-01 Pt.II (Electrical) RESEARCH DESIGNS & STANDARDS ORGANISATION MINISTRY OF RAILWAY POWER SUPPLY & EMU DIRECTORATE TITLE PARTICULAR SPECIFICATION

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT / 2005-06 SR.NO ITEM PAGE 1. SCOPE 2 2. WEATHER CONDITIONS 2 3. RATED VOLTAGE & FREQUENCY 2 4. GENERAL REQUIREMENT

More information

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES: TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES: 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY IPSS SPECIFICATION FOR MAGNETIC OVER- CURRENT RELAYS FOR ac AND dc MOTORS PROTECTION UP TO 650 V (FIRST REVISION) CORRESPONDING INDIAN STANDARD DOES NOT EXIST IPSS:1-04-008-11

More information

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY.

TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. TECHNICAL SPECIFICATIONS FOR LT DISTRIBUTION BOX MADE FROM THERMOSETTING PLASTIC HAVING 200 /400 AMP CAPACITY. 1.0 SCOPE: This specification covers the design, manufacturing and testing of LT Distribution

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Free Static GK E-book Indian Railways at a glance

Free Static GK E-book Indian Railways at a glance Free Static GK E-book Indian Railways at a glance Static GK is an integral part of the general awareness section. Questions related to Indian Railways are common in the general awareness section of Bank

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution

More information

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

More information

ARAI/TA(4G_RV)/SMS/D680/ Dated 21 st Mar 2015 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES

ARAI/TA(4G_RV)/SMS/D680/ Dated 21 st Mar 2015 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s SMS Autoline Equipments Pvt. Ltd. Plot No.AP215, 6 th Street, I Block, Vallalar Colony, Anna Nagar (West) Chennai 600 040 Cert Annex Drg

More information

Dakshin Gujarat Vij Company Limited

Dakshin Gujarat Vij Company Limited Dakshin Gujarat Vij Company Limited CIN U40102GJ2003SGCO42909 Regd. & Corporate Office: Urja Sadan, Nana Varachha Road, Kapodara Char Rasta,Surat 395 006 C & R DEPARTMENT Phone No.: 0261 2506100-200-175

More information

REVISION HISTORY REVISION NUMBER. DATE PAGE CONTENTS New 28-May-2015

REVISION HISTORY REVISION NUMBER. DATE PAGE CONTENTS New 28-May-2015 Title 1 11 REVISION HISTORY REVISION NUMBER DATE PAGE CONTENTS New 28-May-2015 2 11 3 11 1.Scope This standard specifies EVFC whose rated voltage is 500V DC and breaking capacity is 10000A (hereinafter

More information

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : : DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : FOREWORD : Even though 11KV Drop Cut Fuse Cut Outs are widely used for protection / isolation of distribution transformers, their quality

More information

INTER PLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR AC CABIN FAN. Corresponding IS does not exist IPSS:

INTER PLANT STANDARD - STEEL INDUSTRY SPECIFICATION FOR AC CABIN FAN. Corresponding IS does not exist IPSS: INTER PLANT STANDARD - STEEL INDUSTRY IPSS SPECIFICATION FOR AC CABIN FAN FOR EOT CRANES (First Revision) Corresponding IS does not exist IPSS:1-03-011-92 Formerly IPSS:1-03-011-87 0. FOREWORD 0.1 This

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

Name of Zone Head Quarter No. of Divisions

Name of Zone Head Quarter No. of Divisions An overview of Indian Railways Brief History: First passenger train ran in India on 16 th April 1853 between Boribunder and Thane, since then Indian Railways has been a continuous progressing. Following

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

ARAI/TA(4G)/GEN-MAINT/EXOSCAN-V/ Dated 26 th Mar 2009 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES

ARAI/TA(4G)/GEN-MAINT/EXOSCAN-V/ Dated 26 th Mar 2009 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s Gen-Maint 106-107, New Diamond Premises Coop. Soc. Ltd. Off. Western Express Highway Goregaon (E) Mumbai 400 063 Cert Annex Drg Tot al

More information

ARAI/TA(4G_RV)/HORIBA/MEXA 584L/ Dated 25 Mar 2014

ARAI/TA(4G_RV)/HORIBA/MEXA 584L/ Dated 25 Mar 2014 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s Horiba India Pvt. Ltd. Room 1521, 15 th Floor, Eros Corporate Tower, Nehru Place New Delhi 110 019 Cert Annex Drg Total 1 7 0 8 pgs Exhaust

More information

This standard covers the requirements of lighting chains. This standard covers only the safety requirements.

This standard covers the requirements of lighting chains. This standard covers only the safety requirements. FOREWORD (Formal clause will be added later) This standard covers the requirements of lighting chains. This standard covers only the safety requirements. This standard (Part 5/Section 7) is one among the

More information

026-2 : 1996 CEB STANDARD

026-2 : 1996 CEB STANDARD 026-2 : 1996 CEB STANDARD COMPRESSION CONNECTORS & TERMINATIONS FOR OVERHEAD LINE CONDUCTORS CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable

More information

ARAI/TA (4G)/AIRVISOR/AVG500/ Dated 17 th Apr 2017

ARAI/TA (4G)/AIRVISOR/AVG500/ Dated 17 th Apr 2017 Airvisor Technologies Pvt. Ltd. H-155, Adhyapak Nagar, Nangloi, New Delhi 110041. CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES Cert Annex Drg Total 1 7 0 8 pgs Exhaust Gas Analyzer Model

More information

ARAI/TA(4G)/SMS/D680/ Dated 28 Jan 2010

ARAI/TA(4G)/SMS/D680/ Dated 28 Jan 2010 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s SMS Autoline Equipments Pvt. Ltd. Plot No.AP215, 6 th Street I Block, Vallalar Colony, Anna Nagar (West) Chennai 600 040 Cert Annex Drg

More information

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF Power IT MV Live Tank Vacuum Circuit Breaker Model VBF ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable utility

More information

HARYANA VIDYUT PRASARAN NIGAM LTD.

HARYANA VIDYUT PRASARAN NIGAM LTD. HARYANA VIDYUT PRASARAN NIGAM LTD. TECHNICAL SPECIFICATION SSD/S-03/R-1/DGM-605 TECHNICAL SPECIFICATION FOR 33 KV CAPACITOR BANKS CHIEF ENGINEER/MM HVPNL, PANCHKULA TELEPHONE & FAX: 0172-2583724 MARCH-2017-0

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR ac ROLLER TABLE MOTORS (Second Revision) Corresponding IS does not exist IPSS:1-03-007-14 Formerly : IPSS:1-03-007-03 0. FOREWORD 0.1 This Inter

More information

Price List No.: LTD/002 Effective from Supercedes Price List No.: LTD/001 Dated (Added new Series, Options & Accessories)

Price List No.: LTD/002 Effective from Supercedes Price List No.: LTD/001 Dated (Added new Series, Options & Accessories) 1 CG DRIVE-SK Simple to use Compact to fit Power to perform S.No Sensorless Vector Drive Suitable for operation 200/240VAC+/-10% Enclosure IP20,Vertical Mounted as standard Model No. (kw) (HP) Phase Voltage

More information

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36 We thank you for having purchased VCB s from us. We are sure you will be very happy with the performance and service of

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION SECTION - III TECHNICAL SPECIFICATION OF AB SWITCH & HG FUSE NESCO : TN/ 17427/14.11.11-1 - 1. 33 KV 200 Amp 3 Pole HG Fuse (Horizontal Mounting Type) Quantity 15 Sets Technical Specification 1. SCOPE:

More information

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.

More information

City of Storm Lake Fire Department Heavy Rescue Specifications

City of Storm Lake Fire Department Heavy Rescue Specifications INTENT OF SPECIFICATIONS City of Storm Lake Fire Department Heavy Rescue Specifications It shall be the intent of these specifications to provide a complete apparatus equipped as hereinafter specified.

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2

WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO. GUARANTEED TECHNICAL PARTICULARS 1 of 2 Sl. No. WESTERN ELECTRICITY SUPPLY COMPANY OF ORISSA, WESCO GUARANTEED TECHNICAL PARTICULARS 1 of 2 REQUIREMENTS 11 Kv, 200 Amps, A.B Switches. Particulars 1 Maker's name and Country of origin. 2 Type

More information

XMC0 Series DEFINITE PURPOSE CONTACTORS

XMC0 Series DEFINITE PURPOSE CONTACTORS DESCRIPTION American Zettlers XMC0 series of Definite Purpose Contactors are electromechanical switching devices designed ideally for the HVAC industry. The most common applications of our contactors are

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

HS1E Series Full Size Interlock Switch with Locking Solenoid

HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Series HS1E Series Full Size Interlock Switch with Locking Solenoid HS1E Key features include: Basic unit and solenoid unit in one housing Plastic Housing: Light weight Ease of Wiring: All the terminal

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

Selection Guide Automotive Relays

Selection Guide Automotive Relays Selection Guide Automotive Relays Classification Ultra-Miniature PCB Relay Model G8N1 G8ND2 G8NW Features Fully sealed construction Twin automotive relay Fully automated assembly suitable for polarity

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

SPECIFICATION AND PERFORMANCE TABLE OF CONTENT. 1. Scope Reference Documents Material and Components... 2

SPECIFICATION AND PERFORMANCE TABLE OF CONTENT. 1. Scope Reference Documents Material and Components... 2 TABLE OF CONTENT 1. Scope... 2 2. Reference Documents.. 2 3. Material and Components...... 2 4. Design and Construction..... 2 5. Rating.. 2 6. Performance and Test Descriptions. 2 7. Test Requirements

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

SPECIFICATIONS OF REWIRABLE KIT KAT FUSES

SPECIFICATIONS OF REWIRABLE KIT KAT FUSES SPECIFICATIONS OF REWIRABLE KIT KAT FUSES 1. SCOPE: This application cover the manufacture, testing at works and supply of porcelain rewire able kit kat fuses suitable for AC 3 phase 415 V 50 HZ solidly

More information

PERFORMANCE SPECIFICATION SHEET SWITCHES, SENSITIVE, 10 AMPERES AND LOW LEVEL, UNSEALED

PERFORMANCE SPECIFICATION SHEET SWITCHES, SENSITIVE, 10 AMPERES AND LOW LEVEL, UNSEALED INCH-POUND 2 January 201 SUPERSEDING 1 May 200 PERFORMANCE SPECIFICATION SHEET SWITCHES, SENSITIVE, AMPERES AND LOW LEVEL, UNSEALED This specification is approved for use by all Departments and Agencies

More information

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005.

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005. BUREAU OF INDIAN STANDARDS (CENTRAL MARKS DEPARTMENT-III) Our Ref: CMD-III/16:8034 25 Oct 2004 Subject: Implementation of revised IS 8034:2002 Submersible Pump Sets and revised STI (Doc:STI/8034/5 ) IS

More information

Power IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB

Power IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB Power IT MV Live Tank Vacuum Circuit Breaker Model OVB-SDB ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable

More information

OUTDOOR OFF LOAD DISCONNECTORS HCB/HDB Range

OUTDOOR OFF LOAD DISCONNECTORS HCB/HDB Range OUTDOOR OFF LOAD DISCONNECTORS HCB/HDB Range SWITCHGEAR COMPLEX SWITCHGEAR COMPLEX Crompton Greaves Ltd. the name to reckon in Electrical Industry, brings a product with its leading edge technology to

More information

TEST METHODS CONCERNING TRANSPORT EQUIPMENT

TEST METHODS CONCERNING TRANSPORT EQUIPMENT PART IV TEST METHODS CONCERNING TRANSPORT EQUIPMENT - 403 - CONTENTS OF PART IV Section Page 40. INTRODUCTION TO PART IV... 407 40.1 PURPOSE... 407 40.2 SCOPE... 407 41. DYNAMIC LONGITUDINAL IMPACT TEST

More information

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS INTER PLANT STANDARD STEEL INDUSTRY SOFT STARTER FOR VOLTAGE UP TO 690 V AC IPSS: 1-10-040-15 IPSS NO CORRESPONDING IS 0. FOREWORD 0.1 This interplant standard has been prepared by the Standard Committee

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall

More information

PERFORMANCE SPECIFICATION SHEET

PERFORMANCE SPECIFICATION SHEET INCH-POUND MIL-PRF-83536/15A 12 July 2004 SUPERSEDING MIL-PRF-83536/15 27 March 1992 PERFORMANCE SPECIFICATION SHEET RELAYS, ELECTROMAGNETIC, ESTABLISHED RELIABILITY, 4PDT, LOW LEVEL TO 10 AMPERES, PERMANENT

More information

Model Number Structure

Model Number Structure Power Relay G7J Electromechanical Relays A High-capacity, High-dielectric-strength, Multi-pole Relay Used Like a Contactor Miniature hinge for maximum switching power for motor loads as well as resistive

More information

Volume-III : Section-I 370 Technical Specifications

Volume-III : Section-I 370 Technical Specifications Volume-III : Section-I 370 TECHNICAL SPECIFICATION-PIERCING INSULATOR 5.1 Insulation Piercing Connectors (IPC) 5.1.1 Insulation Piercing Connectors (IPC) are used for making Tee/Tap-off/Service connectors

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

Decree of the Ministry of Transport and Communications

Decree of the Ministry of Transport and Communications 579/2000 Decree of the Ministry of Transport and Communications on transportable pressure equipment and tanks discharged or filled by pressure and used for the transport of dangerous goods Adopted in Helsinki,

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

INTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996

INTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996 INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996 IPSS: 1-03-001-14 Formerly: IPSS:1-03-001-05 0. FOREWORD

More information

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017*

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017* SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017* PRODUCT: Screw-Type Superchargers 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for evaluating

More information

TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT

TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT Page 1 (7) TECHNICAL REQUIREMENTS FOR ELECTRICAL EQUIPMENT Title Document Asynchronous electric motors TBE 103 Issue 6 (E) Contents 1 GENERAL... 2 2 DEFINITIONS... 2 3 GENERAL PRODUCT REQUIREMENTS... 3

More information

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)

More information

HS1E Series Full Size Solenoid Locking Switches

HS1E Series Full Size Solenoid Locking Switches HS1E Series Full Size Solenoid Locking Switches AS-Interface Safety at Work Barriers Enabling Switches Door Interlock Switches X Series E-Stops Overview HS1E features: Basic unit and solenoid unit in one

More information

TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077

TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077 spec- 200 Amp. & 400 Amp. LT Dist. Kiosk.doc - 1 - SCHEDULE-III TECHNICAL SPECIFICATION FOR SUPPLY OF LT DISTRIBUTION KIOSK FOR 250/315 KVA & 63/100 KVA RATING DISTRIBUTION TRANSFORMERS AGAINST TN-2077

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS TENDER DOCUMENT TENDER NO.: DLI/C&E/WI-675/275 FOR Tender for Design, Engineering, Supply and Supervision of installation, testing & commissioning of Cable Reeling Drum with Composite Flexible Trailing

More information

Jun06 Rev D

Jun06 Rev D Product Specification High Speed Serial Data 2 Connector 108-1965 27Jun06 Rev D 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the Tyco Electronics High

More information

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil) Ergon Energy Corporation Limited Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear ETS12-01-03 Specification ETS12-01-03 Ver 3 Contents 1. Purpose and Scope...

More information

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air) Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear ETS12-01-02 Specification ETS12-01-02 Ver 3 Contents 1. Purpose

More information

BIHAR STATE POWER TRANSMISSION COMPANY LIMITED MANUFACTURING QUALITY PLAN -- BATTERY CHARGER. Quantum of Check / Sampling with basis

BIHAR STATE POWER TRANSMISSION COMPANY LIMITED MANUFACTURING QUALITY PLAN -- BATTERY CHARGER. Quantum of Check / Sampling with basis A. Section : RAW MATERIAL INSPECTION 1.0 ELECTRONIC COMPONENTS 1.1 RESISTORS (Metal Film, Wire Wound) 1.2 POTENTIOMETERS 1.3 CAPACITORS (Polystyrene, electrolytic) 1.4 TRANSISTORS 1.5 L E D 1.6 1.7 INTEGRATED

More information

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. Technical Specification for 33 KV 200 AMPs,H.G,Fuse set. 1. SCOPE:- This specification covers the manufacture, testing and supply of 33KV 200 Amps, H.G. Fuse sets 2. The 33 KV H.G. Fuses shall be suitable

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

HS1C Interlock Switches with Solenoid

HS1C Interlock Switches with Solenoid HSC es with The guard door remains locked until the machine stops completely. With the actuator mounted on the guard door and the interlock switch on the machine, the door is mechanically locked when closed.

More information

Supply, Installation and Commissioning of 1 No 50 Watt LED. based SPV SLS at Nadia District Library, Krishna Nagar, Nadia.

Supply, Installation and Commissioning of 1 No 50 Watt LED. based SPV SLS at Nadia District Library, Krishna Nagar, Nadia. Supply, Installation and Commissioning of 1 No 50 Watt LED based SPV SLS at Nadia District Library, Krishna Nagar, Nadia. TENDER DOCUMENT. (A Govt. of West Bengal Company) Bikalpa Shakti Bhavan, Plot J1/10,

More information

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Menu. Home About this portal Latest updates. Print Save  Resource detail Citations. Table of Contents Menu Home About this portal Latest updates Print Save Email Resource detail Citations AS/NZS 60898.1:2004 Electrical accessories - Circuit-breakers for overcurrent protection for household and similar

More information

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS 1 Module 2 CONTROL SYSTEM COMPONENTS Lecture - 4 RELAYS Shameer A Koya Introduction Relays are generally used to accept information from some form of sensing device and convert it into proper power level,

More information

SECTION V, 3-PHASE, 630 AMPS MCCB & ENCLOSURE

SECTION V, 3-PHASE, 630 AMPS MCCB & ENCLOSURE SECTION 07 TECHNICAL SPECIFICATIONS OF FOR 415V, 3-PHASE, 630 AMPS MCCB & ENCLOSURE 7.0 TECHNICAL SPECIFICATIONS/ REQUIREMENTS OF 415V, 630A, 3-PHASE MCCB WITH ENCLOSURE 7.1 GENERAL This section of the

More information

SPECIFICATIONS FOR MOTOR OPERATED VALVES

SPECIFICATIONS FOR MOTOR OPERATED VALVES Doc No: 254625-300-SP-INT-004 Rev: B Page 1 of 11 SPECIFICATIONS FOR MOTOR OPERATED VALVES Hindustan Petroleum Corporation Ltd Visakha Dispatch Station VR-ATP Area, Naval Base Post Visakhapatnam - 530

More information

12-SDMS-02 REV. 05 ( )

12-SDMS-02 REV. 05 ( ) 12-SDMS-02 REV. 05 (22-05-2018) SPECIFICATION FOR LUGS AND CONNECTORS FOR LOW-VOLTAGE & MEDIUM-VOLTAGE DISTRIBUTION SYSTEM Saudi Electricity Company 1. SCOPE... 3 2. CROSS REFERENCES TO OTHER SEC STANDARDS...

More information

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause

More information

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59. Single Pole Circuit Protectors 55 Multi-Pole Circuit Protectors 56 Configurations 58 Operating Characteristics 59 Delay Curves 60 Specifications 61 Decision Tables 62 SINGLE POLE CIRCUIT PROTECTORS The

More information