Case Study Balancing a System

Size: px
Start display at page:

Download "Case Study Balancing a System"

Transcription

1 Case Study Balancing a System Piping systems providing heat transfer fluid to a variety of loads can present their own special problems. Since there are multiple paths for the fluid to travel, the system naturally balances so the pressure drop around each loop is equal. It is highly unlikely that when all of the valves are fully open, the flow rate will equal the design flow rate needed to provide the necessary heating or cooling to the various loads. As a result the system must be balanced using flow control valves or orifices. If the heating or cooling system is not balanced, some loads will get excessive flow and other loads will be starved for flow. This results in the system not operating as designed. Anytime a looped heat transfer system is built or expanded, the system should be balanced to insure each load gets its required flow rate. This tedious step can take a crew of operators many days to complete. In this case study, we will see how PIPE-FLO can be used to determine the position of a valve to balance the system, cutting days off the balancing process. In addition, we will see how balancing the system can provide extra system capacity along with minimizing the system's pumping cost. The Piping System In looking at the FLO-Sheet you can see the system consists of an open loop cooling system, which takes suction from the cooling tower sump, through one of two circulating water pumps, then to three buildings. Each building has four cooling loads

2 requiring varying capacity. After exiting the heat exchangers, the fluid goes through a throttle valve, then a common return line to the spray header of the cooling tower. Here the heat is released to the atmosphere. A system expansion was recently completed at which time the loads in Building 123 were added to the system. The circulating water pumps CCW-15 and CCW-16 were sized so one pump could supply the entire cooling loads including the Building 123 expansion. After 6 months of operation with Building 123 online, the circulating water pump CCW-15 tripped due to excessive electrical load. To correct this problem, operations started running both cooling water pumps continually. Since then, there have been no problems with either pump tripping on overload. The plant's engineer at this site was instructed to add a third circulating water pump as a standby to improve the system reliability. Before adding the third pump, the plant engineer wanted to get a better understanding why the existing pump arrangement would not meet the loads as designed. How the System Operates The first step is to determine how the system is currently operating and why the system will no longer work with a single pump. It can be seen that the flow rate through the pump CCW-15 exceeds the pump's run out of 2,978 gpm, which is why the motor for the single pump tripped on overload.

3 Next, see how the system operates with both pumps running: In reviewing the results, with two pumps running neither pump is in a run out condition. That explains why the pumps no longer trip on overload with both pumps running. Notice, however that many of the components are red, indicating the flow rate through those components exceeds the manufacturer's limits. This could cause a problem over time due to high fluid velocities in the heat exchanger tubes. After a trip to the field, the plant engineer noticed all the throttle valves were wide open. After further investigation, it was discovered that the system was never rebalanced after Building 123 was added to the system. When the new building went online, the flow rates to the loads in the two existing buildings dropped. The operators opened the valves in these two buildings to increase the flow rate. As each throttle valve was opened, the flow to the adjacent valves decreased. Before long, the operators opened all the throttle valves in the system to make sure all loads received their required capacity. Before sizing the third pump, the plant engineer decided to use the computer model to see if a balanced system was possible using a single pump, as originally designed. Calculating the Balanced System To adjust the flow rates to the design values, balancing valves in each loop are throttled to increase the differential pressure across the loop, thereby lowering the flow rate in that loop. This also causes the flow rate in the adjoining loops to

4 increase, resulting in increased differential pressure in these. To balance a system, all the valves must be throttled and the system results checked multiple times until the flow rates through each loop are at the design value. This is a tedious and timeconsuming process when done by trial and error in the field. To accomplish this in PIPE-FLO, FCV's are inserted into each loop and set to the design flow rate. The program then calculates the differential pressure across each throttle valve needed to balance the flow for each loop. The table below shows the design flow rates required for each load in the system Load Design Flow Rate (gpm) Load Design Flow Rate (gpm) HX HX HX HX HX HX HX HX HX HX HX HX Regulating the flow rate through the pipelines Now we will set each of the FCVs to the specified flow rate.

5 PIPE-FLO calculates the differential pressure needed to limit the flow rate through the FCVs to the set values. When the system is balanced, the total flow rate through the system is 2,655 US gpm, which is less than the run out flow rate for the pump. As you can see, the system can run with only one CCW pump in operation. This eliminates the need to purchase and install a third standby pump. By having only one pump operating, we also save on annual pumping costs. Finally the system only requires 2655 gpm, which is well within a single pump's operating curve, giving the plant future system capacity as well. Balancing the System The final step in balancing the system is to insert restrictions in each pipeline. These restrictions provide the differential pressure needed in each loop to balance the system as calculated by PIPE-FLO. The FCV restriction calculated by PIPE-FLO can be supplied by: A modulating control valve controlled by a flow control circuit A balancing orifice The method chosen is based on the degree of control desired. Regardless of the method, PIPE-FLO can meet your needs.

6 For a modulating valve, you can have PIPE-FLO select a control valve to be placed into the system. You can then insert the control valve and PIPE-FLO will modulate the valve and display the valve position based on the set point. For a balancing orifice, you can insert an orifice instead of a FCV.You can then use the flow meter sizing feature of PIPE-FLO. This calculates the size of a balancing orifice needed to provide the required pressure drop at a certain flow.

BERMAD Waterworks. Pressure Relief/Sustaining Valve. Model: WW Series. Features and Benefits. Major Additional Features

BERMAD Waterworks. Pressure Relief/Sustaining Valve. Model: WW Series. Features and Benefits. Major Additional Features Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive

More information

Module 6. Actuators. Version 2 EE IIT, Kharagpur 1

Module 6. Actuators. Version 2 EE IIT, Kharagpur 1 Module 6 Actuators Version 2 EE IIT, Kharagpur 1 Lesson 25 Control Valves Version 2 EE IIT, Kharagpur 2 Instructional Objectives At the end of this lesson, the student should be able to: Explain the basic

More information

Modeling a Sprinkler System or a System With Nozzles

Modeling a Sprinkler System or a System With Nozzles This article is also available for viewing online at http://kb.eng-software.com/questions/270/ Modeling a Sprinkler System or a System With Nozzles There are several ways to model a sprinkler system or

More information

Generator, Unit Hydrogen, Seal Oil, Stator Coolant, Demin Water Plant Operations Training Huntly Power Station: Units 1-4 Assessment ID: 8014, 8012, 8009, 8015, 8016 NZQA Unit Standard: 17413 Assessment

More information

Definitions of Technical Terms

Definitions of Technical Terms Definitions of Technical Terms ABSOLUTE A measure having as it s zero point of base the complete absence of the entity being measured. ABSOLUTE PRESSURE A pressure scale with zero point at a perfect vacuum.

More information

Assessing Your Sprinkler Irrigation System

Assessing Your Sprinkler Irrigation System Assessing Your Sprinkler Irrigation System Andrew Petersen, P. Ag Regional Resource Specialist B.C. Ministry of Agriculture Outline 1. Water Supply 2. System Sketch 3. Sprinkler spacing 4. Nozzle size

More information

(770) Turning Parts Changers Into TROUBLESHOOTERS!

(770) Turning Parts Changers Into TROUBLESHOOTERS! Hydraulic Consulting, Inc. Turning Parts Changers Into TROUBLESHOOTERS! This e-book manual is your customized troubleshooting manual in Adobe Acrobat Portable Document File (PDF) format. It requires the

More information

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS INTRODUCTION The two most common methods of measuring the volume of petroleum liquids are tank gauging and liquid metering. The problems associated with

More information

Fact File 59 Extinguishing systems

Fact File 59 Extinguishing systems Fact File 59 Extinguishing systems Foam Inductors: Guidelines on their selection, use and maintenance Foam Inductors: Guidelines on their selection, use and maintenance INTRODUCTION... 3 HOW INDUCTORS

More information

LogSplitterPlans.Com

LogSplitterPlans.Com Hydraulic Pump Basics LogSplitterPlans.Com Hydraulic Pump Purpose : Provide the Flow needed to transmit power from a prime mover to a hydraulic actuator. Hydraulic Pump Basics Types of Hydraulic Pumps

More information

SERIES Waterman* DESCRIPTION FLOW PRESSURE PAGE NO.

SERIES Waterman* DESCRIPTION FLOW PRESSURE PAGE NO. Contents SERIES Waterman* DESCRIPTION FLOW PRESSURE PAGE NO. NVH081...12CNVH1...Needle Valve...10 GPM... 5500 PSI... FC5-FC6 NVH101...15CNVH1...Needle Valve...16 GPM... 5500 PSI... FC7-FC8 NV162...21CNV2...Needle

More information

Section 6.1. Implement Circuit - General System. General: TF Configuration TB Configurations Implement Control Valve:

Section 6.1. Implement Circuit - General System. General: TF Configuration TB Configurations Implement Control Valve: Section 6.1 Implement Circuit - General System General: TF Configuration... 6.1.3 TB Configurations... 6.1.5 Implement Pump Breakdown... 6.1.6 Operational Description: General... 6.1.7 Compensator Control...

More information

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31 LACT MEASUREMENT Prepared By: Ken A. Steward. P.E. Linco-Electromatic, Inc. 4580 West Wall Street Midland, Texas 79703 The Operation of L.A.C.T. Units The simplest approach to the understanding of the

More information

Fire Water Utility 2002 Training Manual Raw Water Storage Area

Fire Water Utility 2002 Training Manual Raw Water Storage Area Effective: 10/21/11 Page 1 of 17 Rev. by J. Shively Fire Water Utility 2002 Training Manual Raw Water Storage Area Document Revision Change Table Revision Number Revision Description Revised By Revision

More information

Troubleshooting Pumps in a System

Troubleshooting Pumps in a System Troubleshooting Pumps in a System First of Two Parts by Ray Hardee In the last three columns ("Troubleshooting Piping Systems" in the September, October and November 2015 issues of Pumps & Systems, read

More information

FC SERIES FLUID COOLERS THE LEADER IN THE INDUSTRY FOR ALL YOUR HVAC NEEDS. Replacement Coils Heat Exchangers Fan Coils

FC SERIES FLUID COOLERS THE LEADER IN THE INDUSTRY FOR ALL YOUR HVAC NEEDS. Replacement Coils Heat Exchangers Fan Coils FC SERIES FLUID COOLERS THE LEADER IN THE INDUSTRY FOR ALL YOUR HVAC NEEDS. Replacement Coils Heat Exchangers Fan Coils Phone: 484-498-8660 Fax: 484-631-0558 www.capitalcoil.com sales@capitalcoil.com FAN

More information

CONTROL BALL VALVES LOW NOISE HIGH CAPACITY ROTARY CONTROL VALVE CBV-8600

CONTROL BALL VALVES LOW NOISE HIGH CAPACITY ROTARY CONTROL VALVE CBV-8600 CONTROL BALL VALVES LOW NOISE HIGH CAPACITY ROTARY CONTROL VALVE CBV-8600 The CBV-8600 design is the solution to applications where increased capacity and large control range is needed, and where noise,

More information

The application rate is automatically maintained even with variations in truck speed at any spray width.

The application rate is automatically maintained even with variations in truck speed at any spray width. Improved control and less maintenance. Electronic asphalt pump speed control provides superior dependability and more precise control than manual systems. The application rate is automatically maintained

More information

Hydraulic Master Cylinders

Hydraulic Master Cylinders Hydraulic Master Cylinders flange mount and side mount, straight-bore and two-stage cylinders Hydraulic Cylinders for Mobile and Industrial Applications Why choose MICO? MICO, Incorporated designs, manufactures

More information

BERMAD Waterworks. Booster Pump Control Valve Active Check Valve. 700 Series. Model 740. Features and Benefits. Major Additional Features

BERMAD Waterworks. Booster Pump Control Valve Active Check Valve. 700 Series. Model 740. Features and Benefits. Major Additional Features Booster Pump Control Valve Active Check Valve Isolates system from the effects of pump starts and stops for: Solitary single speed pumps Battery of single speed pumps (add & switch) Battery of variable

More information

The Discussion of this exercise covers the following points: Centrifugal pumps in series Centrifugal pumps in parallel. Centrifugal pumps in series

The Discussion of this exercise covers the following points: Centrifugal pumps in series Centrifugal pumps in parallel. Centrifugal pumps in series Exercise 2-4 Centrifugal Pumps in Series and in Parallel (Optional Exercise) EXERCISE OBJECTIVE In this exercise, you will observe the effects that connecting two centrifugal pumps in series or parallel

More information

STaSIS / Öhlins Motor Sport Suspension

STaSIS / Öhlins Motor Sport Suspension STaSIS / Öhlins Motor Sport Suspension Damper Model Information Öhlins LMJ Series Damper: Öhlins LMJ stock car shock absorbers are based on the race proven Öhlins 46HRC. A shock absorber featuring a large

More information

IC ENGINE(4 STROKE) G.H.R.I.E&M JALGAON. Sec.(Mech) Sec.(Mech) Sec.(Mech) Sec.(Mech) Mehta chirag Shah sagar Patel jainish talele amit

IC ENGINE(4 STROKE) G.H.R.I.E&M JALGAON. Sec.(Mech) Sec.(Mech) Sec.(Mech) Sec.(Mech) Mehta chirag Shah sagar Patel jainish talele amit IC ENGINE(4 STROKE) G.H.R.I.E&M JALGAON Mehta chirag Shah sagar Patel jainish talele amit Sec.(Mech) Sec.(Mech) Sec.(Mech) Sec.(Mech) 9096297071 9028248697 9028913994 8087260063 1 Abstract The four stroke,

More information

USE OF MAZZEI INJECTORS IN PRESSURIZED SPRINKLER APPLICATIONS

USE OF MAZZEI INJECTORS IN PRESSURIZED SPRINKLER APPLICATIONS USE OF MAZZEI INJECTORS IN PRESSURIZED SPRINKLER APPLICATIONS The selection, installation and use of Mazzei Injectors in pressurized sprinkler systems are simple and straightforward. There are several

More information

Multi-Tank Submersible Pump Install Manual

Multi-Tank Submersible Pump Install Manual Multi-Tank Submersible Pump Install Manual Automated Fuel Maintenance System FTI-5A FUEL TECHNOLOGIES INTERNATIONAL LLC Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 03/01/2011

More information

LIQUID MEASUREMENT STATION DESIGN Class No

LIQUID MEASUREMENT STATION DESIGN Class No LIQUID MEASUREMENT STATION DESIGN Class No. 2230.1 Michael Frey Systems Sales Manager Daniel Measurement & Control, Inc. 5650 Brittmoore Rd. Houston, Texas 77041 INTRODUCTION The industry continues to

More information

BMF TROUBLESHOOTING GUIDE

BMF TROUBLESHOOTING GUIDE BMF TROUBLESHOOTING GUIDE This document contains troubleshooting guidelines for PEP's standard BMF filters with pumps. REFERENCE DOCUMENTS: W-X-0039 BMF Electrical Wiring Drawing WP0011 BMF Control Panel

More information

FLOW TEK VALVES & CONTROL S INC

FLOW TEK VALVES & CONTROL S INC FLOW TEK VALVES & CONTROL S INC e-mail:- info@flowagevalves.com PLOT NO-172,173, ROAD NO-4, KATHWADA, G.I.D.C. AHMEDABAD. PHONE NO:- 079-22900219,22900220, MOBILE:-09824539702, 9824080899. an ISO 9001

More information

NFPA , Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY

NFPA , Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY NFPA 25-2017, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems REVIEW SUMMARY 1) NFPA 25 REVISION SUMMARY For the 2017 edition, new fire pump terms are defined

More information

Cooling System Description and Operation

Cooling System Description and Operation Page 1 of 5 2008 Holden VE Sedan VE, WM, Caprice, Statesman, Lumina, Omega, VXR8 Service Manual Engine Engine Cooling Description and Operation Document ID: 1990377 Cooling System Description and Operation

More information

CH.4 Basic Components of Hydraulic and Pneumatic System/16 M HAP/17522/AE5G

CH.4 Basic Components of Hydraulic and Pneumatic System/16 M HAP/17522/AE5G Content : 4.1 Hydraulic and Pneumatic actuators. 10 Marks Hydraulic Actuators - Hydraulic cylinders (single, double acting and telescopic) construction and working, Hydraulic motors (gear and piston type)

More information

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL 50-01 650-01 & 1 Hytrol (Main ) 2 X42N-2 Strainer & Needle 3 CRL Control Accurate Pressure Control Optional Check Feature Fast Opening to Maintain Line Pressure Slow Closing to Prevents s Completely Automatic

More information

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008. DAN-LIQ-TG-44-rev0208 February 2008 Daniel Liquid Control Valves Technical Guide www.daniel.com Daniel Measurement and Control Theory, Principle of Operation and Applications This brochure has been prepared

More information

Chemical decontamination in nuclear systems radiation protection issues during planning and realization

Chemical decontamination in nuclear systems radiation protection issues during planning and realization Chemical decontamination in nuclear systems radiation protection issues during planning and realization F. L. Karinda, C. Schauer, R. Scheuer TÜV SÜD Industrie Service GmbH, Westendstrasse 199, 80686 München

More information

Engaging Inquiry-Based Activities Grades 3-6

Engaging Inquiry-Based Activities Grades 3-6 ELECTRICITY AND CIRCUITS Engaging Inquiry-Based Activities Grades 3-6 Janette Smith 2016 Janette Smith 2016 1 What s Inside Activity 1: Light it Up!: Students investigate different ways to light a light

More information

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions 6677 N. Gessner, Houston, Texas 77040 Throughout the oil and gas industry, there stems the need for accurate, economical measurement

More information

Tehnical paper. Technical paper Title. Hydraulic balance in. Title. a district heating system. Author(s), Danfoss. heating.danfoss.

Tehnical paper. Technical paper Title. Hydraulic balance in. Title. a district heating system. Author(s), Danfoss. heating.danfoss. Tehnical paper Technical paper Title Hydraulic balance in Title a district heating system Author(s), Danfoss Herman Boysen Published at... and Jan Eric Thorsen heating.danfoss.com districtenergy. districtenergy.danfoss.com

More information

VXI Closed circuit cooling towers

VXI Closed circuit cooling towers Closed circuit cooling towers Key benefits Reliable Quiet Compact characteristics Counter flow, centrifugal fan, forced draft Capacity range up to 2615 kw Maximum entering fluid temperature 82 C Typical

More information

Evaluation of a Gearbox s High-Temperature Trip

Evaluation of a Gearbox s High-Temperature Trip 42-46 tlt case study 2-04 1/13/04 4:09 PM Page 42 Case Study Evaluation of a Gearbox s High-Temperature Trip By Vinod Munshi, John Bietola, Ken Lavigne, Malcolm Towrie and George Staniewski (Member, STLE)

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Acceptance Inspection Date of Review / / BLD20 - Project Address: Project Name: Numbers following worksheet comments represent an NFPA

More information

ECH 4224L Unit Operations Lab I Fluid Flow FLUID FLOW. Introduction. General Description

ECH 4224L Unit Operations Lab I Fluid Flow FLUID FLOW. Introduction. General Description FLUID FLOW Introduction Fluid flow is an important part of many processes, including transporting materials from one point to another, mixing of materials, and chemical reactions. In this experiment, you

More information

PUMP HEART OF PLUMBING SYSTEM V.SRINIVAS

PUMP HEART OF PLUMBING SYSTEM V.SRINIVAS PUMP HEART OF PLUMBING SYSTEM V.SRINIVAS Pump is the most important element in the Plumbing system and may be considered as its Heart. Majority of Energy in Plumbing systems is consumed by Pumps. It is

More information

Regenerative Turbine Chemical Pumps for the Process Industry

Regenerative Turbine Chemical Pumps for the Process Industry www.rothpump.com BULLETIN 1C99 Regenerative Turbine Chemical Pumps for the Process Industry Continuous high pressure pumping of non-lubricating, corrosive, liquefied gasses and liquids at boiling point

More information

Piping Systems. J. David Bankston, Jr., and Fred Eugene Baker*

Piping Systems. J. David Bankston, Jr., and Fred Eugene Baker* SRAC Publication No. 373 December 1994 Piping Systems J. David Bankston, Jr., and Fred Eugene Baker* Whether you are pumping water to fill a pond or to aerate, it pays to do it as economically as possible.

More information

VFC-5 to VFC-500 FLO-COATER

VFC-5 to VFC-500 FLO-COATER VFC-5 to VFC-500 FLO-COATER OPERATION INSTRUCTIONS Page -1- CONTENTS PAGE NUMBER System Description... 2 Flo-Coater Description... 4 Operation of a Flo-Coater... 8 Selective Operator Control... 9 Operating

More information

FAN PERFORMANCE MODULATION

FAN PERFORMANCE MODULATION FAN PERFORMANCE MODULATION Some fan systems have changing air requirement during operation, such as variable air volume systems, while others have changing pressure requirements; both airflow and pressure

More information

Setting the Standard

Setting the Standard Setting the Standard Improved control and less maintenance. Electronic asphalt pump speed control provides superior dependability and more precise control than manual systems. The application rate is automatically

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

Suction Elbow Flow Performance Tests

Suction Elbow Flow Performance Tests Suction Elbow Flow Performance Tests Conducted by: GBW Associates, LLC And Water Supply Innovations, LLC Hunterdon County, New Jersey 2017 GBW Associates, LLC, Westminster, MD Contents Scope of Project

More information

/.4=111. Lubrication Systems 6-23

/.4=111. Lubrication Systems 6-23 Lubrication Systems 6-23 The transducer is designed so that it sends a corrected oil pressure (fluid pressure minus vent "air" pressure) to the cockpit gauge. This design is used because vent pressure

More information

Automobili Lamborghini s.p.a. OBDII MY 07 Section 9 Page 1 POSITIVE CRANKCASE VENTILATION (PCV) SYSTEM MONITORING

Automobili Lamborghini s.p.a. OBDII MY 07 Section 9 Page 1 POSITIVE CRANKCASE VENTILATION (PCV) SYSTEM MONITORING Automobili Lamborghini s.p.a. OBDII MY 07 Section 9 Page 1 POSITIVE CRANKCASE VENTILATION (PCV) SYSTEM MONITORING Automobili Lamborghini s.p.a. OBDII MY 07 Section 9 Page 2 Description Automobili Lamborghini

More information

PALO VERDE NUCLEAR GENERATING STATION

PALO VERDE NUCLEAR GENERATING STATION PALO VERDE NUCLEAR GENERATING STATION Mechanical Maintenance Training Classroom Lesson Mechanical Maintenance Training Date: 7/23/2010 5:42:15 AM LP Number: NMC61C000202 Rev Author: LEE BAKER Title: Lubrication

More information

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Pump Curves...2 Pump End Assembly...3 Disassembly...3 Installation...4

More information

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8

Inspection, Testing, and Maintenance Fire Pumps NFPA 25, Chapter 8 as amended by CCR, Title 19 Page 1 of 8 , Chapter 8 as amended by CCR, Title 19 Page 1 of 8 Address: City: Date of Pump Test: Shaft Orientation: Horizontal Vertical Annual Fire Pump Test Results Number of pumps at this location: If multiple

More information

Fire in a Cooling Tower. July 1997 Texas, USA

Fire in a Cooling Tower. July 1997 Texas, USA Fire in a Cooling Tower July 1997 Texas, USA Cooling Tower-Background Ammonia and Urea plant. Originally constructed in 1968 by M.W. Kellogg. - 1000 tons/day ammonia Capacity expanded in 1989. - 1450 tons/day

More information

Chapter 13: Application of Proportional Flow Control

Chapter 13: Application of Proportional Flow Control Chapter 13: Application of Proportional Flow Control Objectives The objectives for this chapter are as follows: Review the benefits of compensation. Learn about the cost to add compensation to a hydraulic

More information

meters Time Trials, seconds Time Trials, seconds 1 2 AVG. 1 2 AVG

meters Time Trials, seconds Time Trials, seconds 1 2 AVG. 1 2 AVG Constan t Velocity (Speed) Objective: Measure distance and time during constant velocity (speed) movement. Determine average velocity (speed) as the slope of a Distance vs. Time graph. Equipment: battery

More information

TW G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM

TW G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-75G-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM The TW1000-75G-40 Flag Frame Booster System is equipped with a centrifugal pump regulated by a variable frequency drive that controls the pump

More information

Understanding the Modern Automotive Air Conditioning System. Trainer: Grant Hand

Understanding the Modern Automotive Air Conditioning System. Trainer: Grant Hand Understanding the Modern Automotive Air Conditioning System Trainer: Grant Hand AUTOMOTIVE TRAINING SOLUTIONS PTY LTD Training for the future... Automotive Training Solutions IMPORTANT NOTE Copyright The

More information

Applied Fluid Mechanics

Applied Fluid Mechanics Applied Fluid Mechanics 1. The Nature of Fluid and the Study of Fluid Mechanics 2. Viscosity of Fluid 3. Pressure Measurement 4. Forces Due to Static Fluid 5. Buoyancy and Stability 6. Flow of Fluid and

More information

Installation Manual FTI-10A & FTI-20A SINGLE TANK. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL

Installation Manual FTI-10A & FTI-20A SINGLE TANK. Automated Fuel Maintenance System FUEL TECHNOLOGIES INTERNATIONAL Installation Manual Automated Fuel Maintenance System FTI-10A & FTI-20A SINGLE TANK FUEL TECHNOLOGIES INTERNATIONAL 05/01/2016 Rev A Fuel Technologies FTI-10A & FTI-20A Single Tank Installation Manual

More information

AUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS

AUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS Application Bulletin A Unit of IDEX Corporation No. 13 June 21 AUTOGAS 1 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS CORKEN, INC. A Unit of IDEX Corporation P.O. Box 12338, Oklahoma

More information

Masoneilan * Lo-dB Cartridges and Expansion Plates

Masoneilan * Lo-dB Cartridges and Expansion Plates GE Oil & Gas Technical Specifications 05/2013 Masoneilan * Lo-dB Cartridges and Expansion Plates Table of Contents Introduction...3 Application...3 Lo-dB Cartridges...4 Principle of Operation...4 Installation...4

More information

Freescale Cup Competition. Abdulahi Abu Amber Baruffa Mike Diep Xinya Zhao. Author: Amber Baruffa

Freescale Cup Competition. Abdulahi Abu Amber Baruffa Mike Diep Xinya Zhao. Author: Amber Baruffa Freescale Cup Competition The Freescale Cup is a global competition where student teams build, program, and race a model car around a track for speed. Abdulahi Abu Amber Baruffa Mike Diep Xinya Zhao The

More information

BYPASS ROTAMETERS FOR MEASURING RATE OF FLOW IN LARGE PIPELINES

BYPASS ROTAMETERS FOR MEASURING RATE OF FLOW IN LARGE PIPELINES BULLETIN 20-5100-68 BYPASS FOR MEASURING RATE OF FLOW IN LARGE PIPELINES BYPASS ROTOMETERS SK bypass Rotameter systems are designed for the accurate measurement of fluid rate of flow in pipelines 11/2

More information

GRUNDFOS WHITE PAPER. Parallel Pumping by Steve Wilson WHAT IS PARALLEL PUMPING?

GRUNDFOS WHITE PAPER. Parallel Pumping by Steve Wilson WHAT IS PARALLEL PUMPING? GRUNDFOS WHITE PAPER Parallel Pumping by Steve Wilson large percentage of installed pumps in A commercial, industrial, and municipal systems are installed in parallel pumping systems. However, the hydraulic

More information

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring.

Test Which component has the highest Energy Density? A. Accumulator. B. Battery. C. Capacitor. D. Spring. Test 1 1. Which statement is True? A. Pneumatic systems are more suitable than hydraulic systems to drive powerful machines. B. Mechanical systems transfer energy for longer distances than hydraulic systems.

More information

Series PAVC Variable Volume, Piston Pumps

Series PAVC Variable Volume, Piston Pumps Series PVC Variable Volume, Piston Pumps Catalog 26-11-1/US 95 Introduction Series PVC Quick Reference Data Chart Pump Model Displacement CM 3 /REV (IN 3 /REV) Pump Delivery *pprox. Noise Levels db() Input

More information

It s What s Inside that Counts

It s What s Inside that Counts It s What s Inside that Counts Drive Basics Adjustable Frequency Drive Description: Solid State Device Controls the Frequency and Voltage Speed Range Depends on the Motor HP Range - Fractional to 10,000

More information

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters

INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters INSTALLATION, OPERATION AND MAINTENANCE Threaded and Wafer Style Flowmeters Table of Contents Page 1. Principle of Operation...2 2. Installation Planning......2 3. Installation...3 3.1 Safety Considerations...

More information

Why and how to adjust a TXV / TEV

Why and how to adjust a TXV / TEV Why and how to adjust a TXV / TEV As we talked about in an earlier podcast, a TXV is designed to maintain a specified and constant superheat at the outlet of the evaporator coil. It does this through a

More information

When working with original equipment manufacturers, hydraulic system designers and plant maintenance engineers, one of the key factors for long

When working with original equipment manufacturers, hydraulic system designers and plant maintenance engineers, one of the key factors for long 1 When working with original equipment manufacturers, hydraulic system designers and plant maintenance engineers, one of the key factors for long system life and low down time is to provide isolated Off

More information

Installation Manual. Automated Fuel Maintenance System FTI-5A FUEL TECHNOLOGIES INTERNATIONAL

Installation Manual. Automated Fuel Maintenance System FTI-5A FUEL TECHNOLOGIES INTERNATIONAL Installation Manual Automated Fuel Maintenance System FTI-5A FUEL TECHNOLOGIES INTERNATIONAL Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 07/15/2015 Rev E Fuel Technologies

More information

Installation & Design Maintenance for ILBP System

Installation & Design Maintenance for ILBP System Installation & Design Maintenance for ILBP System Before installation of the Chemguard ILBP system(s), check all components to ensure that no damage has occurred during shipment and read the manual before

More information

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM

TW W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-20W-40 FLAG FRAME VARIABLE SPEED BOOSTER PUMP SYSTEM TW1000-20W-40 FLAG FRAME The TW1000-20W-40 Flag Frame Booster System is equipped with a centrifugal pump regulated by a variable frequency drive

More information

Hydro-Max Hydraulic Brake Booster and Master Cylinder. Technical Manual

Hydro-Max Hydraulic Brake Booster and Master Cylinder. Technical Manual Hydro-Max Hydraulic Brake Booster and Master Cylinder Technical Manual * 5+0 Important Service Notes The information in this publication was current at the time of printing. The information presented in

More information

Module 7: Cooling System Components

Module 7: Cooling System Components  Â  Basic Cooling System Components Radiators Common Types of Radiators Coolant Hoses Water Pumps Centrifugal Force Types of Drives for Water Pumps Types of Drive Belts Basic Cooling System Components

More information

Series PVP Variable Volume Piston Pumps

Series PVP Variable Volume Piston Pumps Series PVP Variable Volume Piston Pumps Catalog HY28-2661-CD/US zp2 hpm12-1.p65, lw, jk 1 Notes Series PVP hpm12-1.p65, lw, jk 2 Introduction Series PVP Series Sizes 6-14 Phased Out For Reference Only

More information

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 SEPTEMBER 2001

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 SEPTEMBER 2001 MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 SEPTEMBER 2001 MNSD V MULTIPLE NOZZLE SPRAY DESUPERHEATER Multiple Nozzle Spray Desuperheater Offers High Temperature Capabilities and Low Class

More information

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 APRIL 2004

MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 APRIL 2004 MNSD-V MULTIPLE NOZZLE SPRAY DESUPERHEATER BULLETIN 1144 APRIL 2004 MNSD V MULTIPLE NOZZLE SPRAY DESUPERHEATER Multiple Nozzle Spray Desuperheater Offers High Temperature Capabilities and Low Class V Leakage

More information

BLOWER VACUUM SWITCH FAILED OPEN

BLOWER VACUUM SWITCH FAILED OPEN F1 F1 AC BLOWER VACUUM SWITCH FAILED CLOSED AC BLOWER VACUUM SWITCH FAILED CLOSED UHS If the blower vacuum switch is closed before blower start-up, the control module will not start the blower. Pre-check

More information

Everest. Leaders in Vacuum Booster Technology

Everest. Leaders in Vacuum Booster Technology EVEREST has introduced Mechanical Booster Pumps to meet the growing demand of the Vacuum Process Industry where fast pump down times are required and energy usage concerns rule out any alternative pump

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE February 16, 2007 Foam 304a The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com

More information

Name Date Period. MATERIALS: Light bulb Battery Wires (2) Light socket Switch Penny

Name Date Period. MATERIALS: Light bulb Battery Wires (2) Light socket Switch Penny Name Date Period Lab: Electricity and Circuits CHAPTER 34: CURRENT ELECTRICITY BACKGROUND: Just as water is the flow of H 2 O molecules, electric current is the flow of charged particles. In circuits of

More information

Water System Sizing Worksheet. Joe Agricola Example

Water System Sizing Worksheet. Joe Agricola Example Water System Sizing Worksheet Joe Agricola Example This example is provided to help you size the pump, pressure tank, and water distribution piping for your dugout water system. It contains a written explanation

More information

Exhaust System Bypass Valves and Exhaust Valve Bypass Controller

Exhaust System Bypass Valves and Exhaust Valve Bypass Controller Exhaust System Bypass Valves and Exhaust Valve Bypass Controller Basic Primer on Exhaust System Flow Velocity and Backpressure The information about exhaust system theory was obtained from research on

More information

Designing & Validating a New Intake Manifold for a Formula SAE Car

Designing & Validating a New Intake Manifold for a Formula SAE Car Designing & Validating a New Intake Manifold for a Formula SAE Car Arpit Singhal 1 1 (M.Tech (Computational Fluid Dynamics) University of Petroleum &Energy Studies, India Abstract This paper gives the

More information

INTERNAL COMBUSTION ENGINE (SKMM 4413)

INTERNAL COMBUSTION ENGINE (SKMM 4413) INTERNAL COMBUSTION ENGINE (SKMM 4413) Dr. Mohd Farid bin Muhamad Said Room : Block P21, Level 1, Automotive Development Centre (ADC) Tel : 07-5535449 Email: mfarid@fkm.utm.my HISTORY OF ICE History of

More information

STEALTH INTERNATIONAL INC. DESIGN REPORT #1001 IBC ENERGY DISSIPATING VALVE FLOW TESTING OF 12 VALVE

STEALTH INTERNATIONAL INC. DESIGN REPORT #1001 IBC ENERGY DISSIPATING VALVE FLOW TESTING OF 12 VALVE STEALTH INTERNATIONAL INC. DESIGN REPORT #1001 IBC ENERGY DISSIPATING VALVE FLOW TESTING OF 12 VALVE 2 This report will discuss the results obtained from flow testing of a 12 IBC valve at Alden Research

More information

12VPS TRAK-DT. Block Detection / Signaling Starter Package. 12 VOLT / 0.5 Amp REGULATED POWER SUPPLY. a c t i v a t i o n s e c t i o n

12VPS TRAK-DT. Block Detection / Signaling Starter Package. 12 VOLT / 0.5 Amp REGULATED POWER SUPPLY. a c t i v a t i o n s e c t i o n Block Detection / Signaling Starter Package This package includes 3 Trak-DT's (item 365) and one 12VPS (item 369), 12 volt DC regulated power supply. Drawings are included for basic two and three aspect

More information

Circuit board for R-471/472/481/482 with 1/8 NPT ports SUPPLY. 1/8 NPT typ.

Circuit board for R-471/472/481/482 with 1/8 NPT ports SUPPLY. 1/8 NPT typ. CM-0 Circuit board for R-/// with / NPT ize: x / x / thick - module Use: Port #, the supply to the pilot valve, is connected to the main supply port #. Provides / NPT in the top of the circuit board..000.00..9

More information

Pressure Reducing, Differential and Back Pressure Regulating Valves Spring Loaded Dome Loaded Pilot Actuated

Pressure Reducing, Differential and Back Pressure Regulating Valves Spring Loaded Dome Loaded Pilot Actuated a Proportion-Air brand Pressure Reducing, Differential and Back Pressure Regulating Valves Spring Loaded Dome Loaded Pilot Actuated 1 Burling Valves Largest Cv per valve size - Possible smaller, more cost

More information

Installation Manual. Automated Fuel. Maintenance. System FUEL TECHNOLOGIES INTERNATIONAL LLC

Installation Manual. Automated Fuel. Maintenance. System FUEL TECHNOLOGIES INTERNATIONAL LLC Installation Manual Automated Fuel Maintenance System FTI-10A & FTI-20A FUEL TECHNOLOGIES INTERNATIONAL LLC Replacement Manuals Available on Website: www.fueltechnologiesinternational.com 03/01/2011 -

More information

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8 Header Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations RT 007-11 Balhannah and Uraidla - Final Draft Page 1 of 8 DISCLAIMER The purpose of this document is to inform customers,

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 3-3 Venturi Tubes EXERCISE OBJECTIVE In this exercise, you will study the relationship between the flow rate and the pressure drop produced by a venturi tube. You will describe the behavior of

More information

Type FL Pressure Reducing Regulators

Type FL Pressure Reducing Regulators ulletin 71.2 D103067X012 Type FL January 2017 Type FL Pressure Reducing Regulators Features No tmospheric leed Eliminates nuisance and wasteful bleed gas to atmosphere by utilizing a self-contained control

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Technical Services: Tel: () 31-931 / Fax: () 791-55 Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and

More information

D-040 PN 16 D-040-C PN 16. Combination Air Valve. Description. Applications. Operation. Main Features

D-040 PN 16 D-040-C PN 16. Combination Air Valve. Description. Applications. Operation. Main Features D00.WTR.CAT.ENG0 D-00 PN 1 Water Supply D-00-C PN 1 Combination Air Valve Description The D-00 series Combination Air Valve has the features of both an air release valve and an air & vacuum valve. The

More information

CLOSED CIRCUIT HYDROSTATIC TRANSMISSION

CLOSED CIRCUIT HYDROSTATIC TRANSMISSION Energy conservation and other advantages in Mobile Equipment Through CLOSED CIRCUIT HYDROSTATIC TRANSMISSION C. Ramakantha Murthy Technical Consultant Various features/advantages of HST Hydrostatic transmissions

More information

Series 34. Specifications

Series 34. Specifications Series Air Release Valves Stainless Steel T Trim Standard Stainless Steel Floats Guaranteed Easily Serviced Without Removal From Pipeline Working Pressures to 800 PSI Engineered For Drip Tight Seal At

More information