1 INTER PLANT STANDARD - STEEL INDUSTRY IPSS SPECIFICATION FOR AC CABIN FAN FOR EOT CRANES (First Revision) Corresponding IS does not exist IPSS: Formerly IPSS: FOREWORD 0.1 This Interplant Standard (First Revision) prepared by the Standards Committee on Rotating Electrical Machinery, IPSS 1:3 with the active participation of representatives of the steel plants and other associated organizations, was adopted by the Approval Committee on Consumable Stores and General Equipment, IPSS 1 on 13 February Interplant Standards for steel industry primarily aim at achieving rationalization and unification of parts and assemblies used in steel plant equipment and accessories, and provide guidance in Indenting stores or equipment (or while placing orders for additional requirements) by individual steel plants. For exercising effective control on inventories, it is advisable to select a fewer number of sizes (or types) from among those mentioned in this standard, for the purpose of company standards of individual steel plants. It is not desirable to make deviations in technical requirements. 0.3 This Interplant Standard was first published in This revision has been carried out to update the standard based on the requirements of the steel plants. 0.4 In this standard, frequent references have been made to the following Indian Standards: IS 555:1979 Specification for electric table type fans and regulators (third revision) IS 4691:1985 Degrees of protection provided by enclosures for rotating electrical machinery (first revision) IS 6362:1971 Designation of methods of cooling of rotating electrical machines IS 6680:1972 Specification for railway carriage fans IS 8354:1977 Code of practice for packaging of electric fans

2 1. SCOPE 1.1 This Interplant Standard specifies the requirements of ac cabin fans suitable for operation on 240 V single phase ac 50 Hz square or sine wave form, or 250 V dc in conjunction with an inverter for use in operator's cabin in EOT cranes. 2. SITE CONDITIONS 2.1 The following shall constitute normal site conditions for the purpose of this standard: a) Ambient Temperature - The ambient temperature or the cooling medium temperature not exceeding 50 deg C. b) Relative Humidity - The relative humidity can be up to the maximum of 100 percent. Maximum ambient temperature and 100 percent relative humidity may not occur simultaneously. c) Ambient air - This may contain fair amount of conductive dust. d) Altitude - Not exceeding 1000 m. 3. RATING 3.1 Air Delivery - 30 m 3 /min. 3.2 Speed rpm. 4. GENERAL REQUIREMENTS 4.1 The cabin fan shall have a sweep of 400 mm and shall be of tilting type, but nonoscillating. Provision shall be made for locking it in any desired position. 4.2 The fan shall be suitable for operation on 240 V (+ 6/- 10 %) single phase, 50 Hz, ac supply. 4.3 The fan shall conform to IS 555:1979 with regard to general and safety requirements, air delivery, service value, test requirements etc, unless otherwise specified in this standard. 4.4 There shall be minimum of 3 numbers of holes on the base, to accommodate bolts of at least 9 mm diameter for mounting. 4.5 It shall be possible to mount the fan on a vertical plane or in an inverted position and the fan shall be capable of working efficiently in any position of mounting.

3 4.6 Foundation details as specified by the user. 5. TECHNICAL REQUIREMENTS 5.1 Design and General Construction Motor - The motor shall be of 100 percent duty cycle and so designed that it may readily be dismantled without disturbing the fan base. The fan shall be of robust construction to ensure satisfactory operation under conditions of vibration, rough usage etc, as encountered in the EOT cranes. The fan motor shall be ac capacitor or shaded pole type. It shall have an enclosure conforming to IP 54 degree of protection according to IS 4691:1985. Motor cooling shall correspond to the cooling designation IC 0141 according to IS 6362:1971. The motor shall be so designed that the performance of fans working in dusty atmosphere is not impaired The motor winding shall be of Copper conductor and its insulation shall not be inferior to class `B' The motor shaft shall be mounted on sealed antifriction bearings of size 10 x 30 x 9 packed with lithium base grease. 5.2 Stampings - Stampings of fan motors shall conform to IS 555: Blades - The fan shall be fitted with four well balanced blades made from mild steel sheet of thickness not less than 0.9 mm. It shall conform to clause 7.3 of IS 6680:1972 and shall be securely fixed so that they do not get loose in operation and vibration normally encountered in an EOT crane. The blade carrier shall have a provision to lock it on the motor shaft extension. The minimum gap between the blades and the guard shall not be less than 25 mm. 5.4 Guard - The fan shall have a hinged guard conforming to clause 7.7 and of IS 6680: A knob shall be provided at the centre of the guard for the purpose of tilting the fan. 5.5 Base - The base shall be even and large enough so that the fan does not topple in any position of the tilt and with the fan running. 5.6 Resilient Pad - For damping the vibration normally encountered on EOT cranes, a resilient pad of at least 12 mm thickness shall be secured firmly to the bottom of the base by a suitable adhesive with holes drilled to accommodate bolts of the required size. 5.7 Noise Level - When measured at a distance of one metre from the plane of the blades along the axis, the noise level of the sound coming from the fan shall not exceed 50 db at a reference of 20 micro-pascal.

4 6. MARKING 6.1 Each fan shall be provided with a name plate indelibly marked with the following information: a) Manufacturer's name, trade-mark (if any), b) Type designation or serial number, c) Rated Voltage, d) Input in Watts, e) Size of fan in mm, f) Class of insulation, and g) Details of bearing. 6.2 Earthing terminal or contact shall be indelibly marked with the symbol 7. PACKING 7.1 The assembled fan shall be packed in strong wooden case in accordance with IS 8354:1977. Paste board fillers shall be provided to prevent damage during transit. 8. SPARES 8.1 The manufacturer shall supply full information of the recommended spares. 9. TESTS 9.1 Type Tests - The following type tests shall be conducted: a) Air delivery tests (clause 18.2 of IS 6680:1972), and b) Temperature rise test (clause 15.3 of IS 555:1979 except that the temperature rise test for insulated winding of the motor shall be suitable for class B insulation, the other values remaining the same). 9.2 Routine Tests - The following routine tests shall be conducted a) Flash test (clause of IS 555:1979), b) Insulation resistance test (clause of IS 555:1979), and

5 c) Running test to determine that the fan is in working order. 10. INVERTER 10.1 If the fan is to be fitted on a dc EOT crane operating at 250 V dc, an inverter with the following specification shall be used for operating the fan: Static inverter : Suitable for 400 mm sweep cabin fan for EOT crane Input voltage : From 190 V dc to 270 V dc depending on position of EOT crane with respect to feeding point of power rails Output voltage Output frequency input supply : 220 V ac to 240 V ac at 60 VA load : 50 Hz normal with variation up to maximum 53 Hz at 270 V dc Output wave-form : Overload capacity : Square wave 200 percent continuous Ambient temperature : 50 deg C average 10.2 Polarity reversal on dc side shall have no effect on the operation of the inverter. In other words, it shall be possible to connect the dc supply to the inverter terminals without having to ensure correct polarity. NOTE: It may also be noted that the inverter is to be fitted on EOT cranes subjected to vibrations, dust and heat.

INTER PLANT STANDARD STEEL INDUSTRY

INTER PLANT STANDARD STEEL INDUSTRY INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR ac CRANE (Hoist and Winches) DUTY SQUIRREL CAGE INDUCTION MOTORS (Fourth Revision) BASED ON IS 325:1996 Formerly: IPSS:1-03-004-05 0. FOREWORD

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY IPSS SPECIFICATION FOR MAGNETIC OVER- CURRENT RELAYS FOR ac AND dc MOTORS PROTECTION UP TO 650 V (FIRST REVISION) CORRESPONDING INDIAN STANDARD DOES NOT EXIST IPSS:1-04-008-11

More information

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR ac ROLLER TABLE MOTORS (Second Revision) Corresponding IS does not exist IPSS:1-03-007-14 Formerly : IPSS:1-03-007-03 0. FOREWORD 0.1 This Inter

More information

INTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996

INTER PLANT STANDARD STEEL INDUSTRY. SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996 INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR GENERAL PURPOSE SQUIRREL CAGE INDUCTION MOTORS (Fifth Revision) BASED ON IS 325:1996 IPSS: 1-03-001-14 Formerly: IPSS:1-03-001-05 0. FOREWORD

More information

INTER PLANT STANDARDIZATION STEEL INDUSTRY

INTER PLANT STANDARDIZATION STEEL INDUSTRY INTER PLANT STANDARDIZATION STEEL INDUSTRY IPSS SPECIFICATION FOR IPSS:1-04-027-11 MAGNETIC CLUTCH (FIRST REVISION) Corresponding IS does not exist Formerly : IPSS:1-04-027-93 0. FOREWORD 0.1 This Interplant

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

SPECIFICATION FOR BUTTON HEAD CEASE NIPPLES

SPECIFICATION FOR BUTTON HEAD CEASE NIPPLES INTER PLANT STANDARD IN STEEL INDUSTRY SPECIFICATION FOR BUTTON HEAD CEASE NIPPLES IPSS: 1-02-061-18 (Second Revision) IPSS BASED ON IS4009 (Part 1): 1981 Formerly: IPSS: 1-02-061-97 (First Revision) 0.

More information

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS INTER PLANT STANDARD STEEL INDUSTRY SOFT STARTER FOR VOLTAGE UP TO 690 V AC IPSS: 1-10-040-15 IPSS NO CORRESPONDING IS 0. FOREWORD 0.1 This interplant standard has been prepared by the Standard Committee

More information

INTERPLANT STANDARD STEEL INDUSTRY ACCEPTANCE NORMS FOR CRANE GEAR BOX FOR TWO STAGE HORIZANTAL Corresponding IS does not exist

INTERPLANT STANDARD STEEL INDUSTRY ACCEPTANCE NORMS FOR CRANE GEAR BOX FOR TWO STAGE HORIZANTAL Corresponding IS does not exist INTERPLANT STANDARD STEEL INDUSTRY ACCEPTANCE NORMS FOR CRANE GEAR BOX FOR TWO STAGE HORIZANTAL Corresponding IS does not exist IPSS:1-08-020-18 (Third Revision) Formerly: IPSS:1-08-020-14 (Second Revision)

More information

INTER PLANT STANDARD STEEL INDUSTRY

INTER PLANT STANDARD STEEL INDUSTRY INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR CABLE REELING DRUM (Second Revision) Corresponding IS does not exist IPSS : 1-10-017-11 Formerly : IPSS: 1-10-017-03 0. FOREWORD 0.1 This Inter

More information

INTER PLANT STANDARD IN STEEL INDUSTRY SPECIFICATION OF HYDRAILIC HOSE ASSEMBLY & END FITTING FOR HYDRAULIC LINES

INTER PLANT STANDARD IN STEEL INDUSTRY SPECIFICATION OF HYDRAILIC HOSE ASSEMBLY & END FITTING FOR HYDRAULIC LINES INTER PLANT STANDARD IN STEEL INDUSTRY IPSS SPECIFICATION OF HYDRAILIC HOSE ASSEMBLY & END FITTING FOR HYDRAULIC LINES IPSS: 1-02-007-18 (First Revision) Corresponding IS does not exist Formerly: IPSS:

More information

INTERPLANT STANDARD - STEEL INDUSTRY. SPECIFICATION FOR SINGLE, DOUBLE & TRIPLE SHEAVE PULLEY BLOCKS FOR FIBRE ROPE (Second Revision )

INTERPLANT STANDARD - STEEL INDUSTRY. SPECIFICATION FOR SINGLE, DOUBLE & TRIPLE SHEAVE PULLEY BLOCKS FOR FIBRE ROPE (Second Revision ) INTERPLANT STANDARD - STEEL INDUSTRY IPSS SPECIFICATION FOR SINGLE, DOUBLE & TRIPLE SHEAVE PULLEY BLOCKS FOR FIBRE ROPE (Second Revision ) Corresponding IS does not exist IPSS:1-07-005-14 Formerly: IPSS:1-07-005-00

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

Mixed Flow Roof Fans (RMH)

Mixed Flow Roof Fans (RMH) Mixed Flow Roof Fans (RMH) Motors protected to IP44 Motor insulation Class B Maximum operating temperature 4 C Standard Thermal Overload Protection IP65 service isolator Bird guard included as standard

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Technical standard for AC, DC and street light systems

Technical standard for AC, DC and street light systems Technical standard for AC, DC and street light systems Concept of design: Solar Street Lighting System Street lighting in off-grid areas is a necessity to ensure security in night time. Solar technology

More information

Mixed Flow Roof Fans (RMH)

Mixed Flow Roof Fans (RMH) Mixed Flow Roof Fans (RMH) Features and Benefits Motors protected to IP44 Motor insulation Class B Maximum operating temperature 4 C Standard Thermal Overload Protection IP65 P65 service isolator Guard

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3112:2011 AS/NZS 3112:2011 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets AS/NZS 3112:2011 This Joint Australian/New Zealand Standard was prepared by Joint

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

CORE VALUES TECHNOLOGIES ESS-ESD PRODUCT CATALOGUE Enjoy the peace of mind ENGINE POWER SUPPLIERS AND EQUIPMENT HEAT

CORE VALUES TECHNOLOGIES ESS-ESD PRODUCT CATALOGUE   Enjoy the peace of mind ENGINE POWER SUPPLIERS AND EQUIPMENT HEAT TECHNOLOGIES ENGINE POWER SUPPLIERS AND EQUIPMENT HEAT Enjoy the peace of mind ESS-ESD PRODUCT CATALOGUE CORE VALUES PEACE OF MIND EFFICIENCY FAIRNESS RESPONSIBILITY CUSTOMER ORIENTATION GROWING DEVELOPED

More information

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Menu. Home About this portal Latest updates. Print Save  Resource detail Citations. Table of Contents Menu Home About this portal Latest updates Print Save Email Resource detail Citations AS/NZS 60898.1:2004 Electrical accessories - Circuit-breakers for overcurrent protection for household and similar

More information

champion series motors

champion series motors Introducing A brand new series of Super Performers Data Sheet champion series motors FRAME SIZE 63-132M TEFC 3 Phase Squirrel Cage Induction Motors Siemens CHAMPION Series Cage Motors are suitable for

More information

Terminal Box Are to IP54, as standard, protected against dust and water from any angle allowing outside applications.

Terminal Box Are to IP54, as standard, protected against dust and water from any angle allowing outside applications. EuroSeries (ESR) Cowl & base moulded from recyclable polymeric material All sizes resistant to UV light Sizes 250 to 1000 dia are protected to IP54 Optional backdraught shutters and bird guard (250-630mm)

More information

ISO 8379 INTERNATIONAL STANDARD. Rough terrain trucks Stability tests. Chariots élévateurs tous terrains à fourches Essais de stabillité

ISO 8379 INTERNATIONAL STANDARD. Rough terrain trucks Stability tests. Chariots élévateurs tous terrains à fourches Essais de stabillité INTERNATIONAL STANDARD ISO 8379 First edition 1998-07-01 Rough terrain trucks Stability tests Chariots élévateurs tous terrains à fourches Essais de stabillité A Reference number Provläsningsexemplar /

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

Vent-Axia Sabre Sickle Roof Fans (VSR)

Vent-Axia Sabre Sickle Roof Fans (VSR) Vent-Axia Sabre Sickle Roof Fans (VSR) Features and Benefits High performance roof sickle fan Fully assembled cowl. Optional backdraught shutters and birdguard Moulded from recyclable polymeric material,

More information

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations Only the Danish version is authentic Notice D II-1 D 1 October 2002 Technical regulation on the construction and equipment, etc. of passenger ships on domestic voyages CHAPTER II-1 D Construction subdivision

More information

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION TITLE SPECIFICATION FOR CONTACTORS FOR PUBLIC LIGHTING REFERENCE REV DATE: NOVEMBER 2010 PAGE: 1 OF 16 TABLE OF CONTENTS Page FOREWORD.. 2 INTRODUCTION 3 1 SCOPE...... 3 2 NORMATIVE REFERENCES...... 3

More information

MT/T Translated English of Chinese Standard: MT/T COAL INDUSTRY STANDARD

MT/T Translated English of Chinese Standard: MT/T COAL INDUSTRY STANDARD Translated English of Chinese Standard: MT/T249-1997 www.chinesestandard.net Sales@ChineseStandard.net COAL INDUSTRY STANDARD MT OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.160.30 K 25 MT/T 249-1997 Flameproof

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

PURE SINE WAVE DC TO AC POWER INVERTER

PURE SINE WAVE DC TO AC POWER INVERTER PURE SINE WAVE DC TO AC POWER INVERTER 60S-12A / 60S-24A 60S-12E / 60S-24E 100S-12A / 100S-24A 100S-12E / 100S-24E 150S-12A / 150S-24A 150S-12E / 150S-24E Instruction manual SINE WAVE INVERTER Please read

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number)

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number) POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 480 Volts, 60Hz April 15, 2010: updated capacitor UL File number) Page 1 of 14 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Advantage

More information

Sabre Sickle Fan Assisted Roof Cowls (VSR)

Sabre Sickle Fan Assisted Roof Cowls (VSR) Sabre Sickle Fan Assisted Roof Cowls (VSR) Swept impeller with Aerofoil blades, winglets and serrated trailing edge for optimum performance Fully assembled cowl, separate plate axial fan Optional backdraught

More information

SECTION MOTOR REQUIREMENTS for HVAC

SECTION MOTOR REQUIREMENTS for HVAC PART 1 GENERAL 1.1 SECTION INCLUDES A. Single-phase electric motors B. Three-phase electric motors 1.2 REFERENCES SECTION 23 05 13 MOTOR REQUIREMENTS for HVAC A. ABMA 9 - Load Ratings and Fatigue Life

More information

Modifiable TITAN Horizontal Motors Accessories and Modifications

Modifiable TITAN Horizontal Motors Accessories and Modifications 36. Rotor, Standard And Optional Construction Standard rotor construction of 449, 5000 and 5800 frame TITAN products is typically die-cast aluminum. 720 RPM and slower is typically fabricated aluminum.

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs

More information

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER Solid Dielectric Load Break Switch SPECIFICATION 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED VACUUM LOAD INTERRUPTING

More information

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. DRAFT SPECIFICATION NO : RDSO/PE/SPEC/D/PS/0010-99 (REV. 0 ) SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS. 0. FOREWORD 0.1 This specification covers manufacturing and

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding and Insulation

More information

Performance. Sound Levels. Impellers. Motors. Accessories

Performance. Sound Levels. Impellers. Motors. Accessories EuroSeries (ESP) Die cast aluminium impellers Fully speed controllable Air Volumes up to 13.89m 3 /s Sizes 250 to 1000 dia protected to IP54 Operating Temperatures from -40 C up to +70 C Insulation Class

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

الهيئة السعىدية للمىاصفبت والمقبييس والجىدة Saudi Standards, Metrology and Quality Org (SASO)

الهيئة السعىدية للمىاصفبت والمقبييس والجىدة Saudi Standards, Metrology and Quality Org (SASO) الهيئة السعىدية للمىاصفبت والمقبييس والجىدة Saudi Standards, Metrology and Quality Org (SASO) Draft Standard SASO IEC 60034-30-1:XXXX ROTATING ELECTRICAL MACHINES Part 30-1: Efficiency classes of line

More information

SG-B1 SERIES / SG-A1 SERIES

SG-B1 SERIES / SG-A1 SERIES 643 Door with Solenoid Interlock / Door Ultra-slim SG-B1 SERIES / SG-A1 SERIES Related Information General terms and conditions... F-7 General precautions... P.1501 PHOTO PHOTO Conforming to Machine &

More information

COMMISSION REGULATION (EC)

COMMISSION REGULATION (EC) L 191/26 Official Journal of the European Union 23.7.2009 COMMISSION REGULATION (EC) No 640/2009 of 22 July 2009 implementing Directive 2005/32/EC of the European Parliament and of the Council with regard

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

Elimsan High Voltage Disconnectors

Elimsan High Voltage Disconnectors Elimsan High Voltage Disconnectors Pantograph Type Center-Break Type Double-Break Type Vertical-Break Type Standards IEC 62271-102 IEC 62271-1 Nature is our most distinguished partner YG-EN-12-01 Elimsan

More information

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3 TITLE SPECIFICATION FOR MEDIUM VOLTAGE DATE: FEBRUARY 2015 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD... 2 INTRODUCTION... 3 1 SCOPE... 3 2 NORMATIVE S... 3 3 DEFINITIONS AND ABBIATIONS... 3 4 REQUIREMENTS...

More information

Bifurcated Case Axial Fans (BIFA)

Bifurcated Case Axial Fans (BIFA) Bifurcated Case Axial Fans (BIFA) Sizes 250 to 1000 dia Motors protected to IP55 Motor insulation Class F Maximum ambient temperature 200 C Speed controllable via transformer or inverter (when the ambient

More information

Sabre Plate Mounted Sickle Fans (VSP)

Sabre Plate Mounted Sickle Fans (VSP) Sabre Plate Mounted Sickle Fans (VSP) Swept impeller with Aerofoil blades, winglets and serrated trailing edge for optimum performance One shot die cast impeller, dynamically balanced for smoother operation

More information

1200W INVERTER GENERATOR

1200W INVERTER GENERATOR 1200W INVERTER GENERATOR MODEL NO: IG1200 PART NO: 8877070 OPERATION & MAINTENANCE INSTRUCTIONS LS0117 INTRODUCTION Thank you for purchasing this CLARKE 1200W Inverter Generator. Before attempting to use

More information

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL Design Standard Detailed specifications follow. PART 1 - GENERAL 1.01 SCOPE This design guidelines contained herein include the requirements of electric motors utilized for electric motor driven systems

More information

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS :

: DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : : DGVCL/11KV D.O.FUSE/SPECIFICATION : : 11KV DROP OUT FUSE CUTOUTS : FOREWORD : Even though 11KV Drop Cut Fuse Cut Outs are widely used for protection / isolation of distribution transformers, their quality

More information

Dakshin Gujarat Vij Company Limited

Dakshin Gujarat Vij Company Limited Dakshin Gujarat Vij Company Limited CIN U40102GJ2003SGCO42909 Regd. & Corporate Office: Urja Sadan, Nana Varachha Road, Kapodara Char Rasta,Surat 395 006 C & R DEPARTMENT Phone No.: 0261 2506100-200-175

More information

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances

CONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding 4.4

More information

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...

More information

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS SECTION 26 20 00 LOW-VOLTAGE AC INDUCTION MOTORS SEWPCC UPGRADING/EXPANSION PROJECT PART 1 GENERAL 1.1 RELATED SECTIONS A. This section applies only when referenced by a motor-driven equipment specification.

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S Revised 04/14/2016 SPECIFICATIONS - DETAILED PROVISIONS Section 16151 - Vertical Hollowshaft Electric Motors C O N T E N T S PART 1 - GENERAL... 1 1.01 SCOPE... 1 1.02 SPECIFIC PROJECT REQUIREMENTS...

More information

A6C A5C-B6C B5C B5H A6C A5C B6C B5C B5H. Model. Up to kw. Power. Up to V. Voltages. Model IP55. Frame Pole 2, 4, 6, 8 and 10

A6C A5C-B6C B5C B5H A6C A5C B6C B5C B5H. Model. Up to kw. Power. Up to V. Voltages. Model IP55. Frame Pole 2, 4, 6, 8 and 10 A6C A5C-B6C B5C B5H Model Power Voltages Model IP55 A6C A5C B6C B5C B5H Up to 2.400 kw Up to 11.000 V LV A6C - B6C - A5C - B5C MV B5H Frame 71 560 Pole 2, 4, 6, 8 and 10 Cooling IC 411 ( IC 416 optional)

More information

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

AEEB AEVB LOW VOLTAGE SERIES Three-Phase Squirrel Cage Induction Motor Conforming to SS530 (Occasional Use) Conforming to IE1

AEEB AEVB LOW VOLTAGE SERIES Three-Phase Squirrel Cage Induction Motor Conforming to SS530 (Occasional Use) Conforming to IE1 AEEB AEVB LOW VOLTAGE SERIES Three-Phase Squirrel Cage Induction Motor Conforming to SS530 (Occasional Use) Conforming to IE1 STANDARD AND SPECIFICATION Performance: Meet the requirement of Singapore standard

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Annex A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 400V (750KVA) DIESEL

Annex A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 400V (750KVA) DIESEL Annex A TECHNICAL SPECIFICATION FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 400V (750KVA) DIESEL 1 TECHNICAL SPECIFICATION FOR 400V, 750 kva D.G. SET 1.0 SCOPE This specification covers the

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60034-1 Eleventh edition 2004-04 Rotating electrical machines Part 1: Rating and performance This English-language version is derived from the original bilingual publication

More information

3946 en / a. This manual is to be given to. the end user. HPM x44. A.C. motor. Installation and maintenance

3946 en / a. This manual is to be given to. the end user. HPM x44. A.C. motor. Installation and maintenance This manual is to be given to the end user Installation and maintenance To ensure that the LEROY-SOMER motor you have just purchased is entirely satisfactory, it is essential to adhere to the following

More information

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST TUBE AXIAL DUCT FANS INDUSTRIAL PROPELLER FANS INDUSTRIAL ROOF EXHAUSTERS HEAVY DUTY MAN/PRODUCT COOLERS WARNING BY ACCEPTANCE OF THIS MERCHANDISE,

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.

More information

L7486R Cromwell Word Distribution 8 Inch Bench Grinder KOBE GB 200 December 2009 MD

L7486R Cromwell Word Distribution 8 Inch Bench Grinder KOBE GB 200 December 2009 MD age 1 of 15 L7486R Cromwell Word Distribution 8 Inch Bench Grinder KOBE GB 200 December 2009 MD age 2 of 15 SUMMARY TEST REORT BS EN 61029-1: 2000, with BS EN 61029-2-4: 2003 Safety of transportable motor-operated

More information

EPACT ENERGY POLICY ACT OF 1992: THE SCOPE OF ELECTRIC MOTORS SUBJECT TO EFFICIENCY STANDARDS ON OCTOBER

EPACT ENERGY POLICY ACT OF 1992: THE SCOPE OF ELECTRIC MOTORS SUBJECT TO EFFICIENCY STANDARDS ON OCTOBER EPACT ENERGY POLICY OF 1992: THE SCOPE OF ELECTRIC MOTORS SUBJECT TO EFFICIENCY STANDARDS ON OCTOBER 24, 1997 The Energy Policy Act of 1992 (EPAct) covering efficiency levels of general purpose industrial

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2 BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002

More information

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Special Specification 6058 Battery Back-Up System for Signal Cabinets Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power

More information

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents. PART 1: GENERAL 1.01 This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the

More information

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026 TECHNICAL PERTICULAR FOR 1.6 MVA 6.6/0.433 KV SERVICE TRANSFORMER 1.00.00 GENERAL 1.01.00 Service SERVICE 1.02.00 Make ASHOK/VOLTAMP/DANKE/CGL 1.03.00 Type CORE 1.04.00 Location OUTDOOR 1.05.00 Specification

More information

Contents. Identification

Contents. Identification Contents Identification Type key Product data Introduction Applications Features and benefits Performance range pole pole Construction Sectional drawing Construction features Test pressure Operating conditions

More information

Evaluation of Visibility From Powered Industrial Trucks

Evaluation of Visibility From Powered Industrial Trucks ANSI/ITSDF B56.11.6-2005 (Reaffirmation of ASME B56.11.6 1992) Evaluation of Visibility From Powered Industrial Trucks AN AMERICAN NATIONAL STANDARD INDUSTRIAL TRUCK STANDARDS DEVELOPMENT FOUNDATION A

More information

TRU100 MODEL 937 TEMPERATURE REFERENCE UNIT HANDBOOK

TRU100 MODEL 937 TEMPERATURE REFERENCE UNIT HANDBOOK TRU100 TEMPERATURE REFERENCE UNIT HANDBOOK Isotech North America 158 Brentwood Drive, Unit 4 Colchester, VT 05446 Phone: (802)-863-8050 Fax: (802)-863-8125 www.isotechna.com sales@isotechna.com The company

More information

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators: (1) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

More information

INTER PLANT STANDARD STEEL INDUSTRY. CODE OF PRACTICE FOR REPAIR OF SQUIRRELCAGE HT MOTORS (6.6 kv) (First Revision) Corresponding IS does not exist

INTER PLANT STANDARD STEEL INDUSTRY. CODE OF PRACTICE FOR REPAIR OF SQUIRRELCAGE HT MOTORS (6.6 kv) (First Revision) Corresponding IS does not exist INTER PLANT STANDARD STEEL INDUSTRY IPSS CODE OF PRACTICE FOR REPAIR OF SQUIRRELCAGE HT MOTORS (6.6 kv) (First Revision) Corresponding IS does not exist IPSS:1-03-023-07 Formerly : IPSS:1-03-023-95 0.

More information

SINGLE PHASE TEFC CAGE MOTORS

SINGLE PHASE TEFC CAGE MOTORS SINGLE PHASE TEFC CAGE MOTORS 2 SINGLE PHASE TEF CAGE MOTORS Mechanical protection: IP 54 Voltage: 220 V, 50 Hz Type Output power P N kw Rated speed n N min -1 Efficiency % Power factor cos Rated current

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:-

MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- MGVCL//11KV D.O.FUSE/SPECIFICATIONS -:11KV DROP OUT FUSE CUTOUTS:- 01) SCOPE: This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in 50Hz, 11KV distribution

More information

Product specifications

Product specifications Product specifications 217.2.22 Product : Basic Remote control Sensor 39UA 312UA 315UA 49UA 412UA 415UA 39GA 312GA 315GA 49GA 412GA 415GA 39DA 312DA 315DA 49DA 412DA 415DA PESHK Approval Check Charge PESESGD-BJ

More information

The comparative testing was conducted. Electric Pedestal Fans. Turn on the Breeze

The comparative testing was conducted. Electric Pedestal Fans. Turn on the Breeze Electric Pedestal Fans Turn on the Breeze Standing in a corner literally so doing its job of cooling you (and edgy tempers, if any). And to think that once upon a time (about a hundred years ago) these

More information

USER MANUAL MPS 1-5KW SERIES

USER MANUAL MPS 1-5KW SERIES USER MANUAL MPS 1-5KW SERIES Low Series Frequency Solar and Wind Power Charging Inverter CONTENTS 1 WWW.NEXTGENNRG.COM 1. Introduction... 3 2. Profile Structure 4 2.1. Working Principle 4 2.2.Product Features..5

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

ROBUST LED DRIVERS. EasyLine Industry. EasyLine INDUSTRY , , , , , , ,

ROBUST LED DRIVERS. EasyLine Industry. EasyLine INDUSTRY , , , , , , , ROBUST LED DRIVERS EasyLine INDUSTRY 186452, 186453, 186454, 186455, 186456, 186477, 186510, 186617 Typical Applications Built-in in compact luminaires for Industrial lighting EasyLine Industry ENCAPSULATED

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS

Reg No: 1999/027771/07 ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION PROTECTED APPARATUS Government Approved Test Laboratory (Previously AIA) Reg No: 1999/027771/07 Equipment: Manufacturer: Type: ACCREDITED AND APPROVED TEST LABORATORY IN TERMS OF ARP 0108: REGULATORY REQUIREMENTS FOR EXPLOSION

More information

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007)

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007) Installation, Operation and Maintenance Manual (from February 2007) Publication 2698C (GB) 0207 1A 3319 8035B Donaldson reserve the right to alter design without notice. Freedom from patent restrictions

More information

AXA DALI P20. DALI Broadcast Controller. Installation Manual

AXA DALI P20. DALI Broadcast Controller. Installation Manual AXA DALI P20 DALI Broadcast Controller Installation Manual THE DALI P20 MUST BE INSTALLED BY A LICENSED ELECTRICIAN IMPORTANT INFORMATION ELECTRICIANS MUST READ PRIOR TO INSTALLATION 1) This product must

More information

Three Phase Modifiable NEMA Horizontal Motors Accessories and Modifications

Three Phase Modifiable NEMA Horizontal Motors Accessories and Modifications 1. Altitude Standard motors are designed for 3,300 feet altitude and 40 C ambient temperature. Atmospheric conditions at higher altitudes inhibit the motor s ability to dissipate heat, resulting in an

More information

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES : 1. SCOPE : This specification covers design, manufacturing, testing at manufacturer s works, inspection, packing & delivery of 11 KV Air Break

More information

INSTRUCTIONS FOR USE. Operation and Maintenance manual. Light Industrial Compressor. Hi-Tech Diagnostics Service

INSTRUCTIONS FOR USE. Operation and Maintenance manual. Light Industrial Compressor.   Hi-Tech Diagnostics Service Light Industrial Compressor INSTRUCTIONS FOR USE Operation and Maintenance manual WARNING: Do not plug into the electrical mains power supply before reading this manual. www.velopex.com Hi-Tech Diagnostics

More information

Dimensions WxHxD [mm] Weight [kg]

Dimensions WxHxD [mm] Weight [kg] SPECIFICATIONS The SOLSTART electronic soft starter incorporates two sets of thyristors (Two phase control) to start a threephase squirrel cage induction motor and an internal bypass. By supplying a slowly

More information

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist INTER PLANT STANDARD STEEL INDUSTRY IPSS SAFETY STANDARD FOR EQUIPMENT AND MACHINERY GUARDING IN STEEL INDUSTRY Corresponding IS does not exist IPSS:1-11-025-16 0. FOREWORD 0.1 This Inter Plant standard,

More information