1 Welcome Welcome to Yaskawa Electric America s Training Café Express Today s Topic is Selecting E7/P7/F7 Drives for Single-Phase Input Applications To make this Café enjoyable for all, please follow these tips on web class etiquette. Please do not put us on hold. Others will hear the hold music. Do not use a speaker phone. Background noise can be heard. Don t be shy, we welcome comments and questions. (Press *6 to mute and unmute your phone) Questions not answered during the Café can be ed to training@yaskawa.com or can be entered into the survey sent to you at the end of the class.
2 Single-Phase to Three-Phase Conversion Why the need for single-phase to three-phase power conversion? Areas not originally designated for industrial manufacturing with only single-phase power subject to increased demand to support small manufacturing operations Small start-up companies Custom manufacturing (specialty) operations Residential/ Commercial expansion needing increased water demands Remote pumps (submersible/booster) Increased pump HP (moving water further distances) Increased activity in energy sector Oil/Natural gas wells De-watering pumps Need three-phase power to support increased demand!
3 Single-Phase to Three-Phase Conversion Methods of converting single-phase to threephase power: Phase Converters Rotary Phase Converters (RPC) Static Phase Converters (SPC) Motor-Generator (M-G) Sets Variable Frequency Drives (VFDs) Single-Phase input models Three-Phase input models (with appropriate derating)
4 Single-Phase to Three-Phase Conversion Methods of converting single-phase to three-phase power: Phase Converters Rotary Phase Converters (RPC) Use idler motor to generate third phase Static Phase Converters (SPC) Use inductors/capacitors to generate third phase Unbalanced phase impedance Difficult to balance phase voltages especially with varying load Requires de-rating applied motor (by as much as 50%)!
5 Single-Phase to Three-Phase Conversion Methods of converting single-phase to three-phase power: Motor-Generator (M-G) Sets Uses multiple sets of windings on single rotor to generate three individual new phases Good voltage balance suitable for three-phase motors Easily convert voltage level and frequency from incoming supply Commutators require high maintenance Expensive and bulky
6 Single-Phase to Three-Phase Conversion Methods of converting single-phase to three-phase power: Variable Frequency Drives (VFDs) Single-phase input models Three-phase input models (with appropriate derate) Provide balanced three-phase voltage Can easily vary the voltage and frequency No tuning of capacitors to varying loads Soft start feature, PI control, extensive flexibility/programmability Provides superior protective features (overload, under-voltage, etc.) Reliable/maintenance-free operation
7 Single-Phase Motors Single-Phase Motors: Readily available up to 5HP Available up to and above 15HP but much less common Expensive Long lead times Frequent maintenance Trend is to use three-phase motors (even below 5HP)!
8 Single-Phase Applications Common Single-Phase Applications: Submersible Well Pumps Irrigation Pumps Fountain Systems Pump Jacks (oil/natural gas well pumps) Machining Centers/Lathes Vacuums/Blowers
9 Single-Phase Input Products Yaskawa Single-Phase Product Offering: VS-Mini (GPD205) 115Vac, 1/8 HP to 1 HP, 0.8 Arms to 5 Arms J7 (GPD305) Available through March Vac, 1/8 HP to 2 HP, 0.8 Arms to 8 Arms V7 (GPD315) Obsolete (subject to inventory on-hand) 230Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms V Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms J1000 (use caution output phase loss cannot be disabled) 230Vac, 1/8 HP to 3 HP, 0.8 Arms to 9.6 Arms (ND)
10 Single-Phase Input Products Yaskawa Single-Phase Product Offering: VS-Mini (GPD205) 115Vac, 1/8 HP to 1 HP, 0.8 Arms to 5 Arms J7 (GPD305) Available through March Vac, 1/8 HP to 2 HP, 0.8 Arms to 8 Arms V Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms J1000 (use caution output phase loss cannot be disabled) 230Vac, 1/8 HP to 3 HP, 0.8 Arms to 9.6 Arms (ND) Single-Phase models up to 5 HP only! All models run 230V three-phase motors!
11 Single-Phase Input Products What about single-phase applications at 480V or applications larger than 5 HP? Use E7/P7/F7 and three-phase motor with appropriate derating as outlined in application note AN.AFD.15 Applying E7/P7/F7 Drives To Single-Phase Input Applications What does document AN.AFD.15 contain? Let s take a look!
12 Single-Phase Input Power Application Specifications Important Considerations When Using a Three-Phase Drive with Single-Phase Input Drive Specifications (w/ derating) Drive HP Output Current Input Current DC Link Choke Selection Input Voltage Specifications Different than three-phase Output Voltage Limitation Effect on motor power Overload Rating Limited to low speeds Wiring & Branch Circuit Recommendations DC Link Choke Dimensions
13 Single-Phase Input Drive Derating Why is Drive derating required? Three-phase VFD designed to accommodate 300/360Hz DC bus ripple (3-phase full wave rectification at 50/60Hz)
14 Single-Phase Input Drive Derating Why is Drive derating required? Single-phase 60Hz input results in 120Hz DC bus ripple! DC bus capacitors need to provide more power DC bus level will decrease a larger amount than with threephase input during this time
15 Single-Phase Input Drive Derating Why is Drive derating required? Duration between bus peaks is longer in single-phase case Dc bus circuit will have to supply power for longer period More stress on input and DC bus components t3 Time t1 > t3 Tt1
16 Single-Phase Input Drive Derating Why is Drive derating required? Drive components subject to greater stress with single-phase input DC bus circuit (capacitors, DC link choke, bus bars) Increased ripple voltage and current Capacitors need to deliver more of the power to the load Input diode rectifier Increased input current Input terminals» Higher harmonic content» Using only 2/3rds of the rectifier Increased input current» Higher harmonic content» Using only 2 of 3 input terminals
17 Single-Phase Input Drive Derating Therefore, derating of Drive HP and output amperage will be required so that the Drive components operate within their ratings! Table 1 contains single-phase ratings for 240V and 480V models
18 Selecting the Proper Drive Select Drive that meets or exceeds both motor HP and motor FLA requirements When making selection be sure to take into account operation using the service factor of the motor if required by the application Drive must be selected to accommodate motor S.F. amps and motor S.F. horsepower if applicable!
19 Selecting the Proper Drive Select Drive that meets or exceeds both motor HP and motor FLA requirements. Include Service Factor if required. Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 20Arms Case 2) SF is required: 23Arms Note: 8.6HP = 7.5HP x 23A/20A Select Drive according to load requirement!
20 Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: No SF required: 20Arms SF is required: 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2011: No SF Required
21 Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 20Arms Case 2) SF is required: 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2011: No SF Required
22 Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 20Arms Case 2) SF is required: 23Arms Note: 8.6HP = 7.5HP x 23A/20A Mo del 2015: SF is required
23 Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 20Arms Case 2) SF is required: 23Arms Note: 8.6HP = 7.5HP x 23A/20A Mo del 2015: SF is required
24 Selecting the Proper Drive Select Drive that meets or exceeds both motor HP and motor FLA requirements Drive must be selected to accommodate motor S.F. amps and motor S.F. horsepower if applicable!
25 DC Link Choke Benefits Using a DC Link Choke allows us to pull more power from the VFD Reduces DC bus ripple Lowers input harmonics (from over 100% to 90% ITHD) Improves input power factor (to approx. 0.7 PF) reduces input current Therefore, DC Link Chokes DC Link Chokes are listed in Table 1 must always be Link Chokes selected to optimize performance for used! single-phase use Note: Models 18kW and smaller use a different link choke than what is normally used with three-phase input Select DC link choke according to Table 1 Caution - DC link chokes are open style (no enclosure)
26 DC Link Choke Benefits
27 Input Voltage and Frequency Input Supply Specifications: Standard VFD specifications with three-phase input: /480Vac, +10/-15% 50/60Hz, +/-5% VFD Specifications with single-phase input: 240/480Vac, +10/-5% 60Hz, +/-5% Thus, strict input voltage tolerance of +10 to -5% and 60Hz applies with single-phase use! Note: Wire input using terminals L1(R) and L2(S) to accommodate units that incorporate AC fans and soft-charge circuits (larger models)
28 Input Voltage and Frequency Why the stricter input voltage tolerance? Average bus voltage is lower with single-phase input than with equivalent three-phase input Therefore, output motor voltage will be reduced Motor power will be reduced with lower motor voltage Output voltage of 207V with input voltage of 228V (240V 5%) Output voltage of 414V with input voltage of 456V (480V 5%) Consider using a 208V or 400V motor if rated power must be developed at base speed to eliminate the effect of voltage deprivation! 208V and 400V motor selections are included in Table 1 Note: Additional impedance at the input of the Drive will cause additional voltage drop!
29 Reduced Voltage Motors
30 Input Voltage and Frequency Input Supply Specifications: Standard VFD specifications with three-phase input: /480Vac, +10/-15% 50/60Hz, +/-5% VFD Specifications with single-phase input: 240/480Vac, +10/-5% 60Hz, +/-5% Thus, strict input voltage of 240V(480Vac) +10 to -5% at 60Hz applies with single-phase use! Note: Wire input using terminals L1(R) and L2(S) to accommodate units that incorporate AC fans and soft-charge circuits
31 Single-Phase Input Current Drive input current will be approximately twice the motor current Single-phase to three-phase conversion accounts for majority of input current increase (factor 3) Overall input Power Factor of 0.7 can be expected Input current is included in Table 1
32 Overload Capacity Overload capacity with single-phase input is limited to 120% of Drive single-phase current rating Increased DC bus ripple means the DC bus level will drop to lower level As output power increases (high torque and high speed) average bus voltage decreases Motor voltage further decreases as load increases Therefore, expect 120% overload maximum for starting purposes only! Consult factory with cyclic applications (repeating overload) or when overload in excess of 120% is required
33 E7/P7/F7 Drives with Single-Phase Input Document AN.AFD.15 also includes wiring and branch circuit recommendations Table 2 contains: Wire gauge recommendations Fuse recommendations Circuit Breaker recommendations
34 DC Link Choke Details Table 3 contains DC Link Choke dimensions DC Link Chokes are open type (no enclosure) DC Link Chokes in Table 3 are different from chokes used for threephase input Wire DC Link Chokes to terminals +1 and +2 (remove factory supplied shorting bar)
35 Single-Phase Input Specification Summary Summary: Input Specifications: Voltage: 240/480VAC +10% / -5%, Frequency: 60Hz +/-5% Drive Ratings must meet or exceed both motor HP and FLA Be sure to include Service Factor operation if required DC Link Chokes are required on models 18kW and smaller Consult factory if Link Chokes cannot be used Maximum Overload of 120% for starting purposes only Expect motor voltage of approx. 207Vac (414Vac) with input voltage of 228Vac (456Vac) Consider a reduced voltage motor (208/400V) if full HP is required with low input voltage Specifications not mentioned in this document remain the same as standard three-phase product
36 Input Phase Loss (PF) Faults Final Comments: When using the Drive with single-phase input the Drive s input phase loss protection must remain enabled If Input Phase Loss (PF) faults are encountered, be sure to check the load current and horsepower along with incoming line voltage levels to insure all are within Drive specification Input Phase Loss faults generally indicate the Drive is undersized for the connected load Disabling input phase loss protection will result in permanent Drive damage and void the warranty Reducing Drive output frequency will reduce HP requirement Limiting the maximum frequency may allow an undersized drive to operate the load (Power = Torque x Speed)
37 Input Phase Loss (PF) Faults Final Comments: Consult factory when using other Yaskawa products with single-phase Other products have not been officially evaluated for singlephase use
38 That s A Wrap! Thank you for attending the Yaskawa Electric America Training Café. Please see the Café Schedule in the partner login section of Yaskawa.com for future classes. Training Café classes are held approximately once per month. Please complete the survey sent to you at the end of the class to help us improve the quality and relevance of the Training Café.
Steve Schouten. Donna Densmore
March 12, 2013 2 Steve Schouten Donna Densmore 3 Mike Carter Justin Kale 4 Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality Issues Source: Emerson Industrial Automation
More informationYaskawa Electric America Training Café
The Cost of Stopping Yaskawa Electric America Training Café Today s topic is The Cost of Stopping Presenter is Joe Pottebaum Senior Applications Engineer To make this Café enjoyable for all, please follow
More informationBenefits of VFD for single to three phase conversion
Benefits of VFD for single to three phase conversion Agenda Differences between three phase and single phase power & effects on devices they power What is a VFD and how does it work when used for phase
More informationVariable Frequency Drives
We Make Energy Engaging Variable Frequency Drives Questline Academy Meet Your Panelist Mike Carter questline.com 2 Contents Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality
More informationCommon Bus and Line Regeneration
Common Bus and Line Regeneration Addressing VFD applications when Regenerative Energy is Present Steve Petersen, Drives Technical Training Yaskawa America, Inc. Variable frequency drives (VFDs) are implemented
More informationVariable Frequency Drive Basics
Variable Frequency Drive Basics Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Variable Frequency Drives are
More informationApplication Description
-14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....
More informationREFERENCE MANUAL FORM: MX-TRM-E REL REV MTE
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation
More informationSDC,Inc. SCR-Regenerative Ac Drive
SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency
More informationMatrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages
More informationVFD Best Practices: Getting the Most from Your VFD Investment
TECH TOPICS VFD Best Practices: Getting the Most from Your VFD Investment The purpose of this document is to outline best practices for successful application and installation of VFDs. Following these
More informationLift Station Design Standards and Details. Summary of Revisions
Lift Station Design Standards and Details Summary of Revisions April 2017 Updates Standard Detail SLS 19 SUBMERSIBLE LIFT STATION GROUDING PLAN & S Removed Barbed Wire from FENCE GROUNDING. TYPICAL LIFT
More informationPOWER Wave XR Clean Sophisticated Reliable
POWER Wave XR Clean Sophisticated Reliable Through many hundreds of hours of research and design optimization, TEMCo is proud to offer POWER Wave XR ; a new breed of Phase Conversion technology. Based
More informationPetrochemical processing Ship Yards Oil Fields Irrigation
TITAN is your solution When you have demanding three phase power requirements and when need a phase conversion system that is up to the challenge you need the TITAN. Whether you re powering a single Machine
More informationMODEL 235P INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 08/2009 II_235P_B1
INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 08/2009 MODEL 235P II_235P_B1 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605) 348-5685 BE SURE
More information400/230 Volt 60Hz UPS Power
olt 60Hz Power Using ual Voltage standby generation and in one Nothing protects quite like Piller www.piller.com Contents 1 Abstract...3 2 Introduction...4 3 Alternative Power istribution...6 4 Integrating
More informationVariable Speed Drives Controlling Centrifugal Pumps Energy Savings
2018 Clean and Safe Drinking Water Workshop Hotel Gander Variable Speed Drives Controlling Centrifugal Pumps Energy Savings Presenter: Dave Galbraith What is a Variable Speed (Frequency) Drive? AKA VFD,
More informationSECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
More informationASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.
ASHRAE - Variable Speed Drives By Dan Watkins, LEED BD+C Bornquist, Inc. Adjustable Frequency Drive Fundamentals How does a VFD actually work VS Pumping Analysis VS Pumping Features Harmonics VFDs and
More informationVariable Speed Pumping
Variable Speed Pumping Jim Vukich Application Engineer ITT Corp. Malvern, PA Why Do It? Why Do It? Flow-Matching Minimize Starting & Stopping Flexibility Different Discharge Points, Flows Changing Conditions
More informationElectric Motor Controls BOMA Pre-Quiz
Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationTLE Series UPS 400/500 kw With eboost Technology
TLE Series UPS 400/500 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical power
More informationELECTRICAL POWER and POWER ELECTRONICS
Introduction to ELECTRICAL POWER and POWER ELECTRONICS MUKUND R PATEL (cj* CRC Press Taylor & Francis Group Boca Raton London New York CRC Press is an imprint of the Taylor & Francis Croup, an informa
More informationTLE Series UPS 160/200/225/250 kw with eboost Technology
TLE Series UPS 160/200/225/250 kw with eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical
More informationM T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation
M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter
More informationA Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications
A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications The Reliance Electric LiquiFlo AC drive combines high-performance variable speed drive technology with a patented liquid-cooling
More informationU1000 INDUSTRIAL MATRIX DRIVE
AC DRIVES U1000 INDUSTRIAL MATRIX DRIVE APPLICATIONS 200V CLASS: 10-100 HP (ND); 7.5-75 HP (HD) 400V CLASS: 7.5-800 HP (ND); 5-750 HP (HD) U1000 INDUSTRIAL MATRIX DRIVE THE GREEN CHOICE Ultra-low Harmonics
More informationM T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation
M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter
More informationCITY OF WEST PALM BEACH
REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - WET WELL SECTION VIEW SLS-2 WETWELL DATA PUMP/ELECTRICAL DATA REVISION: OCT. 2018 SUBMERSIBLE LIFT STATION - REQUIRED DATA SLS-3 PUMP TEST / START-UP FORM
More informationSED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options
SED2 Variable Frequency Drive Electronic Bypass (E-Bypass) Options Product Description The SED2 Electronic Bypass (E-Bypass) Options are companion packages for the family of SED2 Variable Frequency Drives
More informationCENTAURI ENERGY SERVER TECHNICAL DATA kw POWER
Chassis Inverter power Rated input Rated output Battery pack Safeties Environment Others Input Voltage Lower Limit Input Voltage Upper Limit Power Input Current Output Voltage Output accuracy Transient
More informationMODEL 233P/111P/233P-1.5
II-111-233-15P-B INSTALLATION INSTRUCTIONS Revision C Rapid City, SD, USA, 07/2015 MODEL 233P/111P/233P-1.5 BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.
More informationDRIVE THE WATER CYCLE. January 10 TH 2013
DRIVE THE WATER CYCLE January 10 TH 2013 DRIVE THE WATER CYCLE EXTENDED FLOW CONTROLS Throttling control Bypass control Parallel Pump control VSD control THROTTLING CONTROL The operation point is modified
More information"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Carol Lewellen-NEEC and BOC Tuesday, May 8, Sessions Session
"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Carol Lewellen-EEC and BOC Tuesday, May 8, 2018 3 Sessions Session 1-8:30-9:25 a.m. Motors 101 Session 2-9:30-10:25 a.m. - Power Session
More information596 Rectifier Retrofit
PRODUCT OVERVIEW 596 Rectifier Retrofit Overview GE Energy has offered the 596 family of rectifiers from the early 1990s. 596 rectifiers can be found in the GPS4812, 2424, PXS Shelves, and OCS Cabinet
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationPump ED 101. Power Factor (Part 2) - - Electricity Behaving Better
Pump ED 101 Power Factor (Part 2) - - Electricity Behaving Better Joe Evans, Ph.D http://www.pumped101.com Last month we took a close look at the flow of voltage and current in purely resistive and inductive
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More informationRVS-AX Instruction Manual
RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationSOLSTART Instruction Manual
Solstart Analog Soft Starter 8-58A, 220-600V Instruction Manual Ver. 23/03/2009 2 Table of Content SOLSTART Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3
More informationPowerWave 33 Efficient power protection for today s IT and process-related work environments
ARTICLE OR CHAPTER TITLE PowerWave 33 Efficient power protection for today s IT and process-related work environments Cooling fan UPS control panel Maintenance bypass isolator Input supply isolator Slot
More informationProduct Description. Application Description
-2 Solid-State Controllers Type TL, Torque Limiter August 6 Contents Description Page Torque Limiters............ -2 Soft Start Controllers........ -4 Soft Start Controllers with Auxiliary Contact.....
More informationSelection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran
4 Project:_ Engineer:_ Mitsubishi Electric Automation, Inc. (MEAU) Variable Frequency Drives - HVAC System Submittal Summary Data Form NEMA 1 Bypass Systems Architect:_ Contractor:_ Submitted by: Date:
More informationFUSES. Safety through quality
Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced
More informationAttachment A: Liquefied Natural Gas Pump Specifications
Attachment A: Liquefied Natural Gas Pump Specifications Vendor shall provide PGW with a new cryogenic submersible pump. The pump shall be tank mounted and removable. The pump shall be cooled and lubricated
More informationWelcome. Power Survey International
Welcome Company profile Established in 1948 Exclusively manufacture capacitor banks and harmonic filters Manufacturer of low and medium voltage products: Power Factor correction system Harmonic Filter
More informationTHE DLS SERIES BATTERY CHARGING POWER CONVERSION
THE DLS SERIES IOTA s DLS Series Battery Chargers and Power Converters provide reliable AC/DC power conversion for a variety of application needs. With a record of proven performance throughout several
More informationPower Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com
Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationDelta Products VFD CP2000 Bypass Control Packages.
Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products
More informationMotor Basics AGSM 325 Motors vs Engines
Motor Basics AGSM 325 Motors vs Engines Motors convert electrical energy to mechanical energy. Engines convert chemical energy to mechanical energy. 1 Motors Advantages Low Initial Cost - $/Hp Simple &
More informationUL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD
UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you
More information4100C BOSS AC Shovel Drive System Overview. WMEA Edmonton - June 2008
4100C BOSS AC Shovel Drive System Overview WMEA Edmonton - June 2008 Overview Drives Partnership with ABB Deck Plan / One-Line Schematic ISU (IGBT Supply Unit) Shovel Motion Inverters Cabling / Grounding
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationHVW701 HVAC Drive with By-Pass
s Automation Energy Transmission & Distribution Coatings HVW701 HVAC with By-Pass Designed Especially for HVAC Systems US.HVW701.By-Pass.07/2017 www.weg.net WEG HVAC-R Products WEG, a leading supplier
More informationApplication Note: SyMAX Permanent Magnet Motor Simple Startup Procedure
Application Note: SyMAX Permanent Magnet Motor Simple Startup Procedure Variable Frequency Drives Optimize Performance and Further Improve Efficiency by using Permanent Magnet Motor Control. AN.SYMAX.01,
More informationLED Drivers A Practical Understanding for Lighting Applications. Dr. Adan Hernandez, Philips-Advance Al Marble, Philips-Advance
LED Drivers A Practical Understanding for Lighting Applications Dr. Adan Hernandez, Philips-Advance Al Marble, Philips-Advance Outline What is a driver? Design types Constant current vs. constant voltage
More informationTLE Series UPS 750/1000 kw With eboost Technology
TLE Series UPS 750/1000 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical
More informationEnergy Independence & Securities Act Frequently Asked Questions
What does EISA stand for? Energy Independence & Securities Act Frequently Asked Questions EISA is the acronym for the Energy Independence & Securities Act. This law was signed on Dec. 19, 2007. This law
More informationSoftstarters. Softstarters Type SSM Medium voltage ,800V 1
Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum
More informationRLW. Reactors. mtecorp.com. Smaller, lighter protection. Power quality. Solved.
mtecorp.com RLW Reactors State-of the-art solution for absorbing everyday power line disturbances Smaller, lighter protection. Proven performance in the field Reliable and economical Compact and lightweight
More informationHigh Speed Fuse Applications Module 5
High Speed Fuse Applications Module 5 Power Semiconductors GTO SSR Semiconductors: High speed electronic switches used to manipulate electrical power Diode Thyristor IGBT Module 5 - page 2 2 Application
More informationTechnical Data Sheets
GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01
More informationELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M
ELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M ELECTRIC MOTOR MANAGEMENT Why bother? Electric motor basics Electricity and electric motors Energy efficient electric motors Electric
More informationLiebert Hipulse E The High-ECO-Availability UPS. AC Power Systems
Liebert Hipulse E The High-ECO-Availability UPS AC Power Systems We re Emerson Network Power, backed by Emerson, a global company that brings technology and engineering together to provide innovative solutions
More informationPresentation Soft starters 0 Altistart 48 soft start - soft stop units
Presentation Soft starters 5 6 7 65_Ver.-EN.fm/ Presentation (continued) Soft starters Applications The Altistart 8 soft start - soft stop unit is a controller with 6 thyristors which is used for the torque-controlled
More information"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Tuesday, May 8, Sessions Session 1-8:30-9:25 a.m. Motors 101 Session
"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Tuesday, May 8, 2018 3 Sessions Session 1-8:30-9:25 a.m. Motors 101 Session 2-9:30-10:25 a.m. Power and Motors Session 3-10:30-10:25
More informationIRT 4000 AT-S/M/L. Technical Manual. quality IN MOTION. quality IN MOTION
IRT quality IN MOTION www.irtsa.com 4000 AT-S/M/L Technical Manual IRT quality IN MOTION E2 0 8 4 1 5 September 2013-Rev. 5 UL Requirements Drives Series 2000 / 4000 AT 1. Field wiring terminal to use
More informationM T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation
M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components
More informationBRCP6SM ITT. CentriPro. 6-10" Submersible Motors. For 6" and Larger Deep Well Pumps. Engineered for life
ITT BRCP6SM CentriPro 6-10" Submersible s For 6" and Larger Deep Well Pumps Engineered for life Single Phase, 6" s (1.15 S.F.) and Required Control Boxes Diameter F.L. S.F. Control Box HP kw Volts Order
More informationMotor Starters. Reduced Voltage. Reduced Voltage Motor Starters Contents
June 5 Vol. 2, Ref. No. [067] -1 Reduced Voltage Motor Starters Contents Description Page Solid-State Controllers Type S701, Soft Start.......................................... -2 Type TL, Torque Limiter........................................
More informationNumber 1 in efficiency
PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter The
More informationFive Reasons for VFDs in HVAC Applications
Five Reasons for VFDs in HVAC Applications Save Money and Improve Performance with HVAC-Specific Drives by Larry Gardner, Yaskawa America, Inc., HVAC Drives Product Marketing Manager yaskawa.com Introduction
More informationEFFEKTA Power Supplies
EFFEKTA GENERAL INFORMATION UPS topology ON LINE - Double Conversion Classification VFI-SS-111 in accordance with IEC 62040-3 Nominal output power (Cos Ø 0,9) - kva 10 15 20 30 40 Nominal output power
More information5067 Mini BDFB / BDCBB
PRODUCT OVERVIEW 5067 Mini BDFB / BDCBB Up to 4 Loads, 600 Amps per Load Compact unit can be placed at the point of load High density models available with 48 circuits in 16RU Digital metering, extended
More informationWhen to use a Soft Starter or an AC Variable Frequency Drive
White Paper When to use a or an AC Variable Frequency Product lines: Smart Motor Controllers (SMCs), AC Variable Frequency s (VFDs) Topic Page Introduction 2 Starting Methods 3 How does a VFD work? 7 Comparisons
More informationJEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC. 5 Credit Hours. Prepared by: William Kaune. Revised Date: March 17, 2014
JEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC 5 Credit Hours Prepared by: William Kaune Revised Date: March 17, 2014 Dena McCaffrey, Ed.D., Dean, Career & Technical Education HRA101 Electricity
More informationIT 318 SUPPLEMENTARY MATERIAL CHAPTER 4
IT 318 SUPPLEMENTARY MATERIAL CHAPTER 4 Electric Motors V. 2013 BARRY M. LUNT Brigham Young University Table of Contents Chapter 4: Electric Motors... 2 Overview... 2 4-1 Commutation... 2 4-2 Stepper Motors...
More informationOptimizing Drive Systems for Energy Savings
Optimizing Drive Systems for Energy Savings Richard Messer Siemens AG, Industry Sector, Drive Technologies, Motion Control Systems Erlangen, Germany AIMCAL Web Handling Conference 2012 Prague, Czech Republic
More informationAC Drives Regenerative Energy Solutions. Product Summary
AC Drives Regenerative Energy Solutions Product Summary #% &TKXGU Regenerative Energy Solutions Snubber Resistor Braking Kits Line Regeneration Controls Synchronous Rectifier Controls AC Drives and Regenerative
More informationPower Supplies. 11/2 Introduction
Siemens AG 2009 Power Supplies 11 11/2 Introduction 4AV Non-Stabilized Power Supplies Filtered for Supply of Electronic Controls 11/4 General data 11/5 4AV2, 4AV4 power supplies, filtered, single-phase
More information3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,
Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,
More informationApplication Guide S-652 S-65T S-522 S-462 S-402 S-352 S-275CH S-693 S-682 S-410 S-675 AUTOSOUND S SERIES SPEAKERS
S-402 S-352 S-275CH S-652 S-65T S-522 S-462 S-693 S-682 S-410 S-675 AUTOSOUND S SERIES SPEAKERS Application Guide Please read through this manual to familiarize yourself with your new speakers. Should
More informationTRANSMISSION SYSTEMS
TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric
More informationTechnical data OT16E3 OT160E3 UL & CSA
Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58
More informationVoltPro VP4 Automatic Voltage Regulator
VoltPro VP4 Automatic Voltage Regulator The VoltPro VP4 Automatic Voltage Regulator is an affordable generator voltage regulator that is designed for the consumer market and can replace many popular voltage
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More information209 Series. Magnetic Circuit Protectors
29 Series Magnetic Circuit Protectors Introduction 249 Power Selector System Multi-Pole Configurations Operating Characteristics Delay Curves Specifications Decision Tables 73 75 77 79 8 82 85 87 29/29/229/249/279
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationApplication Note CTAN #127
Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy
More informationFeatures and Benefits
-52 August 2006 Contents Page Type MV801, Intelligent Technologies (IT.) Medium Voltage Soft Starters Operation.............. -53 Selection.............. -55 Product Selection........ -56 Options................
More informationINSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad
INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad - 500 043 MECHANICAL ENGINEERING ASSIGNMENT Name : Electrical and Electronics Engineering Code : A40203 Class : II B. Tech I Semester Branch :
More informationApplication manual Dry type power factor correction capacitors
Application manual Dry type power factor correction capacitors L O W V O L T A G E N E T W O R K Q U A L I T Y General Index General information... 6.2 6.3 Basic concepts What is power factor Why improve
More informationNorth America Phase Converters & Electrical Supply
North America Phase Converters & Electrical Supply OPERATION AND INSTALLATION MANUAL ROTARY PHASE CONVERTERS (Models PL, UL & CP) 240 VOLTS WARNING: To reduce the risk of injury, the user must read and
More informationTECH XP600/1100 INSTALLATION AND OPERATION MANUAL
TECH 7317 Jack Newell Blvd North Fort Worth, Texas 76118-71 8175954969 voice, 817595129 fax 88864683 toll free e-mail address info@exeltechcom e-mail address sales@exeltechcom website wwwexeltechcom Copyright
More information300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds
Digital Soft Start Controls 9 thru 900 Amps 208-460V 50/60 Hz. 9 thru 900 Amps 208-575V 50/60 Hz. Applications: Controlled ramp start and stop, minimize spillage in material handling, reduced water hammer
More information3/29/2012 ELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M WHY SO DIFFICULT? ELECTRIC MOTOR MANAGEMENT WHY BOTHER?
ELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M Why bother? Electric motor basics Electricity and electric motors Energy efficient electric motors Electric motor inventories and
More informationCT430 - Soft Starters on Motor Applications
CT430 - Soft Starters on Motor Applications Bill Bernhardt Sr. Commercial Engineer May 16, 2018 PUBLIC Copyright 2018 Rockwell Automation, Inc. All Rights Reserved. 1 Topics Traditional Motor Starting
More information