Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Size: px
Start display at page:

Download "Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers"

Transcription

1 Contents Description Page Introduction Step 1: General Breaker Preparation Step 2: Removing the Original Components.. 3 Step 3: Installing the Sensors Step 4: Building the DTA Assembly Step 5: Installing the Breaker Reset Assembly. 7 Step 6: Installing the DTA Assembly Step 7: Preparing the Trip Unit Assembly for Installation on the Breaker Step 8: Mounting the Trip Unit Assembly to the Breaker Step 9: Installing the Auxiliary CT Module Step 10: Installing the CPT Module Step 11: Connecting the Sensor and DTA Harnesses Step 12: Installing the External Harness and Final Connections Step 13: Final Breaker Preparation Step 14: Testing the Breaker Step 15: Mounting the Cell Harness Step 16: Installing the Retrofitted Breaker in the Cell Parts List

2 WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE SIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES INTENDED TO PROVIDE SAFE AND PROPER OPERATING SEQUENCES. TO PROVIDE MAXIMUM PROTECTION FOR PERSONNEL ASSOCIATED WITH THE INSTALLATION, OPERATION, AND MAINTENANCE OF THESE BREAKERS, THE FOLLOWING PRACTICES MUST BE FOLLOWED. FAILURE TO FOLLOW THESE PRACTICES MAY RESULT IN DEATH, PERSONAL INJURY, OR PROPERTY DAMAGE. Safety Precautions Periodic testing of this devise is required (see Step 16: Testing the Breaker for test procedures). Only qualified persons, as defined in the National Electric Code, who are familiar with the installation and maintenance of power circuit breakers and their associated switchgear assemblies should perform any work associated with these breakers. Completely read and understand all instructions before attempting any installation, operation, maintenance, or modification of these breakers. Always turn off and lock out the power source feeding the breaker prior to attempting any installation, maintenance, or modification of the breaker. Do not use the circuit breaker as the sole means for isolating a high voltage circuit. Follow all lockout and tagging rules of the National Electric Code and all other applicable codes, regulations, and work rules. Do not work on a closed breaker or a breaker with the closing springs charged. Trip (open) the breaker and be sure the stored energy springs are discharged before performing any work. The breaker may trip open or the charging springs may discharge, causing crushing or cutting injuries. For drawout breakers, trip (open), and then remove the breaker to a well-lit work area before beginning work. Do not perform any maintenance: including breaker charging, closing, tripping, or any other function which could cause significant movement of the breaker while it is on the extension rails. Doing so may cause the breaker to slip from the rails and fall, potentially causing severe personal injury to those in the vicinity. Do not leave the breaker in an intermediate position in the switchgear cell. Always leave it in the connected, disconnected, or (optional) test position. Failure to do so could lead to improper positioning of the breaker and flashover, causing death, serious personal injury, and / or property damage. Do not defeat any safety interlock. Such interlocks are intended to protect personnel and equipment from damage due to flashover and exposed contacts. Defeating an interlock could lead to death, severe personal injury, and / or property damage Section 1: Introduction Eaton Cutler-Hammer Digitrip Retrofit Kits are available in a number of configurations that provide a wide range of features. The Digitrip System starts with the 510 Basic Kit that offers true RMS sensing, overcurrent protection, and self-testing features. Advanced Digitrip Retrofit Kits feature zone interlocking, digital alphanumeric displays, remote alarm signals, PowerNet communications, energy monitoring capabilities, power factors, and harmonic content measurements. Table 1 provides a quick reference of the components supplied with each level of Retrofit Kit. Before beginning the Retrofit process, take a minute to review the information contained in Table 1. It is important that the Retrofitter understands which level of Retrofit Kit is to be installed and which components are included with the Kit. The instructions contained in this manual cover the installation of all levels of Retrofit Kit. If the Kit you are installing does not contain a certain component, skip the instructions for that component and proceed to the next. Throughout the Retrofit process, refer to the Torque Tables at the back of this manual for specific torque values. If you have any questions concerning the Retrofit Kit and / or the Retrofit process, contact Eaton Cutler-Hammer at:

3 Instruction Leaflet IL 33-RXC-1 Table 1. Available Retrofit Kits Components Trip Unit Rating Plug Auxiliary Current Transformer (CT) Module Auxiliary CT Harness Sensors Sensor Harness Direct Trip Actuator (DTA) Mounting Brackets and Hardware 510 Basic 510 with Zone Interlock External Harness Plug 1 Connector Harness 2 Connector Harness 3 Connector Harness 4 Connector Harness Cell Harness Breaker Mounted Control Power Transformer (CPT Potential Transformer (PT) Module Auxiliary Switch Step 1: General Breaker Preparation Before attempting to remove the Breaker from the Cell or perform any Retrofit Operation, be sure to read and understand the Safety Precautions section of this manual. In addition, be sure to read and understand the Instructions for the Application of Digitrip RMS Retrofit Kits on Power Circuit Breakers (Retrofit Application Data - Publication AD ), supplied with the Digitrip Retrofit Kit. WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. SEVERE PERSONAL INJURY OR DEATH CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. A. Trip the Breaker and remove it from the Cell. Move the Breaker to a clean, well-lit work area. Note: It is the responsibility of the Retrofitter to insure that the Breaker and all original components are in good condition. Visually inspect all Breaker components for signs of damage or wear. If any signs of damage or wear are detected for components not included in the Retrofit Kit, secure the necessary replacement parts before beginning the Retrofit Process. The force necessary to trip the Breaker should not exceed five (5) lbs. Step 2: Removing the Original Components Refer to the Siemens-Allis RLX-1600 Instruction Manual, originally supplied with the Breaker, to perform the following procedures. A. Using a 3/16 in. Allen wrench, remove and save the bottom Finger Clusters from each Phase. They will be reinstalled later in the Retrofit Process. B. Trace the CT wiring from the CT s forward to the Trip Unit terminal block. Disconnect the CT wiring from the terminal block. Pull the CT wiring out through the rear of the Breaker. Scrap the CT wiring. C. Remove and scrap the CT s, spacers, and wiring from each bottom Stud. D. On manually operated Breakers, remove and save the Charging Handle for reinstallation later in the Retrofit Process. E. Remove and save the mounting hardware and Front Cover from the Breaker. They will be reinstalled later in the Retrofit Process. F. Remove and scrap the existing Trip Unit, mounting bracket, and any associated wiring from the bottom right front of the Breaker. G. Remove and scrap the existing Direct Trip Actuator (DTA), mounting bracket, and wiring from the bottom right front of the Breaker. Note: It is the responsibility of the Retrofitter to insure that the proper, manufacturer s recommended crimping tools and terminals are used for each type of connector. It is also the responsibility of the Retrofitter to insure that all wire preparations, connections, strippings, terminations, and wiring techniques are performed according to the latest IEEE, NEC, and / or NEMA industry standards, specifications, codes, and guidelines. To begin the Retrofit Process, refer to the components list at the end of this manual. Layout the components and hardware according to the steps outlined. The parts bags are labeled with the corresponding step number. The components and hardware will be used to complete each step in the Retrofit Process. 3

4 Figure 1. Overview: Original Components Removed from the Breaker. Step 3: Installing the Sensors Figure 3. Finger Clusters Reinstalled and the Proper Orientation of the Sensors and Terminals. Note: The Sensor Harness will be installed later in the Retrofit Process. Step 4: Building the DTA Assembly Figure 2. Overview: Sensors Installed on the Breaker (Shown with Sensor Harness Connected). A. Working from the back of the Breaker, slide a Sensor over each bottom Stud with the terminals on the bottom and facing away from the Breaker. B. Using the original mounting hardware, reinstall the bottom Finger Clusters removed in Step 2-A. Figure 4. Overview: Completed DTA Assembly. 4

5 Instruction Leaflet IL 33-RXC-1 Note: The photos used to illustrate the steps in this procedure were taken using a fully assembled DTA Assembly. Therefore, some components are shown installed on the DTA Assembly before they are installed during this procedure. A. Apply Loc-Tite 242 to the threads on both ends of the DTA Shaft. On the end of the DTA shaft that exits the DTA where the nuts secure the DTA to its frame, install (1) flange nut supplied flange first (flange facing the DTA) on the shaft. Turn the flange nut onto the shaft until the end of the DTA shaft is flush with the nut surface of the flange nut. B. Align the Support bracket with the holes in the DTA Mounting bracket as shown (see Figure 6). Secure the Support bracket to the DTA Mounting bracket using the (2) screws, (4) flat washers, (2) lock washers, and (2) nuts supplied. On the other end of the DTA shaft, install (1) flange nut supplied nut surface first (flange facing away from the DTA) on the shaft. Turn the flange nut onto the shaft until the end of the DTA shaft is flush with the flange surface of the flange nut. See the Loc-Tite label for curing time. Set the DTA aside until the Loc-Tite has fully cured. Figure 6. Support Bracket Installed on the DTA Mounting Bracket. C. Once the Loc-Tite used on the DTA shaft in Step 4-A is cured, align the holes in the Actuator Assembly with the holes in the DTA as shown on the side where the flange nut was installed flange side out (see Figure 7). Note that the Actuator Assembly s lever orientation is opposite to the side that the DTA Wires exit the DTA (top of the DTA). Secure the Actuator Assembly to the DTA using the (2) screws, (2) lock washers, and (2) flat washers supplied. Figure 5. Flange Nuts Properly Installed on the DTA Shaft. Figure 7. Actuator Assembly Mounted to the DTA. 5

6 D. Align the Actuator Support bracket with the holes in the side of the DTA as shown (see Figure 8). At this time, the Actuator Support bracket will only be mounted to the DTA using (3) screws, (1) screw, (4) lock washers, and (4) flat washers supplied. The other two holes in the Actuator Support bracket and DTA will be used to mount the Reset Assembly in the next step. Reference Figure 8 for the locations at which the (3) screws are to be installed. Note: DO NOT fully tighten the four Actuator Support bracket mounting screws at this time. This will allow for adjustment of the Reset Assembly in the next step. Figure 9. Reset Assembly Mounted to the Actuator Support Bracket and DTA Long Screw Long Screws F. Fully tighten the four screws to secure the Actuator Support bracket to the DTA. G. Align the holes in the right side of the Reset Assembly with the top two holes in the right side of the DTA frame. Use (1) screw, (1) lock washer, and (1) flat washer supplied in the top hole of the Reset Assembly to hold it in place. Do Not fully tighten the screw at this time. Figure 8. Actuator Support Bracket Mounted to the DTA with Four Screws. E. Position the fork of the Reset Assembly around the DTA shaft and between the flange nut and DTA frame as shown (see Figure 9). Then align the holes in the left side of the Reset Assembly with the open holes in the Actuator Support bracket and DTA frame. Secure the Reset Assembly to the Actuator Support bracket and DTA using the (2) screws, (2) lock washers, and (2) flat washers supplied. Screw Holding Reset Assembly Figure 10. Right Side of the Reset Assembly Mounted to the DTA Frame with One Screw. 6

7 Instruction Leaflet IL 33-RXC-1 H. Slide the spring over the Actuator shaft. Step 5: Installing the Breaker Reset Assembly I. Slide the Guide plate onto the Actuator shaft then align the mounting holes in the Guide plate with the holes in the right side of the Reset Assembly and DTA (see Figure 11). Loosely secure the Guide plate to the right side of the Reset Assembly and DTA using the (1) screw, (1) lock washer, and (1) flat washer supplied. Also loosely secure the Guide plate to the right side of the Reset Assembly using the (1) screw, (2) flat washers, (1) lock washer, and (1) nut supplied. Figure 12. Overview: Breaker Reset Assembly Installed in the Breaker. A. Remove and scrap the X washers and wrist pin from Phase 3. This is the wrist pin that connects the Phase 3 Insulating Link to the Pole Shaft. B. Install (1) X washer supplied on one end of the new Wrist Pin. Figure 11. Spring in Place on the Actuator Shaft and the Guide Plate Loosely Secured to the Reset Assembly and DTA. J. Fully tighten the hardware securing the right side of the Reset Assembly to the DTA frame. K. Adjust the position of the Guide plate to insure that the Actuator shaft has a full range of movement and does not bind when moving. Fully tighten the hardware securing the Guide plate to the Reset Assembly and DTA. C. From the right, insert the new wrist pin through the Phase 3 Pole Shaft and Insulating Link. D. Slide (1) flat washer supplied and the Breaker Reset Assembly on the left end of the wrist pin. Note that the leg of the Reset Assembly MUST face to the right. Secure the Breaker Reset Assembly and flat washer on the wrist pin using (1) X washer supplied. Note: Insure that the Reset Arm in the Reset Assembly moves freely. If it does not move freely, slightly loosen the Nylock nuts on the Reset Arm pin until free movement is achieved. 7

8 Step 6: Installing the DTA Assembly Figure 15. Drilling Plan B Right Side Breaker Frame. C. Install (1) washer, (1) spring, then (1) washer on the Breaker Reset Shaft. While holding the washers and spring in place on the shaft, align the shaft with the slot in the DTA Reset Arm. D. Slide the Breaker Reset Shaft through the slot in the DTA Reset Arm then align the mounting holes in the DTA Assembly with the holes drilled in Steps 6-A and B. Note that the Trip Bar Shaft goes behind the Breaker Trip Bar. Figure 13. Overview: DTA Assembly Installed in the Breaker. A. Using Drilling Plan A and a bit, drill two holes in the right front side of the breaker platform. Figure 14. Drilling Plan A Right Front Side of the Breaker Platform. B. Using Drilling Plan B and a bit, drill one hole in the right side breaker frame. Figure 16. Proper Positioning of the Breaker Trip Bar and Trip Bar Shaft. E. Once the DTA Assembly is properly aligned, secure it to the right front side of the breaker platform using (2) thread cutting screws, (2) lock washers, and (2) flat washers, and to the right side breaker frame using (1) screw, (2) flat washers, (1) lock washer, and (1) nut supplied. 8

9 Instruction Leaflet IL 33-RXC-1 Figure 19. Insulation Barrier Mounting L Clips Attached to the Insulation Barrier. Figure 17. DTA Assembly Installed in the Breaker. F. Connect a 24 Vdc power supply to the DTA terminals: positive-topositive and negative-to-negative. Close the breaker. Energize the DTA to trip the breaker; de-energize when the breaker trips. Make certain that the DTA resets. If the breaker fails to properly trip, adjust the Guide Plate up or down. If the DTA fails to reset, adjust the spring tension on the Reset Assembly. B. Align the Trip Unit with the holes in the Trip Unit mounting plate, as shown. Secure the Trip Unit to the mounting plate using the (2) screws, (4) flat washers, (2) lock washers, (2) nuts, and (2) brass spacers supplied. Note that the brass spacers are used between the bottom of the Trip Unit and the top of the Trip Unit Mounting Plate. Step 7: Preparing the Trip Unit Assembly for Installation on the Breaker Figure 18. Overview: Trip Unit Assembly Prepared for Installation on the Breaker. Note: While performing the following Steps A through D, only snug the mounting hardware used during each step. This will allow for some adjustment as the components are being mounted during this process. The time at which all snugged hardware can be fully tightened is identified. A. Align the Trip Unit Insulation Barrier mounting L clips with the existing holes in the Insulation Barrier as shown. Note that the small leg of each Insulation Barrier mounting L is used to mount the L clips to the Insulation Barrier. Attach the Insulation Barrier mounting clips to the Insulation Barrier using the (4) screws, (4) lock washers, and (4) flat washers supplied. Figure 20. Proper Positioning of the Brass Spacers. C. Align the left and right Trip Unit support clips with the slots in the sides of the Trip Unit and the existing tapped holes in the Trip Unit mounting plate. Attach the Trip Unit support clips to the mounting plate using the (4) screws, (8) flat washers, (4) lock washers, and (4) nuts supplied. 9

10 Figure 21. Trip Unit Support Clips Attaching the Trip Unit to the Mounting Plate. D. Align the holes in the L clips on the Insulation Barrier Assembly with the threaded holes in the Trip Unit support clips. Attach the Insulation Barrier Assembly to the Trip Unit support clips using the (2) screws, (2) lock washers, and (2) flat washers supplied. Figure 23. Trip Unit Mounting Brackets Secured to the Trip Unit Mounting Plate. G. Remove the Trip Unit Cover. Install the Rating Plug. Reinstall the Trip Unit Cover using the original hardware. Figure 24. Trip Unit with Rating Plug and Cover Installed. H. Install the Digitrip Retrofit Label on the top of the Trip Unit. Figure 22. Insulation Barrier Assembly Attached to the Trip Unit Mounting Clips. E. Fully tighten all mounting hardware used in Steps A through D at this time. F. Align a Trip Unit mounting bracket with the existing holes in each end of the Trip Unit mounting plate. Note that the turned down edge of the Trip Unit mounting plate and the straight edges of the mounting brackets should face in the same direction. Secure the mounting brackets to the mounting plate using the (4) bolts, (8) flat washers, (4) lock washers, and (4) nuts supplied. 10

11 Instruction Leaflet IL 33-RXC-1 For Kits Supplied with a PT Module Only. Step 8: Mounting the Trip Unit Assembly to the Breaker I. Align the PT Module mounting bracket with the existing holes in the Trip Unit mounting plate. Secure the PT Module mounting bracket to the Trip Unit mounting plate using the (2) screws, (4) flat washers, (2) lock washers, and (2) nuts supplied. J. Remove and scrap the PT Module Nameplate extension clip. Using the original mounting hardware, relocate the PT Module Warning Nameplate as shown (see Figure 25). Install the supplied new PT Module Warning label over the existing Warning Nameplate label. Figure 27. Overview: Trip Unit Assembly Mounted to the Breaker. A. Remove the two bolts and bearing caps from each end of the breaker Racking Bar. Figure 25. PT Module s Relocated Warning Nameplate and New Warning Label. B. Position the Trip Unit Assembly down over the insides of the breaker Racking Bar bearing. Secure the Trip Unit Assembly to the breaker using the existing bearing caps and the (4) bolts, (4) lock washers, and (4) flat washers supplied. K. Align the small PT Module Insulation Barrier with the back of the PT Module and then both with the holes in the front of the PT Module mounting bracket. At the same time but from the back, align the holes in the large PT Module Insulation Barrier with the holes PT Module mounting bracket. Secure the PT Module, small Insulation Barrier, and large Insulation Barrier to the PT Module mounting bracket using the (2) screws, (4) flat washers, (2) lock washers, and (2) nuts supplied. Figure 28. Trip Unit Assembly Mounted to the Breaker. Figure 26. PT Module and Insulation Barriers Mounted to the PT Module Mounting Bracket and Trip Unit Assembly. 11

12 For Kits Supplied with a PT Module Only. C. Drill and tap the top of each top Stud on the rear of the breaker, per Drilling Plan C to accept a screw. Figure 30. PT Wires Connected to the Top Breaker Studs. E. Secure the PT Wires away from any moving parts on the breaker using the self-adhesive mounting pads and wire ties supplied. Step 9: Installing the Auxiliary CT Module Figure 29. Drilling Plan C : Drilling the Breaker Studs for PT Wire Connections. D. Refer to Section 7-3, Power Flow Convention of the Retrofit Application Data, supplied with the Retrofit Kit for additional wiring information and to verify the Phase Convention used on this Breaker Application. The PT Wires are marked for connection to Phases 1, 2, and 3 with corresponding numbers. Note: Before cutting the PT Wires, verify the Phase Convention used on the Breaker Application. Route the PT Wires from the PT Module back to the top breaker Studs. Move the PT Wire markers to a position where they will still be attached to the wires after cutting. Cut the wires to the appropriate length, strip each wire.250, and install a.190 ring terminal on each wire. Figure 31. Overview: Aux. CT Module Installed in the Breaker. A. For Kits Supplied with a CPT Module Only. There are four (4) existing holes in the left breaker frame near the front of the breaker. Enlarged all four holes using a drill bit (see Figure 32). Using the (3) screws, (3) lock washers, and (3) flat washers supplied secure the appropriate PT wire to each top Stud. 12

13 Instruction Leaflet IL 33-RXC-1 Enlarge Figure 32. Holes to Be Enlarge to Mount the Aux. CT Module. B. From inside the breaker, align the Aux. CT Module mounting plate with the four (4) holes in the left breaker Frame. Secure the Aux. CT Module mounting plate to the inside of the left breaker frame using the (4) screws, (8) flat washers, (4) lock washers, and (4) nuts supplied. For Kits Supplied with a CPT Module Only. If a CPT Module was included with the Retrofit Kit, DO NOT install the lower two (2) Aux. CT Module mounting plate screws, washers, and nuts at this time. The lower two (2) mounting holes will be used to mount the CPT Module later in this Retrofit process C. Remove and save the two (2) bottom screws from the left side of the Aux. CT Module. D. From the inside of the breaker, align the holes in the left side of the Aux. CT Module with the bottom four (4) holes in the Aux. CT Module mounting plate. Secure the Aux. CT Module to the mounting plate using the original mounting hardware just removed in the bottom holes and (2) thread cutting screws, (2) lock washers, and (2) flat) supplied in the top holes. Figure 33. Aux. CT Module Secured to the Mounting Plate. E. After the Aux. CT Module is mounted, check to insure that the ground lug on the left side of the breaker frame is clear of the Aux. CT module and the mounting bracket. If it is not, loosen the hardware securing the ground lug to the breaker and adjust the lug until proper clearance is achieved. For Kits Supplied with a CPT Module Only. Step 10: Installing the CPT Module Figure 34. Overview: CPT Module Installed in the Breaker. 13

14 A. Remove and save the (2) screws securing the fuse clips and male spade connector installed on the CPT Module. Discard the fuse clips and spade connector, then reinstall the screws in the CPT Terminals. Table 2. CPT High Voltage Taps for Standard and Special Order CPTs Standard CPT (Style #9A10037G01 & G02) Voltage Required CPT Terminals Used 480 volts Circuit H1 & H4 240 Volt Circuit H2 & H4 208 Colt Circuit H3 & H4 Special Order 575 Volt CPT (Style #9A10037G03 & G04) 575 volts Circuit H1 & H4 460 Volt Circuit H2 & H4 230 Colt Circuit H3 & H4 C. Connect the CPT Harness wires to the appropriate X terminals of the CPT Module as shown. See Table 3 for Tap information. Table 3. CPT Low Voltage Taps for Standard and Special Order CPT (After Removing fuse Clips) Standard CPT (Style #9A10037G01 & G02) 120 Voltage Required CPT Terminals Used Figure 35. Fuse Clips and Spade Connector Removed from the CPT. Note: The Load Side HV Wires may be longer than necessary. Before cutting the wires, be sure that sufficient length is left so that the HV Wire Fuses can be mounted in an accessible position and that the connections can be made to the correct H terminals on the CPT Module. Secondary Circuit X1 & X2 Special Order 575 Volt CPT (Style #9A10037G03 & G04) Secondary Circuit X2 & X3 D. Install the A and B Finger-Safe Covers over the CPT Terminals as shown. Secure the Finger-Safe Covers to the CPT using the (4) screws supplied with the CPT Kit. Torque the screws to 8-10 in./lbs. Line Side Load Side CTP Harness Figure 36. Load and Line Sides of the HV Wires. Finger Safe Covers B. Temporarily position the CPT Module and the HV Fuses near the front left corner of the breaker. Route the Load Side HV Wires to the CPT Module. Mark and cut the Load Side of each HV Wire to an appropriate length for connection to the H terminals of the CPT. Strip approximately of insulation from the Load Side HV Wires and attach a ring terminal to each. Attach the HV Wires to the CPT H terminals to achieve the required voltage (see Table 1). Note: The terminals to which the Load Side HV wires are connected determine the voltage of the CPT. Verify that the line voltage of the circuit matches the CPT voltage BEFORE putting the Breaker into service. HV Wires Figure 37. Finger Safe Covers Installed on the CPT. 14

15 Instruction Leaflet IL 33-RXC-1 E. Working from inside the breaker, align the mounting holes in the CPT Module with the holes in the Aux. CT Module mounting plate. Secure the CPT Module to the Aux. CT Module mounting plate and left breaker frame using the (4) screws, (8) flat washers, (4) lock washers, and (4) nuts supplied I. Remove the existing hardware securing the PT wires to the Phase 1 and 2 or Phase 2 and 3 top breaker Studs. Secure the HV Line Side Wires and the PT wires to the top breaker Studs using the hardware just removed. F. Secure the HV Fuses in their desired location within the breaker. Insure that the selected location allows the HV Fuses to clear all moving components within the breaker and will not interfere as the breaker is being racked into the Cell. G. Install the appropriate CPT Voltage Label on the breaker Front Cover. WARNING THIS BREAKER CONTAINS A 50VA CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKER IS USED ON A LINE VOLTAGE OTHER THAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING. FAILURE TO DO SO WILL RESULT IN DAMAGE TO THE TRIP UNIT AND / OR CONTROL POWER TRANSFORMER 208V CONTROL POWER TRANSF. TAPS H1 H4=480V H2 H4=240V H3 H4=208V NP# 9A10039H04 WARNING THIS BREAKER CONTAINS A 50VA CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKER IS USED ON A LINE VOLTAGE OTHER THAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING. FAILURE TO DO SO WILL RESULT IN DAMAGE TO THE TRIP UNIT AND / OR CONTROL POWER TRANSFORMER 240V CONTROL POWER TRANSF. TAPS H1 H4=480V H2 H4=240V H3 H4=208V NP# 9A10039H03 Figure 39. HV Line Side Wires Connected to the Top Breaker Studs. J. Route the CPT Harness from the CPT Module to the right side of the Trip Unit. It will be connected to the Trip Unit later in the Retrofit process. K. Use the self-adhesive mounting pads and wire ties supplied to secure the HV Wires away from any moving breaker components. Step 11: Connecting the Sensor and DTA Harnesses WARNING THIS BREAKER CONTAINS A 50VA CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKER IS USED ON A LINE VOLTAGE OTHER THAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING. FAILURE TO DO SO WILL RESULT IN DAMAGE TO THE TRIP UNIT AND / OR CONTROL POWER TRANSFORMER 480V CONTROL POWER TRANSF. TAPS H1 H4=480V H2 H4=240V H3 H4=208V NP# 9A10039H02 WARNING THIS BREAKER CONTAINS A 50VA CONTROL POWER TRANSFORMER FOR TRIP UNIT DISPLAY. IF BREAKER IS USED ON A LINE VOLTAGE OTHER THAN SHOWN. THE CPT TAPS MUST BE CHANGED BEFORE ENERGIZING. FAILURE TO DO SO WILL RESULT IN DAMAGE TO THE TRIP UNIT AND / OR CONTROL POWER TRANSFORMER 575V CONTROL POWER TRANSF. TAPS H1 H4=575V NP# 9A10039H01 Figure 38. CPT Voltage Labels Supplied with the CPT Kit. Note: The power convention of circuit breakers is normally Top to Bottom, meaning the top breaker Studs are on the Line Side of the breaker and the bottom breaker Studs are on the Load Side. The HV Wires from the CPT MUST BE ATTACHED to the Line Side of the breaker. If it is determined that the power flow for the breaker application is opposite the normal convention, the HV Wires must be attached to the bottom breaker Studs. In the case of the Line Side being the bottom breaker Studs, the HV Wires can be connected to the bottom Studs in a similar manner as the PT wires are connected to the breaker Studs in Step 7. Note: The Line Side HV Wires may be longer than necessary. Before cutting the wires, be sure that sufficient length is left so that the HV Wire Fuses are accessible and that the connections can be made to the Studs. H. Route the HV Line Side Wires to the Phase 1 and 2 or the Phase 2 and 3 top breaker Studs. Cut each HV Wire to an appropriate length for attachment to the same hardware used to secure the PT Wires to the top breaker Studs. Strip.250 from each wire and then install a.190 ring terminal on each wire. Figure 40. Overview: Sensor and DTA Harnesses Connected to the Aux. CT Module. A. Connect the Sensor Harness to the proper terminals of the Aux. CT Module. Refer to Section 12 of the Retrofit Application Data, supplied with the Retrofit Kit, for detailed wiring specifications. The long tan and green wires in the Sensor Harness are used for a remote Neutral Sensor on a 4W Ground Breaker. If these wires are not used in this application, they should be removed from the Sensor Harness. B. Remove the front screw and washers from the right side of the Aux. CT Module. Connect the Sensor Harness Ground Wire (with ring terminal) to the Aux. CT Module using the screw and washers just removed. 15

16 Figure 41. Sensor Harness and Ground Wire Connected to the Aux. CT Module Terminals and Case. C. Route the Sensor Harness back from the Aux. CT Module to the Sensors. Insure that the Sensor Harness is clear of all moving components within the breaker. D. Connect the ring terminals of the Sensor Harness to the Sensors. Refer to Section 12 of the Retrofit Application Data, supplied with the Retrofit Kit, for detailed wiring specifications. Figure 43. DTA Wires Connected to the Aux. CT Module Terminal Block. G. Use the wire ties and clamps supplied to secure the Sensor Harness and DTA Wires so they are clear of any moving components within the breaker. Step 12: Installing the External Harness and Final Connections Figure 44. Overview: Harnesses Connected to the Trip Unit. Figure 42. Sensor Harness Connected to the Sensors. E. Route the DTA wires to the Aux. CT Module. Insure that the DTA wires are clear of any moving components within the breaker. A. Plug the Aux. CT Harness into the connector on the Aux. CT Module Pigtail. B. Route the Aux. CT Harness up through the breaker then across to the right side of the Trip Unit. Connect the Aux. CT Harness to its receptacle in the Trip Unit. F. Connect the + DTA Wire to the OP terminal of the Aux. CT Module Terminal Block and the unmarked wire to the ON terminal. 16

17 Instruction Leaflet IL 33-RXC-1 C. Connect the External Harness to the receptacles in the Trip Unit. D. Attach the External Harness to the right Trip Unit Support Clip with two nylon wire clamps supplied. Use the two screws located there that attach the Support Clip to the Trip Unit Mounting Bracket. Note: For 510 Basic Kits, the External Harness is the Shorting Plug pictured below. It is to be plugged into the corresponding receptacle in the Trip Unit. Figure 47. Microswitch Installed on the Auxiliary Switch Mounting Bracket. Figure Basic Kit External Harness Shorting Plug. E. For Kits Supplied with a PT Module Only: Route the PT Extension Harness between the Trip Unit and Insulation Barrier to the right side of the Trip Unit. Connect the PT Extension to the corresponding plug on the External Harness. F. Route the two wires with Ring Terminals from the External Harness down to the Microswitch. Connect one wire to the normally Open terminal and the other wire to the Common terminal of the Microswitch. Mount the Auxiliary Switch Assembly behind the DTA mounting bracket as shown using the (2) screws, (2) lock washers, and (2) flat washers supplied. The Microswitch Lever operates off of the Phase 3 Insulating Link as shown. The Microswitch must open and close as the breaker opens and closes. Figure 46. Routing and Connection of the PT Extension Harness to the External Harness. For Kits Supplied with an Auxiliary Switch Only. Figure 48. Auxiliary Switch Assembly Installed on the DTA Mounting Bracket. F. Cut 2.12 off the end of the Microswitch Arm. G. Align the holes in the Microswitch with the holes in the Auxiliary Switch mounting bracket. Secure the Microswitch to the Auxiliary Switch Mounting Bracket, as shown, using the (2) screws, (4) flat washers, (2) lock washers, and (2) nuts supplied. 17

18 For Kits Supplied with a CPT Module Only. G. Remove the External Harness plug connected to the Trip Unit. Connect the black plug of the CPT Harness into the same receptacle in the Trip Unit from which the External Harness plug was removed. Reinsert the External Harness plug just removed into the female receptacle on the CPT Harness. A. Use the self-adhesive mounting pads and wire ties supplied to dress all wires and harnesses to keep them away from any moving parts within the Breaker. B. Reinstall the breaker Front Cover using the original hardware removed in Step 2-E. C. If equipped, using the original mounting hardware removed in Step 2-D, reinstall the Manual Closing Handle. Step 14: Testing the Breaker A. Measure the force necessary to trip the Breaker at where the DTA Adjusting Screw impacts the Breaker Trip Paddle. The force necessary to trip the Breaker MUST NOT EXCEED 5 lbs. B. The Retrofit must be tested using primary injection. Refer to Section 8 of the Instructions for the Application of Digitrip RMS Retrofit Kits on Power Circuit Breakers (Publication AD , September 2001), supplied with the Retrofit Kit, for detailed testing procedures and specifications. For test information specific to the Trip Unit, refer to the IL publication supplied with the Retrofit Kit (see the Pick List for the IL number). Figure 49. CPT Harness Connected to the External Harness. For All Retrofit Kits. H. Use the wire ties and clamps supplied to secure all wires and harnesses away from any moving components within the breaker. Step 13: Final Breaker Preparation C. While Section 8 of the Instructions for the Application of Digitrip RMS Retrofit Kits on Power Circuit Breakers provides the information necessary for testing the Breaker, please keep the following notes in mind when reviewing other sections of the publication. CAUTION: When all testing is complete, the Trip Unit must be reset. Failure to do so may cause the battery in the Rating Plug to run down. NOTES: 1. For All Kits Other Than 510 Basic: If testing the Breaker with Short Delay or Ground Fault functions, be sure to either plug in the Cell Harness Assembly or use the Zone Interlock Shorting Plug. Failure to do so may result in shorter than expected trip times. 2. For 810 and 910 Kits Only: Without any power applied to the system (neither the 120 volt power supply nor the Aux. Power Module connected), plug the External Harness into the Cell Harness and check the impedance between COM 1 and COM 2. The impedance should be between one (1) and three (3) ohms. If the impedance is not within this range, trace the wiring and examine each connection to assure its integrity. Confirm that the PowerNet communication wiring is correct by following the procedures detailed in Section 7.4 of the Instructions for the Application of Digitrip RMS Retrofit Kits on Power Circuit Breakers. Note that for 810 and 910 Kits, the impedance between COM 1 and COM 2 should be between one (1) and three (3) ohms. When testing is complete, disconnect the External Harness from the Cell Harness. Final External Harness connection will be performed later in the Retrofit Process. Figure 50. Overview: Breaker Ready for Testing. 18

19 Instruction Leaflet IL 33-RXC-1 Step 15: Mounting the Cell Harness A. The Cell Harness is to be mounted in the Breaker Cell. The connector end is to be mounted on the right side of the Cell, in a location suitable for connection with the External Harness. The Terminal Blocks can be mounted anywhere space is available in the Cell as long as connection to the External Harness can be made. B. Route the Cell Harness wiring to keep it away from any moving parts within the Cell Housing. Step 16: Installing the Retrofitted Breaker in the Cell WARNING: Do not leave the Breaker in an intermediate position in the switchgear cell. Always leave it in the CONNECTED, DISCONNECTED, or (Optional) TEST position. Failure to do so could lead to improper positioning of the Breaker and flashover, causing death, serious personal injury, and / or property damage. Note: It is the responsibility of the Retrofitter to insure proper Breaker / Cell fit. When racking the Breaker into the Connected position, the Retrofitter MUST FOLLOW BOTH the manufacturer s instructions and the customer s safety standards and procedures for racking a Breaker into the Connected position. A. With the Breaker in the Open position and the springs discharged, slowly rack the Breaker into the Connected position, making sure there is no interference or binding. The Breaker should rack smoothly and without mechanical interference between any Breaker and Cell parts. The Retrofitter will feel some resistance when the primary fingers connect onto the stabs of the Cell. This is normal. However, if any unusual resistance is detected that could be abnormal interference between the Breaker and Cell parts, stop immediately and move the Breaker out of the Connected position. Examine what is causing the interference and correct the situation. 19

20 Digitrip Retrofit Kit Installation Components for Siemens-Allis RLX-1600 Breaker RMS/R Retrofits Step Description Qty. Comment Step 3 Sensor 151D995G16 3 Step 4 DTA Assembly 6503C67G13 1 DTA Reset Parts 8153A22G04 1 Mounting Bracket 1 DTA Reset Assembly 1 Bracket Lng. Screw, Stl., Fil Flat Washer Stl Lock Washer Stl Nut Hex Stl. 32 DTA Trip Bar Assembly 8153A22G05 1 Trip Assembly 1 Bracket 1 Spring 1 Loc-Tite Flange Nut, Stl Lng. Screw, Stl., Fil Lng. Screw, Stl., Fil Flat Washer Stl Lock Washer Stl. 114 Step 5 Breaker Reset Parts 8153A22G06 1 Wrist Pin 1 X Washer.500 Stl Flat Washer Stl. 1 Step 6 DTA Mounting Hardware 8153A22G Lng. Screw, Stl., T.C Flat Washer Stl Lock Washer Stl Lng. Screw, Stl., Fil Flat Washer Stl Lock Washer Stl Nut Hex Stl. 1 Step 7 Trip Unit See Pick List 1 Rating Plug See Pick List 1 Trip Unit Assembly Parts 8153A22G08 1 Mounting Plate 1 Mounting Bracket 2 Bracket 1 Support Clip 1 Mounting Clip 2 Insulation Barrier 1 Digitrip Retrofit Label Lng. Hex Bolt Stl Flat Washer Stl Lock Washer Stl Nut Hex Stl. 4 20

21 Instruction Leaflet IL 33-RXC-1 Digitrip Retrofit Kit Installation Components for Siemens-Allis RLX-1600 Breaker RMS/R Retrofits (Cont.) Step 7 Cont Lng. Screw Fil Lng. Screw Nylon P. H Flat Washer Stl Lock Washer Stl Nut Hex Stl Lng. Screw Flat Washer Stl Lock Washer Stl Lng. Screw Fil Flat Washer Stl Lock Washer Stl., Helical Nut Hex Stl Lng. Screw Fil Flat Washer Stl Lock Washer Stl. 4 Spacer, Brass 2 PT Module 6502C82G01 1 Comm. Only Ring Terminal (.190,.250,.312,.375,.500) Each Size 3 PT Harness 6502C85G01 1 Comm. Only From Step 12 PT Module Mounting Plate 1 Comm. Only From Step 12 Insulation Barrier, Small 1 Comm. Only From Step 12 Insulation Barrier, Large 1 Comm. Only From Step 12 PT Module Nameplate 1 Comm. Only From Step 12 PT Harness 1 Comm. Only From Step Lng. Screw, Stl., Fil. HD 3 Comm. Only From Step Flat Washer Stl. 3 Comm. Only From Step Lock Washer Stl. 3 Comm. Only From Step Lng. Screw, Stl., Fil. 2 Comm. Only From Step Flat Washer Stl. 4 Comm. Only From Step Lock Washer Stl. 2 Comm. Only From Step Nut Hex Stl. 2 Comm. Only From Step Lng. Screw Stl., Fil. 2 Comm. Only From Step Flat Washer Stl. 4 Comm. Only From Step Lock Washer Stl. Helical 2 Comm. Only From Step Nut Hex Stl. 2 Comm. Only Step Lng. Hex Bolt Stl. 4 From Step Flat Washer Stl. 4 From Step Lock Washer Stl. 4 From Step 7 Step 9 Aux. CT Module 6503C59G 1 Aux. CT Module Mounting Parts 8153A22G09 1 Mounting Plate Lng. Screw, Stl., P. H Lng. Screw, Stl., Fil Flat Washer Stl Lock Washer Stl Nut Hex Stl. 4 21

22 Digitrip Retrofit Kit Installation Components for Siemens-Allis RLX-1600 Breaker RMS/R Retrofits (Cont.) Step 9 (contd.) Mounting Pad - 1, Self-Adhesive 2 From Step 12 Wire Tie Nylon 2 From Step 12 Step 10 CPT Kit See Pick List 1 CPT Only MTE Transformer 1 CPT Only HV Fused Wires 2 CPT Only CPT Wires 1 CPT Only Mounting Hardware Kit 1 CPT Only Lng. Screw Stl. Fil. 4 CPT Only.190 Flat Washer Stl. 8 CPT Only.190 Lock Washer Stl. 4 CPT Only Nut Hex Stl. 4 CPT Only Ring Terminal (.138,.190,.250,.312,.375, Each Size) 2 CPT Only Warning Label (208, 240, 480, & 575 Volt - Each) 1 CPT Only Wire Tie Nylon 12 CPT Only Finger-Safe Cover Kit FSK4 1 CPT Only Cover (A, B, C, & D Each) 1 CPT Only Lng. Screw Stl. Fil. 4 CPT Only Step 11 Sensor Harness Parts 8153A22G10 1 Sensor Harness 1 Wire Tie Nylon (Panduit) 8 Clamp Nylon Lng. Screw Stl. Fil Flat Washer Stl Lock Washer Stl Nut Hex Stl. 1 Step 12 Auxiliary CT Harness 6502C84G02 1 PT Extension Harness 6502C85G01 1 Comm. Only External Harness 6502C83G 1 Harness Mounting Parts 8152A22G11 1 Comm. Only Lng. Screw Stl., Fil. 2 Comm. Only.138 Flat Washer Stl. 4 Comm. Only.138 Lock Washer Stl. Helical 2 Comm. Only Nut Hex Stl. 2 Comm. Only Clamp Nylon 2 Comm. Only Wire Clamp 2 Comm. Only Wire Tie Nylon (Panduit) 8 Comm. Only Auxiliary Switch Kit 8153A22G02 1 Comm. Only Microswitch 1 Comm. Only Aux. Switch Mounting Bracket 1 Comm. Only Lng. Screw Stl. Fil. HD 5 Comm. Only.190 Flat Washer Stl. 5 Comm. Only.190 Lock Washer Stl. 3 Comm. Only.164 Lock Washer Stl. 2 Comm. Only Lng. Screw Stl. Fil. 2 Comm. Only.138 Flat Washer Stl. 4 Comm. Only.138 Lock Washer Stl. 2 Comm. Only Nut Hex Stl. 2 Comm. Only 22

23 Instruction Leaflet IL 33-RXC-1 Digitrip Retrofit Kit Installation Components for Siemens-Allis RLX-1600 Breaker RMS/R Retrofits (Cont.) Step 15 Cell Harness See Pick List 1 Note: Due to the wide variety of Breakers and the multiple functions of the Retrofit components, some excess hardware may remain when the Retrofit is complete. Table 4. Torque Values for General Mounting and Screw Size Conversion Decimal Size (in) Standard Size Torque (in-lbs) Torque (ft-lbs) / / / / / Table 5. Torque Values for Copper BUS Connectors Decimal Size (in) Standard Size Torque (in-lbs) Torque (ft-lbs).250 1/ / / /

24 Figure 51. Retrofit Components A. Sensors B. RMS/R Trip Unit Assembly C. Auxilliary CT Module D. Direct Trip Actuator and Hardware E. PT Module (810 & 910 Kits Only) F. Sensor Harness G. Auxilliary CT Harness H. External Wire Harness I. PT Extension Harness (810 & 910 Kits Only) J. Auxiliary Switch (810 & 910) Kit Only) K. Cell Harness 24

25 Instruction Leaflet IL 33-RXC-1 Notes: 25

26 Notes: 26

27 Instruction Leaflet IL 33-RXC-1 Notes: 27

28 The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility. The information, recommendations, descriptions, and safety notations in this document are based on Eaton s experience and judgment with respect to Retrofitting of Power Breakers. This instructional literature is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative. The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton. NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein. Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA United States 877-ETN-CARE ( ) Eaton.com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL 33-RXC-1 / TBG April 2010 PowerChain Management is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners.

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers Supersedes IL 33-GS8-2 Dated 10/00 (Manually Operated Only) Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:...............................

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers Supersedes IL 33-A46-2 Dated 01/04 Contents Description Page Introduction.............................. 3 Step 1: General Breaker Preparation......... 4 Step 2: Removing the Original Components.. 5 Step

More information

Digitrip Retrofit System for BBC LKD 8 Breakers

Digitrip Retrofit System for BBC LKD 8 Breakers Supersedes IL 33-LK8-2 Dated 10/00 Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:............................... 4 Step 3:...............................

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2 SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY

More information

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers Supersedes IL 33-AG6-2 Dated 02/08 Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:............................... 4 Step 3:...............................

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers Supersedes IL 33-GDC-5 Dated 07/10 Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers Digitrip Retrofit System for the General Electric AKR Digitrip Retrofit

More information

IL 33-DRC-1 Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers. Table of Contents

IL 33-DRC-1 Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers. Table of Contents IL 33-DRC- Retrofit System for Westinghouse and Cutler-Hammer DS Power Circuit Breakers Table of Contents SAFETY PRECAUTIONS... How to Use this Manual...2 Work Sequence...2 Figure Work Sequence... 3 Tools

More information

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers Instruction Leaflet IL2A12995H02 effective March 2012 Trip Indicator with Remote Reset for Magnum WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS

More information

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit Instruction Leaflet IL01210020E Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit Contents Description Page 1. Removal of R-Frame Electronic Seltronic (RES) Trip Unit and Obsolete Components...

More information

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism Effective October 2010 Supersedes June 2010 IL01301018EH03 Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD

More information

Two-way cable interlock kit for Magnum fixed circuit breakers

Two-way cable interlock kit for Magnum fixed circuit breakers warning (1) Only qualified electrical personnel should be permitted to work on the equipment. (2) Always de-energize primary and secondary circuits if a circuit breaker cannot be removed to a safe work

More information

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK

More information

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2

More information

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches Instruction Leaflet IL 0106001E Contents Description Page Introduction.......................... Installation............................ Manual Operation and Thermal Magnetic Trip Unit Adjustment.......................

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

CM52 Network Protector with Arc Flash Reduction Module

CM52 Network Protector with Arc Flash Reduction Module Contents Description Page 1: General.............................. 2 2: Maintenance Mode Settings.............. 2 3: Arming Maintenance Mode.............. 2 4: Remote Indicator....................... 2

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit Instruction Leaflet IL0131075EN Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit Contents Description Page General information.... 2 Installation

More information

O & M Manual for the EATON Generator Ready Loadcenter

O & M Manual for the EATON Generator Ready Loadcenter O & M Manual for the EATON Instructional Booklet New Information Description Page 1. Introduction............................... 2 2. Receiving, Handling, and Storage................ 4 3. Equipment Description........................

More information

CCP2-FLR1-21_ flange-rod operating mechanism

CCP2-FLR1-21_ flange-rod operating mechanism Installation manual 3A3747 Rev A Contents Description Page General information 1 Required tools 2 Hardware contents 2 Installation and adjustment 2-6 Flange drilling pattern 7 HAZARD OF ELECTRIC SHOCK,

More information

3-way multi-family drawout cable interlock kit - type 32 - RF

3-way multi-family drawout cable interlock kit - type 32 - RF Supersedes August 2015 Power Defense ICCB 3-way multi-family drawout cable interlock kit - type 32 - RF Instructions apply to: Contents Description Page UL489 IEC : PD-RF : PD-RF, IZMX40 General information....

More information

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs and CHGEN ATSs Instruction Leaflet New Information Description Page Installation and Wiring.................................... 2 Page 2 Effective: February 2005 WARNING READ AND UNDERSTAND THE INSTRUCTIONS

More information

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to: Supersedes September 2016 Power Defense ICCB Instructions apply to: UL489 : PD-NF UL489 : PD-RF IEC : PD-NF, IZMX16 IEC : PD-RF, IZMX40 WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED

More information

Instruction Booklet IB E. Contents

Instruction Booklet IB E. Contents Instructions for operation and maintenance of breaker lifting device and breaker lift pan accessory for 5-27 kv type VCP-W circuit breakers and medium voltage switchgear Contents Description Page IIntroduction...

More information

Factory Authorized Mechanism Enhancement (FAME)

Factory Authorized Mechanism Enhancement (FAME) Instruction Leaflet IL182403EN Supersedes April 2017 Effective July 2018 Factory Authorized Mechanism Enhancement (FAME) FAME Upgrade Shown Factory Authorized Mechanism Enhancement (FAME) DISCLAIMER OF

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN Voltage Regulators MN225075EN Effective August 2017 New Issue COOPER POWER SERIES Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet Contents Description Page 1. Introduction...2 2. Description...2 3. Operation...7 4. Maintenance...18 5. Utility approvals...18 Appendix A...19 Appendix B...21. Appendix C...27 CAUTION BECAUSE OF THE UNIQUE

More information

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units EATON CORPORATION Cutler-Hammer Functional Test Kit - Information Leaflet 5721B13H04 I.L. 5721B13H04 Page 1 Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker

More information

Effective June 2016 New Issue

Effective June 2016 New Issue Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation

More information

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN Fault Indicators MN320005EN Effective March 2017 Supersedes December 2008 (S320-50-1) COOPER POWER SERIES S.T.A.R. type LVR faulted circuit indicator installation instructions DISCLAIMER OF WARRANTIES

More information

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS etc-12 e-series, direct replacement retrofit for WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS Section 1 Installation Manual Contents Introduction. 1 Required Tools 2 Pre-Installation 2 Programmer Installation.

More information

Effective November 2016 Supersedes September 1998 (S )

Effective November 2016 Supersedes September 1998 (S ) Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES

More information

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches Instruction Leaflet IL29C107N Effective January 2012 Supersedes IL29C107M 8/11 Installation Instructions for R-Frame Contents Description Page 1. Introduction........................... 2 2. Installation............................

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND

More information

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L. Cutler-Hammer Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N)! WARNING CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE

More information

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035 Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker

More information

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION Page: 1 Instructions for the Type VCP-W Ground & Test Device (Simple) Upper Terminal Set Version IB131007EN Effective May 2015 Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear

More information

Magnum Breaker Remote Racking Device (MRR1000)

Magnum Breaker Remote Racking Device (MRR1000) Contents Description Page 1: Introduction............................ 3 2: Safe Practices.......................... 5 3: Receiving, Handling, and Storage........... 5 4: Procedures............................

More information

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF

More information

Flush Mount AIN ALPHA Meters. General. Hardware Kit

Flush Mount AIN ALPHA Meters. General. Hardware Kit January 2003 IL42-4011B Flush Mount AIN ALPHA Meters General This leaflet contains installation instructions for mounting an AIN ALPHA meter in a semiflush configuration. A mounting kit, style number 1C11497G01,

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

! WARNING I.L D WARNING GENERAL INFORMATION

! WARNING I.L D WARNING GENERAL INFORMATION C Instructions for Drilling and Assembling Flex Shaft TM Handle Mechanism for L, M, MDL, N, and R-Frame Series C Circuit Breakers, Molded Case Switches, and HMCP s! WARNING DO NOT ATTEMPT TO INSTALL OR

More information

Effective May 2017 Supersedes January 2003 (S )

Effective May 2017 Supersedes January 2003 (S ) Reclosers MN280068EN Effective May 2017 Supersedes January 2003 (S280-80-13) CT field modification kit KA906R1 installation and testing instructions COOPER POWER This kit is for use with types RE, RVE,

More information

High-voltage primary bushings installation instructions

High-voltage primary bushings installation instructions OEM Equipment Effective November 2013 Supersedes April 2013 S800-35-2 High-voltage primary bushings installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations,

More information

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking) Instructional Booklet IB022010EN Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking) Contents Description Page Notices and warnings.... 4 Introduction....

More information

Freedom FlashGard Aftermarket Kit Installation Manual

Freedom FlashGard Aftermarket Kit Installation Manual Freedom FlashGard Aftermarket Instructional Literature New Information Description Page 1. General Information............................ 2 2. Receiving, Handling, and Storage.................. 4 3. Installation

More information

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1

More information

Effective May 2017 Supersedes December 2004 (S )

Effective May 2017 Supersedes December 2004 (S ) Reclosers MN280054EN Effective May 2017 Supersedes December 2004 (S280-15-10) COOPER POWER Types L, V4L, E, 4E, and V4E; KA785L10S, KA785L20S, KA785L30S, and KA785L40S Automation upgrade kit installation

More information

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S ) Pad-mounted Switchgear MN285019EN Effective March 2017 Supersedes February 2007 (S285-10-6) COOPER POWER Type VFI fault interrupter with tri-phase control single-phase trip to three-phase trip conversion

More information

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers Cutler-Hammer Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE

More information

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN OEM Equipment MN800008EN Effective February 2016 Supersedes S800-35-2 November 2013 COOPER POWER High-voltage primary bushings installation instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF

More information

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN Voltage Regulators MN225064EN Effective March 2017 Supersedes October 2011 (S225-60-12) Testing a motor capacitor on a voltage regulator procedure instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES

More information

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN Reclosers MN280022EN Effective October 2015 Supersedes S280-40-10 April 2014 COOPER POWER SERIES Mercury switch to microswitch retrofit kit KA349WE installation instructions DISCLAIMER OF WARRANTIES AND

More information

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton Bul. 140U Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton! WARNING CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, OR

More information

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003 Type DTU De-energized Tap Changer Application, Installation & Selection Guide IL 44-750-1A Page 1 September, 2003 Page 2 September, 2003 Scope This leaflet contains general information about ordering and

More information

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives VAC and VAC

Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives VAC and VAC Inverting Fault Circuit Breaker Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 40-75 HP @ 230 VAC and 75-150 HP @ 460 VAC Model Numbers: 906FK1101 and 906FK1201 Instruction Manual D2-3330-2! ATTENTION:

More information

SPX9000 FR10 FR12 Adjustable Frequency Drives

SPX9000 FR10 FR12 Adjustable Frequency Drives Installation Manual New Information MN04003018E For more information visit: www.eatonelectrical.com SPX9000 FR10-FR12 Adjustable Frequency Drives Important Notice Please Read The product discussed in

More information

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches I.L. 29C284B File 29-000 Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON

More information

E.S.P. Embedded Sensing Probes for Motor Brushes

E.S.P. Embedded Sensing Probes for Motor Brushes E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com

More information

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN Reclosers MN280014EN Effective September 2015 Supersedes S280-10-6 April 2003 COOPER POWER SERIES Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits DISCLAIMER OF WARRANTIES AND

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V) Installation Instructions for Auxiliary Switch for JDB, JD, HJD, JDC, JW, HJW, JWC Circuit Breakers, Molded Case Switches, and J-Frame Motor Circuit Protectors I.L. 9C11A! WARNING DO NOT ATTEMPT TO INSTALL

More information

Effective March 2015 Supersedes S August 2012

Effective March 2015 Supersedes S August 2012 Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions

More information

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S ) Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The

More information

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER

More information

Effective November 2016 Supersedes February 2012 (S )

Effective November 2016 Supersedes February 2012 (S ) Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

INSTALLATION INSTRUCTIONS SEMI-HIDDEN WINCH MOUNT Part Number:70005 Application: Ford Super Duty

INSTALLATION INSTRUCTIONS SEMI-HIDDEN WINCH MOUNT Part Number:70005 Application: Ford Super Duty INSTALLATION INSTRUCTIONS SEMI-HIDDEN WINCH MOUNT Part Number:70005 Application: Ford Super Duty Your safety, and the safety of others, is very important. To help you make informed decisions about safety,

More information

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers with Digitrip OPTIM Trip Unit and Powernet and/or Zone Interlock A WARNING CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE

More information

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN Reclosers MN280030EN Effective December 2015 Supersedes S280-20-1 February 1979 Types D and DV recloser installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN Recloser Mountings MN280071EN Effective May 2017 Supersedes February 1997 (S280-85-5) KA662R tank-lifting windlass assembly and installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND

More information

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions Deadbreak Apparatus Connectors MN650005EN Effective February 2015 Supersedes S600-10-2 July 2014 COOPER POWER SERIES 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

More information

LED Downlight Ceiling Fixtures

LED Downlight Ceiling Fixtures ED Downlight Ceiling Fixtures Every attempt has been made to ensure that this documentation is as accurate and up-to-date as possible. However, Vertical Express assumes no liability for consequences, directly

More information

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN Deadbreak Apparatus Connectors MN650004EN Effective February 2015 Supersedes S600-15-3 July 2014 COOPER POWER SERIES 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions DISCLAIMER

More information

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN Deadbreak Apparatus Connectors MN650003EN Effective February 2015 Supersedes S600-55-1 July 2014 COOPER POWER SERIES 600 A 35 kv class BT-TAP connector system installation instructions DISCLAIMER OF WARRANTIES

More information

10260 Retrofit to 10260A Non-Contact Sensor Instructions Kits through -512

10260 Retrofit to 10260A Non-Contact Sensor Instructions Kits through -512 10260 Retrofit to 10260A Non-Contact Sensor Instructions Kits 51404974-501 through -512 Document Number Form: 62-86-33-16D Effective: 3-1-01 Supersedes: 11-00 Summary Retrofitting your 10260 actuator from

More information

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B. Cutler-Hammer Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS

More information

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying

More information

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot. Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling

More information

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN Reclosers MN280070EN Effective May 2017 Supersedes July 2014 (S280-80-23) COOPER POWER Dielectric grease application to recloser cable instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES

More information