STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B

Size: px
Start display at page:

Download "STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B"

Transcription

1 STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B February 2017

2 STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B DRAFT FINAL DRAFT CONTRACT Name Date Sig Name Date Sig Name Date Sig Prepared S. Bar Oz 02/16 Prepared S. Bar Oz 02/17 Prepared Checked Z. Nir 02/16 Checked Z. Nir 02/17 Checked Approved Z. Nir 02/16 Approved Z. Nir 02/17 Approved 2017/SPEC/STR-1415

3 TABLE OF CONTENTS ANNEXURE B 1. Purchaser. B Scope of Work. B Delivery, Shipment, Storage. B 1 4. Standards and Specifications B 2 5. Tender Documents. B 2 6. Approval of Technical Documentation. B 2 7. Quality Assurance, Quality Control and Tests B 2 8. Name Plates B 2 9. Spare Parts.. B Detailed Specification. B Battery Chargers Data 11.1 AC input data DC output data.. B 3 B 3 B Battery Chargers Operating Characteristics Floating (trickle) charge mode Equalize charge mode Boost charge mode B 3 B 3 B 3 B Battery Data. B Measuring Instruments Range.. B General Requirements... B 5 SUMMARY OF DATA Questionnaire.. B Conformity with Bid Documents B /SPEC/STR-1415

4 TABLE OF CONTENTS/Cont.. ANNEXURE "C" Summary of Prices for Battery Charger 220VDC, 30A for Sub-Station and Switching Stations See Specification STR-1416 C1, C3 APPENDIX 1 Representative Spare Parts for Battery Charger 220VDC, 30A. 2017/SPEC/STR-1415

5 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A 1. PURCHASER: The Israel Electric Corporation Limited. 2. SCOPE OF WORK: Design, develop, manufacture, test, preserve, pack and furnish with adequate packing the following Items including training according to Clause 2.3.1, Specification STR ITEM 1 220VDC, 30A Battery Charger. Quantity: 20 (+50% / -50%). 2.2 ITEM 2 Provide a set of spare parts for Battery Charger 220 VDC, 30A according to Appendix 1, Specification STR DELIVERY, SHIPMENT, STORAGE According to Clause 3, Specification STR B-1

6 4. STANDARDS AND SPECIFICATIONS According to Clause 4, Specification STR TENDER DOCUMENTS According to Clause 5, Specification STR APPROVAL OF TECHNICAL DOCUMENTATION According to Clause 6, Specification STR QUALITY ASSURANCE, QUALITY CONTROL AND TESTS 7.1 Quality Assurance and Quality Control: According to Clause 7, Specification STR Tests: According to Clause 8, Specification STR NAME PLATES According to Clause 9, Specification STR SPARE PARTS According to Clause 10, Specification STR DETAILED SPECIFICATION The battery chargers shall comply with the general and detailed requirements of Clause 11, Specification STR B-2

7 11. BATTERY CHARGERS DATA 11.1 AC Input Data Voltage: 3 x 400V 10% Frequency: Hz DC Output Data Nominal voltage: 220V Nominal current: 30A Stability of output voltage not more than ± 0.5v. 12. BATTERY CHARGERS OPERATING CHARACTERISTICS 12.1 Floating Charge Mode (Normal Operation): Operating characteristic type IU, according to Clause and drawing EVK-6375 of Specification STR-1416, and according to IEC Float charge voltage range: V (continuously adjustable) Current limitation: 30A 2% 12.2 Equalizing Charge Mode Operating characteristic type IU, according to Clause and drawing EVK-6375 of Specification STR-1416, and according to IEC B-3

8 Equalizing charge voltage range: V (continuously adjustable) Current limitation: 30A±2% Boost Charge Mode Operating characteristic type IU, according to Clause Specification STR-1416, and according to IEC Boost charge voltage range: V (continuously adjustable) Current limitation: 15A 2%. 13. BATTERY DATA 13.1 Type: lead-acid battery Capacity: 150 Ah. \170Ah Number of cells: Float charging voltage: 2.23V/cell Equalizing charging voltage: 2.4V/cell Boost charge voltage: 2.7V/cell B-4

9 14. MEASURING INSTRUMENTS RANGE 14.1 DC Digital Voltmeter: 300V. Resolution: 4.5 Digits DC Digital Ammeter: 35A. Resolution: 3 Digits The measuring instruments should not be part of the controller or the Display Panel. 15. GENERAL REQUIREMENTS 15.1 The Bidder shall complete all the paragraphs requested in the Summary of Data. In case the bidder cannot answer a paragraph, N/A (not available) shall be mentioned Annexure B (Summary of Data) shall be typewritten and submitted to Purchaser with 5 copies All the technical documentation (catalogue leaflets, reference lists, diagrams etc.) requested in Annexure B shall be submitted, as an integral part of the Bidder s Quotation. B-5

10 SUMMARY OF DATA FOR BATTERY CHARGERS 220VDC, 30A QUESTIONNAIRE Name of Bidder: 16. DOCUMENTATION FOR APPROVAL Time required after contract is awarded for submitting of drawings as per Annexure B, Clause 6, Specification STR days 17. MANUFACTURER S NOMENCLATURE 17.1 Type designation Model or Serial number (if available). 18. What percentage of local participation is labour, materials and parts is there in the manufacture of the total produce? (%) 18.1 Include accountant approval for the above percentage (Yes/No) Yes B-6

11 19. DIMENSIONS & MECHANICAL CONSTRUCTION Name of Bidder: 19.1 Overall Dimensions: Height..(mm) Length... (mm) Depth. (mm) 19.2 Net weight (kg) Steel plate thickness.. (mm) Thickness of the steel profiles used for cabinet's construction... (mm) STR-1416 See Clause Minimum back space to wall or equipment.(mm) 19.6 Cabinets are frontal/rear/both accessible. (Contractor shall state the construction of the doors, if they are removable, lockable). Frontal 19.7 Natural Ventilation...(Yes/No) Yes B-7

12 Name of Bidder: 19.8 Height of equipment on front panel between..(mm) The cubicle shall be provided with appropriate lifting hooks in top for transport.. (Yes/No) Yes Degree of protection according to EN (at least) IP Are cables entrances as required in para, ?...(Yes/No) Yes Is cooper ground bus supplied as required in para (Yes/No) Yes Specify quality assurance system used RATINGS 20.1 AC Supply Nominal voltage... (V %) 400V 10% Current at full load (A) Cos (power factor) for full load Frequency..(Hz %) % - 3% 20.2 DC Output Nominal voltage of charger (V %) 236 1% Stability of output voltage..(v) ± Voltage range for float charge (V) B-8

13 Name of Bidder: Voltage range for equalizing charge.(v) Voltage range for boost charge...(v) Nominal current of charger. (A %) 30 2% Current limit: a. Float operation.. (A) 30 2% b. Equalizing charge.....(a) 30 2% c. Boost charge..(a) 15 2% Operating characteristic diagram draw. No a. Float operation.... b. Equalizing charge... c. Boost charge Maximum Output voltage ripple : - Without battery..(% of rated voltage) 1% rms - At full load...(% of rated voltage) 0.2% rms Overall efficiency at full load (at least). (%) RECOMMENDED SPARE PARTS (LIST ANNEXED) Yes B-9

14 22. TRANSIENT BEHAVIOUR Name of Bidder: 22.1 Necessary time to reach the normal characteristic values at a sudden load change from zero to full load (including short circuit)...(ms) Start-up time..(sec) < Maximum output voltage at start-up time.(%) 23. Is the charger operation influenced by the waveform of AC supply, provided it is within NEMA prescriptions?... (Yes/No) 24. Radio interference voltage level (according to IEC special application(yes/no) Yes 25. Electromagnetic compability according to IEC Class A (Yes/No) 26. Maximum Noise level at 1m distance at full load...(db) Yes 55dbA 27. Maximum over temperature rise, at full load in float or boost charge operation mode, of any component of the charger, above the ambient temperature between 5 and +40 C...( C) 28. TRANSFORMER AND REACTORS 55 C 28.1 Core type Core losses...(w/kg) 28.3 Maximum inrush current (A) B-10

15 Name of Bidder: 28.5 Winding insulation class Manufacturer Max. acceptable temperature.. T=95ºC 29. RECTIFIER UNIT 29.1 Max. SCR voltage. (V) Manufacturer Max. D.C. current at +40 C ambient temperature..(a) 29.4 Maximum over temperature at rated current...( C) 29.5 Heat sink type Temperature of all compartments does not exceed.. 85ºC 29.7 Max impulse current..(amp) 29.8 Impulse current duration.(sec) B-11

16 Name of Bidder: 30. CONTROL UNITS 30.1 Manufacturer Type. 31. MAIN RECTIFIER BRIDGE PROTECTION UNITS 31.1 RC....(Yes/No) 31.2 C.B: Manufacturer/type Rated current (A) Short circuit current.. (KA) A characteristic curve included....(yes/no) 32. AC INPUT M.C.B 32.1 Manufacturer/type Rated current..(a) 32.3 Short circuit current (Ics, according to IEC )..(KA) A characteristic curve included....(yes/no) B-12

17 Name of Bidder: 33. DC OUTPUT C.B 33.1 Manufacturer/type Rated current (A) 33.3 Short circuit current (Ics, according to IEC )..(KA) A characteristic curve included (Yes/No) 34. Are there any fuses for protection of internal circuits?...(yes/no - specify) 35. DIGITAL AMMETER 35.1 Manufacturer/type Scale...(A) 35.3 Accuracy (% of read value).. (%) DIGITAL VOLTMETER 36.1 Manufacturer/type Scale....(V) 36.3 Accuracy (% of read value)..(%) 1 B-13

18 Name of Bidder: 37. ELECTROLYTIC CAPACITORS The bidder shall provide the calculations for capacitor choose for operating life time of 20 years (on DC output). Yes 37.1 Manufacturer 37.2 Type 37.3 ESR (Equivalent Series Resistance) 37.4 Operating temperature 37.5 Operating life at 105 C 37.6 Designed operating life at 40 C 20 years 38. CATALOGUES The Bidder shall provide the following catalogues together with tender documents SCR of Main Rectifier bridge.... (No.) 38.2 Transformer and reactors....(no.) 38.3 Filter capacitors on DC output.. (No.) 38.4 Filter capacitors on AC input..... (No.) 38.5 Main circuit breaker (no.) 38.6 Output circuit breaker of Rectifier bridge.(no.) 38.7 Measuring instruments.. B-14

19 39. REFERENCE LIST The Bidder shall submit a reference list with similar battery chargers in service (list annexed).. (Yes/No) 40. QUALITY CONTROL The Bidder submits herewith a copy of the Israeli Standard Institute or equivalent national or international standard institutes certificate confirming the approval of their quality control organization according to the requirement of standard ISO 9001: TEST 41.1 Bidder shall submit with his bid the description of the tests performed to the offered charger according to Clause 8 spec. STR EMC test report Meantime between failure for the Battery Charger (h). MTBF Gamma-Percentage Operating Time to Failure 43. Meantime to repair for the Battery Charger (h). MTTR. 44. Programmable Controller, according to Clause Spec. STR-1416 B-15

20 Name of Bidder: 45. Communication Adaptor to TCP/IP according to Clause Spec. STR SNMP ALAMS List of all the alarms indicated on the charger..(yes/no) Yes 46.2 Each alarm activates a potential-free contact for remote indication.(yes/no) Yes Contact data: Max. operating voltage..(v) Continuous current rating......(a) Max. switching power for resistive load.(w) 250V DC RELIABILITY, MAINTENANCE, AND SAFETY 47.1 The proposed Battery Charger system shall comply with RMS requirements specified in STR-1416 Appendix No The Contractor shall submit the correct RMS data and information about the proposed Battery Charger system written in the RMS questionnaire. B-16

21 Name of Bidder: 47.3 The proposed Expansion of existing Battery Charger system shall participate in Reliability Field Demonstration (RFD) specified in STR Appendix No. 5 and the Contractor will be responsible for consequences of RFD The Contractor representative shall participate in Failure review board. B-17

22 48. CONFORMITY WITH BID DOCUMENTS Bidder is requested to describe or indicate deviations of tendered equipment from all requirements in the Specification. In case no deviations are mentioned, it will be understood that Bidder s offer complies entirely with all requirements in this Specification. Bidder hereby certifies that he agrees to all provisions of the Bid Documents unless exceptions are specifically and clearly listed in the proposal and identified as Exceptions. Bidder s printed terms and conditions are not considered specific exceptions. Any exceptions which Bidder has taken are listed on page. Bidder hereby certifies that he agrees to all conditions of cover letter of the Israel Electric Corporation Limited which accompanied the Bid Documents. Signature of Bidder Date of Bid B-18

STR-1416 GENERAL SPECIFICATION FOR BATTERY CHARGERS ANNEXURE B

STR-1416 GENERAL SPECIFICATION FOR BATTERY CHARGERS ANNEXURE B STR-1416 GENERAL SPECIFICATION FOR BATTERY CHARGERS ANNEXURE B February 2017 STR-1416 GENERAL SPECIFICATION FOR BATTERY CHARGERS ANNEXURE B DRAFT FINAL DRAFT CONTRACT Name Date Sig Name Date Sig Name Date

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

EU RO Mutual Recognition Technical Requirements

EU RO Mutual Recognition Technical Requirements 1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.

More information

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems Version:- 2.1 Date of Issue:- July 2016 Page 1 of 29 NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems 1. Purpose This document is to detail the technical requirements

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

MESP TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION

MESP TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A STATIONARY CONTROL BATTERY AND CHARGER SET FOR USE IN A SUBSTATION Version: 2 Issued: August 2016 Owner: Head of Engineering

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

INVITATION FOR QUOTATION. TEQIP-II/2015/GJ1G02/Shopping/M-EE-09

INVITATION FOR QUOTATION. TEQIP-II/2015/GJ1G02/Shopping/M-EE-09 INVITATION FOR QUOTATION TEQIP-II/2015/GJ1G02/Shopping/M-EE-09 02-Dec-2015 Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3 TITLE SPECIFICATION FOR MEDIUM VOLTAGE DATE: FEBRUARY 2015 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD... 2 INTRODUCTION... 3 1 SCOPE... 3 2 NORMATIVE S... 3 3 DEFINITIONS AND ABBIATIONS... 3 4 REQUIREMENTS...

More information

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR GETCO/E/TS-50V BCHR(SCADA)

More information

INVITATION FOR QUOTATION. TEQIP-III/2018/uceo/Shopping/48

INVITATION FOR QUOTATION. TEQIP-III/2018/uceo/Shopping/48 INVITATION FOR QUOTATION TEQIP-III/2018/uceo/Shopping/48 29-Dec-2018 To, Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for the

More information

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application) GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR FLOAT CHARGER (100A) & BOOST CHARGER (60A) FOR WITH REQUIREMENT FOR SCADA

More information

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification

More information

NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems

NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems Version:- 2.1 Date of Issue:- August 2016 Page 1 of 28 NPS/003/016 Technical Specification for 48V and 110V Battery and Charger Systems 1. Purpose The purpose of this document is to detail the technical

More information

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

Industrial Chargers and

Industrial Chargers and Industrial Chargers and DC Systems SPR - Single Phase Rectifier TPR - Three Phase Rectifier 12V 250V 5A 1000A Designed for all Industrial applications Oil & Gas, Petrochemicals Offshore, Onshore, Pipelines

More information

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC Manufacturer s declaration in accordance with 8- Frame Model catalogue reference 93PS-XX(20)-YY- 93PS-XX(40)-YY- Number of power modules (UPM) 1 1 or 2 Number of internal batteries 0 to 2 x 32 blocks 0

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220 V BATTERY CHARGER GETCO / E / TS- BCHR 3202 / R2 Oct 15 Seal & Sign

More information

UNIVERSITY OF CALCUTTA Centre for Research in Nanoscience and Nanotechnology JD-2, Sector-III, Salt Lake City Kolkata

UNIVERSITY OF CALCUTTA Centre for Research in Nanoscience and Nanotechnology JD-2, Sector-III, Salt Lake City Kolkata UNIVERSITY OF CALCUTTA Centre for Research in Nanoscience and Nanotechnology JD-2, Sector-III, Salt Lake City Kolkata- 700106 NOTICE INVITING QUOTATION Sealed Quotations are invited from reputed suppliers

More information

INVITATION FOR QUOTATION. TEQIP-III/2018/gcej/Shopping/50

INVITATION FOR QUOTATION. TEQIP-III/2018/gcej/Shopping/50 INVITATION FOR QUOTATION TEQIP-III/2018/gcej/Shopping/50 15-Sep-2018 To, Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for the

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6 I. PART 1 GENERAL 1. SCOPE A. NEMA Premium copper-wound ultra low loss isolation transformer with a higher efficiency than that required by NEMA Std. TP-1. Optimized for energy efficiency over a wide load

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

AME. Rectifier - Battery charger. Industrial applications: Key features:

AME. Rectifier - Battery charger. Industrial applications: Key features: Rectifier - Battery charger AME VRLA batteries, flooded battery or Ni/Cd with output voltage from 24, 48, 110, 220 Vdc up to 150A Industrial applications: Oil&Gas (Petrochemicals Offshore, Onshore, Pipelines);

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

QUEENSLAND URBAN UTILITIES

QUEENSLAND URBAN UTILITIES DOCUMENT NO : EQUIPMENT NO : PREPRED : CHECKED : PPROVED : SHEET NO : 1 of 6 GENERL 1 Battery Charger DCC Inverters 3 DCDC Converters 4 System Design Life (other than batteries) Years 5 Battery Design

More information

SPECIFICATIONS OF Ni-Cd BATTERY BANK

SPECIFICATIONS OF Ni-Cd BATTERY BANK SPECIFICATIONS OF Ni-Cd BATTERY BANK ANNEXURE-Z Supply, Installation and commissioning of Ni-cd battery bank for high rate of discharge type KPH 125V 210 AH consisting of 103 number of cells. Detail technical

More information

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders

Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Fuse-Links and Fuse Holders ETS12-01-01 Specification ETS12-01-01 Ver 3 Contents 1. Purpose and Scope... 1 2. References...

More information

INVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station

INVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station INVITATION TO TENDER MR 84/2016 SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station Fiji Electricity Authority seeks reputable Manufacturer/Supplier

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR SELECTIVE LEVEL METER GETCO/E/TS- PACC SLM 03504/R0, Dt: 2.04.2008 Page

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

POWER kva

POWER kva +44 (0)20 8868 3732 TECHNICAL DATA SHEET B9600 400-800kVA GENERAL INFORMATION UPS Type ON LINE - Doppia Conversione Nominal output power (Cos φ0,8) kva 400 500 600 800 Nominal output power (Cos φ1,0) kw

More information

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System 2004 Specifications CSJ 1068-04-126, 0197-02-108 SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System 1. Description. This work shall consist of furnishing and installing an integrated solar Panel

More information

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February

More information

PART A TENDER SUBMISSION

PART A TENDER SUBMISSION PART A TENDER SUBMISSION Page 1 of 24 FORM A: TENDER (SEE B7) 1. Project Title SUPPLY AND DELIVERY OF REGULAR CAB CHASSIS TRUCKS 2. Bidder Name of Bidder Street City Province Postal Code (Mailing address

More information

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil)

Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear (In Oil) Ergon Energy Corporation Limited Technical Specification for 12kV Powder Filled Current Limiting Fuse-Links for Use in Switchgear ETS12-01-03 Specification ETS12-01-03 Ver 3 Contents 1. Purpose and Scope...

More information

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air)

Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear (In Air) Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Powder Filled Current Limiting Fuse Links for Use in Switchgear ETS12-01-02 Specification ETS12-01-02 Ver 3 Contents 1. Purpose

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

GENERAL SPECIFICATION ELECTRICAL

GENERAL SPECIFICATION ELECTRICAL GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.

More information

M Technical Specification No. for the supply of Battery Charger. Israel Railways Ltd. Rolling Stock Division

M Technical Specification No. for the supply of Battery Charger. Israel Railways Ltd. Rolling Stock Division Technical Specification No. M-03-411 for the supply of Battery Charger Date Comments Signed Approved / Issued by Version 01/01/17 Edit Maksym Pichkur Avi Zalman 29/06/16 Additions ZIV-AV/Avi Bornstein

More information

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA 017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA CONTENTS PAGE 1. Scope 2 2. System Parameters 2 3. Service Conditions 2 4. Applicable Standards 3 5. Basic Features 4 6. Quality

More information

43-SDMS-01 SPECIFICATIONS FOR

43-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3

More information

POWER kva

POWER kva TECHNICAL DATA SHEET B9000 FXS 60-80-100-125-160kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos φ 0,8) kva 60 80 100 125 160 Nominal output power

More information

BIHAR STATE POWER TRANSMISSION COMPANY LIMITED MANUFACTURING QUALITY PLAN -- BATTERY CHARGER. Quantum of Check / Sampling with basis

BIHAR STATE POWER TRANSMISSION COMPANY LIMITED MANUFACTURING QUALITY PLAN -- BATTERY CHARGER. Quantum of Check / Sampling with basis A. Section : RAW MATERIAL INSPECTION 1.0 ELECTRONIC COMPONENTS 1.1 RESISTORS (Metal Film, Wire Wound) 1.2 POTENTIOMETERS 1.3 CAPACITORS (Polystyrene, electrolytic) 1.4 TRANSISTORS 1.5 L E D 1.6 1.7 INTEGRATED

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT. (SPECIFICATION NO. MSEB/Dist/IV/2004.

TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT. (SPECIFICATION NO. MSEB/Dist/IV/2004. TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT (SPECIFICATION NO. MSEB/Dist/IV/2004.) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 18

More information

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION TITLE SPECIFICATION FOR CONTACTORS FOR PUBLIC LIGHTING REFERENCE REV DATE: NOVEMBER 2010 PAGE: 1 OF 16 TABLE OF CONTENTS Page FOREWORD.. 2 INTRODUCTION 3 1 SCOPE...... 3 2 NORMATIVE REFERENCES...... 3

More information

NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links

NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links Version:- 7.0 Date of Issue:- July 2017 Page 1 of 19 NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links 1. Purpose The purpose of this document is to detail

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

D.C. DISTRIBUTION BOARD

D.C. DISTRIBUTION BOARD PRAMBL: The TC is maintaining 50-volt battery backup system for the PLCC communication. The 50-volt D.C. supply from the Float cum Boost charger is brought to D.C. Distribution Board from where supply

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01

More information

Technical data sheets

Technical data sheets GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

QUOTATION REF NO: CBK/019/2013/2014 SUPPLY, INSTALLATION, TESTING AND COMMISSIONING A 20 KVA UNINTERRUPTIBLE POWER SUPPLY UNIT (UPS) FOR

QUOTATION REF NO: CBK/019/2013/2014 SUPPLY, INSTALLATION, TESTING AND COMMISSIONING A 20 KVA UNINTERRUPTIBLE POWER SUPPLY UNIT (UPS) FOR QUOTATION REF NO: CBK/019/2013/2014 SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF A 20 KVA UNINTERRUPTIBLE POWER SUPPLY UNIT (UPS) FOR FINANCIAL REPORTING CENTRE AT CENTRAL BANK OF KENYA, PENSION

More information

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC) TECHNICAL DATA SHEET B9000 FXS 200-250 - 300kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE - Double Conversion Nominal output power (Cos φ0,8) kva 200 250 300 Nominal output power (Cos φ1,0)

More information

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT 33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar,

More information

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out) TECHNICAL DATA SHEET B8033FXS 10 15 20 kva 3Ph(In) 3Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cosϕ 0.9) kva 10 15 20 Nominal output power (Cosϕ 1.0) kw 9 13.5

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out) TECHNICAL DATA SHEET B8031 FXS 10 15 20 kva 3Ph(In) 1Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos 0.9) kva 10 15 20 Nominal output power (Cos 1.0) kw 9 13.5

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT SECTION 22 05 12 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable in the section

More information

AS/NZS AS/NZS

AS/NZS AS/NZS TEST REORT AS/NZS 4777.2 AS/NZS 4777.3 Grid connection of energy systems via inverters Grid protection requirements Report reference number... : 13TH0287-AS/NZS 4777_0 Date of issue......: 2014-01-22 Total

More information

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENT AND QUANTITIES

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENT AND QUANTITIES Tamil Nadu Transmission Corporation Limited Bharat Heavy Electricals Limited 400/110 KV Substation at Thappagundu & 400/230-110 KV Substation at Anikadavu, Technical specification for 420/245/132kV Isolators

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1

E/ECE/324/Rev.2/Add.102/Rev.1 E/ECE/TRANS/505/Rev.2/Add.102/Rev.1 30 August 2011 Agreement Concerning the adoption of uniform technical prescriptions for wheeled vehicles, equipment and parts which can be fitted and/or be used on wheeled vehicles and the conditions for

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

SUBSTATION EQUIPMENT - Page 1 of 8

SUBSTATION EQUIPMENT - Page 1 of 8 BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply

More information

Section S7 - DC and AC auxiliary services installations

Section S7 - DC and AC auxiliary services installations S7/2 Section S7 - DC and AC auxiliary services installations Contents S7. Generalities...3 S7. Generalities...4 S7..1 Scope of work...4 S7..2 Dimensioning the auxiliary services equipment...4 S7.1 General

More information

Single-phase step voltage regulators

Single-phase step voltage regulators Voltage Regulators Catalog Data CA225001EN Supersedes 225-10 February 2014 COOPER POWER SERIES General Eaton's Cooper Power series VR-32 singlephase step voltage regulators are tap-changing autotransformers.

More information

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work Technical Data Sheet Uninterruptible Power Supply TM SG Series 100 &120 PurePulse TM SG Series 60 & 80 PurePulse SGSE_060-120_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino

More information

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. ANNEXURE XI (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I. Sr. No Technical Particulars Confirmation to be given by bidder (Please strike out which ever not applicable)

More information

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS

TECHNICAL SPECIFICATIONS FOR. 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Tender Paper TECHNICAL SPECIFICATIONS FOR 3/5/6/8/10 kva Single phase in/out Single or parallel UNINTERRUPTIBLE POWER SUPPLY SYSTEMS Contents 1. General 2. Tender submission requirements 3. Environmental

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

Illuminator Series CR NEMA 3R

Illuminator Series CR NEMA 3R Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the

More information

SPECIFICATIONS SRF

SPECIFICATIONS SRF 6033 Shawson Dr., Unit 29, Mississauga Ontario, Canada L5T 1H8 e-mail: info@soneil.com Ph.: 905 565 0360 Fax: 905 565 0352 Visit us on the web at www.soneil.com SPECIFICATIONS - 2416SRF Totally Automatic

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

BHAVNAGAR ENERGY CORPORATION LIMITED 2X250 MW CFBC LIGNITE BASED TPP

BHAVNAGAR ENERGY CORPORATION LIMITED 2X250 MW CFBC LIGNITE BASED TPP BHAVNAGAR ENERGY CORPORATION LIMITED 2X250 MW CFBC LIGNITE BASED TPP VOLUME - IIB TECHNICAL SPECIFICATION FOR SPECIFICATION NO.: PE-TS-356-510-E001 (REV. 00) BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR

More information

Section V DC Nickel Cadmium Alkaline BATTERY

Section V DC Nickel Cadmium Alkaline BATTERY Section - 7 TECHNICAL SPECIFICATION OF 110V DC Nickel Cadmium Alkaline BATTERY TECHNICAL SPECIFICATIONS & REQUIREMENTS OF 110V DC Nickel Cadmium Alkaline Battery 7. 1 GENERAL This section of the document

More information

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER Chassis Inverter power Rated input Rated output Battery pack Safeties Environment Others Input Voltage Lower Limit Input Voltage Upper Limit Power Input Current Output Voltage Output accuracy Transient

More information

Technical Data Sheets

Technical Data Sheets GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series

More information

Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications

Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications Ergon Energy Corporation Limited Technical Specification for 12kV and 24kV Current Limiting Fuse- Links for Overhead Applications ETS12-01-04 Specification ETS12-01-04 Ver 3 Contents 1. Purpose and Scope...

More information

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA 023 : 2006 CEB STANDARD 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA Specification for 12kV & 36kV LOAD BREAK SWITCHES CEB Standard 023 : 2006 CEYLON ELECTRICITY BOARD No. 50, Sir

More information

SPECIFICATIONS SR

SPECIFICATIONS SR 6033 Shawson Dr., Unit 29, Mississauga Ontario, Canada L5T 1H8 e-mail: info@soneil.com Ph.: 905 565 0360 Fax: 905 565 0352 Visit us on the web at www.soneil.com SPECIFICATIONS - 4812SR Totally Automatic

More information

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2 BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002

More information