1 Cutler-Hammer Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS ENTIRETY BEFORE INSTALLING OR OPERATING CONTROLLER. INSTALLATION, ADJUSTMENT, REPAIR AND MAINTENANCE OF THESE CONTROLLERS MUST BE PERFORMED BY QUALIFIED PERSONNEL. A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS INVOLVED. THE EQUIPMENT Potential Transformer (PT) and Auxiliary Control Power (ACP) disconnect switch assemblies are enclosed in individual cells 15" (38 cm) high and the full width of the Ampgard enclosure in which they are mounted. The potential transformer versions are used wherever PT s with a separate disconnecting means are required for either protection or metering circuits. The potential transformers they disconnect are usually connected to the bus bar system of an Ampgard lineup rather than to an individual branch circuit. The PT disconnect allow deenergizing and access to the PT's without disrupting the main power source. Fig. 1 PT Disconnect Installed 4 6 Auxiliary Control Power (ACP) versions are used wherever more than 5 kva of control power are required for any single Ampgard motor controller or it is necessary to source control power from remote equipment. ACP disconnects feeding transformers larger than 2kVA incorporate a key-operated mechanical interlock paired with a similar device interlocking the low-voltage circuit breaker which disconnects the load fed from the secondary of the transformer supplying control power. The keyoperated mechanical interlocks are selected such that the single key may be withdrawn only when the ACP disconnect is ON and the low-voltage circuit breaker is OFF. The ACP is available as a fused switch with the fuses for the transformer primary located within the switch (5 Amp, 5 kv maximum) or as an unfused switch, in which case the primary fuses must be mounted externally. Fig. 2 View Showing Transformer Primary Grounded When Operating Handle is in OFF Position 7 Both PT and ACP assemblies ground the transformer primary when in the OFF position. See Figure 2.

2 Page 2 GENERAL DESCRIPTION A view of the right hand, or mechanism, end of the PT disconnect cell is shown in Figure 3. PT s rated above 5 kv must be mounted externally to the PT Disconnect, in which case an ACP configuration (without a key interlock on the secondary) is provided. PT disconnect configuration with internally-mounted PT s is described. The ACP configurations use a similar mechanism, with insulated mounting provisions for the line fingers and fuses. The PT s (1) are mounted on a cradle, or tray (2), which can be rotated 90 about a fixed pivot (3). The PT s have primary fuses (4) and fuse clips terminating in a flexible line finger (5) mounted on their top surface. The fuse clips at the opposite or lower end of the fuses, terminate in a shorter, flexible grounding finger (6) (see Figure 2), which, when the PT s have been rotated to the OFF position, contact a grounding bar (7), to short the PT primary windings to ground. Note that the top, or line end finger of the fuse, is mounted to the transformer by a bracket that provides mechanical support only. It has no electrical connection to the transformer winding. Conversely, a similar supporting bracket at the bottom, or grounding finger end of the fuse, also provides the electrical connection to the transformer primary terminal. Rotation of the PT tray is controlled by the operating handle (8) which drives the system of levers that operates the PT tray and insulating shutter. The main drive lever (9) rotates about a second fixed privot (10) and has a cam surface between ON and OFF detents. A springloaded cam follower (11) engages these detents to give the handle (8) a positive feel for the ON and OFF positions. OPERATION a) Closing Stroke As the operating handle (8) is moved from the OFF to the ON position, the PT s and the tray (2) rotate, and an insulating shutter mounted on the rear barrier (12) (See Figure 6) slides open. After the shutter opens, the flexible line fingers (5) mounted on the PT s pass through the openings (13) in the barrier, and make contact with the line terminals (14). The wiping action of the fingers on the line terminals insures good electrical contact. Immediately after the line fingers make contact, the interlock lever (15) (See Figure 3) operates the auxiliary contacts (16), and the transformer secondary circuits are closed. b) Opening Stroke As the handle (8) is moved from the ON to the OFF position, auxiliary contacts (16) open, and unload the transformer secondary circuits before the primary line contacts separate. This action limits the arcing current at the line contacts to the transformer shutter closes to isolate the line terminals from the PT compartment. When the PT s reach the OFF position, grounding fingers (6) (Figure 2) connect the line fingers to the ground bar (7). DOOR INTERLOCKS Two mechanical interlocks are incorporated into the mechanism. The user should be familiar with the functions of these interlocks before putting the unit into service. The first interlock prevents the disconnect door from being opened when the operating handle is in the ON position. This is achieved with a latch (17) (Figure 3) attached to the handle mechanism which engages a catch (18) (Figure 7) mounted on the door. If it is necessary, this interlock can be deliberately defeated by turning the defeater screw (20) (Fig. 3) counterclockwise. (See WARNING note below.) This screw is located on the operating mechanism faceplate and incorporates a coinproof slot, thereby requiring a tool to operate. The second interlock prevents moving the operating handle from the OFF to the ON position while the door is open. This is achieved with a latch (21) (Fig. 3) that engages the handle mechanism output bar (22). The latch (21) has a finger spring (23) that rotates the latch (21) to release the interlock when the door is closed and fastened. This interlock can be deliberately defeated by pushing in the finger spring (23). (See WARNING note below.) WARNING DEFEATING EITHER INTERLOCK PERMITS THE USER TO OBSERVE THE OPERATION OF THE ASSEMBLY DURING INSTALLATION OR MAINTENENACE. HOWEVER, DEFEATING INTERLOCKS IS A VERY HAZARDOUS PROCEDURE AT ANY TIME. THE USER MUST BE FULLY AWARE OF THE DANGERS, BE FAMILIAR WITH THE ASSEMBLY AND INTERLOCK OPERATION, AND TAKE ALL APPROPRIATE SAFETY PRECAUTIONS BEFORE DEFEATING ANY INTERLOCK.

3 Page 3 ADJUSTMENTS Tray With the tray (2) (Figure 3) in the OFF position, the grounding fingers (6) (Figure 2) should be touching the ground bar (7). If they are not touching, or if the fingers are deflected by more than 0.063" (1.6 mm) then adjust the location of the OFF detent slightly as follows: a) Loosen the two 0.25"-20 bolts (located on the underside of the bottom pan) holding the pivot bracket (25) (Figure 3) in position. These bolts engage a threaded nut plate located inside the pivot bracket so that the nut plate cannot turn. WARNING BE SURE THAT ALL POWER TO THE SWITCH HAS BEEN PROPERLY DE-ENERGIZED, AND ALL NECESSARY SAFETY PRECAUTIONS HAVE BEEN TAKEN PRIOR TO BEGINNING ANY ADJUSTMENTS Fig. 3 Close-Up View of PT, Fuses, Auxiliary Contacts, and Operating Mechanism

4 Page 4 ADJUSTMENTS (Continued) b) Move the pivot bracket (25) either forward, or back slightly, until the tray is positioned properly, as explained above. c) Tighten the two 0.25"-20 bolts and recheck the adjustment. Auxiliary Contacts One or more Type L64 auxiliary contact units, sometimes used as electrical interlocks, are held in place by two bolts (26) (Figure 3). If adjustment is required: a) Place the tray in the ON position. b) Loosen the two bolts (26). c) Move the contact units up or down to establish 0.063" (1.6 mm) of contact overtravel. d) Secure the bolts (26). e) Recheck the adjustment. f) Check to make sure that the operating lever (15) strikes both contact unit plungers at the same time. Bend the lever slightly, if necessary. Door Interlocks When the door interlock is properly adjusted, a slight downward pressure on the operating handle (8) when it is in the OFF position, should release the catch (18) (Figure 7) mounted on the door, and the door should be free to open. Similarly, on closing the door, the bottom edge of bracket (19) should clear the top edge of the bottom pan by not more than 0.125" (3 mm). If adjustment is required: a) Place the tray in the OFF position and open the door. b) Loosen the two bolts (27). c) Move latch (18) and bracket (19) either up or down to meet the conditions described above. d) Retighten the bolts (27) and check the adjustment and operation of the interlock Fig. 4 Two PTs in Open Delta for Typical Metering Circuit Fig. 5 Three PT s in Wye-Delta Connection for Typical Ground Detection Circuit

5 Page 5 COMMON POTENTIAL TRANSFORMER CIRCUITS The most commonly used potential transformer secondary connection diagrams are shown in Figures 4 and 5. START-UP PRECAUTIONS Before attempting to energize a newly installed disconnect assembly, study the wiring diagram and available instruction literature. Learn the hazards involved. DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS ENTIRETY BEFORE INSTALLING OR OPERATING THE DISCONNECTING MEANS. INSTALLATION, ADJUSTMENT, REPAIR AND MAINTENANCE OF THIS EQUIPMENT MUST BE PERFORMED BY QUALIFIED PERSONNEL. A QUALIFIED PERSON IS ONE WHO IS FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THIS EQUIPMENT AND THE HAZARDS INVOLVED. Fig. 6 Rear View of a Three PT Disconnect Assembly 27 In general, be sure that: 1) The power supply to the equipment is OFF, and all safety precaustions have been taken to ensure that an examination and any adjustments can be made safely. 2) The intended power supply voltage agrees with the PT nameplate data. 3) The primary (4) and secondary (24) fuses have been properly installed as shown in Figure 3. 4) The mechanism works smoothly, the shutter slides easily, and the line fingers enter the aperatures in the rear barrier and make contact with at least 0.25" (6mm) of wipe on the line terminals. 5) The auxiliary contacts (16) (Figure 3) open before the line contacts separate. (See ADJUSTMENTS below, if adjustments are required). 6) The line terminals are properly grounded in the OFF position. (See Figure 2.) See ADJUSTMENTS above, if adjustment is required). 7) The door interlocks are properly adjusted and effective. 8) The operating handle is in the OFF position. The door is closed and fastened. The unit is now ready to be energized. Fig. 7 Interlock to Prevent Door Opening While Operating Handle Is in the ON Position

6 Page 6 CONTROL POWER APPLICATIONS The maximum rated exciting currents that Auxiliary Control Power (ACP) disconnect switches can interrupt are shown in Table I, expressed in terms of control power transformer size where the ACP disconnect controls the power to the primary winding of the transformers. The maximum fuse to be used in this primary circuit is rated 10 amperes. To insure that the ACP disconnect is never subjected to more than transformer magnetizing current at the time of opening a system of key-operated mechanical interlocks must be used. See Page 1 for details. A single-phase control power transformer up to 2kVA (5 kv maximum voltage) can be mounted inside the ACP disconnect. Any transformer mounted externally to the ACP disconnect will be key-interlocked with the disconnect to insure that the disconnect is only required to interrupt the transformer s charging current, and not load current. The maximum continuous current rating of the switch is 10 amps and its limited interrupting rating is intended to only interrupt a transformer s charging current and not its load current. SWITCH MAINTENANCE All work on this switch should be done with the main circuit disconnect device open, and using a separate source of control power to test when necessary. Before applying external control circuit power, make certain that the control circuit is electrically isolated, to prevent feedback into a control power transformer that could be hazardous. DANGER WARNING: ALL WORK ON THIS EQUIPMENT SHOULD BE DONE WITH THE MAIN DISCONNECT DEVICE OPEN. AS WITH ANY EQUIPMENT OPERATING AT THIS VOLTAGE, THERE IS DANGER OF ELECTROCUTION AND/OR SEVERE BURNS. MAKE CERTAIN THAT POWER IS OFF. TABLE I. DISCONNECT SWITCH RATINGS Voltage Rating Maximum Single Phase Single Phase Control Power 15 kva 20 kva Transformer Three Phase Three Phase To Be Used 25 kva 35 kva The basic principles to be followed in the maintenance of all electrical equipment are: (1) keep conducting parts as good conductors and (2) keep insulating parts as good insulators, i.e., tighten and clean. A set of three flexible primary fingers, primary fuses, fuse mountings and ground fingers are available as renewal parts. Order Style No. 2147A95G09. See Table II for replacement auxiliary contacts. TABLE II. TYPE L64 AUXILIARY CONTACTS Part Number 843D943G21 843D943G22 843D943G23 Circuit Combination Provided By One Auxiliary Contact Unit Assembly One Normally-Open and One Normally-Closed Two Normally-Open Two Normally-Closed Fig. 8 Typical ACP Connection Diagram

7 Page 7 INDEX PAGE Adjustments... 3 Auxiliary Contact Adjustment... 4 Auxiliary Contact Replacement... 7 Auxiliary Control Power Applications... 1 Auxiliary Control Power Interlocking... 1 Auxiliary Control Power Ratings... 6 Closing Stroke... 2 Component Identification... 3 Control Power Ratings... 6 Disconnect Switch Operation... 2 Door Interlocks... 2 Door Interlock Adjustment... 4 Maintenance... 6 Mechanical Construction... 2 Opening Stroke... 2 Potential Transformer Applications... 4, 5 Primary Circuit Grounding... 1 Ratings, Control Power... 6 Start-Up Precautions... 5 Tray Adjustment... 3 Warnings... 1, 2, 5, 6

8 Page 8 Cutler-Hammer 221 Heywood Road Arden, NC Printed in U.S.A./CCI

TABLE I. AMPGARD EQUIPMENT RATINGS

TABLE I. AMPGARD EQUIPMENT RATINGS Cutler-Hammer Instructions for 36" Wide Vacuum-Break Starters Rated 360 Amperes, 7200 Volts, Slide-Out Type DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS BOOKLET IN ITS ENTIRETY BEFORE INSTALLING

More information

Auxiliary Contact Rating Induction Motor 1750 HP 2250 HP 3000 HP 4500 HP Voltage (Max)

Auxiliary Contact Rating Induction Motor 1750 HP 2250 HP 3000 HP 4500 HP Voltage (Max) Cutler-Hammer Instructions for 26" Wide Vacuum-Break Starters Rated 200 and 400 Amperes, 7200 Volts, Stab-Connected with SL Contactor DANGER HAZARDOUS VOLTAGE. READ AND UNDERSTAND THIS MANUAL IN ITS EN-

More information

Ampgard medium voltage motor control renewal parts

Ampgard medium voltage motor control renewal parts Technical Data TD020001EN Contents Description Page General information.... 2 3 400A starter design.... 4 9 800A starter design.... 10 15 Control and potential transformers.... 16 Current transformers....

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label. Operator s Manual 7000 Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes TABLE OF CONTENTS Note: Refer to the outline and wiring drawings provided with your 7000 Series

More information

Instructions for Replacing

Instructions for Replacing e Instructions for Replacing Vacuum Bottle Subassemblies a on Type SJA, SJS and SJO 360 Amp Contactors l.l. 16-200-348 This l.l. includes illustrations and instructions for replacing vacuum bottle subassemblies

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Instructions for AMPGARD 400A medium voltage starter

Instructions for AMPGARD 400A medium voltage starter Read and understand this manual in its entirety before installing or operating the controller. Installation, adjustment, repair, and maintenance of these controllers must be performed by qualified personnel.

More information

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035 Instruction Bulletin 4402-997-0 February 999 Middletown, OH, USA DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 605 DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches I.L. 29C284B File 29-000 Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

Isolation Switch (behind barrier & inspection window) Power Fuses. Load Cable Connection Box. Contactor. Control Power Transformer Secondary Fuse

Isolation Switch (behind barrier & inspection window) Power Fuses. Load Cable Connection Box. Contactor. Control Power Transformer Secondary Fuse Instruction Bulletin Class 8198 ISO-FLEX Medium Voltage Controller Model 3, Series B Installation and Maintenance Bulletin No. 50006-376-01 August, 1995 Raleigh, NC, USA TABLE OF CONTENTS Introduction...

More information

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter

Cutler-Hammer. Instructions for Installation, Operation, and Maintenance of the AMPGARD Reduced Voltage Soft Starter Operation, and Maintenance of the Instruction Bulletin Read and understand these instructions before attempting any installation, operation, or maintenance of the. This equipment shall be installed and

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 Supersedes July 1997 IB694C694-02 Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII Effective July 2010 PURPOSE This

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2 SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems Instruction Sheet 408-8040 30 NOV 17 Rev H Ram Assembly Ram Post Locking Screw Stock Drag Drag Release

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch Installation Instructions Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch Catalog Numbers 2193FZ Topic Page About This Publication 1 Required Tools 1 Important User Information 2

More information

Tooling Assistance Center

Tooling Assistance Center Safeguards are designed into this application equipment to protect operators and maintenance personnel from most hazards during equipment operation. However, certain safety precautions must be taken by

More information

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA) Instructions for the Use, Operation and Maintenance of Types T-VAC and T-VACR Vacuum Circuit Breakers Effective November 2017 T- VACR Fixed (up to 25kA) T-VAC Draw out (up to 25kA) T- VACR Fixed (up to

More information

Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS IB E

Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS IB E Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS Read and understand these instructions before attempting to unpack, assemble, operate or

More information

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear Contents Description Page Introduction.... 4 Installing indoor switchgear.... 6 A further description of arc-resistant VacClad-W switchgear.... 13 Adjusting and testing.... 20 Operation of the system....

More information

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking) Instructional Booklet IB022010EN Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking) Contents Description Page Notices and warnings.... 4 Introduction....

More information

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label. Operator s Manual 7000 Series ACTS Automatic Closed Transition es 150 through 4000 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness...

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

Bulletin 1494V Variable Depth, Flange Operated Disconnect Switch Kits for 400 and 600 Amperes (Series A) Switches

Bulletin 1494V Variable Depth, Flange Operated Disconnect Switch Kits for 400 and 600 Amperes (Series A) Switches Bulletin 494V Variable Depth, Flange Operated Disconnect Switch Kits for and Amperes (Series A) Switches ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

WLI Medium Voltage Switchgear Renewal Parts

WLI Medium Voltage Switchgear Renewal Parts Page 1 Supersedes Renewal Parts Data, pages 1-2, dated June 1992, WLI Medium Voltage Switchgear Renewal Parts Page 2 Standard Manually Operated Fused WLI Switch ➇ ➁ ➀ ➂➃ WLI Switch Mechanism ➉ ➈ m Replacement

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO) Operator s Manual 7000 Series ATS Automatic Transfer Switches H design 600 through 1200 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

Bulletin 1494C Cable Operated Disconnect Switch Kit (400A) Installation Instructions (Cat 1494C- _ Series 2 : 400A)

Bulletin 1494C Cable Operated Disconnect Switch Kit (400A) Installation Instructions (Cat 1494C- _ Series 2 : 400A) Bulletin 494C Cable Operated Disconnect Switch Kit () Installation Instructions (Cat 494C- _ Series : ) ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only s SFIS-70090-0808 August, 2008 TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only Siemens Energy & Automation, Inc. Hazardous voltage. Will cause death or serious injury.

More information

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps

Operator s Manual Series ATS Automatic Transfer Switches 600 through 1200 amps Operator s Manual 7000 Series ATS Automatic Switches 600 through 1200 amps 600---1000 amp. size An experienced licensed electrician must install the ATS. DANGER is used in this manual to warn of high voltages

More information

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING SAFETY PRECAUTIONS POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE BREAKERS AND THEIR ENCLOSURES ARE DESIGNED WITH SEVERAL BUILT-IN INTERLOCKS AND SAFETY FEATURES

More information

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers Supersedes IL 33-A46-2 Dated 01/04 Contents Description Page Introduction.............................. 3 Step 1: General Breaker Preparation......... 4 Step 2: Removing the Original Components.. 5 Step

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches 150 through 4000 amp. Note: Refer to the outline and wiring drawings provided with your 7000 Series ADTS for all installation and

More information

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1 Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear

More information

INSTRUCTIONS TOSHIBA. JK Medium Voltage Controllers Maximum OPERATION MAINTENANCE

INSTRUCTIONS TOSHIBA. JK Medium Voltage Controllers Maximum OPERATION MAINTENANCE Document: Issued: OH01 TOSHIBA INSTRUCTIONS OPERATION MAINTENANCE JK Medium Voltage Controllers Maximum INTRODUCTION Page 1 READ THIS MANUAL carefully for important information about safety, handling,

More information

Bulletin 1494C Cable Operated Disconnect Switch Kit (600A) Installation Instructions (Cat 1494C- _ Series 2 : 600A)

Bulletin 1494C Cable Operated Disconnect Switch Kit (600A) Installation Instructions (Cat 1494C- _ Series 2 : 600A) Bulletin 494C Cable Operated Disconnect Switch Kit (600A) Installation Instructions (Cat 494C- _ Series : 600A) ATTENTION: To prevent electrical shock, disconnect from power source before installing or

More information

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac 0000 00000 0000 000 0000 000000 00000 0000 00000 0000 000 0000 000000 00000 SIMOVAC and SIMOVAC-AR Medium-voltage controllers 2.3 kv - 6.9 kv usa.siemens.com/simovac 2 SIMOVAC and SIMOVAC-AR - the latest

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing

Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing Introduction A modular system of switchgear building blocks and cassettes provide untouchable

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems

Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems Instruction Sheet 408-8039 02 JUN 16 Rev G Ram Post Wire Disc Insulation Disc Insulation Crimper Stripper

More information

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E

FOR PRICES ON DSII and DSLII BREAKERS, REFER TO PRICE LIST PL.22B.01.P.E Supersedes PL.44B.04.P.E Dated September 1998 600 Volts AC Maximum 200 ka, RMS Sym. Short Circuit Maximum 800-5000 Amps Continuous Effective: October 1999 Page 1 Index Page Table Description/Application...

More information

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps Operator s Manual 7000 Series ADTS Automatic Delayed Transition Switches, 600 1200 amps 600---1000 amp. sizes An experienced licensed electrician must install the ADTS. DANGER is used in this manual to

More information

Cable-Operated Disconnect Switches. Accessories

Cable-Operated Disconnect Switches. Accessories Cable-Operated Disconnect Switches Accessories Description For Use With Auxiliary Contacts 1 N.O. Contact 1494C, 1494F, 1494V, and 1494G ( 1495-N8 1 N.O. Contact (low-level switching) A) Disconnect Switches

More information

RotoTract Remote Racking Operating Manual

RotoTract Remote Racking Operating Manual RotoTract Remote Racking Operating Manual Instruction Leaflet IL04300001E Effective July 2008 RotoTract Remote Racking Accessory for Use with FlashGard Motor Control Center Units Introduction RotoTract

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings Page 1 Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings I. General This specification covers the design requirements for a pad-mounted capacitor

More information

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES FILE 29-900 Instructions for Combination Bypass Isolation and Transfer Switches 100-1000 Amps APPLICATION The Cutler-Hammer combination Bypass Isolation and Transfer Switches are listed under Underwriters

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Instructions for installation, operation, and maintenance of 5/15 kv type VacClad-W arc resistant metal-clad switchgear Contents

Instructions for installation, operation, and maintenance of 5/15 kv type VacClad-W arc resistant metal-clad switchgear Contents arc resistant metal-clad switchgear Contents Description Page Introduction.... 4 Installing indoor switchgear.... 6 Description of arc resistant VacClad-W switchgear.... 13 Adjusting and testing.... 21

More information

Digitrip Retrofit System for BBC LKD 8 Breakers

Digitrip Retrofit System for BBC LKD 8 Breakers Supersedes IL 33-LK8-2 Dated 10/00 Contents Description Page Introduction.............................. 3 Step 1:............................... 4 Step 2:............................... 4 Step 3:...............................

More information

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS Operator s Manual 7000 Series ATS Automatic Switches 30 through 4000 amp. Note: Refer to the outline and wiring drawings provided with your 7000 Series ATS for all installation and connection details and

More information

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers Contents Description Page Introduction.............................. 2 Step 1: General Breaker Preparation......... 3 Step 2: Removing the Original Components.. 3 Step 3: Installing the Sensors..............

More information

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

www. ElectricalPartManuals. com Operator s Manual

www. ElectricalPartManuals. com Operator s Manual Operator s Manual TABLE OF CONTENTS section-page... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness... 1-2 Engine Starting Contacts... 1-2 Functional Test... 1-3, 1-4, 1-5, 1-6

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

section-page Table 1. Transfer switching device ratings. Conditional short circuit current Operator s Manual 7000 Series ATS Automatic Transfer Switching Equipment D design 30 through 200 amperes TABLE OF CONTENTS section-page INSTALLATION... 1-1 Enclosures and Mounting... 1-1 Power Connections...

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

Cutler-Hammer. AMPGARD MV Motor Control Vacuum Break SJ Series II II. Renewal Parts. r II li I. Pages. Contents. Effective: March 2000 Page 1

Cutler-Hammer. AMPGARD MV Motor Control Vacuum Break SJ Series II II. Renewal Parts. r II li I. Pages. Contents. Effective: March 2000 Page 1 ! ' ICc@l Cutler-Hammer New Information Supersedes RPD8855V (August 1994) Renewal Parts Effective: March 2000 Page 1 AMPGARD MV Motor Control Vacuum Break SJ Series Contents Pages 400 Amp Starters ADM

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

COOKSON OWNER'S MANUAL

COOKSON OWNER'S MANUAL COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8

More information

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive

More information

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988 Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

www. ElectricalPartManuals. com It'll Cutler-Hammer WLI Medium Voltage Switchgear Renewal Parts Renewal Parts Data Page 1

www. ElectricalPartManuals. com It'll Cutler-Hammer WLI Medium Voltage Switchgear Renewal Parts Renewal Parts Data Page 1 t'll Cutler-Hammer Supersedes Renewal Parts Data, pages 1-2, dated June 1992 Renewal Parts Data Page 1 WL Medium Voltage Switchgear Renewal Parts Renewal Parts Data Page 2 WL Medium Voltage Switchgear

More information

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN Form 1254 BRAKETRON Electronic Motor Brake Instructions SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN TABLE OF CONTENTS SECTION TITLE PAGE I. Introduction 1 II. Specifications 1 III. Principles

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the medium voltage motor starters as specified herein and as shown on the contract

More information

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices IB 6.2.13.7-1 1 Rev. 4, June 2000 ADVAC TM INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices Power T&D Company, Inc. Distribution Systems Division

More information