1 CASSETTE TYPE AIR CONDITIONER (Cool and Heat) Type ACH2400C ACH2800C ACC2400C ACC2800C ACC4400C Indoor Unit ICH2400C ICH2800C ICC2400C ICC2800C ICC4400C Outdoor Unit UCH2400C UCH2800C UCC2400C UCC2800C UCC4400C Panel IFS095G05 SERVICE Manual AIR CONDITIONER CONTENTS. Installation 2. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts List 5. Refrigerating Cycle Block Diagrams 6. Wiring Diagrams 7. Schematic Diagrams E DB800206A(3)

2 . Installation Refrigerant Refill Procedure Refill an airconditioner with refrigerant when refrigerant has been leaked at installing or using.. Purge air(for new installation only). 2. Turn the 3way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3way valve again. Suspension hook 3. Connect the tank to refill with Refrigerant 4. Set the unit to cool operation mode. 5. Check the pressure indicated by the pressure gauge(low pressure side). * Standard pressure is should be 64~78psi in a regular, high operation mode. Compound gauge For mounting other and of hose when not in use High pressure gauge Hand wheel Finger tight fittings Connected to high pressure side Charging line 6. Open the refrigerant tank and fill with refrigerant until the rated pressure is reached. * It is recommended not to pour the refrigerant in too quickly, but gradually while operating a pressure valve. R22 7. Stop operation of the air conditioner. 8. Close the 3way valve, disconnect the pressure gauge, and open the 3way valve again. 9. Close the cap of each valve.

3 2 Pump down Procedure Pump down shall be carried out when an evaporator is replaced or when the unit is relocated in another area.. Remove the caps from the two 3way valves. 2. Turn the 3way valve clockwise to close and connect a pressure gauge(low pressure side) to the service valve, and open the 3way valve again. 3. Set the unit to cool operation mode. (Check if the compressor is operating.) 3Way Valve (High pressure) 4. Turn the 3way valve(high pressure side) clockwise to close. 3Way Valve (Low pressure) 5. When the pressure gauge indicates "0" turn the 3way valve(low pressure side) clockwise to close. 6. Stop operation of the air conditioner. 7. Close the cap of each valve. Relocation of the air conditioner Refer to this procedure when the unit is relocated.. Carry out the pump down procedure (refer to the details of 'pump down'). 2. Remove the power cord. 3. Disconnect the assembly cable from the indoor and outdoor units. 4. Remove the flare nut connecting the indoor unit and the pipe. At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. 5. Disconnect the pipe connected to the outdoor unit. At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. 6. Make sure you do not bend the connection pipes in the middle and store together with the cables. 7. Move the indoor and outdoor units to a new locatioon. 8. Remove the mounting plate for the indoor unit and move it to a new location. 2

4 2. Disassembly and Reassembly Stop operation of the air conditioner and remove the power cord before repairing the unit. Indoor Unit No. Part name Procedures Picture! Front Grille & Filter. Open the front grille by pushing the tabs on the grille. IMPORTANT You must give attention when disassembling the front grille and must check the safety clips have been installed. If you don't ensure them, the front grille will drop suddenly and you will be hurt. 2. Remove the front grille. 2. Remove the safety clips. 22. Open the front grille about 45 and pull it forward. 3. Pull out the filter air. ;;; ;;; yyy yyysafety Clip 3

5 Disassembly and Reassembly No. Part name Procedures Picture 4. Slowly loosen the four bolts holding the panel to the assembly. Front panel fixing holes Eye 5. Open the electrical component box cover removing the screws. (3EA) 6. Disconnect the two cables between the assembly and the panel. Stepping motor connectors. 6. Disconnect the three cables between the assembly and the panel. Stepping motor connector Receiver & Display unit connector (Optional) Front Panel 4

6 Disassembly and Reassembly No. Part name Procedures Picture <*Optional> Receiver & Display Unit 7. Separate the front panel using two hooks on the both sides of the indoor unit. ;;; yyy ;; yy Hook and Electronic part Do!,!2,!3 and!4 above.. Remove the screws(6ea) on the electrical component box and remove the cover plates. 2. Open the control box. 5

7 Disassembly and Reassembly No. Part name Procedures Picture 3. Disconnect the other end of the cable to the outdoor unit through the ceiling & the hole on the wall between the control box and the assembly. # Method Fan and motor Do! above.. Disconnect FAN MOTOR wire connector, thermistor wire connector, drain pump wire connector. 2. Disconnect wire connects to capacitor. 6

8 Disassembly and Reassembly No. Part name Procedures Picture Fan and motor 3. Disconnect float switch wire connected to terminal board (F, F2). 4. Disconnect all connectors connected to PCB. 5. Remove PCB s from assy case PCB. 6. Remove the screws(9ea) for disconnection of Bell mouth and cushion drain. 7

9 Disassembly and Reassembly No. Part name Procedures Picture Fan and motor Pump 8

10 Disassembly and Reassembly No. Part name Procedures Picture Pump 9

11 Disassembly and Reassembly No. Part name Procedures Picture Fan and motor 7. Seperate Bell mouth and Box Ass y from cushion drain. 8. Loosen the nut and separate the assy holder fan. 9. Lift down carefully the Ass'y fan. 0

12 Disassembly and Reassembly No. Part name Procedures Picture Fan and motor 0. Separate the motor connector wire and separate the wire holder fixed the bottom floor.. Remove the screw fixed onto the bracket wire fixed on the bottom of product and remove screw fixed onto earth wire and separate carefully the ass'y motor in from the product after separation of nut of ass'y motor in and grommet mount motor.

13 Disassembly and Reassembly No. Part name Procedures Picture Fan and motor $ Method 2. Pump Do #, 2, 3 above.. For separation of Ass'y cushion drain from the main body.! Cabinet guide A Cabinet guide B (EA) # Remove each cabinet power cord. $ Remove the obstacles of pump drain and ass'y sensor float wire due to the movement of BKT wire. 2

14 Disassembly and Reassembly No. Part name Procedures Picture Pump 2. For the separation of ass'y cushion drain form the main body, remove the fixing screw of bracket at each corner of cushion drain. 3. Take out the CAP drain socket inserted in the ass'y drain cushion to remove the condensate in the drain cushion. * Care must be taken for the taking out the condensate water. 4. Lift down carefully the Ass'y cushion drain from the main body. 5. Loosen three screws fixing the pump drain. 3

15 Disassembly and Reassembly No. Part name Procedures Picture Pump 6. Separate the hose drain inserted in the outlet of pump drain. 7. Separate from the BKT pump the pump drain separated from the main body from the BKT pump. % Heat exchanger Do $ ~ $4. Separate the partition front evap fixing the heat exchanger to the base of main body. 2. Separate the holder evap (2 EA) fixing the heat exchanger to the base of main body. 4

16 Disassembly and Reassembly No. Part name Procedures Picture 3. Separate holder guide evap (4 EA). 4. Lift up the heat exchanger from the main body. 5

17 Disassembly and Reassembly No. Part name Procedures Picture ^ Front panel Cover Front Do! above. Push 3 cover front fixing screws inside the front panel and snap fixing part to separate the cover front. 6

18 Disassembly and Reassembly No. Part name Procedures Picture & Front panel Stepping Motor Do! above.. Loosen each one of fixing screw at the corner part,! cushion sidea and cushion sideb inside the front panel, and then lift it up. 2. Remove! the screw of housing motor L/R fixed at the corner part of front panel inside and BladeH. 3.! Separate the stepping motor from the housing motor L/R separate the motor wire connected. 7

19 Disassembly and Reassembly No. Part name Procedures Picture * Front panel CushionA Do! above. Remove two screws fixing cushiona inside the front and lift it up. ( Front panel Biopure filter (Optional) and # above.. Separate the bio pure filter from the filter air. (remove 4 fixingscrews) 2. Lift up the bio pure filter case to take the filter out. 8

20 Disassembly and Reassembly Outdoor Unit (24K, 28K) No. Part name Procedures Cabinet Fan Motor & Propeller Fan ) Turn off the unit and remove the power cable. 2) Remove the top cover. 3) Remove the control box cover. 4) Unplug the ass'y cable. 5) Remove the cabiside. 6) Remove the cabifront. * When you assemble the parts, check if the each parts and electric connectors are fixed firmly. ) Do Procedure above. 2) Remove the nut flange. (Turn to the right to remove as it is a left turned screw) 3) Disassemble the propeller fan. Outdoor Unit (44K) No. Part name Procedures Picture! Cabinet ) Turn off the unit and remove the power cable. 2) Remove the top cover. 3) Remove the control box cover. 4) Unplug the ass'y cable. 5) Remove the cabiside. 6) Remove the cabifront. * When you assemble the parts, check if the each parts and electric connectors are fixed Fan Motor & Propeller Fan ) Do Procedure above. 2) Remove the nut flange. (Turn to the right to remove as it is a left turned screw) 3) Disassemble the propeller fan. 9

21 20 MEMO

22 3. Trouble Shooting Trouble shooting by outdoor unit error code ERROR CODE E E5 E6 E9 EA EC ED EL ERROR DESCRIPTION Indoor unit room thermistor error Indoor unit pipe thermistor error Outdoor unit thermistor error Float switch open error Communication error between indoor unit and outdoor unit Communication error between wired remote controller and indoor unit Outdoor unit pipe thermistor error Reverse power of 3 phase power source detected (3 phase model) REFERENCE PART EC0 EC02 EC03 EC04 EC05 EC06 EC07 EC08 Trouble shooting by indoor unit receive board ERROR CODE Reservation LED flickering(hz period) Operation LED and reservation LED flickering (Hz period) Operation LED and filter LED flickering (Hz period) Reservation LED filter LED alternating flickering (Hz period) Reservation LED and filter LED flickering (Hz period) Operation LED and reservation LED alternating flickering (Hz period) Filter LED flickering (Hz period) ERROR CODE Indoor temperature sensor abnormal Indoor pipe temperature sensor abnormal Outdoor temperature sensor abnormal Float switch open abnormal Indoor and outdoor communication abnormal Wired remote controller communication abnormal Outdoor pipe temperature sensor abnormal REFERENCE PART EC0 EC02 EC03 EC04 EC05 EC06 EC07 Trouble shooting by outdoor unit error code ERROR CODE ERROR DESCRIPTION * Indoor unit room thermistor error *5 Indoor unit pipe thermistor error *6 Outdoor unit thermistor error *9 Float switch open error *A Communication error between indoor unit and outdoor unit *C Communication error between wired remote controller and indoor unit *D Outdoor unit pipe thermistor error *L Three phase power incorrect connecting error (In case of three phase power models) The asterisk mark * + ERROR CODE of wired remote controller stands for the set number. ex) ERROR CODE 39 is the FLOAT SWITCH OPEN ERROR of SET no.3. REFERENCE PART EC0 EC02 EC03 EC04 EC05 EC06 EC07 EC08 Trouble shooting by outdoor unit error code ERROR CODE LED flickering ERROR DESCRIPTION Communication error between indoor unit and centralized controller REFERENCE PART EC20 2

23 Trouble Shooting EC0 : Trouble on the thermistor related part of indoor unit. EC0 : Trouble on the room thermistor related part of indoor unit. E of outdoor unit PCB 7segment Reservation lamp of wireless receiving board is flickering with Hz. Action items when * displays on the wired remote controller. Check point : Defect of indoor unit Indoor unit thermistor defect Indoor unit thermistor installed at CN8? Indoor the indoor unit thermistor at CN8 Is the vlotage across the thermistor 4.9V and higher or 0.5V and lower? Replace the indoor unit PCB Replace the thermistor * stands for the indoor unit address. EC02 : Trouble on the pipe thermistor related part of indoor unit. E5 of outdoor unit PCB 7segment. Reservation lamp of wireless receiving board is flickering with Hz. Action items when *5 displays on the wired remote controller. Check point : Indoor unit PCB defect Indoor unit pipe thermistor defect Is the indoor unit pipe thermistor installed at CN8? Install the indoor unit pipe thermistor at CN8 Is the voltage across thermistor 4.9V and higher or 0.5V lower? Replace the indoor unit PCB Replace the thermistor 22

24 Trouble Shooting EC03 : When the trouble is found on the part related to the outdoor unit thermistor. E6 of outdoor unit PCB 7segment Operation lamp and filter lamp of wireless receiving board are flickering with Hz. Action items when *6 displays on the wired remote controller. Check point : Defect of indoor unit Indoor unit thermistor defect Is the outdoor unit thermistor installed at CN4? Install the outdoor unit thermistor at CN4. Is the voltage across the thermistor 4.9V and higher or 0.5V and lower? Replace the outdoor unit PCB Replace the thermistor * stands for the indoor unit address. 23

25 Trouble Shooting EC04 : When the trouble is found on the drain pump and float switch installed on the indoor unit. EC0 : Trouble on the thermistor related part of indoor unit. E9 of 7segment of outdoor unit PCB Reservation lamp of wireless receiving board and filter lamp are flickering with Hz. Action item when *9 displays on the wireless remote controller. Check point : Indoor unit defect Drain pump, float switch defect Start Is available drain pump? SW2 ON? Is available float SW? SW3 ON? Check the float SW Replace indoor unit PCB SW2 ON? Replace PCB Install float SW SET SW2 OFF SET SW3 OFF SET SW2 OFF SET SW3 OFF POWER RESET * stands for the indoor unit address. 24

26 Trouble Shooting EC05 : When the trouble is found in the communication related part between indoor unit and outdoor unit. EA of 7segment of outdoor unit PCB. Reservation lamp and filter lamp of wireless receiving board is flickering with Hz. Action item when *A displays on the wired remote controller. Check point : Indoor unit outdoor unit misconnection Indoor unit PCB defect Outdoor unit PCB defect Are the terminals, 2, 3 of indoor unit and outdoor unit are correctly connected? and is the set power on? Do connection correctly and check. Is the LED of PCB flickering with 6Hz for 250ms and then repeating the on? Indoor unit communication normal. Is the LED of PCB flickering with 6Hz? The Micom of outdoor unit is operating normally, check and replace the communication circuit of outdoor unit and indoor unit. Replace the PCB * stands for the indoor unit address. 25

27 Trouble Shooting EC06 : When the trouble is found in the communication related part between indoor unit and wired remote controller. (during single operation, not group control) EC of 7segment of outdoor unit PCB. Wireless receiving board lamp and reservation lamp is flickering with Hz. Action item when C displays on the wired remote controller. Check point : Short circuit or misconnection of the communication line between indoor unit and wireless remote controller Indoor unit PCB defect Wired remote controller PCB defect Are the terminals R, R2, R3 of indoor unit terminal board connected correctly to R, R2, R3 of wired remote controller? Connect correctly and check. Is 7P(RED) of transformer connected to CN of indoor unit? Is the jump wire inserted into CN20 of indoor unit PCB? Connect correctly and check again Is the address of PCB digital switch of indoor unit to "0"? Set address to "0" Replace the indoor unit PCB Replace the wired remote controller 0 stands for the indoor unit address. 26

28 Trouble Shooting EC07 : When the trouble is found in the communication related part between outdoor unit pipe thermistor. ED of 7segment of outdoor unit PCB. Reservation lamp and filter lamp of wireless receiving board is flickering with Hz. Action item when D displays on the wired remote controller. Check point : Indoor unit pipe thermistor available or not Indoor unit PCB defect Is indoor pipe thermistor installed at CN4? Connect correctly and check. Is the voltage across the thermistor 4.9V and higher or 0.5V and lower? Replace the outdoor PCB Replace the thermistor * stands for the indoor unit address. 27

29 Trouble Shooting EC08 : When the reverse of three phase power is found. Check point : Check CN76 to connect correctly. Check IC5, IC52, IC53 to connect correctly. Check the Misinsertion on CN76? Insert correctly Wire shorted? Check the pin no 4 of IC5, IC52, IC53, does this make round type signal? IC correct Replace wire Take two connected lines to change the string of L, L2, L3 because of the reverse of power. Replace IC that does not make round type signal 28

30 Trouble Shooting EC09 : When the trouble is found on the part related to the wireless receiving board of the indoor unit. Check point : Defect of wireless remote controller PCB Defect of wireless remote controller receiving board PCB Indoor unit PCB defect Misinsertion of CN9? Insert correctly Wire shorted? LED direct/reverse direction check? Check no. and no.2 pin of CN9:DC +5V? Check pin no. of CN9 while pressing SW9 : DC 0V? Replace the wireless receiving board Replace after check of indoor unit main PCB 29

31 Trouble Shooting EC0 : When the trouble is found on the part related to the wired remote controller. (single operation) Check point : Defect of communication line between indoor unit and wired remote controller. Output of indoor unit Micom Defect of wired remote controller PCB Indoor unit PCB defect Is the wired remote controller energized when the power is reset? Is CN20 of indoor unit main PCB inserted? CN20 insertion Is the wire of CN5 to indoor unit terminal board shorted? Is the on/off button command of wired remote controller reflected on the set? Is the address of indoor unit "0" Set to "0" When the power is applied again after removing the power at the operation on, does the previous status display on the wired remote controller display window? More than on indoor unit mounted on the wired remote controller? One unit is installed Replace the wiring Does the error code display? Are the terminals R, R2, R3 of wired remote controlled connected to the R, R2, R3 of indoor unit terminal boards? Check the indoor unit PCB Connect correctly the R, R2, R3 Check the main PCB of indoor unit and replace it. Error correction and recheck 30

32 Trouble Shooting EC : When the trouble is found on the part related to the fan motor of indoor unit. Check point : Defect of PCB relay of indoor unit. Output of indoor unit Micom Indoor fan motor defect Defect of PCB IC06 of indoor unit Is the power source normal? AC208~230 60Hz Is the wire harness for motor connection good? Is the terminal contact of fan motor condenser good? Check the replay part and replace During the wind control, does it change to breeze, mild and strong wind? Normal When changing the wind to breeze, mild and storing, do RY73, RY74, RY75 operate? Check micom and replace Is he output pin of micom high when selecting each wind control mode? Check micom and replace When selecting the each wind control mode, is the voltage across the replay of indoor unit PCB 2V? Check micom and replace When selecting each wind control of micom, are the pin 4 and 5 of indoor unit PCB IC06 low? Check IC06 and replace Is the voltage across the indoor unit fan AC208~230V? Replace PCB Check the indoor unit fan motor and replace 3

33 Trouble Shooting EC2 : When the trouble is found on the part related to the fan motor of outdoor unit. Check point : Outdoor unit PCB relay defect Output of outdoor unit micom Outdoor unit fan motor defect Defect of IC07 of outdoor unit PCB Is the power source normal? AC208~230 60Hz Is the wire harness for motor connection good? Is the terminald contact of fan motor condenser good? Check and replace the related part Does the outdoor fan motor changes to mild and strong wind during the cooling operation? Normal Do the RY73, RY74 operate? Is the wind volume output pin of micom high when each wind control is operation? Check and replace the micom Is the voltage across the PCB relay 2V when the each wind control of micom is opeating? Check and replace the relay Are the pins and 2 of IC07 of outdoor unit PCB low when each wind control mode micom is operation? Check and replace IC07 Is the voltage across the outdoor unit fan motor AC208~230V? Replace PCB Check outdoor unit fan motor and replace 32

34 Trouble Shooting EC3 : When the trouble is found on the part related to comp of outdoor unit. Check point : Indoor unit PCB relay defect Output of indoor unit micom Comp defect Magnet switch defect Is the power source normal? AC208~230 60Hz Is there no wrong connection and contact of indoor and outdoor connection wire? Is the compressor being delayed for 3 minutes? Is the desired temperature set higher than the current one during the cooling operation? Is the desired temperature set lower than the current one during the cooling operation? Check and replace the related part Is the RY7 on and compressor operting when cooling mode operates and indoor unit PCB is shorted? Normal Is the output of outdoor unit micom pin 57 high when the compressor is on? Check and replace micom (IC04) Is the voltage across RY7 coil of outdoor PCB 2V? Is the output of. 0 of IC05 of outdoor unit low then the compressor is on? Check and replace IC05 Is the voltage AC220V across the terminal of outdoor unit when the compressor is on? Replace the magnet replay Replace the compressor 33

35 Trouble Shooting EC4 : When the trouble is found on the part related to the up & down swing motor of indoor unit (cassette model) Check point : Wire short between indoor unit PCB up & down swing motor connector or bad contact. Output of indoor unit micom Defect of up and down swing motor After check of the short circuit of harness for connecting the up and down swing motor, operate the set in the cooling mode and oeprate the wind direction up and down, and then perform the test. Check and replace the related part Perform the operation on and do the up & down swing action on. Is the up & down control panel normally operationg? Normal No short or wrong connection of connection of connector wire? Check and replace wire harness? Are the voltage of pin no. and 6 of indoor unit PCB DC 2V? Is the output of pin no. 2, 3, 4, and 5 of CN 2 and 3 of indoor unit PCB spherical? Replace up and down swing motor Replace indoor unit PCB 34

36 Trouble Shooting EC5 : When the trouble is found on the part related to drain pump of indoor unit. Check point : Indoor unit PCB Drain pump connector wire, indoor unit Micom No.6 Pin output, IC06 No.6 Pin output. Drain pump, RY72, DC2V power, AC208~230V 60Hz power, indoor unit option switch. Check to confirm whether the wire is connected correctly between indoor unit and outdoor unit? After checking of the shortage for the connector wire between indoor unit and dran pump, operate it for cooling, and checking compressor and then test it. Is normal the DC2V, DC5V output of indoor unit? Check IC0, IC02 and replace. Is switch on the No.2, No.3 option switch of indoor unit? Reset the power after turn on. Is LOW the No.6 pin output of IC04? Check IC06 and replace. Is HIGH the No. pin output of IC06? Replace of indoor unit micom Is DC2V the relay both voltage of RY72? Repace the RY72 Is AC208V~AC230V of the No., No3 pin both voltage of CN5. Replace the indoor PCB. Check the drain pump and replace. 35

37 Trouble Shooting EC6 : When the trouble is found on the part related to float switch of indoor unit. Check point : Indoor unit PCB float switch connector wire, voltage level of indoor unit micom pin no. 55 Float switch, DC 5V power, indoor unit option switch Is the wire connected correctly between indoor unit and outdoor unit? After check of short circuit on the wire between indoor unit and connector wire of float switch, start the cooling operation and then check compressor operation and start the test. Is the DC5V of indoor unit normal? Check and replace IC02 Are no.2 and 3 of option swithch of indoor unit on? ERROR CODE = 09 ERROR DISPLAY = FLICKERING Put on and then reset the power Normal Is the level of micon pin no.55 HIGH Replace indoor unit PCB Are no.2 and 3 of option swithch of indoor unit on? 36

38 Trouble Shooting EC7 : When the trouble is found on the part related to ventilator of indoor unit. Check point : Indoor unit PCB ventilator connector wire, output voltage of indoor unit micom pin No. 5 Ventilator, DC 2V power, DC5V power, indoor unit option switch. Is the wire correctly connected between indoor unit and outdoor unit? after check of shot circuit between indoor unit and ventilator wire, start the wind control and check the indoor fan and then start the test. Is the output DC2V, DC5V normal? Check and replace IC0, IC02 Is the option switch of indoor unit off? Is IC06 pin no. 7 HIGH? Is IC06 pin no. 0 LOW? Put off and then reset the power Replace micom Check and replace IC06 Is the voltage across RY77 normal? Check and replace RY77 Is the voltage of CN6 no. and 3 of indoor unit AC208V~AC230V? Replace indoor unit PCB Check and replace ventilator 37

39 Trouble Shooting EC8 : When the trouble is found on the part related to power system of indoor unit. Check point : Indoor unit AC208V~AC230V input voltage, DC2V output, DC5V output, output voltage of pin no.2 and 3 of CN5. Power transformer, F0, F02, F70 After checking the correct connection between indoor unit and outdoor unit, and check again Is the voltage of pin no. and 3 of CN AC208V~AC230V? Check the connection wire of indoor and outdoor and then replace indoor unit PCB No trouble on F0, F02, F70? DC2V output? DC5V output? Replace fuse Check and replace IC02 Check and replace power transformer No trouble on power transformer AC output? No trouble on the power system and finish the test Check and replace IC0 38

40 Trouble Shooting EC9 : When the trouble is found on the part related to power system of output unit. Check point : Outdoor unit AC208V~AC230V input power, DC2V output, DC5V output Power transformer, F0, F70 Check to confirm whether the wire is connected correctly between indoor unit and outdoor unit? Is the voltage between CN7 pin no. 3 and TB AC208V~AC230V? Check power code and replace PCB No trouble on F0, F70? DC2V output? DC5V output? Replace fuse Check and replace IC02 Check and replace power transformer No check on power transformer AC? No trouble on the outdoor unit power system and finish the test Check and replace IC0 39

41 Trouble Shooting EC20 : When the centralized controller lamp is flickering. (during centralized control) Check point : Defect on the address assignment for the relay equipment connected with centralized controller. Defect on centralized controller PCB Defect on the indoor unit PCB Is the address of Transmitter installed on the indoor unit set correct? Set again in order to avoid the duplicated address Is the communication line of SET short circuited? Check and replace the communication line Reset the power of SET and check the status of LED, LED2 of Transmitter Is the LED on after centralized controller on and off after centralized controller off? Replace the PCB of relay equipment Is the LED2 of relay equipment PCB flickering with the consistent interval? Replace the relay equipment PCB Replace the PCB of centralized controller 40

42 MEMO 4

43 4. Exploded Views and Part LIst 4 Indoor Unit

44 Exploded views and parts list Part List (Indoor Unit) No. Code No. Description Specification Q'TY ACC2400C ACC2800C ACH2400C ACH2800C ACC4400C DB A GUARDSAFETY SGCCM,T0.8 2 DB A COVERCONTROL SGCCM,T0.7 3 DB A COVERPCB SGCCM,T0.7 4 DB900027A ASSY CASECONTROL ASS Y 5 DB900028A ASSYCASEPCB ASS Y 6 DB A TERMINALBOARD5P 250V20A,5P 7 DB K TERMINALBOARD8P 250V20A,8P DB64029B HOLDER WIRE PP,T2.0 9 PDDH32000 ASSY PCB PARTS ASS Y PCB PDDH ASSY PCB PARTS ASS Y PCB 0 DB A TRANSPOWER 250V,50HZ DB A FAN BELL MOUTH SUB PP,OD530 DB A FAN BELL MOUTH SUB PP,OD530 2 DB670009A FANBELL MOUTH PS,OD530,AG240E,BLK 3 DB A THERMISTOR IN PCB 03AT,0K,25,20~00,3435K 4 DB940007A ASSY FANTURBO SAN GF20% 5 DB900006A ASSYHOLDERFAN AG240E,PI NUT HEXAGON 2C.M2 7 DB A ASSYCUSHION DRAIN CH8CA,4WAYCASSETTE 8 DB A CABINETGUIDE A SGCCM,T DB A CABINETGUIDE B SGCCM,T DB60034A BRACKETWIRE SGCCM,T DB60057B BRACKETCOVER OUT B SGCCM,T0.8,W90,L DB A ASSY EVAPLF 3 x 8.5SLIT DB A ASSY EVAPLF 2 x 8.4 SLIT DB A ASSY EVAPLF 3 x 0.5SLIT 23 DB A ASSY EVAPRH 3 x 8.5SLIT DB A ASSY EVAPRH 2 x 8.4 SLIT DB A ASSY EVAPRH 3 x 0.5 SLIT 24 DB670000A PARTITIONFRONT EVAP SGCCM,T0.8 DB A PARTITIONFRONT EVAP SGCCM,T0.8, ACC2400C DB A PARTITIONFRONT EVAP SGCCM,T0.8, ACC4400C 25 DB67000A PARTITIONBACK EVAP SGCCM,T0.8 DB670002A PARTITIONBACK EVAP SGCCM,T0.8, ACC2400C DB A PARTITIONBACK EVAP SGCCM,T0.8, ACC4400C 26 DB600453A HOLDEREVAP SGCCM,T DB6003A HOLDEREVAP SGCCM,T0.8 2 DB60042A HOLDEREVAP SGCCM,T DB600573A GUIDE AIREVAP SGCCM,T DB60023A GUIDE AIREVAP SGCCM,T0.8 4 DB60025A GUIDE AIREVAP SGCCM,T DB960232A ASSY TUBECOLLECTOR ACC23ZA3,C220T DB A ASSY TUBECOLLECTOR ACE8ZA3A,C220T DB960064A ASSY TUBECOLLECTOR ACC2400C, CI220T DB960384A ASSY TUBECOLLECTOR ACC35ZA3, CI220T 29 DB960233A ASSY TUBEINLET PART ACE23ZA3A,CI220T DB960470A ASSY TUBEINLET PART ACC23ZA3,C220T DB A ASSY TUBEINLET PART ACE8ZA3A,C220T DB A ASSY TUBEINLET PART ACC2400C DB960480A ASSY TUBEINLET PART ACC35ZA3 30 DB300026E MOTOR FAN OSM56SAC(S803),CASSETTE DB300096B MOTOR FAN OSM976SAC(S82),CASSETTE 3 DB A HOSE DRAIN ACH2400C,ID2.5,,BLK,,,CASSETTETYPE 32 DB A PARTITIONDRAIN PUMP SGCCM,T0.7,AG240E, DB A PARTITIONDRAIN PUMP SGCCM,T0.7,CH44ZA 33 DB660048A PUMPDRAIN STEEL,75*78,0.5,,KS00SACO23 34 DB A ASSY CABIWELD CH8ZA,4WAYCASSETTE DB B ASSY CABIWELD CH44ZA,4WAYCASSETTE 34 DB A ASSYBASECUSHION AG240E,ASSY 35 DB700059A PLATE MOTOR SGCCM, T DB60020A BRACKETPUMP SGCCM,T2.0,,AG240E, DB6002A BRACKETPUMP SGCCM,T2.0,,CH44ZA 37 DB670008A DRAINHOSE SOCKET ABS,,AG240E, 38 DB A ASSYSENSORFLOAT AG240E,WSH L43 39 DB A COVERDRAIN PUMP SGCCM,T0.8,,,AG440G CAPACITOR 4.5UF CAPACITOR 4.0UF CAPACITOR 3.0UF CAPACITOR 2.5UF CAPACITOR 6.0UF 42 DB A THERMISTOR IN EVAP 43

45 42 Panel Front Disassembly Diagram Panel Front

46 Exploded views and parts list ASSY PANEL PART LIST(KCV) No. Code No. Description Specification Q'TY IFS095G05/KCV Remarks DB640005A PANELFRONT HIPS 2 DB690009A CUSHIONSIDEA EPS, L82, W82, T38.5, W DB A CUSHIONSIDEB EPS, L82, W82, T34.6, W20 4 DB A CUSHIONA EPS, L526, W28, T8.4, W9 4 5 DB A CUSHIONB EPS, L490, W66, T37.5, W DB630004A COVERFRONT HIPS 7 DB C BLADE T4.0, PPS(GF) 4 8 DB60007A HOUSINGMOTOR L HIPS 4 9 DB60008A HOUSINGMOTOR R HIPS 4 0 DB A CONNECT WIREMOTOR AWG24/0, AWG#24, 400, PLAT DB A CONNECT WIREMOTOR AWG24/0, AWG#24, 700, PLAT 2 DB3029C MOTORSTEPPING GSP24RW045, DC2V, 40DB 4 3 DB630005A COVEROUT A ABS, T2, BLK 4 4 DB A COVEROUT B ABS, T2, BLK 5 DB A COVEROUT C ABS, T2.0, BLK 3 6 DB700003A PLATEHANGER STS304, T DB A FILTERAIR PP, T20, BLK 8 DB A ASSYGRILLE IN AG240E, ASSY 8 DB A GRILLEAIR INLET HIPS, DB A KBSLIDE HIPS 2 83 DB A SPRINGKB 0D 5.5, STS304, OD0.5, L DB A COVERKB HIPS 2 9 DB A ASSYWIRED REMOTE CONTROL KRH5020, ASSY 45

47 Outdoor unit UCH2400C/2800C UCC2800C/2400C

48 Exploded views and parts list Outdoor Unit Parts list CODE Description Specification Q TY ACC2400C ACC2800C ACH2400C ACH2800C DB L DB B DB L DB A DB A DB A DB G DB B DB A DB A DB C DB D DB A DB A DB96 006B DB A DB A DB B DB B DB D DB90 066D DB D DB F DB A DB A DB B DB C DB B DB A DB F DB A DB A DB A DB A DB A DB B DB B DB A DB A DB A DB62 400G DB62 400E DB D DB B DB A DB B DB C DB B DB C DB B DB B DB A PDDH3200S PDDH3200S3 DB L DB6 0052A DB A DB A DB A DB A ASS Y CABI FRONT ASS Y CABI FRONT ASS YBASE OUT FANPROPELLER FANPROPELLER BOLT SPECIAL MOTOR MOTOR BASEMOTOR ASS Y MOTOR BKT ASS YPARTITION ASS YPARTITION ASS YPARTITION ASS Y COND ASS Y COND ASS Y COND ASS Y COND ASS YCOVER CONTROL ASS Y CABI BACK CABINET SIDE ASS YCABI UPPER ASS YCOMP SCROLL ASS YCOMP SCROLL GROMMETCOMP NUTWASHER ASS Y TUBE4WAY V/V ASS Y SVS V/V 5/8 ASS Y TUBE4WAY V/V ASS Y SVS V/V 5/8 VALVESERVICE VALVE 4WAY VALVE 4WAY SWITCHPRESSURE SOLEIDCOIL ASS Y ASS Y TUBECHECK V/V ASS Y SVS V/V /4 ASS Y TUBECHECK V/V ASS Y SVS V/V /4 TUBECAPI CHECK TUBECAPI CHECK VALVESERVICE VALVESERVICE VALVECHECK ASS Y TUBE DISCHARGE ASS Y TUBE DISCHARGE ASSYBOX, CONTROL OUT ASSYBOX, CONTROL OUT ASSYBOX, CONTROL OUT ASSYBOX, CONTROL OUT SWITCHMAGNET SWITCHMAGNET SWITCHMAGNET COIL COIL ASSY PCB PARTS ASSY PCB PARTS TERMINALBLOCK CASEPCBOUT TRANSPOWER CFILM, MPEPPF CFILM, MPEPPF INSU COMP CLOTH SOUND ASS Y HEATER THERMAL FUSE ASS Y ASS Y AP7650 ABS+GF20, D495, 4BLADE ABS+GF20, D460, 4BLADE M6 OSM296SRC OSM626SRC SGCCM, T.6 SGCCM, T.6 ASS Y ASS Y ASS Y D5 FP.7, H/P D5 FP.3 D5 FP.3 D5 FP.7, H/P ASS Y, V5 ACH2800C, CASSETTETYPE ADH2400E, ASS Y SCROLL, ZR28K3PFV SCROLL, ZR24K3PFV EPDM, T4, BLK HEX, 2C, M8, ZPC 5/8, ASS Y 5/8, SUCTION 5/8, ASS Y 5/8, SUCTION 5/8 CHV03U CHV02U 20~240VAC, 2A, OFF33KG/cm 2 ON24KG/c CHV, 75C, 20~55C, 95%, 00M, 220/240V ASS Y, 3/8 ASS Y, /4 ASS Y, 3/8 ASS Y, /4 ID.7 x L350 ID.7 x L LT/H, 3/8 422LT/H, /4 C220T0,, 2.7, 30KG ASS Y ASS Y ASS Y ASS Y 220V60HZ, 25A, 4NB2AG 220V60HZ, 25A, 45DG20A, FLA25A 220V60HZ, 25A, 45CG20A, FLA20A 45µF, 450V, BK, 53x0mm, µF, 450V, BK, 53x0mm, 20.6 ASS Y 6P, 600V, 35A, NLNLCE, ADH2400E T2.5,, ABS, BLK, V5 DC7, AC230, DC7, DC0.6A 6000nF, +0~5%, 450V, BK, 58x25x40mm, 3000nF, +0~5%, 450V, BK, 58x25x40mm, T2 T2, W800, L350 ASS Y 2A

49 Exploded views and parts list UCC4400C

50 Exploded views and parts list Outdoor Unit Parts list CODE Description Specification Q TY UCC4400C DB A ASSY CABI FRONT ASS Y,SC90073T DB68062A LABELSAMSUNG HARD PC,T0.5,67.5, DB900055A ASSY CABI BACKLF RVSH040B2C0,SC90073T 3 DB A FANPROPELLER ABS+GF20,D495,4BLADE 2 4 DB300060E MOTOR OSM286SRC(S550) 5 DB300060F MOTOR FAN OSM286SRC(S55) 6 DB F ASSY MOUNT MOTORBASIC RVSH040H2C0,CASSETTETYPE 7 DB600398A SUPPORTER MOTOR SGCCM,T.6 8 DB63065A SUPPORTER FRAME SGCCM,T.2 9 DB A PARTITION SBHG,T,389.7X DB630365A SUPPORTERCOND SBHG,T.6,499X22 DB960262A ASSY CONDUP WAVE.7 DB B ASSYCOLLECTOR IN UP ASS Y, CI220T0 2 DB965007B ASSYCOLLECTOR OUT UP ASS Y, CI220T0 2 DB960267A ASSY CONDLOW WAVE.7 2 DB A ASSYCOLLECTOR IN LOW ASS Y, CI220T0 22 DB B ASSYCOLLECTOR OUT LOW ASS Y, CI220T0 3 DB630358B SUPPORTERUNIT OUT SGCCM,T.2 4 DB950279A ASS Y COMP CR42K6PFV, COPELAND 5 DB A INSULATION SOUND T2,W960,L380 FELT 6 DB A ASSY BASE OUT ASS Y,SC90073T 7 DB623554A TUBE SUCTION C220T00 8 DB623553A TUBE DISCHARGE C220T00 9 DB960775A ASS Y VALVE ASS Y, 3/8 20 DB960776A ASS Y VALVE ASS Y, 3/4 2 DB620002C DRYER C220T0, OD2.7, T DB9307A ASSY CONTROL OUT UCC4400C 450V 5.0UF 23 DB320002B THERMISTOR 03AT,0KOHM 24 DB340002A ASS Y HIGH PRESSURE S/W SAGIMIYA, 33K 25 DB A ASSY CABI BACKRH RVSH040B2C0,SC90073T 26 DB900044A ASSY COVERCONTROL ASM3500A,B, FLAME RETARDANT ABS 27 DB A ASSYCABI UPPER ASS Y,SC90073T 49

51 50 MEMO

52 5. Refrigerating Cycle Block Diagram 5 Model : ACH2800C Indoor Unit Outdoor Unit *Allowable pipe length : Max. 30m *Allowable drop distance : Max. 5m 3Way Valve Check Valve Capallary Tube Capillary Tube Capallary Tube Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Gas Side Reservior Cooling Heating Gas leak check point 3Way Valve Accumulator Compressor Muffler 4Way Valve High Pressure switch *Amount of refilling per extension length of m; When extending the pipe length by more than 5m, 40gr(50gr: Outdoor Unit is higher than Indoor Unit) of R22 refrigerant should be refilled per extension length of m. 5

53 52 Model : ACH2400C Indoor Unit Outdoor Unit *Allowable pipe length : Max. 30m *Allowable drop distance : Max. 5m 3Way Valve Check Valve Capallary Tube Capillary Tube Capallary Tube Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Gas Side Cooling Heating Gas leak check point 3Way Valve Accumulator Compressor Muffler 4Way Valve High Pressure switch *Amount of refilling per extension length of m; When extending the pipe length by more than 5m, 40gr(50gr: Outdoor Unit is higher than Indoor Unit) of R22 refrigerant should be refilled per extension length of m. 52

54 53 Model : ACC2400C, ACC2800C, ACC4400C Indoor Unit Outdoor Unit *Allowable pipe length : Max. 30m *Allowable drop distance : Max. 5m 3Way Valve Check Valve Capallary Tube Capillary Tube Capallary Tube Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Gas Side Cooling 3Way Valve Compressor High Pressure switch Gas leak check point *When extending the pipe length by more than 5m, A gr of R22 refrigerant should be refilled per extension length of m. (Refer to the table below for A.) A Model When indoor unit When outdoor unit is higher than is higher than outdoor unit indoor unit ACC2400C ACC2800C ACC4400C

55 54 MEMO

56 6. Wiring Diagrams 6 Indoor Unit ACH2400C/ACH2800C/ACC2800C/ACC2400C/ACC4400C CODE : DB A 55

57 62 Outdoor Unit UCC2800C/2400C CODE : DB A 56

58 Wirning Diagram UCH2800C/UCH2400C CODE : DB A 57

59 Wirning Diagram UCC4400C CODE : DB A 58

60 MEMO Samsung Electronics 59

61 7. Schematic Diagrams 7 Wired Remote Controller 60 Samsung Electronics

62 72 Centralized Controller Samsung Electronics 6

63 73 Indoor Unit 62 Samsung Electronics Samsung Electronics 63

64 74 Outdoor Unit (UCC2400C, UCC2800C, UCC4400C) 64 Samsung Electronics Samsung Electronics 65

65 Outdoor Unit (UCH2800C/UCH2400C) 66 Samsung Electronics Samsung Electronics 67

66 MEMO 68 Samsung Electronics

67 UPDATE LOG SHEET Application date Page Part# Note(Cause & Solution) S/Bulletin# Use this page to keep any special servicing information. (Service Bulletin, etc.) If only parts number changes, Just change parts number directly on parts list. And if you need more information, please see the service website. Itself Solution Integrated technology supporting electronic library Copyright 2002 By Samsung Electronics Co., Ltd. All rights reserved. This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or converted to any electronic or machine readable from without prior written permission of Samsung Electronics Co., Ltd. Printed in Korea.

68 MEMO 70 Samsung Electronics

69 MEMO Samsung Electronics 7

70 MEMO 72 Samsung Electronics

71 MEMO Samsung Electronics 73

72 MEMO 74 Samsung Electronics

73 MEMO Samsung Electronics 75

74 ELECTRONICS

SERVICE Manual AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT US12A2VC US09A2VA US07A2VA AS12A2VC AS09A2VA AS07A2VA. 1. Installation

SERVICE Manual AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT US12A2VC US09A2VA US07A2VA AS12A2VC AS09A2VA AS07A2VA. 1. Installation ROOM AIR CONDITIONER INDOOR UNIT ASAVC AS09AVA AS07AVA OUTDOOR UNIT USAVC US09AVA US07AVA SERVICE Manual AIR CONDITIONER CONTENTS. Installation. Disassembly and Reassembly. Troubleshooting 4. Exploded

More information

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UM27B1C3 INDOOR UNIT AM27B1C07 AM27B1C Installation. 2. Disassembly and Reassembly

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UM27B1C3 INDOOR UNIT AM27B1C07 AM27B1C Installation. 2. Disassembly and Reassembly ROOM AIR CONDITIONER INDOOR UNIT AM27BC07 AM27BC3 OUTDOOR UNIT UM27BC3 SERVICE Manual AIR CONDITIONER. Installation CONTENTS 2. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts

More information

6. Troubleshooting. 6-1 Basic items for trouble shooting. Samsung Electronics 17

6. Troubleshooting. 6-1 Basic items for trouble shooting. Samsung Electronics 17 6. Troubleshooting Since the inverter air conditioner is equipped with Electrical control circuits at both Indoor & outdoor unit, the trouble shooting shall be performed according to the error mode. Inside

More information

No Operation of air conditioner Explanation

No Operation of air conditioner Explanation 12. Troubleshooting 12-1 Items to be checked first 1. The input voltage should be rating voltage ±10% range. The air conditioner may not operate properly if the voltage is out of this range. 2. Is the

More information

SPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E

SPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit C24YE MC24Y3E MR24Y3E1 SPECIFICATIONS TYPE COOL & HEAT INDOOR UNIT MC24Y3E OUTDOOR UNIT MR24Y3E1 COOLING CAPACITY 23,500-22,500

More information

SPARE PARTS CATALOG OFFICE PRO 24

SPARE PARTS CATALOG OFFICE PRO 24 SPARE PARTS CATALOG Table of Contents No. UNIT PART NUMBER SERIAL NUMBER RANGE REFRIGERANT SECTION 1 GX484000-681 GX484000-680 0407XXXX240 to Present R410A Page to 1 SP0025-02 2 LA484000-410 LA484000-290

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................

More information

5. Exploded Views and Parts List 5-1 Indoor Unit

5. Exploded Views and Parts List 5-1 Indoor Unit 5. Exploded Views and Parts List 5-1 Indoor Unit 5-1 Exploded Views and Parts List Parts List No. Code No. Description Specification 1 Q TY AQV18VBAN AQV18VSAN AQV24VBAN AQV24VSAN DB92-00926C ASSY PANEL

More information

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYA24LCC ASYA24LCC ASYA24LCC Outdoor unit AOYR24LCC AOYR24LCD AOYR24LCL CONTENTS SPECIFICATIONS..................1 DIMENSIONS.....................

More information

SPARE PARTS CATALOG OFFICE PRO 60

SPARE PARTS CATALOG OFFICE PRO 60 SPARE PARTS CATALOG Table of Contents No. UNIT PART NUMBER PRODUCTION PERIOD REFRI- GERANT SECTION ISSUE DATE (mm/ yy) 1 GX484000-3690 FROM April 2007 (0407) TO Present R410A SP0010-01 Page 3 ~ 13 04/

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC. Models Indoor unit Outdoor unit

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC. Models Indoor unit Outdoor unit SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit Outdoor unit ASY9USBCW AOY9UGBC ASY12USBCW AOY12UGBC CONTENTS SPECIFICATIONS....................... 1 OUTLINE AND DIMENSIONS............

More information

SPARE PARTS CATALOG OFFICE PRO 18. DocID: 00G00077EB

SPARE PARTS CATALOG OFFICE PRO 18. DocID: 00G00077EB SPARE PARTS CATALOG DocID: 00G00077EB Table of Contents No. UNIT PART NUMBER SERIAL NUMBER RANGE REFRIGERANT SECTION 1 GX8000-711 GX8000-710 007XXXX180 to Present (From April 2007 to Present) R10A Page

More information

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UM26A1C2 UM18A1C2 INDOOR UNIT AM26A1C13 AM18A1C Installation. 2. Disassembly and Reassembly

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UM26A1C2 UM18A1C2 INDOOR UNIT AM26A1C13 AM18A1C Installation. 2. Disassembly and Reassembly ROOM AIR CONDITIONER INDOOR UNIT AM6AC3 AM8AC09 OUTDOOR UNIT UM6AC UM8AC SERVICE Manual AIR CONDITIONER. Installation CONTENTS. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts

More information

SPARE PARTS CATALOG. 24HFU and 24HFU-1

SPARE PARTS CATALOG. 24HFU and 24HFU-1 SPARE PARTS CATALOG 24HFU and 24HFU-1 DENSO SALES CALIFORNIA, INC. REGISTERED TO ISO 9002 FILE NO. A557 (800) 264-957 www.movincool.com 2000 DENSO SALES CALIFORNIA, INC. All rights reserved. This book

More information

SPARE PARTS CATALOG OFFICE PRO 60

SPARE PARTS CATALOG OFFICE PRO 60 SPARE PARTS CATALOG Table of Contents No. UNIT PART NUMBER SERIAL NUMBER RANGE REFRIGERANT SECTION 1 GX484000-3691 GX484000-3690 0407XXXX600 to Present (From April 2007 to Present) R410A Page 3 to 13 SP0010-03

More information

SERVICE Manual AIR CONDITIONER INDOOR UNIT AS24A2RC AS18A6RC AS18A0RCD OUTDOOR UNIT US24A2RC US18A6RC US18A0RCD. 1. Installation

SERVICE Manual AIR CONDITIONER INDOOR UNIT AS24A2RC AS18A6RC AS18A0RCD OUTDOOR UNIT US24A2RC US18A6RC US18A0RCD. 1. Installation ROOM AIR CONDITIONER INDOOR UNIT AS4ARC AS8A6RC AS8A0RCD OUTDOOR UNIT US4ARC US8A6RC US8A0RCD SERVICE Manual AIR CONDITIONER. Installation CONTENTS. Disassembly and Reassembly 3. Troubleshooting 4. Exploded

More information

PANcharge1k Battery Charger User's Manual

PANcharge1k Battery Charger User's Manual PANcharge1k Battery Charger User's Manual Ver.1.00E Table of Contents 1. Important Safety Instructions... 3 1-1 General Safety Precautions... 3 1-2 Battery Precautions... 3 1-3 Electromagnetic Disturbance...

More information

10. EXPLODED VIEW AND PART LIST

10. EXPLODED VIEW AND PART LIST 10. EXPLODED VIEW AND PART LIST 1 INDOOR UNIT TAS-12H l 49 Indoor Unit Part List (TAS-12H) Caution : In this Manual, some parts can be changed for improving, their performance without notice in the parts

More information

SPARE PARTS CATALOG OFFICE PRO W20

SPARE PARTS CATALOG OFFICE PRO W20 SPARE PARTS CATALOG DocID: 00G0007E Table of Contents No. UNIT PART NUMBER PRODUCTION PERIOD REFRI- GERANT SECTION ISSUE DATE (mm/ yy) 1 GX484000-420 FROM January 2011 (0111) TO Present R410-A Page ~ 15

More information

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4.

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. SYSTEM AIR CONDITIONER 4 WAY CASSETTE SERIES INDOOR UNIT Model : AC018NN4DCH/AA AC024NN4DCH/AA AC030NN4DCH/AA AC036NN4DCH/AA AC042NN4DCH/AA AC048NN4DCH/AA OUTDOOR UNIT AC018JXADCH/AA AC024JXADCH/AA AC030JXADCH/AA

More information

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5.

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5. SYSTEM AIR CONDITIONER 4 WAY CASSETTE SERIES Model : INDOOR UNIT AC052MN4DKH AC071MN4DKH AC090MN4DKH AC100MN4DKH AC120MN4DKH AC140MN4DKH OUTDOOR UNIT AC090MXADKH AC100MXAD H AC120MXAD H AC140MXAD H AIR

More information

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-90EB RO-90EPB C O N T E N T S SPECIFICATIONS... OUTLINE AND DIMENSIONS... CIRCUIT DIAGRAM...5 REFRIGERANT SYSTEM DIAGRAM...6

More information

CASSETTE type SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS

CASSETTE type SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit AUU8RC AUU4RC AOU8RC AOU4RC CONTENTS SPECIFICATIONS........................................ OUTLINE AND DIMENSIONS..............................

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-25CA RCW-30CA RO-25A RO-30A C O N T E N T S SPECIFICATIONS........................................ 1 OUTLINE AND DIMENSIONS..............................

More information

5. Exploded Views and Parts List

5. Exploded Views and Parts List 5. Exploded Views and Parts List Operating Instructions and Installation 5 Indoor Unit 3 3 4 4 2 2 4 07 0 03 8 8 6 5 5 72 7 73 09 0 04 05 02 9 92 93 7 74 00 06 95 96 0 08 94 97 99 9 98 90 92 9 02 Samsung

More information

2. LS-Q096AAG, LS-Q096AAL, LS-Q096ACG LS-Q096ADL, LS-Q096ADG, LS-Q096BAG LS-Q096BAG, LS-Q096BDG, LS-Q096BDL LS-Q082BAM CN-TH TRIAC MOTOR CN-U/D STEP

2. LS-Q096AAG, LS-Q096AAL, LS-Q096ACG LS-Q096ADL, LS-Q096ADG, LS-Q096BAG LS-Q096BAG, LS-Q096BDG, LS-Q096BDL LS-Q082BAM CN-TH TRIAC MOTOR CN-U/D STEP Wiring Diagram (1) Indoor Unit 1. LS-Q076A, LS-Q076BBG, LS-Q076BEL LS-Q096A, LS-Q096ABG, LS-Q066AHG LS-Q096AEL, LS-Q096BBG, LS-Q096ABM LS-Q096AEM 2. LS-Q096AAG, LS-Q096AAL, LS-Q096ACG LS-Q096ADL, LS-Q096ADG,

More information

4. Exploded Views and Parts List

4. Exploded Views and Parts List 4. Exploded Views and Parts List 4 Indoor Unit 6 7 7 8 5 6 4 4 9 5 5 6 8 54 4 8 7 5 5 8 5 You can search for the updated part code number through the ITSELF. URL : http://itself.sec.samsung.co.kr 4 Parts

More information

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UD26A1C2 UD18A1C2 INDOOR UNIT AD26A1C13 AD18A1C Installation. 2. Disassembly and Reassembly

SERVICE Manual AIR CONDITIONER OUTDOOR UNIT UD26A1C2 UD18A1C2 INDOOR UNIT AD26A1C13 AD18A1C Installation. 2. Disassembly and Reassembly ROOM AIR CODITIOER IDOOR UIT AD6AC3 AD8AC09 OUTDOOR UIT UD6AC UD8AC SERVICE Manual AIR CODITIOER. Installation COTETS. Disassembly and Reassembly 3. Troubleshooting 4. Exploded Views and Parts List 5.

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE Indoor unit AGYF09LAC AGYFLAC AGYFLAC AGYFLAC Outdoor unit AOYV09LAC AOYVLAC AOYVLAC AOYVLAL CONTENTS SPECIFICATIONS..................... DIMENSIONS.........................

More information

Prodigy Eclipse ECC, EH330 and EH430 C or D Service Parts

Prodigy Eclipse ECC, EH330 and EH430 C or D Service Parts This part list contains the service parts for the Eclipse 00, 00, and 800 systems. D series models began early 0 The models that are covered include: EH0 C & D EH0 C & D ECC00 ECC00 ECC800 Contents Head

More information

Eclipse 2000 Service Parts

Eclipse 2000 Service Parts This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior

More information

HEAVY DUTY POWER RELAYS FEATURES

HEAVY DUTY POWER RELAYS FEATURES VDE VC HEAVY DUTY POWER RELAYS VC RELAYS Faston terminal Screw terminal mm 9 FEATURES VC power relays are designed for controlling heavy duty loads safely: Contact gap of 3 mm or more -point contacts for

More information

SPARE PARTS CATALOG CM 12. DocID: 00G00065E

SPARE PARTS CATALOG CM 12. DocID: 00G00065E SPARE PARTS CATALOG CM 12 DocID: 00G00065E Table of Contents No. UNIT PART PRODUCTION PERIOD REFRI- GERANT SECTION ISSUE DATE (mm/ yy) 1 484000-3940 FROM January 2009 (0109) TO Present R410A Page 3 ~ 12

More information

FTXS50EV1B, FTXS60EV1B (RoHS application) FTXS50EV1B, FTXS60EV1B Wiring Diagram

FTXS50EV1B, FTXS60EV1B (RoHS application) FTXS50EV1B, FTXS60EV1B Wiring Diagram 42 FTXS50EV1B, FTXS60EV1B (RoHS application) FTXS50EV1B, FTXS60EV1B Diagram FTXS50EV1B, FTXS60EV1B (RoHS application) 43 44 FTXS50EV1B, FTXS60EV1B (RoHS application) Parts Parts Name Drwg. Parts Model

More information

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi 1 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTE... 3 FAULT FINDING AND DIAGNOSTICS... 3 ABBREVIATIONS... 3 PCB S... 4 OUTDOOR MAIN PCB... 4 INDOOR PCB...

More information

Oil Cooler AKZ328-D142 PL

Oil Cooler AKZ328-D142 PL Oil Cooler PL-1009-15 1 2 Parts Parts Name Drwg. Parts Model & Specifi cation A1 A 1250093 SWING COMPRESSOR 1YC23HXD 1 M2C A2 0401393 RUBBER BUSH/ LEAD WIRE W443132-2 1 A4 390204 NUT WITH WASHER R4911377-1

More information

SPARE PARTS CATALOG CLASSIC 40. DocID: 00G00086EA

SPARE PARTS CATALOG CLASSIC 40. DocID: 00G00086EA SPARE PARTS CATALOG DocID: 00G00086EA Table of Contents No. UNIT PART NUMBER PRODUCTION PERIOD REFRI- GERANT SECTION ISSUE DATE (mm/'yy) 1 GX484000-4090 FROM May 2009 (0509) TO Present R410A Page 3 ~ 13

More information

Fault Codes. J control

Fault Codes. J control J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the

More information

SYSTEM AIR CONDITIONER

SYSTEM AIR CONDITIONER SYSTEM AIR CONDITIONER INDOOR UNIT AC071MN4PKH AC090MN4PKH AC100MN4PKH AC120MN4PKH AC140MN4PKH CIRCULAR CASSETTE SERIES OUTDOOR UNIT AC090MXADKH AC100MXAD*H AC120MXAD*H AC140MXAD*H SYSTEM AIR CONDITIONER

More information

Parts Lists. Forward Series. Rev. Feb. 2017

Parts Lists. Forward Series. Rev. Feb. 2017 s HSU09VHJ(DB)-G / HSU09VHJ(DB)-W HSU12VHJ(DB)-G / HSU12VHJ(DB)-W HSU18VHJ(DB)-G / HSU18VHJ(DB)-W HSU24VHJ(DB)-G / HSU24VHJ(DB)-W 1800 Valley Road Wayne, NJ 07470 Tel +973.617.1800 www.haier.com - Edition

More information

9. Maintenance. 9.1 Precautions before Maintenance. Service Manual. electrolytic capacitor after power off. maintenance safely.

9. Maintenance. 9.1 Precautions before Maintenance. Service Manual. electrolytic capacitor after power off. maintenance safely. 9. Maintenance 9.1 Precautions before Maintenance electrolytic capacitor after power off. A B A B maintenance safely. 50 9.2 Error Code List Unit o. ame Display 8 nixie 0.5s) Operation Indicator Cool Indicator

More information

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART. Vi håper de får stor glede av et Novema kulde produkt!

Driftsinstruks. Utopia kontroller feilkoder PCP-2HTE og PC-ART.   Vi håper de får stor glede av et Novema kulde produkt! Driftsinstruks Utopia kontroller feilkoder PCP-2HTE og PC-ART Vi håper de får stor glede av et vema kulde produkt! www.novemakulde.no 8/14 TROUBLESHOOTING 8.2. TROUBLESHOOTING PROCEDURE 8.2.1. ALARM CODE

More information

PRODUCT CODE MODEL NAME RASC-10HNPE. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty REMARKS

PRODUCT CODE MODEL NAME RASC-10HNPE. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty REMARKS 7E343107 RASC-4HNPE RASC-5HNPE RASC-6HNPE 7E343108 7E343109 No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty REMARKS 1 Foot Assy XEK38712 A E04359 1 1 1 Assembly 1 Foot Assy XEK39008 A E04384 1 1 Assembly

More information

SPARE PARTS CATALOG CLASSIC 40

SPARE PARTS CATALOG CLASSIC 40 SPARE PARTS CATALOG Table of Contents No. UNIT PART NUMBER SERIAL NUMBER RANGE REFRI- GERANT SECTION 1 GX484000-4090 0509XXXXC40 to Present (From May 2009 to Present) R410A Page 3 ~ 13 SP0031-03 2 484000-3630

More information

Service Manual. 9. Maintenance. 9.1 Precautions before Maintenance. discharge resistance or plug of soldering iron. Installation and Maintenance

Service Manual. 9. Maintenance. 9.1 Precautions before Maintenance. discharge resistance or plug of soldering iron. Installation and Maintenance 9. Maintenance 9.1 Precautions before Maintenance Service Manual pacitor after power off. - discharge resistance or plug of soldering iron A B A B - nance safely. 40 9.2 Error Code List O. 1 2 3 4 5 6

More information

CHILLER MANUAL. SAM JUNG ENC CO.,LTD.

CHILLER MANUAL. SAM JUNG ENC CO.,LTD. CHILLER MANUAL SAM JUNG ENC CO.,LTD. http:/www.speedchiller.com E-Mail: sskim8913@naver.com 756-1, Kwarim-dong, shiheung-city, Kyeong-ki 429-120, Korea TEL: 02)2686-3315~6 / 02)2686-3658 FAX: TEL02)2686-3317

More information

PL Split Indoor Units (RoHS application) CDKS30JVLT CDKS40JVLT CDXS30JVLT CDXS40JVLT

PL Split Indoor Units (RoHS application) CDKS30JVLT CDKS40JVLT CDXS30JVLT CDXS40JVLT Split Indoor Units (RoHS application) CDKS30 CDKS40 CDXS30 CDXS40 Sky Air, Packaged Indoor Units (RoHS application) 25, 30, 40, 50, 60 PL-1007-1 CDKS30 (RoHS application) 1 2 CDKS30 (RoHS application)

More information

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units Universal and Multi Split Units If there is a fault on any LG Universal or Multi unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller

More information

Prodigy Eclipse 600, 800, 1000 Service Parts

Prodigy Eclipse 600, 800, 1000 Service Parts Prodigy Eclipse 600, 00, 000 Service Parts This part list contains the service parts for the Eclipse 600, 00 and 000 systems. The B series references changes to panels. The models that are covered include:

More information

CDK25JVEC, CDK35JVEC, CDX25BVMC, CDX25BVMC9, CDX25JVEC, CDX35BVMC, CDX35BVMC9, CDX35JVEC, CDX50AVMC9, CDX60AVMC9 CDK35HAVER1, CDK60HAVER1

CDK25JVEC, CDK35JVEC, CDX25BVMC, CDX25BVMC9, CDX25JVEC, CDX35BVMC, CDX35BVMC9, CDX35JVEC, CDX50AVMC9, CDX60AVMC9 CDK35HAVER1, CDK60HAVER1 Split, Multi Type Room Air Conditioner Split Indoor Units CDK25JVEC, CDK35JVEC, 25BVMC, 25BVMC9, 25JVEC, 35BVMC, 35BVMC9, 35JVEC, 50AVMC9, 60AVMC9 CDK35HAVER1, CDK60HAVER1 Packeged Type Air Conditioner-Indoor

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS RO-25A RO-25RA RO-30A RO-30RA RC-25A RC-25RA RC-30A RC-30RA

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit CONTENTS RO-25A RO-25RA RO-30A RO-30RA RC-25A RC-25RA RC-30A RC-30RA SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RC-25A RC-25RA RC-30A RC-30RA RO-25A RO-25RA RO-30A RO-30RA CONTENTS SPECIFICATIONS........................................

More information

12. Troubleshooting Items to be checked first. Samsung Electronics

12. Troubleshooting Items to be checked first. Samsung Electronics 12. Troubleshooting 12-1 Items to be checked first 1. The input voltage should be rating voltage ±10% range. The air conditioner may not operate properly if the voltage is out of this range. 2. Is the

More information

Prodigy Eclipse 600, 800, 1000 Service Parts

Prodigy Eclipse 600, 800, 1000 Service Parts Prodigy Eclipse 600, 800, 000 Service Parts This part list contains the service parts for the Eclipse 600, 800 and 000 systems. The B series references changes to panels. The models that are covered include:

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit Outdoor unit RSW-17AC ROW-17AC C O N T E N T S SPECIFICATIONS........................................ 1 REFRIGERANT SYSTEM DIAGRAM........................

More information

Elegant. Floor Standing Split Systems 53QFJ HEAT PUMP SPARE PARTS MANUAL

Elegant. Floor Standing Split Systems 53QFJ HEAT PUMP SPARE PARTS MANUAL R22 220-240V ~ 50Hz 1Ph 380-420V ~ 50Hz 3Ph Elegant Floor Standing Split Systems 53QFJ 36-48 HEAT PUMP SPARE S MANUAL Carrier is committed to continuously improving its products according to national and

More information

KSID MINI Split DC Inverter QUICK CONNECT Air Conditioner TROUBLESHOOTING KSID016-H215Q. Model Numbers:

KSID MINI Split DC Inverter QUICK CONNECT Air Conditioner TROUBLESHOOTING KSID016-H215Q. Model Numbers: KSID MINI Split DC Inverter QUICK CONNECT Air Conditioner TROUBLESHOOTING Model Numbers: KSID012-H115Q KSID022-H215Q KSID016-H215Q WARNING Installation MUST conform with local building codes or, in the

More information

SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type

SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit ARY7RLB AOY7RGA CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... 2 CIRCUIT DIAGRAM... 3 INDOOR P. C. BOARD CIRCUIT DIAGRAM...

More information

SPARE PARTS MANUAL. Specifications are subject to change without notice according to Carrier Policy of continuous development. Revision : (0)

SPARE PARTS MANUAL. Specifications are subject to change without notice according to Carrier Policy of continuous development. Revision : (0) SPARE PARTS MANUAL Specifications are subject to change without notice according to Carrier Policy of continuous development. 03502525 Revision : (0) - 2009 EXPLODED VIEW OF INDOOR UNIT PART LIST OF INDOOR

More information

SERVICE MANUAL TAC-600 SPARE PARTS FOR AIR CONDITIONER MODELS ANS ANS 50 ANS 60 ANS 65 ANS 77 ANS OCT ELECTRONIC CONTROL

SERVICE MANUAL TAC-600 SPARE PARTS FOR AIR CONDITIONER MODELS ANS ANS 50 ANS 60 ANS 65 ANS 77 ANS OCT ELECTRONIC CONTROL S TA R T S TO P D A I LY POWER TIMER AIR CON. FILTER START STOP 1 2 3 SLEEP DAILY MODE FAN SWEEP WIRELESS DIGIT AL REMOTE CONTROLLER ANS 51302651021 SERVICE MANUAL SPARE PARTS FOR AIR CONDITIONER MODELS

More information

FBQ125KMV2C (RoHS application) FBQ125KMV2C Wiring Diagram

FBQ125KMV2C (RoHS application) FBQ125KMV2C Wiring Diagram FBQ125KMV2C (RoHS application) FBQ125KMV2C Diagram 167 FBQ125KMV2C (RoHS application) 168 FBQ125KMV2C (RoHS application) Parts Parts Name Drwg. Parts Model & Specifi cation FBQ125KMV2C B1 6002954 EVAPORATOR

More information

Service Manual No-Frost Combi-Refrigerator

Service Manual No-Frost Combi-Refrigerator Service Manual No-Frost Combi-Refrigerator Models: ERF-366N, 366A ERF-396N, 396A ERF-416N, 416A DAEWOO ELECTRONICS MANUFACTURING ESPAÑA, S.A. . CONTENTS 1. SPECIFICATIONS 2. EXTERNAL DRAWINGS 3. REAL VIEW

More information

LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS

LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS www.source1parts.com HVAC SERVICE PARTS Supersedes: Nothing 035-23403-001 Rev. A (0912) 1 of 10 Figure 1: MULTI-SPLIT DUCTLESS SYSTEM Outdoor Model Number

More information

technical data air conditioning systems MXS-B Multi Application Split Sky Air

technical data air conditioning systems MXS-B Multi Application Split Sky Air technical data MXS-B Multi Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment

More information

ASU18RLB ASU24RLB AOU18RLB AOU24RLB SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS

ASU18RLB ASU24RLB AOU18RLB AOU24RLB SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASU8RL ASURL Outdoor unit AOU8RL AOURL CONTENTS SPECIFICATIONS................... DIMENSIONS...................... REFRIGERANT SYSTEM DIAGRAM....

More information

NM1250R SERVICE PARTS

NM1250R SERVICE PARTS This section contains the parts illustrations and parts lists for the NM150R. When ordering parts of assemblies, to avoid costly delays and errors in shipment, give the part number, the complete description

More information

PRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS

PRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS ERSATZTEILE RAS-4HNC1E, 3~ 400V 50Hz RAS-5HNC1E, 3~ 400V 50Hz RAS-6HNC1E, 3~ 400V 50Hz 1 Rear Cover Assy XEK24870 A E03946 1 1 1 1 1 1 Assembly 1-1 Pipe Cover B 17C86251 A P27003 1 1 1 1 1 1 1-2 Handle

More information

MODEL : 55A240IUBEM ROTARY COMPRESSOR SPECIFICATION SHEET 1. APPLICATION 2. COMPRESSOR DATA 3. MOTOR DATA 4. ELECTRICAL COMPONENTS

MODEL : 55A240IUBEM ROTARY COMPRESSOR SPECIFICATION SHEET 1. APPLICATION 2. COMPRESSOR DATA 3. MOTOR DATA 4. ELECTRICAL COMPONENTS SPECIFICATION SHEET 1. APPLICATION H/P & Cooling Type Air conditioner Rated & Frequency... 208~230V 1Φ 60Hz Refrigerant.. R-22 2. COMPRESSOR DATA Pump Type Rolling Piston Type Displacement. 33.43cc/rev

More information

NM650 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor...

NM650 SERVICE PARTS TABLE OF CONTENTS. Cabinet Air Cooled Refrigeration Water Cooled Refrigeration Water System Gearmotor... This parts list contains the service parts and wiring diagrams for this model. Check the model number in question to be sure that it is applicable to this parts list. Caution: This model ice maker has

More information

For more Parts Information:

For more Parts Information: For more Parts Information: https://manitowocfsg.sysonline.com/default.aspx TABLE OF CONTENTS Manitowoc Foodservice [Updated: Apr. 23, 2015] Manitowoc - Ice & Related Parts Catalog Ice Machine Indigo Series

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2012.10 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram 8. Capacity tables 9. Electric characteristics

More information

PREMIUM SERIES 22 SEER SINGLE SPLIT DUCTLESS, COOLING SYSTEMS (CONTAINS INDOOR AND OUTDOOR MODELS)

PREMIUM SERIES 22 SEER SINGLE SPLIT DUCTLESS, COOLING SYSTEMS (CONTAINS INDOOR AND OUTDOOR MODELS) www.source1parts.com HVAC SERVICE PARTS PREMIUM SERIES 22 SEER SINGLE SPLIT DUCTLESS, COOLING SYSTEMS (CONTAINS INDOOR AND OUTDOOR MODELS) Supersedes: Nothing 035-23394-001 Rev. A (0912) 1 of 16 Figure

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners YD360/480/600, YJ-30/-40/-50 and J30/40/50 YD Models 642546-UAI-A-080 GENERAL Standard operation

More information

For more Parts Information:

For more Parts Information: For more Parts Information: https://manitowocfsg.sysonline.com/default.aspx TABLE OF CONTENTS Manitowoc Foodservice [Updated: Sep. 30, 2013] Manitowoc - Ice & Related Parts Catalog Ice Machine S Series

More information

Split-Sky Air FDYP-B7 Concealed Ceiling Unit

Split-Sky Air FDYP-B7 Concealed Ceiling Unit TECHNICAL DATA Split-Sky Air FDYP-B7 Concealed Ceiling Unit Split Sky Air ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU18RLXFW AOU24RLXFW ASU18RLF ASU24RLF R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU18RLXFW AOU24RLXFW ASU18RLF ASU24RLF R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU18RLF ASU24RLF AOU18RLXFW AOU24RLXFW R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL OPERATION

More information

34.0 EMF SERIES FLAKERS EMF 450, EMF800, EMF1106 AIR, WATER AND REMOTE

34.0 EMF SERIES FLAKERS EMF 450, EMF800, EMF1106 AIR, WATER AND REMOTE Shaded Code indicates updated information AIR COOLED 5 Air Condenser 9141002-01 X 5 Air Condenser 9141017-01 X 5 Air Condenser 9141046-01 X 10 Fan Blade 9131133-02 10 Fan Blade 9131133-01 X 10 Fan Blade

More information

NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B)

NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B) www.source1parts.com HVAC SERVICE PARTS NL SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (R-410A, STYLE B) Supersedes:Nothing 035-23123-001 Rev. A (1011) 1 of 8 CONDENSER ROOF (SEE FIGURE 2) EVAPORATOR

More information

C1448, C1848, C2148 Service Parts

C1448, C1848, C2148 Service Parts C8, C88, C8 Service Parts This part list contains the service parts for the air cooled, water cooled and remote air cooled C8, C88, C8 ice machines. To avoid costly and time consuming errors, double check

More information

troubleshooting Outdoor Unit: KSIE009-H221-O, KSIE012-H220-O, KSIE018-H220-O KSIE024-H220-O, KSIR036-H218, KSIR048-H218

troubleshooting Outdoor Unit: KSIE009-H221-O, KSIE012-H220-O, KSIE018-H220-O KSIE024-H220-O, KSIR036-H218, KSIR048-H218 troubleshooting Table of Contents 1. Troubleshooting Model Numbers: Indoor Unit: KDIR09-H2, KTIR09-H2, KUIR09-H2 KDIR12-H2; KTIR12-H2, KUIR12-H2 KDIR18-H2, KTIR18-H2, KUIR18-H2 KDIR24-H2, KTIR24-H2, KUIR24-H2

More information

SPARE PARTS MANUAL. Specifications are subject to change without notice according to Carrier Policy of continuous development. Rev.

SPARE PARTS MANUAL. Specifications are subject to change without notice according to Carrier Policy of continuous development. Rev. SPARE PARTS MANUAL Specifications are subject to change without notice according to Carrier Policy of continuous development. 03502523 Rev. (0) -2009 TABLE OF CONTENTS PAGE NO. 1. Unit Model Designation

More information

Parts Lists. Novel Series. Rev. Feb. 2017

Parts Lists. Novel Series. Rev. Feb. 2017 s HSU09VHG(DB)-G / HSU09VHG(DB)-W HSU12VHG(DB)-G / HSU12VHG(DB)-W HSU18VHG(DB)-G / HSU18VHG(DB)-W HSU24VHG(DB)-G / HSU24VHG(DB)-W 1800 Valley Road Wayne, NJ 07470 Tel +973.617.1800 www.haier.com - Edition

More information

TOP-MOUNT REFRIGERATOR. Frigidaire P.O. BOX 8020 CHARLOTTE, NC Model No. FFHT2021T

TOP-MOUNT REFRIGERATOR. Frigidaire P.O. BOX 8020 CHARLOTTE, NC Model No. FFHT2021T Product No. B0 W0 Series R134a R134a Color black white Volts 115 115 Wiring Diagram A02646801 A02646801 Owner's Guide Eng/Spn 807876506 807876506 Owner's Guide Frn 807877206 807877206 Market North America

More information

FM800R SERVICE PARTS

FM800R SERVICE PARTS This parts list contains the service parts and wiring diagrams for this model. Check the model number in question to be sure that it is applicable to this parts list. Caution: This model ice maker has

More information

SkyAir, Packaged Outdoor Units (RoHS application) RQ71KBV4A, RZQ71KBV1, RZQ71KBV4A, RZQ100KBV1 RZQ150HY4A RZQ150KV4A PL-908-1

SkyAir, Packaged Outdoor Units (RoHS application) RQ71KBV4A, RZQ71KBV1, RZQ71KBV4A, RZQ100KBV1 RZQ150HY4A RZQ150KV4A PL-908-1 SkyAir, Packaged Outdoor Units (RoHS application) RQKBV4A, KBV1, KBV4A, 100KBV1 150HY4A 150KV4A PL-908-1 RQKBV4A / KBV1 / KBV4A / 100KBV1 (RoHS application) RQKBV4A / KBV1 / KBV4A / 100KBV1 (RoHS application)

More information

Fan Coil Units. Technical Data ECDEN FWL-DT/DF

Fan Coil Units. Technical Data ECDEN FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF TABLE OF CONTENTS FWL-DT/DF 1 Features.............................................................

More information

SYSTEM AIR CONDITIONER

SYSTEM AIR CONDITIONER SYSTEM AIR CONDITIONER INDOOR UNIT AC018KN4DCH AC024KN4DCH AC030KN4DCH AC036KN4DCH AC042KN4DCH AC048KN4DCH CIRCULAR CASSETTE SERIES OUTDOOR UNIT AC018JX4DCH AC024JX4DCH AC030JX4DCH AC036JX4DCH AC042JX4DCH

More information

This air conditioner uses new refrigerant HFC (R410A).

This air conditioner uses new refrigerant HFC (R410A). This air conditioner uses new refrigerant HFC (R40A). 5 cm or over The basic installation work procedures are the same as conventional refrigerant models. However, pay careful attention to the following

More information

LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS

LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS LX SERIES 16 SEER MULTI-SPLIT DUCTLESS, HEAT PUMPS www.source1parts.com HVAC SERVICE PARTS Supersedes: 035-23403-001 Rev. B (1213) 035-23403-001 Rev. C (0114) 1 of 10 Figure 1: MULTI-SPLIT DUCTLESS SYSTEM

More information

Exploded Views and Parts List 1. AG015KSVAFH/AA. Exploded View. Copyright SAMSUNG. All rights reserved.

Exploded Views and Parts List 1. AG015KSVAFH/AA. Exploded View. Copyright SAMSUNG. All rights reserved. Exploded Views and Parts List 1. AG015KSVAFH/AA Exploded View Copyright 1995-2016 SAMSUNG. All rights reserved. 1 Parts List 1 2 DB61-06633A BRACKET-BODY; GI-SGCC,T0.8 2 2 DB61-06642A BRACKET TUBE; EGI-SECC,T2.0,EARTH

More information

For more Parts Information: https://manitowocfsg.sysonline.com/default.aspx

For more Parts Information: https://manitowocfsg.sysonline.com/default.aspx For more Parts Information: https://manitowocfsg.sysonline.com/default.aspx TABLE OF CONTENTS Manitowoc Foodservice [Updated: Sep. 30, 2013] Manitowoc - Ice & Related Parts Catalog Ice Machine S Series

More information

14 EXPLODED DIAGRAM/PARTS LIST. SMMS-i OUTDOOR UNIT MMY-MAP0804HT8P, MMY-MAP1004HT8P, MMY-MAP1204HT8P

14 EXPLODED DIAGRAM/PARTS LIST. SMMS-i OUTDOOR UNIT MMY-MAP0804HT8P, MMY-MAP1004HT8P, MMY-MAP1204HT8P 4 EXPLODED DIAGRAM/PARTS LIST SMMS-i OUTDOOR UNIT MMY-MAP0804, MMY-MAP004, MMY-MAP04 035 00 00 0 064 065 004 058 037 053 036 003 06 059 007 009 068 077 05 060 055 89 040 00 03 046 050 078 045 046 078 044

More information

PL-604. Compressor 3H64QML-F. Split Indoor Units FTYN25DV1A, FTYN35DV1A FTYN50DV1A FTYN60DV1A. Decolation Panels BYCP125K-W1

PL-604. Compressor 3H64QML-F. Split Indoor Units FTYN25DV1A, FTYN35DV1A FTYN50DV1A FTYN60DV1A. Decolation Panels BYCP125K-W1 Split Indoor Units FTYN25DV1A, FTYN35DV1A FTYN50DV1A FTYN60DV1A VRV Indoor Units CBXLS71DV2C CDXLS28DV2C, CDXLS36DV2C CDXLS56DV2C CDXLS71DV2C FDYQ16PFY1L, FDYQ20PFY1L FJDP22NVC, FJDP25NVC, FJDP28NVC FJDP63MVC,

More information

TOP-MOUNT REFRIGERATOR. Frigidaire P.O. BOX 8020 CHARLOTTE, NC Model No. FFTR18G2Q

TOP-MOUNT REFRIGERATOR. Frigidaire P.O. BOX 8020 CHARLOTTE, NC Model No. FFTR18G2Q Product No. S1 W1 Series R134a R134a Color stainless white Volts 115V 115V Wiring Diagram A01475501 A01475501 Owner's Guide 807332458 807876505 Market North America North America Energy Guide 807332458

More information

SERVICE MANUAL R407C SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS. August No.OC336. Outdoor unit [model names]

SERVICE MANUAL R407C SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS. August No.OC336. Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS August 00 No.OC SERVICE MANUAL R07C Outdoor unit [model names] PUH-PVGAA PUH-PVGAA PU-PVGAA [Service Ref.] Service Ref. is on page. This

More information

Split-Sky Air RMX-JZ Super Multi Plus

Split-Sky Air RMX-JZ Super Multi Plus TECHNICAL DATA Split-Sky Air RMX-JZ Super Multi Plus Split Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment from the potential

More information

Unitary Air Conditioner Indoor Unit Service Manual R22/R410A,60/50HZ (GC I)

Unitary Air Conditioner Indoor Unit Service Manual R22/R410A,60/50HZ (GC I) R22/R410A,60/50HZ (GC201208-I) CONTENTS PRODUCT...2 1 MODELS LIST... 2 1.1 Air Handler...2 1.2 Fan Coil...2 1.3 Floor Ceiling...3 2 NOMENCLATURE... 3 3 FUNCTION... 4 4 PRODUCT DATA... 4 4.1 Product Data

More information

Manual for Control Panel

Manual for Control Panel - 1 - Manual for Control Panel ver.4.0 MODEL: BP2006 Pro.:2006.12.Rev.:2007.08 http://www.olb.kr - 2 - Contents. 1. Front Operation. 2. Parts Names. 3. Initial setting cost. 4. Temperature setting method.

More information

QUARTZ INVERTER TROUBLESHOOTING GUIDE

QUARTZ INVERTER TROUBLESHOOTING GUIDE QUARTZ INVERTER TROUBLESHOOTING GUIDE QIN415H2V31 QIN618H2V31 QIN721H2V31 QIN1129H2V31 INVERTER MINI SPLIT SYSTEM WARNING The information contained in the manual is intended for use by a qualified service

More information

FFTR1821TB0 FFTR1821TS0 FFTR1821TW0

FFTR1821TB0 FFTR1821TS0 FFTR1821TW0 Product No. B0 S0 W0 Series R134a R134a R134a Color black stainless white Volts 115 115 115 Wiring Diagram 241582401 241582401 241582401 Owner's Guide A04555602 A04555602 A04555602 Market North America

More information

INSTALLATION MANUAL. Free Joint Multi & Multi-Split Type Room Air Conditioner (Cooling and Heating)

INSTALLATION MANUAL. Free Joint Multi & Multi-Split Type Room Air Conditioner (Cooling and Heating) INSTALLATION MANUAL Free Joint MH040FXEA2A MH052FXEA2A Fixed MH18VV1X MH19VV1X ENGLISH Free Joint Multi & Multi-Split Type Room Air Conditioner (Cooling and Heating) EΛΛHNIKA PORTUGUÊS ITALIANO ESPAÑOL

More information