1 TEST REORT AS/NZS AS/NZS Grid connection of energy systems via inverters Grid protection requirements Report reference number... : 13TH0287-AS/NZS 4777_0 Date of issue......: Total number of pages......: 15 Testing laboratory name... : Address... : Bureau Veritas Consumer roducts Services Germany GmbH Businesspark A Türkheim Germany Applicant's name... : Address... : SMA Solar Technology AG Sonnenallee 1, Niestetal Test specification Standard... : AS/NZS :2005 AS/NZS :2005 Certificate... : Certificate of suitability Test report form number.... : AS/NZS 4777 Master TRF... : Bureau Veritas Consumer roducts Services Germany GmbH Test item description... : Battery inverter Trademark... : Model / Type... : SI8.0H-11, SI6.0H-11 Ratings... : SI8.0H-11 SI6.0H-11 Input DC voltage range [V]... : Input DC current [A]... : range: 41V 63V nom. 48V In nom.: 136A Out nom.: 115A range: 41V 63V nom. 48V In nom.: 103A Out nom.: 90A Output AC voltage [V]... : 230V / 50Hz 230V / 50Hz Output AC current [A]... : In nom.: 26,1A Out nom.: 50A In nom.: 20A Out nom.: 50A Output power [VA]... : 6000W 4600W Copyright Bureau Veritas Consumer roducts Services Germany GmbH
2 age 2 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Testing Location... : Address... : Tested by (name and signature)... : Approved by (name and signature)... : Bureau Veritas Consumer roducts Services Germany GmbH Businesspark A96, Türkheim, Germany Alastair Schmid Georg Loritz Manufacturer s name... : SMA Solar Technology AG Factory address... : Sonnenallee Niestetal Germany Document History Date Internal reference Modification / Change / Status Revision Alastair Schmid Initial report was written 0 Supplementary information: Copyright Bureau Veritas Consumer roducts Services Germany GmbH
3 age 3 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Test items particulars Equipment mobility...: ermanent connection Operating condition...: Continuous Class of equipment...: Class I rotection against ingress of water...: I54 according to EN Mass of equipment [kg]...: 63 Test case verdicts Test case does not apply to the test object... : Test item does meet the requirement... : Test item does not meet the requirement... : N/A (ass) F(ail) Testing Date of receipt of test item... : Date(s) of performance of test... : until General remarks: The test result presented in this report relate only to the object(s) tested. This report must not be reproduced in part or in full without the written approval of the issuing testing laboratory. (see Annex #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma is used as the decimal separator. The unit was reviewed to AS/NZS :2005 Grid connection of energy systems via inverters, art 2: Inverter requirements AS/NZS :2005 Grid connection of energy systems via inverters, art 3: Grid protection requirements and the unit fulfils the requirements of the European EMC directive requirements. The EMC requirements of AS/NZS (flicker) refer to the same standards as the EMC directive; therefore the EMC report documents show the compliance. The grid trip tests were conducted as per clause B4, Appendix B of AS/NZS This Test Report consists of the following documents: 1. Test Results 2. Annex No. 1 EMC Test Report 3. Annex No. 2 ictures of the unit 4. Annex No. 3 Test equipment list Copyright Bureau Veritas Consumer roducts Services Germany GmbH
4 age 4 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Copy of marking plate: Copyright Bureau Veritas Consumer roducts Services Germany GmbH
5 age 5 of 15 Report No.: 13TH0287-AS/NZS 4777_0 General product information The battery inverter converts DC voltage from a battery into AC voltage. 1. The ambient temperature range is specified as -25 to +60 C 2. Dimension of EUT: 467 by 612 by 242 mm. 3. The model SI6.0H-11 which are part of this report provides the same construction and differ only in the power rating which is limited by software of the model SI8.0H-11 The inverter supplies AC loads in the grid from a battery or charges the battery with the energy provided by sources on the AC side. AC sources in the grid supply loads and are used by the battery inverter to recharge the battery. In order to increase the availability of the grid and reduce the battery capacity, the Sunny Island can use and control external energy sources (e.g. a generator) as an energy reserve. The Sunny Island supplies the loads with active power and reactive power. The battery system must be a TN or TT system. The Sunny Island does not support IT systems. Block diagram: The product with serial number ( ) was tested on: Software version: 2.55 All tests were performed on EUT SI 8.0H-11. Tests of the EUT SI 8.0H-11 not applicable for the model SI 6.0H- 11 were performed on the concerned model(s) and a statement is given at the relevant test. Copyright Bureau Veritas Consumer roducts Services Germany GmbH
6 age 6 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Connection logic of the SI8.0H/SI6.0H Copyright Bureau Veritas Consumer roducts Services Germany GmbH
7 age 7 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Copyright Bureau Veritas Consumer roducts Services Germany GmbH
8 age 8 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Copyright Bureau Veritas Consumer roducts Services Germany GmbH
9 age 9 of 15 Report No.: 13TH0287-AS/NZS 4777_0 Default interface protection settings according AS/NZS : arameter Max. clearance time Trip setting Over voltage 2s 230V +17% (270V) Under voltage 2s 230V -87% (200V) Over frequency 2s 50Hz +10% (55,0Hz) Under frequency 2s 50Hz -10% (45,0Hz) Reconnection time ermanent DC-injection Loss of main >=60s 0,5% of rated inverter output current Inverter shall detect and disconnect within 2s The stated currents and voltages are true r.m.s. -values. The voltages in this table are - phase-to-neutral in 230 V single phase systems and 230/400 V systems, - phase-to-phase in a multiphase 230 V system. Tolerances on trip values: - Voltage: +/- 5V of the set voltage value; - Frequency: +/- 0,1Hz of the set frequency value - Clearance time: less or equal clearance limit Copyright Bureau Veritas Consumer roducts Services Germany GmbH
10 age 10 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict 4 INVERTER REQUIREMENTS 4.1 General The inverter shall comply with the appropriate electrical safety requirements of AS/NZS NOTE: AS/NZS 3100 allows that if an individual Standard dealing with specific features of the design, construction and testing of any particular class or type of equipment is issued, it supersedes the general requirements of AS/NZS 3100 that are specifically dealt with in that individual Standard. 4.2 Compatibility with electrical installation The inverter shall have a.c voltage and frequency ratings compatible with AS NOTE: The nominal voltage at the point of supply is 230 V a.c. single phase line-to-neutral and 400 V a.c. three phase line-to-line with a tolerance of +10% -6% and a frequency of 50 Hz. 4.3 ower flow direction ower flow between the energy source and the grid may be in either direction. 4.4 (A1) ower factor The power factor of the inverter, considered as a load from the perspective of the grid, shall be in the range from 0.8 leading to 0.95 lagging for all output from 20% to 100% of rated output. These limits shall not apply if the inverter is approved by the relevant electricity distributor to control power factor outside this range for the purpose of providing voltage support. Compliance shall be determined by type testing in accordance with the power factor test described in Appendix A. NOTE: Lagging power factor is defined to be when reactive power flows from the grid to the inverter; that is, when the inverter acts as an inductive load from the perspective of the grid. 4.5 (B1) Harmonic currents The harmonic currents of the inverter shall not exceed the limits specified in Tables 1 and 2 and the total harmonic distortion (THD) (to the 50th harmonic) shall be less than 5%. Compliance shall be determined by type testing in accordance with the harmonic current limit test specified in Appendix B. NOTE: The inverter should not significantly radiate or sink frequencies used for ripple control by the local electrical distributor. The distributor should be consulted to determine which frequencies are used. 4.6 Voltage fluctuations and flicker The inverter shall conform to the voltage fluctuation and flicker limits as per AS/NZS for equipment rated less than or equal to 16 A per phase and AS/NZS for equipment rated greater than 16 A per phase. An applicable test report according to AS/NZS 3100 must be provided by the manufacturer. The inverter has voltage and frequency ratings compatible with AS (230V AC, 50Hz) In either direction See test report 4.4 See test report 4.5 See test report 4.6. Covered by EMC Report. Copyright Bureau Veritas Consumer roducts Services Germany GmbH
11 age 11 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict Compliance shall be determined by type testing in accordance with the appropriate Standard. 4.7 Impulse protection The inverter shall withstand a standard lightning impulse of 0.5 J, 5 kv with a 1.2/50 waveform. Compliance shall be determined by type testing in accordance with the impulse voltage withstand test of IEC Transient voltage limits When type tested in accordance with the transient voltage limit test described in Appendix C, the voltage-duration curve derived from measurements taken at the a.c. terminals of the inverter shall not exceed the limits. 4.9 Direct current injection In the case of a single-phase inverter, the d.c. output current of the inverter at the a.c. terminals shall not exceed 0.5% of its rated output current or 5 ma, whichever is the greater. In the case of a three-phase inverter, the d.c. output current of the inverter at the a.c. terminals, measured between any two phases or between any phase and neutral, shall not exceed 0.5% of its rated per-phase output current or 5 ma, whichever is the greater. If the inverter does not incorporate a mains frequency isolating transformer, it shall be type tested to ensure the d.c. output current at the a.c. terminals of the inverter is below the above limits at all power levels Data logging and communication devices Any electronic data logging or communications equipment incorporated in the inverter should comply with the appropriate requirements of AS/NZS articular attention is drawn to requirements for electrical insulation and creepage and clearance distances. See Test report 4.7 See Test report 4.8 See Test report 4.9 An applicable test report according to IEC60950 or an equivalent report must be provided. The provided internal devices in the inverter were tested according the AS3100 requirements Creepage distances and clearance distances for applicances and 8.4 High voltage (electrical strength). Copyright Bureau Veritas Consumer roducts Services Germany GmbH
12 age 12 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict 4 GENERAL AND SAFETY REQUIREMENTS 4.1 General Grid protection of the inverter energy system shall be provided by a grid protection device. This does not preclude the grid protection device being integral to the inverter, nor a single grid protection device being used to protect an inverter energy system comprising multiple inverters. Compliance with this Standard shall be determined by type testing the grid protection device on its own and, if necessary, in combination with an inverter. Compliance of this combination shall be conditional on their being used together in the same manner in which they have been type tested. Compliance of one combination of inverter and grid protection device does not preclude compliance of either device as part of a different combination. 4.2 Electrical Safety The grid protection device shall comply with appropriate electrical safety requirements of AS/NZS NOTE: AS/NZS 3100 allows that if an individual Standard dealing with specific features of the design, construction and testing of any particular class or type of equipment is issued, it shall supersede the general requirements of AS/NZS 3100 that are specifically dealt with in that individual Standard. 4.3 Connection to Low-Voltage distribution network The grid protection device shall be compatible with the low-voltage distribution network. NOTE: The nominal voltage is 230 V a.c. single phase lineto-neutral and 400 V a.c. three phase line-to-line with a tolerance of +10% -6% at a frequency of 50 Hz. 4.4 Voltage flicker The grid protection device shall conform to the voltage flicker limits specified in AS/NZS for equipment rated less than or equal to 16 A (a.c. current) or AS/NZS for equipment rated at greater than 16A (a.c. current). Compliance shall be determined by type testing in accordance with the appropriate Standard. 4.5 Impulse protection The grid protection device shall withstand a standard lightning impulse of 0.5 J, 5 kv with a 1.2/50 waveform. Compliance shall be determined by type testing in accordance with the impulse voltage withstand test of IEC Data logging and communication devices Any electronic data logging or communications equipment incorporated in the inverter should comply with the appropriate requirements of AS/NZS articular attention is drawn to The automatic disconnection device is integral part of the inverter. An applicable test report according to AS/NZS 3100 must be provided by the manufacturer. The inverter has voltage and frequency in accordance with AS (230V AC, 50Hz) See appended table 4.6 See enclosed EMC Report See Test report 4.7 An applicable test report according to IEC60950 or an equivalent report must be provided. Copyright Bureau Veritas Consumer roducts Services Germany GmbH
13 age 13 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict requirements for electrical insulation and creepage and clearance distances. The provided internal devices were tested according the AS3100 requirements Creepage distances and clearance distances for applicances and 8.4 High voltage (electrical strength). 5. GRID ROTECTION REQUIREMENTS 5.1 General The grid protection device shall operate (a) if supply from the grid is disrupted; or (b) when the grid goes outside preset parameters (e.g. under/over voltage, under/over frequency); or (c) to prevent islanding. Specific requirements are contained in Clauses 5.2 to Disconnect device The grid protection device shall incorporate a disconnection device which shall prevent power (both a.c. and d.c.) from the inverter energy system entering the grid when the disconnection device operates. NOTE: The disconnection device need not disconnect sensing circuits. The disconnection device shall incorporate an electromechanical switch if (a) there is no galvanic isolation between the energy source(s) and the grid; or (b) the inverter system continues to provide electrical power to any portion of the electrical installation (i.e. it operates as an uninterruptible power supply (US) system) in the event of the disruption of the grid supply. NOTES: 1 Galvanic isolation can be achieved by using either a two winding high-frequency transformer or a two winding mains frequency transformer. 2 Galvanic isolation is not required on sensing circuits. Any disconnection device intended for use with a US system shall only break the active conductor(s). The disconnection device may incorporate semiconductor devices if galvanic isolation exists between the energy source(s) and the grid and the system does not operate as an uninterruptible power supply system. 5.3 Voltage and frequency limits (passive anti islanding protection) The grid protection device shall incorporate passive anti-island protection in the form of under- and over-voltage and under- and over- The device includes an automatic disconnecting facility for renewable power generator installations (under/ over voltage/ under/ over frequency and anti islanding), see test Report The unit provides galvanic separation. The unit is switched off redundant by the high power bridge of the inverter and the relays in line and neutral. See enclosed report 5.3 Copyright Bureau Veritas Consumer roducts Services Germany GmbH
14 age 14 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict frequency protection. If the voltage goes outside the range V min to V max or its frequency goes outside the range f min to f max, the disconnection device (see Clause 5.2) shall operate within 2 s, where (a) V min shall lie in the range V for a single-phase system or V for a threephase system; (b) V max shall lie in the range V for a single-phase system or V for a threephase system; (c) f min shall lie in the range Hz; and (d) f max shall lie in the range Hz. The limits V max, V min, f max and f min may be either preset or programmable. The values V max, V min, f max and f min may be negotiated with the relevant electricity distributor. The settings of the grid protection device shall not exceed the capability of the inverter. 5.4 Limits for sustained operation The introduction of limits for sustained operation is under consideration. NOTE: See Appendix A for further information about the proposal. 5.5 Active anti islanding protection The grid protection device shall incorporate at least one method of active anti-islanding protection. Examples of such methods include shifting the frequency of the inverter away from nominal conditions in the absence of a reference frequency (frequency shift), allowing the frequency of the inverter to be inherently unstable in the absence of a reference frequency (frequency instability), periodically varying the output power of the inverter (power variation) and monitoring for sudden changes in the impedance of the grid by periodically injecting a current pulse (current injection). NOTE: Active anti-islanding protection is required in addition to the passive anti-islanding protection described in Clause 5.3 above to prevent the situation where islanding may occur because multiple inverters provide a frequency and voltage reference for one another. The active anti-islanding protection system shall operate the disconnection device (see Clause 5.2) within 2 s of disruption to the power supply from the grid. 5.6 Reconnection procedure Only after all the following conditions have been met shall the disconnection device operate to reconnect the inverter to the electricity distribution network (a) the voltage of the electricity distribution network has been maintained within the range Informative See enclosed report 5.5 The unit provides monitoring of the voltage, frequency and synchronisation. If one of these conditions is not met, then the unit is not switching on. Copyright Bureau Veritas Consumer roducts Services Germany GmbH
15 age 15 of 15 Report No.: 13TH0287-AS/NZS 4777_0 AS/NZS Clause Requirement Test Result - Remark Verdict V min V max for at least 1 m, where V min and V max are as defined in Clause 5.3; and (b) the frequency of the electricity distribution network has been maintained within the range f min f max for at least 1 m, where f min and f max are as defined in Clause 5.3; and (c) the inverter energy system and the electricity distribution network are synchronized and inphase with each other. 5.7 Security of protection settings The internal settings of the grid protection device shall be secured against inadvertent or unauthorized tampering. Changes to the internal settings shall require use of a tool and special instructions not provided to unauthorized personnel. NOTE: Special interface devices and passwords are regarded as tools. 5.8 Compliance with grid protection requirements Compliance with the anti-islanding protection requirements shall be determined by type testing in accordance with the anti-islanding protection tests described in Appendix B. Settings only available with password for the service personal. Appendix B4 noticed Copyright Bureau Veritas Consumer roducts Services Germany GmbH
Certificate of Conformity self-generation unit
Seite 1 von 7 Certificate of Conformity self-generation unit Manufacturer / applicant: SMA Solar Technology AG Sonnenallee1 34266 Niestetal Germany Type of power generation unit: Active power (nominal
More informationTEST REPORT DIN V VDE V
Test Report issued under the responsibility of: TEST REORT DIN V VDE V 0126-1-1 Report Number....: EFSH16041203-IE-01-L12 Date of issue...: 2016-11-28 Total number of pages... 25 pages Testing Laboratory...
More informationTEST REPORT DIN V VDE V
Test Report issued under the responsibility of: TEST REORT DIN V VDE V 0126-1-1 Report Number....: EFSH16041203-IE-01-L21 Date of issue...: 2016-11-28 Total number of pages... 26 pages Testing Laboratory...
More informationCertificate of Conformity self-generation unit
Seite 1 von 7 Certificate of Conformity self-generation unit Manufacturer / applicant: Type of power generation unit: SMA Solar Technology AG Sonnenallee 1 34266 Niestetal Germany Grid-tied photovoltaic
More informationCertificate of Conformity self-generation unit
Seite 1 von 7 Certificate of Conformity self-generation unit Manufacturer / applicant: Type of power generation unit: SMA Solar Technology AG Sonnenallee 1 34266 Niestetal Germany Grid-tied photovoltaic
More informationCertificate of Conformity self-generation unit
Seite 1 von 7 Certificate of Conformity self-generation unit Manufacturer / applicant: Type of power generation unit: SMA Solar Technology AG Sonnenallee 1 34266 Niestetal Germany Grid-tied photovoltaic
More informationGRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS
GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS Prof. Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology Bombay OUTLINE Intoduction Grid
More informationZHEJIANG MAXGE ELECTRIC TECHNOLOGY CO., LTD. Address... :
Test Report issued under the responsibility of: TEST REORT IEC 60898-1 Circuit-breakers for over current protection for household and similar installations art 1 - Circuit-breakers for a.c. operation Report
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More informationSA Power Networks Commissioning Witnessing Checklist
SA Power Networks Commissioning Witnessing Checklist CUSTOMER NAME: SOLAR PV APPROVED CAPACITY: BATTERY APPROVED CAPACITY: kw (AC) kw (AC) OPERATING PHILOSOPHY: MAXIMUM EXPORT: Non-Export/Export kw (AC)
More informationTesting Laboratory...: TÜV Rheinland Taiwan Ltd., Taichung Laboratory. Address...: 10F, No.219, Min Chuan Road, Taichung 403, Taiwan.
11009797 002 age 1 of 11 TEST REORT Flat non-rewirable two-pole plugs, 2.5 A 250 V, with cord, for the connection of class II - equipment for household and similar purposes Report Reference No....: 11009797
More informationInstallation Couplers intended for permanent connection in fixed installation
Test Report issued under the responsibility of: TEST REORT Installation Couplers intended for permanent connection in fixed installation Report Reference No....: 2167493.50-DCC Date of issue...: 2013-11-26
More informationPage 2 of 6. Summary of testing The clause 17 and clause 29 are considered and check on the appliance.
12012453 003 age 2 of 6 Summary of testing The clause 17 and clause 29 are considered and check on the appliance. Test items particulars Serial umber... : rototype samples Additional information... : (.A.)...
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 400 & 500 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 60 80 100 120 kva PurePulse 400 Vac CE Series 1 SG-CE Series 100-120 kva PurePulse SG-CE Series
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series 10 20 30 40 kva 400 Vac CE Series 5 GE Consumer & Industrial SA General Electric Company CH
More informationLVD TEST REPORT EN : 2006+A12: MEASUREMENT AND TEST REPORT For. Ingtron Enterprise Co., Ltd.
LVD TEST REORT EN 60950-1: 2006+A12: 2011 MEASUREMENT AND TEST REORT For Ingtron Enterprise Co., Ltd. No. 211-1, Qingfeng Road, Qingxi Town, Dongguan City, Guangdong, China Model: reference page 2 Feb.
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationTEST REPORT IEC Low-voltage switchgear and control gear Part 7-4: Ancillary equipment PCB terminal blocks for copper conductors
r Test Report issued under the responsibility of: TEST REORT Low-voltage switchgear and control gear art 7-4: Ancillary equipment CB terminal blocks for copper s Report Number.... : 2169331.75 Date of
More informationNet Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland
More informationNet Metering Interconnection Requirements
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TM SG Series 100 &120 PurePulse TM SG Series 60 & 80 PurePulse SGSE_060-120_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company imagination at work QUITO: Elia Liut N45-26 y Edmundo Chiriboga Telf:
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TLES_040-120_S1_UPS_GE_Floor_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply SGSE_400-500_S3_UPS_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91
More informationNet +Plus Connection Code
Net +Plus Connection Code LANKA ELECTRICITY COMPANY (PRIVATE) LIMITED 1.0 BACKGROUND The existing Net Metering Concept launched in the year 2010 noticed an exponential growth in the recent year and at
More informationTechnical Data Sheet. Uninterruptible Power Supply. Digital Energy. imagination at work
Digital Energy Technical Data Sheet Uninterruptible Power Supply LPS33_010-020_S6_UPS floor_ge_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply SGSE_010-040_S1_UPS_GE_01 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More informationTechnical Requirements for Renewable Energy Power System
Hotline: 2843 3228 Email address: RE@hkelectric.com Issued on 20 Nov 2018 1. Introduction 1.1. This document aims to provide the technical requirements for renewable energy power system (the REPS) connected
More informationCobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications
Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System
More informationREFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS
TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3
More informationAnnex I Tested by (name + signature)...: Approved by (name + signature)...: Date of issue... : 22/11/2012. TUV RHEINLAND ITALIA S.r.l.
TEST REORT Rotating electrical machines art 5: Degrees of protection provided by the integral design of rotating electrical machines (I code) Classification Report Reference No....: 28105442 002 Annex
More information< > Page 2 of 84
age 2 of 84 articulars: test item vs. test requirements Equipment mobility...: Building-in Operating condition...: Continuous Mains supply tolerance (%)...: -10%, +10% Tested for IT power systems...: Yes
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationGUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM
GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19 Table of Contents 1.0 SCOPE...4 2.0 PURPOSE...4 3.0 LIMITATIONS...5 4.0 GENERAL INTERCONNECTION
More informationRULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS
RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 1. PURPOSE This document describes the technical requirements for connecting Renewable Generation Systems ( RGS ) up to 150kW, or larger if approved
More informationTechnical Data Sheets
GE Consumer & Industrial Technical Data Sheets Digital Energy Uninterruptible Power Supply SG-CE Series 160 200 250 300 kva PurePulse TM 400 Vac CE Series 1 Date of issue: 15.02.2007 SGSE160-200S1UPS01
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More informationTANZANIA BUREAU OF STANDARDS
EDC 5 (5235) P3 Mini-Grid Systems DRAFT TANZANIA STANDARD (Draft for comments only) Part 2: Application of Inverters TANZANIA BUREAU OF STANDARDS TBS 2017 First Edition 2017 T able of content 1 2 3 4 5
More informationDycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD
Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain
More informationSmart connections. Certificates. PIKO-Inverter
EN Smart connections. Certificates PIKO-Inverter 3.0 3.6 4.2 5.5 8.3 10.1 EU Declaration of Conformity The company KOSTAL Solar Electric GmbH Hanferstraße 6 79108 Freiburg i. Br., Deutschland hereby declares
More informationENEC LICENCE. Licence No. ENEC Page 1/3 Date of Issue
ENEC LICENCE Licence No. ENEC-01360 Page 1/3 Date of Issue 2016-03-04 Licence Holder WAGO KONTAKTTECHNIK GMBH & CO KG HANSASTRASSE 27 MINDEN, 32423 Germany Production site WAGO CONTACT SA ROUTE DE L'INDUSTRIE
More informationTEST REPORT. Low Voltage Directive 2006/95/EC. Report No.: STDGZ L
TEST REORT Low Voltage Directive 2006/95/EC Report No.: STDGZ-01721-L 8th Floor, Block B,No.11 Caipin Road,GZ Science City,Tianhe, Guangzhou 510663, China TEST REORT IEC/EN 62040-1 Uninterruptible power
More informationTEST REPORT IEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REPORT IEC 60950-1 Information technology equipment Safety Part 1: General requirements Report Number.... : 31282706.003 Date of issue... : 22 nd March,
More informationTEST REPORT IEC Connectors Safety requirements and tests
IECEE OD-2020-F1:2017 IEC 2017 Ed.1.0 TRF Template 2017-05-17 Test Report issued under the responsibility of: TEST REORT Connectors Safety requirements and tests Report Number... : 249955-TL6-1 Date of
More informationTest Report issued under the responsibility of: Report Number... : CB131104C Date of issue... : Total number of pages...
Test Report issued under the responsibility of: TEST REORT Secondary cells and batteries containing alkaline or other non-acid electrolytes Safety requirements for portable sealed secondary cells, and
More informationFortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting
More informationTEST REPORT IEC Connectors Safety requirements and tests
IECEE OD-2020-F1:2017 IEC 2017 Ed.1.0 TRF Template 2017-05-17 Test Report issued under the responsibility of: TEST REORT Connectors Safety requirements and tests Report Number... : 250150-TL6-1 Date of
More informationTechnical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work
Technical Data Sheet Uninterruptible Power Supply TM SG Series 200-250 - 300 PurePulse CE S3 TM SG Series 160 PurePulse CE S3 GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno)
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,
More informationTest Report issued under the responsibility of: Report Reference No... : AS9-7 Date of issue... : Total number of pages...
Test Report issued under the responsibility of: TEST REORT EHA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat umps
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More information& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL
72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com
More informationPage 2 of 23 UNT150420C11
Page 2 of 23 UNT150420C11 United Nations, Recommendations on the Transport of Dangerous Goods, Manual of Test and Criteria (Rev. 5 th, Amendment 2), Section 38.3 Report Reference No.... : Compiled by...
More informationIlluminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System
Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical
More informationE-15 Uninterruptible Power Systems (UPS)
Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,
More informationPage 2 of 39 Report No. CTI PA Testing location:
age 2 of 39 Report No. CTI A 2841-2 Tests performed (name of test and test clause): according to :2009: 5 - Interface characteristics, 6 Information, 7 - Service conditions, 10.2.3.3 - Verification of
More informationGuideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society
Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More informationDycon D2430 EN54-4 Fire Alarm Power Supply Series
Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 10 20 30 kva 400 VAC CE Series 4 SGT4000_010-020-030 GE_01 Manufactured by: GE
More informationTEST REPORT IEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REPORT IEC 60950-1 Information technology equipment Safety Part 1: General requirements Report Number.... : 207809-CI3-3 CB DE1-9640/A2 Date of issue...
More informationPage 3 of 34 Report No Part I
www.tuv.com age 3 of 34 Report No. 14717090 001 art I List of Attachments (including a total number of pages in each attachment): Besides of the tests according to : 2008 +A1 +A2, the following tests are
More informationIlluminator Series CR NEMA 3R
Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the
More informationCOVER PAGE FOR TEST REPORT
Issue Date: 2005-08-06 Page 1 of 1 Report Reference # E137006-A6-CB-1 COVER PAGE FOR TEST REPORT Test Item Description: Model/Type Reference: Rating(s): Standards: Applicant Name and Address: Factory Location(s):
More informationGuideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society
Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection
More informationTEST REPORT IEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REPORT IEC 60950-1 Information technology equipment Safety Part 1: General requirements Report Number.... : 1510050STO-001 Date of issue... : 26 October
More informationTEST REPORT IEC Part 1: General requirements for basic safety and essential performance
jhćmtc Test Report issued under the responsibility of: TEST REPORT IEC 60601-1 Part 1: General requirements for basic safety and essential performance Report Number.... : T223-0128/16 Date of issue...
More informationHarmonic current emissions as EN Harmonic Test Value in Amps % of fund Limit value in Amps
POWER QUALITY Harmonic current emissions as EN 61000-3-2 Harmonic Test Value in Amps % of fund Limit value in Amps 2 0.014 0.143 1.080 3 0.106 1.108 2.300 4 0.003 0.036 0.430 5 0.044 0.463 1.140 6 0.008
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationBANGALORE ELECTRICITY SUPPLY COMPANY LIMITED
GUIDELINES FOR EMPANELMENT OF GRID TIED INVERTER MANUFACTURERS FOR IMPLEMENTATION OF SRTPV PROGRAM IN BESCOM. I. NEW EMPANELMENT 1. The grid tied inverter manufacturer shall register their application
More informationDraft Guideline for the connection of smallscale inverter based distributed generation. EEA Asset Management Forum 22 June 2016 Dr Richard Strahan
Draft Guideline for the connection of smallscale inverter based distributed generation EEA Asset Management Forum 22 June 2016 Dr Richard Strahan Outline 1. Introduction and Issues to Address 2. Methodology
More informationTechnical Standard - TS 129. Small Inverter Energy Systems (IES) - Capacity not exceeding 30kW. SA Power Networks. Published: November 2017
TS 130: Inverter Energy Systems (IES) - capacity up to or equal to 200 kw Technical Standard - TS 129 Small Inverter Energy Systems (IES) - Capacity not exceeding 30kW Published: November 2017 SA Power
More informationGuideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society
Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and
More informationIndustrial PFC UPS System
Based on Statron s leading A.T.I.S. (Advanced Technology Industrial System) platform, the S3000 range is a true-industrial UPS system using the latest Power Factor Corrected (PFC) IGBT rectifier technology.
More informationTechnical Data Sheets
GE Digital Energy Power Quality Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33U Series / 10 20 30 40 50 60 kva 208 VAC UL Series 1 Date of issue: 11/05/2008 LPS33U_030-040_S1 GE_01
More informationGuidelines for connection of generators:
Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...
More informationEU RO Mutual Recognition Technical Requirements
1. PRODUCT DESCRIPTION... 1 2. DESIGN EVALUATION... 2 3. PRODUCTION REQUIREMENTS... 6 4. MARKING REQUIREMENTS... 6 5. TYPE APPROVAL CERTIFICATE CONTENT... 7 6. APPROVAL DATE AND REVISION NUMBER... 7 7.
More information10 20KVA 3Ph/1Ph KVA 3Ph / 3Ph
VEGA INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY 10 20KVA 3Ph/1Ph 10 120KVA 3Ph / 3Ph - 6 pulse SCR rectifier - IGBT inverter - Power output transformer - Low and stable ripple on battery for the highest battery
More informationMGE TM Galaxy TM 6000 : Specification guide. Single UPS, three-phase, 250 to 600 kva
MGE TM Galaxy TM 6000 : Specification guide Single UPS, three-phase, 250 to 600 kva Contents 1 - UPS definition... C-3 1.1 - Purpose... C-3 1.2 - Brief description... C-3 2 - Operating principle... C-3
More informationSolarMax S series (United Kingdom) Maximising solar plant yields can be so easy.
SolarMax S series (United Kingdom) Maximising solar plant yields can be so easy. The convincing solution. We have been developing and producing transformerless inverters for over 20 years. Our engineers
More informationElectric Networks/Ina Lehto Updated Original 12/2011
1 TECHNICAL APPENDIX 2 TO THE GUIDELINES CONNECTING AN ELECTRICITY GENERATION INSTALLATION TO THE DISTRIBUTION NETWORK CONNECTING AN INSTALLATION WITH A NOMINAL RATED CAPACITY OF OVER 100 These instructions
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationTechnical specifications
KINGDOM OF SAUDI ARABIA THE SAUDI FUND FOR DEVELOPMENT ( SFD) ITB -207-7 Technical specifications Project name: Reconstruction, Furniture and Equipping of Three Schools Photovoltaic Solar System for Holly
More informationTEST REPORT IEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REPORT IEC 60950-1 Information technology equipment Safety Part 1: General requirements Report Number.... : 1510053STO-001 Date of issue... : 2 November
More informationSola/Hevi-Duty S3K Series Mini-Tower UPS
Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical
More informationL7486R Cromwell Word Distribution 8 Inch Bench Grinder KOBE GB 200 December 2009 MD
age 1 of 15 L7486R Cromwell Word Distribution 8 Inch Bench Grinder KOBE GB 200 December 2009 MD age 2 of 15 SUMMARY TEST REORT BS EN 61029-1: 2000, with BS EN 61029-2-4: 2003 Safety of transportable motor-operated
More informationTEST REPORT IEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REPORT IEC 60950-1 Information technology equipment Safety Part 1: General requirements Report Number.... : 221868-CI3-2 CB DE1-56824 Date of issue...
More informationSunny Tripower. Can do everything that we can
Sunny Tripower Can do everything that we can New Features Optiflex Flexible Plant Design Optiprotect Electronic String Fuse Optiprotect Integrable Type II Overvoltage Protection Optiprotect Intelligent
More informationSummary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System
Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical
More informationAPPLICATION FOR CONSTRUCTION PRODUCTS DIRECTIVE. On Behalf of Shenzhen Changen Industry Co.,Ltd. 2 interactive pins 5 color cylinder.
ALICATION FOR CONSTRUCTION RODUCTS DIRECTIVE On Behalf of Shenzhen Changen Industry Co.,Ltd. 2 interactive pins 5 color cylinder Model No: 385T repared For : repared By : Shenzhen Changen Industry Co.,Ltd.
More informationDART Charger Product Description, Information and Specification
g Digital Energy DART Charger Product Description, Information and Specification Document Number : PRPI-029 Version : 1.00 Revision : 2 Date : 03.02.11 Classification: NOTICE OF COPYRIGHT & PROPRIETARY
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs
More informationIEC Information technology equipment Safety Part 1: General requirements
Test Report issued under the responsibility of: TEST REORT IEC 60950-1 Information technology equipment Safety art 1: General requirements Report Number....: CB110708E01 001 Date of issue...: August 10,
More informationStandard specification Galaxy PWi, three-phase, 10 to 200 kva
Galaxy PWi, three-phase, 10 to 200 kva Contents 1 - UPS definition... 2 1.1 - Purpose... 2 1.2 - Brief description... 2 2 - Operating principle... 2 2.1 - Normal operation... 2 2.2 - Operation on battery
More informationApplicant s address. Identification: (Model No.) Serial No.: Lab Name Lab address
Test Report No.: xx001 Page 1 of xx Issue Date: DD/MM/YYYY Manufacturer: Applicant s Name Applicant s address Test item: Set Top Box Identification: (Model No.) Serial No.: Receipt No.: Date of receipt:
More information