1 Welcome
2 Company profile Established in 1948 Exclusively manufacture capacitor banks and harmonic filters Manufacturer of low and medium voltage products: Power Factor correction system Harmonic Filter system Sales throughout United States, Canada, South America, etc.
3 Power Factor - Ratio of working power (kw) to apparent power (kva) - Measures how effectively electrical energy is being used PF = kw/kva kva kvar kw
4 Power Factor - Power factor = 100 / 142 = 70% 142kVA 100 kvar 100kW
5 Power Factor - Power factor = 100 / 105 = 95% - At 70% PF, it takes 35% more current to do the same useful work!! 105kVA 33 kvar 100kW
6 Power Factor & Buck of beer!!
7 Utilities - Many utilities will penalize their customer for power factor less than 0.90 or Utility has to provide transformers, power lines to provide the total kva - The penalty can disappear of the customer provides their own kvar - CAPACITORS
8 Capacitors - Capacitors are kvar generators - Reactive current is provided internally to the system as opposed to drawn from the utility - Eliminates the penalty on your power bill - Typical payback is 1 2 years for a 20-year product
9 Electrical network without capacitor Active Power (kw) Reactive Power (kvar) Apparent Power (kva) Utility Motor load
10 Electrical network with capacitor Active Power (kw) Reactive Power (kvar) Apparent Power (kva) Utility Motor load Power Cap
11 Why Install Capacitors? - Reduce electric utility bills - Increase system capacity - Improve voltage stability - Reduced losses through out system
12 Monthly Savings from utility bill
13 Solution to increase PF to 92% Propose an automatic capacitor bank: Type: PowerVar Required power: 589 kvar Suggested power: 600 kvar Number of steps: 6 Power per step: 100
14 Increased system capacity - 500kVA transformer operating at 480kVA. PF = Want to add a production line and increase load by 25% from 360kW to 450kW - Currently draws 480kVA at PF = 75% - Working power available is only 360kW due to poor PF - You could - Upsize transformer to 750kVA - Or improve PF and free up more capacity in the existing transformer
15 Before & After PF chart
16 Increased system capacity - Improving PF to 0.95 would free up kw on the transformer - To increase PF from 0.75 to 0.95, we go to multiplier table - 450kW x = 248.8kVAR - Install a 250kVAR capacitor bank at about $2600 material cost
17 Improved Voltage Conditions - Low voltage cause by excessive current draw results in lower efficiency from motors - As PF goes down - Line current increases - Dragging voltage further down - Adding capacitors to your system will improve motor performance and increase motor life
18 Capacitor selection as per motor size
19 Capacitor Location Now that you have decided that a capacitor would provide benefit, where to you put it? At the load - Cap sized for specific motor - Switches with the motor - Reduced line losses - Increased system capacity - Motors and caps can be relocated together - BUT higher installation and maintenance cost Good where you have a few large inductive loads
20 Capacitor Location At the feeder or substation - Lower cost per kvar - Improves total plant PF covers all motors and inductive loads - Automatic switching matches kvar required to kvar supplied Use where you have widely distributed inductive loads (i.e. small motors) Often some combination of fixed and variable is optimal
21 PowerCap Low Voltage Range kvar Network voltage 208v 600v Other voltage available Type Dry or wet Phase 1 or 3 phase Option Contactor (semi-automatic) External Fuse Blown Fuse Indicator NEMA 3R Enclosure
22 Power Cap Medium Voltage Capacity 25 kvar and up Network voltage Type 2400v 4160v Other voltage available Wet Phase 3 Phase Option Fuse
23 PowerVar Low Voltage Capacity kvar Network voltage Option 208v 600v Other voltages available NEMA 12 & 3R enclosure Main breaker Main disconnect Main fuse disconnect Blown fuse indicator Others
24 PowerVAR - Medium Voltage Capacity 100kVAr and up Network voltage 2400v 35,000v Other voltages available Option NEMA 12 & 3R enclosure Main breaker Main disconnect Main fuse disconnect Grounding switch Unbalance protection Others
25 Power Factor Controller Power Survey (Standard) PF indication and number of step Energization sequence - FIFO Manual and automatic selection Up to 14 steps Alarm if harmonic are overloaded Etc. Nokian (Optional) As per Power Survey and more: Up to 12 steps Indication of PF, current, THD Etc.
26 Installation of a PowerCap and/or PowerVar
27 Harmonics!! Capacitors do not cause harmonics, but they can aggravate existing conditions Harmonic producing equipment: Variable frequency drives DC Drive Welder UPS equipment AC & DC rectifier Welders
28 Harmonics!! Capacitors and transformers can create a dangerous resonant condition Harmonics can be amplified many multiples if they are at the resonant frequency Capacitors act as a low impedence drain for the harmonics and typically fail prematurely Rule of thumb is that if 20% or more of total load is non-linear, then harmonic filtering should be used.
29 Harmonics!! What to do? I require capacitors to improve my PF, but I do have potential or existing harmonic issues Can use harmonically hardened caps Capacitors can be harmonically filtered with iron core reactors Filter is tuned to provide capacitance at the primary frequency and inductance at higher harmonics Filtered units (especially automatic) can get very expensive
30 Harmonics!! What to do? If a known harmonic environment, a harmonic / demand analysis is best
31 Harmonics and a river! Ideal condition Clean water Electrical network without harmonic Line Pump Motor Capacitor
32 Harmonic and a river! Non-ideal condition Polluted water Polluted electrical network Filter in series Reactor in series Water pump Protection of the installation Capacitor
33 PowerCap Filter Low Voltage Capacity kvar Network voltage Option 208v 600v Other voltages available NEMA 12 & 3R enclosure Main breaker Main disconnect Main fuse disconnect Blown fuse indicator
34 PowerCap Filter Medium Voltage Capacity kvar Network voltage 2400v 4160v Other voltages available Type Oil Phase 3 Phase Option Contactor
35 PowerVar Filter Low Voltage Capacity kvar Network voltage 208v 600v Other voltages available Option NEMA 12 & 3R enclosure Main breaker Main disconnect Main fuse disconnect Blown fuse indicator
36 PowerVAR Filter Medium Voltage Capacity 100 kvar and up Front view Voltage 2400v 35,000v Other voltages available Option NEMA 12 & 3R enclosure Main breaker Main disconnect Main fuse disconnect Ground switch Unbalance protection Others Rear view
37 Industrial Loads Industrial customers Type Typical PF Printer 70% Plastic 70% Automobile 65% Saw mill 75% Pulp & Paper 70% Cement plant 70% Food & Process 80% Fisheries 80% Etc
38 Commercial Loads Commercial customers Type Typical PF Office tower 85% Shopping center 80% Grocery store 80% Arena 75% Pump station 75% Hospital 80% Etc
39 HOW DO I START? For basic power factor correction to reduce utility bills, gather Utility bills for prior 12 months PF charge is not always apparent. We can find it. One line of the system Understanding of potential harmonic issues Is non-linear load > 20% of total load? Gather all motor information for specific motor load PF improvement
40 MAINTENANCE Caps operate warm to the touch. If cool, investigate further Check fuses on regular basis Blown fuse indicating lights No moving parts on a capacitor
41 SUMMARY Capacitors can be useful for applications where poor power factor Is resulting in penalties from local utility Is stealing capacity from your system Is dragging down your voltage and stealing efficiency from your motors Is causing I2R losses throughout your system Be careful in harmonic environments to ensure long and happy life of your caps and electrical system
42 COME VISIT US If you would like to discuss further, come see Patrick Lyons at booth 216 TE / Power Survey booth THANK YOU!
ABB n.v Power Quality in LV installations
ABB n.v. - 1 - Power Quality in LV installations PQ problems in LV installations 750 500 250 Volts 0-250 -500 Amps -750 3000 2000 1000 0-1000 -2000-3000 10:25:43.72 10:25:43.73 10:25:43.74 10:25:43.75
More informationPower Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com
Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric
More informationPower Factor Correction
Power Factor Correction Power Factor Correction and Voltage Optimisation have been around since the turn of the 20 th century and although in many cases their individual benefits and attributes make them
More informationChapter 3.1: Electrical System
Part-I: Objective type Questions and Answers Chapter 3.1: Electrical System 1. The heat input required for generating one kilo watt-hour of electrical output is called as. a) Efficiency b) Heat Rate c)
More informationMYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.
MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC. CALMANUAL HOW TO APPLY CAPACITORS TO LOW VOLTAGE POWER SYSTEMS. SECTION INDEX SECTION I POWER FACTOR UNDERSTANDING POWER FACTOR...
More informationPower Factor and Harmonics Primer
Power Factor and Harmonics Primer www.stacoenergy.com Your tailored power solutions provider TM 1.866.261.1191 937.253.1191 sales@stacoenergy.com Your tailored power solutions provider Table of Contents
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationOne Solution for Ideal Power Quality
One Solution for Ideal Power Quality 1 P a g e www.poweronesolutions.com One Solution for Ideal Power Quality PowerOne s patented P1Advantage TM virtually eliminates harmonic distortion while simultaneously
More informationUltravar TM AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS
AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS Contents Benefits of Power Factor Improvement... 4 ACCU-VAR Plus - AVC (50 to 600 KVAR) Standard and Optional Features... 5 240, 480, 600 Volt Equipment...
More informationMedium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.
Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution
More informationPower System Solutions (PSS)
About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and
More informationPPHVC Power Quality Solutions. ABB PQC-STATCON Benefits and advantages
PPHVC Power Quality Solutions ABB PQC-STATCON Benefits and advantages Reasons for investing in power quality Poor power quality costs Sector Financial loss per incident Semi-conductors production(*) 3
More informationTechnical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction
Technical brochure The Vector series The ABB comprehensive solution for automatic power factor correction 2 Applications The Vector series The Vector series The Vector series is a powerful and compact
More informationApplication manual Dry type power factor correction capacitors
Application manual Dry type power factor correction capacitors L O W V O L T A G E N E T W O R K Q U A L I T Y General Index General information... 6.2 6.3 Basic concepts What is power factor Why improve
More informationPower factor correction: a guide for the plant engineer
Supersedes April 2008 Power factor correction: banks and passive harmonic filters Contents Description Page Description Page Part one: power factor What is power factor?.... 2 Should I be concerned about
More informationCLASS 5870 ReactiVar Power Factor Capacitors AT6000/AT7000 Transient Free Reactive Compensation
CLASS 5870 ReactiVar Power Factor Capacitors AT6000/AT7000 Transient Free Reactive Compensation ReactiVar Transient Free Reactive Compensation Systems are ideal for use on sensitive networks Transient
More informationMedium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks
Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Product Selection & Application Guide Product Description GE's Thyristor Switched Harmonic Filter Banks (TSC), are custom designed
More informationPQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads
PQC-STATCON PPHVC-Power Quality Solutions Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads Contents What is poor power quality? Reasons for investing
More informationPF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual
PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means,
More informationDESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)
DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN) -A.R. Subraaanian -R.A.A. Palani -J. Thomson A new 3.3 K.V. 4200 KVAR auto switching capacitor bank has been installed
More informationMetal-enclosed medium-voltage power factor correction system
Technical Data TD02607011E Supersedes June 2011 Metal-enclosed medium-voltage power factor correction system Contents Description Page Medium-voltage power factor correction... 1 Product description...
More informationPower Quality and Energy Management
Power Quality and Energy Management 1 2 Contents Power Quality...2 Power Factor Correction...4 Voltage Optimisation...8 Harmonic Filters and Reactors...12 1 Captech is Power Investigation and identification
More informationBeaver Power Factor Correction Capacitors
Beaver Power Factor Correction Capacitors Beaver Low Voltage Power Factor Correction Capacitors are designed for long life and are made with the highest quality materials. All units are assembled in Canada
More informationAPC03 capacitor bank series The ABB comprehensive solution for automatic power factor correction
APC03 capacitor bank series The ABB comprehensive solution for automatic power factor correction APC03 series provides the ideal power factor correction solution for industrial and commercial applications.
More informationPRESENTER PETER NJENGA CHIEF ENGINEER, CUSTOMER SERVICE, KENYA POWER EAST AFRICAN POWER INDUSTRY CONVENTION 2012
PRESENTER PETER NJENGA CHIEF ENGINEER, CUSTOMER SERVICE, KENYA POWER EAST AFRICAN POWER INDUSTRY CONVENTION 2012 Introduction Power reliability Power Quality Harmonics Distortion Poor power factor Circuit
More informationPOWER FACTOR IMPROVEMENT CONCEPT FOR LARGE MOTORS
POWER FACTOR IMPROVEMENT CONCEPT FOR LARGE MOTORS POWERFLOW TECHNOLOGIES Inc 4031 FAIRVIEW ST, Burlington,Ontario, CANADA, L7L-2A4 905-336 2686, www.powerflowtechnologies.com 1 POWER FACTOR REQUIREMENTS
More informationThree Phase Capacitors KNK
Three Phase Capacitors KNK Features Connection profile Φ 90 and 116 mm 2-16 mm 2, Φ 136 mm 2-25 mm 2 *Use of flexible conductors only with ferrules Capacitors equipped with discharge resistors Rated power
More informationPump ED 101. Power Factor (Part 2) - - Electricity Behaving Better
Pump ED 101 Power Factor (Part 2) - - Electricity Behaving Better Joe Evans, Ph.D http://www.pumped101.com Last month we took a close look at the flow of voltage and current in purely resistive and inductive
More informationMetal-enclosed medium voltage power factor correction system
Supersedes November 2008 Contents Description Page Medium voltage power factor correction... 1 Product description... 1 Application description.... 2 Benefits.... 2 Univar XV (5 kv class).... 3 Product
More informationsmartvar Dynamic VAR Compensator
smartvar Dynamic VAR Compensator DOES YOUR BUSINESS NEED TO SAVE MONEY? Discover a quick and easy way to identify cost saving opportunities. Improve the dynamic processes in your facility with smartvar.
More informationPower Factor Correction
Motors Automation Energy Transmission & Distribution Coatings USA3846PF 08/12 WEG www.weg.net Electric Improving Plant Life with Capacitors Reduce Utility Costs - improved Power Factor can reduce or eliminate
More informationIndex Low Voltage Network Quality. Low Voltage Network Quality
Index Low Voltage - Low Voltage General information...1 -.6 Description & capacitor construction...2,.3 Options for correcting power factor...4 Sizing capacitors at the motor load...5 Sizing capacitors
More informationLV Capacitor Bank APC
LV Capacitor Bank APC The ABB comprehensive solution for automatic power factor correction: APC standard, reinforced and de-tuned automatic capacitor banks The ABB comprehensive solution for automatic
More informationPower Quality Luis Vargas Research Engineer 9/18/2008
Page: 1 of 5 Luis Vargas Research Engineer 9/18/2008 Page: 2 of 5 As we make advances on green technology, we get a better understanding of the efficiencies and deficiencies on how we consume electricity.
More informationLV Capacitor Bank APC
LV Capacitor Bank APC The ABB comprehensive solution for automatic power factor correction: APC standard, reinforced and de-tuned automatic capacitor banks The ABB comprehensive solution for automatic
More informationTransforming Energy.. For Advanced Technology
Transforming Energy.. Manufacturers of CE approved Transformers & Reactors Five Decades of Manufacturing Experience Manufacturers of Quality Reliable Transformers. Auto C 201,4 th Cross Peenya Induatrial
More information1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN
APPLICATION The KNK capacitors are used for power - factor correction of inductive consumers (transformers, electric motors, rectifiers) in industrial networks for voltages of up to 660 V. DESIGN Cylindrical
More informationDynamic Reactive Power Control. By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West)
Dynamic Reactive Power Control By V. R. Kanetkar Full Time Consultant Technical Services at Veretiv Energy Private Limited Thane (West) Acknowledgement The author acknowledges with deep gratitude the experience
More informationIJRASET 2013: All Rights are Reserved
Power Factor Correction by Implementation of Reactive Power Compensation Methods of 220 KV Substation MPPTCL Narsinghpur Ria Banerjee 1, Prof. Ashish Kumar Couksey 2 1 Department of Energy Technology,
More informationPower Factor Correction
AE9-1249 R10 August 2008 Power Factor Correction Index Page 1. Introduction... 1 2. Electrical Fundamentals... 1 3. Electrical Formulas... 2 4. Apparent Power and Actual Power... 2 5. Effects of Poor Power
More informationTVA Distributor Retail Rates and Comprehensive Services Program Power Factor Case Studies. Gerald Johns, P.E. Power Utilization Engineer, TVA
TVA Distributor Retail Rates and Comprehensive Services Program Power Factor Case Studies Gerald Johns, P.E. Power Utilization Engineer, TVA 1 TVA Comprehensive Services Power Factor Studies/Recommendations
More informationkvah Billing - Frequently Asked Questions (FAQs)
kvah Billing - Frequently Asked Questions (FAQs) 1. What is kvah billing? a. Electrical Energy has two components viz. Active Energy (kwh) and Reactive Energy (kvarh). Vector sum of these two components
More informationProper Application of Power Factor Capacitors and How They Can Reduce Energy Costs Eaton Corporation. All rights reserved.
Proper Application of Power Factor Capacitors and How They Can Reduce Energy Costs 1 2008 Eaton Corporation. All rights reserved. Learning Objectives At the end of this web session, you will be able to:
More informationShunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian
Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission
More informationWorking Principle of Power Saver as per Manufacture:
Analysis the Truth behind Household Power Savers Introduction: A House hold power saving devices has recently received a lot of attention from both consumers and manufacturers. It is generally used in
More informationSynchronous motor control. 8/15/2007 Powerflow Technologies Inc 1
Synchronous motor control 8/15/2007 Powerflow Technologies Inc 1 PLC Lubrication units Cooling Water DCS PLC Dampers SUB BD Breaker Protection relay Field Application Kiln System Fan Hydraulic Unit Instrumentation
More informationEskisehir Light Train- Correcting Capacitive
Case Study-Estram Light Train Eskisehir Light Train- Correcting Capacitive Power Factor Eskisehir, a city in the Anatolia region of Turkey is located in an area inhabited since at least 3500 BCE- the copper
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear
More informationPower factor correction Harmonic filtering Dynamic flicker compensation
Power factor correction Harmonic filtering Dynamic flicker compensation Products & Systems.1 1SXU 000 023 C01 General information General description & capacitor construction Large terminals for easy cable
More informationAmerican Journal of Science, Engineering and Technology
American Journal of Science, Engineering and Technology 017; (4): 10-131 http://www.sciencepublishinggroup.com/j/ajset doi: 10.11648/j.ajset.017004.14 Application of Distribution System Automatic Capacitor
More informationIs Uncorrected Power Factor Costing You Money?
Is Uncorrected Power Factor Costing You Money? Are You Being Overcharged by Your Energy Provider? Find Out! Everyone s trying to lower their energy bill these days. If you re a business owner, facilities
More informationPower Quality Solutions POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS
Power Quality Solutions 2018 POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS ACTIVE Ematic FA40 New Series ICAR: products and solutions Founded in 1946, ICAR is a leading manufacturer of capacitors and
More informationWhite Paper Load Banks for Power System Testing
White Paper s for Power System Testing A load bank provides a consistent and repeatable electrical load that can be accurately controlled, measured and recorded. Load banks convert or dissipate the resultant
More informationARTECHE LOW VOLTAGE CAPACITOR BANKS. smartbat LV.
ARTECHE LOW VOLTAGE CAPACITOR BANKS. smartbat LV. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products described here. Moving together
More informationPQC - STATCON The ultra fast Power Quality Compensator
PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast power quality compensator PQC - STATCON is based on IGBT voltage source inverter technology. It is a shunt connected
More informationINSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT
INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT Prof. Chandrashekhar Sakode 1, Vicky R. Khode 2, Harshal R. Malokar 3, Sanket S. Hate 4, Vinay H. Nasre 5, Ashish
More informationWhite Paper. Application of Resistive/Reactive Load Banks for kva Testing
White Paper Application of Resistive/Reactive Load Banks for kva Testing Application of Resistive/Reactive Load Banks for kva Testing Resistive load banks are the most commonly used load banks for the
More informationUnrivalled in Power Factor Correction.
Unrivalled in Power Factor Correction. Static VAR Generators (SVG) What is Power Factor? Power Factor is a measure of how effectively incoming power is used in your electrical system and is defined as
More informationSynchronous motor with fluid coupling drive arrangement for a preheater ID Fan. presenter Nathan Schachter CIMENTEC Engineering Ltd
Synchronous motor with fluid coupling drive arrangement for a preheater ID Fan presenter Nathan Schachter SLC PLC Lubrication units Cooling Water DCS SUB BD Breaker SR469 GE STAT-XTOR PLC Field Application
More informationPower factor correction Don t pay the price for poor power quality
POWER QUALITY Power factor correction Don t pay the price for poor power quality Avoid new penalty charges under DCP161 SEE PAGE 3 Copyright 2017 ABB. All rights reserved. Specifications subject to change
More informationAutomatic COSYS PFC. Automatic power factor correction system NEW
Automatic COSYS PFC Automatic power factor correction system NEW cosys_178_a_1_x_cat cosys_178_a_1_x_cat appli_xxx_a  Function Your reactive energy consumption vary depending on the type and using conditions
More informationChapter 3.2: Electric Motors
Part I: Objective type questions and answers Chapter 3.2: Electric Motors 1. The synchronous speed of a motor with 6 poles and operating at 50 Hz frequency is. a) 1500 b) 1000 c) 3000 d) 750 2. The efficiency
More informationM T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation
M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter
More informationHV Compensation & Filtering Products
GE Grid Solutions HV Compensation & Filtering Products Providing Power Quality and Energy Efficiency High Voltage (HV) reactive power compensation and harmonic filtering solutions help customers to improve
More informationVolume 2 Charts, Formulas, and Other Useful Information
Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase
More informationLow Voltage Power Factor Corrections
Low Voltage Power Factor Corrections Capacitors Contents General information on Iskra Capacitors Type Page Introduction 4 1. Single-phase capacitor type KNK5015 230 550 V, 1,67.5 kvar 2. Three-phase capacitors
More informationApplication Notes Getting concrete: PFC at SIW Co., Thailand
Power Factor Correction Getting concrete: mediumvoltage PFC successfully replaced by low-voltage PFC at Siam Industrial Wire Co., Thailand Siam Industrial Wire is a member of NatSteel Holdings and a wholly
More informationSouthern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management
Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements
More informationSurabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality
Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100
More informationOne Solution for Ideal Power Quality
One Solution for Ideal Power Quality PowerOne s solution to poor power quality mitigates harmonics to less than 5% and simultaneously corrects power factor to over 99% www.poweronesolutions.com Complete
More informationChapter 08 Dynamic power factor correction systems (real time PFC) Dynamic power factor correction systems (real time PFC) Optimised, thermal design
Dynamic power factor correction systems (real time PFC) Optimised, thermal design Long service life De-tuned version Minimised grid distortion Dynamic power factor correction systems (real time PFC) Hardly
More informationTechnical News. Power Factor Correction. What technology is best for you? Specialists in electrical and automation products, systems and solutions
Issue #79 - Winter 2018 Technical News Specialists in electrical and automation products, systems and solutions Power Factor Correction What technology is best for you? Written by Samuel Hodgetts NHP nhp.com.au
More informationBASIC ELECTRICAL MEASUREMENTS By David Navone
BASIC ELECTRICAL MEASUREMENTS By David Navone Just about every component designed to operate in an automobile was designed to run on a nominal 12 volts. When this voltage, V, is applied across a resistance,
More informationSharda Electronics & Co. An ISO 9001:2015 Certified Company
Sharda Electronics & Co. An ISO 9001:2015 Certified Company Business Profile We have been witnessing to change all our life and change continues to happen all around us every moment. Change is happening
More informationCUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)
GENERATOR INTERCONNECTION APPLICATION Category 2 (Combined) For All Projects with Aggregate Generator Output of More Than 20 kw but Less Than or Equal to 150 kw Also Serves as Application for Category
More informationDO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO.
DO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO. By Patrick J. Lynch, P.Eng. PROBLEMS CAN BE GENERATED BY THE ACTUAL BUILDING LOCATION, OTHERS BY EQUIPMENT WITHIN THE BUILDING
More informationM T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation
M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter
More informationProduct Groups. Standard Features
Product Groups UCW series Single-phase capacitor UCWT series Three-phase capacitor unit up to MCW series Three-phase module with single-phase units BCWT series Bank of three phase capacitors with or without
More informationCTU 02. Thyristor switching module for fast PF compensation. User manual
CTU 02 Thyristor switching module for fast PF compensation User manual version 1.3 Czech Republic Czech Republic 1 Content 1. Function description... 3 2. Device description and indication features...
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationCONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS
LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low
More informationStatic Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray
Product LINE Guide Static Phase Converters Rotary Phase Converters Double-Throw Switches Fused Disconnect Double-Throw Switches Non-Fused Disconnect Switches Stray Voltage Isolation Power Factor Correction
More informationDYNACOMP. The top-class reactive power compensator
DYNACOMP The top-class reactive power compensator Dynacomp vs Electromechanical switching of capacitors Electromechanical switching of capacitors The Dynacomp : the top-class dynamic compensator Transients
More informationPower Quality Compensator - Reactive (PQCR) Enhancing power quality and energy efficiency of your electrical network
LOW VOLTAGE STEPLESS PRODUCTS Power Quality Compensator - Reactive (PQCR) Enhancing power quality and energy efficiency of your electrical network ABB Ltd. LV Capacitors and Power Quality Solutions Plot
More informationELG4125: Flexible AC Transmission Systems (FACTS)
ELG4125: Flexible AC Transmission Systems (FACTS) The philosophy of FACTS is to use power electronics for controlling power flow in a transmission network, thus allowing the transmission line to be loaded
More informationAutomatic capacitor banks and Automatic Power factor Correction Panels of inductive character loads in low voltage power networks.
SME APFC Panels Description: APFC Panel means Automatic Power Factor Correction Panel. In some cases, in industrial applications, the loading pattern of the entire network will change from time to time.
More informationENERGY EFFICIENT MOTORS AND POWER SAVING Dr. K. Brahmanandam E.E.E Department, M.V.S.R.E.C, Hyderabad, India
ENERGY EFFICIENT MOTORS AND POWER SAVING Dr. K. Brahmanandam E.E.E Department, M.V.S.R.E.C, Hyderabad, India Abstract In the Industries most of the motors are standard three phase induction motors. The
More informationSteve Schouten. Donna Densmore
March 12, 2013 2 Steve Schouten Donna Densmore 3 Mike Carter Justin Kale 4 Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality Issues Source: Emerson Industrial Automation
More informationG PULLAIAH COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
G PULLAIAH COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ENERGY AUDITING AND DEMAND SIDE MANAGEMENT (15A02706) UNIT-2 ENERGY EFFICIENT MOTORS AND POWER FACTOR IMPROVEMENT
More informationTargeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More informationOptimizing Drive Systems for Energy Savings
Optimizing Drive Systems for Energy Savings Richard Messer Siemens AG, Industry Sector, Drive Technologies, Motion Control Systems Erlangen, Germany AIMCAL Web Handling Conference 2012 Prague, Czech Republic
More informationHARMONIC FILTER REACTOR
380V 50Hz Series Resonance Frequency : 204Hz or p = 6% To be used with 415V capacitor only Design : According to VDE 0550/0532 & IEC 76 l 250 = 0.31 x l N Testing : Insulation strength tested at 2.5kV
More informationCHAPTER 3. Basic Considerations and Distribution System Layout
CHAPTER 3 Basic Considerations and Distribution System Layout Utility Load Classifications The electrical power distribution system is that portion of the electrical system that connects the individual
More informationEPRLAB FAQ v1.0 Page 1 / 8 Copyright EPRLAB December 2015
e EPRLAB FAQ v1.0 Page 1 / 8 e EPRLAB Electric Power Research Laboratory, EPRLAB is a high-tech power electronics company that has been specialized on design, manufacturing and implementation of industrial
More informationVariable Frequency Drives
We Make Energy Engaging Variable Frequency Drives Questline Academy Meet Your Panelist Mike Carter questline.com 2 Contents Basics Motor Loads Operation Advantages/ Disadvantages Sizing a VFD Power Quality
More informationUNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49
UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5
More informationCustomer Requirements Downtown Secondary Network Service
Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard
More informationPOWER FACTOR REBATE-BOLD DECISION FROM REGULATOR
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 153 POWER FACTOR REBATE-BOLD DECISION FROM REGULATOR Shefali K.Talati, S.B.Modi, U.C.Trivedi, K.M.Dave # Electrical Research and Development
More information1. ELECTRICAL SYSTEM 1.1 Introduction to Electric Power Supply Systems
1. ELECTRICAL SYSTEM 1.1 Introduction to Electric Power Supply Systems 1 Power Generation Plant : Where fuels are the source of generation, a common term used is the HEAT RATE which reflects the efficiency
More informationWELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2
WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 DESCRIPTION OF SERVICE A. General: RULE NO. 2 1. Alternating current service at 60-hertz (cycles per second)
More information