1
2
3 FROM B.C. HYDRO FOR OVERHEAD INSTALLATION ONLY DUCT SEAL (SEE NOTE 8) PULL BOX (SEE NOTE 5) PULL BOX (SEE NOTE 5) FROM B.C. HYDRO 7- REVISED NOTES & TABLES ON PAGES,3,4,5,.MARCH AJ - GENERAL REV.MA 08 MK BARRIER (SEE NOTE 7) CONDUCTORS (SEE NOTES & ) LINE LUGS (SEE NOTE ) SERVICE ENTRANCE LINE ENCLOSURE LINE GROUNDED LOAD (SEE NOTE 4) LOAD NEUTRAL LUGS (SEE NOTE ) ALTERNATIVE ALTERNATIVE ALTERNATIVE (SEE NOTE ) RIGID CONDUITS (SEE NOTE 8) B.C. HYDRO ENTRY AT THE TOP B.C. HYDRO ENTRY ON THE SIDE (LEFT HAND ENTRY SHOWN) PULL BOX (SEE NOTE 5) ALTERNATIVE ALTERNATIVE BARRIER (SEE NOTE 7) LINE LOAD FROM B.C. HYDRO SERVICE ENTRANCE ENCLOSURE SERVICE ENTRANCE ENCLOSURE WITH CIRCUIT LINE BREAKER LOAD CONDUCTORS (SEE NOTES & ) PULL BOX (SEE ALTERNATIVE NOTE 5) RIGID CONDUITS (SEE NOTE 8) FROM B.C. HYDRO B.C. HYDRO ENTRY AT THE BOTTOM ALTERNATE B.C. HYDRO ENTRY AT THE BOTTOM (LEFT HAND ENTRY SHOWN) FOR CIRCUIT BREAKERS ONLY DRAFTER: BB ORIGINAL ISSUE DATE: FEBRUARY 98 PAGE OF THREE PHASE TO 00A,08V AND 00V SERVICE ENTRANCE ENCLOSURE DETAILS ES53 S-0.0 7
4 NOTES:. Position, quantity and type of line lugs and neutral lug in the service entrance equipment may vary with manufacturer and service size. There must be one lug for each service conductor.. Under no circumstances shall load conductors cross or otherwise interfere with the incoming BC Hydro conductors. 3. Service entrance equipment shall be adequately rated for the available fault levels. Consult district or divisional engineering about the available fault levels. 4. Service entrance enclosure shall facilitate a fusible switch enclosure or a circuit breaker. For single service 00 A or less at 0/08 V, service entrance enclosure shall be the meter base, provided that fault level is less than 0kA. Above 0kA, over current protection device must be installed ahead of meter base. 5. Some services 00 A or less with top entry (see note 3.5b on ES54 S-0.0) or with alternate bottom entry for circuit breaker may not require a pullbox. See drawings ES54 S-0.0 to S-0. for details.. Minimum bending radius for any conductor shall be in accordance with drawing ES53 U Barrier between the pullbox and service entrance enclosure may not exist or may be slotted to allow conductors to be broken out of the bundle in the pullbox. For steel barrier, conductors must remain in the bundle when passing through barrier to prevent eddy currents. If conductors must be broken out of the bundle chase nipples made of aluminum must be used. 8. All service ducts shall be rigid type conduits with sealed factory bends and fittings sealed thoroughly with duct seal (Stock No ) at the point where BC Hydro conductors enter the pullbox. 9. This drawing is based upon customer service instructions (CSIs) S0- and S All 0/08V services larger than 800A and 347/00V services larger than 00A shall be served from padmount transformers only.. In the event that there is a conflict between Section "S" of ES53 Standards and the Requirements for Secondary Voltage Revenue Metering 700V and less, the latter takes precedence for Metering Applications only. DRAFTER: DM ORIGINAL ISSUE DATE: DECEMBER 989 THREE PHASE TO 00A,08V AND 00V SERVICE ENTRANCE INSTALLATION NOTES PAGE OF ES53 S-0.0 7
5 LIST OF CONDUCTOR SIZES AND STOCK NUMBERS TO SINGLE COMMERCIAL AND INDUSTRIAL CUSTOMERS ON PRIVATE PROPERTY, WITH 80% RATED MAIN BREAKER 3 Phase (Quadraplex) Customer Main Aluminum Copper Switch/Breaker No. of Bundles Stock Number No. of Bundles Stock Number Up to 5A # AWG A 400A #4/0 AWG 500 kcm #/0 AWG 350 kcm A 800A 350 kcm 500 kcm #4/0 AWG 350 kcm A kcm kcm A kcm kcm NOTES: The peak demand was assumed to be 80% of the rating of the main service entrance breaker, and the load factor 0.8 (or 80%), as per note. Cable ampacity has been calculated using a Load Factor (LF) of 0.8 and the corresponding multiplying factors, where LF is defined based on a 4 hour cycle as per ES53 U-0.0. Cable ampacities in conduits are as per BCH standard ES53 U Cable ampacities in vertical runs at the terminal pole are based on the following assumptions: - Ambient air temperature of 30^C - Wind speed of ft/s - Parallel runs use large cable guards and the two sets of cables are strapped to the pole individually, so that they are not in contact. 5. The maximum number of U/G ducts is 4 and the maximum number of parallel runs at the terminal pole is.. The maximum service size supplied from a bank of polemounted transformers is 800A, due to the limitation of runs at the terminal pole. DRAFTER: DM ORIGINAL ISSUE DATE: FEBRUARY 007 THREE PHASE TO 00A,08V AND 00V CONDUCTOR SIZES FOR 80% RATED CUSTOMER SERVICE BREAKER PAGE OF 3 ES53 S
6 LIST OF CONDUCTOR SIZES AND STOCK NUMBERS TO SINGLE COMMERCIAL AND INDUSTRIAL CUSTOMERS ON PRIVATE PROPERTY, WITH 00% RATED MAIN BREAKER 3 Phase (Quadruplex) Customer Main Aluminum Copper Switch/Breaker No. of Bundles Stock Number No. of Bundles Stock Number Up to 5A 00A 400A 00A 800A 00A 00A 3 #4/0 AWG 500 kcm 500 kcm 750 kcm 750 kcm #/0 AWG kcm 500 kcm 500 kcm kcm kcm (Note 5) NOTES: The peak demand was assumed to be 00% of the rating of the main service entrance breaker, and the load factor 0.8 (or 80%), as per note. Cable ampacity has been calculated using a Load Factor (LF) of 0.8 and the corresponding multiplying factors, where LF is defined based on a 4 hour cycle as per ES53 U-0.0. Cable ampacities in conduits are as per BCH standard ES53 U Cable ampacities in vertical runs at the terminal pole are based on the following assumptions: - Ambient air temperature of 30^C - Wind speed of ft/s - Parallel runs use large cable guards and the two sets of cables are strapped to the pole individually, so that they are not in contact. The following additional requirements apply to 00A services with 00% rated main service breaker: - The customer must provide to BCH Design Office the daily load profile; - The maximum load must not exceed 00A; - The 4 hours average load must not exceed 80A (0.8 load factor); - The maximum load of 00A is allowed for not more than 8 hours within any 4 hours period. If the customer cannot demonstrate compliance with all the above requirements, then the service entrance breaker will be required to trip at 80A, the equivalent of an 80% rated breaker.. The maximum number of U/G ducts is 4 and the maximum number of parallel runs at the terminal pole is. 7. The maximum service size supplied from a bank of pole mounted transformers is as per note 0 of ES53 S-0.0. DRAFTER: DM ORIGINAL ISSUE DATE: FEBRUARY 007 THREE PHASE TO 00A,08V AND 00V CONDUCTOR SIZES FOR 00% RATED CUSTOMER SERVICE BREAKER PAGE OF 4 ES53 S
7 RECOMMENDED SIZE OF TRANSFORMERS TO SINGLE COMMERCIAL AND INDUSTRIAL CUSTOMERS ON PRIVATE PROPERTY Customer Main Switch/ Breaker O/H Bank kva High (80%) Med (0%) PMT kva High (80%) Med (0%) Up to 5A 3 x 50 3 x A 3 x 50 3 x A 3 x 00 3 x A 3 x 7** 3 x 7** A 750* A 000* 750* 00A 500* 000* NOTES:. The following load categories are covered in the transformer selection tables: High- average 4 hours load could reach 80% of the peak load, as defined at. Medium- average 4 hours load could reach 0% of the peak load, as defined at.. The term "peak load" referred to in note, is 80% of the main breaker rating for 80% rated breakers and 00% of the main breaker rating for 00% rated breakers. 3. The load categories are for guidance only. A designer must assess the load and size the transformer accordingly. 4. Services with 00% rated main service breaker are classified as "High" load. 5. BCH supplied transformers are suitable for 0% of the nameplate kva for a maximum duration of 8 hours within a 4 hour period, with a preload of 80% and a maximum temperature rise of 5^C over 30^C ambient. The maximum short-time overload is 30% of the nameplate KVA for a maximum total duration of one hour within a 4 hour period. * 750kVA, 000kVA and 500kVA units are available only with a primary voltage of 4,940V. ** Transformer banks consisting of 7kVA units shall be platform mounted only. The preference is to install three phase pad mounted units instead. DRAFTER: DM ORIGINAL ISSUE DATE: FEBRUARY 007 PAGE OF THREE PHASE TO 00A,347V/00V TRANSFORMER SIZES FOR SINGLE SERVICE 5 ES53 S
8 RECOMMENDED SIZE OF TRANSFORMERS TO SINGLE COMMERCIAL AND INDUSTRIAL CUSTOMERS ON PRIVATE PROPERTY Customer Main Switch/ Breaker O/H Bank kva PMT kva High (80%) Med (0%) High (80%) Med (0%) Up to 5A 00A 400A 00A 800A 00A 00A 3 x 5 3 x x 5 3 x x 50 3 x x 75 3 x x 75 3 x NOTES:. The following load categories are covered in the transformer selection tables: High- average 4 hours load could reach 80% of the peak load, as defined at. Medium- average 4 hours load could reach 0% of the peak load, as defined at.. The term "peak load", referred to in note, is 80% of the main breaker rating for 80% rated breakers and 00% of the main breaker rating for 00% rated breakers. 3. The load categories are for guidance only. A designer must assess the load and size the transformer accordingly. 4. Services with 00% rated main service breaker are classified as "High" load. 5. BCH supplied transformers are suitable for 0% of the nameplate kva for a maximum duration of 8 hours within a 4 hour period, with a preload of 80% and a maximum temperature rise of 5^C over 30^C ambient. The maximum short-time overload is 30% of the nameplate kva for a maximum total duration of one hour within a 4 hour period. DRAFTER: DM ORIGINAL ISSUE DATE: FEBRUARY 007 PAGE OF THREE PHASE TO 00A,0/08V TRANSFORMER SIZES FOR SINGLE SERVICE ES53 S-0.0 7
9 GROUND ROD FOR CONNECTOR INSTALLATION DETAILS - QUANTITY CHANGE PAGE.MARCH AJ SEE DRAWING NO. ES53 N-0 x 4" DUCTS TO T.P. T0 NEUTRAL ONLY 3 4 OR SECTION A-A (ONLY ONE PHASE SHOWN) 5 x 4" DUCTS RIGID, SEALED TO CUSTOMER SERVICE 4- TITLE CHANGE.FEB. 07 MK 5- TITLE REVISED.MA 08 MK FOR INSTALLATION & STOCK NO. OF CABLE GUARDS, COVERS AND METHOD OF ATTACHMENT OF CABLES, SEE SECTION-M IN THIS STANDARD BOOK A FOR PILASTER INSTALLATION DETAILS SEE DRAWING NO. ES54 S-0 IN THE UNDER- GROUND CIVIL STANDARDS BOOK SECTIONAL ELEVATION FOR DETAILS OF LID OPTIONS SEE DRAWING NO. ES54 B-0 IN THE UNDERGROUND CIVIL STANDARDS BOOK A T0 NEUTRAL ONLY DRAFTER: BB ORIGINAL ISSUE DATE: OCTOBER 98 PAGE OF 00% RATED 800A MAX. 3 PHASE POLE DIP WIRING AND INSTALLATION DETAILS ES53 S-0.0
10 # AWG GROUND CONDUCTOR 3 or 4 TO NEUTRAL ONLY TO TERMINAL POLE TO SERVICE 5 SERVICE BOX ONE-LINE DIAGRAM OF CONNECTIONS BILL OF MATERIAL Item Quantity Description Stock No. or 3 4 per phase per phase per phase Cable, 4/C - 500kcm - Cu Cable, 4/C - 500kcm - Cu Cable, 4/C - 750kcm - Al Insulated Secondary Multi-connector, 000A, 5 Terminal Insulated Secondary Multi-connector, 000A, Terminal 33 Concrete Box as required Box Riser M/H Lid Riser or 33 Lid Collar NOTES:.. For stock numbers of insulated secondary multi-connectors accessories see drawing ES53 Z4-08. The highest allowed load factor for this type of installation is 0.4 (40%). Services supplying customers with higher load factors cannot be provided by using this standard. 3. The selected cable sizes are suitable for services with 00% rated main breakers. ES54 S-0 ES54 B-05 ES53 Z4-08 ES53 N3-0 ES53 M Sect. ES53 M3-0 3 Phase Dip Service, 00A, Civil Details 33 S.B. - Civil Details Multi-connector - 00A Compression Service Box Capacities Terminal Pole Structures Multi-connector - 00A Compression REFERENCE DRAWINGS DRAFTER: DM ORIGINAL ISSUE DATE: OCTOBER 98 00% RATED 800A MAX. 3 PHASE POLE DIP WIRING AND INSTALLATION DETAILS PAGE OF ES53 S-0.0
11
12
13
14
15
Pretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationSOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS
SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial
More informationMINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates
MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More information320A Single Phase URD Meter Loop Installations
320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal
More informationWisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power
Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that
More informationTransmission & Distribution Glossary of Electrical Terms
Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to
More informationSpring Test 7 due 05/03/2013
Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous
More informationD9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE
SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.
More informationEngineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes
Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationSPECIFICATIONS FOR COMMERCIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR COMMERCIAL CONSTRUCTION REVISED 06/28/18 Commercial Construction Specifications Revision List REVISION Date Page No. Description 03/01/00 4.2-4.3 Changed leveling
More informationCurrent Transformer, Termination & Disconnect Cabinets WE Energies Approved
Current Transformer, Termination & Disconnect Cabinets WE Energies Approved 2 TABLE OF CONTENTS Table of Contents Current Transformer Cabinets Overhead Entry... 4 Underground Entry and Underground Exit...
More informationTABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet
DRAWING NUMBER INTRODUCTORY INFORMATION Important Notices Underground Plant Protection Information Code Clearances Commercial/Industrial Information Sheet Work Management Customer Projects Engineering
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationApproved Contractor Construction e-guide Residential Commercial
Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13
More informationELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016
UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department
More informationSYSTEM PROTECTION SYSTEM PROTECTION. Underground Electric Distribution Standards I. FUSE COORDINATION
I. FUSE COORDINATION I.1. GENERAL I.1.1. The purpose of protective coordination is to provide isolation of a fault as close to the fault as possible so that a minimum of customers will be affected. The
More informationFeatures, Benefits and Functions
-8 Buck-Boost and Lighting Single- and Three-Phase February 007 Single- and Three-Phase Applications, 60 Hz Type EP Product Description Types EP, EPT Sand and Resin Encapsulated design. Suitable for indoor
More informationPentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION
PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company
More informationSECTION 300 OVERHEAD SERVICE
SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to
More informationElectric & Gas Service Requirements (Greenbook) Overview
INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed
More informationRevised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall
More informationUNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.
UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.
More informationSECTION 500 METERING AND ASSOCIATED EQUIPMENT
SECTION 500 METERING AND ASSOCIATED EQUIPMENT 500.0 General Meter sockets shall be provided, installed and maintained by Customer. When the ratings of meter sockets are exceeded, transockets shall be used.
More information2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code
2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More information34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE
4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationCONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES
CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE
More informationSERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us SERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS
More informationBUSINESS PROCEDURE. January 1, 2015
PURPOSE To provide uniform charges and standard estimating unit charges for electric supply and service to all classes of customers as required and supported by other NB policies. SCOPE This pricing policy
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationQuik-Spec Coordination Panelboard Specifications
Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY
More informationTechnical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA
Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA Table of Contents TPS NQ & AQ Series Overview 2 Switchboard Technical Data 3-5 Panelboard Technical Data 5-11 1 Tier Power
More informationCustomer Requirements Downtown Secondary Network Service
Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard
More informationItem Code Description Unit Qty Total
UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories
More informationSECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS
CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More informationApplication guide. Tmax Link OEM UL 891 Switchboard Program
Application guide Tmax Link OEM UL 891 Switchboard Program 04 Tmax Link Overview 04 Standards 04 UL File Extension Process Overview 05 Electrical Data 05 Technical Data 05 Ambient Conditions 08 Circuit
More informationRequirements for Secondary Voltage Revenue Metering (750 V and less)
Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.
More informationUNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.
UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationIndianapolis Power & Light Company
Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis
More informationTECHNICAL GUIDELINE. Medium Voltage Conductor Ampacities ALUMINUM COPPER. Single Conductor 5kV - 35kV
Medium Voltage Ampacities Single 5kV - 35kV 2 130 145 150 165 2 100 115 115 130 1 155 175 170 190 1 120 135 130 150 1/0 180 200 195 215 1/0 140 155 150 170 2/0 205 225 225 255 2/0 160 175 175 200 3/0 240
More informationUNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.
UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.
More informationCompany Directive STANDARD TECHNIQUE : TP4B/2. Relating to 11kV and 6.6kV Transformer Protection
Company Directive STANDARD TECHNIQUE : TP4B/2 Relating to 11kV and 6.6kV Protection Policy Summary This document describes the detailed requirements for 11kV/415V and 6.6kV/415V distribution transformer
More informationOVERHEAD SERVICE. Items to consider
OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must
More informationMetering and Service Installation:
Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...
More informationSINGLE PHASE WIRING SPECIFICATIONS
SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationChapter 1 Electrical Theory...1
Electrical Formulas with Sample Calculations Table of Contents Chapter 1 Electrical Theory...1 Unit 1 Electrician s Math and Basic Electrical Formulas...3 Part A Electrician s Math...3 1 1 Fractions...3
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationGENERAL INFORMATION 1.01 PURPOSE
GENERAL INFORMATION 1.01 PURPOSE The purpose of this manual is to supply essential information to customers, employees, architects, engineers, contractors, and others concerned with electrical installations
More informationSERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company
More informationElectrical Design/Build Guide
2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel
More informationSERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp
Printed from NIPSCO.com 04-01-17 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS REVISION
More informationSpring Test 10 due 05/11/2013
Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationSolar Power Switchgear & Energy Storage Renewable Energy Systems
7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH
More informationPower Mod. Introduction.
Power Mod Siemens is proud to introduce Power Mod with QuickSystem - a new robust and featurerich line of modular metering designed with the contractor in mind. Power Mod features a unique combination
More informationSwitchgear Skid, C1192
CUSTOM SOLUTIONS 15kV Modular Stairs stored on floor in front of battery bay Ground grid stored on front tongue of trailer Stairs deployed for unit access Storage box for fencing materials and other parts
More informationBGE STRATEGIC CUSTOMER ENGINEERING
TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND
More informationTOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)
TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT-29499-1A) Contractor: Please read these instructions before starting installation. After installation, please forward this guide to the user
More informationTHREE PHASE WIRING SPECIFICATIONS
THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationDesign Guide for Integration of Fixed-Mount Circuit Breakers
Design Guide Design Guide for Integration of Fixed-Mount Circuit Breakers WL Low Voltage Power Circuit Breakers www.usa.siemens.com/wlbreaker Contents Introduction... 3 Mounting... 3 Mounting Surface...
More informationTransformer Installation, Operation, and Maintenance Manual
Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................
More informationELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours
Candidate Code No. IT 36 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY
More informationAFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationNew Commercial Service Request-Job Process
New Commercial Service Request-Job Process HILCO Electric Cooperative, Inc. thanks you for the opportunity to be your electric provider. We are committed in providing you the best electric service promptly
More informationPUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS
PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS 1. General Metering Requirements a. Interpretation The District s metering requirements shall not be interpreted to conflict with the
More informationCommercial Electric Policy
Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.4 Multi-Unit/Multi-Service Buildings....4 Secondary Termination Enclosures.4 Meter Bases.5 Temporary
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationRESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS
SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and
More informationFor Conduit Inspections
Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit
More informationMetering Products. 4.1 Meter Sockets. 4.2 Meter Breakers. 4.3 Group Metering
Metering Products and Meter Breaker Family.1 Meter Sockets Single Meter Sockets...................................... Commercial Lever Bypass Sockets........................... Multiple Position Horizontal
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to
More informationZG 521 Padvault Three-Phase Transformer
E n g in e e r :R.An th o n Ap p r o v e r :Jo s h u a Jo n e s 2 0 De c 1 7 2 0 De c 1 7 ZG 521 Padvault Three-Phase Transformer ZG 521 Padvault Three-Phase Transformer 1. Scope This material specification
More informationMeter Installation. -and- Padmount Transformer Guide
Meter Installation -and- Padmount Transformer Guide Feb. 2016 METERING REQUIREMENTS The following information shall be used as a guide for installing metering equipment. A self-contained meter has all
More informationKIUC Service Installation Manual
KIUC Service Installation Manual Second Edition (November 2016) This manual provides the general requirements for electric service and metering for Kauaʻi Island Utility Cooperative ("KIUC") and is meant
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationThe cost estimation methodology used to update the charges and credits is the same methodology the Company utilized in the prior year s filing.
LISA D. NORDSTROM Lead Counsel lnordstrom@idahopower.com December 28, 2018 Public Utility Commission of Oregon Filing Center 201 High Street SE, Suite 100 P.O. Box 1088 Salem, Oregon 97301 Re: Tariff Advice
More informationElectrical Tech Note 106
Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the
More informationCLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001
CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS
More informationPROTECTION OF THE BRANCH CIRCUIT
PROTECTION OF THE BRANCH CIRCUIT Branch circuit should always be protected from over current. Hence, an overall current devices shall be installed in all branch circuitries. Function of the over-current
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationFor Options, Modifications and Accessories, see pages Discount Schedule A6
Main and Feeder Units Bulletin 191F and 191M Outgoing Feeder Lug Compartment (FLUG) and Incoming Main Lug Compartment (MLUG)................................................. The Bulletin 191M and 191F
More information